EXPRESSION OF INTEREST
|
|
- Julius Bradley
- 6 years ago
- Views:
Transcription
1 र ष ट र य पवन ऊर स स थ न, च नन ई NATIONAL INSTITUTE OF WIND ENERGY म व प ( न ऊर जव प र द य ग क कप द र Formerly Centre for Wind Energy Technology ) (न न और न करण य ऊर जव त रजलय, भजरत सरकजर Ministry of New and Renewable Energy, Government of India) EXPRESSION OF INTEREST NIWE is inviting submission of Expression of Interest (EOI) from suitable and experienced equipment Suppliers for comprehensive Low Voltage Ride Through (LVRT) Testing & Measurement services for Wind Turbines. The details of the specification and other details can be found attached as ANNEXURE A & B. The EOI is proposed for acquisitions of new equipment as per the specifications mentioned and also on rental basis. Meeting at NIWE, Chennai with respect to the EOI will be convened with the interested parties within two weeks from the last date of submission of the inputs, if needed, to finalize the Tender terms and conditions. The Interested Bidders shall submit their EOI proposals for the supply of equipment by outright purchase basis (in a sealed cover ) super-scribing EOI from suitable and experienced Equipment suppliers for comprehensive Low Voltage Ride Through (LVRT) Testing & Measurement services for Wind Turbines, Due on 31/01/2018 at 5.30 P.M in the prescribed format to NIWE at the following address: The Deputy Director General (F&A) National Institute of Wind Energy (NIWE) (Formerly Centre for Wind Energy Technology) Velachery Tambaram Main Road, Pallikaranai, Chennai , Tamil Nadu Ph: , , , Mobile: directorfa.niwe@gov.in Any amendment to the EoI will be published only in the NIWE Website : It is the responsibility of participating organization to visit the NIWE website frequently to know about the latest updates / amendments / corrigendum / addendum / clarifications if any. DEPUTY DIRECTOR GENERAL (F&A)
2 Guidelines SPECIFICATIONS FOR LOW VOLATAGE RIDE THROUGH (LVRT) Annexure -A The CEA (Technical Standards for Connectivity to the Grid) 15 th October 2013 for wind and solar generating stations which stipulates that, the wind generating stations connected to the grid at 66 kv voltage level and above shall have the Low Voltage Ride Through (LVRT) capability. FigureA1: LVRT requirement Curve as per Central Electricity Authority (CEA), India During the fault ride through, wind turbine generators in wind farm shall have the capability to meet the following requirements. Shall minimize the reactive power drawal from the grid The wind turbine generator shall provide the active power in proportional to retained grid voltage as soon as the fault is cleared. This Indian Electricity Grid Code (IEGC) and CEA requires Low Voltage Ride-Through (LVRT) capability during voltage drops in Transmission System to 15% of nominal voltage during 300 ms with recovery up to 80% of nominal voltage after 3000ms, with the slope shown in figurea1. An inductive voltage divider is recommended by the international standard for measurement of power quality characteristics of wind turbines (IEC , Edition 2.0, ) which is to be connected ahead of the wind turbine to be tested. This voltage divider consists of a series impedance (coil) Z1 and a short-circuit impedance Z2. Page 1 of 14
3 Figure A2: LVRT test schematic at turbine side The figure A2 shows a simplified view of the test equipment. The impedances Z1 and Z2 consists of several coils each (series and parallel connection). By changing the ratio Z1 to Z2 the depth of the voltage dip can be configured. Test Description The local grid where the wind turbine is to be connected operates at nominal frequency equal to 50 Hz and nominal medium voltage level equal to 11kV,22kV and 33 kv. The test is basically for verifying wind turbine response to voltage drops (due to grid faults) and providing a basis for wind turbine numerical simulation model validation. The voltage dip tests to be carried out with voltage dip test equipment (LVRT-mobile Container). This test equipment is based on the classical voltage divider, consisting of a series impedance Z1 and a short circuit impedance Z2, as illustrated in Figure A3. Figure A3: Test setup diagram. The measurements to be carried out at low, medium and ground as shown in the figure A3. Page 2 of 14
4 Grid Characteristics at possible test location The LVRT testing of a wind turbine is dictated by the grid characteristics of the point of connection of the wind turbine. The stiffness and other parameters are taken into consideration while performing the LVRT testing so that the fault seen at the turbine terminals does not have a severe effect on the grid. General grid characteristics for testing in India: Voltage levels 11, 22 and 33kV Short circuit ratio 3 to 10 Short circuit MVA 100 to 175MVA Cases of Measurements As per IEGC The test should be performed with a voltage dip of minimum of 0.15 p.u and shall remain so for 0.3s. During this period, the turbine shall produce maximum reactive power. After 0.3s, the dip shall be taken away and then the turbine shall produce active power in proportion will the reactive power for the next 2.7s at which time the voltage level shall be raised to 0.85 p.u and be abated. This is shown in figure A4. Cases Special Case 1 - Symmetrical Three phase voltage drop Special Case 2 - Symmetrical Two phase voltage drop Figure A4: IEGC recommendations Magnitude of Voltage (phase to Phase) as a fraction before drop occurs Table A1: Test Cases to be performed for LVRT as per IEGC As per IEC Duration (ms) The response of the wind turbine to the voltage drops specified in Table A2 shall be stated for the wind turbine operating at a) between 0,1 Pn and 0,3 Pn and b) above Page 3 of 14
5 0,9 Pn. The stated response shall include results from 2 consecutive tests of each case (VD1-VD6) by time- series of active power, reactive power, active current, reactive current and voltage at the wind turbine terminals for the time shortly prior to the voltage drop and until the effect of the voltage drop has abated, but also the wind turbine operational mode shall be specified. Table A2 Specification of voltage drops. The specified magnitudes, duration and shape are for the voltage drop occurring when the wind turbine under test is not connected as per IEC Edition 2.0, Measuring Instruments The voltage transducers (transformers) and current transducers (transformers) are the required sensors of the measurement system. The signal conditioning is for connecting these to the low-pass filter that are required for anti-aliasing. The analogue to digital conversion (A/D) shall be of at least 12 bit resolution. Equipment Required accurac y Compliance with Voltage transformers Class IEC Current transformers Class IEC Filter + A/D converter + data acquisition 1 % of full scale IEC Table A3 Specification of requirements for measurement equipment The digital data acquisition system is assumed to log, calculate and store results as specified in the above test description. This requires a sample rate of at least 2 khz per channel of the voltage and current signals. The basis for the above shall be as per the recommendations of IEC Edition 2.0, High Voltage Equipment The switch gears/surge arrestors shall have to operate as per relevant standards, without causing external flashovers to equipment, other test equipment and earthed structures. Some list of equipment s and its relevant standards are mentioned in the below table A4. Page 4 of 14
6 Sl. Product Standard/ Specification 1 High-voltage alternating current circuit-breakers IS IEC Alternating current disconnectors and earthing switches IS 9921 Part 1, 2, 3, 4 & 5 IEC ) 3 Switches for rated voltages above 1 kv and less than 52 kv 4 High-voltage alternating current switch-fuse combinations 5 High-voltage alternating current switchgear-fuse combinations IS 9920 Part 1, 3 & 4 IEC IS IEC IEC Switchgear having combined functions IEC Automatic circuit reclosers IS AC insulation enclosed switchgear and control gear for rated voltages above 1 kv and up to and including 38 kv IS IEC High voltage fuses IS 9385 IEC IS 9402 IEC IS IEC Residual current operated circuit breaker for house hold and similar uses IS IEC IEC IEC Low Voltage Circuit breakers IS Part 2 IEC Low voltage fuses for voltages not exceeding 1000 Vac or 1500 Vdc IS IEC Miniature Fuses IEC Table A4. List of equipment s and its relevant standards Analysis Program/Software The codes supplied may include data acquisition, simulation, calculation and analysis as per relevant standards. Necessary training for capacity building may also be included. Page 5 of 14
7 SAFETY The equipment shall adhere to Indian Electricity Rules and any Regulatory requirements of the Central and State Government, for safety. The equipment layout shall provide adequate working space at each work center to enable unrestricted movement during working. The equipment supplier shall adequately take care of safety aspects on the following points and ensure compliance with suitable display, training, guidance etc. 1. The equipment are expected to comply with the safety requirements of electrical shocks 2. A danger notice board with a sign of skull and bones shall be displayed in Electrical testing area with voltages above 400 Volts. SP 30 charts where required shall be displayed. 3. Instructions for resuscitation of persons suffering from electrical shocks shall be prominently displayed. 4. Switchboard shall have clear space around as specified by statutory authority. 5. Due care shall be taken where the equipment is likely to have emissions in test which may endanger the operator/ equipment. 6. Fire buckets filled with clear and dry sand and water ready for immediate use for extinguishing fires in addition to fire extinguishers for dealing with electric fires shall be available. 7. Fire extinguishers of suitable type depending upon class of fire. 8. Availability of first aid kit. 9. Ensure minimum safe clearance in air between high voltage terminal and earth during testing at different voltage levels of AC/ DC/ Impulse applications. 10. Ensure proper earthing of equipment before making physical contact. 11. Use of safety interlocks. 12. Restrict entry with prominent display boards, of un-authorized persons during testing. 13. Where necessary, control desks shall have inter-locks and control shall be with the authorized persons only. Page 6 of 14
8 Annexure -B LVRT Equipment Requirement The wind turbine testing unit at NIWE is proposing to expand its testing facilities by introducing LVRT testing for wind turbines to ensure turbines installed comply with the guidelines of the Indian Electricity Grid code. This facility will help the manufactures in the country to conduct LVRT test which is mandated by the CEA. Technical Specification Mobile test container (not more than 45 feet, IP 64 class) Vaccum or Air circuit breakers Rated for 36kV voltage levels Lightning withstand voltage 170kV Power frequency withstand voltage 70kV Current values to be defined as per rating levels SF6 breakers to be included where required Rated for 36kV voltage levels Lightning withstand voltage 170kV Power frequency withstand voltage 70kV Current values to be defined as per rating levels Functionality up to 2000m altitude Minimum fault occurrence time 100ms T-connectors to be included Load banks as required IEC cables to be used Voltage level for equipment 11,22 and 33kV / 240V Page 7 of 14
9 Maximum power of turbine to be tested 3MW for 11kV,22kV & 33kV Measurement points at grid and test side Busbars Surge arresters Rated for 45kV Operating voltage 36kV Basic Insulation Level 242kV Current probes, Transducers and data acquisition units to be included Current and Voltage transformers of at least 0.5 class or better Rated voltage of 36kV and current as per MW class Data acquisition unit sample at 2kHz or better with 12 bit resolution and chain accuracy of 1% of full scale value Required software for analysis Voltage dip and test system design according IEC Voltage dip resolution Time adjustment of dip length with 1ms Voltage dip level definition with 1-5% steps of nominal voltage Min voltage dip time 100ms Max voltage dip time ms (however depending on influencing factors of the test site => typical min) PLC Control System Time compensation of circuit breakers Different dip configurations (1-phase / 2-phase / 3-phase) Different dip sequences (single dip / double dip / step dip) Temperature monitoring for the inductances UPS buffered Page 8 of 14
10 Phase angle switching for testing reproduction/repetition Personal and functional safety requirements and standards Emergency stop system with multi surveillance systems Signaling Column Signal horn Mimic Table UPS for control and lights Mains contactor (WIP-Relais) Pressure relief vent Emergency lights Current transformers Digital protection relays Earthing equipment for the Switching Container Earthing equipment for the Reactor Container Surge Arresters Voltage relays Equipment Main components for test ABS switchgear Series reactance s Short circuit reactance s Circuit breakers Two-phase disconnector s Measurements Single-phase Voltage Transformers Single-phase Current Transformers / Transducers Surge arrester protection Phase-to-earth Surge Arresters Phase-to-phase Surge Arresters Page 9 of 14
11 Series Reactance Surge Arresters Short Circuit Reactance Surge Arresters Test system containers Air dehumidifier Heating system Temperature range - 10 C to + 40 C Page 10 of 14
12 ANNEXURE - C Invitation to Submit Expression of Interest (EOI) for c o m p r e h e n s i v e Low Voltage Ride Through Testing & measurement services for Wind Turbines. 1. Introductory Details: a. Name of the equipment supplier b. Whether it is a Govt. /Public/Private Sector/Partnership/Proprietorship firm c. Address with phone/fax numbers d. Name of the Contact Person: Name: Designation: Tel.No.: Mobile no.: ID: e. Annual Turnover for the previous three years Brief profile of the equipment supplier : 3. MNRE approval no. and details if any (Pl. attach a copy of the approval) 4. Experience in supplying the similar type of the above equipment. Briefly specify the details of the company supplied 5. Equipment Compliance certificates as per IEC/IEGC if any 6. Date of Visit to NIWE for technical discussion if any (ref Annexure D) : : : : 7. Additional information if any : Authorized Signatory with Designation Page 11 of 14
13 ANNEXURE-D PROOF FOR TECHNICAL DISCUSSION/ CLARIFICATION Name of the person Designation Mobile No: ID: Company Name Address Phone No: Purpose of Visit Technical discussion/clarification for c o m p r e h e n s i v e Low Voltage Ride Through Testing & measurement services for Wind Turbines, with reference to NIWE EOI Signature Signature of the NIWE official with seal This should be submitted along with the EOI Document. Page 12 of 14
14 ANNEXURE-E EOI SUBMISSION FORMAT Sl.No. List of Documents to be enclosed Remarks 1 Cover letter illustrating the Authorized Official s signature 2 Annexure C duly filled in and signed. 3 Copies of the Registration / Incorporation certificate Pan No./ Income Tax Returns GSTIN Organizational Structure 4 Copies of the certified Audited Statement of Accounts or Separate Audited certificates confirming the turnover for the last three years 5 Copy of MNRE Registration Certificate if any List of relevant Experience and capacity 6 order/sanction letter & certificate of completion 7 CVs of Experts and Professionals within Organization 8 Brief Report with complete technical details for this EOI 9 Annexure D duly signed by the NIWE official (if any) 10 Any other Documents relevant for Assessment & Evaluation Page 13 of 14
15 ANNEXURE-F EOI Eligibility Criteria Criteria Sub- Criteria Weightage* Break-up of Weightage Past experience of the firm with similar requirement 20 Financial Strength of the vendor 10 Turnover figures of the last three years Net profit figures of the last three years 5 5 Quality accreditations, licensing requirements 20 Manufacturing capabilities/tie-ups 10 After-sales support infrastructure 15 Product support 15 Total Remarks : The bidder who secure minimum of 60 out of 100 shall be eligible Page 14 of 14
Enquiry Generation Details
Enquiry Generation Details Page 1 of 4 ल म अन स ध न स थ न INSTITUTE FOR PLASMA RESEARCH परम ण ऊज वभ ग, भ रत सरक र क एक सह यत त स थ न An Aided Institute of Department of Atomic Energy, Government of India
More informationREQUEST FOR PROPOSAL RFP for 12 th Five Year Plan Period (ending )
Annexure-I NATIONAL INSTITUTE OF WIND ENERGY Scientific and Technical Research REQUEST FOR PROPOSAL RFP for 12 th Five Year Plan Period (ending 31.03.2017) National Institute of Wind Energy an Autonomous
More informationAMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS
AMENDMENT NO. 1 SEPTEMBER 2011 TO IS 15086 (Part 1) : 2001/IEC 60099-1 (1991) SURGE ARRESTORS PART 1 NON-LINEAR RESISTOR TYPE GAPPED SURGE ARRESTORS FOR a.c. SYSTEMS (The Amendment was originally published
More informationVI 3 - i TABLE OF CONTENTS
VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3
More informationएस.आर.प.स 40व प र ट क शनउप सम त क ब ठकक मऱएएज ड Additional Agenda Points for 40 th meeting of Protection Sub-Committee of SRPC
ANNEXURE I एस.आर.प.स 40व प र ट क शनउप सम त क ब ठकक मऱएएज ड Additional Agenda Points for 40 th meeting of Protection Sub-Committee of SRPC 1. ग र डडडस टबबन स / ग र डइन सडन टक वववरण - Details of Grid incidents:
More informationQUESTIONNAIRE for Wind Farm Power Stations only
TRANSMISSION SYSTEM OPERATOR QUESTIONNAIRE for Wind Farm Power Stations only To be submitted by the Generation Licensees together with the Application for Connection Certificate according to IEC 61400-21
More informationSouthern Company Interconnection Requirements for Inverter-Based Generation
Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection
More informationस एसआइआर-खन ज एव पद र थ प र द य ग क स स र
स एसआइआर-खन ज एव पद र थ प र द य ग क स स र CSIR-INSTITUTE OF MINERALS & MATERIALS TECHNOLOGY (व ज ञ न क तर औद य ग क अ स ध पररषद) (COUNCIL OF SCIENTIFIC & INDUSTRIAL RESEARCH) BHUBANESWAR /भ व श वर-751013
More informationPROCEDURE FOR INSPECTION OF ELECTRICAL INSTALLATIONS ABOVE 250KVA
PROCEDURE FOR INSPECTION OF ELECTRICAL INSTALLATIONS ABOVE 250KVA Generally inspection of electrical installations is carried out under Regulation-30 (Periodical inspection & testing) & Regulation-43 (Approval
More informationSPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.
1. SCOPE The requirements of this document apply to all Plant, Equipment and Apparatus that are part of, or are Directly connected to, the Company network. Requirements contained herein may be modified
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More informationTable of Contents. Introduction... 1
Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...
More informationINVITATION FOR EXPRESSION OF INTEREST
प रत भ त म द रण ऱय/ SECURITY PRINTING PRESS (भ र प रत भ त म द रण थ म द र त म ण त गम लऱलमट ड क इक ई/ A Unit of Security Printing & Minting Corporation of India Ltd.,) भ र सरक र क प ण सव लम व ध /Wholly owned
More informationMEDIUM VOLTAGE COMPACT STARTER TYPE KAE
MEDIUM VOLTAGE COMPACT STARTER TYPE KAE up to 5 MW up to 17,5 kv up to 400 A Mocotech presents the compact motor starter t ype KAE with integrated autotransformer, switches, control and many more advantages.
More informationشركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.
Our Ref.: 14/2018- Date : Messrs: Dear sir, Tender 14/2018 11& 33 KV Lightning Arrestors. You are kindly requested to quote for the supply and delivery to our stores in Shufat Jerusalem, (DDP) of the following
More informationIssue No : 2 Dt of Revision :
PURCHASE DIVISION DEPARTMENT QUALITY MANUAL Revision No. : 02 Issue No : 2 Dt of Revision : 17.9.2012 Issue Dt. : 30.06.2003 Page No. : 1 OF 3 Issued by : Q A Section : 0 Document : DQM-01 Topic : FORMAT
More informationA Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment
International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV
More informationHigh voltage shunt capacitor banks HIGH VOLTAGE COMPENSATION AND HARMONIC FILTERING PRODUCTS
High voltage shunt capacitor banks Alstom Grid high voltage shunt capacitor bank offering is divided in: By bank construction HV open rack capacitor banks HV enclosed capacitor banks By bank design HV
More informationGrid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017
Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationKENYA ELECTRICITY GENERATING COMPANY LTD
KENYA ELECTRICITY GENERATING COMPANY LTD TENDER No. KGN-HYD-014-2016 TENDER FOR REHABILITATION OF PROTECTION EQUIPMENT FOR MASINGA HYDRO POWER STATION 20/06/2016 ADDENDUM NO. 1 In accordance with the tender
More informationStandard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction
A. Introduction 1. Title: Generator Frequency and Voltage Protective Relay Settings 2. Number: PRC-024-1 3. Purpose: Ensure Generator Owners set their generator protective relays such that generating units
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements
Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system
More informationPOWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.
POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products
More informationRequirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH
Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 5th October 2010 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT
More informationDocuments and Addresses
Report No.: 14-041-MS Sheet: 2 Documents and Addresses Accreditation The Prüffeld der Schaltwerke, Berlin has been approved by the DAkkS (German accreditation body) according to EN ISO/IEC 17025 for tests
More informationForm-IV. Form of Inspection/Test Report. (Under Regulation 43)
Form-IV Form of Inspection/Test Report (Under Regulation 43) 1. Name and address of the Chartered Electrical Safety Engineer 2. Name and address of the consumer (or) Owner(or) supplier: Contact No: E-Mail:
More informationConnection Impact Assessment Application Form
Connection Impact Assessment Application Form This Application Form is for Generators applying for a Connection Impact Assessment (CIA). In certain circumstances, London Hydro may require additional information
More informationELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER
Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...
More informationTS RES - OUTSTANDING ISSUES
TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next
More informationTitle Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)
Discipline Engineering Standard NSW Category Electrical Title Substation Auxiliary Transformer from Rectifier Transformer Secondary Reference Number PDS 01 (RIC Standard: EP 05 00 00 01 SP) Document Control
More informationHigh voltage engineering
High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationत न ब. BUREAU OF INDIAN STANDARDS Hallmarking Department, BIS. Subject: Draft BIS Hallmarking Regulations for comments
त न ब ल र व, ए 11 प ल 2017 व :- ट प पव वलए ए ल र व वन द त न ब ( ए ) व वन 2016 प न त त त क ए ए ए ल र व वन द, व त ज न ट प पव वलए प स ट प पव, कद ल जट ए hallmarking@bis.gov.in 28/04/2017 त ज ज त लग :- ऊप क
More informationPOWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:
POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION
More informationChapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two
Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead
More informationSI.No Parameters CPRI Specification/Requirements To be Completed by the Bidder Guaranteed Technical
Section II Technical Specifications Tender enquiry no. : STDS/12-1/2016-17/PUR/STL/A-1849 Name of the equipment : SPECIFICATIONS OF SYSTEM FOR CONDUCTING DETERMINATION OF ERRORS TEST ON INSTRUMENT TRANSFORMERS
More informationLIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED
LIGHTNING ARRESTOR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, SectorII, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements
Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission
More informationTECHNICAL SPECIFICATION
TECHNICAL SPECIFICATION 1. SCOPE : TECHNICAL SPECIFICATION FOR LIGHTNING ARRESTORS 1.1. This Specification covers design, manufacture, testing at manufacturer's Works, packing, supply, delivery of 42 KV
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationStandard PRC Generator Frequency and Voltage Protective Relay Settings. A. Introduction. See the Implementation Plan for PRC
A. Introduction 1. Title: Generator Frequency and Voltage Protective Relay Settings 2. Number: PRC-024-2 3. Purpose: Ensure Generator Owners set their generator protective relays such that generating units
More informationRENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana
RENEWABLE ENERGY SUB-CODE for Distribution Network connected Variable Renewable Energy Power Plants in Ghana JANUARY 2015 i Table of Content PART A: 1 1 Introduction 1 1.1 Scope 1 1.2 Status 1 1.3 Terms
More information36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)
CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994
More informationTECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This
More informationElectricity Ten Year Statement November Electricity Ten Year Statement November Appendix D
Electricity Ten Year Statement November 2017 01 Electricity Ten Year Statement November 2017 001 Appendix D 1 Short-circuit currents 02 2 Short-circuit current terminology 04 3 Data requirements 07 4 Fault
More informationDESIGN PRACTICE NOTE DESIGN/REVIEW REQUIREMENTS FOR TRACTION BONDING PLAN
Approval Amendment Record Approval Date Version Description 01/04/2014 1 Initial Issue under MTM PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 7 Table of Contents
More informationIDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)
IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone
More informationCustomer Standard. Standard for Embedded Generation (5MW and above)
Standard 01188 Version: 1 Released: 1/10/2014 STANDARD FOR EMBEDDED GENERATION (5MW AND ABOVE) Customer Standard Standard for Embedded Generation If this standard is a printed version, to ensure compliance,
More informationSUB: EMPANELMENT OF CONSULTANCY AGENCIES FOR BUILDING PROJECTS/WORKS.
M/s ----------------------------------------- ----------------------------------------- ------------------------------------------- SUB: EMPANELMENT OF CONSULTANCY AGENCIES FOR BUILDING PROJECTS/WORKS.
More informationBusiness reform Action Plan Rec # 299 to 303 Certification of Electrical Installation by Electrical inspectorate
Business reform Action Plan 2017- Rec # 299 to 303 Certification of Electrical Installation by Electrical inspectorate Statutory requirements for electrical work execution and electrical safety approval
More information(2) New Standard IEEE P (3) Core : (4) Windings :
(d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.
More informationTransformers connected via a cable Overvoltage protection
A P P L I C AT I O N N OT E 2. 1 Transformers connected via a cable Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage
More informationSystem grounding of wind farm medium voltage cable grids
Downloaded from orbit.dtu.dk on: Apr 23, 2018 System grounding of wind farm medium voltage cable grids Hansen, Peter; Østergaard, Jacob; Christiansen, Jan S. Published in: NWPC 2007 Publication date: 2007
More informationUBC Technical Guidelines Section Edition Medium-Voltage Transformers Page 1 of 5
Page 1 of 5 1.0 GENERAL 1.1 Coordination Requirements.1 UBC Energy & Water Services.2 UBC Building Operations 1.2 Description.1 UBC requirements for Substation Transformers. 2.0 MATERIAL AND DESIGN REQUIREMENTS
More informationIEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4
IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 This report records the results of type tests made on H4 series 20 ka Line Discharge Class
More informationUProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy
UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected
More informationWFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS
WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS WFPS1.1 INTRODUCTION 2 WFPS1.2 OBJECTIVE 2 WFPS1.3 SCOPE 3 WFPS1.4 FAULT RIDE THROUGH REQUIREMENTS 4 WFPS1.5 FREQUENCY REQUIREMENTS 5 WFPS1.6 VOLTAGE
More informationSummary of Relaying Reviews Reporting
Revised Attachment B (Agenda Item 6) Summary of Relaying Reviews -- 12-31-04 Reporting This form shall be used without modification to provide a summary of relaying reviews performed by each Transmisission
More informationPOWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC
CITY OF LETHBRIDGE ELECTRIC ENGINEERING STANDARDS POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS The City of Lethbridge acknowledges the use of other utility industry and industry committee
More informationConnection Impact Assessment Application
Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,
More informationEDS FAULT LEVELS
Document Number: EDS 08-1110 Network(s): Summary: EPN, LPN, SPN ENGINEERING DESIGN STANDARD EDS 08-1110 FAULT LEVELS This standard provides guidance on the calculation, application and availability of
More informationTransmission Interconnection Requirements for Inverter-Based Generation
Transmission Requirements for Inverter-Based Generation June 25, 2018 Page 1 Overview: Every generator interconnecting to the transmission system must adhere to all applicable Federal and State jurisdictional
More informationPOWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009
POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power
More informationAnalysis of Major Changes to Arrester Standards IEC STEVE BREWER
Analysis of Major Changes to Arrester Standards IEC 60099-4 STEVE BREWER Analysis of Major Changes to Arrester Standard IEC 60099-4 Steve Brewer- Senior Product Manager - HPS Arrester Business Unit Agenda
More information5 Summary LOW VOLTAGE RIDE THROUGH WITH HIGH CURRENT INJECTION. Motivation. Future Requirements. Test results for symmetrical failures
LOW VOLTAGE RIDE THROUGH WITH HIGH CURRENT INJECTION 1 2 3 4 Motivation Future Requirements Test results for symmetrical failures Test results for asymmetrical failures 5 Summary 1 DYNAMIC VOLTAGE CONTROL:
More informationShunt Reactors. Global Top Energy, Machinery & Plant Solution Provider
Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical
More informationANNEXURE-I. Documents to be uploaded 1 Certificate of Registration with Industries 2 VAT Certificate 3 Service Tax Certificate
ANNEXURE-I Documents to be uploaded 1 Certificate of Registration with Industries 2 VAT Certificate 3 Service Tax Certificate 4 Excise Duty Registration Certificate 5 Pan Card 6 Approved Vendor Certificates
More informationCompany Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System
Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels
More informationNORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:
NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information
More informationStarSine Power Quality Products
StarSine Power Quality Products Medium Voltage Static Voltage Regulator ( MV SVR ) MV SVR PROTECTS THE WHOLE FACILITY LOADS FROM VOLTAGE SAGS CAUSED BY UTILITY GRID FAULTS Voltage sags, whether due to
More informationشركة الوقت للكهرباء والمقاوالت ذ.م.م.
CONTRACTING COMPANY W.L.L. is a leading corporate in the United Arab Emirates offering quality services in the field of High Voltage Electrical work 400, 132 & 33 kv and Medium Voltage Power Distribution
More informationPROCUREMENT OF GOODS UNDER OPEN TENDER PROCEDURE
IFB NO. KGEC/DST-WB/EE /2018-19/995 PROCUREMENT OF GOODS UNDER OPEN TENDER PROCEDURE Kalyani Government Engineering College Kalyani 741 235; Nadia, West Bengal 1 Government of West Bengal Office of the
More informationRemotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application
General Application Information Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application Hydro One Remote Communities Inc. Lori.Rice@hydroone.com 1-807-474-2828 This Application
More informationTHE KENYA POWER AND LIGHTING CO. LTD. SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT
THE KENYA POWER AND LIGHTING CO. LTD SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT NAME DESIGNATION SIGNATURE DATE Compiled by Ephantus Nyagah Ag. Senior Engineer Checked by Eng. Thagichu Kiiru Deputy
More informationSUPPLY OF CARRIER PROTECTION COUPLER TYPE NSD-50
(I) GENERAL : Indoor PLCC Equipments are required for important 400KV, 220KV and 132KV Sub/station for Speech, Data Transmission, Protection and Teleprinter Links. (II) GENERAL REQUIREMENT : The equipments
More informationNOTICE INVITING TENDER Limited Tender on Single Bid Basis Milling Cutters. Tender Enquiry No: Due Date:
SCOOTERS INDIA LIMITED Sarojini Nagar, Lucknow - 226008 (Phones: 0522-2476090, 2476242 (Exchange) Direct: 0522-2476139) Fax: 91-522-2476190 Email: materials@scoootersindia.com NOTICE INVITING TENDER Limited
More informationLIMITS FOR TEMPORARY OVERVOLTAGES IN ENGLAND AND WALES NETWORK
LIMITS FOR TEMPORARY OEROLTAGES IN ENGLAND AND WALES NETWORK This document is for internal and contract specific use only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept
More informationTABLE OF CONTENT
Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES
More informationFinal ballot January BOT adoption February 2015
Standard PRC-024-21(X) Generator Frequency and Voltage Protective Relay Settings Standard Development Timeline This section is maintained by the drafting team during the development of the standard and
More informationElectrical Description
History of this Document Rev. no.: Date: Description of change 0 First edition 2 2003-10-08 Section 3: The rated power of the transformer can be increased by 40% if they are equipped with 6 fans for forced
More informationWind Power Facility Technical Requirements CHANGE HISTORY
CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical
More informationModeling insulation in high-voltage substations
38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other
More informationExperience with Connecting Offshore Wind Farms to the Grid
Oct.26-28, 2011, Thailand PL-22 CIGRE-AORC 2011 www.cigre-aorc.com Experience with Connecting Offshore Wind Farms to the Grid J. FINN 1, A. SHAFIU 1,P. GLAUBITZ 2, J. LOTTES 2, P. RUDENKO 2, M: STEGER
More informationPROCUREMENT OF SERVO CONTROLLED VOLTAGE STABILIZER FOR STPI-NASIK
PROCUREMENT OF SERVO CONTROLLED VOLTAGE STABILIZER FOR STPI-NASIK Sealed quotations are invited under Two-Bid system from reputed agencies, either by themselves or as a joint venture/consortium/partnership
More informationI -limiter The world s fastest switching device
I S -limiter 2 I S -limiter The world s fastest switching device Reduces substation cost Solves short-circuit problems in new substations and substation extensions Optimum solution for interconnection
More informationMedium voltage circuit breaker technical guide
IEC 56-1987 - ANSI C37-06 1987 COMPARISON CONTENTS page 1 - Rated voltage 3 2 - Rated isolating level 3 3 - Rated voltage during normal running 4 4 - Allowable short time current 4 5 - Allowable current
More informationSelection of MO surge arresters Overvoltage protection
A P P L I C AT I O N N OT E 1. 1 Selection of MO surge arresters Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage protection
More informationPURCHASE DIVISION DEPARTMENT QUALITY MANUAL Revision No. : 02 Issue No: : 2 Dt of Revision : Issue Dt. :
Section : 0 Document : DQM-01 Topic : FORMAT 6 OF PROCUREMENT PROCEDURE OF CPRI (NON-WORKS) Section I(B)-Technical Specification Tender Enquery No PUR/UARC-02/14-15 Name of the Equipment: Damped Oscillatory
More information7. INSPECTION AND TEST PROCEDURES
7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationMESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION
Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:
More informationFixed Series Compensation
Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and
More informationEE 1402 HIGH VOLTAGE ENGINEERING
EE 1402 HIGH VOLTAGE ENGINEERING Unit 5 TESTS OF INSULATORS Type Test To Check The Design Features Routine Test To Check The Quality Of The Individual Test Piece. High Voltage Tests Include (i) Power frequency
More informationNIC Project Medium Voltage Direct Current Link Technical Specification
1 SCOPE This Specification details SP Energy Networks (SPEN) requirements for a bidirectional Medium Voltage Direct Current (MVDC) Link for the Angle-DC project, being carried out in conjunction with Ofgem
More informationINDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR , INDIA
INDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR- 721302, INDIA No. IIT/ISE/RO WATER PURIFIER/2018-19/1 Date: 18.04.2018 Last date for submission: Friday, May 11,2018 at 3:00 PM Time &Date for Opening: Friday,
More informationAppendix D Fault Levels
Appendix D Fault Levels Page 1 Electricity Ten Year Statement November 2013 D.1 Short Circuit Currents Short Circuit Currents Three phase to earth and single phase to earth short circuit current analyses
More informationFACILITY RATINGS METHOD TABLE OF CONTENTS
FACILITY RATINGS METHOD TABLE OF CONTENTS 1.0 PURPOSE... 2 2.0 SCOPE... 3 3.0 COMPLIANCE... 4 4.0 DEFINITIONS... 5 5.0 RESPONSIBILITIES... 7 6.0 PROCEDURE... 8 6.4 Generating Equipment Ratings... 9 6.5
More informationLevel 6 Graduate Diploma in Engineering Electrical Energy Systems
9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,
More information