Analysis of Major Changes to Arrester Standards IEC STEVE BREWER
|
|
- Milo Anthony
- 5 years ago
- Views:
Transcription
1 Analysis of Major Changes to Arrester Standards IEC STEVE BREWER
2 Analysis of Major Changes to Arrester Standard IEC Steve Brewer- Senior Product Manager - HPS Arrester Business Unit
3 Agenda Fundamental Differences between IEC Edition 2.2 and Edition 3.0 Arrester Classification Arrester Type Tests Repetitive Charge Transfer Operating Duty Power-frequency voltage versus time Arrester disconnector / fault indicator Weather ageing test polymer
4 Edition 3.0 Edition 2.2 IEC Arrester Classifications Standard nominal discharge current A A A A Rated Voltage U r (kv rms) 360 < U r < < U r < 360 U r 132 U r 36 Arrester Class Station Distribution Designation SH SM SL DH DM DL Nominal discharge current 20 ka 10 ka 10 ka 10 ka 5 ka 2.5 ka Switching impulse discharge current 2 ka 1 ka 0.5 ka Qrs (Coulombs) Wth (kj/kv of Rated Voltage) Qth (Coulombs) MAIN CHANGES Classifications now more associated with application Now 6 classes instead of 4, more finely divided according to expected duty Addition of the definitions for distribution and substation
5 Edition 3.0 IEC Arrester Classifications Arrester Class Station Distribution Designation SH SM SL DH DM DL Nominal discharge current 20 ka 10 ka 10 ka 10 ka 5 ka 2.5 ka Switching impulse discharge current 2 ka 1 ka 0.5 ka Qrs (Coulombs) Wth (kj/kv of Rated Voltage) Qth (Coulombs) Distribution Class Arrester intended for use on distribution systems to protect components primarily from the effects of lightning. Station Class Arrester intended for use in stations to protect the equipment from transient over-voltages.
6 Edition 3.0 IEC Arrester Classifications Arrester Class Station Distribution Designation SH SM SL DH DM DL Nominal discharge current 20 ka 10 ka 10 ka 10 ka 5 ka 2.5 ka Switching impulse discharge current 2 ka 1 ka 0.5 ka Qrs (Coulombs) Wth (kj/kv of Rated Voltage) Qth (Coulombs) Sub-classifications within each class there are designations relating to the duty that the arrester will experience as noted below. SH = Station High duty SM = Station Medium duty SL = Station Low duty DH = Distribution High duty DM = Distribution Medium duty DL = Distribution Low duty
7 Edition Insulation withstand tests on the arrester housing a) Lightning impulse b) Switching impulse c) Power-frequency 2 Residual voltage test a) Steep current b) Lightning impulse c) Switching impulse 3 Long-duration current impulse withstand test 4 Operating duty test a) High-current impulse operating duty b) Switching surge operating duty test 5 Short circuit 6 Arrester disconnector / fault indicator (when fitted) 7 Polluted housing test 8 Internal partial discharge test 9 Bending moment 10 Environmental tests 11 Seal leak rate 12 Radio interference voltage (RIV) 13 Weather ageing test - polymer Note: Section 6.10 required Power-frequency voltage versus time characteristics to be measured with prior duty only. IEC Arrester Type Tests Edition Insulation withstand tests on the arrester housing a) Lightning impulse b) Switching impulse c) Power-frequency 2 Residual voltage test a) Steep current b) Lightning impulse c) Switching impulse 3 Test to verify long term stability under continuous operating voltage 4 Repetitive charge transfer withstand 5 Heat dissipation behaviour verification of test sample 6 Operating duty test 7 Power-frequency voltage versus time 8 Arrester disconnector / fault indicator (when fitted) 9 Short-circuit tests 10 Bending moment 11 Environmental tests 12 Seal leak rate 13 Radio interference voltage (RIV) 14 Test to verify the dielectric withstand of the internal components of an arrester 15 Test of internal grading components 16 Polluted housing test 17 Weather ageing test polymer
8 Edition Insulation withstand tests on the arrester housing a) Lightning impulse b) Switching impulse c) Power-frequency 2 Residual voltage test a) Steep current b) Lightning impulse c) Switching impulse 3 Long-duration current impulse withstand test 4 Operating duty test a) High-current impulse operating duty b) Switching surge operating duty test 5 Short circuit 6 Arrester disconnector / fault indicator (when fitted) 7 Polluted housing test 8 Internal partial discharge test 9 Bending moment 10 Environmental tests 11 Seal leak rate 12 Radio interference voltage (RIV) 13 Weather ageing test - polymer Note: Section 6.10 required Power-frequency voltage versus time characteristics to be measured with prior duty only. IEC Arrester Type Tests Removed Edition Insulation withstand tests on the arrester housing a) Lightning impulse b) Switching impulse c) Power-frequency 2 Residual voltage test a) Steep current b) Lightning impulse c) Switching impulse 3 Test to verify long term stability under continuous operating voltage 4 Repetitive charge transfer withstand 5 Heat dissipation behaviour verification of test sample 6 Operating duty test 7 Power-frequency voltage versus time 8 Arrester disconnector / fault indicator (when fitted) 9 Short-circuit tests 10 Bending moment 11 Environmental tests 12 Seal leak rate 13 Radio interference voltage (RIV) 14 Test to verify the dielectric withstand of the internal components of an arrester 15 Test of internal grading components 16 Polluted housing test 17 Weather ageing test polymer Formerly part of Operating Duty Test Legend Significant Addition Significant Change Unchanged or Minor Minor Addition
9 Edition 3.0 (8.4) Test to verify long term MOV stability with U c applied CHANGES In Edition 2.2 there was no pass / fail criteria. P end could be any value as related to P start. A penalty factor was imposed on later testing based on the ratio - P end /P start 1000 Hr Power Loss EDITION EVALUATION Test considered passed if all three samples behave as follows: After P min established any increase is not greater than 1.3 x P min P end 1.3 x P start
10 Power Loss (Watts) MOV Aging Test Example Time (Hours)
11 Edition 2.2 (8.4) Long-duration current impulse withstand test X μsec 3 arresters samples required 6 groups of 3 impulses to each sample seconds between impulses Cool samples to ambient between groups EVALUATION No physical damage is evident (puncture, flashover, cracking) Measure residual EVALUATION voltage before and after test sequence - Discharge voltage shall not change more than 5% from initial measurements Impulse Close-up View Duration (X) LDC μsec LDC μsec LDC μsec LDC μsec LDC μsec
12 Edition 3.0 (8.5) Repetitive charge transfer rating test - Q rs 10 Samples minimum required 10 groups of 2 impulses to each sample seconds between impulses Cool samples to ambient between groups Charge levels shall equal the claimed value multiplied by 1.1 Waveshape selection Station class rect. (2-4ms) Distribution class 8/20 Claimable charge ratings Q rs 0.1 C to 1.2 C in steps of 0.1 C 1.2 C to 4.4 C in steps of 0.4 C 4.4 C to 10 C in steps of 0.8 C 10 C to 20 C in steps of 2 C 20 C up in steps of 4 C EVALUATION No physical damage is evident (puncture, flashover, cracking) Measure Residual Voltage before and after testing - shall not change more than 5% Measure Reference Voltage before and after testing - shall not change more than 5%
13 Edition 2.2 (8.5) Operating Duty Tests MOV Pre-conditioning Three samples 4 groups of 5 impulses at nominal discharge current seconds between impulses Interval between groups: min During the impulses the MOVs are energized at 1.2 X U c
14 Preheat to 60 C Edition 2.2 (8.5.4) High Current Impulse Operating Duty Test For Class 1 arresters and below (5kA, 2.5kA) Amplitude per table below 10 sec 30 minutes U r U c Arrester Classification 10kA 5kA 2.5kA Peak 4/10 current 100kA 65kA 25kA Apply 1 st 4/10 impulse, Preheat to 60 C, Apply 2 nd 4/10 impulse Less than 100msec after 2 nd impulse apply U r for 10 seconds Within 1 second after the overvoltage apply U c for 30 minutes Measure temperature, resistive component of current or watts loss for 30 minutes to demonstrate thermal stability
15 Preheat to 60 C Edition 2.2 (8.5.5) Switching Surge Operating Duty Test For Class 2 arresters and above 100kA 4/10 impulses Duration and Amplitude matches Long Duration Impulse Test 10 sec 30 minutes U r U c Apply 2 x 4/10 impulses, Preheat to 60 C, Apply 2 x LD impulses sec apart Less than 100msec after 2 nd impulse apply U r for 10 seconds Within 1 second after the overvoltage apply U c for 30 minutes Measure temperature, resistive component of current or watts loss for 30 minutes to demonstrate thermal stability
16 Cool to Ambient Edition 3.0 (8.7) Operating Duty Tests MOV Pre-conditioning For Distribution Class Arresters 4/10 Current Impulse amplitude requirements For Station Class Arresters Arrester Nominal Discharge Current (I n ) 20kA and 10kA 5kA 2.5kA Peak 4/10 current 100kA 65kA 25kA
17 Edition 3.0 (8.7) Operating Duty Tests Q th Injection - Distribution Preheat to 60 C 10 sec 30 minutes U r U c 1 min Distribution Class Arresters Two x 8/20 current impulses within one minute Arrester Classification Qth Rating (Coulombs) Qth per Impulse (Coulombs) Corresponding 8/20 current amplitude DH 10kA kA DM 5kA kA DL 2.5kA kA
18 Preheat to 60 C Edition 3.0 (8.7) Operating Duty Tests W th Injection - Station Showing 2 but could be any number 10 sec 30 minutes U r U c 3 MIN Station Class Arresters One or more long duration impulses (2-4 msec duration) within 3 minutes provided the accumulated energy is at least equal to a claimable thermal energy rating W th. W th Units: kj / kv of U r Claimable W th Values: 1 to 5 steps of to 16 steps of 1 16 to 30 steps of 2 30 and up steps of 6
19 Preheat to 60 C Edition 3.0 (8.8) Power-frequency (TOV) Voltage Versus Time Test Station rectangular waves shown. If DH these would be 8/20 Duration per Chart U c for 30 minutes This voltage is what is plotted Prior Duty Test requires injection of Q th or W th energy exactly like operating duty test. Four tests, One in each range = 4 data points. Without Prior Duty Test has no impulses prior to start of TOV time period. Two tests, One from two ranges = 2 data points TOV Required Time Ranges (Seconds) Range to 1.0 Range to 10 Range to 100 Range to 3,600
20 Edition 2.2 (8.6) Arrester Disconnector Tests Withstand without operating: Long-duration current impulse test Operating duty test Time versus current curve test 20A, 200A, 800A Edition 3.0 (8.9) Arrester Disconnector Tests Withstand without operating: Repetitive Charge transfer test - Q rs Operating duty test W th or Q th Time versus current curve test 20A, 200A, 800A Bending moment, tensile load and torsional load tests Temperature cycling and seal pumping tests Added
21 Edition 2.2 ( ) Weather Ageing test for Polymer Housed Arresters 1000 hour salt fog at U c NaCl concentration between 1 and 10 kg/m 3 If requested by the user and agreed to by the manufacturer 5000 hour multi-stress test UV, rain, dry heat, damp heat, high humidity, salt fog Removed } Edition 3.0 ( ) Weather Ageing test for Polymer Housed Arresters 1000 hour salt fog at U c NaCl concentration between 1 and 10 kg/m hour UV light test of the housing materials Added
22 Basic differences between Edition 2.2 and Edition 3.0 Line Discharge Classes eliminated Q rs is a test of the MOV durability only claimable charge rating comes from this test Operating Duty test determines arrester s 2 shot capability WITH subsequent thermal recovery. Station = W th = actual measurement in kj/kv of Ur Distribution = Q th = compliance to DL,DM or DH charge transfer levels (.45C, 0.7C, 1.1C) TOV test is more standardized and required both prior duty and without prior duty Disconnector testing expanded to include mechanical and seal testing. For polymer arresters the Weather Ageing test has been modified 5000 hour multi-stress test option removed, UV test requirement added.
UltraSIL Polymer-Housed VariSTAR Normal-Duty, Heavy-Duty and Riser Pole Distribution-Class Arresters
File Ref: Cat. Sec. 235-35 UltraSIL Polymer-Housed VariSTAR Normal-Duty, Heavy-Duty and Riser Pole Distribution-Class Arresters Bulletin 95062 September 2012 Supersedes 04/09 2012 Cooper Industries. All
More informationUltraSIL Polymer-Housed Evolution Distribution Class Surge Arrester Certified Test Report
CP No.: CP0804 Page: 1 of 20 UltraSIL Polymer-Housed Evolution Distribution Class Surge Arrester Certified Test Report October 2014 Supersedes 09/11 2014 Eaton CP No.: CP0804 Page: 2 of 20 UltraSIL Polymer-Housed
More informationEffective February 2017 Supersedes January 2012 (CP1122)
File Ref: Cat. Sec. CA235013EN CT235003EN Supersedes January 2012 (CP1122) COOPER POWER SERIES UltraSIL Polymer-Housed VariSTAR Type US, UH, and UX Station Class Surge Arresters Certified Test Report Certification
More informationSelection of MO surge arresters Overvoltage protection
A P P L I C AT I O N N OT E 1. 1 Selection of MO surge arresters Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage protection
More informationIEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4
IEC Type Test Report Report No. EU1517-H-00.1 H4 Series Porcelain-housed Arrester 20,000 A Line Discharge Class 4 This report records the results of type tests made on H4 series 20 ka Line Discharge Class
More informationANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester
ANSI DESIGN TEST REPORT Report No. EU1295-H-00 Type PVN Station Class Surge Arrester This report records the results of the design tests made on Type PVN Station Class surge arresters in accordance with
More informationTransformers connected via a cable Overvoltage protection
A P P L I C AT I O N N OT E 2. 1 Transformers connected via a cable Overvoltage protection The APPLICATION NOTES (AN) are intended to be used in conjunction with the APPLICATION GUIDELINES Overvoltage
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60099-4 Edition 2.1 2006-07 Edition 2:2004 consolidated with amendment 1:2006 Surge arresters Part 4: Metal-oxide surge arresters without gaps for a.c. systems IEC 2006 Copyright
More informationCLU Arrester. Certified Test Report. IEEE Standard C
CP No.: CP0605 Page 1 of 8 CLU Arrester Certified Test Report IEEE Standard C62.11-1999 CERTIFICATION Statements made and data shown are, to the best of our knowledge and belief, correct and within the
More informationSPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS
-1- INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION June 2013 SPECIFICATION No 150 kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS I. SCOPE This specification
More informationEaton s Cooper Power Series DEADFRONT ARRESTERS
File Ref: 235-65, 235-68, 235-97, 235-101 Effective June 2015 CT235001EN Supersedes CP9314 May 2011 CERTIFIED TEST REPORT Eaton s Cooper Power Series DEADFRONT ARRESTERS CT235001EN Supersedes CP9314 May
More informationEnergy Division. Bowthorpe LV/MV Surge Arresters
Energy Division Bowthorpe LV/MV Surge Arresters Bowthorpe EMP LV/MV surge arresters OCP, Open Cage Polymeric series Bowthorpe pioneered the development of polymeric housed surge arresters in the early
More informationA Review Comprehension: Guideline for Testing of HV, EHV and UHV Substation Equipment
International Research Journal of Engineering and Technology (IRJET) eissn: 23 0056 Volume: 04 Issue: 02 Feb 2017 www.irjet.net pissn: 072 A Review Comprehension: Guideline for Testing of HV, EHV and UHV
More informationVariSTAR Type AZL heavy-duty distribution-class MOV arrester
Surge s Catalog Data CA235006EN Supersedes TD235007EN September 2014 COOPER POWER SERIES VariSTAR Type AZL heavy-duty distribution-class MOV arrester General Eaton incorporates the latest in metal oxide
More informationCOOPER POWER. UltraSIL Polymer-Housed VariSTAR Type U2Surge Arrester for Systems through 275 kv IEC 10-kA; Line Discharge Class 2 SERIES
Surge Arresters CA235033EN Supersedes February 2012 (I235-92) COOPER POWER SERIES UltraSIL Polymer-Housed VariSTAR Type U2Surge Arrester for Systems through 275 kv IEC 10-kA; Line Discharge General Eaton
More informationDevice Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.
/9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala
More informationAPPLICATION GUIDELINES. Overvoltage protection Metal-oxide surge arresters in medium-voltage systems
APPLICATION GUIDELINES Overvoltage protection Metal-oxide surge arresters in medium-voltage systems First published November 1994 2nd revised edition: September 1995 3rd revised edition: May 1999 4th revised
More informationOVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems
PPLICATION GUIDELINES OVERVOLTAGE PROTECTION Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems Foreword Up until 1998 no international standards
More informationCHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS
CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS 1. Introduction 2. Classification of High Voltage Tests 3. Test Voltages 4. High Voltage Testing of Electrical Apparatus 1. INTRODUCTION Purpose
More informationSurge Arresters. VariSTAR Type AZS Normal Duty Distribution Class MOV Arrester
Surge rresters VariSTR Type ZS Normal Duty Distribution Class MOV rrester Electrical pparatus 235-73 GENERL The Cooper Power Systems VariSTR Type ZS normal duty distribution class MOV arrester (Figure
More informationMODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT
MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral
More informationEE 1402 HIGH VOLTAGE ENGINEERING
EE 1402 HIGH VOLTAGE ENGINEERING Unit 5 TESTS OF INSULATORS Type Test To Check The Design Features Routine Test To Check The Quality Of The Individual Test Piece. High Voltage Tests Include (i) Power frequency
More informationElectric Stresses on Surge Arrester Insulation under Standard and
Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems
More informationFixed Series Compensation
Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and
More informationLIGHTNING ARRESTOR. September 2017 WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED
LIGHTNING ARRESTOR September 2017 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, SectorII, Bidhannagar, Kolkata 700091. CIN: U40101WB2007SGC113474;
More informationشركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.
Our Ref.: 14/2018- Date : Messrs: Dear sir, Tender 14/2018 11& 33 KV Lightning Arrestors. You are kindly requested to quote for the supply and delivery to our stores in Shufat Jerusalem, (DDP) of the following
More informationVariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester
Surge Arresters Catalog Data CA235016EN Supersedes TD235001EN September 2014 COOPER POWER SERIES VariSTAR Type AZU heavy-duty distribution-class under-oil MOV surge arrester General Eaton's Cooper Power
More informationInsulation Co-ordination For HVDC Station
Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating
More informationAMENDMENT NO. 1 SEPTEMBER IS (Part 1) : 2001/IEC (1991) SURGE ARRESTORS
AMENDMENT NO. 1 SEPTEMBER 2011 TO IS 15086 (Part 1) : 2001/IEC 60099-1 (1991) SURGE ARRESTORS PART 1 NON-LINEAR RESISTOR TYPE GAPPED SURGE ARRESTORS FOR a.c. SYSTEMS (The Amendment was originally published
More informationType DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv
Type DMX-N Surge Arresters Maximum System Voltage 2 to 36 kv DMX-N gapless metal oxide surge arresters DMX-N surge arresters are used for the protection of switchgear, transformers and other equipment
More informationTab 8 Surge Arresters
s en em Tab 8 Surge Arresters Si Distribution System Engineering Course Unit 10 2017 Industry Inc., All Rights Reserved Surge Arresters The main protective devices against system transient overvoltages.
More informationTab 2 Voltage Stresses Switching Transients
Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles
More informationSMD - Resistors. Pulse Withstanding Thick Film Chip Resistor-SMDP Series. Product: Size: 0603/0805/1206/1210/2010/2512. official distributor of
Product: Pulse Withstanding Thick Film Chip Resistor-SMDP Series Size: 0603///12// official distributor of 1. Scope Pulse Withstanding Thick Film Chip Resistor-SMDP Series -This specification applies to
More informationConstruction zglass passivated collar zaluminum termination for pressure contact
EPCOS Product Brief 2018 Energy Varistors For the Protection of Power Distribution Systems SIOV metal oxide varistors in the E series are designed to be used as active elements in gapless surge arresters
More information(2) New Standard IEEE P (3) Core : (4) Windings :
(d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.
More informationTest Specification for Type Approval
A2 (1991) (Rev.1 1993) (Rev.2 1997) (Rev. 2.1 July 1999) (Rev.3 May 2001) (Corr.1 July 2003) (Rev.4 May 2004) (Rev.5 Dec 2006) (Rev.6 Oct 2014) Test Specification for Type Approval.1 General This Test
More informationA Study on Lightning Overvoltage Characteristics of Grounding Systems in Underground Distribution Power Cables
J Electr Eng Technol Vol. 9, No. 2: 628-634, 2014 http://dx.doi.org/10.5370/jeet.2014.9.2.628 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 A Study on Lightning Overvoltage Characteristics of Grounding
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationMetal Film Precision Resistor. Features
Features -Excellent overall stability -Tight tolerance down to ±0.1% -Extremely low TCR down to ±10 PPM/ C -High power rating up to 1 Watts Applications -Telecommunication -Medical Equipment Construction
More informationMetal Film Precision Resistor. Features
Features -Excellent overall stability -Tight tolerance down to ±0.1% -Extremely low TCR down to ±10 PPM/ C -High power rating up to 1 Watts Applications -Telecommunication -Medical Equipment Construction
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60071-2 Third edition 1996-12 Insulation co-ordination Part 2: Application guide This English-language version is derived from the original bilingual publication by leaving out
More informationPOWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009
POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power
More informationOur experience. Our products
Our experience With 20 years know-how in the field of Medium Voltage network protection, DERVASIL designs and manufactures lightning arresters with zinc oxide varistors and synthetic housings. Our products
More informationTECHNICAL SPECIFICATION
TECHNICAL SPECIFICATION 1. SCOPE : TECHNICAL SPECIFICATION FOR LIGHTNING ARRESTORS 1.1. This Specification covers design, manufacture, testing at manufacturer's Works, packing, supply, delivery of 42 KV
More informationChip Varistor LVS B DESCRIPTION APPLICATIONS FEATURES ORDERING INFORMATION. Capacitance 030 = 3pF 300 = 30pF 301 = 300pF
DESCRIPTION The LVS series is metal oxide based chip varistor for transient voltage suppression. They have non-linear voltage-current behavior, similar to zener diode. Multilayer structured varistor, however,
More informationMetal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester
Surge Arresters Catalog Data CA235025EN Supersedes November 2015 COOPER POWER SERIES Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester General Eaton combines metal (zinc) oxide varistor technology in
More informationTRANSMISSION ENGINEERING STANDARD TES-P , Rev. 0 TABLE OF CONTENTS 1.0 SCOPE 2.0 BONDING METHODS
1.0 SCOPE 2.0 BONDING METHODS 2.1 Introduction 2.2 Design 2.3 Single-Point Bonding 2.4 Cross Bonding 2.5 Sheath Sectionalizing Joints 2.6 Sheath Standing Voltage 2.7 Sheath Voltage at Through Fault 2.8
More informationPRODUCT SPECIFICATION
0.8x1.2 mm Board to Board Socket Connectors Page 1 1.0 SCOPE This specifies 0.8x1.2mm pitch Socket Connectors. The connector shall meet the performances, specified here under the condition with the plug
More informationSOLARLOK PV BAR Junction Box
SOLARLOK PV BAR Junction Box Table of contents 1. SCOPE... 2 1.1. Content... 2 1.2. Qualification... 3 2. APPLICABLE DOCUMENTS... 3 2.1. TE Connectivity Documents... 3 2.2. Commercial Standard... 3 3.
More information36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)
CEB STANDARD 022 : 1994 Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEYLON ELECTRICITY BOARD SRI LANKA Specification for 36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE) CEB Standard 022 : 1994
More information35 kv Class M.O.V.E. DirectConnect elbow arrester
Surge Arresters Catalog Data CA235026EN Supersedes November 2015 COOPER POWER SERIES 35 kv Class M.O.V.E. DirectConnect elbow arrester General Eaton's Cooper Power series M.O.V.E. DirectConnect elbow arrester
More informationSMD MELF - Resistors. Metal Film Precision Resistor - SMDM Series Size: 0204/ official distributor of
Product : Metal Film Precision Resistor - SMDM Series Size: 0204/ 0207 official distributor of Metal Film Precision Resistor (SMDM Series) 1. Features -Excellent overall stability -Tight tolerance down
More informationArrester 2050 JONATHAN WOODWORTH
JONATHAN WOODWORTH Arrester 2050 Jonathan Woodworth - Arresterworks Introduction This paper is about the future of surge protection and what the arresters of 2050 may be like. In order to understand where
More informationMetal-Oxide Varistors (MOVs) Thermally Protected Varistors > SMOV 25S Varistor Series
S25S Varistor Series RoHS Description The Littelfuse S 25S thermally protected varistor is a self-protected device. It consists of a 25mm square varistor with an integral thermal designed to open in the
More informationElectronic Combined Current and Voltage Transformer Altea CVS-24-O Technical Specifications
/7 Electronic Combined Current and Voltage Transformer Altea CVS-24- Technical Specifications Rev. Date Revision Description Prepared by Checked by Approved by 0 26/06/4 First Issue E. Scala L. Peretto
More informationSPECIFICATIONS. Metal Film Precision Resistor. CSR-Serie SWISSDIS. Swissdis AG Grasweg 7 CH-4911 Schwarzhäusern
SWISSDIS Swissdis AG Grasweg 7 CH-4911 Schwarzhäusern Tel.: +41 62 919 44 00 Fax: +41 62 919 44 01 info@swissdis.ch www.swissdis.ch SPECIFICATIONS CSR-Serie Version June 2017 Features -Excellent overall
More informationAnalysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP
IJSTE - International Journal of Science Technology & Engineering Volume 3 Issue 2 August 216 ISSN (online): 2349-784X Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP
More informationPRODUCT SPECIFICATION
2.54mm Board to Board Socket Connectors Page 1 1.0 SCOPE This specifies 2.54mm pitch Socket Connectors. The connector shall meet the performances, specified here under the condition with the plug connector
More informationLow voltage products in high altitudes
WHITE PAPER Low voltage products in high altitudes Information and technical guidance for applications above 2000 m sea level This white paper provides information including technical guidance for high
More informationSmart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INSTRUMENTRANSFORMER
Customer : REV. 0 Page 1/16 Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INRUMENTRANSFORMER CVS - 24 - G - Revision Prepared Description Checked by Rev. Date by 0 13/06/16 First issue E.
More informationSPTS 1 - Ratings and General Requirements for Plant, Equipment and Apparatus for The ScottishPower System and Connection Points to it.
1. SCOPE The requirements of this document apply to all Plant, Equipment and Apparatus that are part of, or are Directly connected to, the Company network. Requirements contained herein may be modified
More informationPRODUCT SPECIFICATION
2.54mm Board to Board Header Connectors Page 1 1.0 SCOPE This specifies Pitch 2.54mm Headers Connectors. The connector shall meet the performances, specified here under the condition with the plug connector
More informationTECHNICAL NOTE 2.0. Overvoltages origin and magnitudes Overvoltage protection
ECHNICAL NOE 2.0 Overvoltages origin and magnitudes Overvoltage protection he ECHNICAL NOES (N) are intended to be used in conjunction with the APPLICAION GIDELINES Overvoltage protection Metaloxide surge
More informationDescription. Features. Continuous BA Series BB Series Units Steady State Applied Voltage: AC Voltage Range (V M(AC)RMS
BA/BB Varistor Series RoHS Description The BA and transient surge suppressors are heavy-duty industrial Metal-Oxide Varistors (MOVs) designed to provide surge protection for motor controls and power supplies
More informationEvaluating the Response of Surge Arresters
1 Jens Schoene Chandra Pallem Tom McDermott Reigh Walling Evaluating the Response of Surge Arresters to Temporary Overvoltages Panel Session of the IEEE Wind and Solar Collector Design Working Group 2014
More informationInsulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet
ArresterWorks Insulation Coordination Fundamentals Where Arrester and Insulator Characteristics Meet 6/23/2012 Jonathan Woodworth Transient overvoltages are a fact of life on power systems. Arresters can
More informationMetal-Oxide Varistors (MOVs) Radial Lead Varistors > TMOV 25S Varistor Series
TMOV 25S Varistor Series RoHS Description Metal Oxide Varistors (MOVs) are rated for specific AC line operating voltages, and exceeding these limits through the application of a sustained abnormal over-voltage
More informationประกาศกระทรวงอ ตสาหกรรม
หน า ๔๙ เล ม ๑๒๖ ตอนพ เศษ ๑๗ ง ราชก จจาน เบกษา ๒ ก มภาพ นธ ๒๕๕๒ ประกาศกระทรวงอ ตสาหกรรม ฉบ บท ๓๘๖๔ (พ.ศ. ๒๕๕๑) ออกตามความในพระราชบ ญญ ต มาตรฐานผล ตภ ณฑ อ ตสาหกรรม พ.ศ. ๒๕๑๑ เร อง ก าหนดมาตรฐานผล ตภ ณฑ
More informationHVR. Lead Wire Length (H, mm)
High Resistor Features Special conductive film withstands high voltage d L H D working voltage far over that of generalpurpose resistors Suitable for applications such as TV s, high voltage power supply,
More informationPEAK OUTPUT CURRENT 1. MAP V 4.7V to 5.8V 8A 11A 0.2% ±1% 1% 4.9V to 5.1V PEAK OUTPUT CURRENT 4 LINE REGULATION
The Bel Power Solutions MAP30/40/42 Series of power supplies combines low cost and universal input in a board-only power solution to meet commercial and industrial requirements. Full international safety,
More informationContinuous C-III Series Units. ) 2ms Rectangular Wave 40 to 530 J Operating Ambient Temperature Range (T A
RoHS Description The C-III Series of Metal-Oxide Varistors (MOVs) are specifically designed for applications requiring high surge energy absorption ratings and superior multiple pulse absorption rating.
More informationSingle-output models feature wide-range output adjustability to meet a wide variety of standard and user-specific output voltage requirements.
Bel Power Solutions MAP55 Series of power supplies provides reliable, tightly-regulated DC power for commercial and industrial systems. Wide-range AC input and full international safety, EMI, and ESD compliance
More informationISOLATING TRANSFORMERS FOR TLC PLANTS
ISOLATING TRANSFORMERS FOR TLC PLANTS Isolating transformers for TLC plants The power supply of telecommunication plants and FM/TV relay stations has always entailed numerous problems and specific needs
More informationSRM VDE. REG.-Nr. E932. Cap Diameter (D1, mm) Body Diameter (D2, mm)
D2 VDE REG.-Nr. E932 Specifications Per IEC 605- Features B L D IEC60065 & UL676 Compliant MELF packaging yet capable of high power handling Special conductive film enhances anti-surge capability. Absorbs
More informationHigh voltage engineering
High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency
More informationPrepared by Mick Maytum
IEC Technical Committee 109: Standards on insulation co-ordination for low-voltage equipment Warning Prepared by Mick Maytum mjmaytum@gmail.com The document content is of a general nature only and is not
More informationCut and formed product is available on select sizes; contact factory for details Flameproof coating per UL94 V-0 RoHS compliant / lead-free
Features: Excellent anti-surge characteristics Stable characteristics through the resistance range Good alternative to carbon composition resistors Applications include power supplies, CRT s, and antisurge
More informationPOSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) Surge Arrester
s Catalog Data CA3508EN Supersedes November 015 COOPER POWER SERIES POSI-BREAK Metal Oxide Varistor Elbow (M.O.V.E.) General Eaton s Cooper Power series POSI-BREAK M.O.V.E. surge arrester combines metal
More informationTECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES
INDEPENDENT POWER TRANSMISSION OPERATOR S.A. TNPRD/ SUBSTATION SPECIFICATION & EQUIPMENT SECTION October 2014 TECHNICAL DESCRIPTION 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES I. SCOPE This
More information3EE2 Special-Purpose Surge Arresters for the Protection of Motors, Generators and Furnace Transformers
3EE2 Special-Purpose Surge Arresters for the Protection of Mors, Generars and Furnace Transformers Rated 5.6 52 for ZnO types Low protection level Very high energy absorption capacity Very high short-circuit
More informationA Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid
A Case Study on Selection and Application of Lightning Arrester and Designing its Suitable Grounding Grid 1 Arpan K. Rathod, 2 Chaitanya H. Madhekar Students Electrical Engineering, VJTI, Mumbai, India
More informationVI 3 - i TABLE OF CONTENTS
VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3
More informationElectrical Specifications. Maximum Maximum Resistance Working Overload Temperature. Mechanical Specifications
Features: Thin Film Technology for precision and stability Excellent power to size ratio Exhibits good pulse power characteristics RoHS compliant / lead-free Type / Code MLF12 0207 MLFM1 Package Size 0207
More informationSurge Withstanding Chip Resistor SWR Series
SR Series Features -High power rating -Excellent surge withstanding & pulse withstanding performance -Improved working voltage ratings -Standard package sizes of 0603~ -EC-Q200 Compliance pplications -Metering
More informationWeidong Zhang, May.9, 2016 Development of Pre-Insertion Resistor for an 800kV GIS Circuit Breaker. ABB Group May 11, 2016 Slide 1
Weidong Zhang, May.9, 2016 Development of Pre-Insertion Resistor for an 800kV GIS Circuit Breaker Group Slide 1 Background & Objects EHV/UHV system: Widely application for long distance transmission from
More informationSurge Arrester Placement for Substation Lightning Protection. Qianxue Xia
Surge Arrester Placement for Substation Lightning Protection Qianxue Xia qxia11@asu.edu 1 Agenda Introduction Modelling Results Conclusions 2 Introduction 3 Introduction Most utilities install surge arresters
More informationDATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection
DATASHEET - ETR4-70-A Delivery program Timing relay, 2W, 0.05s-100h, multi-function, 24-240VAC/DC, potentiometer connection Part no. ETR4-70-A Catalog No. 031888 Eaton Catalog No. XTTR6A100H70B EL-Nummer
More informationREPORT OF PERFORMANCE TIC
REPORT OF PERFORMANCE TIC 1580-13 OBJECT TYPE Three-core power cable 18/30(36) kv, 3x500 mm2, 2XWY(P)-FR XLPE Rated voltage, U 0/U (U m) 18/30 (36) kv Conductor material Cu Conductor cross-section 3x500
More informationPowerPact H-, J-, and L-Frame Circuit Breakers General Information. Vibration. Electromagnetic disturbances. Tropicalization
General Information Vibration PowerPact H-, J-, and L-frame devices resist mechanical vibration. Tests are carried out in compliance with standard UL 489 SA and SB for the levels required by merchant-marine
More informationCHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES
23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation
More informationAll the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.
1. Scope This specification defines the methods, the procedures and the requirements to verify the cables manufactured according to I.E.C. Specifications NPS361. 2. Standards All the standards referred
More informationDC Chopper Based Test Circuit for High Voltage DC Circuit Breakers
DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers D. Jovcic*, M.H. Hedayati *University of Aberdeen,UK, d.jovcic@abdn.ac.uk University of Aberdeen,UK, mhh@abdn.ac.uk Keywords: High Voltage
More informationPower Frequency Withstand Voltage On-site testing of 400 kv GIS
Power Frequency Withstand Voltage On-site testing of 400 kv GIS D. Anaraki Ardakani, A. Omidkhoda, M. Solati High Voltage Engineering Center ACECR Tehran, Iran Da_ardakani@yahoo.com Paper Reference Number:
More informationComputer Based Model for Design Selection of Lightning Arrester for 132/33kV Substation
IOSR Journal of Engineering (IOSRJEN) ISSN (e): 2250-3021, ISSN (p): 2278-8719 Vol. 04, Issue 05 (May. 2014), V2 PP 32-36 www.iosrjen.org Computer Based Model for Design Selection of Lightning Arrester
More informationMetal Film Precision Resistor. Features
Features -Excellent overall stability -Tight tolerance down to ±0.1% -Extremely low TCR down to ±10 PPM/ C -High power rating up to 1 Watts Construction & Dimension 6 5 1 2 3 4 Applications -Telecommunication
More informationDATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC
DATASHEET - ETR4-51-A Timing relay, star-delta, 50 ms, 1W, 3-60s, 24-240VAC/DC Part no. ETR4-51-A Catalog No. 031884 Eaton Catalog No. XTTR6A60S51B EL-Nummer 0004133308 (Norway) Delivery program Product
More informationArresterFacts-002. Field Testing Arresters ArresterWorks.com. ArresterFacts are information modules pertaining to the arrester world.
ArresterFacts are information modules pertaining to the arrester world. This Field Testing of Arresters module will clarify the many questions about assessing the quality of an installed high voltage arrester
More informationSAMSUNG ELECTRO-MECHANICS CO., LTD
Model Name : Features : ㅡ Suitable for LED lighting application ㅡ UL8750, UL1310 Class 2 ㅡ For use in Dry and Damp Location ㅡ Full-protection provided: OCP/OVP/OTP/SCP ㅡ 0-10V Dimming Control ㅡ IP67 ㅡ
More informationModeling insulation in high-voltage substations
38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other
More informationMETHODS AND CIRCUITS FOR POWER ARC TEST IN AC CURRENT OF THE SIMPLE AND DOUBLE INSULATOR SETS WITH COMPOSITE MATERIAL FOR AERIAL ELECTRIC LINES
METHODS ND CIRCUITS FOR POWER RC TEST IN C CURRENT OF THE SIMPLE ND DOUBLE INSULTOR SETS WITH COMPOSITE MTERIL FOR ERIL ELECTRIC LINES George CURCNU, Constantin INCU, Corneliu CHICIU ICMET-Craiova, Calea
More information