1 Sizing Current Transformers Rating To Enhance Digital Relay Operations Using Advanced Saturation Voltage Model *J.O. Aibangbee 1 and S.O. Onohaebi 2 *Department of Electrical &Computer Engineering, Bells University of Technology, Ota, Nigeria Department of Electrical / Electronic Engineering, University of Benin, Nigeria ABSTRACT Current transformers for transmission lines are rated to avoid saturation during the asymmetrical portion of the maximum fault current. The selection of current transformers (CTs) rating to maximize microprocessor-based (MPB) relay operations was investigated. This paper examines the effects of saturation on protection relays, and developed an advanced saturation voltage (VS) algorithm for the selection of CT rating for Microprocessorbased relays applications in transmission lines with high short circuit levels. Results show that Instantaneous MPB relay operation using 1200:5A ratio can be guaranteed with Voltage burden of 525, within 1-cycle trip time as compared to Voltage burden of 20 times rated voltage at standard burden to avoid saturation specified by IEEE standard for EMR. A criterion for selecting minimum CT rating for MPB overcurrent relay operations in transmission lines to avoid saturation using the developed voltage saturation (VS) algorithm is presented. It allows protection engineers to determine the limits of high current applications in terms of the fault current magnitude, the X/R ratio, and relay burden. The criteria address the limitation of CT ratings used in line protections. Small cores, long leads, high burdens, high currents, and dc offset lead to saturated CTs. Improper selection of CTs results in CT s saturation during fault conditions and this causes relay mal-operation or fail-to-trip. Keywords: Microprocessor-based relays, Relay burden, EMR, Current Transformers, Relay burden, Saturation Voltage (VS), dc offset, Fault current. 1. Introduction Most of the generating stations in Nigeria are retrofitted with Microprocessor-based (digital) relays and protection equipment with the rest of the installation such as Current transformers (CTs) and control cables (lead) remaining unchanged. In the past, due to the high burden of electromechanical relays (EMRs), it was the rated power of the CTs and potential transformers (PT) that was the crucial parameter. In recent time, it is the transient performance of instrument transformers that has become the over-riding influence within the digital relays, measuring and controlling devices. It is utmost important therefore to evaluate the dimensioning of CTs while planning such up-grade. The existing CT sizes and lead sizes of EMRs may not be adequate for the latest protective relays which might demand a different CT performance [1, 2, 4]. CTs are the basic interconnection between the power system networks and protective relays. CTs step the primary current down to a nominal secondary level for use by protective relays, meters, and other monitoring devices. CTs perform reasonably in most operating scenarios, faithfully reproducing primary current as a secondary current, with little distortion or error CTs for transmission lines are rated to avoid saturation during the asymmetrical portion of the maximum fault current. Saturation is avoided by selecting the voltage rating larger than the maximum fault burden voltage with the (X/R+1) factors applied according to [3]. This is possible in line protection applications since large load currents result in the use of high ratio CTs, and fault currents are typically limited from 5 to 7, and rarely exceed 10 times the CT primary current rating. In this paper, the relationship between the flux density and the time integral of the voltage is examined. Using this as a basis, the relationship between fault current, CT burdens, and system X/R ratio is established and this ultimately determines the useful range of any CT. II. Current Transformers Burden and Accuracy Class The burden of current transformers is the property of the circuit connected to the secondary winding, which determines the active and reactive power at the secondary terminals [3]. The external load applied to the secondary of a CT is called the burden The total burden is the combination of internal CT burden and the external burden connected to the CT terminals. In selecting CT, the process is to minimize the total burden that consists of the internal resistance of the CT winding itself, the resistance of the leads from the CT to the relay including the return path, and the burden of the connected relays. The accuracy of CT s is defined as the extent to which the current in the secondary circuit reproduces the current in the primary circuit as stated by the marked ratio. In many applications the use of the ANSI/IEEE accuracy class designation is adequate to assure satisfactory relay performance. The accuracy class can be obtained by calculation or by test, followed by the minimum secondary terminal voltage that transformer will produce at 20 times rated secondary current with one of the standard burdens without exceeding the accuracy class limit of 10%. The secondary voltage rating is the voltage the CT will deliver to a standard burden at 20 time s rated secondary current without exceeding 10% ratio correction. The standard burden values ISSN: Page 298
2 for relaying are 1.0, 2.0, 4.0, and 8.0 ohms all with an impedance angle of 60 0 [4,5,6]. Consequently, at 20 times the rated current of 5 amperes the standard voltage ratings are 100, 200, 400, and 800 volts respectively. Table 1 presents standard current transformers burdens with 5A secondary windings. Table 1: Standard burdens for current transformers with 5A Secondary [6] Burden Desig- nation Resis- tance (Ω) Induct- ance (mh) Imped- ance (Ω) Volt- Amp (VA) Pf Secon- dary voltage C C C C , Figure 1 shows the shaded volt-time area produced by asymmetrical fault current. Where I f is the magnitude of the fault current in the secondary; Z b is the burden impedance, and L/R is the time constant of the primary fault current. The sine wave and the exponential components of the wave are shown dashed for comparison. The plot shows the change of burden voltage with the time. The volt-time area of the asymmetrical fault is increases compared to the normal sine wave and hence will affect the performance of the CT and the relay [8]. III. System X/R Ratio on CT s Saturation CT performance is affected significantly by the D.C component of the ac current. When a current change occurs in the primary ac system, one or more of the three-phase currents may obtain some D.C offset. This results from the necessity to satisfy two conflicting requirements that may occur [7]. In a highly inductive network, the current wave must be near maximum when the voltage is at or near zero, and The actual current at the time of the change, which is determined by the prior networks conditions. During asymmetrical faults, the fault current can be represents by two parts, namely the d.c and ac components as follows: The total fault current can be rewritten as: Figure 1: Burden Voltage for Asymmetrical Fault current Using the asymmetrical burden voltage equation (3) and substituting in equation (5) will result in the following equation: The burden voltage can be expressed as follows: In equation (6), the limit of the integral of the exponential term is the X/R ratio of the primary circuit. Since the limit integral of the cosine term is unity, we can write the equation as follows: The burden voltage V is related to the core turn (N) of the CT and the rate of change of the core flux by the induction equation. Integrating equation (4) show that the flux density in the core is represented by the area under the voltage waveform. In other words, for a given secondary fault current, more burden voltage from the CT will be required and the core density is proportional to the time interval of this voltage. Therefore the flux linkages in the core are given by the interval of equation (5) where the flux is expressed as flux density B times the core cross sectional area A Equation (7) expresses the CT-rating voltage in terms of the physical parameters of the CT, namely the saturated flux density Bs, system turns ratio N, the core cross sectional areas A; and angular frequency w. A different form of Equation (7) can be derived by recognizing that the rating voltage is 20 times the voltage across the standard burden at rated current. If we then express the fault current I f in per unit of the rated current and the burden Z b in per unit of the standard burden, equation (8) becomes the simple criterion to avoid saturation. 20 (X/R + 1).* I F * Z b (8) Where VS = 20 ISSN: Page 299
3 I F = the maximum fault current in per unit of CT rating, undistorted CT secondary current to perform phasor Z b = the CT burden in per unit of standard burden and measurement in the presents of the dc offset. X/R = the system X/R ratio, that is the primary system Using class 1200:5 CT ratio with standard burden of reactance and resistance up to the point of fault. 4Ω, the calculated total burden is express as: However, most times, these rules result in impractically large CTs, which are not economically acceptable. CT cables of m full circuit run of #10 AWG (1.0 Ω/1000 feet) = 0.40 A. CT Selection Procedures CT winding of 240 turns at Ω/turn = 0.60 The algorithms for the selection of current transformers in a given transmission line relay application is outline as follows (IEEE standard C ). (1) Determine the maximum fault current I f in primary amperes (2) Determine the corresponding primary circuit X/R ratio. (3) Select the CT voltage rating based on the load requirements. (4) Determine the total burden in per unit of the CT standard burden. (5) Divide the maximum primary fault current I f by the per unit current to determine the CT nominal current rating. Select the nearest standard rating greater than the calculated value. (6) Calculate the saturation voltage VS. (7) Finally, compare VS to the current transformer rating. If the voltage rating is greater than or equal to the calculated secondary voltage, the current transformer is acceptable for the application. IV. Methodology Description Advanced Saturation Voltage Model Microprocessor-based (MPB) relays have a relatively small burden of 0.2 VA (0.008 Ω). The secondary burden is the impedance of the CT windings and cables (leads) full circuit runs; and it is purely resistive. In this paper, the CT selection criteria are based on the degree of saturation voltage produced by the 120KA fault in the 1200:5 CT primary rating. Evaluation of the effects of asymmetrical faults with DC offset on operation of instantaneous microprocessor-based relay is considered. In order to avoid DC saturation, the saturation voltage equation VS is as expressed in equation 9. VS (9) Where I f = the maximum faults current in per unit of CT rating, Z b is the CT burden in per unit of standard burden, VS is the CT saturation voltage in per unit, X/R is the X/R ratio of the primary fault current. A. CTs Selection for line Protection Modern Microprocessor-based relays clear faults in few cycles to preserve stability, accurately identify fault type for single-pole reclosing applications, and determine an accurate fault location. To accomplish this, line relays require Total burden = 1.00 Ω The burden is primarily due to the CT winding and external cables to the relay. Equation (10) determines the maximum burden in per unit of the standard burden: Z b = (10) With an X/R ratio of 20, the saturation voltage can be calculated using equation (9) as follows: Vs [20+1]* 100 * 0.25 = 525 Consequently, CTs used with the microprocessor relays should meet the criteria in equation 11; 525 (11) Calculated maximum load current of the protected line is A, so select CT of 1200:5A, being the nearest CT standard rating greater than the calculated value. Also, the calculated Voltage Saturation of CT 1200:5A rating from the enhanced model is 302 Volts. This is less than the 400 Volts rating of CT 1200:5A ratio, hence the selected CT rating of 1200:5A is thus adequate and suitable for protection application. For evaluation purposes, microprocessor overcurrent relay with a 240A instantaneous setting and X/R ratio of 20 (worst case) is considered. The equation for maximum fault current in terms of primary CT and ANSI voltage rating, burden in ohms, and X/R ratio is as express in equation 12, I max = * (12) The acceptable calculated saturated voltage VS is 525 volts, substituting equation (12) above, the maximum fault current for secure operation can be calculated as follows: I max = B. Simulation: Evaluation of CT Secondary Burden: * 1200 = 120,000 A for MPBRs In the simulation conducted at BELLS University of Technology, Power Laboratory, different secondary burdens of 1.0, 3.0, 5.0, and 10Ω were injected at different times into the SEL-551 MPB instantaneous overcurrent relay by the secondary test equipment ISA T2000, using a CT of 1200:5A ratio. Starting from a burden of 1.0 Ω; the burden is ISSN: Page 300
4 primary due to CT winding itself, and external leads (a wire size of #10 AWG) of a total length of 400ft (121.92m) from CTs to the relay including the return path. With total burden of 1.0 ohm, secondary current waveform results was obtained from ATP simulations base on transmission network parameters as shows in Figure 2; it indicates an undistorted waveform throughout the duration of the simulation. When secondary burden of 3.0 ohm was injected into the secondary circuit, the CT core saturates for at least four (4) cycles after the fault occurs. Subsequently increasing the burden to 5.0 ohm, and then 10 ohms respectively, the waveform distortion became more present (visible) during the entire simulation. The severe CT saturation (distortions) caused by the heavy fault current (115 KA) with maximum offset and different values of secondary burden (3, 5, and 10 ohms) is shown in Figure 3; these caused RMS current to be smaller than in fact it was, i.e. the secondary current is substantially reduced under severe saturation of main CTs. This proves that relative small burden can influence CT accuracy if the fault current is not correctly anticipated. Conclusively, proper selection of a CT is required for a better protection scheme operation. Figure 2: Non-saturated Waveform secondary burden (1.0 ohm). Since MPB instantaneous relays operates within one cycle (1) and that the CTs operation was accurate from one to four cycles of its operation before saturation start to occurs, this proved that MPB instantaneous relays operation is not affected by CT saturation. Thus the trip time of MPB relay is unimpaired by CT saturation due to DC offset with extremely high fault currents. Figure 3: Severe CT Saturation (Distorted Waveforms) due to varying burden (3, 5, and10ω). V. Case Study and Application A case study is considered to show the area of application of the work. A transmission line under protection with MPB overcurrent relay installed at the source of the busbar to protect against over load and short circuits is rated 600 MVA, three phase, 330 KV, 50Hz, line reactance (X) and resistance (R) of Ω/km and Ω/km (i.e, X/R of 11.4 ratios). A CT rating of 1200:5A ratio is selected based on the full load current of A. Short circuit faults occurred at 5km away from source, with maximum fault current calculated to be A. The CT performance data is shown in table 2. Table 2: CT Performance Data Description Current transformer in used Instantaneous element pickup setting (1200:5) Values Class 1200:5 240A secondary X/R ratio ( / ) 11.4 (85º) Maximum fault current at 5 km A Using and a total burden of 1.0 ohms, the minimum CT rating can be determine in terms of maximum fault current, X/R ratio, ANSI rating, and burden as in equation (13), CT Rating =.. 13 The parameters presented are the maximum fault current of 120 KA, X/R = 20 (worst case) and a total burden of 1.0 Ω. CT rating = = 1200 Table 3 lists the maximum fault current versus X/R ratio for which saturation is avoided. Using ANSI Class of CT ratio s of 2000:5, 1500: 5, 1200: 5, or 1000: 5, with varying burdens at various inception angles is presented. ISSN: Page 301
5 Table 3: Maximum current (Amps) to avoid saturation using Microprocessorbased Relays Line Angle X/R Ratio 2000:5 1.5 Ω 1500:5 1.2 Ω Amperes 1200:5 1.0 Ω 1000:5 0.8 Ω , , , , The CT primary current accuracy describes the highest fault current magnitude at which the CT will fulfill the specified accuracy. Beyond this level the secondary current of the CT will be distorted and it might have severe effects to the performance of the protective relay. Compliance with saturation voltage equation depends on the X/R ratio and the magnitude of the maximum fault current. Either by calculation or measuring the burden and the X/R ratio, the saturation voltage equation can be applied to calculate the maximum fault current for a given CT ratio. Thus, relay operations with 1200:5 CT can be selected and guaranteed with a saturation voltage of 525 for the relay trip operations as show in table 3. b) Transient Behavior of CT during Faults. The total secondary burden of the installation is Ω primarily due to the CT winding and external CT control wire of (400ft) m full circuit runs of #10 AWG to the relay. From equation (11), saturation voltage VS = 525 (X/R+I) * I f * Z b Fault current at 5 km away from source I f(5) = = = A Substitute these values into equation (11) to determine the limit of saturation voltage. 525 (11.4+1) * * = 302 Volts Result shows that the instantaneous operations of MPB relay using 1200:5A CT can be guaranteed with 302 times CT rating with X/R ratio of Figure 4 show the response of the relay with A short circuit fault currents for the case presented. The thick line indicates the root mean square current (I RMS) while the dash waveform is the secondary currents. It confirmed that the MPB relay with 240A instantaneous setting will respond to the fault in this case with no more than three cycles. Figure 4: Case Study Test Result with X/R =11.4 Applying the developed algorithm, instantaneous microprocessor-based relays will operate properly with 1200:5A CT ratio and high short circuit levels. CT performance will be satisfactory as the CT secondary maximum symmetrical fault current multiplied by the total secondary burden is less than the ANSI-class voltage rating of the CT. The criteria allow protection engineers to determine the limits of high current applications in terms of the fault current magnitudes, the X/R ratio and relay burden. The developed algorithm has addressed the limitation of CT ratings used in line protection where fault current exceed 525 times the CT primary rating. As shown in equation (9), a smaller size CT rating and accuracy class with adequate capability can be employ for line protection. However, the CT ratings that avoid saturation for asymmetrical current are impractical in applications near a generator bus-bar where X/R ratio and the fault current are both extremely high. A limit to the criterion is shown in table 3 where the permissible maximum fault current for a given CT rating is severely decreasing with increasing X/R ratio. The limit occurs where high X/R ratio and high fault current are experienced near the bus-bar. VI. Conclusion The effect of CT saturation on protective relays has been investigated. The relation between the ANSI voltage rating, CT burden, maximum fault current, and system X/R ratio defines the threshold of CT saturation. The derived equation provides the CT rating criteria for line protection in new installations and can identify the threshold of CT saturation in older installations. CT rating is selected based on short circuit level available, secondary burden connected, X/R ratio and required relay trip time. Consequently, the need for higher CT ratio with higher class could be eliminated. ISSN: Page 302
6 CT of smaller size rating can be used for MPBR as [4] Aibangbee J.O. Ph.D. Thesis, Current Transformer saturation impacts on Microprocessor-Based Protective Relays Application in Nigeria against the heavy and bulky type CT rating currently Electricity Transmission Network, university of Benin, Nigeria, used for electromechanical relays. The criterion used CT selection procedure for line [5] ABB Inc, Instrument Transformers Technical Information and protection which determined the CT ratio using the Application Guide maximum fault in amperes, the system X/R ratio and [6] U.S. Department of the Interior Bureau of Reclamation Denver, the ct burden expressed in per unit of a CT rated Colorado: Facilities Instructions, Operation, Maintenance, and Field standard burden. Testing Procedures for Protective Relays and associated circuits Vol.3- The instantaneous operations of microprocessor 8, May based relay can be guarantee with the advanced [7] ABB Inc Instrument Transformers Application Guides SE saturation voltage Algorithm developed. LUDVIKA, Sweden, REFERENCES [1] G. Benmouyal, and S. E. Zocholl Current Transformer Concepts Proceedings of the 46 th Annual Georgia Tech Protective Relay Conference, Atlanta, GA, April 29, [2] S. E. Zocholl, Armando Guzmán, and Daqing Hou, Transformer Modeling as Applied to Differential Relaying, Proceedings of the 22nd Annual Western Protective Relay Conference,Spokane, WA. October 24-26, [3] IEEE C , the Guide for the Application of Current Transformers Used for Protective Relaying Purposes. [8] Blackburn J. L. and Thomas J. Domin Protective Relaying Principles and Applications third edition CRC Press, 2007 [9] G. Benmouyal, E. O. Schweitzer III and Jeff Roberts, Distance Relay Element Design, Proceedings of the 19th Annual Western Protective Relay Conference, Spokane, WA, [10] IEEE Standard C57.13, 2008.Standard requirements for Instrument Transformers ISSN: Page 303
Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software
Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software Govind Pandya 1, Rahul Umre 2, Aditya Pandey 3 Assistant professor, Dept. of Electrical & Electronics,
More informationDistance Element Performance Under Conditions of CT Saturation
Distance Element Performance Under Conditions of CT Saturation Joe Mooney Schweitzer Engineering Laboratories, Inc. Published in the proceedings of the th Annual Georgia Tech Fault and Disturbance Analysis
More informationCURRENT TRANSFORMER CONCEPTS
CURRENT TRANSFORMER CONCEPTS S. E. Zocholl Schweitzer Engineering Laboratories, Inc. Pullman, WA USA D. W. Smaha Southern Company Services, Inc. Birmingham, AL USA ABSTRACT This paper reviews the C and
More informationBeyond the Knee Point: A Practical Guide to CT Saturation
Beyond the Knee Point: A Practical Guide to CT Saturation Ariana Hargrave, Michael J. Thompson, and Brad Heilman, Schweitzer Engineering Laboratories, Inc. Abstract Current transformer (CT) saturation,
More informationDistance Relay Response to Transformer Energization: Problems and Solutions
1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering
More informationReprinted from IEEE PCIC CONFERNECE, SEPTEMBER 2005, PAPER 32. This material is posted here with permission of the IEEE.
Copyright 2005 IEEE Reprinted from IEEE PCIC CONFERNECE, SEPTEMBER 2005, PAPER 32. This material is posted here with permission of the IEEE. Such permission of the IEEE does not in any way imply IEEE endorsement
More informationGE Multilin technical note
GE Digital Energy Multilin GE Multilin technical note GE Multilin releases fast and dependable short circuit protection enhanced for performance under CT saturation GE publication number: GER-4329 GE Multilin
More informationVerifying Transformer Differential Compensation Settings
Verifying Transformer Differential Compensation Settings Edsel Atienza and Marion Cooper Schweitzer Engineering Laboratories, Inc. Presented at the 6th International Conference on Large Power Transformers
More informationSATURATION OF CURRENT TRANSFORMERS AND ITS IMPACT ON DIGITAL OVERCURRENT RELAYS NABIL H. AL-ABBAS
SATURATION OF CURRENT TRANSFORMERS AND ITS IMPACT ON DIGITAL OVERCURRENT RELAYS by NABIL H. AL-ABBAS A Thesis Presented to the DEANSHIP OF GRADUATE STUDIES In Partial Fulfillment of the Requirements for
More information2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd
2C73 Setting Guide High Impedance Differential Relay relay monitoring systems pty ltd Advanced Protection Devices 1. INTRODUCTION This document provides guidelines for the performance calculations required
More information2C73 Setting Guide. High Impedance Differential Relay. relay monitoring systems pty ltd Advanced Protection Devices
2C73 Setting Guide High Impedance Differential Relay relay monitoring systems pty ltd Advanced Protection Devices 1. INTRODUCTION This document provides guidelines for the performance calculations required
More informationBus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero
Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic
More informationSymmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines
Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India
More informationDesign of Differential Protection Scheme Using Rogowski Coil
2017 IJSRST Volume 3 Issue 2 Print ISSN: 2395-6011 Online ISSN: 2395-602X National Conference on Advances in Engineering and Applied Science (NCAEAS) 16 th February 2017 In association with International
More informationCurrent Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...
TECHNICAL REPORT APPLICATION GUIDE TITLE: Current Transformer Requirements for VA TECH Reyrolle ACP Relays PREPARED BY:- A Allen... APPROVED :- B Watson... REPORT NO:- 990/TIR/005/02 DATE :- 24 Jan 2000
More informationNERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationBack to the Basics Current Transformer (CT) Testing
Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of
More informationImpact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis
1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationMotor Protection. May 31, Tom Ernst GE Grid Solutions
Motor Protection May 31, 2017 Tom Ernst GE Grid Solutions Motor Relay Zone of Protection -Electrical Faults -Abnormal Conditions -Thermal Overloads -Mechanical Failure 2 Setting of the motor protection
More informationComparison of recloser and breaker standards
s Technical Data TD280024EN Supersedes February 1994 (R280-90-5) COOPER POWER SERIES Comparison of recloser and breaker standards Technical Data TD280024EN Comparison of recloser and breaker standards
More informationECE 2006 University of Minnesota Duluth Lab 11. AC Circuits
1. Objective AC Circuits In this lab, the student will study sinusoidal voltages and currents in order to understand frequency, period, effective value, instantaneous power and average power. Also, the
More informationBED INTERCONNECTION TECHNICAL REQUIREMENTS
BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2
More informationNERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June
More informationReducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems
Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Alexander Apostolov AREVA T&D Automation I. INTRODUCTION The electric utilities industry is going through significant
More informationATP modeling of internal transformer faults for relay performance testing
Michigan Technological University Digital Commons @ Michigan Tech Dissertations, Master's Theses and Master's Reports - Open Dissertations, Master's Theses and Master's Reports 2011 ATP modeling of internal
More informationCURRENT TRANSFORMER SELECTION TECHNIQUES FOR LOW-VOLTAGE MOTOR CONTROL CENTERS
CURRENT TRANSFORMER SELEION TECHNIQUES FOR LOW-OLTAGE MOTOR CONTROL CENTERS Copyright Material IEEE Paper No. PCIC-TBD Scott Manson Senior Member, IEEE Schweitzer Engineering Laboratories, Inc. 235 NE
More informationAddendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays
Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General
More informationForward to the Basics: Selected Topics in Distribution Protection
Forward to the Basics: Selected Topics in Distribution Protection Lee Underwood and David Costello Schweitzer Engineering Laboratories, Inc. Presented at the IEEE Rural Electric Power Conference Orlando,
More informationShort Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
More informationARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS
The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com ARC FLASH PPE GUIDELINES FOR
More informationAlternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER
Alternative Testing Techniques for Current Transformers Dinesh Chhajer, PE Technical Support Group MEGGER Agenda Current Transformer Definition and Fundamentals Current Transformer Applications o Metering
More informationENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES
ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES N. Perera 1, A. Dasgupta 2, K. Narendra 1, K. Ponram 3, R. Midence 1, A. Oliveira 1 ERLPhase Power Technologies Ltd. 1 74 Scurfield
More informationInnovative Science and Technology Publications
Innovative Science and Technology Publications Manuscript Title SATURATION ANALYSIS ON CURRENT TRANSFORMER Thilepa R 1, Yogaraj J 2, Vinoth kumar C S 3, Santhosh P K 4, 1 Department of Electrical and Electronics
More informationSATURATION ANALYSIS ON CURRENT TRANSFORMER
Volume 118 No. 18 2018, 2169-2176 ISSN: 1311-8080 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu SATURATION ANALYSIS ON CURRENT TRANSFORMER MANIVASAGAM RAJENDRAN
More informationCurrent Transformer Performance study Using Software Tools.
Current Transformer Performance study Using Software Tools. A. Mechraoui, A. Draou, A. Akkouche, and S. AL Ahmadi Department of Electronics Technology Madinah College of Technology, Madinah Council of
More information3Ø Short-Circuit Calculations
3Ø Short-Circuit Calculations Why Short-Circuit Calculations Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective
More informationExtensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network
Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example
More informationCHAPTER 9. Sinusoidal Steady-State Analysis
CHAPTER 9 Sinusoidal Steady-State Analysis 9.1 The Sinusoidal Source A sinusoidal voltage source (independent or dependent) produces a voltage that varies sinusoidally with time. A sinusoidal current source
More informationPOWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS
POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS Juan Manuel Gers, PhD Example - Single Line Example 1 - Data Calculate the following: 1. The three phase short circuit levels on busbars
More informationPower. Power is the rate of using energy in joules per second 1 joule per second Is 1 Watt
3 phase Power All we need electricity for is as a source of transport for energy. We can connect to a battery, which is a source of stored energy. Or we can plug into and electric socket at home or in
More informationThe InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.
The InterNational Electrical Testing Association Journal FEATURE PROTECTION GUIDE 64S Theory, Application, and Commissioning of Generator 100 Percent Stator Ground Fault Protection Using Low Frequency
More informationSolutions to Consider in Current Transformer Selection for APR1400 Nuclear Power Plant Medium Voltage Switchgears
Journal of Energy and Power Engineering 11 (2017) 670-678 doi: 10.17265/1934-8975/2017.10.008 D DAVID PUBLISHING Solutions to Consider in Current Transformer Selection for APR1400 Nuclear Power Plant Medium
More informationUniversity of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab
University of Jordan School of Engineering Electrical Engineering Department EE 219 Electrical Circuits Lab EXPERIMENT 7 RESONANCE Prepared by: Dr. Mohammed Hawa EXPERIMENT 7 RESONANCE OBJECTIVE This experiment
More informationGenerator Protection GENERATOR CONTROL AND PROTECTION
Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault
More informationApplication Guide High Impedance Differential Protection Using SIEMENS 7SJ602
Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602 1 / 12 1 INTRODUCTION This document provides guidelines for the performance calculations required for high impedance differential
More informationData. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner
Digital Protective Relay Dr Murari Mohan Saha ABB AB KTH/EH2740 Lecture 3 Introduction to Modern Power System Protection A digital protective relay is an industrial microprocessor system operating in real
More informationA Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems
A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems T. C. Dias, B. D. Bonatto, J. M. C. Filho Abstract-- Isolated industrial power systems or with high selfgeneration,
More informationMODEL POWER SYSTEM TESTING GUIDE October 25, 2006
October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date
More informationReyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy
Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Additional Options 15kV Isolation
More information7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management
Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Solkor R & Solkor Rf
More informationUsing Event Recordings
Feature Using Event Recordings to Verify Protective Relay Operations Part II by Tony Giuliante, Donald M. MacGregor, Amir and Maria Makki, and Tony Napikoski Fault Location The accuracy of fault location
More information7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy
Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Additional Options Solkor
More informationMaintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems
Maintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems Brian Kingham, Utility Market Manager, Schneider Electric, PMC Division Abstract: Historical power quality measurement
More informationEvaluating the Impact of Increasing System Fault Currents on Protection
Evaluating the Impact of Increasing System Fault Currents on Protection Zhihan Xu, Ilia Voloh GE Grid Solutions, LLC Mohsen Khanbeigi Hydro One Abstract Every year the capacity of power systems is increasing,
More informationGenerator Protection Overcomes Current Transformer Limitations
Generator Protection Overcomes Current Transformer Limitations Marcos Donolo, Armando Guzmán, Mangapathirao V. Mynam, Rishabh Jain, and Dale Finney, Schweitzer Engineering Laboratories, Inc. Abstract Following
More informationWATT TRANSDUCER. Instruction Manual
WT 9200 WATT TRANSDUCER Instruction Manual IM-2 September 2003 USA: 6428 Ridglea Drive, Watauga, Texas 76148 Tel/Fax 1-817-427-2060/2067 E-mail: wes@westecinstruments.com SPECIFICATIONS Power Supply Input
More informationShort-Circuit Current Calculations
Basic Point-to-Point Calculation Procedure Step. Determine the transformer full load amps (F.L.A.) from either the nameplate, the following formulas or Table : Multiplier = 00 *% Z transformer Step 2.
More informationRELAY LOADABILITY CHALLENGES EXPERIENCED IN LONG LINES. Authors: Seunghwa Lee P.E., SynchroGrid, College Station, Texas 77845
RELAY LOADABILITY CHALLENGES EXPERIENCED IN LONG LINES Authors: Seunghwa Lee P.E., SynchroGrid, College Station, Texas 77845 Joe Perez P.E., SynchroGrid, College Station, Texas 77802 Presented before the
More informationPerformance Analysis of Traditional and Improved Transformer Differential Protective Relays
Performance Analysis of Traditional and Improved Transformer Differential Protective Relays Armando Guzmán, Stan Zocholl, and Gabriel Benmouyal Schweitzer Engineering Laboratories, Inc. Hector J. Altuve
More informationProtection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin
Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad
More informationSTRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS
1 STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS Z. GAJIĆ S. HOLST D. BONMANN D. BAARS ABB AB, SA Products ABB AB, SA Products ABB AG, Transformers ELEQ bv Sweden Sweden Germany Netherlands zoran.gajic@se.abb.com
More informationPinhook 500kV Transformer Neutral CT Saturation
Russell W. Patterson Tennessee Valley Authority Presented to the 9th Annual Fault and Disturbance Analysis Conference May 1-2, 26 Abstract This paper discusses the saturation of a 5kV neutral CT upon energization
More informationImproved differential relay for bus bar protection scheme with saturated current transformers based on second order harmonics
Journal of King Saud University Engineering Sciences (2016) xxx, xxx xxx King Saud University Journal of King Saud University Engineering Sciences www.ksu.edu.sa www.sciencedirect.com ORIGINAL ARTICLES
More informationUnit Auxiliary Transformer (UAT) Relay Loadability Report
Background and Objective Reliability Standard, PRC 025 1 Generator Relay Loadability (standard), developed under NERC Project 2010 13.2 Phase 2 of Relay Loadability: Generation, was adopted by the NERC
More informationOutdoor Instrument Transformers. Application Guide
Outdoor Instrument Transformers Application Guide Introduction Edited by Knut Sjövall, knut.sjovall@se.abb.com ABB Power Technologies AB Department: PTHV/HV/MT SE-771 80 LUDVIKA, Sweden 2 1HSE 9543 40-00en
More informationReview 6. unlike poles cause the magnets to attract. like poles cause the magnets to repel.
Review 6 1. The two characteristics of all magnets are: they attract and hold Iron, and, if free to move, they will assume roughly a south - north position. 2. Lines of flux always leave the north pole
More informationDelayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines
Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,
More informationTransmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection
Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed
More informationCompany Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System
Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels
More informationOverview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.
Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential
More informationProtection of Microgrids Using Differential Relays
1 Protection of Microgrids Using Differential Relays Manjula Dewadasa, Member, IEEE, Arindam Ghosh, Fellow, IEEE and Gerard Ledwich, Senior Member, IEEE Abstract A microgrid provides economical and reliable
More informationA NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *
Iranian Journal of Science & Technology, Transaction B, Engineering, Vol. 30, No. B6, pp 643-654 Printed in The Islamic Republic of Iran, 2006 Shiraz University A NEW DIFFERENTIAL PROTECTION ALGORITHM
More informationKeywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer
Vol. 3 Issue 2, February-2014, pp: (69-75), Impact Factor: 1.252, Available online at: www.erpublications.com Modeling and Simulation of Modern Digital Differential Protection Scheme of Power Transformer
More informationIDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)
IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone
More information1
Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive
More informationBus Protection Fundamentals
Bus Protection Fundamentals Terrence Smith GE Grid Solutions 2017 Texas A&M Protective Relay Conference Bus Protection Requirements High bus fault currents due to large number of circuits connected: CT
More informationUsing a Multiple Analog Input Distance Relay as a DFR
Using a Multiple Analog Input Distance Relay as a DFR Dennis Denison Senior Transmission Specialist Entergy Rich Hunt, M.S., P.E. Senior Field Application Engineer NxtPhase T&D Corporation Presented at
More informationSection 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services
Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality
More informationComparative Performance of Conventional Transducers & Rogowski Coil for Relaying Purpose
Comparative Performance of Conventional Transducers & Rogowski Coil for Relaying Purpose Ashish S. Paramane1, Avinash N. Sarwade2 *, Pradeep K. Katti3, Jayant G. Ghodekar4 1 M.Tech student, 2 Research
More informationBurdens & Current Transformer Requirements of MiCOM Relays. Application Notes B&CT/EN AP/B11. www. ElectricalPartManuals. com
Burdens & Current Transformer Requirements of MiCOM Relays Application Notes B&CT/EN AP/B11 Application Notes B&CT/EN AP/B11 Burdens & CT Req. of MiCOM Relays Page 1/46 CONTENTS 1. ABBREVIATIONS & SYMBOLS
More informationMultimeter 500CVD21 RTU500 series
Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase
More informationTransformer Waveforms
OBJECTIVE EXPERIMENT Transformer Waveforms Steady-State Testing and Performance of Single-Phase Transformers Waveforms The voltage regulation and efficiency of a distribution system are affected by the
More informationFigure 1 System One Line
Fault Coverage of Memory Polarized Mho Elements with Time Delays Hulme, Jason Abstract This paper analyzes the effect of time delays on the fault resistance coverage of memory polarized distance elements.
More informationProtection of a 138/34.5 kv transformer using SEL relay
Scholars' Mine Masters Theses Student Theses and Dissertations Fall 2016 Protection of a 138/34.5 kv transformer using SEL 387-6 relay Aamani Lakkaraju Follow this and additional works at: http://scholarsmine.mst.edu/masters_theses
More informationE N G I N E E R I N G M A N U A L
1 1 1.0 PURPOSE The purpose of this document is to define policy and provide engineering guidelines for the AP operating companies (Monongahela Power Company, The Potomac Edison Company, and West Penn
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities
More informationSubstation Testing and Commissioning: Power Transformer Through Fault Test
1 Substation Testing and Commissioning: Power Transformer Through Fault Test M. Talebi, Member, IEEE, Power Grid Engineering Y. Unludag Electric Power System Abstract This paper reviews the advantage of
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION
23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB
More informationMVCT. Megger VT & CT Analyzer. MVCT Megger VT & CT Analyzer
MVCT Ability to test both VT and CT Easy to use one-button automated test plans Industry leading test duration using patented simultaneous tap measurements Smallest and lightest unit on the market CT Kneepoints
More informationAnalyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System
Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System Lalit Ghatpande, SynchroGrid, College Station, Texas, 77840 Naveen Ganta, SynchroGrid, College Station, Texas,
More informationElectrical Protection System Design and Operation
ELEC9713 Industrial and Commercial Power Systems Electrical Protection System Design and Operation 1. Function of Electrical Protection Systems The three primary aims of overcurrent electrical protection
More informationMICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2
PART 1 PART 2 PRODUCTS 2.01 MANUFACTURERS A. Eaton products B.. C.. The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features
More informationTHE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES
THE OLE OF SYNCHOPHASOS IN THE INTEGATION OF DISTIBUTED ENEGY ESOUCES Alexander APOSTOLOV OMICON electronics - USA alex.apostolov@omicronusa.com ABSTACT The introduction of M and P class Synchrophasors
More informationT/3000 T/3000. Substation Maintenance and Commissioning Test Equipment
T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY
More informationSolution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection
ABSTRACT National conference on Engineering Innovations and Solutions (NCEIS 2018) International Journal of Scientific Research in Computer Science, Engineering and Information Technology 2018 IJSRCSEIT
More informationManual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual.
Manual Title: 550A Getting Started Supplement Issue: Part Number: 415509 Issue Date: 9/18 Print Date: November 01 Page Count: 19 Revision/Date: This supplement contains information necessary to ensure
More informationMinnesota Power Systems Conference 2015 Improving System Protection Reliability and Security
Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security Steve Turner Senior Application Engineer Beckwith Electric Company Introduction Summarize conclusions from NERC
More information