POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS

Size: px
Start display at page:

Download "POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS"

Transcription

1 POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS Juan Manuel Gers, PhD

2 Example - Single Line

3 Example 1 - Data Calculate the following: 1. The three phase short circuit levels on busbars 1 and 2 2. The transformation ratios of the CTs associated with breakers 1 to 8, given that the number of primary turns is a multiple of 100 The CT for breaker number 9 is 250/5 3. The settings of the instantaneous elements, and the TAP and DIAL settings of the relays to guarantee a coordinated protection arrangement, allowing a discrimination margin of 0.4 seconds 4. The percentage of the 34.5 kv line protected by the instantaneous element of the overcurrent relay associated with breaker 6 The p.u. impedances are calculated on the following bases: V = 34.5 kv, P = 100 MVA

4 Example 1 - Data The settings of relay 7 are: TAP = 4 A DIAL = 5 Instantaneous = 1100 A All the relays are of the inverse time type with the following characteristics: TAP=1to12A,instepsof1A DIAL = as shown in next figure

5 Calculation of short circuit levels Example V (34,500V ) ZTHEVENIN = = = 6.5 ohms referred to34. 5kV 6 P *10 SC Z transf 1 (34500) = *10 2 = = 7.93ohms, referred to34.5kv ohms, referred to115kv Z transf 2 (34500) = *10 2 = 28.96ohms, referred to34.5kv Z line (34500) = * = 12.93ohms, referred to34.5kv

6 Short circuit levels - Example 1 Z transf1 Z + = Network ( 34.5) = 9.18 ohms, referred to 34.5 kv = ohms, referred to 115 kv Z Network = Ω Ω = Ω, referred to 115 kv

7 Network equivalent - Example 1 Positive Sequence Network (Impedances are referred to 34.5 kv)

8 Nominal currents - Example 1 = A at 34.5 kv I nom.6 = A at 34.5 kv I nom.7 = A at 34.5 kv I nom.8 = A at 34.5 kv = A at 115 kv

9 Short circuit levels - Example 1 = A at 34.5 kv = A at 13.2 kv = A at 34.5 kv

10 Short circuit levels - Example 1 = A at 34.5 kv = A at 34.5 kv = A at 115 kv

11 Example 1 Short circuit printout

12 Selection of current transformers Example 1 The two criteria to be fulfilled are: The CT withstands the nominal current continuously The maximum short circuit current does not saturate the CT. This is verified with the following expression assuming C100 CTs and a burden of 1 Ohm : (Isc 5/X) 100 X (Isc 5/100)

13 Summary of currents and CT ratios Example 1 Breaker No. Pnom (MVA) Inom (A) Isc (A) 5/100 Isc (A) CT Ratio ,2, /5 300/5 200/5 200/5 100/5 200/5 100/5

14 Tap setting - Example 1 I load1,2,3 = A; TAP 1,2,3 = (1.5)(43.74)(5/100) = 3.28; TAP 1,2,3 = 4 A I load4 = 131,22 A; TAP 4 = (1.5)(131.22)(5/200) = 4.92: TAP 4 = 5 A I load5 = A; TAP 5 = (1.5)(50.20)(5/100) = 3.76 A; TAP 5 = 4 A I load6 = A; TAP 6 = (1.5)(50.20)(5/200) = 1.88 A; TAP 6 = 2 A I load8 = A; TAP 8 = (1.5)(251.02)(5/300) = 6.28 A; TAP 8 = 7 A I load9 = A; TAP 9 = (1.5)(75.31)(5/250) = 2.26 A; TAP 9 = 3 A

15 Instantaneous and DIAL setting - Example 1 Relays 1, 2 and 3 Inst. trip = 9 I nom (1/CTR) = (5/100) = A 20 A I prim. trip = 20 (100/5) = 400 A MULT = 20 (1/4) = 5 times. At 5 times and DIAL 1/2, t=0.11 sec. Relay 4 To discriminate with relay 3 at 400 A requires operation in t4 = = 0.51 sec. MULTa = (400)(5/200)(1/5) = 2 times. At 2 times and t op =0.51 sec., DIAL 1/2 MULTb = (0.86)( )(5/200)(1/5) = 4.63 times. At 4.63 times and DIAL 1/2 tb = 0.13 sec.

16 Typical time/current characteristic t relay = 0.71 se``c t 2 = 0.51 sec 0.40 sec t 1 = 0.11 sec

17 Summary of relay settings Example 1 Relay No. CT ratio Tap DIAL Instantaneous 1,2, /5 200/5 100/5 200/5 200/5 300/5 250/ /2 1/ A 26 A 32 A 27.5 A 17 A

18 Coordination curves with a W CO-11

19 Settings with a numerical relay Consider a numerical relay with the following constants: α = 1.0, β = 13.5 L = 0 Therefore t = [(dial) 13.5]/ (MULT 1) Where: MULT = Fault current (in secondary amps)/tap For setting of the instantaneous element consider ten (10) times the maximum load current

20 Settings with a numerical relay Relays 1, 2 and 3 Iinst. trip = 10 Inom (1/CTR) = (5/100) = A set at 22 A. Iprim. trip = 22(100/5) = 440 A. MULT = 22/4 = 5.5 times with dial = 0.05, t = ( )/(5.5 1) = 0.15 s. To coordinate with relays 1,2 and 3 at 440 A, t 4a = = 0.55 s.

21 Settings with a numerical relay Relay 4 MULT 4a = (440)(5/200)(1/5) = 2.2 times. At 2.2 times, and t 4a = 0.55 s, dial = 0.55 (2.2 1)/13.5 = The operating time for a line-to-line fault is determined by taking 86% of the three-phase fault current. MULT 4b = (0.86)( )(5/200)(1/5) = 4.63 times. t 4b = ( )/(4.63 1) = 0.19 s. This relay has no setting for the instantaneous

22 Example 1- Coordination Curves with NR RELAY SETTINGS R1, R2, R3: Tap=4.0 Amp Time Dial=0.05 Inst=22.0 Amp CT=100/5 Amp R4: Tap=5.00 Amp Time Dial=0.05 Inst=Disable CT=200/5 Amp R5: Tap=4.0 Amp Time Dial=0.2 Inst=26.0 Amp CT=100/5 Amp R6: Tap=2.0 Amp Time Dial=0.4 Inst=32.0 Amp CT=200/5 Amp R7: Tap=4.0 Amp Time Dial=0.3 Inst=27.5 Amp CT=200/5 Amp R8: Tap=7.0 Amp Time Dial=0.1 Inst=Disable CT=300/5 Amp R9: Tap=3.0 Amp Time Dial=0.2 Inst=17.0 Amp CT=250/5 Amp THERMAL LIMITS TR1, TR2: Power Transformer L1: Feeder Cable

23 Coverage of the instantaneous unit Example 1 Percentage of 34.5 kv line protected by the instantaneous element of the overcurrent relay associated with breaker 6. Given that: % = K s (1-K i )-1/K i where K i =I sc pickup /I sc end = 1280/ = and K s =Z source /Z element From the computer listing: Z f =V 2 /P = / = 6.5 and, Ks = 6.50/12.92 = 0.50 Therefore: % = 0.50 x ((( )+1)/1.248) = 0.70 so that the instantaneous element covers 70% of the line

24 Minimum short circuit levels When the time delay unit has been set using maximum fault levels, it is necessary to check that the relays will operate at the minimum fault levels and in the correct sequence. For this, it is sufficient to verify that the TAP multiplier under these conditions is greater than 1.5.

25 Questions?

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS Juan Manuel Gers, PhD Protection coordination principles Relay coordination is the process of selecting settings that will assure that the relays

More information

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE Professor Akhtar Kalam Victoria University The Problem Calculate & sketch the ZPS, NPS & PPS impedance networks. Calculate feeder faults. Calculate

More information

Time-current Coordination

Time-current Coordination 269 5.2.3.1 Time-current Coordination Time that is controlled by current magnitude permits discriminating faults at one location from another. There are three variables available to discriminate faults,

More information

PROTECTION of electricity distribution networks

PROTECTION of electricity distribution networks PROTECTION of electricity distribution networks Juan M. Gers and Edward J. Holmes The Institution of Electrical Engineers Contents Preface and acknowledgments x 1 Introduction 1 1.1 Basic principles of

More information

Electrical Protection System Design and Operation

Electrical Protection System Design and Operation ELEC9713 Industrial and Commercial Power Systems Electrical Protection System Design and Operation 1. Function of Electrical Protection Systems The three primary aims of overcurrent electrical protection

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

Overcurrent Protective Relays

Overcurrent Protective Relays Power System Protection Overcurrent Protective Relays Dr.Professor Mohammed Tawfeeq Lazim Alzuhairi 99 Power system protection Dr.Mohammed Tawfeeq Overcurrent Protective Relays Overcurrent relays Overcurrent

More information

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General

More information

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series

More information

MV network design & devices selection EXERCISE BOOK

MV network design & devices selection EXERCISE BOOK MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester

More information

Overcurrent Elements

Overcurrent Elements Exercise Objectives Hands-On Relay Testing Session Overcurrent Elements After completing this exercise, you should be able to do the following: Identify overcurrent element settings. Determine effective

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

BUS2000 Busbar Differential Protection System

BUS2000 Busbar Differential Protection System BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection 1 Typical Busbar Arrangements Single Busbar Double Busbar with Coupler Breaker and a Half

More information

Coordination of protective relays in MV transformer stations using EasyPower Protector software

Coordination of protective relays in MV transformer stations using EasyPower Protector software Coordination of protective relays in MV transformer stations using EasyPower Protector software S. Nikolovski, Member, IEEE, I. Provci and D. Sljivac In this paper, the analysis of digital protection relays

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Relay withdrawn from case Application The type CDG 11 relay

More information

Setting and Verification of Generation Protection to Meet NERC Reliability Standards

Setting and Verification of Generation Protection to Meet NERC Reliability Standards 1 Setting and Verification of Generation Protection to Meet NERC Reliability Standards Xiangmin Gao, Tom Ernst Douglas Rust, GE Energy Connections Dandsco LLC. Abstract NERC has recently published several

More information

Protection Introduction

Protection Introduction 1.0 Introduction Protection 2 There are five basic classes of protective relays: Magnitude relays Directional relays Ratio (impedance) relays Differential relays Pilot relays We will study each of these.

More information

Transformer Fault Categories

Transformer Fault Categories Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)

More information

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525.

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525. Time Overcurrent Relays More or less approximates thermal fuse» Allow coordination with fuses Direction of Current nduced Torque Restraining Spring Reset Position Time Dial Setting Disk Basic equation

More information

Distance Protection for Distribution Feeders. Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng.

Distance Protection for Distribution Feeders. Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng. Distance Protection for Distribution Feeders Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng. Why use distance protection for distribution feeders? Distance protection is mainly used for protecting

More information

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June

More information

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants Martin Best and Stephanie Mercer, UC Synergetic, LLC Abstract Wind generating plants employ several

More information

Relay Coordination in the Protection of Radially- Connected Power System Network

Relay Coordination in the Protection of Radially- Connected Power System Network Relay Coordination in the Protection of Radially- Connected Power System Network Zankhana Shah Electrical Department, Kalol institute of research centre, Ahemedabad-Mehshana Highway, kalol, India 1 zankhu.shah@gmail.com

More information

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8] Code No: RR320205 Set No. 1 1. (a) Explain about Bewley s Lattice diagrams and also mention the uses of these diagrams. [6+2] (b) A line of surge impedance of 400 ohms is charged from a battery of constant

More information

DISTRIBUTION DEVICE COORDINATION

DISTRIBUTION DEVICE COORDINATION DISTRIBUTION DEVICE COORDINATION Kevin Damron & Calvin Howard Avista Utilities Presented March th, 08 At the 5 th Annual Hands-On Relay School Washington State University Pullman, Washington TABLE OF CONTENTS

More information

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY SECTION 16075 - SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Provide a short-circuit, component protection, flash

More information

Overcurrent and Overload Protection of AC Machines and Power Transformers

Overcurrent and Overload Protection of AC Machines and Power Transformers Exercise 2 Overcurrent and Overload Protection of AC Machines and Power Transformers EXERCISE OBJECTIVE When you have completed this exercise, you will understand the relationship between the power rating

More information

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Solkor R & Solkor Rf

More information

Back to the Basics Current Transformer (CT) Testing

Back to the Basics Current Transformer (CT) Testing Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed

More information

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost

More information

Unit Protection Differential Relays

Unit Protection Differential Relays Unit Protection PROF. SHAHRAM MONTASER KOUHSARI Current, pu Current, pu Protection Relays - BASICS Note on CT polarity dots Through-current: must not operate Internal fault: must operate The CT currents

More information

Motor Protection. May 31, Tom Ernst GE Grid Solutions

Motor Protection. May 31, Tom Ernst GE Grid Solutions Motor Protection May 31, 2017 Tom Ernst GE Grid Solutions Motor Relay Zone of Protection -Electrical Faults -Abnormal Conditions -Thermal Overloads -Mechanical Failure 2 Setting of the motor protection

More information

ISSN: Page 298

ISSN: Page 298 Sizing Current Transformers Rating To Enhance Digital Relay Operations Using Advanced Saturation Voltage Model *J.O. Aibangbee 1 and S.O. Onohaebi 2 *Department of Electrical &Computer Engineering, Bells

More information

Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602

Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602 Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602 1 / 12 1 INTRODUCTION This document provides guidelines for the performance calculations required for high impedance differential

More information

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Additional Options 15kV Isolation

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

APPENDIX A MATLAB CODE FOR CALCULATION OF MOTOR TORQUE

APPENDIX A MATLAB CODE FOR CALCULATION OF MOTOR TORQUE APPENDIX A MATLAB CODE FOR CALCULATION OF MOTOR TORQUE Table 1 MATLAB code for calculating motor torque[1] %Definition of Motor Parameters V=4000/sqrt(3); %Phase voltage NoPh=3; %Number of Phase NoPo=2

More information

PROTECTIVE DEVICES CO-ORDINATTION TOOLBOX ENHANCED BY AN EMBEDDED EXPERT SYSTEM - MEDIUM AND LOW VOLTAGE LEVELS

PROTECTIVE DEVICES CO-ORDINATTION TOOLBOX ENHANCED BY AN EMBEDDED EXPERT SYSTEM - MEDIUM AND LOW VOLTAGE LEVELS PROTECTIVE DEVICES CO-ORDINATTION TOOLBOX ENHANCED BY AN EMBEDDED EXPERT SYSTEM - MEDIUM AND LOW VOLTAGE LEVELS Attia El-Fergany Zagazig University - Egypt el_fergany@hotmail.com SUMMARY Industrial utilities

More information

Protection of a 138/34.5 kv transformer using SEL relay

Protection of a 138/34.5 kv transformer using SEL relay Scholars' Mine Masters Theses Student Theses and Dissertations Fall 2016 Protection of a 138/34.5 kv transformer using SEL 387-6 relay Aamani Lakkaraju Follow this and additional works at: http://scholarsmine.mst.edu/masters_theses

More information

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2 BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY The BE1-67N Ground Directional Overcurrent Relay provides ground fault protection for transmission and distribution lines by sensing the direction and magnitude

More information

Height: inches Width: inches Depth: inches, inches. Listings/Certification UL 1053 ANSI C37-90 IEC 255. General Description

Height: inches Width: inches Depth: inches, inches. Listings/Certification UL 1053 ANSI C37-90 IEC 255. General Description 1rcJll Cutler-Hammer New nformation Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer protection Backup

More information

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd. Functional Range - Earth Fault Relay C&S Protection & Control Ltd. 2 Contents Page No. 1. Application 2. Operating Principle. Current Transformer Connections 5. Connections, Contact Arrangement and Setting

More information

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION GEK-00682D INTRODUCTION INTRODUCTION. PRODUCT DESCRIPTION The MDP Digital Time Overcurrent Relay is a digital, microprocessor based, nondirectional overcurrent relay that protects against phase-to-phase

More information

9 Overcurrent Protection for Phase and Earth Faults

9 Overcurrent Protection for Phase and Earth Faults Overcurrent Protection for Phase and Earth Faults Introduction 9. Co-ordination procedure 9.2 Principles of time/current grading 9.3 Standard I.D.M.T. overcurrent relays 9.4 Combined I.D.M.T. and high

More information

MULTI FUNCTION OVER CURRENT AND EARTH FAULT RELAY[50/51X3,50/51N]

MULTI FUNCTION OVER CURRENT AND EARTH FAULT RELAY[50/51X3,50/51N] DOG-M51D Feature The multi-ocr is a microprocessor based digital type protective relay that has 3 phases overcurrent and ground overcurrent element which are provided with inverse, very inverse, extremely

More information

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Additional Options Solkor

More information

Bus Protection Fundamentals

Bus Protection Fundamentals Bus Protection Fundamentals Terrence Smith GE Grid Solutions 2017 Texas A&M Protective Relay Conference Bus Protection Requirements High bus fault currents due to large number of circuits connected: CT

More information

PD300. Transformer, generator and motor protection Data sheet

PD300. Transformer, generator and motor protection Data sheet PD300 Transformer, generator and motor protection Data sheet DSE_PD300_eng_AO No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam T&D. One of

More information

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities

More information

INSTRUCTIONS. SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays. GE Power Management

INSTRUCTIONS. SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays. GE Power Management g INSTRUCTIONS SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays Manual Part Number: GEK-86069J Copyright 2002 215 Anderson Avenue Markham, Ontario L6E 1B3 Canada Telephone: (905) 294-6222 Fax:

More information

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device ABB AG - EPDS The worldʼs fastest limiting and switching device Agenda The world s fastest limiting and switching device Customers Function: Insert-holder with insert Comparison: I S -limiter Circuit-breaker

More information

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM BY MR. H. C. MEHTA AT 1 ST INDIA DOBLE PROTECTION AND AUTOMATION CONFERENCE, NOV 2008 POWER-LINKER Wisdom is not Virtue but Necessity hcmehta@powerlinker.org

More information

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority S. Songsiri * and S. Sirisumrannukul Abstract This paper presents an application

More information

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson... TECHNICAL REPORT APPLICATION GUIDE TITLE: Current Transformer Requirements for VA TECH Reyrolle ACP Relays PREPARED BY:- A Allen... APPROVED :- B Watson... REPORT NO:- 990/TIR/005/02 DATE :- 24 Jan 2000

More information

Transmission System Phase Backup Protection

Transmission System Phase Backup Protection Reliability Guideline Transmission System Phase Backup Protection NERC System Protection and Control Subcommittee Draft for Planning Committee Approval June 2011 Table of Contents 1. Introduction and Need

More information

ECE456 Power System Protection

ECE456 Power System Protection ECE456 Power System Protection Assignment : #5 (Solutions) 1. A phase b-c-g fault is experienced at F in the system shown in figure 1. Calculate the impedances seen by the b-c, b-g and c-g units of the

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Generator Protection GENERATOR CONTROL AND PROTECTION

Generator Protection GENERATOR CONTROL AND PROTECTION Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault

More information

2015 Relay School Bus Protection Mike Kockott March, 2015

2015 Relay School Bus Protection Mike Kockott March, 2015 2015 Relay School Bus Protection Mike Kockott March, 2015 History of Bus Protection Circulating current differential (1900s) High impedance differential (1940s) Percentage restrained differential (1960s)

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

3-phase short-circuit current (Isc) at any point within a LV installation

3-phase short-circuit current (Isc) at any point within a LV installation 3-phase short-circuit current (Isc) at any point within a LV installation In a 3-phase installation Isc at any point is given by: where U 20 = phase-to-phase voltage of the open circuited secondary windings

More information

2C73 Setting Guide. High Impedance Differential Relay. relay monitoring systems pty ltd Advanced Protection Devices

2C73 Setting Guide. High Impedance Differential Relay. relay monitoring systems pty ltd Advanced Protection Devices 2C73 Setting Guide High Impedance Differential Relay relay monitoring systems pty ltd Advanced Protection Devices 1. INTRODUCTION This document provides guidelines for the performance calculations required

More information

Line Protection Roy Moxley Siemens USA

Line Protection Roy Moxley Siemens USA Line Protection Roy Moxley Siemens USA Unrestricted Siemens AG 2017 siemens.com/digitalgrid What is a Railroad s Biggest Asset? Rolling Stock Share-holders Relationships Shipping Contracts Employees (Engineers)

More information

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3 Power System Protection Dr. Lionel R. Orama Exclusa, PE Week 3 Operating Principles: Electromagnetic Attraction Relays Readings-Mason Chapters & 3 Operating quantities Electromagnetic attraction Response

More information

Table 1 Various IRD models and their associated time/current characteristics Time/Current Characteristics. Definite Time Moderately Inverse Time

Table 1 Various IRD models and their associated time/current characteristics Time/Current Characteristics. Definite Time Moderately Inverse Time IRD SCOPE This test procedure covers the testing and maintenance of Westinghouse IRD relays. The Westinghouse Protective Relay Division was purchased by ABB, and new relays carry the ABB label. Refer to

More information

www. ElectricalPartManuals. com Type CGR Ratio Ground Relay Descriptive Bulletin Page 1

www. ElectricalPartManuals. com Type CGR Ratio Ground Relay Descriptive Bulletin Page 1 November, 1981 New nformation Mailed to: E,D,C/211, 219/DB Westinghouse Electric Corporation Relay-nstrument Division Coral Springs, FL 65 Page 1 Type CGR Ratio Ground Relay "" Page 2 Application Three

More information

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when

More information

UNIVERSITY OF SWAZILAND

UNIVERSITY OF SWAZILAND UNVERSTY OF SWAZLAND SUPPLEMENTARY EXAMNATON, SECOND SEMESTER MAY 2017 FACULTY OF SCENCE AND ENGNEERNG DEPARTMENT OF ELECTRCAL AND ELECTRONC ENGNEERNG TTLE OF PAPER: Switchgear and Protection COURSE CODE

More information

Conventional Paper-II-2011 Part-1A

Conventional Paper-II-2011 Part-1A Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance

More information

TEST PROCEDURE FOR THE RMS-2012AF PROGRAMMABLE LOGIC CONTROLLER USING AN AMPTECTOR SECONDARY TEST SET.

TEST PROCEDURE FOR THE RMS-2012AF PROGRAMMABLE LOGIC CONTROLLER USING AN AMPTECTOR SECONDARY TEST SET. 1 TEST PROCEDURE FOR THE RMS-2012AF PROGRAMMABLE LOGIC CONTROLLER USING AN AMPTECTOR SECONDARY TEST SET. The Amptector Adapter Plug, shown above, is available from WESTRIP to facilitate the testing of

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com ARC FLASH PPE GUIDELINES FOR

More information

Notes 1: Introduction to Distribution Systems

Notes 1: Introduction to Distribution Systems Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission

More information

3 Pole high impedance differential relay 7VH83

3 Pole high impedance differential relay 7VH83 Fig 1. High impedance differential protection relay 7VH83 Features l Integral CT shorting relay. l Robust solid state design. l Inrush stabilisation through filtering. l Fast operating time. l LED indicator.

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

A Guide to the DC Decay of Fault Current and X/R Ratios

A Guide to the DC Decay of Fault Current and X/R Ratios A Guide to the DC Decay of Fault Current and X/R Ratios Introduction This guide presents a guide to the theory of DC decay of fault currents and X/R ratios and the calculation of these values in Ipsa.

More information

DIAC Type 66K. DIGITAL OVERCURRENT RELAY Instruction Manual. GE Power Management

DIAC Type 66K. DIGITAL OVERCURRENT RELAY Instruction Manual. GE Power Management g GE Power Management DIAC Type K DIGITAL OVERCURRENT RELAY Instruction Manual DIAC K Revision: SPDV0.A0 Manual P/N: GEK-0C Copyright 000 GE Power Management GE Power Management Anderson Avenue, Markham,

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc. The InterNational Electrical Testing Association Journal FEATURE PROTECTION GUIDE 64S Theory, Application, and Commissioning of Generator 100 Percent Stator Ground Fault Protection Using Low Frequency

More information

Differential Protection with REF 542plus Feeder Terminal

Differential Protection with REF 542plus Feeder Terminal Differential Protection with REF 542plus Application and Setting Guide kansikuva_bw 1MRS 756281 Issued: 09.01.2007 Version: A Differential Protection with REF 542plus Application and Setting Guide Contents:

More information

Feeder Protection Challenges with High Penetration of Inverter Based Distributed Generation

Feeder Protection Challenges with High Penetration of Inverter Based Distributed Generation Feeder Protection Challenges with High Penetration of Inverter Based Distributed Generation Harag Margossian 1, Florin Capitanescu 2, Juergen Sachau 3 Interdisciplinary Centre for Security, Reliability

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Volts Per Hertz (24), Undervoltage (27), Overvoltage (59), and Under/Overfrequency (81) Protection System Protection and Control Subcommittee

More information

EASUN REYROLLE LIMITED

EASUN REYROLLE LIMITED OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Testing Numerical Transformer Differential Relays

Testing Numerical Transformer Differential Relays Feature Testing Numerical Transformer Differential Relays Steve Turner Beckwith Electric Co., nc. ntroduction Numerical transformer differential relays require careful consideration as to how to test properly.

More information

Overcurrent relays coordination using MATLAB model

Overcurrent relays coordination using MATLAB model JEMT 6 (2018) 8-15 ISSN 2053-3535 Overcurrent relays coordination using MATLAB model A. Akhikpemelo 1 *, M. J. E. Evbogbai 2 and M. S. Okundamiya 3 1 Department of Electrical and Electronic Engineering,

More information

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT. MODBUS/BECO2200-M3425A Communication Data Base for M-3425A Integrated Protection System Device I.D. = 150 Specifications presented herein are thought to be accurate at the time of publication but are subject

More information

La protection sélective des réseaux électriques

La protection sélective des réseaux électriques La protection sélective des réseaux électriques ULG 21. 11. 2012 The T&D grids Generation Transmission Distribution Industry The electricity network ensure an efficient supply of energy High Voltage Transformers

More information

Relaying 101. by: Tom Ernst GE Grid Solutions

Relaying 101. by: Tom Ernst GE Grid Solutions Relaying 101 by: Tom Ernst GE Grid Solutions Thomas.ernst@ge.com Relaying 101 The abridged edition Too Much to Cover Power system theory review Phasor domain representation of sinusoidal waveforms 1-phase

More information

Content. 1. Dimensiong of CT s. 2. Error definitions. 3. General design aspects. 4. Linear cores. Certified acc. to ISO 9001/14001, SN EN 45001

Content. 1. Dimensiong of CT s. 2. Error definitions. 3. General design aspects. 4. Linear cores. Certified acc. to ISO 9001/14001, SN EN 45001 Content 1. Dimensiong of CT s 2. Error definitions 3. General design aspects 4. Linear cores Certified acc. to ISO 9001/14001, SN EN 45001 Dimensioning of CT s N P x I P = N S x I S N S = ( I P x N P )

More information

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd 2C73 Setting Guide High Impedance Differential Relay relay monitoring systems pty ltd Advanced Protection Devices 1. INTRODUCTION This document provides guidelines for the performance calculations required

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone

More information

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection) Differential Protection (Unit protection) Differential Protection Differential protection is the best technique in protection. In this type of protection the electrical quantities entering and leaving

More information

NERC Protection Coordination Webinar Series July 15, Jon Gardell

NERC Protection Coordination Webinar Series July 15, Jon Gardell Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information