Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11

Size: px
Start display at page:

Download "Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11"

Transcription

1

2 Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11 COMMISSIONING DRAWINGS

3 1. INTRODUCTION APPLICATION The MIT121 / MIT131 is micro-controller based numerical TRUE RMS single pole directional over current protection with voltage polarization and the relay will operate depending on the direction of fault current and relay setting. Moreover, supervisory components and self-monitoring features give high confidence of serviceability. M I T 121 M I T 131 Single pole directional over current protection Relay Single pole directional over current protection Relay with DC transient free High set. 1.1 MULTIPLE CHARACTERISTICS MIT121 / MIT131 relay is suitable for various inverse characteristics and also for definite time lag characteristic, any one of them can be selectable at site. Standard Inverse characteristic - SI 3 theoretical operating time is 3 seconds at 10 times current setting at time multiplier setting (TMS) Standard Inverse characteristics - SI 1 theoretical operating time is 1.3 seconds at 10 times current setting at time multiplier setting (TMS) Very Inverse characteristic - VI curve is suited to networks where there is a significant reduction in fault current as the distance from the source increases. The operating time is shorter for large fault currents and increases at a greater rate as the fault current decreases. This permits the use of the same time multiplier setting for several relays in series. Extremely Inverse characteristic - EI is very much useful to grade the relay with the fuse and applications where short duration transients over currents occur. e.g. motor starting or reacceleration. Long time Inverse characteristic - LTI is generally used for Standby Fault protection for Neutral / Ground Earthing Resistor. The same characteristics can be used to guard against overheating / over loading protection, when it matches with thermal characteristics of the motor, generator, transformer or capacitor banks. Definite Time Lag characteristic - DTL is used for grading the system where source impedance determines fault current level and the fault current does not vary to a considerable amount down the length of the line. 1.2 DIRECTIONAL ELEMENT The directional element detects the direction of the fault. If the fault direction is with in the directional element boundary the IDMTL element starts timing. 2

4 1.3 DC TRANSIENT FREE HIGHSET On transmission lines or transformer feeders where the source impedance is small compared with the protection circuit, to reduce the tripping time at high fault level the highset instantaneous over current element is used in addition to the inverse time over current element. The MIT 131 relay is provided with highset over current elements. Depending upon the point on wave switching of the fault and the X/R ratio of the system, the initial current may have DC offset. The highset over current unit being instantaneous one, it should not over reach due to initial DC offset current though it may exceed the highset pick-up value. The MIT 131 relay is provided with the DC transient free highset instantaneous elements, which will not over reach for DC transient condition. 1.4 RESET TIME DELAY The increasing use of plastic cables, both, conventionally buried types and aerial bundled conductor types have given rise to the number of "pecking" or "flashing" intermittent faults on distribution systems. At the fault position, the plastic melts and temporarily reseals the faulty cable for a short time, after which the insulation falls again. The same phenomenon has occurred in joint boxes where an internal flashover temporarily reseals. The behavior of different types of over current relays under flashing fault condition is compared in Fig.1. The repeating process often caused electromechanical disc relays to "ratchet up and eventually trip the faulty circuit provided that the reset time of the relay was longer than the time between successive flashes. Early electronic IDMTL relays with instantaneous reset features were not at all effective in dealing with this condition and only tripped after the flashing fault had developed into a solid permanent fault. To overcome this the MIT relay has a reset time setting which can be user programmed to be either instantaneous or delayed from 1 to 60 seconds. On the other hand, on overhead line networks, particularly where reclosers are incorporated in the protected system, instantaneous resetting is desirable to ensure that, on multiple shot reclosing schemes, correct grading between the source relays and the relays associated with the reclosers is maintained. FAULT CURRENT Flashing Faults Fault becomes permanent ELECTROMECHANICAL SLOW RESET TRIP STATIC INSTANTANEOUS RESET TRIP NUMERICAL (MIT) DELAYED RESET TRIP Figure 1 Flashing Fault Protection 3

5 1.5 LIGHTLY LOADED SYSTEMS The lower range of the current setting is available in the MIT relay setting makes the relay suitable for lightly loaded system. The setting can be changed to higher value when the system load is upgraded. 1.6 PARALLEL OR RING FEEDER PROTECTION The directional element can be set for Forward or Reverse direction with wide range of required MTA suitable for protection of Parallel or Ring Feeder Protection. 1.7 RELAY CHARACTERISTIC a. Phase fault 90 connection 45 lead The recommended connection for phase fault is 90 i.e. R phase relay is polarised with YB voltage. 45 -lead characteristic gives MTA when current leads the voltage by 45. Refer Fig. 4 for connection diagram. Other connection and characteristic angles are also possible by selecting appropriate input and MTA angle. b. Earth fault Characteristic The relay should be polarised with open delta voltage for directional determination and the relay MTA angle can be selected base on type of grounding. Normally 15 lag MTA & 45 lag MTA settings are recommended for resistive grounding and solid grounding respectively. 4

6 1.1 UNPACKING INSTALLATION On receipt, remove the relay from the carton box in which it was received and inspect it for obvious damage. It is recommended that the relay is not removed from the relay case. To prevent the possible ingress of dirt, the sealed polythene bag should not be opened until the relay is to be used. If damage has been sustained, please inform Easun Reyrolle Ltd., for necessary action. 1.2 STORAGE When the relay is not required for immediate use, it should be returned to its original carton and stored in a clean dry place. 1.3 HANDLING The relay's electronic circuits are protected from damage by static discharge when the relay is housed in its case. When relay is withdrawn from the case, static handling procedures should be observed: Before removing the relay from its case the operator must first ensure that he is at the same potential as the relay, by touching the case. The relay must not be handled by any of the relay terminals at the rear of the chassis. Ensure that anyone else handling the relay is at the same potential. As there are no user serviceable parts and adjustable user settings inside the relay, there should be no requirement to remove any modules from the chassis. If any module is removed or tampered with, then the guarantee will be invalidated. 1.4 MOUNTING Mount the relay using 2 nos. mounting straps and 1no earth strap. Ensure that an earth wire is connected to the earth strap from the earth terminal 23. Terminal 23 should be directly connected to the system ground. Only settings or trip details can be accessed via the pushbuttons when the cover is fitted. To change the settings the front cover has to be removed. Sealing arrangement is provided in one of the four knurling screws fitted on the cover. Sealing can be done using a sealing wire. Thus mechanical interlock is provided to avoid unauthorized setting change. 2. EQUIPMENT 2.1 CURRENT TAP SELECTION MIT relays are suitable for 1A or 5A application. However the relays are internally wired for either 1A or 5A as per the customer requirement. Internal wiring are to be changed (Fast on crimp connections) for changing the relay rating from one to other. 5

7 To ensure the current rating of the relay, check the connection of CT wires connected to the bottom TB (Terminal Block) at the rear of the chassis as per the following table: For 1A Phase Terminal No. of TB Ferrule No. of CT wire(black) Phase 9 9A For 5A Phase Terminal No. of TB Ferrule No. of CT wire(black) Phase 9 9B Following are the steps to change the current rating of the relay from 1A to 5A. th 1) Identify 9 terminal from number strip on bottom terminal block at the rear of the chassis. 2) The black colour wire 9A is inserted to 9th terminal of TB. 3) First, carefully lift the PVC boot of the wire by means of a tool (like nose pliers) to expose terminal 9A. 4) Hold the crimp by means of the same tool at the crimp point and lift to remove from the fixed terminal. Remove the 9B wire from the terminal parking rack (fixed on terminal block) and insert the crimp of 9B wire on to the terminal No.9 by means of the tool. Insert "9A" wire back to the terminal parking rack. 5) Ensure proper insertion of 9B wire by pulling the wire by hand and the wire should not come off the terminal. 6) Push the boot of 9B wire, to completely cover the crimp. Same procedure in reverse is to be followed to change from 5A to 1A using appropriate wire numbers 2.2 VOLTAGE INPUT MIT directional relays are suitable for AC 110 V application. V phase Terminal No. 11 & V neutral Terminal No

8 2.3 HUMAN MACHINE INTERFACE (HMI) The user friendly HMI provided on the front panel has following features: 1. Six digit, 7 segment LED display (First two digits are Red colour and other four digits are Green colour). First two digits (Red) displays the main menu when selected for setting mode. Remaining four digits (Green) displays Sub menu or "Trip" indication respectively. 2. Green LED - Protection healthy indication 3. Yellow LED (STARTER) - Starter indication 4. Yellow LED (DIRECTION) - Direction is favorable for tripping indication 5. Red LED (TRIP) - Trip indication, 6. Red LED (in Þ key) - Sub Menu 7. Ý Key - Up scrolling 8. ß Key - Down scrolling 9. Þ Key - Sub menu 10. X Key - Enter / Reset / Cancel / To check Version 3.0 SETTING INSTRUCTIONS 3.1 HOW TO OPERATE HMI Remove the front cover by unscrewing the four knurling screws. Apply DC supply. Terminals 22, 24 and 23 are for positive, negative and earth respectively as per relay rating. When the relay powers up it takes few seconds to complete the self-check routing. Ensure Protection Healthy LED (Green) is ON and busy indication appears on the LED display unit. Wait until the busy indication goes off. Press Ý or ß key nni t l2 is displayed nni t l2 Represents MIT 121 relay nni t l3 Represents MIT 131 relay Press ß key repeatedly scrolls down the Factory setting Main menu in the following order on the display. C 5I 3 - Characteristics setting is Standard Inverse 3.0 Sec I I00 - Current setting is 100% 7

9 t I Time multiplier setting is d off - Directional is OFF rt 0 - Reset time delay is 0 Sec H off - Highset is OFF 3.2 SELECT CHARACTERISTICS Pressing ß key repeatedly get C 5I3 Main menu, press Submenu Þ key, 3mm LED in the Key Lit to indicate that the Sub menu is activated. Pressing ß key repeatedly the Sub menu will scroll down in the following order on the display. 5I 3 5II UI EI Lt I dt I - Standard Inverse 3.0 Sec characteristics - Standard Inverse 1.3 Sec characteristics - Very Inverse characteristics - Extremely Inverse characteristics - Long Time Inverse characteristics - Definite Time Lag characteristics By pressing Ý or ß key choose the desired characteristic and press Þ key. Now the Submenu LED goes OFF and the Main menu appears on the LED display. 3.3 CURRENT SETTING Setting range: 5% to 250% insteps of 5% Pressing ß key repeatedly get I I00 Main menu (represents the current setting has been set to 100%), press Þ key (Submenu LED On) to get the Sub menu. Pressing Ý or ß key changes the current setting in 5% increment or decrement. Upon selecting the desired setting, once again press the Þ key (Sub menu LED goes OFF) to return to the main menu. 3.4 TIME SETTING / TIME MULTIPLIER SETTING If characteristic is selected as Definite Time Lag, the Time setting range is Sec to Sec in steps of 0.01Sec. If characteristic is selected as Inverse, the Time Multiplier setting range is to in steps of

10 For Inverse Characteristics Pressing ß key repeatedly get t I.000 Main menu (represents Time Multiplier setting has been set to 1.000), press Þ key (Submenu LED On) to get the Sub menu. Pressing ß or Ý key changes the time setting by increment or decrement. Upon selecting the desired setting, once again pressing Þ key (Sub menu LED goes OFF) to return to the main menu. For Definite Time Lag Characteristics Pressing ß key repeatedly get t main menu (represents Time setting has been set to 3.00 Secs), press Þ key (Submenu LED On) to get the Sub menu. Pressing ß or Ý key changes the time setting by 0.01Seconds increment or decrement. Upon selecting the desired setting, once again press the Þ key (Sub menu LED goes OFF) to return to the main menu. 3.5 DIRECTIONAL SETTING Directional setting: Forward, Reverse, OFF Pressing ß key repeatedly get d off main menu (represents directional has been set to off), press Þ key (Submenu LED On) to get the Sub menu. Pressing the ß key repeatedly the Sub menu will scroll down in the following order on the display. d off - Direction setting is OFF d Frd - Direction setting is Forward d reu - Direction setting is Reverse Upon selecting the desired directional setting, once again press the Þ key (Sub menu LED goes OFF) to return to the main menu CHARACTERISTICS ANGLE SETTING Characteristics Angle setting range: 1 to 90 lead insteps of to 90 lag insteps of 1 The Characteristics angle menu will not appear in the display when the Directional setting is chosen to "OFF Pressing ß or Ý repeatedly get dald 45 main menu (represents Characteristics angle has been set to 45 lead). Press Þ key (Submenu LED On) to get the sub menu. Pressing Ý or ß key continuously, changes the Characteristics angle setting by 1 increments or decrements. When the angle setting reach to dald 90 main menu (represents Characteristics angle has been set to 90 lead) and still pressing the Ý key the menu will be changed to dal 990 (represents Characteristics angle has been set to 90 lag) and further continuous Ý key pressing the Lag angle will be decremented by 1, when reaching dal 9 I (represents Characteristics angle has been set to 1 lag) and pressing Ý key the setting changes to da 0 (represents Characteristics angle has been set to 0 ) 9

11 Upon selecting the desired characteristics angle setting, once again press the Þ key (Sub menu LED goes OFF) to return to the main menu. 3.6 RESET TIME Setting range: 0 Sec to 60 Sec in steps of 1 Sec. Pressing ß key repeatedly get rt 0 Main menu (represents reset time has been chosen as 0 sec). Press Þ key (Submenu LED On) to get Submenu. Pressing Ý or ß key, changes reset time delay by 1 second for each pressing. After selecting the desired setting, once again press the Þ key (Sub menu LED goes OFF) to get back the main menu. The recommended setting is 0sec. 3.7 HIGHSET (FOR MIT 131 TYPE ONLY) Setting range: 50% to 2500% in steps of 50%. From H off Main menu, Press Þ key (Submenu LED On) to get Submenu. Pressing Ý or ß key, changes highset value by 50% increments. After selecting the desired setting, once again press the Þ key (Sub menu LED goes OFF) to return to the main menu. When we select High set mode, automatically Directional High set mode will enable. In this mode we can select Directional High set is ON or OFF. 3.8 ACCEPTANCE OF SETTINGS (ENTER) For the relay to accept the above setting changes press X key once, now the display goes off and the settings are updated. By pressing any key again nni t I2 Indication will appear Ensure all the chosen settings are as per requirements. In case of any changes required use Sub menu key and then do the changes and finally press enter X key once. ENSURE TO PRESS 'X' KEY TO ACCEPT THE CHANGES 3.9 TO CHECK THE RELAY VERSION Press X key four times, example of relay version display is as follows: I2 I.00 I - Represent M I T 121 relay version 1 I3 I.00 I - Represent M I T 131 relay version 1 To get back the main menu, press Ý or ß key. 10

12 4. TO CANCEL SETTING WHILE CHANGING (CANCEL) While the particular setting is being changed (using Ý or ß key) with Submenu LED ON, by pressing X key, the original setting is restored 5. TRIP INDICATION AND RESETTING OF TRIP INDICATION (RESET) When the relay operates, RED " TRIP" LED indicates tripping. To find which element operated press Ý or ß key. There is possibility for the following display after the trip, I tri P Indicates Over current trip. H tri P Indicates Highset trip. Once the fault is cleared, press X key twice to reset the trip indication. The trip indication and settings will be retained in Non - volatile memory during auxiliary DC power supply failure. 6. CT RATING Pull out the relay from relay box and ensure the required current transformer tapping (1Amp/5Amp) is inserted into live terminal 9. 1Amp tapping is ferruled with 9A and 5Amp tapping is ferruled with 9B. Terminal No.10 is common for both 1Amp and 5Amp. 11

13 COMMISSIONING 1. REQUIRED TEST EQUIPMENT'S 500V insulation test sets. Variable secondary injection current source rated 10A or greater. Variable voltage source. Phase shifting transformer and phase angle meter. Time interval meter. Primary injection equipment. A DC supply with a nominal voltage within the working range of the relays DC auxiliary supply ratings. 2. INSPECTION Ensure that all connections are tight and in accordance with the relay wiring diagram and the scheme diagram. Check if the relay is correctly programmed and the relay is fully inserted into the case. 3. APPLYING SETTINGS The relay settings for the particular application should be applied before any secondary testing is started. 4. PRECAUTIONS Before testing commences, the equipment should be isolated from the current transformers and the CT's to be short-circuited, in line with the local site procedures. The tripping and alarm circuits should also be isolated, where practical. Also, ensure that trip links are removed. Ensure that correct DC auxiliary voltage and polarity is applied. See the relevant scheme diagrams for the relay connections. 5. TESTS 5.1 INSULATION Connect together all relay C.T. terminals and measure the insulation resistance between these terminals and all of the other relay terminals connected together and to earth. Connect together all relay V.T. terminals and measure the insulation resistance between these terminals and all of the other relay terminals connected together and to earth. Connect together the terminals of the DC auxiliary supply (only +ve and -ve) and measure the insulation resistance between these terminals and all of other terminals connected together and to earth. Connect together all the output relay terminals and measure the insulation resistance between these terminals and all of other terminals connected together and to earth. 12

14 Satisfactory values for the various readings depend upon the amount of wiring concerned. Where considerable multi-core wiring is involved a reading of 2.5 to 3.0 megohms can be considered satisfactory. For short lengths of wiring higher values can be expected. A value of 1.0 megohm should not be considered satisfactory and should be investigated. 5.2 SECONDARY INJECTION Select the required relay configuration and settings for the application. Note that the MIT relay can be connected either as 1A or 5A rated device. The user should check this before commencing secondary testing. Please refer Sec in Installation a. Pick up and Reset The test checks the accuracy of the current settings for the relay's main over current characteristics. Apply single-phase current into the current inputs. Slowly increase the current until the starter LED (yellow) operates and record the pick up current in Table 1. Reduce the current until the LED goes off and record this as the reset level. Check all the pick up current levels are measured within % or + 10 ma of the applied setting value. Check the reset levels are > 94% of pickup value. POLE PICK-UP SETTING MEASURED PICK-UP PICK-UP ERROR MEASURED PICK-UP RESET ERROR PHASE TABLE 1 b. IDMTL / DTL Characteristics This test checks the accuracy of the main time delay characteristics (IDMTL / DTL). Select the relay current setting, characteristics and time multiplier setting as required and then inject a level of current which is a multiple of the relay setting. A time interval meter should be connected to the correct output contact terminals. The timer should be started by the source and stopped by the relay trip contacts. A secondary injection timing test circuit is illustrated in Fig. 2. The secondary injection test equipment should be made 'OFF', once the relay contact is closed Table 2 shows theoretical value of each characteristic with time multiplier set to Record the actual results in Table 3 and check that the measured times lies within + 5% of the theoretical value. For DTL characteristics check the measured operating time lies with in + 1% of the setting. 13

15 CURVE 2xIs 5 x Is 10 x Is 20 x Is SI SI EI VI LTI DTL * * * * * USER SETTING TABLE 2 Pole Characteristic 2xls 5xls 10xls 20xls (SI3, SI1, EI, DTL Delay Error Delay Error Delay Error Delay Error VI, LTI) (5%) (5%) (5%) (5%) Phase c. Highset TABLE 3 Program the current settings for the highset characteristics to the required level. Inject a level of current below the setting of the relay, then increase the current until the output operates. Record the pick up level in Table 4. and confirm that it occurs within 100% + 4% or + 10 ma of applied setting. When the highset setting is above the continuous thermal rating of the relay, care should be taken, such that the duration of the applied current should not damage the relay. Refer catalogue for thermal rating. POLE Phase HIGHSET SETTING MEASURED PICK-UP ERROR TABLE 4 14

16 d. Output relays 1.Starter - C/O This contact to be used whiles testing the pick up and reset value of the relay. 2.IDMTL 1N/O contacts This contact to be used while testing the IDMTL characteristics. 3.Highset 1 N/O contacts This contact to be used while testing the highset characteristic. 4. Alarm - 1 N/O contact 5. Trip - 1 N/O contact 6. Protection Unhealthy - 1 N/C contact 5.3 DIRECTIONAL TESTING The following test deal specifically with directional functionality. Note that the directional response for each characteristic (e.g. IDMTL, Highset etc.) is programmable, and may be selected as either non-directional, forward or reverse on the requirement of the scheme. The 'Directional Control' settings should now be correctly programmed. Firstly remove the voltage fuses and check that the magnitude and phase sequences of the system voltages are correct DIRECTIONAL POLARITY CHECK This test checks for correct polarity of the directional circuits. Using the phase sequence indicator, first check that the phase sequence of the voltage in the relay is correct and see by inspection that the phasing of the connections is correct. Check the magnitudes of the voltage transformer voltage. Pass a single phase load current of about 25% or more of the current rating of the relay as per table no 5 and see that the directional elements operate or restrain depending upon the direction of flow of the primary current. If the flow of current is such that the relay should operate, see that in fact it does operate, then reverse the connections to the current coils and see that the relay restrains. If the flow of current is such that the relay should restrain, see that in fact it does restrain, then reverse the connections to the current coils and see that the relay operates. This test is based on the assumption that the load current has a normal power factor. 15

17 I phase I neutral V phase V neutral Phase Table 5. Terminal Details for directional polarity test CHECK THE OPERATING ANGLE OF THE DIRECTIONAL ELEMENT The maximum torque angle of a directional relay is defined as the phase angle between the current in the current coil and the voltage applied to the voltage coil at which the relay develops maximum torque. The available maximum torque angles are: - 1 to 90 lead in steps of to 90 lag in steps of 1 Energize the voltage coil with rated voltage and the current coil with rated current. Use the circuit shown in Fig.5 for connection. Set the phase shifting transformer at the phase angle for maximum torque. Set the indicator on the phase shifting transformer to zero; then adjust the control to give lagging and leading phase angles until the Starter LED drop off. The angle at which this occurs should be to the actual MTA, 88 lagging or leading with respect 5.4 PRIMARY INJECTION Primary injection tests are essential to check the ratio and polarity of the current transformers as well as the secondary wiring. Using the circuit shown in Fig. 3 check the current transformer ratio. Inject a current of sufficient magnitude The secondary current is Is = Primary current / CT ratio 5.5 PUTTING INTO SERVICE After completing all tests satisfactorily, the relay should be put back into service as follows: 1. Make a final check of the secondary wiring and tightness of all terminal connections. 2. Insert the DC supply fuse. 3. Check the relay healthy indication/display. 4. Replace the relay cover. 5. Insert the trip links. 6. Perform trip test by secondary injection. 7. Remove all test connections 16

18 Ph Switch MIT V AC SUPPLY Rheostat A ~ 9 Current input Nu 10 Start TIMER 22 Aux DC Ve -Ve Stop 3 4 Fig. 2 Secondary Injection Timing Test Circuit MIT 121 I A ~ 9 Current input I 10 Aux DC Ve -Ve 23 Primary Injection Kit Fig. 3 Primary Test Circuit 17

19 BUS MIT121-A MIT121-B MIT121-C P1 S1 S1 S1 A B C P2 S2 S2 S2 A C Phase Rotation B Voltage Tfr A B C Fwd Direction Fig. 4 Directional Over Current, 45 Lead p.f ( 90 Connection ) Ph MIT V AC SUPPLY Nu Phase Shifting Transofmer V ~ 11 Voltage input 12 Phase Angle Meter Aux DC VE -VE 23 Rheostat A ~ 9 Current input 10 Fig. 5 Directional Test Circuit 18

20 NOTES 19

21 NOTES 20

22

EASUN REYROLLE LIMITED

EASUN REYROLLE LIMITED OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT

More information

Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16

Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16 Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16 COMMISSIONING 17-22 WIRING DIAGRAM 23 1. INTRODUCTION

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Function diagrams amended,

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS Juan Manuel Gers, PhD Protection coordination principles Relay coordination is the process of selecting settings that will assure that the relays

More information

ECM3 EARTH CONTINUITY RELAY

ECM3 EARTH CONTINUITY RELAY TECHNICAL DATASHEET ECM3 EARTH CONTINUITY RELAY Electrical Protection for Hard Rock Mines Application The ECM3 has been designed to provide earth continuity protection for cables containing pilot cores.

More information

GE Power Management. Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C

GE Power Management. Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C GE Power Management Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C 7$%/(2)&217(176 1. DESCRIPTION...2 2. APPLICATION...6 3. CHARACTERISTICS...7

More information

McPherson Voltage Regulators 4501 NW 27 Ave Miami FL

McPherson Voltage Regulators 4501 NW 27 Ave Miami FL McPherson Voltage Regulators 4501 NW 27 Ave Miami FL 33142 305-634-1511 To avoid of possible personal injury or equipment damage read and understand this manual before installation. (A.V.R) 208 / 380 /

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Relay withdrawn from case Application The type CDG 11 relay

More information

DEPARTMENT OF ELECTRICAL ENGINEERING BENGAL ENGINEERING AND SCIENCE UNIVERSITY, SHIBPUR

DEPARTMENT OF ELECTRICAL ENGINEERING BENGAL ENGINEERING AND SCIENCE UNIVERSITY, SHIBPUR DEPARTMENT OF ELECTRICAL ENGINEERING BENGAL ENGINEERING AND SCIENCE UNIVERSITY, SHIBPUR Power system protection Laboratory (EE 852) 8 th Semester Electrical Expt. No. 852/1 BIFFI S METHOD FOR TESTING CURRENT

More information

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when

More information

Back to the Basics Current Transformer (CT) Testing

Back to the Basics Current Transformer (CT) Testing Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of

More information

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson... TECHNICAL REPORT APPLICATION GUIDE TITLE: Current Transformer Requirements for VA TECH Reyrolle ACP Relays PREPARED BY:- A Allen... APPROVED :- B Watson... REPORT NO:- 990/TIR/005/02 DATE :- 24 Jan 2000

More information

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features CT ratio Power Harmonics ac+dc 200ADM-P Current Injection System with Phase Shift Features 0-200A output current True RMS metering with 1 cycle capture Variable auxiliary AC voltage/current output with

More information

3 Pole high impedance differential relay 7VH83

3 Pole high impedance differential relay 7VH83 Fig 1. High impedance differential protection relay 7VH83 Features l Integral CT shorting relay. l Robust solid state design. l Inrush stabilisation through filtering. l Fast operating time. l LED indicator.

More information

MBCI (Translay S) Technical Manual. Differential Feeder and Transformer Feeder Protection. Publication Reference: GRID

MBCI (Translay S) Technical Manual. Differential Feeder and Transformer Feeder Protection. Publication Reference: GRID MBCI (Translay S) Technical Manual Differential Feeder and Transformer Feeder Protection Publication Reference: R8011G R8011G 2011. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks

More information

DOCUMENTATION SET 7SR224 RECLOSER CONTROLLER

DOCUMENTATION SET 7SR224 RECLOSER CONTROLLER (7) (7) (5) Applications Installation Guide 7SR224 7SR21 ARGUS-M 7SR21 Recloser 7SR22 ARGUS-M Controller 7SR21 DOCUMENTATION SET This document is part of a set. The full list of documents in the set, and

More information

POWER SYSTEM II LAB MANUAL

POWER SYSTEM II LAB MANUAL POWER SYSTEM II LAB MANUAL (CODE : EE 692) JIS COLLEGE OF ENGINEERING (An Autonomous Institution) Electrical Engineering Department Kalyani, Nadia POWER SYSTEM II CODE : EE 692 Contacts :3P Credits : 2

More information

7SR210 Non-Directional Relay 7SR220 Directional Relay Applications Guide

7SR210 Non-Directional Relay 7SR220 Directional Relay Applications Guide 7SR210 Non-Directional Relay 7SR220 Directional Relay Applications Guide (Software Version 2435H85008R7a-7a) (7SR210) (Software Version 2435H85009R7a-7a) (7SR220) The copyright and other intellectual property

More information

Conventional Paper-II-2011 Part-1A

Conventional Paper-II-2011 Part-1A Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET

ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET Candidate Code No. ET43 For Board Use Only Result Date Int Result Date Int ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET INSTRUCTIONS READ CAREFULLY Time Allowed: Three

More information

Electrical Protection System Design and Operation

Electrical Protection System Design and Operation ELEC9713 Industrial and Commercial Power Systems Electrical Protection System Design and Operation 1. Function of Electrical Protection Systems The three primary aims of overcurrent electrical protection

More information

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General

More information

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:

More information

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION GEK-00682D INTRODUCTION INTRODUCTION. PRODUCT DESCRIPTION The MDP Digital Time Overcurrent Relay is a digital, microprocessor based, nondirectional overcurrent relay that protects against phase-to-phase

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

ASHIDA Numerical 3OC + 1EF Protection Relay

ASHIDA Numerical 3OC + 1EF Protection Relay PROTH. ERR L5 PKP FAULT DT REC LOCK BF L6 L7 CLOSE TRIP ADR 241B Protection Features : 4 Element (3 Phase + EF + Sensitive EF) Over current IDMT/DMT with instant trip. Programmable (Non- Volatile) Setting

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES PURPOSE The following is PG&E's procedure for pre-energization inspections. For PG&E to provide the Load

More information

PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY

PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY Sheet 1 of 15 TEST DATE: CUSTOMER: SERIAL NO: OLTC ACKNOWLEDGE SETUP AUTOMATIC or FEEDBACK CONTROL PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY Issue Date Level A 06/01/1997 Initial issue. Summary

More information

Phase and neutral overcurrent protection

Phase and neutral overcurrent protection Phase and neutral overcurrent protection Page 1 ssued June 1999 Changed since July 1998 Data subject to change without notice (SE970165) Features Two-phase or three-phase time-overcurrent and earth fault

More information

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009 Catalog 00 Contactors up to 5 A Motor Starters up to 55 kw 03/009 Kraus & Naimer The development of the Blue Line rotary switch, contactor and motor starter product ranges is based on more than hundred

More information

BlockMon Block Monitor LongMon Long Monitor

BlockMon Block Monitor LongMon Long Monitor BlockMon Block Monitor LongMon Long Monitor Bypass range 2.2V to 5.0V. Bypass current 0A to 2A (typically 1A). Over-voltage protection up to ±20V. Noise immune opto-isolated. Cell temperature and bypass

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Earth Fault Relay EFSPL-1A/5A

Earth Fault Relay EFSPL-1A/5A Earth Fault Relay EFSPL-1A/5A IEEE DEVICES CODE-50N Features Static Device Compact, Reliable with Aesthetic Value Rugged, Robust and Tropicalised design Consistent repeat accuracy Wide Current Operating

More information

OVERCURRENT PROTECTION RELAY GRD110

OVERCURRENT PROTECTION RELAY GRD110 INSTRUCTION MANUAL OVERCURRENT PROTECTION RELAY GRD110 TOSHIBA Corporation 2002 All Rights Reserved. ( Ver. 3.1) Safety Precautions Before using this product, please read this chapter carefully. 1 This

More information

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax : NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE

More information

9 Overcurrent Protection for Phase and Earth Faults

9 Overcurrent Protection for Phase and Earth Faults Overcurrent Protection for Phase and Earth Faults Introduction 9. Co-ordination procedure 9.2 Principles of time/current grading 9.3 Standard I.D.M.T. overcurrent relays 9.4 Combined I.D.M.T. and high

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

ASHIDA Numerical OC/EF Protection Relay

ASHIDA Numerical OC/EF Protection Relay ASHIDA Numerical OC/EF Protection Relay Features: 4 Element (3 Phase + EF) over current IDMT with instant trip. Back - lit LCD display for settings. Display of fault current. / Load current. Selection

More information

Time-current Coordination

Time-current Coordination 269 5.2.3.1 Time-current Coordination Time that is controlled by current magnitude permits discriminating faults at one location from another. There are three variables available to discriminate faults,

More information

3.0 CHARACTERISTICS. Type CKO Overcurrent Relay. switch, which allows the operation indicator target to drop.

3.0 CHARACTERISTICS. Type CKO Overcurrent Relay. switch, which allows the operation indicator target to drop. 41-101.3A Type CKO Overcurrent Relay switch, which allows the operation indicator target to drop. The front spring, in addition to holding the target, provides restraint for the armature and thus controls

More information

ASHIDA Numerical Directional 3OC + 1EF Protection Relay

ASHIDA Numerical Directional 3OC + 1EF Protection Relay Ashida Numerical Directional 3O/C + 1E/F PROTH. PROTH. ERR L5 FAULT PKP PKP FAULT L6 PT DT REC LOCK BF L7 CLOSE TRIP TRIP CLOSE ADR 145B 245B Protection Features: 4 Element (3 Phase + EF +sensitive EF)

More information

Relay Types and Applications Dr. Sasidharan Sreedharan

Relay Types and Applications Dr. Sasidharan Sreedharan O&M of Protection System and Relay Coordination Relay Types and Applications Dr. Sasidharan Sreedharan www.sasidharan.webs.com Detailed Schedule 2 SIMPLE RELAY Magnitude Rate of Change Phase Angle Direction

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities

More information

ET 40 - Electrician Theory Examination Marking Schedule

ET 40 - Electrician Theory Examination Marking Schedule ET 40 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions. A marker

More information

PM 305 Operating Guide

PM 305 Operating Guide PM 305 Operating Guide Northern Design PREFACE PM305 Operating Guide Revision 2.05 October 2000 This manual represents your meter as manufactured at the time of publication. It assumes standard software.

More information

No. 139 Jinghai Third Road, BDA, Beijing, China, Office TEL. +86 (10) Website

No. 139 Jinghai Third Road, BDA, Beijing, China, Office TEL. +86 (10) Website PONOVO POWER CO., LTD No. 139 Jinghai Third Road, BDA, Beijing, China, 100176 Office TEL. +86 (10) 5908 9666 E-Mail Info@relaytest.com Website www.relaytest.com T1000 Series Universal Tester VERSION: DATE:

More information

Relion 605 series. Self-Powered Feeder Protection REJ603 Application manual

Relion 605 series. Self-Powered Feeder Protection REJ603 Application manual Relion 605 series Relion 605 series Relion 605 series Self-Powered Feeder Protection REJ603 Application manual Document ID: 1MDU07206-YN 6 2 4 This document and parts thereof must not be reproduced or

More information

Earth Fault Indicator EFI-BLZ-50 User Manual

Earth Fault Indicator EFI-BLZ-50 User Manual Earth Fault Indicator EFI-BLZ-50 User Manual CONTENTS SAFETY NOTICE.................................................................................... 3 1 OVERVIEW......................................................................................

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

Replacement solution

Replacement solution Replacement solution for the ABB DPU2000R protection and control relay Specification File, Revision, Date (Pages) Replacement Relay Specification_ABB DPU2000R_0.doc, Revision 0, August 2, 2013 (37) Table

More information

Coordination of protective relays in MV transformer stations using EasyPower Protector software

Coordination of protective relays in MV transformer stations using EasyPower Protector software Coordination of protective relays in MV transformer stations using EasyPower Protector software S. Nikolovski, Member, IEEE, I. Provci and D. Sljivac In this paper, the analysis of digital protection relays

More information

Instantaneous Overcurrent Relay

Instantaneous Overcurrent Relay Midos Type MCRI Instantaneous Overcurrent Relay Features High speed operation Not slowed by dc transients Settings readily adjustable on relay front plate Two phase and earth fault relay Figure 1: Type

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT. MODBUS/BECO2200-M3425A Communication Data Base for M-3425A Integrated Protection System Device I.D. = 150 Specifications presented herein are thought to be accurate at the time of publication but are subject

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

2V68-S User Guide. CT Supervision And Shorting Relay. User Guide

2V68-S User Guide. CT Supervision And Shorting Relay. User Guide 2V68-S User Guide CT Supervision And Shorting Relay User Guide Visit www.rmspl.com.au for the latest product information. Due to RMS continuous product improvement policy this information is subject to

More information

ARC FLASH HAZARD ANALYSIS AND MITIGATION

ARC FLASH HAZARD ANALYSIS AND MITIGATION ARC FLASH HAZARD ANALYSIS AND MITIGATION J.C. Das IEEE PRESS SERIES 0N POWER ENGINEERING Mohamed E. El-Hawary, Series Editor IEEE IEEE PRESS WILEY A JOHN WILEY & SONS, INC., PUBLICATION CONTENTS Foreword

More information

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR). RETROFITTING Motor Protection Relay NPM800R (R2 case) and NPM800RE (R3 case) are dedicated to the refurbishment of 7000 series (R2 and R3 cases) of CEE relays providing the protection of medium voltage

More information

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed

More information

Table 1 Various IRD models and their associated time/current characteristics Time/Current Characteristics. Definite Time Moderately Inverse Time

Table 1 Various IRD models and their associated time/current characteristics Time/Current Characteristics. Definite Time Moderately Inverse Time IRD SCOPE This test procedure covers the testing and maintenance of Westinghouse IRD relays. The Westinghouse Protective Relay Division was purchased by ABB, and new relays carry the ABB label. Refer to

More information

Operating Instructions

Operating Instructions 4XH35QB151210 Small General Frequency Converter Operating Instructions 220V 0.75KW 5.5KW 400V 0.75KW 15KW Please read the instruction carefully and understand the contents so that it can be installed and

More information

Installation and Operating Instructions. Power IT Power Factor Controller RVC

Installation and Operating Instructions. Power IT Power Factor Controller RVC Installation and Operating Instructions Power IT Power Factor Controller RVC Table of contents Page 1. Read this first... 3 About this Instruction Manual... 3 Safety... 3 Electromagnetic compatibility...

More information

SPAJ 111 C. Sensitive earth-fault relay SPAJ 111 C. User s manual and Technical description. U aux V ~ V. f n. n ( I o>> SPCJ 1C7

SPAJ 111 C. Sensitive earth-fault relay SPAJ 111 C. User s manual and Technical description. U aux V ~ V. f n. n ( I o>> SPCJ 1C7 SPAJ 111 C Sensitive earth-fault relay User s manual and Technical description I n = 1A 5A ( I ) f n = 50Hz 60Hz 2 5 B I o I IRF SPAJ 111 C 80...265V ~ 18...80V U aux STEP I o > [%] I n 1.0 6.0 10 STEP

More information

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection Quick Start Guide TECO F510 Inverter This guide is to assist you in installing and running the inverter and verify that it is functioning correctly for it s main and basic features. For detailed information

More information

INSTRUCTIONS FOR THE COMMISSIONING AND MAINTENANCE OF DIGITAL GENERATOR PROTECTION 3 I - PRINCIPLES AND APPLICATIONS 4 on 5 6 7 Figure 5 - Inverse time curve (N1) 8 9 1 0 1 1 1 2 1 3 All relays are delivered

More information

User s manual and Technical description. Self-Powered Feeder Protection REJ603

User s manual and Technical description. Self-Powered Feeder Protection REJ603 and Technical description Self-Powered Feeder Protection 2 Document ID: Issued: 18.02.2008 Revision: A Product version:1.0 Copyright 2008 ABB. All rights reserved 3 Copyright This document and parts thereof

More information

FINAL - ET 60 - Electrician Theory Examination Marking Schedule

FINAL - ET 60 - Electrician Theory Examination Marking Schedule FINAL - ET 60 - Electrician Theory Examination Marking Schedule Notes:1. means that the preceding statement/answer earns 1 mark. 2. This schedule sets out the accepted answers to the examination questions.

More information

7PG23 5B3 Restricted Earth Fault Answers for energy

7PG23 5B3 Restricted Earth Fault Answers for energy Reyrolle Protection Devices 7PG23 5B3 Restricted Earth Fault Answers for energy 7PG23 5B3 Contents Contents Technical Manual Chapters 1. Description of Operation 2. Performance Specification 3. Applications

More information

CableTroll 2410 PN: /03. User Manual

CableTroll 2410 PN: /03. User Manual CableTroll 2410 PN: 01-2410- 02/03 User Manual UG CT 2410-RMU February 2010 This document describes the installation and configuration of the RMU Fault Indicator Product no: 01-2410- 02/03 Rev. 0.1 (21.01.09)

More information

Type VDG 13 Undervoltage Relay

Type VDG 13 Undervoltage Relay Type VDG 13 Undervoltage Relay Type VDG 13 Undervoltage Relay VDG 13 relay withdrawn from case Features l Identical time/voltage characteristics on all taps. l Frequency compensated. l Simple construction,

More information

CDV 22, 62. Voltage Controlled Overcurrent Relay GRID PROTECTION

CDV 22, 62. Voltage Controlled Overcurrent Relay GRID PROTECTION PROTECTION CDV 22, 62 Voltage Controlled Overcurrent Relay CDV22 relay is used for overload and fault protection for ac generators when the sustained short circuit current is less than the full load current.

More information

Distribution/Substation Transformer

Distribution/Substation Transformer Distribution/Substation Transformer Type VFI, Vacuum Fault Interrupter Transformer Option Functional Specification Guide Functional specification for 15 kv, 25 kv, or 35 kv vacuum fault interrupter distribution/substation

More information

PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY

PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY Sheet 1 of 12 TEST DATE CUSTOMER SERIAL No OLTC ACKNOWLEDGE SETUP AUTOMATIC or FEEDBACK CONTROL PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY Issue Date Level I 21/05/1998 Initial issue. Summary

More information

INSPECTION 1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

INSPECTION 1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it. CEH51A SCOPE This test procedure covers the testing and maintenance of the GE CEH51A loss of excitation relay. Refer to IL GEK-27887 for testing support information and component level identification.

More information

Type CVX and CVX-1 Synchro-Verifier Relays

Type CVX and CVX-1 Synchro-Verifier Relays I.L. 41-682.11 Type CVX and CVX-1 Synchro-Verifier Relays TIME DIAL POTENTIOMETER (R3) CIRCLE ADJUST RESTRAINT ELECTROMAGNET Figure 1. CVX-1 Relay Front View, Out of Case OPERATING ELECTROMAGNET TELEPHONE

More information

Height: inches Width: inches Depth: inches, inches. Listings/Certification UL 1053 ANSI C37-90 IEC 255. General Description

Height: inches Width: inches Depth: inches, inches. Listings/Certification UL 1053 ANSI C37-90 IEC 255. General Description 1rcJll Cutler-Hammer New nformation Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer protection Backup

More information

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht Temperature Controller model MFC-301/T-Dry Version for Dry Transformers and Motors Technical Manual Licht Contents 1 Introduction 2 2 Operating principle 3 2.1 General principle 3 2.2 RTD operation 3 3

More information

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300 Monitoring Technique VARIMETER IMD Insulation monitor RN 5897/300 0274214 Your Advantages For mobile generator sets according to DIN VDE 0100-551 Preventive fire and system protection Detection of symmetric

More information

CROSS Chassis from 160 A to 450 A

CROSS Chassis from 160 A to 450 A CROSS Chassis from 160 A to 450 A STS CATALOGUE Important note! The technical data enclosed is for general information. Please note that the operating instructions and references indicated on the products

More information

MRS1 - Negative sequence relay. Manual MRS1 (Revision A)

MRS1 - Negative sequence relay. Manual MRS1 (Revision A) MRS1 - Negative sequence relay Manual MRS1 (Revision A) Woodward Manual MRS1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided

More information

SPAJ 135 C. Combined overcurrent and earth-fault relay SPAJ 135 C. User s manual and Technical description. U aux V ~ V.

SPAJ 135 C. Combined overcurrent and earth-fault relay SPAJ 135 C. User s manual and Technical description. U aux V ~ V. SPAJ 135 C Combined overcurrent and earth-fault relay User s manual and Technical description I n = 1A 5A ( I ) I n = 1A 5A ( I o ) f n = 50Hz 60Hz 2 5 B I L1 I L3 I o 2 I > I IRF SPAJ 135 C 80...265V

More information

COPYRIGHTED MATERIAL. Index

COPYRIGHTED MATERIAL. Index Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

Overcurrent Protective Relays

Overcurrent Protective Relays Power System Protection Overcurrent Protective Relays Dr.Professor Mohammed Tawfeeq Lazim Alzuhairi 99 Power system protection Dr.Mohammed Tawfeeq Overcurrent Protective Relays Overcurrent relays Overcurrent

More information

BE1-32R, BE1-32 O/U DIRECTIONAL POWER RELAY

BE1-32R, BE1-32 O/U DIRECTIONAL POWER RELAY BE1-32R, BE1-32 O/U DIRECTIONAL POWER RELAY The BE1-32R Directional Overpower Relay and the BE1-32 O/U Directional Over/Underpower Relay are solid-state devices which provide versatility and control in

More information

PLAN... RESPOND... RESTORE! Utility Automation & Information Technology... Automation Rising

PLAN... RESPOND... RESTORE! Utility Automation & Information Technology... Automation Rising Automation Rising Q U A R T E R LY First Quarter 2013 The Digital Magazine of Automation & Information Technology for Electric, Gas and Water Utilities Utility Automation & Information Technology... PLAN...

More information

Industrial Electrician Level 3

Industrial Electrician Level 3 Industrial Electrician Level 3 Industrial Electrician Unit: C1 Industrial Electrical Code I Level: Three Duration: 77 hours Theory: Practical: 77 hours 0 hours Overview: This unit is designed to provide

More information

DIGITAL EARTH FAULT RELAY

DIGITAL EARTH FAULT RELAY DIGITAL IDMT / DEFINITE TIME / INSTANTANEOUS Features Compact IDMT (4 IEC curves), Definite Time & Instantaneous Wide setting ranges Fully digital acquisition & processing of data Wide operating voltages

More information

Type KLF Generator Field Protection-Loss of Field Relay

Type KLF Generator Field Protection-Loss of Field Relay Supersedes DB 41-745B pages 1-4, dated June, 1989 Mailed to: E, D, C/41-700A ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA For Use With Delta Connected Potential Transformers

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator Test results and settings are saved into local memory

More information

INVERTER INSTRUCTION MANUAL. 16 bit digital input function. Plug-in option FR-A7AX PRE-OPERATION INSTRUCTIONS INSTALLATION AND WIRING

INVERTER INSTRUCTION MANUAL. 16 bit digital input function. Plug-in option FR-A7AX PRE-OPERATION INSTRUCTIONS INSTALLATION AND WIRING INVERTER Plug-in option FR-A7AX INSTRUCTION MANUAL 16 bit digital input function PRE-OPERATION INSTRUCTIONS INSTALLATION AND WIRING CONNECTION DIAGRAM AND TERMINAL PARAMETERS 1 2 3 4 Thank you for choosing

More information

Intermittent transient earth fault protection

Intermittent transient earth fault protection Intermittent transient earth fault protection The directional intermittent transient earth fault protection is used to detect short intermittent transient faults in compensated cable networks (figure 3).

More information