SOUTHERN REGIONAL POWER COMMITTEE BENGALURU

Size: px
Start display at page:

Download "SOUTHERN REGIONAL POWER COMMITTEE BENGALURU"

Transcription

1

2 SOUTHERN REGIONAL POWER COMMITTEE BENGALURU Minutes of the Special Meeting held on 21 st June, 2017 at TPCIL plant in Nellore w.r.t. perturbations at their plant in Nellore in the recent past A. Introduction A Special Meeting was held on 21 st June, 2017 at TPCIL plant in Nellore to deliberate on all outstanding protection issues noticed w.r.t. perturbations experienced at their plant in Nellore in the recent past. The list of participants is enclosed at Annexure-I. The issue was discussed in the 64 th meeting of PCSC held on , when the following were noted: It was noted that there were no actual tripping of any of TPCIL evacuating lines in any of the stated events. However, experience of perturbations in line/ GT relays had been a recurrent phenomenon at TPCIL end. From the corresponding PMU plots presented by SRLDC (Annexure-IV), it was noted that in almost all of the perturbation events, there was flow of negative and zero sequence currents, which pointed to occurrence of actual faults. Further, it was also noted that there was not a single instance of delayed clearance of faults, which meant that the protection systems in place had operated correctly. Accordingly, the issue came down to one of identifying the plausible locations of the fault so that suitable remediable measures for such frequent occurring of faults could be suggested. Thus, to zero in on the plausible fault locations, it was felt necessary to analyze SRLDC SCADA Sequence of Events (SoE) by juxtaposing it with that of SLDC of Andhra Pradesh. The idea was since protection systems were found to have operated correctly in the stated instances, it is appropriate to go into the reasons for such high frequency of trippings by identifying the probable fault locations. Further, since TPCIL is connected to Nellore Pooling Station (NPS) of PGCIL (SR-I), to ascertain whether protection systems put in place are being properly maintained, it was also decided to conduct protection audit of 765/ 400 kv NPS. Subsequently, as decided in PCSC-64 meeting, SCADA data correlation with perturbation events, and protection audit of 765/ 400 kv NPS were conducted. Further, the settings adopted by TPCIL for their protection relays had also been verified for correctness. The observations made and recommendations/ measures suggested to various Utilities w.r.t. the issues involved are detailed in the following Sections. B. Protection Audit of 765/ 400 kv Nellore PS of PGCIL (SR-I) Protection audit of 765/ 400 kv Nellore PS of PGCIL (SR-I) was conducted by a team comprising Officials from SRPC, SRLDC, APTRANSCO and TPCIL during June, 2017 to ascertain whether protection systems put in place are being properly maintained. The remarks of the audit team for compliance by PGCIL (SR-I) are given at Annexure-II. Minutes of the Special Meeting on TPCIL Perturbations held on 21 st June, 2017 Page 1

3 After observing the state of various protection systems in place and verifying the settings adopted for various protection relays at Nellore PS, the audit team concluded that there was nothing suspicious that could have contributed to perturbations experienced at TPCIL plant. C. Identification of probable fault locations The list of perturbation events provided by TPCIL is given below: Sl. No. Date & Time of Perturbation Nature of Perturbation (Voltage dip / Current Variation / Voltage Variation With Voltage Details)(Fault Phase ref- RYB) @2.01&7.38hrs Fault on B, IN> @18.03hrs Fault on R, Zone @ 4.55hrs, 6.01hrs, 6.15hrs, 6.25 & 6.54hrs @ 4.53hrs, 5.15hrs, 5.44hrs & 6.36hrs hrs, 3.55hrs, 3.55hrs, 5.02&6.05 IN>1 Fault on B,V< 1 Fault on B, Zone3&V< @ 2.41 & 2.56hrs Fault on Y, Zone @ 2.51hrs IN> @ 2.50, 3.59 & 4.38hrs Fault on Y, IN> @ 13.40, 14.05, 14.38, 14.58, & 16.16hrs Fault on Y, Zone-3, IN>1, V<1 Since in most of the above events, TPCIL end relays had sensed the apparent faults in Zone-3, it was set out to arrive at the possible paths for Zone-3 as given below: For this, since TPCIL is connected to NPS, and Zone-3 reach at TPCIL has been set as to protect the longest line connected to NPS, which is 400 kv NPS Gooty line of length 289 km, other possible paths falling in Zone-3 reach for TPCIL end relays have been arrived at by considering various transmission line (s) emanating from NPS subject to total line length of 289 km. 400 kv NPS TPCIL D/C line = 32.7 km 400 kv NPS Gooty D/C line = 289 km 400 kv NPS SGPL D/C lines = 33.5 km 400 kv NPS MEPL line = km 400 kv NPS SEL line = km 400 kv NPS Nellore-PG D/C line = 6.7 km 765 kv NPS-Kurnool D/C line = km Minutes of the Special Meeting on TPCIL Perturbations held on 21 st June, 2017 Page 2

4 400 kv Nellore-PG Sriperumbudur D/C line = 189 km Sriperumbudur SV Chatram D/C line = 17.9 km SV Chatram NCTPS D/C line = 95 km NCTPS-II NTECL-Vallur = 3.5 km NCTPS-II Alamathy D/C line = 84 km Nellore-PG Tiruvalam D/C line = km SDSTPS Nellore-AP D/C line = km SDSTPS - Chittoor D/C line = 189 km Minutes of the Special Meeting on TPCIL Perturbations held on 21 st June, 2017 Page 3

5 To further zero in on the probable fault locations, SCADA sequence of events (SoE) were obtained from SRLDC & SLDC, APTRANSCO and juxtaposed with the TPCIL provided perturbation events. From this, it can be concluded that Zone-3 perturbations as experienced by TPCIL end relays could be attributed mainly to (i) the faults on the 400 kv transmission lines emanating from generating stations (Vallur TPS, NCTPS) in the Chennai metro area, and (ii) the faults on 400 kv Nellore-AP (Manubolu) Krishnapatnam (SDSTPS) D/C line (esp. within 10 km radius from SDSTPS). In this connection, it may be noted that some of these events had already been discussed & addressed appropriately in regular monthly meetings of PCSC. The correlated data along with related PCSC deliberations is enclosed at Annexure-III. In this connection, it was noted that some of the SCADA events recorded by SLDC, APTRANSCO had not been captured in SRLDC s SCADA system. It was therefore recommended that SRLDC and SLDC, APTRANSCO may appropriately address the underlying communication issues involved. It was also noted that Auto-reclosure (A/R) feature kept in service from Krishnapatnam (SDSTPS) end on 400 kv Krishnapatnam Nellore-AP D/C line at Krishnapatnam end was unhealthy and found to be operating erratically. It was therefore recommended that APGENCO (SDSTPS) take steps to rectify A/R logic at SDSTPS end, and make it functional at the earliest. C.1 Measures taken with respect to reducing frequency of faults on transmission lines in Chennai metro area: The issue had been elaborately dealt with by PCSC forum in their 64 th meeting held on The measures taken and stated to be under progress by the concerned utilities [TANTRANSCO & PGCIL (SR-II)] as brought out in the minutes of PCSC-64 meeting are reproduced below: *********************************************************************************** Deliberations w.r.t. GD-I.1 & GD-I.2 & GD-I.3: Insulators Replacement: It was noted that the above GDs were mainly due to Insulators flashovers/ decapping on the 400 kv evacuating lines of NCTPS, Stage-II. Since the Chennai (NCTPS) area falls in the most vulnerable terrain (coastal & pollution & generating) category, the applicable patrolling protocol and maintenance procedures along with necessary remedial measures required to be taken had been suggested way back in April, 2014 when similar trippings had been encountered. Then it was decided that all conventional insulators in the stretches prone to pollution & saline effects would be replaced with polymer type insulators. When asked about the status of replacement of insulators on their lines, TANTRANSCO informed that the Insulator replacement works on the fault-prone stretches on all six evacuating lines of NCTPS-II had already been completed. And the present status in this regard was as follows: Insulators replacement on 400 kv NCTPS2 Vallur lines 1 & 2 had been completed. Insulators replacement on 400 kv NCTPS2 SV Chatram lines 1 & 2 was presently going on, and would be completed soon. Insulators replacement on 400 kv NCTPS2 Alamathy lines 1 & 2 would be completed in 3-month time. When asked about the status of replacement of insulators on the portions of the lines belonging to them, PGCIL (SR-II) informed the following: Insulators replacement on 400 kv Vallur - Alamathy lines 1 & 2 had been completed. Minutes of the Special Meeting on TPCIL Perturbations held on 21 st June, 2017 Page 4

6 Insulators replacement on major portion of the 400 kv Vallur Kalavindapattu lines 1 & 2 had been completed. The left out portions would be completed in 2-3 months. In this regard, the need to undertake various maintenance activities like hot-line washing of insulators and condition-based monitoring of equipment including attending to hot-spots was emphasized. Auto-Reclosure Issues: When enquired about the remedial action taken w.r.t. restoring A/R on the evacuating lines of NCTPS-II, TANTRANSCO informed the following: FO link on 400 kv NCTPS2 Alamathy lines 1 & 2 was restored on FO link on 400 kv NCTPS2 SV Chatram lines 1 & 2 was restored on FO link on 400 kv NCTPS2 Vallur lines 1 & 2 was restored on When asked about the undue delay (about 20 days) taken in restoring the above links, TANTRANSCO informed that due to the critical nature of the areas through which above lines were passing, they had to grapple with various operational & logistical issues, and assured that efforts would be made to reduce FO link restoring time to the minimum possible in future. In this regard, TANTRANSCO was asked to ensure that A/R is functional on all 400 kv lines in Chennai area and steps shall be taken to restore promptly any disruptions on account of FO link failures. Recommendations: TANTRANSCO and PGCIL (SR-II) to take steps to complete insulator replacement works on the 400 kv lines owned by them in Chennai area within 3 months. Deliberations w.r.t. GD-I.4: When enquired about the status of insulators replacement on the 230 kv lines in NCTPS area, TANTRANSCO informed that the works are under progress. To this, it was emphasized that the same level of seriousness given for 400 kv lines should also be given for 230 kv lines in replacing conventional insulators with that of polymer type. When enquired about the status of A/R implementation on 230 kv lines emanating from NCTPS-I, originally A/R had not been provided due to NCTPS-I being a generating station. However, in line with extant regulations and guidelines, they have decided to implement A/R on those transmission lines where one end is connected to a generating station. As already intimated to SRPC, steps would be taken to provide the same in 6 months. Recommendations: TANTRANSCO to take steps to complete insulator replacement works on the 230 kv lines owned by them in NCTPS area within 6 months. TANTRANSCO to take steps to implement A/R on all 230 kv lines emanating from NCTPS-I at the earliest. ********************************************************************************************* Minutes of the Special Meeting on TPCIL Perturbations held on 21 st June, 2017 Page 5

7 C.2 Measures taken with respect to reducing frequency of faults on 400 kv Krishnapatnam (SDSTPS) Nellore-AP (Manubolu) D/C line: It was noted that the primary cause of the faults was basically insulator flashovers/ failures/ tracking. It was further noted that 400 kv Krishnapatnam Nellore-AP D/C line is of length km, and covers about 140 tower locations. It was further noted that this D/C line [owned/ maintained by APTRANSCO], have conventional disc type insulators; whereas all other lines in Nellore complex [owned/ maintained by PGCIL (SR-I)], have composite polymer type insulators which explains the frequent occurrence of faults on the former. It was also noted that when the occurrence of the faults due to insulator failures on 400 kv Krishnapatnam Nellore (AP) D/C line was on the rise a couple of years ago, APTRNSCO had then replaced insulators on first 20 tower locations starting from SDSTPS, after which the faults frequency came down. Now again when these were on the rise in the past few months, APTRANSCO had started replacing conventional insulators with SCR polymer type insulators covering tower locations When enquired about the present status, APTRANSCO informed that they had completed insulator replacement works for tower locations 21 40, and that for is under progress, and is expected to be completed by mid-july, To this, it was pointed out that since the lines are of only km length, and are subjected to severe pollution & saline effects on continuous basis, replacement of conventional insulators on all 140 tower locations is an effective solution to avoid similar faults in future. Accordingly, APTRANSCO was recommended to replace conventional disc-type insulators with SCR/ CLR polymer type insulators on all 140 tower locations in 400 kv Krishnapatnam Nellore (AP) D/C line. APTRANSCO was also suggested make provision for composite polymer type insulators whenever they undertake to plan evacuation system for a generator coming up in coastal & highly polluted areas. In this context, it was also informed that as per the SRPC issued Transmission Line Patrolling Protocol/ Guidelines, in coastal and heavy to-medium polluted areas, the line maintenance activities including hot-line/ cold-line washing of insulators are to be carried out at least once in every four months, and TPCIL, PGCIL (SR-I), APGENCO, APTRANSCO were asked to strictly adhere to these guidelines. D. Status-Check of various protection settings adopted at TPCIL It was noted that by and large, the settings adopted in various protection relays at 400 kv TPCIL Switchyard are in order except for the following: 1. Presently, Zone-2 time delay for distance relays has been kept at 300 msec. However, since Nellore Pooling Station is connected to Nellore-PG SS by very short lines (of length 6.7 km), to allow proper time-coordination, it is recommended to keep Zone-2 time delay of 500 msec. 2. In setting resistive reach values for various zones, load resistance, R(L), has been calculated considering 1.2 times the full load current. It is recommended to revise resistive reach values for various zones by considering a load resistance that has been obtained with 1.5 times the full load current. Minutes of the Special Meeting on TPCIL Perturbations held on 21 st June, 2017 Page 6

8 3. Since the Zone-4 (reverse) primarily provides back-up to busbar protection, the present Zone-4 (reverse) time delay of 1.1 sec may be suitably revised to a lower value (say, 0.5 sec). 4. It is noted that back-up directional over-current protection (67) has been kept enabled on 400 kv feeders, and its setting is based on the CT ratio of 3000/ 1 A, which is in much excess of full load current. Even though this may not pose any problem as of now, as and when TPCIL decides to use CT s of lower ratio (say, 2000/ 1 A), the back-up directional over-current protection (67) shall be kept disabled. 5. It is noted that Over Voltage Protection settings have been presently kept as Stage-I: 110 %, 3 sec; Stage-II: 160 %, 0.5 sec. These shall be changed to SRPC provided settings intimated vide letter no: SRPC/SE-III/OVR/2017/ dated These are given below for kind reference: 400 kv TPCIL NPS line-1: OVR, Stage-I: A (111% of Vnom, 10 sec); OVR, Stage-II: 140% of Vnom, 100 msec. 400 kv TPCIL NPS line-2: OVR, Stage-I: D (110% of Vnom, 8 sec); OVR, Stage-II: 140% of Vnom, 100 msec. 6. It is further noted that Directional Earth Fault Protection (DEF, 67N) and Distance Protection (DP, 21) have been simultaneously kept enabled on 400 kv feeders. Since, this may create time-coordination issues, it is recommended, in line with SRPC philosophy, to keep DEF protection in blocked condition as long as Distance Protection is active, and shall be configured to become active only when distance protection does not pickup. ***** Minutes of the Special Meeting on TPCIL Perturbations held on 21 st June, 2017 Page 7

9 Annexure - I

10 Annexure- II Remarks of Protection Audit Team vis-à-vis 765 / 400 kv Nellore Pooling Station of PGCIL (SRTS-I) Sl. No. Observations on which action may be taken 1 Substation is well maintained in all aspects. 2 The following have been found to be satisfactory: (i) Operation of various electrical & mechanical interlocks (ii) Remote operation of Isolators from work-station (iii) No oil leakage from any of the CT's & ICT's & Reactors. 3 As most of the numerical relays have completed 4-years of in-service operation, comprehensive testing of the same may be carried out. 4 In addition to blocking of distance protection under VT fuse-fail conditions, it shall be ensured that upon detection of a fault (sensed by negative sequence component), blocking of distance protection gives rise to operation of its inherent Over- Current protection with a suitable definite time delay of (say) 500 msec. 5 It is observed that Zone-1 time delay for Gooty lines 1 & 2 is kept as 100 msec, which may be clarified/ reviewed. 6 Z2, Z3 and Z4 Resistive reaches for Ph-G faults for Main-I & Main 2 have been found to be kept differently on 400 kv NCC lines 1 & 2, 400 kv Gooty lines & 765 kv Kurnool lines, which may be reviewed. 7 PLCC db level (signal strength) measurements are being done on yearly basis.

11 Perturbation Events Correlation with SCADA Data Annexure-III Sl. No. Date & Time Nature of Perturbation (Voltage dip / Current Variation / Voltage Variation With Voltage Details)(Fault Phase ref- RYB) at 2.01 hrs Fault on B, IN>1 SLDC, APTRANSCO: No Trippings recorded by SRLDC at 7.38 hrs Fault on B, IN>1 SLDC, APTRANSCO: No Trippings recorded by SRLDC at hrs Fault on R, Zone-3 No Trippings recorded by SLDC, APTRANSCO No Trippings recorded by SRLDC at 4.55 hrs IN>1 (PCSC-62 held on ) No Trippings recorded by SLDC, APTRANSCO PCSC Deliberations: Page 1 of 10

12 Annexure-III at 6.01 hrs, IN>1 (PCSC-62 held on ) No Trippings recorded by SLDC, APTRANSCO PCSC Deliberations: Page 2 of 10

13 Annexure-III at 6.15hrs IN>1 (PCSC-62 held on ) No Trippings recorded by SLDC, APTRANSCO PCSC Deliberations: at 6.25 hrs IN>1 (PCSC-62 held on ) No Trippings recorded by SLDC, APTRANSCO PCSC Deliberations: Page 3 of 10

14 at 6.54 hrs IN>1 (PCSC-62 held on ) Annexure-III No Trippings recorded by SLDC, APTRANSCO PCSC Deliberations: at 4.53 hrs Fault on B,V< 1 SLDC, APTRANSCO: No Trippings recorded by SRLDC at 5.15 hrs Fault on B,V< 1 (PCSC-63 held on ) SLDC, APTRANSCO: PCSC Deliberations: Page 4 of 10

15 at 5.44 hrs Fault on B,V< 1 Annexure-III No Trippings recorded by SLDC, APTRANSCO No Trippings recorded by SRLDC at 6.36 hrs Fault on B,V< 1 No Trippings recorded by SRLDC SLDC, APTRANSCO: at 1.57 hrs Fault on B, Zone3 & V<1 (PCSC-63 held on ) at 2.04 hrs Fault on B, Zone3 & V<1 No Trippings recorded by SLDC, APTRANSCO No Trippings recorded by SRLDC at 3.55 hrs Fault on B, Zone3 & V<1 (PCSC-63 held on ) SLDC, APTRANSCO: Page 5 of 10

16 PCSC Deliberations: Annexure-III at 5.02 hrs Fault on B, Zone3 & V<1 No Trippings recorded by SRLDC SLDC, APTRANSCO: at 6.05 hrs Fault on B, Zone3 & V<1 No Trippings recorded by SRLDC SLDC, APTRANSCO: at 2.41 hrs Fault on Y, Zone-3 (PCSC-64 held on ) SLDC, APTRANSCO: Page 6 of 10

17 PCSC Deliberations: Annexure-III at 2.56 hrs Fault on Y, Zone-3 No Trippings recorded by SRLDC SLDC, APTRANSCO: at 2.51 hrs IN>1 (PCSC-64 held on ) SLDC, APTRANSCO: PCSC Deliberations: at 2.50 hrs Fault on Y, IN>1 SRLDC: Page 7 of 10

18 SLDC, APTRANSCO: Annexure-III at 3.59 hrs Fault on Y, IN>1 (PCSC-64 held on ) SLDC, APTRANSCO: PCSC Deliberations: at 4.38 hrs Fault on Y, IN>1 SLDC, APTRANSCO: PCSC Deliberations: Page 8 of 10

19 at hrs Fault on Y, Zone-3, IN>1, V<1 Annexure-III No trippings recorded by SLDC, APTRANSCO SRLDC: at hrs Fault on Y, Zone-3, IN>1, V<1 (PCSC-65 held on ) No trippings recorded by SLDC, APTRANSCO PCSC Deliberations: Kurnool-PG (PGIL-SR1) end: As per FIR/EL/TR, line tripped (in Y-ph) at 14:05: hrs on Y-E fault due to DPR, Z1 (A/R, 3.28 km, 16.6 ka) operation, and successfully auto-reclosed after about 1.1 sec. After about further 6 sec (i.e., at 14:05:50.470), line tripped in 3-ph due to receipt of DT from the remote end. It was stated in FIR that 765 kv Kurnool NPS line-1 was under LVRD. (Always keep second ckt of D/C line out of service for voltage regulation --- to SRLDC). As per DR, line tripped (in 3-ph) at 14;05: hrs due to DT receipt from remote end. DR corresponding to successful A/R operation not furnished. NPS (PGIL-SR1) end: FIR & DR furnished were that of Kurnool station. As per DR/EL, line tripped (in 3-ph) at 14:05: hrs on Y-E fault due to A/R (Z2, CAT) operation. It was noted from EL that A/R LOCKOUT had operated around the same time due to which line had not tried for A/R. From EL, it was further observed that DT was sent to the remote end at 02:05: hrs. However, the cause of DT send was not recorded in EL. DR pertaining to DT send was not furnished. If DT send was because of OVR-I protection operation, then also tripping was not in order, as it does not match with the settings provided at hrs Fault on Y, Zone-3, IN>1, V<1 No trippings recorded by SLDC, APTRANSCO PCSC Deliberations: FNN not followed by APTRANSCO and APGENCO SDSTPS (APGENCO) end: As per FIR/DR/EL, line tripped (in 3-ph) at 14:41: hrs on R-E fault due to DPR, Z1 (62.8 km) operation. It was observed from EL that the line was given 3-ph trip straight way without initiating A/R. Reasons for 3-ph trip and A/R failure? Chittoor (APTRANSCO) end: As per FIR/DR/EL/TR, line tripped (in R-ph) at 14:41: hrs on R-E fault due to DPR, Z1 (114.7 km) operation, and auto-reclosed successfully after about 1sec. However, it was observed that only Main-CB got auto-reclosed successfully; whereas Tie-CB got tripped in 3-ph while attempting A/R. Page 9 of 10

20 at hrs Fault on Y, Zone-3, IN>1, V<1 Annexure-III SLDC, APTRANSCO: SRLDC: at hrs Fault on Y, Zone-3, IN>1, V<1 No trippings recorded by SLDC, APTRANSCO SRLDC: ***** Page 10 of 10

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

एस.आर.प.स 40व प र ट क शनउप सम त क ब ठकक मऱएएज ड Additional Agenda Points for 40 th meeting of Protection Sub-Committee of SRPC

एस.आर.प.स 40व प र ट क शनउप सम त क ब ठकक मऱएएज ड Additional Agenda Points for 40 th meeting of Protection Sub-Committee of SRPC ANNEXURE I एस.आर.प.स 40व प र ट क शनउप सम त क ब ठकक मऱएएज ड Additional Agenda Points for 40 th meeting of Protection Sub-Committee of SRPC 1. ग र डडडस टबबन स / ग र डइन सडन टक वववरण - Details of Grid incidents:

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

SUBJECT HEADING: Switching Programmes ISSUE: 18

SUBJECT HEADING: Switching Programmes ISSUE: 18 SUBJECT: Switchgear/Switching PROCEDURE: S04 SUBJECT HEADING: Switching Programmes ISSUE: 18 DATE: Apr 2017 1. INTRODUCTION 1.1 A written programme of switching operations shall be prepared. This programme

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected

More information

Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL)

Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL) Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL) 1.0 Introduction: 1.1 DTL vide letter No. F.DTL/206/F.06/2015-16/Mgr(Bawana)/353 dated

More information

Hands-On-Relay School 2015 Distribution Event Analysis. Randy Spacek Protection Engineer Manager

Hands-On-Relay School 2015 Distribution Event Analysis. Randy Spacek Protection Engineer Manager Hands-On-Relay School 2015 Distribution Event Analysis Randy Spacek Protection Engineer Manager OVERVIEW Available Tools Fault Type Identification: line and transformer Relay Event Record: Oscillography

More information

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 Prepared by System Planning Division Transmission Planning Department PJM 2016 Table of Contents Table of Contents Approval...6

More information

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

Education & Training

Education & Training Distribution System Operator Certificate This program provides you with a proficient working knowledge in modern electric power distribution systems. These four classes are designed to walk students through

More information

Distance Protection for Distribution Feeders. Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng.

Distance Protection for Distribution Feeders. Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng. Distance Protection for Distribution Feeders Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng. Why use distance protection for distribution feeders? Distance protection is mainly used for protecting

More information

PROCEDURE FOR INSPECTION OF ELECTRICAL INSTALLATIONS ABOVE 250KVA

PROCEDURE FOR INSPECTION OF ELECTRICAL INSTALLATIONS ABOVE 250KVA PROCEDURE FOR INSPECTION OF ELECTRICAL INSTALLATIONS ABOVE 250KVA Generally inspection of electrical installations is carried out under Regulation-30 (Periodical inspection & testing) & Regulation-43 (Approval

More information

SYNCHRONISING AND VOLTAGE SELECTION

SYNCHRONISING AND VOLTAGE SELECTION SYNCHRONISING AND VOLTAGE SELECTION This document is for Relevant Electrical Standards document only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept any liability for any

More information

Trip of four 220 kv transmission lines at Mt Beauty on 24 November 2014

Trip of four 220 kv transmission lines at Mt Beauty on 24 November 2014 Trip of four 0 kv transmission lines at Mt Beauty on 4 November 04 AN AEMO POWER SYSTEM OPERATING INCIDENT REPORT FOR THE NATIONAL ELECTRICTY MARKET PUBLISHED MARCH 05 Trip of four 0 kv transmission lines

More information

Hamdy Faramawy Senior Application Specialist ABB Sweden

Hamdy Faramawy Senior Application Specialist ABB Sweden Design, Engineering and Application of New Firm Capacity Control System (FCCS) Mohammed Y. Tageldin, MSc. MIET Senior Protection Systems Engineer ABB United Kingdom mohammed.tageldin@gb.abb.com Hamdy Faramawy

More information

No. SSIEC-PRC SHINSUNG. Polymer Recloser SIREC SERIES 15kV, 27kV, 38kV 400A, 630A, 800A

No. SSIEC-PRC SHINSUNG. Polymer Recloser SIREC SERIES 15kV, 27kV, 38kV 400A, 630A, 800A No. SSIEC-PRC-00803-1 SHINSUNG Polymer Recloser SIREC SERIES 15kV, 27kV, 38kV 400A, 630A, 800A Introduction SIREC(Solid Insulated Recloser) is designed for outdoor application with lightweight, longlife,

More information

Distribution/Substation Transformer

Distribution/Substation Transformer Distribution/Substation Transformer Type VFI, Vacuum Fault Interrupter Transformer Option Functional Specification Guide Functional specification for 15 kv, 25 kv, or 35 kv vacuum fault interrupter distribution/substation

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A SHINSUNG Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A Enhanced Self Healing System General SILO is 3 phase, solid insulated load break switch (LBS) and vacuum interruption

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE

CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE CHOICE OF MV FEEDER BIL TO MAXIMIZE QOS AND MINIMIZE EQUIPMENT FAILURE Willem DIRKSE VAN SCHALKWYK ESKOM - South Africa vschalwj@eskom.co.za ABSTRACT A high BIL (300 kv) on a MV feeder ensures that no

More information

SUPPLY OF CARRIER PROTECTION COUPLER TYPE NSD-50

SUPPLY OF CARRIER PROTECTION COUPLER TYPE NSD-50 (I) GENERAL : Indoor PLCC Equipments are required for important 400KV, 220KV and 132KV Sub/station for Speech, Data Transmission, Protection and Teleprinter Links. (II) GENERAL REQUIREMENT : The equipments

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 1T-18

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 1T-18 BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 1T-18 LIVE LINE PERMITS, ASSURANCE OF NO RECLOSE PERMITS AND CAUTION TAGS Supersedes OO 1T-18 issued 13 October 2010 Review Year: 2019 Original signed by:

More information

Form-IV. Form of Inspection/Test Report. (Under Regulation 43)

Form-IV. Form of Inspection/Test Report. (Under Regulation 43) Form-IV Form of Inspection/Test Report (Under Regulation 43) 1. Name and address of the Chartered Electrical Safety Engineer 2. Name and address of the consumer (or) Owner(or) supplier: Contact No: E-Mail:

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

MV network design & devices selection EXERCISE BOOK

MV network design & devices selection EXERCISE BOOK MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester

More information

Detecting and Managing Geomagnetically Induced Currents With Relays

Detecting and Managing Geomagnetically Induced Currents With Relays Detecting and Managing Geomagnetically Induced Currents With Relays Copyright SEL 2013 Transformer Relay Connections Voltage Current Control RTDs Transformer Protective Relay Measures differential current

More information

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS Juan Manuel Gers, PhD Protection coordination principles Relay coordination is the process of selecting settings that will assure that the relays

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS S1. Standard Interconnection Methods with Typical Circuit Configuration for Single or Multiple Units Note: The protection requirements

More information

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES Authors: Joe Perez, P.E.: SynchroGrid, College Station, Texas Hung Ming Chou, SynchroGrid, College Station, Texas Mike McMillan, Bryan

More information

Testing Manual for Electrical Equipment

Testing Manual for Electrical Equipment EPPM, Singapore, 20-21 Sep 2011 Abstract Testing Manual for Electrical Equipment Nahed Al-Hajeri 1 and Anantha Madhavan 2 Quality Assurance (QA) refers to a program for the systematic monitoring and evaluation

More information

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Solkor R & Solkor Rf

More information

Using a Multiple Analog Input Distance Relay as a DFR

Using a Multiple Analog Input Distance Relay as a DFR Using a Multiple Analog Input Distance Relay as a DFR Dennis Denison Senior Transmission Specialist Entergy Rich Hunt, M.S., P.E. Senior Field Application Engineer NxtPhase T&D Corporation Presented at

More information

Southern Company Interconnection Requirements for Inverter-Based Generation

Southern Company Interconnection Requirements for Inverter-Based Generation Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

Notes 1: Introduction to Distribution Systems

Notes 1: Introduction to Distribution Systems Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission

More information

A short introduction to Protection and Automation Philosophy

A short introduction to Protection and Automation Philosophy Training Center A short introduction to Protection and Automation Philosophy Philippe Goossens & Cédric Moors Training Center Contents Definitions and basic concepts Differential and distance protection

More information

ESB National Grid Transmission Planning Criteria

ESB National Grid Transmission Planning Criteria ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and

More information

IMPLEMENTATION OF ADVANCED DISTRIBUTION AUTOMATION IN U.S.A. UTILITIES

IMPLEMENTATION OF ADVANCED DISTRIBUTION AUTOMATION IN U.S.A. UTILITIES IMPLEMENTATION OF ADVANCED DISTRIBUTION AUTOMATION IN U.S.A. UTILITIES (Summary) N S Markushevich and A P Berman, C J Jensen, J C Clemmer Utility Consulting International, JEA, OG&E Electric Services,

More information

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION! PREFACE This publication has been prepared as a guide for Architectural and Engineering (A&E) firms in the preparation of documents for the design and construction of new structures and the remodeling

More information

PLAN... RESPOND... RESTORE! Utility Automation & Information Technology... Automation Rising

PLAN... RESPOND... RESTORE! Utility Automation & Information Technology... Automation Rising Automation Rising Q U A R T E R LY First Quarter 2013 The Digital Magazine of Automation & Information Technology for Electric, Gas and Water Utilities Utility Automation & Information Technology... PLAN...

More information

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June

More information

MAINTENANCE MANUAL 1B170K17 FOUR SHOT AUTO RECLOSE RELAY

MAINTENANCE MANUAL 1B170K17 FOUR SHOT AUTO RECLOSE RELAY Sheet 1 of 9 MAINTENANCE MANUAL 1B170K17 FOUR SHOT AUTO RECLOSE RELAY The Maintenance Manual is to be read in conunction with Product/Test Manual Sheet 2 of 9 INDEX 1. FULL DESCRIPTION OF OPERATION 1.1

More information

ASHIDA Numerical 3OC + 1EF Protection Relay

ASHIDA Numerical 3OC + 1EF Protection Relay PROTH. ERR L5 PKP FAULT DT REC LOCK BF L6 L7 CLOSE TRIP ADR 241B Protection Features : 4 Element (3 Phase + EF + Sensitive EF) Over current IDMT/DMT with instant trip. Programmable (Non- Volatile) Setting

More information

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) 1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1

More information

Increased Reliability of EHV Systems through Station Switchable Spare Transformer and Shunt Reactor Design and Operation

Increased Reliability of EHV Systems through Station Switchable Spare Transformer and Shunt Reactor Design and Operation 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium Increased Reliability of EHV Systems through Station Switchable Spare Transformer and

More information

Transmission System Phase Backup Protection

Transmission System Phase Backup Protection Reliability Guideline Transmission System Phase Backup Protection NERC System Protection and Control Subcommittee Draft for Planning Committee Approval June 2011 Table of Contents 1. Introduction and Need

More information

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström EH27401 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsn@ics.kth.se 1 Course map 2 Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids

More information

Transformer energisation after network blackout

Transformer energisation after network blackout Transformer energisation after network blackout Impact on network restoration and improvement of its process ABSTRACT According to ENTSO-E Network policy 5, responsibility for system restoration after

More information

This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor.

This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor. Basis of Design This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor. Background Information A Short Circuit and Coordination

More information

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment

A Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV

More information

How to maximize reliability using an alternative distribution system for critical loads

How to maximize reliability using an alternative distribution system for critical loads White Paper WP024001EN How to maximize reliability using an alternative distribution system for critical loads Executive summary The electric power industry has several different distribution topologies

More information

4. CONNECTIONS. Make sure all connections to and in your Universal Rectifier are tight.

4. CONNECTIONS. Make sure all connections to and in your Universal Rectifier are tight. OPERATING AND MAINTENANCE INSTRUCTIONS FOR CONSTANT CURRENT RECTIFIERS USING SATURABLE CORE REACTORS I. WARNING Operating personnel should observe the following before attempting to operate or adjust the

More information

DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS

DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS Abdelrahman AKILA Ahmed HELAL Hussien ELDESOUKI SDEDCO Egypt AASTMT Egypt AASTMT Egypt Abdurrahman.akela@gmail.com ahmedanas@aast.edu hdesouki@aast.edu

More information

Overcurrent relays coordination using MATLAB model

Overcurrent relays coordination using MATLAB model JEMT 6 (2018) 8-15 ISSN 2053-3535 Overcurrent relays coordination using MATLAB model A. Akhikpemelo 1 *, M. J. E. Evbogbai 2 and M. S. Okundamiya 3 1 Department of Electrical and Electronic Engineering,

More information

Greenlining and Bluelining of Ergon Energy Substation Drawings

Greenlining and Bluelining of Ergon Energy Substation Drawings Greenlining and Bluelining of Ergon Energy Table of Contents Purpose and Scope... 1 Responsibilities... 1 Definitions, Abbreviations and Acronyms... 1 References... 1 General... 1 Requirements... 3 Testing

More information

Location of Generating Station. Seeking Connectivity (MW) Raigarh, Chhattisgarh WR

Location of Generating Station. Seeking Connectivity (MW) Raigarh, Chhattisgarh WR Agenda for the 31 st Western Region constituents regarding Connectivity/LTA Applications to be held on 24.10.2018 1.0 Minutes of the 30th Western Region constituents regarding Connectivity / LTA Applications

More information

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions 1 Transmission transformers are important links in the bulk power system. They allow transfer of power from generation centers, up to the high-voltage grid, and to bulk electric substations for distribution

More information

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years

Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years 21, rue d Artois, F-758 PARIS B4-18 CIGRE 216 http : //www.cigre.org Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years T G MAGG, Power System

More information

Transmission Availability Data System Definitions

Transmission Availability Data System Definitions Table of Contents Transmission Availability Data System Definitions February 1, 2018 1 of 31 3353 Peachtree Road NE Suite 600, North Tower Atlanta, GA 30326 404-446-2560 www.nerc.com Table of Contents

More information

Agenda for the 18 th Northern Region constituents meeting regarding Connectivity/LTA Applications in NR

Agenda for the 18 th Northern Region constituents meeting regarding Connectivity/LTA Applications in NR Agenda for the 18 th Northern Region constituents meeting regarding Connectivity/LTA Applications in 1.0 Minutes of 17 th Meeting of Northern Region constituents regarding Connectivity / Long Term Access

More information

Guidance Material for ILS requirements in RSA

Guidance Material for ILS requirements in RSA Guidance Material for ILS requirements in RSA General:- Controlled airspace required with appropriate procedures. Control Tower to have clear and unobstructed view of the complete runway complex. ATC to

More information

GUJARAT TECHNOLOGICAL UNIVERSITY, AHMEDABAD, GUJARAT COURSE CURRICULUM COURSE TITLE: SWITCHGEAR & PROTECTION (COURSE CODE: )

GUJARAT TECHNOLOGICAL UNIVERSITY, AHMEDABAD, GUJARAT COURSE CURRICULUM COURSE TITLE: SWITCHGEAR & PROTECTION (COURSE CODE: ) GUJARAT TECHNOLOGICAL UNIVERSITY, AHMEDABAD, GUJARAT COURSE CURRICULUM COURSE TITLE: SWITCHGEAR & PROTECTION (COURSE CODE: 3360901 ) Diploma Programme in which this course is offered Electrical Engineering

More information

Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan

Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan Arizona Public Service Company and the Transmission Partnership for National Electric Power Company of Jordan Mark Hackney October 5-8, 2009 Amman, Jordan Energy Control Center Layout 2 Energy Control

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60071-2 Third edition 1996-12 Insulation co-ordination Part 2: Application guide This English-language version is derived from the original bilingual publication by leaving out

More information

Module 9. Fault Type Form 4.X RELIABILITY ACCOUNTABILITY

Module 9. Fault Type Form 4.X RELIABILITY ACCOUNTABILITY Module 9 Fault Type Form 4.X 1 M9 Fault Type The descriptor of the fault, if any, associated with each Automatic Outage of an Element. 1. No fault 2. Phase-to-phase fault (P-P) 3. Single phase-to-ground

More information

2 Grounding of power supply system neutral

2 Grounding of power supply system neutral 2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the

More information

Smart Grid Smarter Protection: Lessons Learned

Smart Grid Smarter Protection: Lessons Learned 1 Smart Grid Smarter Protection: Lessons Learned Kevin Damron and Randy Spacek Avista Utilities Abstract Avista embarked on a smart grid initiative through grants provided by the Department of Energy (DOE)

More information

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE Professor Akhtar Kalam Victoria University The Problem Calculate & sketch the ZPS, NPS & PPS impedance networks. Calculate feeder faults. Calculate

More information

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11 Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11 COMMISSIONING 12-16 DRAWINGS 17-18 1 1. INTRODUCTION APPLICATION

More information

Transmission Interconnection Requirements for Inverter-Based Generation

Transmission Interconnection Requirements for Inverter-Based Generation Transmission Requirements for Inverter-Based Generation June 25, 2018 Page 1 Overview: Every generator interconnecting to the transmission system must adhere to all applicable Federal and State jurisdictional

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements Section 502.8 SCADA Technical and Operating Requirements Applicability 1 Subject to subsections 2 and 3 below, section 502.8 applies to: (a) (c) (d) the legal owner of a generating unit or an aggregated

More information

Final ballot January BOT adoption February 2015

Final ballot January BOT adoption February 2015 Standard PRC-024-21(X) Generator Frequency and Voltage Protective Relay Settings Standard Development Timeline This section is maintained by the drafting team during the development of the standard and

More information

STANDARDS/MANUALS/ GUIDELINES FOR SMALL HYDRO DEVELOPMENT

STANDARDS/MANUALS/ GUIDELINES FOR SMALL HYDRO DEVELOPMENT STANDARDS/MANUALS/ GUIDELINES FOR SMALL HYDRO DEVELOPMENT Electro-Mechanical Works Guidelines for Power Evacuation and Interconnection with Grid Sponsor: Ministry of New and Renewable Energy Govt. of India

More information

Benefits of SFRA - Case Studies

Benefits of SFRA - Case Studies 6 th International Conference on Large Power Transformers- Modern Trends Benefits of SFRA - Case Studies B B Ahir Gujarat Energy Transmission Corporation Limited 1 Outline Condition Monitoring in GETCO

More information

Alberta Interconnected Electric System Protection Standard

Alberta Interconnected Electric System Protection Standard Alberta Interconnected Electric System Protection Standard Revision 0 December 1, 2004 APEGGA Permit to Practice P-08200 Table of Contents Signature Page... 2 Table of Contents... 3 1.0 STAKEHOLDER REVIEW

More information

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES

MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES MINING EARTH LEAKAGE PROTECTION WITH VARIABLE SPEED DRIVES White Paper Tim Wylie, Ampcontrol s Chief Technology Officer discusses the impact of Variable Speed Drives (VSDs) on earth fault limited networks.

More information

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General

More information

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions ENOSERV 2014 Relay & Protection Training Conference Course Descriptions Day 1 Generation Protection/Motor Bus Transfer Generator Protection: 4 hours This session highlights MV generator protection and

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section SCADA Technical and Operating Requirements Section 502.8 SCADA Technical and Operating Applicability 1 Section 502.8 applies to: (a) the legal owner of a generating unit: (i) connected to the transmission facilities in the balancing authority area

More information

- 1 - NEUTRAL CONNECTION TO EARTH IN MEDIUM VOLTAGE NETWORKS: OPERATION EXPERIENCE IN ENEL

- 1 - NEUTRAL CONNECTION TO EARTH IN MEDIUM VOLTAGE NETWORKS: OPERATION EXPERIENCE IN ENEL NEUTRAL CONNECTION TO EARTH IN MEDIUM VOLTAGE NETWORKS: OPERATION EXPERIENCE IN ENEL B. Ceresoli CESI S.p.A. - Italy A. Cerretti ENEL Distribuzione S.p.A - Italy E. De Berardinis CESI S.p.A - Italy A.

More information

FRIENDS Devices and their Coordination

FRIENDS Devices and their Coordination INDIAN INSTITUTE OF TECHNOLOGY, KHARAGPUR 721302, DECEMBER 27-29, 2002 425 FRIENDS Devices and their Coordination R. L. Meena, Arindam Ghosh and Avinash Joshi Abstract-- The paper discusses various aspects

More information

WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS

WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS WFPS1.1 INTRODUCTION 2 WFPS1.2 OBJECTIVE 2 WFPS1.3 SCOPE 3 WFPS1.4 FAULT RIDE THROUGH REQUIREMENTS 4 WFPS1.5 FREQUENCY REQUIREMENTS 5 WFPS1.6 VOLTAGE

More information

EXPRESSION OF INTEREST

EXPRESSION OF INTEREST र ष ट र य पवन ऊर स स थ न, च नन ई NATIONAL INSTITUTE OF WIND ENERGY म व प ( न ऊर जव प र द य ग क कप द र Formerly Centre for Wind Energy Technology ) (न न और न करण य ऊर जव त रजलय, भजरत सरकजर Ministry of New

More information

INTERNATIONAL TELECOMMUNICATION UNION DATA COMMUNICATION NETWORK: INTERFACES

INTERNATIONAL TELECOMMUNICATION UNION DATA COMMUNICATION NETWORK: INTERFACES INTERNATIONAL TELECOMMUNICATION UNION CCITT X.21 THE INTERNATIONAL (09/92) TELEGRAPH AND TELEPHONE CONSULTATIVE COMMITTEE DATA COMMUNICATION NETWORK: INTERFACES INTERFACE BETWEEN DATA TERMINAL EQUIPMENT

More information

Standard Prices for Generators 2010

Standard Prices for Generators 2010 Standard Prices for Generators 2010 Distribution System Operator ESB Networks Page 1 of 13 CONTENTS 1.0 Background...3 2.0 Standard Pricing Approach...3 Schedule of Charges for generators excluding VAT...6

More information

Phase Rolling and the Impacts on Protection

Phase Rolling and the Impacts on Protection Phase Rolling and the Impacts on Protection Denglin (Dennis) Tang Burns & McDonnell 1700 West Loop South, Houston, TX 77027 Office: (713) 622-0227 Fax: (713) 622-0224 dtang@burnsmcd.com Abstract: During

More information

E N G I N E E R I N G M A N U A L

E N G I N E E R I N G M A N U A L 1 1 1.0 PURPOSE The purpose of this document is to define policy and provide engineering guidelines for the AP operating companies (Monongahela Power Company, The Potomac Edison Company, and West Penn

More information

INCENTIVE FOR TRANSMISSION EFFICIENCY

INCENTIVE FOR TRANSMISSION EFFICIENCY INCENTIVE FOR TRANSMISSION EFFICIENCY - T. UMESH, SEE, RETD. KPTCL - & - N. RAGHUPRAKASH, EE, RA, KPTCL IN THIS SESSION Brief introduction to Transmission System Efficiency Parameters in Transmission Activity

More information

Solutions to Common Distribution Protection Challenges

Solutions to Common Distribution Protection Challenges Solutions to Common Distribution Protection Challenges Jeremy Blair, Greg Hataway, and Trevor Mattson Schweitzer Engineering Laboratories, Inc. Copyright SEL 2016 Common Distribution Protection Problems

More information

RELEVANT ELECTRICAL STANDARDS

RELEVANT ELECTRICAL STANDARDS RELEVANT ELECTRICAL STANDARDS Issue 2 October 2014 Issue 2 September 2014 National Grid 2014 2014 Copyright owned by National Grid Electricity Transmission plc, all rights reserved. No part of this publication

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Alexander Apostolov AREVA T&D Automation I. INTRODUCTION The electric utilities industry is going through significant

More information

UNIFORM NETWORK CODE OFFTAKE ARRANGEMENTS DOCUMENT SECTION E TELEMETRY, ETC

UNIFORM NETWORK CODE OFFTAKE ARRANGEMENTS DOCUMENT SECTION E TELEMETRY, ETC 1 General 1.1 Introduction Joint Office of Gas Transporters UNIFORM NETWORK CODE OFFTAKE ARRANGEMENTS DOCUMENT 1.1.1 This Section E sets out: SECTION E TELEMETRY, ETC National Grid NTS' requirements for

More information

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC

Standard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC A. Introduction 1. Title: Generator Frequency and Voltage Protective Relay Settings 2. Number: PRC-024-2 3. Purpose: Ensure Generator Owners set their generator protective relays such that generating units

More information

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Substation Auxiliary Transformer from Rectifier Transformer Secondary Reference Number PDS 01 (RIC Standard: EP 05 00 00 01 SP) Document Control

More information