ECE456 Power System Protection

Size: px
Start display at page:

Download "ECE456 Power System Protection"

Transcription

1 ECE456 Power System Protection Assignment : #5 (Solutions) 1. A phase b-c-g fault is experienced at F in the system shown in figure 1. Calculate the impedances seen by the b-c, b-g and c-g units of the distance relay installed at circuit breaker 2. Solution Figure 1 The equivalent sequence diagram for the given system and its connection for a B-C-G fault are shown below in figure 1a and 1b respectively. For a two phase to ground fault all the three impedance networks are connected in parallel at the fault point as shown in figure 1b. In addition since the transformer configuration is YnD, there will not be any zero sequence current at the relay location for ground faults on the star side of the transformer. 1 Of 11

2 Figure 1a Figure 1b The three phase transformer ratio is considered to be 1. Since we are only interested in finding the impedance at location 2, we have not considered the 30 shift in the sequence currents introduced by the transformer (this shift will affect the phase relationship between the currents and voltages across the primary and secondary of the transformer and will not affect the phase relationship between voltages and currents on any one side). We can calculate the sequence currents and voltages at the relay point looking at the figure 1b as follows (All values are given in per unit) Total equivalent impedance; Zeq = Zs1+ZL1+Zt1+Zt2+ZL2+Zs2 = j 1.14 pu. Sequence currents at the relay location ir1 = E1/Zeq = 1/( j1.14) = j pu ir2 = -ir1 = j pu ir0 = 0 Sequence voltages at the relay location vr1 = E1-iR1*Zs1 = j pu vr2 = -ir2*zs2 = j pu vr0 = 0 The phase currents and voltages can then be calculated as, ira=ir0+ir1+ir2 = 0 pu irb = ir0 + a 2 * ir1 + a * ir2 = j pu = <-179º irc = ir0 + a * ir1 + a 2 * ir2 = j pu m = <1.005 º irn = ira+irb+irc = 0 2 Of 11

3 vra=vr0+vr1+vr2 = i pu = < º vrb = vr0 + a 2 * vr1 + a * vr2 = j pu = < º vrc = vr0 + a * vr1 + a 2 * vr2 = j pu = < º The impedance measured by BC, B-G and C-G units are calculated as BC = (vrb RB-vRC)/(iRB vrc)/(irb-irc) irc) = j 0.37 pu ZBC BG = vrb/(irb+k*irn) = j pu CG = vrc/(irc+k*irn) = j pu ZBG ZCG Where k is the earthfault compensation setting of the impedance relay calculated as k = (z0 - z1)/(3*z1) 2. A three-phase line is connected to sources A, B and C (figure 2). A threephase fault occurs at the half way point between T and C. Calculate the impedance seen by the relays at circuit breaker 1 and 2 before any circuit breaker open. Assume that the voltages of all the three sources are 1.0 p.u. Solution Figure 2 The equivalent circuit of the above system can be drawn as shown in the figure 2a below; 3 Of 11

4 j0.2 j0.35 j0.05 j0.05 j0.25 Figure 2a Which can be re-drawn for reduction as shown in figure 2b; A j0.2 T j0.15 B j0.2 c j0.35 j0.05 j0.05 I T j0.25 E 1.0 pu Figure 2b From the above circuit we can find the fault current and current flowing in different branches as; Ic = E / j( ) = 1.0 / j( ) = -j 2.5 pu E 1.0 It = = = j j j If = It + Ib = -j ( ) = -j 6.5 pu 0.4 Ia = j 4 = j Of 11

5 Ic = It-Ia = -j(4-2) = -j 2 We have been asked to calculate the impedance seen by the relays at circuit breaker 1 (location A) and circuit breaker 3 (location C). Impedance seen by relay at A, Za = Va/Ia Where Va, is the voltage at the point A with respect to ground. This voltage can be found as Va = E Ia * j 0.20 = 1.0 (-j 2) * (j 0.20) = 0.6 pu Therefore, Za = Va/Ia = 0.6 / (-j ( 2) ) = j 0.3 p.u But from the system diagram we know that the relay at A should have measured only =0.25 p.u, but in actual case the relay measures higher impedance and thus will make it to underreach. This under reaching is due to the infeed at point T from the source B. Similarly the impedance seen by the relay at B, Zb = Vb/Ib Where Vb, is the voltage at the point B with respect to ground. This voltage can be calculated as Vb = E Ib * j 0.25 = 1.0 (-j 2) * (j 0.25) = 0.5 pu Therefore, Zc = Vb/Ib = 0.5 / (-j ( 2) ) = j 0.25 p.u. Again we know that the relay at C should have measured only =0.2 p.u, but due to the infeed at T from the source A, the relay measures the fault impedance as 0.25 p.u., thus causing it to underreach. 3. Determine the three zone settings for the relay Rab in the system shown in figure 3. The system nominal voltage is 138 kv and the positive sequence impedances for the various elements are given in the figure3. Assume that the maximum load at the relay site is 120MVA, and select a CT ratio accordingly. The available distance relay has zone 1 and zone 2 5 Of 11

6 settings from 0.2 to 10 ohms and zone 3 settings from 0.5 to 40 ohms in increments of 0.1 ohm. The angle of maximum torque can be adjusted to 75 or 90. Solution Figure 3 First we have to select an appropriate CT. The primary of the CT should be close to the maximum load current. In our case the maximum load current is given as 120MVA, therefore the load current can be calculated as I L = = 502A Thus we can select a CT ratio of 600:5 Since the system voltage is given as 138KV, the VT ratio would be 138KV/120V Thus the impedance transformation ratio (for transforming the impedance from system primary to relay secondary values) will be Tr = CTR / VTR = (600/5) / (138000/120) = Zone 1 of the relay has to be set to protect 80% of the line, thus Z1 = 0.8 * (3+j40) * = Ω Since the setting range available in the relay for impedance is in steps of 0.1Ω, we will set the zone 1 as 3.3Ω. 6 Of 11

7 The angle setting available in the relay is either 75 or 90 only. So select the angle setting as 90 Zone 2 of the relay has to be set to protect atleast 120% of the protected line. At the same time this setting should not reach beyond the zone 1 setting of the shortest downstream line relay, which is the relay on line BD. So we can write that the Z2 setting should be more than Z2min = 1.2 * (3+j40) * = Ω And less than Z2max = [(3+j40)+0.8*(1.5+j25)] * = Ω So we will set the Z2 to 5.5 Ω, which would cover 100% of the protected line and 50% of the shortest adjacent line Zone 3 element of the relay should provide back-up protection to the longest line from the remote bus, which in this problem is the line BE, with 5+j100 Ω impedance. Normally it s a practice to set the Z3 as 110% of the sum of the protected line plus the longest adjacent line. So we get; Z3 = 1.1*(3+j j100) * = Ω Select a Z3 setting of 14.6 Ω, which would be a value settable in the given realy. So the settings for the relay Rab would be Zone Ω Zone Ω Zone Ω Relay characteristic angle 90 4 Consider the system shown in figure 4, assume that F in that figure is a AG fault at the end of the line. Considering no load condition, calculate the impedance seen by AG unit of the relay at circuit breaker 2 for the two following cases: a. the current in the parallel circuit is available to the relay at breaker 2 7 Of 11

8 b. the current in the parallel circuit is not available to the relay at breaker 2 Figure 4 Solution In order to calculate the seen impedance, fault calculation should be performed to determine the fault currents and voltages at the relay 2 and 3 locations. Since there is AG fault, three sequence network are in series as shown in Figure 5. Figure 5 8 Of 11

9 In order to calculate the fault current simplified sequence network shown in right hand side of figure 5 is used to drive equivalent sequence impedances as follow: Zeqpos=ZL1pos*ZL2pos/(ZL1pos+ZL2pos)+Zs1= j Zeqneg=Zeqpos= j Zeqzero=(ZL1zero*ZL2zero-ZLm0^2)/( ZL1zero+ZL2zero-2*ZLm0)+Zs0= j Fault current is calculated as below Ifzero=230/sqrt(3)/(Zeqpos+Zeqneg+Zeqzero)= j Ifpos=Ifzero= j Ifneg=Ifzero= j Fault current seen by relay 2 IR2pos=Ifpos*ZL2pos/(ZL1pos+ZL2pos)= j IR2neg=Ifneg*ZL2neg/(ZL1neg+ZL2neg)= j IR2zero=Ifzero*(ZL2zero-ZLm0)/(ZL1zero+ZL2zero-2*ZLm0)= j IR2a=1.8208< IR2b= < IR2c= < Fault current seen by relay 3 IR3pos=Ifpos*ZL1pos/(ZL1pos+ZL2pos)= j IR3neg=Ifneg*ZL1neg/(ZL1neg+ZL2neg)= j IR3zero=Ifzero-IR2zero = j Voltage at relay point is calculated: VRpos=230/sqrt(3)-Zs1*Ifpos = j VRneg=-Zs2*Ifneg = j VRzero=-Zs0*Ifzero = j VRa= < VRb= < VRc= < k0=(zl1zero - ZL1pos)/(ZL1pos)= j k0m=(zlm0)/(zl1pos) = Of 11

10 a) For double circuit line having access to second line current, seen impedance is calculated from following equation: ZR2seen=VRa/(IR2a+k0*IR2zero+k0m*IR3zero)=4+j40 Ω b) if there is no access to second line current, IR3zero should be considered as zero in above equation. Hence we have: ZR2seen=VRa/(IR2a+k0*IR2zero) = j Ω As you see, relay2 under-reaches in this case. 5 A zone of a distance relay with mho characteristic is set at 10 ohms secondary. The CT ratio is 500:5 and the VT ratio is 20,000: What is the fault resistance, which this relay tolerates for a fault at a distance of 80% of the zone boundary? You may assume that the remote terminal of the line is out of service. The line impedance angle is equal to 80 while the relay maximum torque angle is equal to 70. Solution We have to calculate the available fault resistance coverage at 80% of the relay impedance setting for mho characteristics. For this we have to find the distance of the zone boundary from the relay characteristics line at 80% parallel to the R axis (0 ). We can either do this by constructing the characteristics on a graph paper and measuring the distance or by analytical geometry as follows; 10 Of 11

11 Relay Characteristic Line 8sin(80)= x Figure 5a Referring to figure 5a, we can write We have to find the point on the circle which has the same longitude as the 80 percent of the transmission line characteristic as below: (x-5cos(70)) 2 + (8*sin(80)-5sin(70)) 2 = 5 2 By solving above equation: X= & According to the figure 5a, is acceptable. Fault resistance of relay characteristics at 80% of setting can be faind as R = cos(80) = 4.18 Ω Impedance transformation ratio = (500/5)/(20000/69.3) = The relay will operate for a fault resistance upto 4.18/0.347 = Ω (primary) at 80% of its setting 11 Of 11

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed

More information

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME Donald M. MACGREGOR Electrocon Int l, Inc. USA eii@electrocon.com Venkat TIRUPATI Electrocon Int l, Inc. USA eii@electrocon.com Russell

More information

Using Event Recordings

Using Event Recordings Feature Using Event Recordings to Verify Protective Relay Operations Part II by Tony Giuliante, Donald M. MacGregor, Amir and Maria Makki, and Tony Napikoski Fault Location The accuracy of fault location

More information

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June

More information

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS Juan Manuel Gers, PhD Example - Single Line Example 1 - Data Calculate the following: 1. The three phase short circuit levels on busbars

More information

Distance Relay Response to Transformer Energization: Problems and Solutions

Distance Relay Response to Transformer Energization: Problems and Solutions 1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering

More information

Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK

Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK Omar G. Mrehel Hassan B. Elfetori AbdAllah O. Hawal Electrical and Electronic Dept. Operation Department Electrical

More information

which is used to shift the phase angle between the two sets of coils to produce torque.

which is used to shift the phase angle between the two sets of coils to produce torque. KLF-1 SCOPE This test procedure covers the testing and maintenance of the ABB KLF-1 loss of excitation relay. The Westinghouse Protective Relay Division was purchased by ABB, and new relays carry the ABB

More information

AEP s 765kV Transmission Line Model Validation for Short Circuit and System Studies. T. YANG, Q. QIU, Z. CAMPBELL American Electric Power USA

AEP s 765kV Transmission Line Model Validation for Short Circuit and System Studies. T. YANG, Q. QIU, Z. CAMPBELL American Electric Power USA 1, rue d Artois, F-75008 PARI CIGRE U National Committee http : //www.cigre.org 015 Grid of the Future ymposium AEP s 765kV Transmission Line Model Validation for hort Circuit and ystem tudies T. YANG,

More information

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE Professor Akhtar Kalam Victoria University The Problem Calculate & sketch the ZPS, NPS & PPS impedance networks. Calculate feeder faults. Calculate

More information

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS) SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS) SLIDE In this video, we will cover a sample exam problem for the Power PE Exam. This exam problem falls under the topic of Protection, which accounts for

More information

which is used to shift the phase angle between the two sets of coils to produce torque.

which is used to shift the phase angle between the two sets of coils to produce torque. KLF SCOPE This test procedure covers the testing and maintenance of the ABB KLF loss of excitation relay. The Westinghouse Protective Relay Division was purchased by ABB, and new relays carry the ABB label.

More information

Setting Generic Distance Relay UTP-100#WPSC1. in the. Computer-Aided Protection Engineering System (CAPE)

Setting Generic Distance Relay UTP-100#WPSC1. in the. Computer-Aided Protection Engineering System (CAPE) Setting Generic Distance Relay UTP-100#WPSC1 in the Computer-Aided Protection Engineering System (CAPE) Prepared for CAPE Users' Group August 6, 1998 Revised August 24, 1998 Electrocon International, Inc.

More information

Unit 8 Combination Circuits

Unit 8 Combination Circuits Unit 8 Combination Circuits Objectives: Define a combination circuit. List the rules for parallel circuits. List the rules for series circuits. Solve for combination circuit values. Characteristics There

More information

Performance Assessment of Distance Relay using MATLAB DibyaDarshiniMohanty, Ashwin Sharma, Ashutosh Varma M.S.I.T. M.S.I.T. M.S.I.

Performance Assessment of Distance Relay using MATLAB DibyaDarshiniMohanty, Ashwin Sharma, Ashutosh Varma M.S.I.T. M.S.I.T. M.S.I. Performance Assessment of Distance Relay using MATLAB DibyaDarshiniMohanty, Ashwin Sharma, Ashutosh Varma M.S.I.T. M.S.I.T. M.S.I.T Abstract This paper studies the performance of distance relay using MATLAB.

More information

In Class Examples (ICE)

In Class Examples (ICE) In Class Examples (ICE) 1 1. A 3φ 765kV, 60Hz, 300km, completely transposed line has the following positive-sequence impedance and admittance: z = 0.0165 + j0.3306 = 0.3310 87.14 o Ω/km y = j4.67 410-6

More information

Teaching Distance Relay Using Matlab/Simulink Graphical User Interface

Teaching Distance Relay Using Matlab/Simulink Graphical User Interface Available online at www.sciencedirect.com Procedia Engineering 53 ( 2013 ) 264 270 Malaysian Technical Universities Conference on Engineering & Technology 2012, MUCET 2012 Part 1 - Electronic and Electrical

More information

Adaptive Settings Of Distance Relay For MOV- Protected Series Compensated Line With Distributed Capacitance Considering Wind Power

Adaptive Settings Of Distance Relay For MOV- Protected Series Compensated Line With Distributed Capacitance Considering Wind Power Clemson University TigerPrints All Theses Theses 5-216 Adaptive Settings Of Distance Relay For MOV- Protected Series Compensated Line With Distributed Capacitance Considering Wind Power Oleg Viktorovich

More information

Transmission System Phase Backup Protection

Transmission System Phase Backup Protection Reliability Guideline Transmission System Phase Backup Protection NERC System Protection and Control Subcommittee Draft for Planning Committee Approval June 2011 Table of Contents 1. Introduction and Need

More information

MV network design & devices selection EXERCISE BOOK

MV network design & devices selection EXERCISE BOOK MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester

More information

Practical Transformer on Load

Practical Transformer on Load Practical Transformer on Load We now consider the deviations from the last two ideality conditions : 1. The resistance of its windings is zero. 2. There is no leakage flux. The effects of these deviations

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

Chapter 2: Transformers

Chapter 2: Transformers Chapter 2: Transformers 2-1. The secondary winding of a transformer has a terminal voltage of v s (t) = 282.8 sin 377t V. The turns ratio of the transformer is 100:200 (a = 0.50). If the secondary current

More information

INSTRUCTION MANUAL DISTANCE RELAY GRZ100 - D

INSTRUCTION MANUAL DISTANCE RELAY GRZ100 - D INSTRUCTION MANUAL DISTANCE RELAY GRZ00 - D Toshiba Energy Systems Solutions Corporation 207 All Rights Reserved. ( Ver. 2.2 ) Safety Precautions Before using this product, please read this chapter carefully.

More information

Distance Protection in Distribution Systems: How It Assists With Integrating Distributed Resources

Distance Protection in Distribution Systems: How It Assists With Integrating Distributed Resources 1 Distance Protection in Distribution Systems: How It Assists With Integrating Distributed Resources David Martin and Pankaj Sharma, Hydro One Networks Inc. Amy Sinclair and Dale Finney, Schweitzer Engineering

More information

Summary of Relaying Reviews Reporting

Summary of Relaying Reviews Reporting Revised Attachment B (Agenda Item 6) Summary of Relaying Reviews -- 12-31-04 Reporting This form shall be used without modification to provide a summary of relaying reviews performed by each Transmisission

More information

Generator Protection GENERATOR CONTROL AND PROTECTION

Generator Protection GENERATOR CONTROL AND PROTECTION Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault

More information

Breaker Pole Scatter and Its Effect on Quadrilateral Ground Distance Protection

Breaker Pole Scatter and Its Effect on Quadrilateral Ground Distance Protection Breaker Pole Scatter and Its Effect on Quadrilateral Ground Distance Protection James Ryan Florida Power & Light Company Arun Shrestha and Thanh-Xuan Nguyen Schweitzer Engineering Laboratories, Inc. 25

More information

IGEE 402 Power System Analysis. FINAL EXAMINATION Fall 2004

IGEE 402 Power System Analysis. FINAL EXAMINATION Fall 2004 IGEE 40 Power System Analysis FINAL EXAMINATION Fall 004 Special instructions: - Duration: 150 minutes. - Material allowed: a crib sheet (double sided 8.5 x 11), calculator. - Attempt 4 out of 7 questions.

More information

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,

More information

Time-current Coordination

Time-current Coordination 269 5.2.3.1 Time-current Coordination Time that is controlled by current magnitude permits discriminating faults at one location from another. There are three variables available to discriminate faults,

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Short-Circuit Analysis IEC Standard 1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Purpose of Short-Circuit Studies A Short-Circuit Study can be used to determine any or all of

More information

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions

More information

Mho. MiCOMho P443. A Guide How To Draw and Test P443 Distance Characteristics using Omicron

Mho. MiCOMho P443. A Guide How To Draw and Test P443 Distance Characteristics using Omicron Mho MiCOMho P443 A Guide How To Draw and Test P443 Distance Characteristics using Omicron This document serves as a guide how to draw P443 Mho and Quad characteristics. P443 is a self+memory polarised

More information

Phase Rolling and the Impacts on Protection

Phase Rolling and the Impacts on Protection Phase Rolling and the Impacts on Protection Denglin (Dennis) Tang Burns & McDonnell 1700 West Loop South, Houston, TX 77027 Office: (713) 622-0227 Fax: (713) 622-0224 dtang@burnsmcd.com Abstract: During

More information

, ,54 A

, ,54 A AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate

More information

Distance Protection. Course No: E Credit: 4 PDH. Velimir Lackovic, Char. Eng.

Distance Protection. Course No: E Credit: 4 PDH. Velimir Lackovic, Char. Eng. Distance Protection Course No: E04-034 Credit: 4 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There? What Is a Distance Protection Element?

Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There? What Is a Distance Protection Element? Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There? Edmund O. Schweitzer, III and Bogdan Kasztenny Schweitzer Engineering Laboratories Copyright SEL 2017

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Using a Multiple Analog Input Distance Relay as a DFR

Using a Multiple Analog Input Distance Relay as a DFR Using a Multiple Analog Input Distance Relay as a DFR Dennis Denison Senior Transmission Specialist Entergy Rich Hunt, M.S., P.E. Senior Field Application Engineer NxtPhase T&D Corporation Presented at

More information

Modeling and Performance Analysis of Mho-Relay in Matlab

Modeling and Performance Analysis of Mho-Relay in Matlab Modeling and Performance Analysis of Mho-Relay in Matlab Purra Sai Kiran M.Tech Student, Padmasri Dr. B V Raju Institute of Technology, Narsapur, Medak, Telangana. ABSTRACT: This paper describes the opportunity

More information

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost

More information

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost

More information

Distance Element Performance Under Conditions of CT Saturation

Distance Element Performance Under Conditions of CT Saturation Distance Element Performance Under Conditions of CT Saturation Joe Mooney Schweitzer Engineering Laboratories, Inc. Published in the proceedings of the th Annual Georgia Tech Fault and Disturbance Analysis

More information

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525.

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525. Time Overcurrent Relays More or less approximates thermal fuse» Allow coordination with fuses Direction of Current nduced Torque Restraining Spring Reset Position Time Dial Setting Disk Basic equation

More information

Relay-assisted commissioning

Relay-assisted commissioning Relay-assisted commissioning by Casper Labuschagne and Normann Fischer, Schweitzer Engineering Laboratories (SEL) Power transformer differential relays were among the first protection relays to use digital

More information

RELAY LOADABILITY CHALLENGES EXPERIENCED IN LONG LINES. Authors: Seunghwa Lee P.E., SynchroGrid, College Station, Texas 77845

RELAY LOADABILITY CHALLENGES EXPERIENCED IN LONG LINES. Authors: Seunghwa Lee P.E., SynchroGrid, College Station, Texas 77845 RELAY LOADABILITY CHALLENGES EXPERIENCED IN LONG LINES Authors: Seunghwa Lee P.E., SynchroGrid, College Station, Texas 77845 Joe Perez P.E., SynchroGrid, College Station, Texas 77802 Presented before the

More information

Electric Circuits I. Simple Resistive Circuit. Dr. Firas Obeidat

Electric Circuits I. Simple Resistive Circuit. Dr. Firas Obeidat Electric Circuits I Simple Resistive Circuit Dr. Firas Obeidat 1 Resistors in Series The equivalent resistance of any number of resistors connected in series is the sum of the individual resistances. It

More information

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series

More information

2015 Relay School Bus Protection Mike Kockott March, 2015

2015 Relay School Bus Protection Mike Kockott March, 2015 2015 Relay School Bus Protection Mike Kockott March, 2015 History of Bus Protection Circulating current differential (1900s) High impedance differential (1940s) Percentage restrained differential (1960s)

More information

Notes 1: Introduction to Distribution Systems

Notes 1: Introduction to Distribution Systems Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission

More information

DOUBLE-ENDED FAULT LOCATORS

DOUBLE-ENDED FAULT LOCATORS The InterNational Electrical Testing Association Journal FEATURE END-TO-END TESTING OF DOUBLE-ENDED FAULT LOCATORS BY STEVE TURNER, Beckwith Electric Company, Inc.. www.netaworld.org FOR HIGH VOLTAGE,

More information

An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays

An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third one of Distance Relays M. Azari, M. Ojaghi and K. Mazlumi* Electrical Engineering Department University of anjan anjan,

More information

To Ground or Not to Ground? That is the Question. Bill Kersting

To Ground or Not to Ground? That is the Question. Bill Kersting To Ground or Not to Ground? That is the Question Bill Kersting What Was Taught A grounded wyedelta transformer connection will serve threephase loads upon loss of a primary phase An ungrounded wyedelta

More information

Adaptive Phase and Ground Quadrilateral Distance Elements

Adaptive Phase and Ground Quadrilateral Distance Elements Adaptive Phase and Ground Quadrilateral Distance Elements Fernando Calero, Armando Guzmán, and Gabriel Benmouyal Schweitzer Engineering Laboratories, Inc. evised edition released November 217 Previously

More information

Figure 1 System One Line

Figure 1 System One Line Fault Coverage of Memory Polarized Mho Elements with Time Delays Hulme, Jason Abstract This paper analyzes the effect of time delays on the fault resistance coverage of memory polarized distance elements.

More information

9 Overcurrent Protection for Phase and Earth Faults

9 Overcurrent Protection for Phase and Earth Faults Overcurrent Protection for Phase and Earth Faults Introduction 9. Co-ordination procedure 9.2 Principles of time/current grading 9.3 Standard I.D.M.T. overcurrent relays 9.4 Combined I.D.M.T. and high

More information

LRC Circuit PHYS 296 Your name Lab section

LRC Circuit PHYS 296 Your name Lab section LRC Circuit PHYS 296 Your name Lab section PRE-LAB QUIZZES 1. What will we investigate in this lab? 2. Figure 1 on the following page shows an LRC circuit with the resistor of 1 Ω, the capacitor of 33

More information

PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay

PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay PSCAD Simulation High Resistance Fault in Transmission Line Protection Using Distance Relay Anurag Choudhary Department of Electrical and Electronics Engineering College of Engineering Roorkee, Roorkee

More information

SIPROTEC 5 Application Note

SIPROTEC 5 Application Note www.siemens.com/protection SIPROTEC 5 Application Note SIP5-APN-015: Answers for infrastructure and cities. SIPROTEC 5 - Application: SIP5-APN-015 Content 1 Application 3 1.1 Introduction 3 1.2 Overview

More information

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when

More information

Conventional Paper-II-2013

Conventional Paper-II-2013 1. All parts carry equal marks Conventional Paper-II-013 (a) (d) A 0V DC shunt motor takes 0A at full load running at 500 rpm. The armature resistance is 0.4Ω and shunt field resistance of 176Ω. The machine

More information

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS DFFERENTAL PROTECTON METHODOLOGY FOR ARBTRARY THREE-PHASE POWER TRANSFORMERS Z. Gaji ABB AB-SA Products, Sweden; zoran.gajic@se.abb.com Keywords: power transformer, phase shifting transformer, converter

More information

Protection Challenges for Transmission Lines with Long Taps

Protection Challenges for Transmission Lines with Long Taps Protection Challenges for Transmission Lines with Long Taps Jenny Patten, Majida Malki, Quanta Technology, Matt Jones, American Transmission Co. Abstract Tapped transmission lines are quite common as they

More information

Open Circuit (OC) and Short Circuit (SC) Tests on Single Phase Transformer

Open Circuit (OC) and Short Circuit (SC) Tests on Single Phase Transformer Open Circuit (OC) and Short Circuit (SC) Tests on Single Phase Transformer 1 Aim To obtain the equivalent circuit parameters from OC and SC tests, and to estimate efficiency & regulation at various loads.

More information

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic

More information

Relaying 101. by: Tom Ernst GE Grid Solutions

Relaying 101. by: Tom Ernst GE Grid Solutions Relaying 101 by: Tom Ernst GE Grid Solutions Thomas.ernst@ge.com Relaying 101 The abridged edition Too Much to Cover Power system theory review Phasor domain representation of sinusoidal waveforms 1-phase

More information

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson... TECHNICAL REPORT APPLICATION GUIDE TITLE: Current Transformer Requirements for VA TECH Reyrolle ACP Relays PREPARED BY:- A Allen... APPROVED :- B Watson... REPORT NO:- 990/TIR/005/02 DATE :- 24 Jan 2000

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

COURSE PLANNER SUBJECT: ELECTRICAL POWER SYSTEM II

COURSE PLANNER SUBJECT: ELECTRICAL POWER SYSTEM II COURSE PLANNER SUBJECT: ELECTRICAL POWER SYSTEM II [260908] B.E. Third Year Class Electrical 204 Term: 6/2 (DEC-6 to APR-7) Faculty: PROF. J. I. JARIWALA PROF. A. S. SHAH PROF. T. M. PANCHAL PROF. N. B.

More information

The power transformer

The power transformer ELEC0014 - Introduction to power and energy systems The power transformer Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 35 Power transformers are used: to transmit

More information

Modeling and Testing of a Digital Distance Relay Using MATLAB/SIMULINK

Modeling and Testing of a Digital Distance Relay Using MATLAB/SIMULINK Modeling and Testing of a Digital Distance Relay Using MATLAB/SIMULINK Li-Cheng Wu, Chih-Wen Liu,Senior Member,IEEE, Ching-Shan Chen,Member,IEEE Department of Electrical Engineering, National Taiwan University,

More information

3-phase short-circuit current (Isc) at any point within a LV installation

3-phase short-circuit current (Isc) at any point within a LV installation 3-phase short-circuit current (Isc) at any point within a LV installation In a 3-phase installation Isc at any point is given by: where U 20 = phase-to-phase voltage of the open circuited secondary windings

More information

Analysis of Phenomena, that Affect the Distance Protection

Analysis of Phenomena, that Affect the Distance Protection Analysis of Phenomena, that Affect the Distance Protection C. Gallego, J. Urresty, and J. Gers, IEEE Abstract--This article presents the impact of changes in distance protection reach and zone changes

More information

1

1 Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive

More information

Digital Line Protection System

Digital Line Protection System Digital Line Protection System! Microprocessor Based Protection, Control and Monitoring System! Waveform Sampling! Proven Protection! Economical! Ease of Retrofit 1 DLP-D D Enhancements ASCII SUBSET Three

More information

Bus Protection Fundamentals

Bus Protection Fundamentals Bus Protection Fundamentals Terrence Smith GE Grid Solutions 2017 Texas A&M Protective Relay Conference Bus Protection Requirements High bus fault currents due to large number of circuits connected: CT

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Methods to Increase Line Relay Loadability

Methods to Increase Line Relay Loadability Methods to Increase Line Relay Loadability A Technical Document Prepared by the System Protection and Control Task Force of the NERC Planning Committee For the North American Electric Reliability Council

More information

Electric Circuits II Three-Phase Circuits. Dr. Firas Obeidat

Electric Circuits II Three-Phase Circuits. Dr. Firas Obeidat Electric Circuits II Three-Phase Circuits Dr. Firas Obeidat 1 Table of Contents 1 Balanced Three-Phase Voltages 2 Balanced Wye-Wye Connection 3 Balanced Wye-Delta Connection 4 Balanced Delta-Delta Connection

More information

Improve Transmission Fault Location and Distance Protection Using Accurate Line Parameters

Improve Transmission Fault Location and Distance Protection Using Accurate Line Parameters Improve Transmission Fault Location and Distance Protection Using Accurate Line Parameters Hugo E. Prado-Félix and Víctor H. Serna-Reyna Comisión Federal de Electricidad Mangapathirao V. Mynam, Marcos

More information

Unit Protection Differential Relays

Unit Protection Differential Relays Unit Protection PROF. SHAHRAM MONTASER KOUHSARI Current, pu Current, pu Protection Relays - BASICS Note on CT polarity dots Through-current: must not operate Internal fault: must operate The CT currents

More information

Transformer Fault Categories

Transformer Fault Categories Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)

More information

Verifying Transformer Differential Compensation Settings

Verifying Transformer Differential Compensation Settings Verifying Transformer Differential Compensation Settings Edsel Atienza and Marion Cooper Schweitzer Engineering Laboratories, Inc. Presented at the 6th International Conference on Large Power Transformers

More information

Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications

Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications Working Group D-3, Line Protection Subcommittee IEEE PES Power System Relaying Committee Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications

More information

PAPER-II (Subjective)

PAPER-II (Subjective) PAPER-II (Subjective) 1.(A) Choose and write the correct answer from among the four options given in each case for (a) to (j) below: (a) Improved commutation in d.c machines cannot be achieved by (i) Use

More information

PH213 Chapter 26 solutions

PH213 Chapter 26 solutions PH213 Chapter 26 solutions 26.6. IDENTIFY: The potential drop is the same across the resistors in parallel, and the current into the parallel combination is the same as the current through the 45.0-Ω resistor.

More information

Module 7. Transformer. Version 2 EE IIT, Kharagpur

Module 7. Transformer. Version 2 EE IIT, Kharagpur Module 7 Transformer Lesson 28 Problem solving on Transformers Contents 28 Problem solving on Transformer (Lesson-28) 4 28.1 Introduction. 4 28.2 Problems on 2 winding single phase transformers. 4 28.3

More information

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection) Differential Protection (Unit protection) Differential Protection Differential protection is the best technique in protection. In this type of protection the electrical quantities entering and leaving

More information

Back to the Basics Event Analysis Using Symmetrical Components

Back to the Basics Event Analysis Using Symmetrical Components Back to the Basics Event Analysis Using Symmetrical Components Amanvir Sudan Schweitzer Engineering Laboratories, Inc. 218 SEL Motivation Overview Back to Basics Introduction Symmetrical components refresher

More information

Defining and Measuring the Performance of Line Protective Relays

Defining and Measuring the Performance of Line Protective Relays Defining and Measuring the Performance of Line Protective Relays Edmund O. Schweitzer, III, Bogdan Kasztenny, Mangapathirao V. Mynam, Armando Guzmán, Normann Fischer, and Veselin Skendzic Schweitzer Engineering

More information

Lecture # 3 Circuit Configurations

Lecture # 3 Circuit Configurations CPEN 206 Linear Circuits Lecture # 3 Circuit Configurations Dr. Godfrey A. Mills Email: gmills@ug.edu.gh Phone: 0269073163 February 15, 2016 Course TA David S. Tamakloe CPEN 206 Lecture 3 2015_2016 1 Circuit

More information

A Guide to the DC Decay of Fault Current and X/R Ratios

A Guide to the DC Decay of Fault Current and X/R Ratios A Guide to the DC Decay of Fault Current and X/R Ratios Introduction This guide presents a guide to the theory of DC decay of fault currents and X/R ratios and the calculation of these values in Ipsa.

More information

Lab #5 ENG RC Circuits

Lab #5 ENG RC Circuits Name:. Lab #5 ENG 220-001 Date: Learning objectives of this experiment is that students will be able to: Measure the effects of frequency upon an RC circuit Calculate and understand circuit current, impedance,

More information

Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines

Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines David K Olson Paul Nyombi Xcel Energy Pratap G Mysore Pratap Consulting Services Minnesota Power Systems Conference St.

More information

Impedance protection on power transformer.

Impedance protection on power transformer. Impedance protection on power transformer www.siemens.com/siprotec5 SIPROTEC 5 Application Impedance Protection on Power Transformer APN-045, Edition 1 Content 1...3 1.1 Introduction...3 1.2 Application

More information

Experiment No. Experiments for First Year Electrical Engg Lab

Experiment No. Experiments for First Year Electrical Engg Lab Experiment No im: To determine Regulation and Efficiency of a single phase transformer using open circuit (O.C.) and short circuit (S.C.) tests pparatus: - Single phase transformer Single phase dimmer

More information

SELECTION OF DISTANCE RELAYING SCHEMES WHEN PROTECTING DUAL CIRCUIT LINES

SELECTION OF DISTANCE RELAYING SCHEMES WHEN PROTECTING DUAL CIRCUIT LINES SELECTION OF DISTANCE RELAYING SCHEMES WHEN PROTECTING DUAL CIRCUIT LINES Darren Spoor* and Joe Zhu** *Transmission Development TransGrid ** School of Electrical Engineering University of Technology, Sydney

More information