POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics
|
|
- Edith McKinney
- 5 years ago
- Views:
Transcription
1 POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics EE589-Power System Quality & Harmonics Electrical Engineering Department School of Engineering University of Jordan 1
2 Control of Harmonics Two common causes of harmonic problems Nonlinear loads injecting excessive harmonic currents Interaction between harmonic currents and the system frequency. 2
3 Principles for Controlling Harmonics When a problem occurs, the basic options for controlling harmonics are: 1. Reduce the harmonic currents produced by the load. 2. Add filters to either siphon the harmonic currents off the system, block the currents from entering the system, or supply the harmonic currents locally. 3. Modify the frequency response of the system by filters, inductors, or capacitors. 3
4 1. Reducing harmonic Currents in Loads 1. Adding a line reactor or transformer in series will significantly reduce harmonics, as well as provide transient protection benefits. 2. Transformer connections can be employed to reduce harmonic currents in three-phase systems. I. Phase-shifting half of the 6-pulse power converters in a plant load by 30 o can approximate the benefits of 12-pulse loads by dramatically reducing the fifth and seventh harmonics. II. III. Delta-connected transformers can block the flow of zerosequence harmonics (typically triplens) from the line. Zigzag and grounding transformers can shunt the triplens off the line. 4
5 Three-Phase Transformer Connection Zig-zag transformer application as third harmonic filter. Cancellation of fifth and seventh harmonic currents by using 30 phaseshifted transformer connections. 12-Pulse Converter 5
6 2. Filtering 1. The shunt filter works by short-circuiting harmonic currents as close to the source of distortion as practical. I. This keeps the currents out of the supply system. II. The most common type of filtering applied because of economics and because it also tends to correct the load power factor as well as remove the harmonic current. 2. Another approach is to apply a series filter that blocks the harmonic currents. I. This is a parallel-tuned circuit that offers a high impedance to the harmonic current. 3. Active filters work by electronically supplying the harmonic component of the current into a nonlinear load. 6
7 Harmonics Filters Shunt Passive Filter Series Passive Filter Active Filter 7
8 3. Modifying the System Frequency Response There are a number of methods to modify adverse system responses to harmonics: Adding or removing capacitor banks Changing the size of the capacitor banks Adding shunt filters Adding reactors to detune the system away from harmful resonance 8
9 3. Modifying the System Frequency Response 1. Add a shunt filter. Not only does this shunt a troublesome harmonic current off the system, but it completely changes the system response, most often, but not always, for the better. 2. Add a reactor to detune the system. Harmful resonances generally occur between the system inductance and shunt power factor correction capacitors. I. The reactor must be added between the capacitor and the supply system source. II. Add reactor in series with the capacitor to move the system resonance without actually tuning the capacitor to create a filter. h r X reactor X c X source 9
10 3. Modifying the System Frequency Response 3. Change the capacitor size. This is often one of the least expensive options for both utilities and industrial customers. h r MVA Q C sc X X c SC 4. Move a capacitor to a point on the system with a different short-circuit impedance or higher losses. 5. Remove the capacitor and simply accept the higher losses, lower voltage, and power factor penalty. If technically feasible, this is occasionally the best economic choice. 10
11 Where to Control Harmonics? The strategies for mitigating harmonic distortion problems differ somewhat by location. The following techniques are ways for controlling harmonic distortion on both the I. Utility distribution feeder II. End- user power system 11
12 Solution On Utility Distribution Feeders The X/R ratio of a utility distribution feeder is generally low. Therefore, the magnification of harmonics by resonance with feeder banks is usually minor in comparison to what might be found inside an industrial facility. Utility distribution engineers are accustomed to placing feeder banks where they are needed without concern about harmonics. However, voltage distortion from the resonance of feeder banks may exceed limits in a few cases and require mitigation. When problems do occur, the usual strategy is to first attempt a solution by moving the offending bank or changing the capacitor size or neutral connection. 12
13 Solution On Utility Distribution Feeders Some harmonic problems associated with feeder capacitor banks are due to increasing the triplen harmonics in the neutral circuit of the feeder. To change the flow of zero-sequence harmonic currents, changes are made to the neutral connection of Y-connected banks. To block the flow, the neutral is allowed to float (Ungrounded). In other cases, it is more advantageous to aid the flow by putting a reactor in the neutral to convert the bank into a tuned resonant shunt for a zero-sequence harmonic. 13
14 Solution On Utility Distribution Feeders Harmonic problems on distribution feeders often exist only at light load. The voltage rises, causing the distribution transformers to produce more harmonic currents and there is less load to damp out resonance. Switching the capacitors off at this time frequently solves the problem. 14
15 Solution In end-user Facilities When harmonic problems arise in an end-user facility, the first step is to determine if the main cause is resonance with power factor capacitors in the facility. When it is, first attempt a simple solution by using a different capacitor size. With automatic power factor controllers, it may be possible to select a control scheme that avoids the configuration that causes problems. In other cases, there will be so many capacitors switched at random with loads that it will be impossible to avoid resonant conditions. Filtering will be necessary. 15
16 Solution In end-user Facilities Installation of filters on end-user low-voltage systems is generally more practical and economical than on utility distribution systems. The criteria for filter installation are more easily met, and filtering equipment is more readily available on the market. When the magnitude of harmonic currents injected by loads is excessive, industrial users should also investigate means of reducing harmonics by using different transformer connections and line chokes. In office buildings, zigzag transformers and triplen harmonic filters can reduce the impact of triplen harmonic currents on neutral circuits. 16
17 Solution In end-user Facilities Installation of filters on end-user low-voltage systems is generally more practical and economical than on utility distribution systems. The criteria for filter installation are more easily met, and filtering equipment is more readily available on the market. When the magnitude of harmonic currents injected by loads is excessive, industrial users should also investigate means of reducing harmonics by using different transformer connections and line chokes. In office buildings, zigzag transformers and triplen harmonic filters can reduce the impact of triplen harmonic currents on neutral circuits. 17
18 In-line Reactors or Chokes A simple, but often successful, method to control harmonic distortion generated by adjustable-speed drives involves a relatively small reactor, or choke, inserted at the line input side of the drive. This is particularly effective for PWM-type drives. A typical 3% input choke can reduce the harmonic current distortion for a PWM-type drive from approximately 80% to 40% percent. The choke size is computed on the drive kva base. Isolation transformers can provide the same benefit as a choke but may be more costly. However, isolation transformers with multiple drives offer the advantage of creating effective 12-pulse operation. 18
19 In-line Reactors or Chokes A typical 3% input choke can reduce the harmonic current distortion for a PWM-type drive from approximately 80% to 40% percent. Typical line chokes used in 480-V ASD applications 19
20 In-line Reactors or Chokes Comparison between the effectiveness of a 3% choke in reducing harmonic current distortion to the condition without a choke for various ASD sizes (ASD sizes are normalized to the service transformer kva). The larger waveform is without the choke. A substantial improvement is achieved by inserting a choke in the ASD line. 20
21 12-Pulse Configuration A 12-pulse configuration can be achieved by supplying one drive through a -Y connected transformer, and another drive through a - connected transformer. Current waveforms for two separate six-pulse ASDs. 21
22 12-Pulse Configuration When the two waveforms are added together on the primary, the resulting waveform injected onto the utility system has much lower distortion, primarily because the fifth and seventh harmonics are cancelled out. These two harmonics are responsible for most of the distortion for six-pulse drives. 22
23 Zigzag Transformers Zigzag transformers are often applied in commercial facilities to control zero-sequence harmonic components. A zigzag transformer acts like a filter to the zero-sequence current by offering a low-impedance path to neutral. This reduces the amount of current that flows in the neutral back toward the supply by providing a shorter path for the current. To be effective, the transformer must be located near the load on the circuit that is being protected drives. 23
24 Zigzag Transformers The two most important problems in commercial facilities are overloaded neutral conductors and transformer heating. Both of these problems can be solved with proper zigzag transformer placement. Some new commercial buildings include zigzag transformers on the 480/208- V supply transformer secondaries to prevent transformer overheating. 24
25 Zigzag Transformers Typical results with a zigzag transformer show that it can shunt about 50% of the 3 rd -harmonic current away from the main circuit neutral conductors. Thus, the zigzag transformer can almost always reduce neutral currents due to zero-sequence harmonics to acceptable levels. The largest zero-sequence harmonic will nearly always be the third harmonic in office buildings with many computers and related equipment. X=5% V V L H = kv = 480V ~ i(t) 1 A 500 PCs 25
BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP
The BEST Group THE BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP -Winter Lecture Series HARMONICS Presented by: Syed Khundmir T Department of Electrical Engineering University at Buffalo khundmir@buffalo.edu
More informationPrinciples for Controlling Harmonics
Principles for Controlling Harmonics Harmonic distortion is present to some degree on all power systems. Fundamentally, one needs to control harmonics only when they become a problem. There are three common
More informationDo Capacitor Switching Transients Still Cause Problems?
Do Capacitor Switching Transients Still Cause Problems? Mark McGranaghan We have been evaluating problems related to capacitor switching transients for many years. Capacitor banks have been used on distribution
More informationHarmonic control devices
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 24 1 Today Harmonic control devices In-line reactors (chokes)
More informationHarmonic Distortion Evaluations
Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion
More informationHarmonic control devices. ECE 528 Understanding Power Quality
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)
More informationEffects of Harmonic Distortion I
Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,
More information22.0 Harmonics in Industrial Power Systems
1.0 Harmonics in Industrial Power Systems Harmonic frequencies are multiples of the line (fundamental) frequency, which in North America is usually 60 Hz, while it is 50 Hz elsewhere. Figure 1 shows a
More informationUnderstanding Input Harmonics and Techniques to Mitigate Them
Understanding Input Harmonics and Techniques to Mitigate Them Mahesh M. Swamy Yaskawa Electric America YASKAWA Page. 1 Organization Introduction Why FDs Generate Harmonics? Harmonic Limit Calculations
More informationMulti-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7
White Paper Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 Dr. Jun-koo Kang, Yaskawa Electric America Doc#: WP.AFD.02 Copyright Yaskawa Electric America,
More informationAnalysis of Hybrid Power Conditioner in Three-Phase Four-Wire Distribution Power Systems for Suppressing Harmonics and Neutral-Line Current
Analysis of Hybrid Power Conditioner in Three-Phase Four-Wire Distribution Power Systems for Suppressing Harmonics and Neutral-Line Current B. Pedaiah 1, B. Parameshwar Reddy 2 M.Tech Student, Dept of
More informationARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services
ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services edarat group INTRODUCTION Harmonics are a mathematical way of describing distortion
More informationHarmonic Power. A VFDs.com Whitepaper Written by Ernesto Jimenez
Harmonic Power A VFDs.com Whitepaper Written by Ernesto Jimenez Table of Contents 1. Need for Clean Electricity 2. What Are Harmonics? 3. Lower Order Harmonics 4. Causes of Harmonics 5. Effects of Harmonics
More informationHarmonic Distortion Effects and Mitigation in Distribution Systems
Journal of American Science 00;6(0) Harmonic Distortion Effects and Mitigation in Distribution Systems Hussein A. Attia, M. El-Metwally and Osama M. Fahmy Cairo University, Faculty of Engineering, Electrical
More informationEconomical Solutions to Meet Harmonic Distortion Limits[4]
Economical Solutions to Meet Harmonic Distortion Limits[4] Abstract: The widespread adoption of variable frequency drive technology is allowing electricity to be utilized more efficiently throughout most
More informationHarmonic Mitigation for Variable Frequency Drives. HWEA Conference February 15, Kelvin J. Hurdle Rockwell Bus. Dev. Mgr.
Harmonic Mitigation for Variable Frequency Drives HWEA Conference February 15, 2011 Kelvin J. Hurdle Rockwell Bus. Dev. Mgr. 1 OVERVIEW Linear vs. Non- Linear Load Definitions AC Drive Input Current Harmonics
More informationHARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N
HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N Harmonic Basics 3 rd Harmonic Fundamental 5 t1h Harmonic 7 th Harmonic Harmonic
More informationElectromagnetic Harmonic Filters Technical Guide
Eliminator Series Electromagnetic Harmonic Filters Technical Guide Neutral Eliminator TM (NCE TM ) Parallel connected, 3-phase, 4-wire passive electromagnetic device that diverts 3rd and other triplen
More informationHarmonic Filters for Single Phase Equipment
POWER QUALITY Harmonic Filters for Single Phase Equipment Agriculture Call Centers Casino Slot Machines Computer Centers Distributed Generation Electronic Power Converter Oil & Gas On-Line UPS Power Electronics
More informationAN EQUIVALENT CIRCUIT MODEL FOR A THREE PHASE HARMONIC MITIGATING TRANSFORMER
AN EQUIVALENT CIRCUIT MODEL FOR A THREE PHASE HARMONIC MITIGATING TRANSFORMER Riccardo Eric Maggioli A dissertation submitted to the Faculty of Engineering and the Built Environment, University of the
More informationHarmonic Analysis and Its Mitigation Using Different Passive Filters
Harmonic Analysis and Its Mitigation Using Different Passive Filters Ashlin Gloria Reginald 1, K J Thomas 2 1 PG Scholar, Amal Jyothi College of Engineering, Kanjirapally Kottayam, India ashlingloriar@gmail.com
More informationGuide to Harmonics. Reactive Power and Harmonic Compensation POWER QUALITY. The Basics of Harmonics
Reactive Power and Harmonic Compensation Guide to Harmonics POWER QUALITY The Basics of Harmonics All business types, commercial, industrial, government and energy/utility have a concern with power quality.
More information2 Grounding of power supply system neutral
2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the
More informationNJWA - Harmonics and Drives Proper System Design
Session Goals Larry Stanley, Sr. Regional Business Development Engineer, Water Segment Matthew LaRue, ABB Drives Product Manager Philadelphia District, Baldor of Philadelphia NJWA - Harmonics and Drives
More informationPQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.
General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand
More informationCompensation of Reactive Power Case Study
15 Compensation of Reactive Power Case Study Stefan Fassbinder and Alan Ascolari C15.1 FLUORESCENT LAMP Fluorescent lamps are the only common device where putting the most efficient way of compensation,
More informationPower Quality and Power Factor Correction
Power Quality and Power Factor Correction Introduction Since most loads in modern electrical distribution systems are inductive, there is an ongoing interest in improving power factor. The low power factor
More informationHarmonic Solutions in Electrical Systems. Raed Odeh Application Specialist - Power Quality & Electrical Distribution
Harmonic Solutions in Electrical Systems Raed Odeh Application Specialist - Power Quality & Electrical Distribution Agenda I. Harmonic Basics II.Harmonic Mitigation Solutions III.Case Study 2 Harmonic
More informationEvaluation of Harmonic Suppression Devices
Evaluation of Harmonic Suppression Devices Leon M. Tolbert, Member, IEEE Harold D. Hollis and Peyton S. Hale, Jr. Oak Ridge National Laboratory* U.S. Army Center for Public Works, CECPW-K P.O. Box 28,
More informationTECHNICAL BULLETIN 004a Ferroresonance
May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques
More informationHarmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE Solutions
Harmonic Filters for Power Conversion Equipment (Drives, rectifiers, etc) Effects of Harmonics IEEE - 519 Solutions Harmonics Tutorial 1 Power Conversion Equipment can save energy and control motors, heaters,
More informationHARMONIC MITIGATIONCASE STUDY
HARMONIC MITIGATIONCASE STUDY CNCE AND NCE INSTALLATION AT BROADCASTING STUDIO Concerned about video noise detected on some of its studio equipment, E! Entertainment Television (ETV), commissioned a study
More informationHarmonic Solutions. Clean Power Drive Solution to Harmonic Distortion
Harmonic Solutions Clean Power Drive Solution to Harmonic Distortion UTILITY GRID UTILITY SWITCH YARD IN THE FACILITY IEEE-519 POINT OF COMMON COUPLING POWER PLANT GENERATION TRANSMISSION MEDIUM VOLTAGE
More informationApplication of Reactive Compensation equipment in industrial systems under aspects of harmonics and switching transients: A study of real case
Application of Reactive Compensation equipment in industrial systems under aspects of harmonics and switching transients: A study of real case Patrick Roberto de Almeida BREE patrick.almeida@bree.com.br
More information7/15/2002 PP.AFD.08 1 of 28
Power Quality Considerations When Applying Adjustable Frequency Drives Explanations and Various Countermeasures 7/15/2002 PP.AFD.08 1 of 28 Power Quality Why the Renewed Interest in Power Quality? Copy
More informationTHE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY
by Cesar Chavez, Engineering Manager, Arteche / Inelap, and John Houdek, President, Allied Industrial Marketing, Inc. Abstract: Industrial facility harmonic distortion problems can surface in many different
More informationHarmonics White Paper
Harmonics White Paper New Breakthrough In PWM Drives Technology Reduces Input Line Harmonics Without the Use of Filtering Devices Harmonic Distortion Damages Equipment and Creates a Host of Other Problems
More information2.10. Adjustable Frequency Drives. Clean Power Drives. Clean Power Drives
.0 Volume 6 Solid-State Control CA0800007E March 05 www.eaton.com V6-T-47 .0 Adjustable Frequency Drives Overview What Are Harmonics? Take a perfect wave with a fundamental frequency of 60 Hz, which is
More informationE S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --
D.,.,.,. E S C R I P T I V E B U L L E T I N Bulletin DB-106 Square D Company October, 1990 ---1 I SQU ARED COMPANY -- Electrical Power Distribution System - The Heart of the Business From small commercial
More informationPOWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC
CITY OF LETHBRIDGE ELECTRIC ENGINEERING STANDARDS POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS The City of Lethbridge acknowledges the use of other utility industry and industry committee
More informationThyristorised Automatic Power Factor
Thyristorised Automatic Power Factor Correction with 7% D Tune Harmonics Suppression (Reactor/Filtering) System Power quality? In the present Low voltage (LV) industrial distribution system the power factor
More informationAlternators Reactance for Nonlinear Loads
Alternators Reactance for Nonlinear Loads Allen Windhorn. P.E. 26 July, 2013 Introduction Widespread invocation of IEEE Std 519 on systems powered by generators, together with increased use of equipment
More informationCHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS
86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the
More informationInternational Journal of Advance Engineering and Research Development ANALYSIS AND MITIGATION OF HARMONICS IN MEDICAL FIELD
Scientific Journal of Impact (SJIF): 5.71 International Journal of Advance Engineering and Research Development Volume 5, Issue 04, April -2018 e-issn (O): 2348-4470 p-issn (P): 2348-6406 ANALYSIS AND
More informationLow Pass Harmonic Filters
Exclusive e-rated Provider PRODUCT SHEET HARMITIGATOR TM Low Pass Harmonic Filters A solution for electrical distribution systems that require stable, reliable power, characterized by unparalleled power
More informationHarmonic Filters and Reactors
Harmonic Filters and Reactors Harmonics are invisible but costly If one looks up the meaning of harmonics in any one of several technical dictionaries, it is normally defined as being A sinusoidal component
More informationp. 1 p. 6 p. 22 p. 46 p. 58
Comparing power factor and displacement power factor corrections based on IEEE Std. 18-2002 Harmonic problems produced from the use of adjustable speed drives in industrial plants : case study Theory for
More informationshunt (parallel series
Active filters Active filters are typically used with diode/thyristor rectifiers, electric arc furnaces, etc. Their use in electric power utilities, industry, office buildings, water supply utilities,
More informationImpact of Distributed Generation on Network Voltage Levels
EEE8052 Distributed Generation Taster Material Impact of Distributed Generation on Network Voltage Levels Steady-state rise in network voltage levels Existing practice is to control distribution voltage
More informationHarmonic Mitigating Transformer - Technical Guide
Harmonic Mitigating - Technical Guide HARMONY Series s HARMONY-1 www.mirusinternational.com Benefits: Prevent voltage flat-topping while reducing energy costs. Reduce voltage distortion caused by harmonic
More informationPerformance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System
Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System Engr.Kavitha Vasantha 1 Lecturer, BSIE, College of Engineering, Salmabad, Kingdom of Bahrain 1 Abstract: As end
More informationPerformance of Indirectly Controlled STATCOM with IEEE 30-bus System
Performance of Indirectly Controlled STATCOM with IEEE 30- System Jagdish Kumar Department of Electrical Engineering, PEC University of Technology, Chandigarh, India E-mail : jk_bishnoi@yahoo.com Abstract
More informationFluke 40/41 Power Harmonics Analysers
Data Pack A Issued March 2002 232-4752 Fluke 40/41 Power Harmonics Analysers This data sheet refers to the Fluke 40 and Fluke 41 Power Harmonics Analysers. RS stock no. Description 215-9621 Fluke 41B power
More informationSize Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM
Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM Dr. Jagdish Kumar, PEC University of Technology, Chandigarh Abstract the proper selection of values of energy storing
More informationPower Quality. Answering Today s Power Challenges. Why Your Existing Transformer May Be Inadequate. How Harmonics Affect Transformers
Power Quality 13 Answering Today s Power Challenges Jefferson Electric is continually updating its product line to remain on the forefront of transformer technology. Electrical harmonics have become a
More informationFERRORESONANCE SIMULATION STUDIES USING EMTP
FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in
More informationPOWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:
POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION
More informationR. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder
R. W. Erickson Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder 16.4. Power phasors in sinusoidal systems Apparent power is the product of the rms voltage and
More informationVARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY
VARIABLE FREQUENCY DRIVE OPERATION AND APPLICATION OF VARIABLE FREQUENCY DRIVE (VFD) TECHNOLOGY Carrier Corporation Syracuse, New York October 2005 TABLE OF CONTENTS INTRODUCTION... 2 Common VFD Terms
More informationPower Quality Notes 2-2 (AK)
Power Quality Notes 2-2 (AK) Marc Thompson, Ph.D. Senior Managing Engineer Exponent 21 Strathmore Road Natick, MA 01760 Alex Kusko, Sc.D, P.E. Vice President Exponent 21 Strathmore Road Natick, MA 01760
More informationMinimizing Input Filter Requirements In Military Power Supply Designs
Keywords Venable, frequency response analyzer, MIL-STD-461, input filter design, open loop gain, voltage feedback loop, AC-DC, transfer function, feedback control loop, maximize attenuation output, impedance,
More informationAlternator winding pitch and power system design
Our energy working for you. TM Power topic #5981 Technical information from Cummins Power Generation Alternator winding pitch and power system design White Paper Rich Scoggins Applications Engineering
More informationthepower to protect the power to protect i-gard LITERATURE Low and medium voltage
thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors
More informationEffective Harmonic Mitigation with Active Filters
Advancing Power Quality White Paper Effective Harmonic Mitigation with Active Filters Written by: Ian Wallace Variable Speed Drive with no Harmonic Mitigation Industry standard variable speed drives, with
More informationNew power tools provide quality and efficiency By
Typical Delta-wye transformer New power tools provide quality and efficiency By Steve Terry For quite some time, it has been well understood that phase-control SCR dimming systems used in the entertainment
More informationPQ01. Harmonic Solutions for VFD s. Review of Power Control Harmonics, Power Factor, Distortion & Displacement
PQ01 Harmonic Solutions for VFD s Review of Power Control Harmonics, Power Factor, Distortion & Displacement Related Content at the Expo PQ02 Power Quality and Monitoring.. PQ03 Using Test Eqipment to
More informationMitigation of Harmonics and Interharmonics in VSI-Fed Adjustable Speed Drives
Mitigation of Harmonics and Interharmonics in VSI-Fed Adjustable Speed Drives D.Uma 1, K.Vijayarekha 2 1 School of EEE, SASTRA University Thanjavur, India 1 umavijay@eee.sastra.edu 2 Associate Dean/EEE
More informationMitigation of Harmonics Produced by Nonlinear Loads in Industrial Power System
Mitigation of Harmonics Produced by Nonlinear Loads in Industrial Power System Muhammad Abid 1, Tehzeeb-ul-Hassan 2, Tehseen Ilahi 3 1 National University of Computer and Emerging Sciences, Lahore, Pakistan;
More informationUnderstanding Harmonic Suppression Systems
Slot Tech Feature Article Understanding Harmonic Suppression Systems Get a Handle on Wasted Energy and Excess Heat A typical casino will have thousands of switched-mode power supplies on-line, twenty-four
More informationA New Control Method for Series Active Filter in Distribution System using Unit Vector Control
A New Control Method for Series Active Filter in Distribution System using Unit Vector Control T.Guna Sekar Assistant Professor Kongu Engineering College Erode-638052, India R. Anita, PhD. Professor &
More informationBhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)
ISSN: 2349-7637 (Online) RESEARCH HUB International Multidisciplinary Research Journal (RHIMRJ) Research Paper Available online at: www.rhimrj.com Modeling and Simulation of Distribution STATCOM Bhavin
More informationHarmonic Design Considerations for Wind Farms
Harmonic Design Considerations for Wind Farms To Ensure Grid Code Compliance Liam Breathnach Power System Studies Group ESB International Agenda Introduction Harmonic Theory and Concepts Grid Code Requirements
More informationLiterature Review for Shunt Active Power Filters
Chapter 2 Literature Review for Shunt Active Power Filters In this chapter, the in depth and extensive literature review of all the aspects related to current error space phasor based hysteresis controller
More informationComparison of Different Common Passive Filter Topologies for Harmonic Mitigation
UPEC21 31st Aug - 3rd Sept 21 Comparison of Different Common Passive Filter Topologies for Harmonic Mitigation H. M. Zubi IET and IEEE member hz224@bath.ac.uk R. W. Dunn IEEE member E-mail r.w.dunn@bath.ac.uk
More informationCHAPTER 4 HARMONICS AND POWER FACTOR
4.1 Harmonics CHAPTER 4 HARMONICS AND POWER FACTOR In this research a comparative study of practical aspects of mixed use of diode and Thyristor converter technologies in Aluminium Smelters has been carried
More informationHow adjustable speed drives affect power distribution
How adjustable speed drives affect power distribution Application Note Adjustable speed drives (ASDs) can be both a source and a victim of poor power quality. ASDs as victim loads Although ASDs are usually
More informationNew Methods to Mitigate Distribution System Harmonics
Alberta Power Industry Consortium 214 Power & Energy Innovation Forum New Methods to Mitigate Distribution System Harmonics By Wilsun Xu Power Disturbance & Signaling Research Lab November 5, 214 Outline
More informationHarmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits
WREF 01 Paper # 048 Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits Ketut Dartawan Ricardo Austria, Le Hui and Mark Suehiro* Pterra Consulting Maui Electric Company*
More informationHarmonics, its Mitigation & Result of Case study of Spinning Mill
International Journal of Innovative Research in Engineering & Management (IJIREM) ISSN: 2350-0557, Volume-2, Issue-4, July 2015, its Mitigation & of Case of Spinning Mill Yogesh Subhash Shimpi M. Tech
More informationUse only for doing work with or for BC Hydro. Complete Legal Acknowledgement is at
Reviewed: Sergey Kryuchkov Distribution Engineering Scott Merriman Distribution Standards Valentina Dabic Distribution Planning Warren Quan Distribution Operations, FVO Raj Solanki Distribution Engineering
More informationDesign and Simulation of Passive Filter
Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt
More informationAPPLICATION NOTE. Applying Type DD60 Capacitors in Harmonic Filter Applications. Total Power Factor PF = cosine ɸ
APPLICATION NOTE SEPTEMBER 12, 2017 F-AN-001 FRAKO North America W67N222 Evergreen Bvd Suite 209 Cedarburg, WI 53012 Phone: 1-262-618-2403 Fax: 1-262-618-2303 www.frako.de Applying Type DD60 Capacitors
More informationInternational Research Journal of Engineering and Technology (IRJET) e-issn: Volume: 02 Issue: 04 July p-issn:
HARMONICS REDUCTION Key Words: Harmonic analyzer, Power quality etc 1. INTRODUCTION Harmonics are the byproduct of modern electronic equipments which are non linear loads. In today s environment, all systems
More informationA PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits
CS 36 HOSP 14 36 Abstract A leading hospital in southern India faced chronic problems in terms of humming noise in capacitor bank, its failure, high temperature in transformer, and disturbances on the
More informationSummary of the Impacts of Grounding on System Protection
Summary of the Impacts of Grounding on System Protection Grounding System grounding big impact on ability to detect ground faults Common ground options:» Isolated ground (ungrounded)» High impedance ground»
More informationLong lasting transients in power filter circuits
Computer Applications in Electrical Engineering Vol. 12 2014 Long lasting transients in power filter circuits Jurij Warecki, Michał Gajdzica AGH University of Science and Technology 30-059 Kraków, Al.
More informationP2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company
P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Quality Power within your Reach P2 Power Magnetics P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. provides EMC and power quality solutions,
More informationElectrical Energy Saving and Economic Benefits from Power System Harmonics Mitigation in the Petrochemical Plants
Electrical Energy Saving and Economic Benefits from Power System Harmonics Mitigation in the Petrochemical Plants Sherif M. Ismael Electrical Engineering Division, Engineering for the Petroleum and Process
More informationAnalysis of Harmonic Distortion in Non-linear Loads
Analysis of Harmonic Distortion in Non-linear Loads Anne Ko Department of Electrical Power Engineering Mandalay Technological University, Mandalay, Myanmar.Phone:+95-09-2225761 anneko101082@gmail.com Wunna
More informationNon-Linear Load Transformers
Non-Linear Load Transformers Acme s Non-Linear Load and Harmonic Mitigating Transformers protect equipment on the line and prevent damage caused by harmonic currents. Many of today s electronic devices
More informationUnit 29 Three-Phase Transformers
Unit 29 Three-Phase Transformers Objectives: Discuss the construction of three-phase transformers. Discuss the formation of a three-phase transformer bank. Discuss primary and secondary connections. Objectives:
More informationZ-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION
Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION 1 Arsha.S.Chandran, 2 Priya Lenin 1 PG Scholar, 2 Assistant Professor 1 Electrical & Electronics Engineering 1 Mohandas College of Engineering
More informationSynchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement
Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement Amaljith M K, Senthil kumar R Abstract This paper presents a three-phase, four-wire, four-leg
More information1C.4.1 Harmonic Distortion
2 1 Ja n 1 4 2 1 J a n 1 4 Vo l.1 -Ge n e r a l;p a r tc-p o we r Qu a lity 1. Scope This handbook section contains of PacifiCorp s standard for harmonic distortion (electrical pollution) control, as well
More informationThe increase in the application
Harmonic mitigation for AC variable frequency pump drives Pump applications increasingly use AC variable speed drives. However, their operation introduces harmonic distortion of voltage supplies, which
More informationTransients under energizing multiple power filter circuits
Computer Applications in Electrical Engineering Vol. 14 2016 DOI 10.21008/j.1508-4248.2016.0008 Transients under energizing multiple power filter circuits Jurij Warecki, Michał Gajdzica AGH University
More informationPower Factor. Power Factor Correction.
Power Factor. Power factor is the ratio between the KW and the KVA drawn by an electrical load where the KW is the actual load power and the KVA is the apparent load power. It is a measure of how effectively
More informationThree-Phase Multi-Pulse Converter with Phase-Shifting Transformer
89 International Journal of Electronics, Electrical and Computational System Three-Phase Multi-Pulse Converter with Phase-Shifting Transformer Department of Electrical Engienring MITS Gwalior Abstract-In
More informationPOWER FACTOR CORRECTION AND ITS PITFALLS
Technical Note No. May 1999 POWER FACTOR CORRECTION AND ITS PITFALLS This Technical Note considers power factor correction as applied by large customers and the possible consequences when power factor
More informationHARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus
1592 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005 The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus Ahmed Faheem Zobaa, Senior Member, IEEE Abstract A
More information