Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...

Size: px
Start display at page:

Download "Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson..."

Transcription

1 TECHNICAL REPORT APPLICATION GUIDE TITLE: Current Transformer Requirements for VA TECH Reyrolle ACP Relays PREPARED BY:- A Allen... APPROVED :- B Watson... REPORT NO:- 990/TIR/005/02 DATE :- 24 Jan 2000 K:\Arthur Allen\4 Arthur\C.T_Requirements_for_VATECH_Prot_Products_Dec03.doc Page 1 of 11

2 Issue Date Modification Revision 1 24 Jan 2000 Original Issue Revision 2 Jan 2004 Reference to BS standard changed to IEC. Relays added. Minor corrections. K:\Arthur Allen\4 Arthur\C.T_Requirements_for_VATECH_Prot_Products_Dec03.doc Page 2 of 11

3 CURRENT TRANFORMER REQUIREMENTS FOR VA TECH REYROLLE - ACP RELAYS 1. ARGUS 1 to 6 (Numeric) & 2TJM10 (Electro-mechanical): I.D.M.T.L., Definite Time and Instantaneous Overcurrent and Earth Fault Protection 1.1 Introduction A protection 'P' class CT must be used, e.g. in accordance with IEC 60044:Pt1. Typically the CT is specified by means of an accuracy class and an overcurrent accuracy limit factor up to which the CT remains within accuracy error limits with the maximum specified load burden connected to its secondary circuit. eg.: 5VA class 5P 10 5P10 5VA Accuracy Overcurrent Maximum burden Class Accuracy at nominal current Limit Factor rating The accuracy class '5P', defines the maximum composite error at the rated accuracy limit, with rated burden connected, i.e. 5%. This declared maximum error takes account of both phase and magnitude errors and is due to the excitation current and also any turns ratio compensation, expressed as a percent of the primary current. The overcurrent accuracy limit factor is the multiple of the CT rating up to which the ratio, phase angle and composite errors of the CT remain within the accuracy class limits. Thus in the example the 5VA, 5P10 CT will transform primary current of up to 10x its rating and remain within the composite accuracy limit of 5% with a burden of 5VA (at rated current) connected to the CT secondary. If the load burden is less than the rated burden a higher overcurrent accuracy limit factor can be tolerated although not necessarily exactly in inverse proportion, i.e. half the external burden, will not give twice the overcurrent factor. The internal burden of the CT (e.g. its secondary resistance) must be taken in to account if the true equivalent accuracy limit factor is to be established for a lower load burden. Typically, CT requirements for this type of protection vary dependent on the project specific requirements. The following considerations must be made. a) CT Rating - should be chosen at least equal to the maximum continuous load current of the circuit. This includes any emergency rating, e.g. of a power transformer where typically one hour or two hour overload ratings are often provided. b) Accuracy Class - Typically standard values of 5P or 10P are employed. 5P where current grading requirements are onerous e.g. where the circuits being graded have similar ratings and there are several stages of grading. In these circumstances an accuracy of 5P assists in allowing small grading steps to be applied. Accuracy levels of 10P are acceptable where large grading steps can be tolerated and only a small number of grading steps are required. c) Overcurrent Accuracy Limit Factor - The factor should be chosen to ensure:- i i.d.m.t.l. timing accuracy is not adversely affected by CT ratio errors at high fault levels. ii That any a.c. saturation effects and errors resulting from very large fault current are not so severe as to result in excessive distortion of the secondary current which may cause the relay to slow down or not operate. d) Burden - the total CT load in VA, at rated secondary current. The calculation must include pilot-lead loop-resistance plus the relay and any other burdens. Pilot burden can be high, particularly for 5 amp rated CTs, i.e. I 2 R is 25x compared to only 1x for a 1A CT. Numeric or static protection relays have a very low fixed impedance independent of setting, see the table below for Argus relay burdens. However, for electromechanical relays the impedance is normally dependent on the setting of the relay. e) Examples of typical applications are as follows. 1.2 Phase Fault I.D.M.T.L. Overcurrent a) For industrial systems with relatively low fault current and no onerous grading requirements - a class 10P10 with VA rating to match the load. K:\Arthur Allen\4 Arthur\C.T_Requirements_for_VATECH_Prot_Products_Dec03.doc Page 3 of 11

4 b) For utility distribution networks with relatively high fault current and several grading stages - a class 5P20, with VA rating to match the load. 5A Phase/Earth 1A Phase/Earth 5A SEF/REF 1A SEF/REF < 0.2 VA < 0.05 VA < 0.4 VA < 0.2 VA < 0.01Ω < 0.05Ω < 0.02Ω < 0.2Ω Note: if an accuracy limit factor is chosen which is much lower than the maximum fault current it will be necessary to consider any effect on the protection system performance and accuracy e.g. grading margins. For i.d.m.t.l. applications, because the operating time at high fault current is approaching a definite minimum value, partial saturation of the CT at values beyond the overcurrent factor has only a minimal effect. However, this must be taken into account in establishing the appropriate setting to ensure proper grading. 1.3 Definite Time and Instantaneous Overcurrent a) For industrial systems with requirements as for i.d.m.t.l. relays item (a) above, a class 10P10 (or 20). b) For utilities as for (b) above - a class 5P10 (or 20), with rated burden to suit the load. Note: Overcurrent factors do not need to be high for definite time protection because once the setting is exceeded magnitude accuracy is not important. Often, however, there is also the need to consider instantaneous HighSet overcurrent protection as part of the same protection system and the settings would normally be of the order of 10x the CT rating or higher. Where higher settings are to be used then the overcurrent factor must be raised accordingly, e.g. to P Earth Fault Protection Considerations and requirements for earth fault protection are the same as for Phase fault. Usually the relay employs the same CT's e.g. three phase CTs star connected to derive the residual earth fault current. The accuracy class and overcurrent accuracy limit factors are therefore already determined and for both these factors the earth fault protection requirements are normally less onerous than for overcurrent. Minimum CT recommended rated Burdens are as follows: For 1A relays = 2.5VA For 5A relays = 7.5VA This allows for series connection of Argus phase /EF/SEF inputs (0.3VA at 1A and 0.8VA at 5A) and a maximum CT wiring loop burden of 2.2VA for 1A CT (e.g. up to 200 metres of 2.5sq mm copper wire or 6.7VA for 5A CT (e.g. up to 30 metres of 2.5 sq mm copper wire) 1.6 2TJM Burdens < 3VA at setting, for burden impedance characteristics see the 2TJM Manual. A major consideration for an electro-mechanical relay is its burden at nominal current. Selecting a low earth fault setting results in a high nominal burden. In these circumstances the rated burden of the CT must be chosen on the basis of the requirements of the earth fault element. 2. DUOBIAS 4C21 (Electro-Mechanical): Transformer Diffe rential Protection All CTs should be of the low reactance type and the knee point voltage (Vk) should be equal to, or exceed twice the maximum steady state working voltage under any through fault condition. To assess the steady state working voltage the impedances of the Duobias relays are ignored and only the CT winding and interconnecting lead resistances considered. As a general guide the knee point voltage Vk should equal or exceed:- For Star connected CTs - Vk equal or greater than 2.If (A+C) For Delta connected CTs - Vk equal or greater than 2.If (B+3D) If = Maximum through fault current referred to the secondary winding of the star connected CTs with a three phase system fault. 1.5 ARGUS Burdens AC rated Impedance A = Secondary winding resistance of each of the star connected CTs. K:\Arthur Allen\4 Arthur\C.T_Requirements_for_VATECH_Prot_Products_Dec03.doc Page 4 of 11

5 B = Secondary winding resistance of each delta connected CT C = Resistance of each lead between the star connected CT terminals and the relay terminals. D = Resistance of each lead between the delta connected terminals and the relay terminals. Class 'PX' current transformers to IEC 60044: pt1 can be specified to meet the above requirements, and this type are recommended. (Formerly class X to BS3938) 3. B3/5B3 (Electro-mechanical);DAD (Static); Argus 1/2 (Numeric High Impedance/REF): High Impedance Differential and Restricted Earth Fault Circulating Current Protection The basic requirements are: a) All the current transformers should have identical turns ratios. b) The knee point voltage of the current transformers should be at least twice the relay voltage setting. The knee point voltage is expressed as the voltage at fundamental frequency applied to the secondary circuit of the current transformer which when increased in magnitude by 10% causes the magnetising current to increase by 50%. c) The current transformers should be of the low leakage reactance type. Low leakage reactance CTs have a jointless core with the secondary winding evenly distributed along the whole length of the magnetic circuit, and the primary conductor passes through the centre of the core, alternatively a uniformly wound primary. Class 'PX' current transformers to IEC 60044: pt1 are recommended to meet the above requirements. 4. DUOBIAS M (Numeric): Transformer Differential and Restricted Earth Fault For high-speed operation under all fault conditions and for through fault stability the minimum current transformer knee point voltage should equal or exceed: Vk = 41 (Rct+Rl) I = The high-set differential should always be enabled and this setting value employed for the CT calculations. This will be higher than the maximum through fault current but considerably less than the maximum in-zone fault current. Rct = Secondary resistance of the current transformer in ohms Re = The maximum CT secondary loop lead resistance in ohms For restricted earth fault protection it is recommended that all CTs should have an equal number of secondary turns. Line CTs are normally star connected and standard ratios can be selected according to the transformer rating, ratios need not be exact provided they are within the range of the Duobias-M relay current settings ranges and do not cause the CT or relay thermal ratings to be exceeded. Ideally the line CT ratios should be selected to allow Duobias-M relay settings for CT ratio correction factors to be employed in order to balance the secondary current to normal relay current. This allows maximum sensitivity to be achieved for internal faults. Class 'PX' current transformers to IEC 60044: pt1 are recommended, to meet the above requirements. 5. SOLKOR R/RF (Electro-mechanical): Pilot Wire, Feeder Current Differential Protection The minimum knee point voltage of the line current transformers is given by: Vk = 50 + If (Rct + Rl) In N In = Nominal rated current of relay in amp s If = Primary current under maximum steady state through fault conditions N = Current transformer ratio Rct = Current transformer secondary resistance in ohms K:\Arthur Allen\4 Arthur\C.T_Requirements_for_VATECH_Prot_Products_Dec03.doc Page 5 of 11

6 Rl = The maximum CT secondary wiring loop lead resistance in ohms Generally it is not recomme nded that any other equipment burdens should be included in the current transformer circuit in order to avoid any possible mal-operation due to through-faults. However, in some instances the protection design often requires the inclusion of starting relays for the Solkor protection and occasionally the addition of i.d.m.t.l. protection to the same CTs, for backup protection. In such cases the extra burden should be carefully established and included in the calculation. The additional burden on each phase should be reasonably balanced. The secondary magnetising currents of the current transformer at opposite ends of the feeder should not differ by more than In/20 amperes for output voltage up to 50/In volts. To ensure good balance of the protection the current transformers at the two ends should have equal turns ratios. Close balance of ratio is provided by current transformers to IEC60044: pt1, class PX, whose ratio error is limited to ± 0.25% and these CTs are recommended to meet the above requirements. 6. SOLKOR N (Numeric): Feeder Current Differential Protection Ideally, CTs for current differential schemes should have a high knee-point voltage such that they do not saturate under maximum fault current plus associated X/R. However CTs meeting this requirement tend to be both large and expensive. To reduce CT size and cost, differential protection relay characteristics are designed to tolerate some degree of saturation. On Solkor N this is accommodated by the second stage of bias. Using the default second stage bias settings (which will be suitable for the vast majority of applications): Slope 2 = 150% I break = 2.0 x In And assuming a through-fault X/R <12, the minimum CT knee-point voltage can be calculated using; X/R = X/R ratio for the maximum through-fault condition (includes both sources and line impedance's). If = Primary current under maximum steady state through fault OR 7.5 x N I Break, whichever is the greater in amps. N = Current Transformer ratio. R CT = Current Transformer secondary Rl = The maximum CT secondary wiring loop lead resistance in ohms R b = Burden of the Relay in ohms For higher values of X/R, VA TECH Reyrolle should be contacted for advice. It is not recommended that any other burden should be included in the current transformer circuit, but where this cannot be avoided the additional burden should be added to those listed when determining the current transformer output voltage required. In addition to the above, the secondary magnetising currents of the current transformers at opposite ends of the feeder should not differ by more than In/20 amperes for output voltages up to 50/In volts. To ensure good balance of the protection the current transformers at the two ends should have equal turns ratios. Close balance of ratios is provided by current transformers to IEC60044:ptl, Class PX, ratio error limited to ± 0.25%, and these are recommended. 7. SOLKOR M (Numeric): Feeder Current Differential Protection The minimum knee point voltage for the line current transformer is given by: Vk = k x X/R x If/N x (Rct + Rl + Rb) where: k = stability factor = 0.3 for system voltages up to 33kV = 0.5 for system voltages of kV = 0.8 for system voltages 132kV and above X/R = X/R ratio for the maximum through fault conditions. (Includes both source and line impedance) If = primary current (amps) under maximum through-fault conditions Vk> ( X/R) x If/N x (R CT + Rl + R b ) Where N = Current Transformer ratio K:\Arthur Allen\4 Arthur\C.T_Requirements_for_VATECH_Prot_Products_Dec03.doc Page 6 of 11

7 Rct = Current transformer secondary resistance in ohms Rl = The maxi mum CT secondary wiring loop lead resistance in ohms Rb = burden of relay (ohms). The ac burden of the relay per phase is 0.05V at 1A for 1A tap = 0.05 ohm 0.3VA at 5A for 5A tap = ohm It is not recommended that any other burden should be included in the current transformer circuit, but where this cannot be avoided the additional burden should be added to those listed when determining the current transformer output voltage required. In addition to the above, the secondary magnetising currents of the current transformers at opposite ends of the feeder should not differ by more than In/20 amperes for output voltages up to 50/In volts. For example, consider a 33kV feeder with a worst case through-fault of 8kA with a X/R of 10. The minimum current transformer knee point required, given a turns ratio of 400:1, secondary CT resistance of 2Ω and max. lead loop burden of 2Ω is :- Vk 0.3 x 10 x 8000/400 x ( ) = 270volts The secondary burden of the two current transformers should be kept similar. This will then allow a low value of stability factor to be used, hence reducing the knee point voltage requirements of the current transformers. To ensure good balance between relays at each end of the circuit, the current transformers at the two ends shall have equal turns ratios. Close balance of ratios is provided by current transformers to IEC60044: pt1: class PX, the ratio error is limited to ±0.25%, and these are recommended 8. MicroPHASE-FM (Numeric): Current Differential The minimum knee point voltage for the line current transformers is given by: Vk = k x X/R x If/N x (Rct + Rl + Rb) K = stability factor = 0.8 X/R = X/R ratio for the maximum through-fault condition. (Includes both source line impedance's) If = Primary current under maximum steady state through fault conditions (amps) N = Current transformer ratio Rct = Current transformer secondary resistance in ohms Rl = The maximum CT secondary wiring loop lead resistance in ohms Rb = Burden of relay in ohms It is not recommended that any other burden should be included in the current transformer circuit, but where this cannot be avoided the additional burden should be added to those listed when determining the current transformer output voltage required. In addition to the above, the secondary magnetising currents of the current transformers at opposite ends of the feeder should not differ by more than In/20 amperes for output voltages up to 50/In volts. To ensure good balance between relays at each end of the protected circuit, the current transformers at the two ends shall have equal turns ratios. Close balance of ratios is provided by current transformers to IEC60044: pt1: class PX, the ratio error is limited to ±0.25%, and these are recommended Relay AC Burden per phase 0.05VA at 1A for 1A tap = 0.05 ohm 0.3VA at 5A for 5A tap = ohm Stability Under through-fault conditions the relay will be stable with fault current equivalent to 50 times the nominal current rating. 9. THR (Static): Distance (Impedance) Protecti on for overhead Transmission Circuits For high speed operation and accurate impedance measurement the CTs should be class PX to IEC60044: pt1 and have a knee point voltage (Vk) equal to or greater than the following:- Vk If [R1 + R2 + X/R (R3 + R2] K:\Arthur Allen\4 Arthur\C.T_Requirements_for_VATECH_Prot_Products_Dec03.doc Page 7 of 11

8 If = Secondary fault current for fault at end of Zone 1 R1 = Resistance burden of THR relay (see table below) R2 = Resistance of connected loads plus CT secondary winding plus lead loop resistances. X/R = Ratio of reactance to resistance of the system for a fault at the end of zone 1 R3 = Constant depending on impedance setting of zone 1 The table below gives values of R1 and R3 for a 1 Amp relay. To calculate values of R1 and R3 for 2A or 5A relays, divide values in the table by 4 or 25 respectively. Relay Nominal Rating (A) Setting of Zone to 4 4 to 8 8 to to to 48 R R3 Earth Phase Fault Fault OHMEGA 300/400 (Numeric): Distance (Impedance) Protection for Transmission Circuits For high speed operation and accurate impedance measurement the CTs should be class PX to EC60044; pt1 and have a knee point voltage (Vk) equal or greater than the higher of the following two expressions: a) For phase-phase faults :- Vk k. Ip (1 + Xp) ( Rct + Rl) N Rp b) For phase-earth faults :- Vk k. Ie (1 + Xe ) ( Rct + Rl) N Re Ip Ie N = Phase fault current calculated for Xp/Rp ratio at the end of zone 1 = earth fault current calculated for Xe/Re ratio at the end of zone 1 = CT ratio Xp/Rp = power system reactance to resistance ratio for the total plant including the feeder line parameters calculated for a phase fault at the end of zone 1 Xe/Re = similar ratio to above but calculated for an earth fault at the end of zone 1 Rct = CT internal resistance Rl K = lead burden, CT to Ohmega terminals = Factor chosen to ensure adequate operating speed and is <1. K is usually 0.5 for distribution systems. A higher value is chosen for primary transmission systems. Reyrolle ACP should be consulted. Both Vk values should be calculated, and the highest calculated value defines the CT to be used. 11. GAMMA (Numeric): Generator Protection a) Two off, 3 phase inputs (line end and neutral end) The current transformer minimum requirements depend on the protection application, the functions employed and the primary circuit configuration. For satisfactory operation of all functions, except the low impedance biased differential function, the use of a class 5P20 to IEC60044: pt1 or any equivalent, would be satisfactory for any application since the fault levels never exceed 20 x the CT rating. The VA rating is chosen to allow for all the circuit burden (e.g. CT secondary cabling and relay burden). For stability of the low impedance biased differential function it may be necessary to provide a design of CT which ensures neither of the two 3- phase sets of CTs are overfluxed, e.g. in the event of re-occurring, high magnitude fault current on circuits with a high X/R ratio source impedance. In these circumstances, the CTs can be left with a high level of remnant flux. Any subsequent faults may then cause one of the CTs to fully saturate and the differential function may mal-operate. If this is possible, e.g. for a directly connected generator (no generator transformer), where the two sets of CTs may be supplied by different manufacturers and with slightly different characteristics, and where there is a multi-shot delayed auto -reclose scheme on feeders local to the grid connection, or where the differential setting chosen is very sensitive, in these circumstances it is K:\Arthur Allen\4 Arthur\C.T_Requirements_for_VATECH_Prot_Products_Dec03.doc Page 8 of 11

9 recommended that any low reactance CTs (ie with high remanance factor) should have a knee point voltage compliant with the following formula:- Vk > 50In (Rct + Rl + Rb) Where maximum through fault current = 10 x In with maximum X/R = 120. Minimum Vk must be 60 volts. Vk > 30In (Rct + Re + Rb) Where maximum through fault current = 10 x In with maximum X/R = 60. Minimum Vk must be 60 volts Vk = Knee point voltage In = Rated current X/R = X/R ratio for the maximum through-fault condition Rct = Secondary resistance of the current transformer in ohms Rl = Lead loop resistance between the current transformers and the rela y in ohms Rb = Resistance of any other protection functions sharing the current transformer in ohms Where all the onerous conditions described above are not required to be met or the CT accommodation facility is limited, the requirements can be reduced. In these circumstances contact VA TECH Reyrolle ACP Ltd for advice. b) Neutral Earth C.T. Inputs: For solid earthed (e.g. direct connected generator), use the same specification for a class X c.t. as (a) above. For impedance earthed neutrals, a lower specification can be employed, e.g. 5P5. c) Use of CTs Common to More Than One GAMMA Relay Generally the CTs employed for generator protection should be dedicated to that one duty, for security of the protection. Technically however there is no reason why other equipment may not share the same CTs, provided that the additional burden is taken into account and also that the CTs for the three phase inputs should have a reasonably balanced burden on each phase. This ensures no possibility of mal-operation of the differential function. For the requirement of redundancy, there is no problem with the performance of either relay when connecting two Gamma relays is series. However, we recommend that the redundancy philosophy be extended and separate CTs used for each relay. Use of duplicate Gamma relays, particularly on high rated generator units e.g. over 15MW, provides a high level of security and integrity which is still cost effective. 12. RHO (Numeric): Motor Protection and Electrical Plant Thermal Overload 12.1 RHO 0 for low voltage 3 phase A.C. motors The RHO 0 relay is compatible with CTs having either 25mA or 5A secondary ratings. 25mA rated output CTs are recommended for motor currents up to 100A and 5A up to 3000A. For a 5amp relay input rating some motor control systems result in high multiples of rated current flowing during the start up period, and for some motors the run-up time may be very long e.g. 60 seconds. Because of this there are some limitations on the motor rating that can be utilised with a particular CT rating, due to the thermal capacity of the relay CT input terminals. If the motor rating is limited to less than 75% of the CT rating there is unlikely to be any problem with overheating no matter how onerous the starting current, the starting time or the number of starts in a period of time, i.e. for all practical considerations. The classification for the phase mounted CT s should be 10P10 or better (e.g. 5P10 for improved accuracy), and have a rating to suit the CT secondary total burdens, i.e. CT leads, the RHO 0 relay phase c.t. input burden and any equipment connected in series with the relay. The RHO 0 CT input circuit burden is fixed and is less than 0.25VA, e.g ohm at 5 amp The rated burden is therefore established by selecting a value in excess of the CT secondary circuit loading, e.g. for phase inputs:- K:\Arthur Allen\4 Arthur\C.T_Requirements_for_VATECH_Prot_Products_Dec03.doc Page 9 of 11

10 Rated VA In 2. (Rct + Rl + Rb + Re) In = Rated secondary current Rct = Current transformer secondary resistance in ohms Rl = Secondary lead loop resistance in ohms Rb = Relay circuit burden ohm for 5amp 11 ohm for 25mA Re = Other equipment burden in ohms per phase For earth fault detection RHO 0 has a separate input which can be employed from a separate core balance CT (CBCT). Alternatively the relay can be set to calculate the earth fault (3-phase residual) current. The CBCT solution is the preferred option and the CT is supplied with the relay, chosen based on motor rating and physical size of the main cables which need to be passed through the centre of the CBCT. The relay is set to the selected mode, e.g. Residual Connection or CBCT in the setting menu. In residual connection mode the trip setting and primary CT rating setting establish the pick-up level. In CBCT mode the primary current setting range is 30mA to 3000mA, and the CBCT ratio is chosen with this in mind to establish a required primary trip current. The actual current input range at the relay terminals is 0.06 to 6.0 milliamps RHO 3 for high voltage 3 phase A.C. motors and electrical plant The CT class recommended is 5P10. This provides accurate measurement for overloads and also for high current magnitudes beyond typical motor stall current e.g. 6 x full load current. The rated burden is established by selecting a value in excess of the CT secondary circuit loading e.g.- In = Rated secondary current Rct = Current transformer secondary resistance in ohms Rl = Secondary lead loop resistance in ohms Rb = Relay circuit burden ohm for 5 Amp 11 ohm for 25mA Re = Other equipment burden in ohms per phase RHO 3 Burdens:- AC Burden 5A Phase 0.2 VA 1A Phase 0.05 VA 5A Earth 0.4 VA 1A Earth 0.2 VA Impedance 0.01Ω 0.05Ω 0.02Ω 0.2Ω For earth fault detection RHO 3 has a separate input which can be employed either from a residual connection of the phase inputs or a separate core balance CT (the preferred option). There is no selection made within the relay, the primary current setting is determined by the re lay current setting and the CT ratio.. If a residual connection is employed and the earth fault setting chosen is both sensitive (e.g. less than 0.5In) and instantaneous, it is recommended that a stabilising resistor be employed in the earth fault input circuit. This must then be taken into account in establishing R1. For residual connection arrangement, Rb will be a summation of the phase fault and earth fault input burdens. 13. PH1 (Numeric): Point-on-Wave Circuit Breaker Controller The PH1 uses its current transformer inputs for monitoring and control rather than protection. The class of CT is therefore not important and either instrument or protection class CTs can be employed, i.e. any CTs already employed for another function. It is only necessary to ensure the additional small burden of the PH1 relay is included in the requirements of the CTs being employed. Rated VA In 2. (Rct +Rl + Rb + Re) K:\Arthur Allen\4 Arthur\C.T_Requirements_for_VATECH_Prot_Products_Dec03.doc Page 10 of 11

11 14. DELTA Feeder Manager The CT requirements for Accuracy Class and Overcurrent Accuracy Limit Factor, for Phase and Earth Fault circuits, are identical to those of the ARGUS Overcurrent relays. Generally, where high accuracy is needed, 5P20 CTs should be specified with VA rating to suit the load. Delta Burdens:- 5A Phase/Earth 1A Phase/Earth 5A SEF/REF 1A SEF/REF AC Burden < 0.2 VA < 0.05 VA < 0.4 VA < 0.2 VA Impedance < 0.01Ω < 0.05Ω < 0.02Ω < 0.2Ω 15. MICROTAPP Automatic Voltage Control The MicroTAPP uses its current transformer inputs for monitoring and control rather than protection. The class of CT is therefore not important and either instrument or protection class CTs can be employed i.e. any CTs already employed for another function. It is only necessary to ensure the additional small burden of the Micro TAPP relay is included in the requirements of the CTs being employed. MicroTAPP BURDENS:- 1 Amp 5 Amp AC Burden < 0.03 VA < 1 VA Impedance < 0.03Ω < 0.03Ω K:\Arthur Allen\4 Arthur\C.T_Requirements_for_VATECH_Prot_Products_Dec03.doc Page 11 of 11

Burdens & Current Transformer Requirements of MiCOM Relays. Application Notes B&CT/EN AP/B11. www. ElectricalPartManuals. com

Burdens & Current Transformer Requirements of MiCOM Relays. Application Notes B&CT/EN AP/B11. www. ElectricalPartManuals. com Burdens & Current Transformer Requirements of MiCOM Relays Application Notes B&CT/EN AP/B11 Application Notes B&CT/EN AP/B11 Burdens & CT Req. of MiCOM Relays Page 1/46 CONTENTS 1. ABBREVIATIONS & SYMBOLS

More information

2C73 Setting Guide. High Impedance Differential Relay. relay monitoring systems pty ltd Advanced Protection Devices

2C73 Setting Guide. High Impedance Differential Relay. relay monitoring systems pty ltd Advanced Protection Devices 2C73 Setting Guide High Impedance Differential Relay relay monitoring systems pty ltd Advanced Protection Devices 1. INTRODUCTION This document provides guidelines for the performance calculations required

More information

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Additional Options 15kV Isolation

More information

Unit Protection Differential Relays

Unit Protection Differential Relays Unit Protection PROF. SHAHRAM MONTASER KOUHSARI Current, pu Current, pu Protection Relays - BASICS Note on CT polarity dots Through-current: must not operate Internal fault: must operate The CT currents

More information

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd

2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd 2C73 Setting Guide High Impedance Differential Relay relay monitoring systems pty ltd Advanced Protection Devices 1. INTRODUCTION This document provides guidelines for the performance calculations required

More information

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Solkor R & Solkor Rf

More information

Electrical Protection System Design and Operation

Electrical Protection System Design and Operation ELEC9713 Industrial and Commercial Power Systems Electrical Protection System Design and Operation 1. Function of Electrical Protection Systems The three primary aims of overcurrent electrical protection

More information

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Additional Options Solkor

More information

Transformer Fault Categories

Transformer Fault Categories Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)

More information

7PG21 Solkor Rf Feeder Protection Energy Management

7PG21 Solkor Rf Feeder Protection Energy Management Reyrolle Protection Devices 7PG21 Solkor Rf Feeder Protection Energy Management 7PG21 Solkor Rf Contents Contents Technical Manual Chapters 1. Description of Operation 2. Performance Specification 3.

More information

Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602

Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602 Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602 1 / 12 1 INTRODUCTION This document provides guidelines for the performance calculations required for high impedance differential

More information

Transformer Protection

Transformer Protection Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis 1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current

More information

7SG14 Duobias-M Transformer Protection

7SG14 Duobias-M Transformer Protection 7SG14 Duobias-M Transformer Protection Document Release History This document is issue 2010/02. The list of revisions up to and including this issue is: Pre release Revision Date Change 2010/02 Document

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

Back to the Basics Current Transformer (CT) Testing

Back to the Basics Current Transformer (CT) Testing Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of

More information

MFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work

MFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work GE Grid Solutions MFAC High Impedance Differential Relay MFAC relays provide high speed differential protection for various types of power systems plants including generators, reactors, busbars, motors

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Type MCAG 14, 34 T&D. High Stability Circulating Current Relay

Type MCAG 14, 34 T&D. High Stability Circulating Current Relay PROTETION Type MAG, 3 High Stability irculating urrent Relay The MAG relay, used with a stabilising resistor, is designed for applications where sensitive settings with stability on heavy through faults

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd. Functional Range - Earth Fault Relay C&S Protection & Control Ltd. 2 Contents Page No. 1. Application 2. Operating Principle. Current Transformer Connections 5. Connections, Contact Arrangement and Setting

More information

PROTECTION of electricity distribution networks

PROTECTION of electricity distribution networks PROTECTION of electricity distribution networks Juan M. Gers and Edward J. Holmes The Institution of Electrical Engineers Contents Preface and acknowledgments x 1 Introduction 1 1.1 Basic principles of

More information

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series

More information

ISSN: Page 298

ISSN: Page 298 Sizing Current Transformers Rating To Enhance Digital Relay Operations Using Advanced Saturation Voltage Model *J.O. Aibangbee 1 and S.O. Onohaebi 2 *Department of Electrical &Computer Engineering, Bells

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Power Station Electrical Protection A 2 B 2 C 2 Neutral C.T E M L } a 2 b 2 c 2 M M M CT Restricted E/F Relay L L L TO TRIP CIRCUIT Contents 1 The Need for Protection 2 1.1 Types of Faults............................

More information

CONTENTS. 1. Introduction Generating Stations 9 40

CONTENTS. 1. Introduction Generating Stations 9 40 CONTENTS 1. Introduction 1 8 Importance of Electrical Energy Generation of Electrical Energy Sources of Energy Comparison of Energy Sources Units of Energy Relationship among Energy Units Efficiency Calorific

More information

Power systems 2: Transformation

Power systems 2: Transformation Power systems 2: Transformation Introduction In this series of articles, we will be looking at each of the main stages of the electrical power system in turn. s you will recall from our Introduction to

More information

~=E.i!=h. Pre-certification Transformers

~=E.i!=h. Pre-certification Transformers 7 Transformers Section 26 of the electrical code governs the use and installations of transformers. A transformer is a static device used to transfer energy from one alternating current circuit to another.

More information

Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content

Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION Sr. No. Course Content 1.0 Fault Current Calculations 1.1 Introduction to per unit and percentage impedance 1.2

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities

More information

Transformer Protection Principles

Transformer Protection Principles Transformer Protection Principles 1. Introduction Transformers are a critical and expensive component of the power system. Due to the long lead time for repair of and replacement of transformers, a major

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic

More information

2 Grounding of power supply system neutral

2 Grounding of power supply system neutral 2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the

More information

Impedance protection on power transformer.

Impedance protection on power transformer. Impedance protection on power transformer www.siemens.com/siprotec5 SIPROTEC 5 Application Impedance Protection on Power Transformer APN-045, Edition 1 Content 1...3 1.1 Introduction...3 1.2 Application

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

EASUN REYROLLE LIMITED

EASUN REYROLLE LIMITED OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT

More information

2015 Relay School Bus Protection Mike Kockott March, 2015

2015 Relay School Bus Protection Mike Kockott March, 2015 2015 Relay School Bus Protection Mike Kockott March, 2015 History of Bus Protection Circulating current differential (1900s) High impedance differential (1940s) Percentage restrained differential (1960s)

More information

9 Overcurrent Protection for Phase and Earth Faults

9 Overcurrent Protection for Phase and Earth Faults Overcurrent Protection for Phase and Earth Faults Introduction 9. Co-ordination procedure 9.2 Principles of time/current grading 9.3 Standard I.D.M.T. overcurrent relays 9.4 Combined I.D.M.T. and high

More information

1

1 Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive

More information

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example

More information

Enhanced Quality with a Touch of Style

Enhanced Quality with a Touch of Style Rudolf Current Transformer Enhanced Quality with a Touch of Style Current Transformer Enhanced Quality with a Touch of Style New Products Rudolf launched our new encapsulated current transformer. Portraying

More information

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at   Modeling and Analysis of Transformer ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering

More information

Deploying Current Transformers in Applications Greater Than 200 A

Deploying Current Transformers in Applications Greater Than 200 A Deploying Current Transformers in Applications Greater Than 200 A Andrew Schaeffler Step-down Current Transformers (CTs) are common, and useful, in large motor applications. They provide isolation between

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

Short-Circuit Current Calculations

Short-Circuit Current Calculations Basic Point-to-Point Calculation Procedure Step. Determine the transformer full load amps (F.L.A.) from either the nameplate, the following formulas or Table : Multiplier = 00 *% Z transformer Step 2.

More information

HPS Universal BUCK-BOOST TRANSFORMERS

HPS Universal BUCK-BOOST TRANSFORMERS BUCK-BOOST TRANSFORMERS Single and Three Phase Potted Buck-Boost Transformers Buck-Boost Applications & Standard Specification... 80 Selecting Buck-Boost Transformers... 81 Single Phase Selection Tables...

More information

Motor Protection. May 31, Tom Ernst GE Grid Solutions

Motor Protection. May 31, Tom Ernst GE Grid Solutions Motor Protection May 31, 2017 Tom Ernst GE Grid Solutions Motor Relay Zone of Protection -Electrical Faults -Abnormal Conditions -Thermal Overloads -Mechanical Failure 2 Setting of the motor protection

More information

COPYRIGHTED MATERIAL. Index

COPYRIGHTED MATERIAL. Index Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,

More information

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM BY MR. H. C. MEHTA AT 1 ST INDIA DOBLE PROTECTION AND AUTOMATION CONFERENCE, NOV 2008 POWER-LINKER Wisdom is not Virtue but Necessity hcmehta@powerlinker.org

More information

Differential Protection with REF 542plus Feeder Terminal

Differential Protection with REF 542plus Feeder Terminal Differential Protection with REF 542plus Application and Setting Guide kansikuva_bw 1MRS 756281 Issued: 09.01.2007 Version: A Differential Protection with REF 542plus Application and Setting Guide Contents:

More information

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

High-Tech Range. IRI1-ER- Stablized Earth Fault Current Relay. C&S Protection & Control Ltd.

High-Tech Range. IRI1-ER- Stablized Earth Fault Current Relay. C&S Protection & Control Ltd. High-Tech Range IRI1-ER- Stablized Earth Fault Current Relay C&S Protection & Control Ltd. Contents 1. Summary 7. Housing 2. Applications 3. Characteristics and features 4. Design 7.1 Individual housing

More information

CHAPTER 3 SOFTWARE DEVELOPMENT. communications, control design, test and measurement, financial modeling and analysis,

CHAPTER 3 SOFTWARE DEVELOPMENT. communications, control design, test and measurement, financial modeling and analysis, CHAPTER 3 SOFTWARE DEVELOPMENT 3.1 Introduction MATLAB has a wide range of applications, including signal and image processing, communications, control design, test and measurement, financial modeling

More information

Coordination of protective relays in MV transformer stations using EasyPower Protector software

Coordination of protective relays in MV transformer stations using EasyPower Protector software Coordination of protective relays in MV transformer stations using EasyPower Protector software S. Nikolovski, Member, IEEE, I. Provci and D. Sljivac In this paper, the analysis of digital protection relays

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES

More information

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria

More information

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June

More information

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software Govind Pandya 1, Rahul Umre 2, Aditya Pandey 3 Assistant professor, Dept. of Electrical & Electronics,

More information

Application of Low-Impedance 7SS601 Busbar Differential Protection

Application of Low-Impedance 7SS601 Busbar Differential Protection Application of Low-Impedance 7SS601 Busbar Differential Protection 1. Introduction Utilities have to supply power to their customers with highest reliability and minimum down time. System disturbances,

More information

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS Ljubomir KOJOVIC Cooper Power Systems - U.S.A. Lkojovic@cooperpower.com INTRODUCTION In steel facilities that use Electric Arc Furnaces (EAFs) to manufacture

More information

WATT TRANSDUCER. Instruction Manual

WATT TRANSDUCER. Instruction Manual WT 9200 WATT TRANSDUCER Instruction Manual IM-2 September 2003 USA: 6428 Ridglea Drive, Watauga, Texas 76148 Tel/Fax 1-817-427-2060/2067 E-mail: wes@westecinstruments.com SPECIFICATIONS Power Supply Input

More information

Problems connected with Commissioning of Power Transformers

Problems connected with Commissioning of Power Transformers Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.

More information

DOCUMENTATION SET 7SR224 RECLOSER CONTROLLER

DOCUMENTATION SET 7SR224 RECLOSER CONTROLLER (7) (7) (5) Applications Installation Guide 7SR224 7SR21 ARGUS-M 7SR21 Recloser 7SR22 ARGUS-M Controller 7SR21 DOCUMENTATION SET This document is part of a set. The full list of documents in the set, and

More information

Centralized busbar differential and breaker failure protection function

Centralized busbar differential and breaker failure protection function Centralized busbar differential and breaker failure protection function Budapest, December 2015 Centralized busbar differential and breaker failure protection function Protecta provides two different types

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE Professor Akhtar Kalam Victoria University The Problem Calculate & sketch the ZPS, NPS & PPS impedance networks. Calculate feeder faults. Calculate

More information

PIPSPC. Prepared by Eng: Ahmed Safie Eldin. And. Introduction. Protection Control. Practical. System. Power

PIPSPC. Prepared by Eng: Ahmed Safie Eldin. And. Introduction. Protection Control. Practical. System. Power PIPSPC Practical Introduction Power System Protection Control Practical Introduction To Power System Protection And Control Prepared by Eng: Ahmed Safie Eldin 2005 Contents POWER SYSTEMS PRINCIPALS. 1

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

Beyond the Knee Point: A Practical Guide to CT Saturation

Beyond the Knee Point: A Practical Guide to CT Saturation Beyond the Knee Point: A Practical Guide to CT Saturation Ariana Hargrave, Michael J. Thompson, and Brad Heilman, Schweitzer Engineering Laboratories, Inc. Abstract Current transformer (CT) saturation,

More information

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS Juan Manuel Gers, PhD Protection coordination principles Relay coordination is the process of selecting settings that will assure that the relays

More information

High Voltage Busbar Protection

High Voltage Busbar Protection High Voltage Busbar Protection Course No: E05-012 Credit: 5 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F:

More information

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection) Differential Protection (Unit protection) Differential Protection Differential protection is the best technique in protection. In this type of protection the electrical quantities entering and leaving

More information

Protection Introduction

Protection Introduction 1.0 Introduction Protection 2 There are five basic classes of protective relays: Magnitude relays Directional relays Ratio (impedance) relays Differential relays Pilot relays We will study each of these.

More information

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:

More information

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS S1. Standard Interconnection Methods with Typical Circuit Configuration for Single or Multiple Units Note: The protection requirements

More information

ESB National Grid Transmission Planning Criteria

ESB National Grid Transmission Planning Criteria ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and

More information

Catastrophic Relay Misoperations and Successful Relay Operation

Catastrophic Relay Misoperations and Successful Relay Operation Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations

More information

3 Pole high impedance differential relay 7VH83

3 Pole high impedance differential relay 7VH83 Fig 1. High impedance differential protection relay 7VH83 Features l Integral CT shorting relay. l Robust solid state design. l Inrush stabilisation through filtering. l Fast operating time. l LED indicator.

More information

Transmission System Phase Backup Protection

Transmission System Phase Backup Protection Reliability Guideline Transmission System Phase Backup Protection NERC System Protection and Control Subcommittee Draft for Planning Committee Approval June 2011 Table of Contents 1. Introduction and Need

More information

Line protection with transformer in the protection zone

Line protection with transformer in the protection zone Line protection with transformer in the protection zone www.siemens.com/siprotec5 Three-end line protection with transformer in the protection range SIPROTEC 5 Application Three-end line protection with

More information

Alternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER

Alternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER Alternative Testing Techniques for Current Transformers Dinesh Chhajer, PE Technical Support Group MEGGER Agenda Current Transformer Definition and Fundamentals Current Transformer Applications o Metering

More information

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11 Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11 COMMISSIONING 12-16 DRAWINGS 17-18 1 1. INTRODUCTION APPLICATION

More information

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with

More information

EE402-Protection and Switchgear Dept. of EEE

EE402-Protection and Switchgear Dept. of EEE UNIT II - ELECTROMAGNETIC RELAYS Part A 1. Name the different kinds of over current relays. Induction type non-directional over current relay, Induction type directional over current relay & current differential

More information

Earth Fault Relay EFSPL-1A/5A

Earth Fault Relay EFSPL-1A/5A Earth Fault Relay EFSPL-1A/5A IEEE DEVICES CODE-50N Features Static Device Compact, Reliable with Aesthetic Value Rugged, Robust and Tropicalised design Consistent repeat accuracy Wide Current Operating

More information

WHITE PAPER. Medium Voltage On-Site Generation Overview. BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems

WHITE PAPER. Medium Voltage On-Site Generation Overview. BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems WHITE PAPER Medium Voltage On-Site Generation Overview BY MIKE KIRCHNER Technical Support Manager at Generac Power Systems INTRODUCTION It seems that just about everyone is looking for more power. As our

More information

Chapter 6. WIRING SYSTEMS Safe Electrical Design

Chapter 6. WIRING SYSTEMS Safe Electrical Design Chapter 6 WIRING SYSTEMS Safe Electrical Design Topic 6-3 CABLE SELECTION BASED ON CURRENT CARRYING CAPACITY REQUIREMENTS INSTALLATION CONDITIONS Current carrying capacity (CCC) is the maximum continuous

More information

Generator Protection GENERATOR CONTROL AND PROTECTION

Generator Protection GENERATOR CONTROL AND PROTECTION Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault

More information

Solutions to Consider in Current Transformer Selection for APR1400 Nuclear Power Plant Medium Voltage Switchgears

Solutions to Consider in Current Transformer Selection for APR1400 Nuclear Power Plant Medium Voltage Switchgears Journal of Energy and Power Engineering 11 (2017) 670-678 doi: 10.17265/1934-8975/2017.10.008 D DAVID PUBLISHING Solutions to Consider in Current Transformer Selection for APR1400 Nuclear Power Plant Medium

More information