Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Size: px
Start display at page:

Download "Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)"

Transcription

1 Discipline Engineering Standard NSW Category Electrical Title Substation Auxiliary Transformer from Rectifier Transformer Secondary Reference Number PDS 01 (RIC Standard: EP SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards and Systems Refer to Reference Number Signalling Standards Engineer T Moore GM Infrastructure Strategy & Performance M Owens Safety Committee Refer to minutes of meeting 24/01/05

2 Disclaimer Australian Rail Track Corporation has used its best endeavors to ensure that the content, layout and text of this document is accurate, complete and suitable for its stated purpose. It makes no warranties, express or implied, that compliance with the contents of this document shall be sufficient to ensure safe systems of work or operation. Australian Rail Track Corporation will not be liable to pay compensation in respect of the content or subsequent use of this document for any other purpose than its stated purpose or for any purpose other than that for which it was prepared except where it can be shown to have acted in bad faith or there has been willful default. Document Approval The technical content of this document has been approved by the relevant ARTC engineering authority and has also been endorsed by the ARTC Safety Committee. Document Supply and Control The Primary Version of this document is the electronic version that is available and accessible on the Australian Rail Track Corporation Internet and Intranet website. It is the document user s sole responsibility to ensure that copies are checked for curency against the Primary Version prior to its use. Copyright The information in this document is Copyright protected. Apart from the reproduction without alteration of this document for personal use, non-profit purposes or for any fair dealing as permitted under the Copyright Act 1968, no part of this document may be reproduced, altered, stored or transmitted by any person without the prior written consent of ARTC. March 2005 Page 2 of 14

3 About This Standard This document details the whole of life performance requirements for the purchase and maintenance of a substation indoor auxiliary transformer that is supplied from one of the 600 V secondary windings of a rectifier transformer. The substation auxiliary transformer provides the supply for the auxiliary services in Australian Rail Track Corporation (ARTC) traction substations. This document does not cover auxiliary transformers supplied from a rectifier transformer with 2420 V secondary windings or auxiliary transformers that are supplied from a high voltage busbar. Auxiliary transformers with a three-phase 220 V secondary winding are also not covered. March 2005 Page 3 of 14

4 Document History Primary Source RIC Standard EP SP Version 1.0 List of Amendments ISSUE DATE CLAUSE DESCRIPTION /01/2005 Reformatted to ARTC Standard /03/2005 Disclaimer Minor editorial change March 2005 Page 4 of 14

5 Contents About This Standard...3 Document History Scope and Application References Australian Standards ARTC documents Drawings Definitions and abbreviations Introduction Functional characteristics General Whole-of-life cost Performance characteristics Technical characteristics Rated insulation level Harmonic voltages Rating plate Terminal arrangement Enclosure Earth terminal Lifting attachments Temperature-rise limits Finish Maintenance...12 March 2005 Page 5 of 14

6 9. Tests Acceptance tests Periodic tests Data set associated with the equipment Equipment manuals Test results Life cycle costing Technical information Technical schedule...14 March 2005 Page 6 of 14

7 1 Scope and Application This document details the whole of life performance requirements for the purchase and maintenance of a substation indoor auxiliary transformer that is supplied from one of the 600 V secondary windings of a rectifier transformer. The substation auxiliary transformer provides the supply for the auxiliary services in Australian Rail Track Corporation (ARTC) traction substations. This document does not cover auxiliary transformers supplied from a rectifier transformer with 2420 V secondary windings or auxiliary transformers that are supplied from a high voltage busbar. Auxiliary transformers with a three-phase 220 V secondary winding are also not covered. The requirements of this document apply from this document s date-of-issue to all new auxiliary transformers that are supplied from one of the 600 V secondary windings of a rectifier transformer. 2 References 2.1 Australian Standards The following Australian Standards are either referenced in this document or can provide further information. AS Degrees of protection provided by enclosures for electrical equipment (IP Code) AS Power transformers Part 1: General AS Power transformers Part 2: Temperature rise AS Power transformers Part 3.0: Insulation levels and dielectric tests General requirements AS Power transformers Part 3.1: Insulation levels and dielectric tests External clearances in air AS Power transformers Part 5: Ability to withstand shortcircuit AS Power transformers Part 6: Determination of transformer and reactor sound levels AS Colour standards for general purposes AS Dry-type power transformers AS/NZS Electromagnetic Compatibility (EMC) Part 3.6: Limits Assessment of emission limits for distorting loads in MV and HV power systems (IEC :1996, MOD) 2.2 ARTC documents PDS 16 Transformer Loss Evaluation. March 2005 Page 7 of 14

8 PDS 04 System Substation Earthing. 2.3 Drawings The following drawings form part of this document: None. 3 Definitions and abbreviations For the purpose of this document the definitions given in AS 2374 apply. In addition the following definitions also apply: Primary winding The winding that receives the active power from the supply system, usually the winding having the highest rated voltage. Principal tapping Is the mean tapping position. It is also the tapping to which the rated quantities are related. Secondary winding The winding that delivers the active power to the load circuit, usually the winding having the lowest rated voltage. 4 Introduction The 1500 V traction system is unearthed, therefore the secondary of the rectifier transformer and the primary of the auxiliary transformer cannot be earthed. Special design considerations are required to ensure that the transformer will not be affected by faults on the traction system. 5 Functional characteristics 5.1 General The substation auxiliary transformer provides the supply for the auxiliary services in ARTC traction substations. The transformer primary winding is supplied from one of the secondary windings of a rectifier transformer. The rectifier transformer supplies a series bridge rectifier for the 1500 V traction system. The auxiliary services include lighting, low voltage power, dc power supplies, ventilation and compressed air. They are not used for supplying dc traction loads. The auxiliary services may be three-phase 415 V or single phase 240 V. The traction substations are in the area bounded by Newcastle (north), Dapto (south) and Lithgow (west). 5.2 Whole-of-life cost The selection of the most suitable transformer shall be made on the basis of minimising the whole-of-life cost. The following factors must be considered in determining this: March 2005 Page 8 of 14

9 Initial purchase price. Cost of changes to the Technical Maintenance Plan and Service Schedules or the creation of new manuals and schedules. Cost of manuals. Cost of maintenance. Cost of replacement parts. Cost of inventory spares. Environmental costs. Electrical losses. Refer to document PDS 16 Transformer Loss Evaluation for the method of evaluating transformer losses. Cost of installation. Reliability and cost of failures. Cost of modifications to other parts of the installation. Lifetime of equipment. Discount rate. Cost of staff training. Cost of decommissioning and disposal. Cost of special tools. Cost of changes and management of drawings. 6 Performance characteristics Number of phases 1 or 3. Frequency Type Type of cooling 50 Hz. Indoor, Enclosed dry-type. Air natural. Rated Voltages Primary 600 Vrms Secondary 240 Vrms (1) or 415 Vrms (3) Tappings Full kva tappings on the primary winding at ± 2.5% and ± 5% of the principal tapping. The tappings shall be controlled by off-circuit bolted links. March 2005 Page 9 of 14

10 System highest voltage Primary 3.6 kvrms Secondary 1.1 kvrms System earthing Non-effectively earthed. Rated insulation level Primary 16 kvrms (power frequency) Connection vector symbol Neutral terminal Dyn 1 (three-phase transformer). Star point of lower voltage winding shall be connected to a suitable terminal and fully insulated from earth. Impedance voltage at rated Refer to AS , Table 1. current and 75 C Sound pressure level Refer to AS , Appendix AA. Special physical characteristics Refer to section 7. 7 Technical characteristics 7.1 Rated insulation level The primary winding(s) are connected to the unearthed secondary of the rectifier transformer. During fault conditions, the voltage to earth of this winding can exceed 3.5 kvdc. Special attention is drawn to the rated insulation level requirements in section Harmonic voltages The rectifiers create high harmonic distortion of the current waveform. This distorted current waveform interacts with the impedance of the rectifier transformer resulting in harmonic voltages. The design of the auxiliary transformer must therefore take these harmonic currents and voltages into account. 7.3 Rating plate The rating plate shall meet the requirements of AS , Clause 7, and shall include a diagram of connections. A terminal marking plate complying with the requirements of AS , Clause ZC7, shall also be attached to the transformer. The plates shall not be attached to a removable cover. 7.4 Terminal arrangement The three primary winding leads and the four secondary winding leads (two leads per winding for 240 V) shall be brought out from each transformer winding and terminated on screwed terminal studs suitable for use with crimp lugs. The terminals shall be suitably proportioned and marked to the requirements of AS , Clause ZC4. An insulated barrier shall separate the primary terminals and the secondary terminals. The complete arrangement shall be enclosed in the transformer enclosure. March 2005 Page 10 of 14

11 7.5 Enclosure The transformer shall be enclosed to meet the requirements of AS 2735 Clause and AS 1939 with a degree of protection of IP21. A method for securing the input and output cables shall be incorporated into the enclosure. 7.6 Earth terminal An earthing terminal suitable for the connection of a 70 mm 2 cable shall be located externally on the transformer enclosure. 7.7 Lifting attachments Suitable lifting lugs shall be provided for lifting the transformer. 7.8 Temperature-rise limits The transformer shall be capable of continuous operation at rated power without exceeding the maximum temperature-rise limits as specified in AS , Clause Finish The transformer enclosure (internal and external) shall be painted with a smooth semi-gloss enamel. 8 Maintenance The relevant ARTC Technical Maintenance Plans (TMP) shall be adhered to for the maintenance of the type of transformer. Where a new type of transformer is purchased and installed that is not covered by the TMP, then a new service schedule shall be created and the TMP updated. This shall include: The Maintenance Policy, defining the practical means of maintaining the equipment. The tasks to be performed at each level of maintenance and staff skill levels required. Test equipment and tools. It is preferable that the period for routine maintenance shall not be more frequent than for the types of transformers currently detailed in the ARTC Technical Maintenance Plan. 9 Tests 9.1 Acceptance tests Routine tests shall be carried out on each transformer to AS Clause The results shall be recorded. A record of a test certificate for type tests carried out on a similar transformer to AS Clause shall also be available for each transformer. March 2005 Page 11 of 14

12 9.2 Periodic tests Refer to ARTC Technical Maintenance Plan. 10 Data set associated with the equipment The following data shall be maintained for each transformer. This data shall be the property of ARTC and maintained by the Maintenance Provider responsible for the installation in which the transformer is installed Equipment manuals The Equipment Manuals must be provided for the installation and shall include full instructions for the preventative, surveillance and corrective maintenance, comprehensive fault diagnosis, rectification procedures and staff training requirements. It shall include all drawings needed for the above. All drawings shall show sufficient detail to enable satisfactory maintenance of the equipment Test results The results of all tests relating to the transformer, including acceptance tests and periodic and corrective maintenance tests, shall be recorded Life cycle costing All the data and assumptions pertaining to the determination of the whole-of-life cost calculations shall be recorded Technical information The information listed in the attached Technical Schedule shall be maintained for each transformer. March 2005 Page 12 of 14

13 11 Technical schedule Manufacturer... Serial number... Year of manufacture... Rated primary voltage... V Rated secondary voltage... V Rated power... kva Connection vector symbol... Maximum temperature rise of windings... C Impedance voltage at rated current and 75 C/115 C* (Expressed as percentage of rated voltage)... % No-load current with rated voltage applied to the principal tapping (Expressed as percentage of rated current)... % No-load current with 110% of rated voltage applied to the principal tapping (Expressed as percentage of rated current)... % No-load loss... W Load loss... W Type of core steel - hot or cold rolled... Brand or trade name and grade of core steel... Flux density based on net cross-section of steel with rated voltage at rated frequency applied to the principal tapping Limbs... T Yoke... T Mass of windings only... kg Mass of transformer core and windings only... kg Mass of one transformer complete with metal enclosure... kg Mean audible sound level... db March 2005 Page 13 of 14

14 Voltage withstand test: primary terminals - Lightning impulse withstand voltage... kv p - Power frequency withstand voltage... kv rms secondary terminals - Power frequency withstand voltage... kv rms Terminals, minimum clearance in air: primary secondary mm mm between phases... mm phase to earth... mm Is heat-shrink material provided on the primary terminals?... * YES / NO Type of insulating material used for windings... Type of material used for windings - copper or aluminium... Temperature class of insulation... Overall transformer dimensions: Length... Width... Height... mm mm mm Protective treatment applied to: Internal surfaces... External surfaces... * Cross out where not applicable. Departures from Specification Are there any departures from the requirements of this Specification... * YES / NO Departures from the requirements of this Specification must be highlighted. March 2005 Page 14 of 14

Reference Number PPS 05 - (RIC Standard: EP SP)

Reference Number PPS 05 - (RIC Standard: EP SP) Discipline Engineering Standard - NSW Category Electrical Title Low Voltage Isolating Transformer Reference Number PPS 05 - (RIC Standard: EP 17 00 00 11 SP) Document Control Status Date Prepared Reviewed

More information

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved Discipline Engineering Standard - NSW Category Signalling Title Power Supply Units for Signalling Equipment - DC Track Feeds Reference Number SPS 29 - (RIC Standard: SC 09 10 06 00 SP) Document Control

More information

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved Discipline Engineering Standard NSW Category Services Title Compilation of Historical Records of Buildings Scheduled for Demolition Reference Number EYP 01 (RIC Standard: G 2650) Document Control Status

More information

Reference Number PCP 02 (RIC Standard: EP SP)

Reference Number PCP 02 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Reference Number PCP 02 (RIC Standard: EP 20 00 00 20 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

Reference Number PDS 07 (RIC Standard: EP SP)

Reference Number PDS 07 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Reference Number PDS 07 (RIC Standard: EP 12 10 00 20 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Jan 05 Standards

More information

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved Discipline Engineering Standard - NSW Category Signalling Title Reference Number SPS 19 - (RIC Standard: SC 07 40 04 00 SP) Document Control Status Date Prepared Reviewed Endorsed Approved May 05 Standards

More information

Title Operating Work - Low Voltage Distribution System. Reference Number POP 06 - (RIC Standard: EP SI)

Title Operating Work - Low Voltage Distribution System. Reference Number POP 06 - (RIC Standard: EP SI) Discipline Engineering Standard - NSW Category Electrical Title Operating Work - Low Voltage Distribution System Reference Number POP 06 - (RIC Standard: EP 95 30 00 03 SI) Document Control Status Date

More information

Title Lightning/ Surge Protection - Power Inductors. Reference Number SPS 37 - (RIC Standard: SC SP)

Title Lightning/ Surge Protection - Power Inductors. Reference Number SPS 37 - (RIC Standard: SC SP) Discipline Engineering Standard NSW Category Signalling Title Reference Number SPS 37 - (RIC Standard: SC 09 15 04 00 SP) Document Control Status Date Prepared Reviewed Endorsed Approved May 05 Standards

More information

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER Approval Amendment Record Approval Date Version Description 03/05/2017 1 Initial issue PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 13 Table of Contents 1. Purpose...

More information

Reference Number PDS 04 (RIC Standard: EP SP)

Reference Number PDS 04 (RIC Standard: EP SP) Discipline Engineering Standard NSW Category Electrical Title Reference Number PDS 04 (RIC Standard: EP 12 10 00 10 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved Discipline Engineering Standard NSW Category Signalling Title Reference Number SDS 17 (RIC Standard: SC 00 13 01 17 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION

MESP TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Engineering Specification Head of Electrical Engineering MESP 050100-01 TECHNICAL SPECIFICATION FOR AN AUXILIARY OR ESSENTIAL SERVICES AND AUXILIARY TRANSFORMER FOR USE IN A RAILWAY SUBSTATION Version:

More information

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved Discipline Engineering Standard - NSW Category Signalling Title Reference Number SPS 12 - (RIC Standard: SC 07 10 01 00 SP) Document Control Status Date Prepared Reviewed Endorsed Approved May 05 Standards

More information

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER Engineering Specification TECHNICAL SPECIFICATION FOR AN ESSENTIAL Version: 3 Issued: 14 October 2016 Owner: Chief Engineer Approved By: Andrew Russack Head of Engineering - Electrical PRINTOUT MAY NOT

More information

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved Discipline Engineering Standard - NSW Category Signalling Title Reference Number SPS 20 - (RIC Standard: SC 07 42 00 00 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Revision 2 May

More information

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved Discipline Engineering Standard NSW Category Electrical Title Reference Number PDS 05 (RIC Standard: EP 12 10 00 11 SP) Document Control Status Date Prepared Reviewed Endorsed Approved Mar 05 Standards

More information

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW)

DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) DELHI METRO RAIL CORPORATION LIMITED DMRC ELECTRICAL STANDARDS & DESIGN WING (DESDW) SPECIFICATION NO. DMES- 0005/ DMRC-E-TR-TRANSF-05 SPECIFICATIONS FOR THREE PHASE 33 kv/415 V AUXILIARY Issued on: Date

More information

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA) 0.415/33kV DESIGN AND CONSTRUCTION General 1. The transformer shall be three phase, oil immersed type, air cooled, core type, outdoor

More information

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS

PURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

Distribution transformers Part 2 Ground mounted transformers not closecoupled

Distribution transformers Part 2 Ground mounted transformers not closecoupled PRODUCED BY THE OPERATIONS DIRECTORATE OF ENERGY NETWORKS ASSOCIATION Technical Specification 35-1 Distribution transformers Part 2 Ground mounted transformers not closecoupled www.energynetworks.org PUBLISHING

More information

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER

MESP TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER TRANSFORMER Engineering Specification Electrical Networks TECHNICAL SPECIFICATION FOR A 1500V DC RECTIFIER Version: 3 Issued: February 2018 Owner: Head of Engineering - Electrical Approved By: Andrew Russack Head

More information

K Factor Power Transformers

K Factor Power Transformers Ashley-Edison AsiaElectricTransformers (UK) K Factor Power Transformers DTKF series Low Voltage Dry Type K Factor Power Transformers AET-DTKF-2004-01: Page 1 Asia Electric Transformers, Entrepreneur Business

More information

Cast resin transformers HARMONY TM

Cast resin transformers HARMONY TM Cast resin transformers HARMONY TM HARMONY TM the optimum solution for higher performance At a time when we are all seeking to preserve our way of life, the production of equipment whilst ensuring safety

More information

CSEE UM71 AF Jointless Track Circuits Set-up, Test and Certification

CSEE UM71 AF Jointless Track Circuits Set-up, Test and Certification Discipline: Engineering (Signalling) Category: Standard CSEE UM71 AF Jointless Track Circuits Set-up, Test and Certification SES 06 Applicability New South Wales CRIA (NSW CRN) Primary Source RIC Standard

More information

WB&S FS2500 AF Jointless Track Circuits Set-Up, Test and Certification

WB&S FS2500 AF Jointless Track Circuits Set-Up, Test and Certification Discipline: Engineering (Signalling) Category: Standard WB&S FS2500 AF Jointless Track Circuits Set-Up, Test and Certification SES 07 Applicability New South Wales CRIA (NSW CRN) Primary Source RIC Standard

More information

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994

More information

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.

SPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it. 1. SCOPE The requirements of this document apply to all Plant, Equipment and Apparatus that are part of, or are Directly connected to, the Company network. Requirements contained herein may be modified

More information

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide

MGM Transformer. Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Vacuum Pressure Impregnated (VPI) Dry-Type Substation Transformer Specification Guide MGM Transformer Company 5701 Smithway Street Commerce, CA 90040 www.mgmtransformer.com Phone: 323.726.0888

More information

ML TI21 AF Jointless Track Circuits Set Up, Test and Certification

ML TI21 AF Jointless Track Circuits Set Up, Test and Certification Discipline: Engineering (Signalling) Category: Standard ML TI21 AF Jointless Track Circuits Set Up, Test and Certification SES 08 Applicability New South Wales CRIA (NSW CRN) Primary Source RIC Standard

More information

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers SPECIFICATION GUIDE ABB VACUUM CAST COIL DRY TRANFORMERS CONTENTS 1. General 1.1. Codes and standards 1.2. Service conditions 1.3. System characteristics 1.4. Documentation 2. Design and construction 2.1.

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

Electrical Description

Electrical Description History of this Document Rev. no.: Date: Description of change 0 First edition 2 2003-10-08 Section 3: The rated power of the transformer can be increased by 40% if they are equipped with 6 fans for forced

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

AS/NZS :2013 (IEC , , MOD)

AS/NZS :2013 (IEC , , MOD) AS/NZS 60076.7:2013 (IEC 60076-7, Ed. 1.0 2005, MOD) Australian/New Zealand Standard Power transformers Part 7: Loading guide for oil-immersed power transformers AS/NZS 60076.7:2013 AS/NZS 60076.7:2013

More information

Capacitive voltage transformers

Capacitive voltage transformers Capacitive voltage transformers Outdoor operation Oil-paper insulated ECF (72 550) kv General description Capacitive voltage transformers of type ECF are used in high-voltage switchgears from 72 to 550

More information

Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INSTRUMENTRANSFORMER

Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INSTRUMENTRANSFORMER Customer : REV. 0 Page 1/16 Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INRUMENTRANSFORMER CVS - 24 - G - Revision Prepared Description Checked by Rev. Date by 0 13/06/16 First issue E.

More information

OIL-IMMERSED ARC-SUPPRESSION COILS

OIL-IMMERSED ARC-SUPPRESSION COILS ISO 9001:2000 99-320 Żychlin, ul. Narutowicza 70 ISO 14001:2004 PN-N-18001:2004 www.ftz.pl Secretary s Office Tel.: +48 24 285 46 05, Fax: +48 24 285 46 31 zarzad@ftz.pl Sales and Marketing Department

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60076-21 Edition 2.0 2018-12 IEEE Std C57.15 Power transformers Part 21: Standard requirements, terminology, and test code for step-voltage regulators INTERNATIONAL ELECTROTECHNICAL

More information

Test description for dry-type transformers chapter for special tests

Test description for dry-type transformers chapter for special tests Test description for dry-type transformers chapter for special tests 1. SCOPE 4 2. STANDARDS 5 3. LIGHTNING IMPULSE TEST 6 4. SOUND LEVEL MEASUREMENT 7 4.1. STANDARD 7 4.2. AIM 7 4.3. THEORETICAL PRINCIPAL

More information

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

NT & NQ CLASS II TRANSFORMERS FOR SIGNALLING SYSTEMS. A Balfour Beatty and Alstom Company

NT & NQ CLASS II TRANSFORMERS FOR SIGNALLING SYSTEMS. A Balfour Beatty and Alstom Company NT & NQ CLASS II TRANSFORMERS FOR SIGNALLING SYSTEMS A Balfour Beatty and Alstom Company NT Transformers CLASS II DOUBLE INSULATED HYBRID TRANSFORMERS / LOW POWER-T/J COMBINED UNITS FOR RELAY AND SSI SIGNALLING

More information

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1 GENERAL: The scope of this document is to provide instruction for the installation and testing of Medium Voltage, 3 Phase, Pad Mounted Transformers installed at the University of Missouri. Preferred transformers

More information

General Electricity Company of Libya

General Electricity Company of Libya GES 22214 Technical Specification of GECOL 11/0.4kV Oil Immersed Ground Mounted Three Phase Sealed Type Distribution Transformers (Revision history) Issued on: Jan. 01, 2007 General Electricity Company

More information

Australian Standard. Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv AS

Australian Standard. Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv AS AS 2067 1984 Australian Standard Switchgear assemblies and ancillary equipment for alternating voltages above 1 kv [Title allocated by Defence Cataloguing Authority: SWITCHGEAR ASSEMBLIES, ELECTRICAL AND

More information

Collection of standards in electronic format (PDF) 1. Copyright

Collection of standards in electronic format (PDF) 1. Copyright Collection of standards in electronic format (PDF) 1. Copyright This standard is available to staff members of companies that have subscribed to the complete collection of SANS standards in accordance

More information

Introduction. Centrado leading-edge transformer. Introduction

Introduction. Centrado leading-edge transformer. Introduction Introduction Centrado leading-edge transformer products are designed to optimize safety and produced to deliver a great electrical power experience and solution - for factory, infrastructure, home industry,

More information

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.

Device Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L. /9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala

More information

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS

Australian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS AS 60044.1 2007 AS 60044.1 2007 Australian Standard Instrument transformers Part 1: Current transformers (IEC 60044-1 Ed.1.2 (2003) MOD) This Australian Standard was prepared by Committee EL-013, Measurement

More information

Status Date Prepared Reviewed Endorsed Approved

Status Date Prepared Reviewed Endorsed Approved Discipline Engineering Standard NSW Category Signalling Title Reference Number SMS 12 (RIC Standard: SC 07 44 04 00 EQ) Document Control Status Date Prepared Reviewed Endorsed Approved Issue 1 Revision

More information

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads.

and cured to reduce hot spots and seal out moisture. The assembly shall be installed on vibration-absorbing pads. -156 Purpose & Industrial Control Purpose (1000 kva and Below) mounted dry-type transformers of the two-winding type, self-cooled, with ratings and voltages as indicated on the drawings. shall be manufactured

More information

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS SECTION 16461C - DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.1 This section includes design and performance requirements for dry-type transformers rated for use on secondary distribution systems rated 600

More information

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class

GE Ventilated Dry-Type Transformers. Secondary Substation Transformers - 5 and 15kV Class GE Ventilated Dry-Type Transformers Secondary Substation Transformers - 5 and 15kV Class GE ventilated dry-type transformers are designed for indoor or outdoor applications in schools, hospitals, industrial

More information

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016)

Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016) Typical Specification 1.2kV Class Energy Efficient Dry-Type Distribution Transformers Compliant to DOE 10, CFR Part 431 (effective as of January 1 st, 2016) Canada 595 Southgate Drive Guelph, Ontario N1G

More information

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS

51-SDMS-02 SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36KV 400/230 VOLTS This specification is property of SEC and Subject to change or modification without any notice Table of Contents Clause Page 1.0 SCOPE

More information

Test Report CESI A6/ Approved Page 1. MF Trasformatori s.r.l. - Calcinato (BS) Italy

Test Report CESI A6/ Approved Page 1. MF Trasformatori s.r.l. - Calcinato (BS) Italy A6/028659 Test Report CESI Approved Page 1 Client MF Trasformatori s.r.l. - Calcinato (BS) Italy Tested equipment Non-enclosed three-phase dry-type power transformer with three windings, with encapsulated

More information

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V

51-SDMS-04 SPECIFICATIONS FOR. DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V SPECIFICATIONS FOR DISTRIBUTION TRANSFORMERS UP TO 36 kv WITH ALUMINUM WINDINGS FOR DUAL SECONDARY 400/230 V AND 230/133 V This specification is property of SEC and subject to change or modification without

More information

50-SDMS-01 SPECIFICATIONS FOR

50-SDMS-01 SPECIFICATIONS FOR SPECIFICATIONS FOR CURRENT TRANSFORMERS UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice C O N T E N T S CLAUSE TITLE PAGE NO. ------------ --------

More information

Power Quality Solutions

Power Quality Solutions Power Quality Solutions What is Power Quality? For electrical systems to function in their intended manner without significant loss of performance or life, they require a supply of electricity that is

More information

Capacitive voltage transformers

Capacitive voltage transformers Capacitive voltage transformers Outdoor operation Oil-paper insulated ECF (72 550) kv General description Capacitive voltage transformers of type ECF are used in high-voltage switchgears from 72 to 550

More information

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS 006: 2008 CEB SPECIFICATION COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS CEYLON ELECTRICITY BOARD SRI LANKA Specification for COMBINED METERING TRANSFORMERS (OUTDOOR TYPE) FOR

More information

Test description for dry-type transformers chapter for type tests

Test description for dry-type transformers chapter for type tests Test description for dry-type transformers chapter for type tests 1. SCOPE 4 2. STANDARDS 5 3. LIGHTNING IMPULSE TEST 6 3.1. STANDARD 6 3.2. AIM 6 3.3. TEST 6 Test wave 6 Remarks to wave shapes on special

More information

TMC Transformers TMC

TMC Transformers TMC TMC Product & Technology Presentation Cast Resin Transformer (CRT) History Cast resin transformers first appeared in Germany during the 1960s. This new style of dry type transformer was developed with

More information

Earthing Requirements for HV Transmission Structures

Earthing Requirements for HV Transmission Structures Engineering Standard Electrical MEST 000002-07 Earthing Requirements for Transmission Structures Version: 1 Issued: February 2015 Owner: Engineering Approved By: Patrick Kelly Head of Electrical Engineering

More information

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO PART - A : SPECIFIC REQUIREMENTS THIS DATA SHEET IS APPLICABLE FOR IN BOILER A CLIMATIC CONDITIONS PACKAGE 1 DESIGN AMBIENT TEMPERATURE 45 C 2 ALTITUDE ( ABOVE MSL ) 6.71 MTRS. 3 RELATIVE HUMIDITY 74 %

More information

(

( (www.xatianhong.com) Introduction to XATH Xi'an Tianhong Electric Co., Ltd. (XATH) is a solely state-owned enterprise, set up by China Shipbuilding Industry Corporation (CSIC). It is one of the largest

More information

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL

APDRP SCHEME, WESCO. Technical Specification for Distribution Transformers ( 11/0.4KV ) PART 1: GENERAL PART 1: GENERAL 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, offloading and performance requirements of 11/0.433kV distribution transformers for outdoor

More information

PANELMDP Main Distribution Panel. Descriptions Energy Efficient Transformer

PANELMDP Main Distribution Panel. Descriptions Energy Efficient Transformer PANELMDP Main Distribution Panel Eaton Corp Catalog Number Manufacturer Description Weight per unit Product Category Descriptions Product Type PANELMDP Eaton Corp 1.0 (lbs/each) Three Phase Energy Efficient

More information

Series P. Applications

Series P. Applications Ratings 25 800 VA Voltage Primary 230 / 400 / 460 V range Secondary 6 / 12 V 12 / 24 V 24 / 48 V 115 / 230 V Voltage selection by means of metal connection bridges, offering the full rated power at any

More information

CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv

CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv CUSTOMER SUPPLIED HIGH VOLTAGE METERING UNIT SPECIFICATION FOR 11, 22 & 33 kv June 2016 Issue 1 1. INTRODUCTION Introduction of contestability and the ability of all major customers to become contestable

More information

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers save energy, it is precious Mfg. of all types of Distribution / Power & Furnace Transformers SYNERGY transformers SAFETY AND EFFICIENCY, COMBINED WITH LONG-TERM RELIABILITY, ARE THE HALLMARKS OF WORLD-RENOWNED

More information

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A Group F : No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS Table : A No. Description 1. Make & Manufacturer 2. Place of Manufacturer 3. Voltage Ratio 4. Rating

More information

SHARDA Make Harmonics Filter

SHARDA Make Harmonics Filter SHARDA Make Harmonics Filter SHARDA offers perfect solution to minimize Harmonics level of industries where non-linear load like, VFD, Electronics load, Convertors, Voltage booster equipment s are present.

More information

Efacec work every day to anticipate solutions for a sustainable world in the new energy era.

Efacec work every day to anticipate solutions for a sustainable world in the new energy era. Transformers Efacec is the largest industrial portuguese company of the electric and electromechanical sector developing high technology products, solutions and systems used every day by millions of people

More information

DESIGN PRACTICE NOTE DESIGN/REVIEW REQUIREMENTS FOR TRACTION BONDING PLAN

DESIGN PRACTICE NOTE DESIGN/REVIEW REQUIREMENTS FOR TRACTION BONDING PLAN Approval Amendment Record Approval Date Version Description 01/04/2014 1 Initial Issue under MTM PRINTOUT MAY NOT BE UP-TO-DATE; REFER TO METRO INTRANET FOR THE LATEST VERSION Page 1 of 7 Table of Contents

More information

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868) THREE-PHASE SUBSURFACE UNDERGROUND COMMERCIAL DISTRIBUTION (UCD) TRANSFORMER NOTE: This "Guide" summarizes the opinions, recommendations, and practices

More information

MEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly

MEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly MEDIUM VOLTAGE PRODUCT PARAMETERS GUIDE How to specify the indoor instrument transformers correctly The range of electric values in the power supply systems is very extensive. This is why it is necessary

More information

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection:

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection: Utility Systems Technologies, Inc. Sag Fighter TM Deep Voltage Sag Protection: D e e p Vo l t a g e S a g P r o t e c t i o n For three phase application: Q u a l i t y P o w e r. B e t t e r B u s i n

More information

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2

TECHNICAL SPECIFICATION FOR. CONTACT WIRE HARD-DRAWN COPPER 161mm2 Engineering Specification Electrical TECHNICAL SPECIFICATION FOR CONTACT WIRE HARD-DRAWN COPPER 161mm2 Version: 2 Issued: May 2018 Owner: Engineering Approved by: Andrew Russack, Head of Engineering Electrical

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION Single-Phase Low Voltage Dry- Type Transformers 5-400 kva Three-Phase Low Voltage Dry- Type Transformers 7.5-1000 kva TECHNICAL INFORMATION TABLE OF CONTENTS Introduction...3 Technical Explanations...4

More information

MEDIUM VOLTAGE PRODUCT. TJP 6.1, TJP 6.2 Indoor voltage transformers

MEDIUM VOLTAGE PRODUCT. TJP 6.1, TJP 6.2 Indoor voltage transformers MEDIUM VOLTAGE PRODUCT TJP 6.1, TJP 6.2 Indoor voltage transformers 2 TJP 6.1, TJP 6.2 INDOOR VOLTAGE TRANSFORMERS Parameters Highest voltage for equipment Power frequency test voltage, 1 min. Lightning

More information

ULTRA-K Series 600K - he

ULTRA-K Series 600K - he 5 kva 500 kva ULTRA-K Series 600K - he High Efficiency K-Rated Power Conditioning Transformers Designed to be used with linear or non-linear loads. Applications: Audio / Video Recording Equipment IT Systems

More information

Arc Suppression Coils

Arc Suppression Coils Arc Suppression Coils (22kV Arc Suppression Coils ) Introduction Resonance grounding by Petersen coils (Arc Suppression Coils) has been used in Scandinavia and other European countries for some eighty

More information

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER This manual contains proprietary information, which is protected by copyright. All rights are reserved. No part of this manual

More information

Jewell DPM Power / Power Factor Size 96/96 BEST IN CLASS

Jewell DPM Power / Power Factor Size 96/96 BEST IN CLASS Application: The Jewell DPM Power 96x96 series measures system active Power (Import/Export), Reactive Power (Import/Export), Apparent Power & Power Factor of Three Phase and Single Phase Network. It has

More information

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS

CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS CONDITIONS FOR A TENTATIVE APROVAL FOR CONNECTION OF TRANSFORMERS Management has tentatively approved your request subject to the following conditions: 1. All distribution materials/equipment must be purchased

More information

Neutral Earthing. For permanent or temporary neutral earthing in HV systems

Neutral Earthing. For permanent or temporary neutral earthing in HV systems Neutral Earthing Resistors RESISTORS For permanent or temporary neutral earthing in HV systems For continuous or temporary low-resistance neutral grounding in medium voltage systems Neutral point connection

More information

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice Issued: April 1999 Status: Updated Version: B/08.11.200 Data subject to change without notice Features Versatile, multifunction line fault indicator for distribution networks Overcurrent, earth-fault and

More information

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C 1 Tender Notice No. NESCO Utility / O&M Materials/58 / 8267, dtd.17.7.15 Group-C Sl no. Material Description Unit Quantity 1 33KV C.T. Oil

More information

QUESTIONNAIRE for Wind Farm Power Stations only

QUESTIONNAIRE for Wind Farm Power Stations only TRANSMISSION SYSTEM OPERATOR QUESTIONNAIRE for Wind Farm Power Stations only To be submitted by the Generation Licensees together with the Application for Connection Certificate according to IEC 61400-21

More information

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase

More information

Ritz Instrument Transformers GmbH. Welcome

Ritz Instrument Transformers GmbH. Welcome Ritz Instrument Transformers GmbH Welcome About Ritz together with over 200 years of experience in instrument transformer production since 1945 since 1945 since 1945 since 1904 RITZ Group - Organization

More information

Basics of electrical transformer

Basics of electrical transformer Visit: https://engineeringbasic.com Complete basics and theory of Electrical Transformer Electrical Transformer is the most used electrical machine in power system. Both in the power transmission and distribution

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 60044-2 Edition 1.2 2003-02 Edition 1:1997 consolidated with amendments 1:2000 and 2:2002 Instrument transformers Part 2: Inductive voltage transformers IEC 2003 Copyright -

More information

ahead of time Static Digital Voltage Stabilisers

ahead of time Static Digital Voltage Stabilisers ahead of time Static Digital Voltage Stabilisers Founded in 1969, ORTEA SpA is a leading company in manufacturing and engineering voltage stabilisers and magnetic components. Over forty years in the business

More information

DISTRIBUTION TRANSFORMER 11 / kv

DISTRIBUTION TRANSFORMER 11 / kv Ministry of Electricity (MOE) Power Distribution Office Baghdad IRAQ SPECIFICATION No. D-26 DISTRIBUTION TRANSFORMER 11 / 0.416 kv 2BREVISION 3BYEAR 2013 1 Table of Contents: Clause : no. 1. Scope of The

More information

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS

PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS PRESENTATION ON IS 1180 (Part 1): 2014 DISTRIBUTION TRANSFORMERS SHYAM KUMAR SCIENTIST B ELECTROTECHNICAL BUREAU OF INDIAN STANDARDS n Bureau of Indian Standards (BIS) is the NATIONAL STANDARD BODY. Established

More information

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope

Technical Questionnaire 9.101/6 Transformer Test System. Personal Data. Application. Test of. Delivery scope Date: Page: 1 / 10 Personal Data Name: Company / institution: Phone: E-mail: Fax: Application Quotation number: (will be filled in by HIGHVOLT) Test field, stationary research institute mobile on-site

More information