EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

Size: px
Start display at page:

Download "EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM"

Transcription

1 EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM BY MR. H. C. MEHTA AT 1 ST INDIA DOBLE PROTECTION AND AUTOMATION CONFERENCE, NOV 2008 POWER-LINKER Wisdom is not Virtue but Necessity hcmehta@powerlinker.org 1

2 2 EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

3 3 IN AN ELECTRICAL SYSTEM, CLOSE TO 70% TO 80% OF FAULTS ARE EARTH FAULTS. THE MAGNITUDE OF EARTH FAULT CURRENT IS DEPENDENT UPON: SYSTEM (SOURCE) GROUNDING VECTOR OF TRANSFORMER AND CORRESPONDING STAR NEUTRAL GROUNDING METHOD. ARC RESISTANCE VALUE

4 4 GROUNDING METHODS SOLID GROUNDING o FAULT CURRENT IN K AMPS LOW (MEDIUM) RESISTANCE GROUNDING o FAULT CURRENT LIMITED TO 1000 AMPS TO 2000 AMPS HIGH RESISTANCE GROUNDING o FAULT CURRENT LIMITED TO 100 AMPS VERY HIGH RESISTANCE GROUNDING o CURRENT LIMITED TO LESS THAN 15 AMPS

5 5 GENERALLY GROUNDING METHOD OF TRANSFORMER RECEIVING POWER FROM GRID IS SOLID GROUNDING OR LOW RESISTANCE GROUNDING GROUNDING OF GENERATING SOURCE IS HIGH RESISTANCE GROUNDING, OR VERY HIGH RESISTANCE GROUNDING

6 6 CASE STUDY : o CEMENT PLANT RUNNING SYSTEM OPERATION IS WITH SOURCE GROUNDED THROUGH LOW RESISTANCE GROUNDING AT RECEIVING END. FAULT CURRENT MAGNITUDE IS LIMITED TO 1313 AMPS

7 UTILITY 5000 MVA CB6 RECEIVING GRID POWER BUS4 132 kv CB7 CB8 GROUNDED THROUGH LOW RESISTANCE TR-1 15 MVA 132/ % Z TR-2 15 MVA 132/ % Z 2.9 CB9 2.9 OHMS 1313 A BUS5 NO CB10 BUS7 OHMS 1313 A CB12 CB11 CB13 FIG 1: EXISTING SYSTEM SINGLE LINE DIAGRAM 7

8 8 CASE STUDY : OUTGOING FEEDER C.T. RATIO IS 2000/1 ACCORDINGLY, EARTH FAULT PROTECTION RELAY SENSITIVITY IS GOOD. PU = 10% = 0.1 SENSITIVITY = MIN.CURRENT FOR SENSING MAX. FAULT CURRENT = 0.15 = 15 % = RELAYS OPERATE EFFICIENTLY FOR ALL EARTH FAULTS.

9 9 MODIFICATION IN SYSTEM : CAPTIVE POWER PLANT GENERATORS ARE ADDED TO EXISTING ELECTRICAL DISTRIBUTION.

10 UTILITY 5000 MVA CB6 BUS4 132 kv NGR 100 A CB1 BUS1 TG-1 G 15 MW 1640 A % Xd NO NGR 100 A CB2 G TG-2 15 MW 1640 A % Xd BUS3 CB7 CB8 TR-2 15 MVA 132/ % Z 2.9 OHMS 1313 A TR-1 15 MVA 132/ % Z 2.9 CB9 BUS5 NO CB1 0 BUS7 OHMS 1313 A CB4 CB3 CB5 CB12 CB11 CB13 FIG. SLD AFTER ADDITION OF 2X15MW CAPTIVE POWER PLANT 10

11 11 GENERATORS ARE GROUNDED THROUGH HIGH RESISTANCE. CURRENT LIMITED TO 100 AMPS EARTH FAULT CURRENT CONTRIBUTION BY GENERATOR IS SMALL

12 HIGH RESISTANCE GROUNDING NGR 100 A NGR 100 A G TG-1 15 MW 1640 A % Xd G TG-2 15 MW 1640 A % Xd MAX 100A CB1 CB2 BUS1 NO BUS3 CB4 CB3 CB5 FIG. SLD AFTER ADDITION OF 2X15MW CAPTIVE POWER PLANT 12

13 13 PROBLEMS : o GROUNDING METHODS ARE MIXED UP, HENCE, o GRID CONTRIBUTES HIGH CURRENT (1313 AMPS) TO GENERATOR FAULTS, AGAINST 100 AMPS LIMITATIONS ENVISAGED BY GENERATOR MANUFACTURER.

14 UTILITY 5000 MVA CB6 BUS4 132 kv NGR 100 A CB1 BUS1 TG-1 G 15 MW 1640 A % Xd NGR 100 A 100 A NO 1413 A CB2 G TG-2 15 MW 1640 A % Xd BUS3 CB7 CB8 TR-2 15 MVA 132/ % Z 2.9 OHMS 1313 A TR-1 15 MVA 132/ % Z A CB9 BUS5 NO CB1 0 BUS7 OHMS 1313 A CB4 CB3 CB5 CB12 CB11 CB13 FIG. SLD AFTER ADDITION OF 2X15MW CAPTIVE POWER PLANT 14

15 15 PROBLEMS : o THIS CAN DAMAGE GENERATOR WINDING & CORE GENERATOR CORE CAN WITHSTAND 100 A FOR APP = 0.7 SEC.

16 FIG: TYPICAL CORE DAMAGE CURVE 16

17 17 o VARIATION IN EARTH FAULT CURRENT FOR OUTGOING FEEDERS WITH GRID (1313 A A) WITHOUT GRID TRANFOFMER WITH ONE GENERATOR-100A WITH TWO GENERATORS (100 A +100 A). A PROBLEM FOR PROTECTION RELAY SETTING CHOOSE DMT CHARACTERISTICS

18 o FEEDER WITH HIGHER C.T RATIO AND EXISTING RELAYS MAY NOT PICK UP. o FOR EARTH FAULT CURRENT MAGNITUDE OF 200 A WITH TWO GENERATORS IN OPERATION. o RELAY SETTING MIN 10%, CT RATIO = 2000/1 SENSITIVITY = = 1 100% EQUIPMENTS NOT PROTECTED o IF FAULT HAS AN ARC RESISTANCE THEN RELAY MAY NOT PICK UP. 18

19 EARTH FAULT CURRENT ISOLATION SENSITIVITY REDUCED DRASTICALLY. WITH ONE GENERATOR, MAX. EARTH FAULT CURRENT = 100 A. 200 RELAY DO NOT PICK UP. AS SENSITIVITY = = 200% 100 DUE TO MIX UP OF GROUNDING METHODS REDUCED EARTH FAULT CURRENT SENSITIVITY PROPOSED SYSTEM DISRIBUTION NOT ACCEPTABLE 19

20 20 POSSIBLE SOLUTION : o RATIONALIZE GROUNDING SYSTEM OR o EXISTING EARTH FAULT PROTECTION RELAYS TO BE REPLACED BY SENSITIVE EARTH FAULT PROTECTION RELAY.

21 21 RATIONALIZATION OF GROUNDING SYSTEM o SOLUTION : I ADD GENERATOR TRANSFORMER (SOME TIMES UNIT RATIO TRANSFORMER : URT) IN SERIES WITH GENERATORS VECTOR OF TRANSFORMER DELTA / STAR

22 FIG. 4 RATIONALIZATION OF GROUNDING SYSTEM BY ADDITION OF UNIT RATIO GENERATOR TRANSFORMER 22 LOW RESISTANCE GROUNDING GENERATOR TRANSFORMER OR URT UTILITY 5000 MVA NGR 100 A NGR 100 A BUS4 CB6 132 kv EXISTING SYSTEM GT-1 20 MVA 6.6/ 10 % Z TG-1 15 MW G 1640 A % Xd GT-2 20 MVA 6.6/ 10 % Z 2.9 OHMS A G TG-2 15 MW 1640 A % Xd 2.9 OHMS A CB7 TR-1 15 MVA 132/ % Z 2.9 OHMS 1313 A CB8 TR-2 15 MVA 132/6.6 kv % Z 2.9 OHMS 1313 A CB1 CB2 CB9 CB10 BUS1 NO BUS3 BUS5 NO BUS7 CB4 CB3 CB5 CB12 CB11 CB13

23 23 LOAD SIDE STAR WINDING IS GROUNDED THROUGH LOW RESISTANCE. NGR OF SAME RATING AS THAT OF GRID TRANSFORMER TO BE INTRODUCED. FAULT CURRENT LIMITED TO 1313 AMPS.

24 24 ADVANTAGES WITH ADDITION OF GENERATOR TRANSFORMER (URT) o EARTH FAULT CURRENT MAGNITUDE SUFFICIENT TO MAINTAIN HIGH EARTH FAULT CURRENT SENSITIVITY. o GENERATOR CORE AND WINDING PROTECTED AGAINST HIGH EARTH FAULT CURRENT FROM GRID TRANSFORMER o GENERATOR FAULT CURRENT LIMITED TO 100 A.

25 ADVANTAGES WITH ADDITION OF GENERATOR TRANSFORMER (URT) o GENERATOR ISOLATED FROM DISTRIBUTION SYSTEM S PHASE AS WELL AS EARTH FAULT CURRENT. o DISTRIBUTION SYSTEM FAULTS ARE NOT SEEN AS GENERATOR TERMINAL FAULTS. DISADVANTAGES : o NO DISADVANTAGES. o ONLY ADDITIONAL CAPITAL INVESTMENT ON GENERATOR TRANSFORMER 25

26 26 SOLUTION : II o RATIONALIZATION OF GROUNDING SYSTEM BY MODIFYING EXISTING SOURCE GROUNDING. CONVERTING EXISTING LOW RESISTANCE GROUNDING TO HIGH RESISTANCE GROUNDING. REPLACE EXISTING NGR.

27 NGR VALUE SAME UTILITY 5000 MVA CB6 NEW HIGH RESISTANCE NGR NGR 100 A 38.1 OHMS TG-1 G 15 MW 1640 A % Xd NGR 100 A 38.1 OHMS G TG-2 15 MW 1640 A % Xd CB7 TR-1 15 MVA 132/ % Z BUS4 132 kv 100 A 38.1 OHMS CB8 TR-2 15 MVA 132/ % Z 100 A 38.1 OHMS EXISTING NGR REPLACED CB1 CB2 CB9 CB10 BUS1 NO BUS3 BUS5 NO BUS7 CB4 CB3 CB5 CB12 CB11 CB13 FIG. 5 RATIONALIZATION OF GROUNDING SYSTEM BY REPLACEMENT OF NGR 27

28 28 NEUTRAL GROUNDING RESISTOR OF GRID TRANSFORMER IS REPLACED. NEW NGR HAS THE SAME RATING AS THAT OF GENERATOR NGR, CURRENT LIMITED TO 100 AMPS.

29 29 PRECAUTIONS. o GRID TRANSFORMER GROUNDED THROUGH LOW RESISTANCE. NEUTRAL INSULATION CAN BE GRADED. TO CHANGE TO HIGH RESISTANCE GROUNDING CHECK THAT TRANSFORMER NEUTRAL IS FULLY INSULATED. (PRACTICALLY UNGROUNDED SYSTEM INSULATION). TRANSFORMER NEUTRAL, WITH GRADED INSULATION CANNOT BE HIGH RESISTANCE GROUNDED.

30 o THIS CEMENT PLANT CASE TRANSFORMER WAS 15 YEARS OLD, NOT FEASIBLE TO GET DESIGN DATA VERIFIED. o MANUFACTURER LATER CONFIRMED THAT TRANSFORMER NEUTRAL WAS FULLY INSULATED. o INSERTED HIGH RESISTANCE NGR, AS NEUTRAL WAS FULLY INSULATED. o RATIONALIZED THE GROUNDING SYSTEM BY LIMITING THE EARTH FAULT CURRENT TO 100 AMPS FROM EACH SOURCE. 30

31 ADVANTAGES : o EARTH FAULT CURRENT MAGNITUDE LIMITED TO 100 AMPS, o THUS IN CASE OF GENERATOR FAULT, DAMAGE TO GENERATOR WINDING & CORE IS LIMITED. DISADVANTAGE : o SENSITIVITY OF CLEARING EARTH FAULT CURRENT REDUCED. o CONDITION IS CRITICAL WITH ONE GENERATOR IN OPERATION. o MAXIMUM EARTH FAULT CURRENT IS 100 AMPS. o THIS REQUIRES REPLACEMENT OF EXISTING EARTH FAULT PROTECTION RELAYS. SOLUTION TO PROBLEM: ADD SENSITIVE EARTH FAULT PROTECTION. 31

32 50N/2 : TIME DELAYED SENSITIVE EARTH FAULT RELAY 59 : NEUTRAL DISPLACEMENT RELAY BUS4 UTILITY 5000 MVA CB6 132 kv (+) (-) 50N/ /a 52 TC TYPICAL CONTROL CIRCUIT NGR 100 A NGR 100 A CB7 CB8 CB1 BUS1 TG-1 G 15 MW 1640 A % Xd R 50N/2 NO CB2 TG-2 G 15 MW 1640 A % Xd R 50N/2 BUS3 TR-1 15 MVA 132/ % Z 38.1 OHMS 100 A TR-2 15 MVA 132/ % Z 38.1 OHMS 100 A 3000/1 R 50N/2 R 50N/2 3000/1 SENSITIVE CB9 CB10 EARTH FAULT PROTECTION BUS5 NO BUS7 CB4 CB5 CB12 59 CB3 PT CB11 R 50N/2 R R 50N/2 R 50N/2 NDR FIG. 6 INTRODUCTION OF NDR WITH SENSITIVE EARTH FAULT RELAY 50N/2 32

33 o EARTH FAULT CURRENT MAGNITUDE LIMITED TO 100 AMPS. o THE HIGHEST RATING FEEDER IS 2000 AMPS. o MAXIMUM EARTH FAULT CURRENT WITH ONE GENERATOR = 100A. o CT RATIO = 2000/1 CT SECONDARY CURRENT = 100/2000 MINIMUM PU < 0.05 A < 5% o NEW SENSITIVE EARTH FAULT RELAY RECOMMENDED WITH o PICK UP (SENSITIVITY) <5% o BUILT IN FUTURE TO FILTER 3RD HARMONIC CURRENT o HIGH RELAY RESET CURRENT (GREATER THAN 95% OF OPERATING CURRENT) o SHORT TIME DELAY RANGE ( SEC) 33

34 SUSPECTED MALOPERATION : o SENSITIVE (VERY LOW) EARTH FAULT RELAY SETTING (<5%). o MAL-OPERATION OF THIS RELAY SUSPECTED DURING TRANSIENT CONDITION TO ENSURE RELIABILITY AND STABILITY. o NEUTRAL DISPLACEMENT RELAY RECOMMENDED o RELAY TO BE CONNECTED ON PT SECONDARY OPEN DELTA WINDING. o A CONTACT OF NDR WAS RECOMMENDED TO BE CONNECTED IN SERIES WITH EARTH FAULT RELAY. 34

35 35 CONCLUSION : o TWO POWER SOURCES WITH DIFFERENT GROUNDING METHODS SHALL NOT BE OPERATED IN PARALLEL. o THIS CAN DAMAGE THE EQUIPMENT GROUNDED THROUGH HIGH RESISTANCE GROUNDING SYSTEM. o GROUNDING METHODS OF TWO SOURCES SHALL ALWAYS BE RATIONALIZED FOR CONTINUOUS PARALLEL OPERATION.

36 RECOMMENDATION : o RATIONALIZE GROUNDING SYSTEM OF SOURCES AT POINT OF COMMON COUPLING (PCC) BY INTRODUCING GENERATOR TRANSFORMER, THUS RETAINING, SECONDARY GROUND FAULT CURRENT MAGNITUDE SAME AS EXISTING & SENSITIVITY OF DETECTING GROUND FAULT CURRENT MAGNITUDE BY RETAINING EXISTING EARTH FAULT PROTECTION SCHEME / RELAYS. OR 36

37 RECOMMENDATION : o REPLACE EXISTING SOURCE GROUNDING TO MATCH WITH THE EQUIPMENT GROUNDED THROUGH HIGH RESISTANCE. o PROVIDE HIGH SENSITIVITY EARTH FAULT RELAY TO DETECT LOW MAGNITUDE EARTH FAULT CURRENT. o TO PREVENT MAL-OPERATION, RELAY SHALL HAVE PROTECTION AGAINST 3RD HARMONIC CURRENT. SHALL HAVE HIGH RESET CURRENT. PROVIDE CONTACT OF NEUTRAL DISPLACEMENT RELAY IN SERIES WITH SENSITIVE EARTH FAULT RELAY. 37

38 38

39 POWER-LINKER POWER - LINKERS Times Square, 602B, B Wing, Near Marol Metro Station, Andheri (E), Mumbai , India. hcmehta@powerlinker.org Website : 39

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Connection Impact Assessment Application

Connection Impact Assessment Application Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,

More information

Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content

Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION Sr. No. Course Content 1.0 Fault Current Calculations 1.1 Introduction to per unit and percentage impedance 1.2

More information

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

thepower to protect  the power to protect i-gard LITERATURE Low and medium voltage thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering) R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP Kiran V. Natkar 1, Naveen Kumar 2 1 Student, M.E., Electrical Power System, MSS CET/ Dr. B.A.M. University, (India) 2 Electrical Power System,

More information

Optimal neutral ground resistor rating of the medium voltage systems in power generating stations

Optimal neutral ground resistor rating of the medium voltage systems in power generating stations Journal of International Council on Electrical Engineering ISSN: (Print) 2234-8972 (Online) Journal homepage: http://www.tandfonline.com/loi/tjee20 Optimal neutral ground resistor rating of the medium

More information

Impedance protection on power transformer.

Impedance protection on power transformer. Impedance protection on power transformer www.siemens.com/siprotec5 SIPROTEC 5 Application Impedance Protection on Power Transformer APN-045, Edition 1 Content 1...3 1.1 Introduction...3 1.2 Application

More information

एस.आर.प.स 40व प र ट क शनउप सम त क ब ठकक मऱएएज ड Additional Agenda Points for 40 th meeting of Protection Sub-Committee of SRPC

एस.आर.प.स 40व प र ट क शनउप सम त क ब ठकक मऱएएज ड Additional Agenda Points for 40 th meeting of Protection Sub-Committee of SRPC ANNEXURE I एस.आर.प.स 40व प र ट क शनउप सम त क ब ठकक मऱएएज ड Additional Agenda Points for 40 th meeting of Protection Sub-Committee of SRPC 1. ग र डडडस टबबन स / ग र डइन सडन टक वववरण - Details of Grid incidents:

More information

Connection Impact Assessment Application Form

Connection Impact Assessment Application Form Connection Impact Assessment Application Form This Application Form is for Generators applying for a Connection Impact Assessment (CIA). In certain circumstances, London Hydro may require additional information

More information

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Expo - Nov. 3, 2014 Index Normal Distribution System

More information

Substation Testing and Commissioning: Power Transformer Through Fault Test

Substation Testing and Commissioning: Power Transformer Through Fault Test 1 Substation Testing and Commissioning: Power Transformer Through Fault Test M. Talebi, Member, IEEE, Power Grid Engineering Y. Unludag Electric Power System Abstract This paper reviews the advantage of

More information

Upgrading Your Electrical Distribution System To Resistance Grounding

Upgrading Your Electrical Distribution System To Resistance Grounding Upgrading Your Electrical Distribution System To Resistance Grounding The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding

More information

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected

More information

EASUN REYROLLE LIMITED

EASUN REYROLLE LIMITED OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT

More information

Transformer Fault Categories

Transformer Fault Categories Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations A.R. Sultan, M.W. Mustafa, M.Saini Faculty of Electrical Engineering Universiti Teknologi Malaysia (UTM)

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Southern Company Interconnection Requirements for Inverter-Based Generation

Southern Company Interconnection Requirements for Inverter-Based Generation Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection

More information

MV network design & devices selection EXERCISE BOOK

MV network design & devices selection EXERCISE BOOK MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester

More information

Notes 1: Introduction to Distribution Systems

Notes 1: Introduction to Distribution Systems Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission

More information

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device ABB AG - EPDS The worldʼs fastest limiting and switching device Agenda The world s fastest limiting and switching device Customers Function: Insert-holder with insert Comparison: I S -limiter Circuit-breaker

More information

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson... TECHNICAL REPORT APPLICATION GUIDE TITLE: Current Transformer Requirements for VA TECH Reyrolle ACP Relays PREPARED BY:- A Allen... APPROVED :- B Watson... REPORT NO:- 990/TIR/005/02 DATE :- 24 Jan 2000

More information

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority S. Songsiri * and S. Sirisumrannukul Abstract This paper presents an application

More information

Babak Enayati National Grid Thursday, April 17

Babak Enayati National Grid Thursday, April 17 2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April

More information

Ground Fault Detection using Zigzag Grounding Transformer in Ungrounded System

Ground Fault Detection using Zigzag Grounding Transformer in Ungrounded System Ground Fault Detection using Zigzag Grounding Transformer in Ungrounded System Dhruvita Mandaliya 1, Ajay M. Patel 2, Tarang Thakkar 3 1 PG Student, Electrical Engineering Department, Birla Vishvakarma

More information

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE Professor Akhtar Kalam Victoria University The Problem Calculate & sketch the ZPS, NPS & PPS impedance networks. Calculate feeder faults. Calculate

More information

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding

More information

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone

More information

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example

More information

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS Juan Manuel Gers, PhD Example - Single Line Example 1 - Data Calculate the following: 1. The three phase short circuit levels on busbars

More information

Grounding System Theory and Practice

Grounding System Theory and Practice Grounding System Theory and Practice Course No. E-3046 Credit: 3 PDH Grounding System Theory and Practice Velimir Lackovic, Electrical Engineer System grounding has been used since electrical power systems

More information

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8] Code No: RR320205 Set No. 1 1. (a) Explain about Bewley s Lattice diagrams and also mention the uses of these diagrams. [6+2] (b) A line of surge impedance of 400 ohms is charged from a battery of constant

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

A Study on Ferroresonance Mitigation Techniques for Power Transformer

A Study on Ferroresonance Mitigation Techniques for Power Transformer A Study on Ferroresonance Mitigation Techniques for Power Transformer S. I. Kim, B. C. Sung, S. N. Kim, Y. C. Choi, H. J. Kim Abstract--This paper presents a comprehensive study on the ferroresonance mitigation

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

2 Grounding of power supply system neutral

2 Grounding of power supply system neutral 2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the

More information

Single Line Diagram of Substations

Single Line Diagram of Substations Single Line Diagram of Substations Substations Electric power is produced at the power generating stations, which are generally located far away from the load centers. High voltage transmission lines are

More information

Problems connected with Commissioning of Power Transformers

Problems connected with Commissioning of Power Transformers Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.

More information

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

Catastrophic Relay Misoperations and Successful Relay Operation

Catastrophic Relay Misoperations and Successful Relay Operation Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application

Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application General Application Information Remotes Case 2&3 Form REINDEER Cases 2&3 -Connection Impact Assessment (CIA) Application Hydro One Remote Communities Inc. Lori.Rice@hydroone.com 1-807-474-2828 This Application

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods

Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods Proceedings of the th WSEAS International Conference on Power Systems, Beijing, China, September -, 200 Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing

More information

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945

More information

DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS

DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS Abdelrahman AKILA Ahmed HELAL Hussien ELDESOUKI SDEDCO Egypt AASTMT Egypt AASTMT Egypt Abdurrahman.akela@gmail.com ahmedanas@aast.edu hdesouki@aast.edu

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Transformer Protection

Transformer Protection Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary

More information

International Journal of Advance Engineering and Research Development ANALYSIS OF INTERNAL AND EXTERNAL FAULT FOR STAR DELTA TRANSFORMER USING PSCAD

International Journal of Advance Engineering and Research Development ANALYSIS OF INTERNAL AND EXTERNAL FAULT FOR STAR DELTA TRANSFORMER USING PSCAD Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 6, June -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 ANALYSIS OF

More information

International Journal of Advance Engineering and Research Development. Short-circuit analysis of Industrial plant

International Journal of Advance Engineering and Research Development. Short-circuit analysis of Industrial plant Scientific Journal of Impact Factor (SJIF): 5.71 International Journal of Advance Engineering and Research Development Volume 5, Issue 03, March -2018 Short-circuit analysis of Industrial plant Ashokkumar

More information

Unit 2. Single Line Diagram of Substations

Unit 2. Single Line Diagram of Substations Unit 2 Single Line Diagram of Substations Substations Electric power is produced at the power generating stations, which are generally located far away from the load centers. High voltage transmission

More information

Solution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection

Solution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection ABSTRACT National conference on Engineering Innovations and Solutions (NCEIS 2018) International Journal of Scientific Research in Computer Science, Engineering and Information Technology 2018 IJSRCSEIT

More information

Table of Contents. Introduction... 1

Table of Contents. Introduction... 1 Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:

More information

Short Circuit Current and Voltage Stability Analysis of a Realistic Generation System Using Fault Current Limiter and SVC

Short Circuit Current and Voltage Stability Analysis of a Realistic Generation System Using Fault Current Limiter and SVC Short Circuit Current and Voltage Stability Analysis of a Realistic Generation System Using Fault Current Limiter and SVC 1 Ezz Badry, 1 Salah Kamel, 1 Loai S.Nasrat, 1,2 Ziad M. Ali 1 Department of Electrical

More information

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series

More information

XD1-T - Transformer differential protection relay

XD1-T - Transformer differential protection relay XD1-T - Transformer differential protection relay Contents 1. Application and features 2. Design 3. Characteristics 3.1 Operating principle of the differential protection 3.2 Balancing of phases and current

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

Transmission System Phase Backup Protection

Transmission System Phase Backup Protection Reliability Guideline Transmission System Phase Backup Protection NERC System Protection and Control Subcommittee Draft for Planning Committee Approval June 2011 Table of Contents 1. Introduction and Need

More information

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd 2C73 Setting Guide High Impedance Differential Relay relay monitoring systems pty ltd Advanced Protection Devices 1. INTRODUCTION This document provides guidelines for the performance calculations required

More information

Testing Numerical Transformer Differential Relays

Testing Numerical Transformer Differential Relays Feature Testing Numerical Transformer Differential Relays Steve Turner Beckwith Electric Co., nc. ntroduction Numerical transformer differential relays require careful consideration as to how to test properly.

More information

EE402-Protection and Switchgear Dept. of EEE

EE402-Protection and Switchgear Dept. of EEE UNIT II - ELECTROMAGNETIC RELAYS Part A 1. Name the different kinds of over current relays. Induction type non-directional over current relay, Induction type directional over current relay & current differential

More information

Differential Protection with REF 542plus Feeder Terminal

Differential Protection with REF 542plus Feeder Terminal Differential Protection with REF 542plus Application and Setting Guide kansikuva_bw 1MRS 756281 Issued: 09.01.2007 Version: A Differential Protection with REF 542plus Application and Setting Guide Contents:

More information

ELE-CMOS-E-2001 Electrical Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS

ELE-CMOS-E-2001 Electrical Engineer PERSONAL DATA EDUCATION LANGUAGES COMPUTER SKILLS TRAINING COURSES AND CERTIFICATIONS 101135-ELE-CMOS-E-2001 Electrical Engineer Holds a B. Sc. in Electrical Power & Machines Engineering and has over 14 years hands-on experience, including 13 years working in operation, maintenance, construction

More information

Unit Protection Differential Relays

Unit Protection Differential Relays Unit Protection PROF. SHAHRAM MONTASER KOUHSARI Current, pu Current, pu Protection Relays - BASICS Note on CT polarity dots Through-current: must not operate Internal fault: must operate The CT currents

More information

EE 741 Spring Electric Power Distribution Systems An Overview

EE 741 Spring Electric Power Distribution Systems An Overview EE 741 Spring 2017 Electric Power Distribution Systems An Overview Basic Power System Layout There are over 100 substations in the Las Vegas Valley pic of closest substation Substation Design Substation

More information

Relion 605 series. Self-Powered Feeder Protection REJ603 Application manual

Relion 605 series. Self-Powered Feeder Protection REJ603 Application manual Relion 605 series Relion 605 series Relion 605 series Self-Powered Feeder Protection REJ603 Application manual Document ID: 1MDU07206-YN 6 2 4 This document and parts thereof must not be reproduced or

More information

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. The Importance of the Neutral-Grounding Resistor Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. Presentation Preview What is high-resistance grounding (HRG)? What is the purpose of HRG? Why

More information

Hamdy Faramawy Senior Application Specialist ABB Sweden

Hamdy Faramawy Senior Application Specialist ABB Sweden Design, Engineering and Application of New Firm Capacity Control System (FCCS) Mohammed Y. Tageldin, MSc. MIET Senior Protection Systems Engineer ABB United Kingdom mohammed.tageldin@gb.abb.com Hamdy Faramawy

More information

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES U AJMAL, GE Grid Solutions UK Ltd, usman.ajmal@ge.com S SUBRAMANIAN, GE Grid Solutions UK Ltd, sankara.subramanian@ge.com H Ha GE Grid Solutions

More information

Safety through proper system Grounding and Ground Fault Protection

Safety through proper system Grounding and Ground Fault Protection Safety through proper system Grounding and Ground Fault Protection November 4 th, 2015 Presenter: Mr. John Nelson, PE, FIEEE, NEI Electric Power Engineering, Inc. Event to start shortly Scheduled time:

More information

Line Protection Roy Moxley Siemens USA

Line Protection Roy Moxley Siemens USA Line Protection Roy Moxley Siemens USA Unrestricted Siemens AG 2017 siemens.com/digitalgrid What is a Railroad s Biggest Asset? Rolling Stock Share-holders Relationships Shipping Contracts Employees (Engineers)

More information

XD1-T Transformer differential protection relay. Manual XD1-T (Revision A)

XD1-T Transformer differential protection relay. Manual XD1-T (Revision A) XD1-T Transformer differential protection relay Manual XD1-T (Revision A) Woodward Manual XD1-T GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design IEEE PES Transmission and Distribution Conference 2008 Panel Session Large Wind Plant Collector Design Wind Farm Collector System Grounding by Steven W. Saylors, P.E. Chief Electrical Engineer Vestas Americas

More information

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 6545(Print), ISSN 0976 6545(Print) ISSN 0976 6553(Online)

More information

Type VAEM 22 Negative Potential Biasing Relay

Type VAEM 22 Negative Potential Biasing Relay Type VAEM 22 Negative Potential Biasing Relay Type VAEM 22 Negative Potential Biasing Relay VAEM 22 Relay withdrawn from case Features l Simple and robust construction l High sensitivity Application The

More information

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd. Functional Range - Earth Fault Relay C&S Protection & Control Ltd. 2 Contents Page No. 1. Application 2. Operating Principle. Current Transformer Connections 5. Connections, Contact Arrangement and Setting

More information

Class 300 Equipment CBS 305, 320 Current Boost Systems FEATURES. DESCRIPTION Page 2. SPECIFICATIONS Pages 2 through 4.

Class 300 Equipment CBS 305, 320 Current Boost Systems FEATURES. DESCRIPTION Page 2. SPECIFICATIONS Pages 2 through 4. Class 300 Equipment CBS 305, 320 Current Boost Systems CBS 320 Current Transformer CBS 305 The CBS 305 and CBS 320 Current Boost Systems are electronic devices designed to provide the Basler APR series

More information

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics EE589-Power System Quality & Harmonics Electrical Engineering Department School of Engineering University of Jordan 1 Control of Harmonics

More information

UNIVERSITY OF SWAZILAND

UNIVERSITY OF SWAZILAND UNVERSTY OF SWAZLAND SUPPLEMENTARY EXAMNATON, SECOND SEMESTER MAY 2017 FACULTY OF SCENCE AND ENGNEERNG DEPARTMENT OF ELECTRCAL AND ELECTRONC ENGNEERNG TTLE OF PAPER: Switchgear and Protection COURSE CODE

More information

Transmission Interconnection Requirements for Inverter-Based Generation

Transmission Interconnection Requirements for Inverter-Based Generation Transmission Requirements for Inverter-Based Generation June 25, 2018 Page 1 Overview: Every generator interconnecting to the transmission system must adhere to all applicable Federal and State jurisdictional

More information

Line protection with transformer in the protection zone

Line protection with transformer in the protection zone Line protection with transformer in the protection zone www.siemens.com/siprotec5 Three-end line protection with transformer in the protection range SIPROTEC 5 Application Three-end line protection with

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

Overcurrent Elements

Overcurrent Elements Exercise Objectives Hands-On Relay Testing Session Overcurrent Elements After completing this exercise, you should be able to do the following: Identify overcurrent element settings. Determine effective

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Initial Application Form for Connection of Distributed Generation (>10kW)

Initial Application Form for Connection of Distributed Generation (>10kW) Please complete the following information and forward to Vector Contact Details Primary Contact (who we should contact for additional information) Contact person Company name Contact numbers Daytime: Cell

More information

9 Overcurrent Protection for Phase and Earth Faults

9 Overcurrent Protection for Phase and Earth Faults Overcurrent Protection for Phase and Earth Faults Introduction 9. Co-ordination procedure 9.2 Principles of time/current grading 9.3 Standard I.D.M.T. overcurrent relays 9.4 Combined I.D.M.T. and high

More information

SCHEME OF COURSE WORK ( ) Electrical & Electronics Engineering. Electrical machines-i, II and power transmission engineering

SCHEME OF COURSE WORK ( ) Electrical & Electronics Engineering. Electrical machines-i, II and power transmission engineering SCHEME OF COURSE WORK (2015-2016) COURSE DETAILS: Course Title Course Code Program Branch Semester Prerequisites Course to which it is prerequisite Switchgear and Protection 15EE1116 B.Tech Electrical

More information

Back to the Basics Current Transformer (CT) Testing

Back to the Basics Current Transformer (CT) Testing Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of

More information

A1-101 INFLUENCE OF SPECIAL SHORT CIRCUIT ON ELECTRICAL GENERATOR DESIGN. Ding Zhong MENG (HONG KONG, CHINA)

A1-101 INFLUENCE OF SPECIAL SHORT CIRCUIT ON ELECTRICAL GENERATOR DESIGN. Ding Zhong MENG (HONG KONG, CHINA) 1, rue d'artois, F-758 Paris http://www.cigre.org A1-11 Session 4 CIGRÉ INFLUENCE OF SPECIAL SHORT CIRCUIT ON ELECTRICAL GENERATOR DESIGN Ding Zhong MENG (HONG KONG, CHINA) SUMMARY Refer to the IEC Standard

More information

7SG14 Duobias-M Transformer Protection

7SG14 Duobias-M Transformer Protection 7SG14 Duobias-M Transformer Protection Document Release History This document is issue 2010/02. The list of revisions up to and including this issue is: Pre release Revision Date Change 2010/02 Document

More information

Our Brands. Where we are?

Our Brands. Where we are? CATALOG 2019 Our Brands Aktif trade mark for Measuring, Protection, Automatic Meter Reading, Billing and Energy Management Software. by Aktif Aktif trade mark for Measuring, Protection, Control and Power

More information

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS DFFERENTAL PROTECTON METHODOLOGY FOR ARBTRARY THREE-PHASE POWER TRANSFORMERS Z. Gaji ABB AB-SA Products, Sweden; zoran.gajic@se.abb.com Keywords: power transformer, phase shifting transformer, converter

More information