IGEE 402 Power System Analysis. FINAL EXAMINATION Fall 2004

Size: px
Start display at page:

Download "IGEE 402 Power System Analysis. FINAL EXAMINATION Fall 2004"

Transcription

1 IGEE 40 Power System Analysis FINAL EXAMINATION Fall 004 Special instructions: - Duration: 150 minutes. - Material allowed: a crib sheet (double sided 8.5 x 11), calculator. - Attempt 4 out of 7 questions. - Make any reasonable assumption. - All questions and sub-questions carry equal weight. - Return the completed answer sheet attached. QUESTION 1 (0 points) A single-phase 600 V, 60 Hz feeder, with a series reactance of 0. pu, supplies a motor load. The motor draws 8 times base current at a power factor of 0. (lagging) at start-up under 600 V. The motor can be represented by a series R-L combination. Assume a base power of 5 kva. Give results in real quantities (Ω, V, A). (a) Find the equivalent series R-L combination of the motor in Ω. Taking into account the feeder impedance, compute the line current and the voltage across the motor. (b) A series capacitor is used to cancel 75 % of the feeder inductance. Compute the voltage across the motor and the line current. (c) A capacitor, of 3 pu reactance, is connected in parallel with the motor. Compute the voltage across the motor and the line current. Compare with the previous case and explain the difference. QUESTION (0 points) A three-phase 13.8 kv/138 kv, 00 MVA, 60 Hz transformer, with a series equivalent impedance of j0.08 pu (on the transformer base) is connected to a transmission line of impedance + j0 Ω. The line feeds a 00 MVA load, with a power factor of (a) Give the transformer and line equivalent circuits, in real and pu values. Draw the single line diagram of the system, showing impedances and voltages in pu and in Ω, V. (b) The sending-end voltage is adjusted so that the load voltage is 138 kv. Compute the current flowing in the transmission line. Use pu values. Find the amplitude in V and angle of the voltage on the low voltage side of the transformer. Compute the voltage regulation. (c) Series compensation, equal to 75 % of the line reactance, is added to the transmission line. The sending-end voltage is adjusted so that the load voltage is 138 kv. Find the amplitude and angle of the voltage on the low voltage side of the transformer. Compute the voltage regulation and compare to the uncompensated case.

2 IGEE 40 Power System Analysis FINAL EXAMINATION Joós, G. QUESTION 3 (0 points) A three-phase 600 V, 60 Hz feeder supplies two three-phase loads: (a) a Y connected inductor, of per phase impedance of 0 Ω and (b) a Δ connected capacitor, of per phase impedance of 0 Ω. (a) Compute the current in each capacitor and inductor. Compute the total current drawn by the loads. Draw the phasor diagram showing the phase voltage and inductor, capacitor and total current per leg, based on a Y equivalent. (b) Compute the power associated with each load, real and reactive component. Find the total power. (c) One of the capacitors becomes an open circuit. Find the total line current flowing in each of the three lines. QUESTION 4 (0 points) A 400 km, 765 kv, 60 Hz transmission line has the following distributed parameters: x = 0.30 Ω/km, y = j5.0 x 10-6 S/km. Losses are neglected. (a) Compute the nominal π equivalent circuit parameters and draw the circuit. Compute the corresponding ABCD parameters. Find the surge impedance and surge impedance loading. (b) The line delivers 000 MW at 735 kv with a power factor of 0.95 lagging. Using the ABCD parameters, compute the sending end voltage, current and δ angle. Confirm using the nominal π equivalent circuit, and the short line equivalent. (c) Series compensation of 70 % is introduced. Using the short line equivalent, compute the new load angle and maximum steady state power transfer capability. Compare with the uncompensated line. QUESTION 5 (0 points) A two-bus transmission system consists of the following: (i) a voltage regulated generator bus (1.0 pu), the swing bus; (ii) a voltage regulated bus (1.0 pu), with a generator supplying real power (0.5 pu) and reactive power, and a load of power (1.0 + j0.5) pu. The transmission line impedance is (j0.5). (a) Draw the single line diagram. Identify the type of buses. Compute the Y bus matrix. Write the current equation and the power equation. (b) Formulate the Newton Raphson solution. Compute the first iteration. (c) Indicate the changes required to the formulation above if a load bus replaces the voltage controlled bus. Compute the first iteration. QUESTION 6 (0 points) A three-phase generator has a Y connected winding, with a neutral grounded through an impedance of j0. pu. The generator positive (transient), negative and zero sequence components are respectively, j0.4, j0.5, j0.0. The transmission line impedance is j0.4 pu, with a zero sequence component of 0. The generator prefault voltage is assumed to be regulated at 1 pu. Ignore all prefault currents. (a) A three-phase symmetrical short circuit occurs at the end of the transmission line, with a 0.1 pu impedance. Give the sequence impedance matrix for the fault current. Draw the sequence networks corresponding to the fault. Compute the sequence components of the fault currents. Convert into phase quantities. (b) A single line-to-ground fault occurs on phase a with an impedance of 0.1 pu. Calculate the sequence components of the fault current. Draw the sequence networks corresponding to the fault. Compute the value of the sequence components of the fault currents. Convert into phase quantities. (c) For the symmetrical three-phase fault and the single line-to-ground fault, compute the symmetrical components of the voltage at the fault, and convert to abc values. Draw conclusions as to the severity and impact of those two types of faults on the voltages at the load. Page of 4

3 IGEE 40 Power System Analysis FINAL EXAMINATION Joós, G. QUESTION 7 (0 points) A three-phase. 60 Hz, round rotor hydroelectric generator has an H constant of 4 s. It delivers P m = 1.0 pu power at a power factor of 0.85 lagging to an infinite bus through a transmission line of reactance X = 0.7. The voltage at the infinite bus is 1.0 pu with an angle of 0 deg. The machine transient reactance X d = 0.35 pu. (a) Compute the transient machine internal voltage and angle δ. Give the corresponding equation for the electric power. Write the pu swing equation. (b) A three-phase bolted short occurs midway along the transmission line. Determine the power angle 5 cycles after the initiation of the short circuit. Assume the mechanical input power remains constant at the initial value. Draw the pre-fault and post-fault P- δ curves. Indicate the initial conditions, and the fault clearing point. Explain the application of the equal area criterion to this case. (c) The fault is cleared after 5 cycles. Find the maximum δ angle. Indicate if the system recovers from the fault. APPENDIX A SYMMETRICAL COMPONENT TRANSFORMATION MATRICES A = 1 a a 1 a a A -1 = 1/3 1 a a 1 a a Page 3 of 4

4 QUESTION 1 (0 points) A single-phase 600 V, 60 Hz feeder, with a series reactance of 0. pu, supplies a motor load. The motor draws 8 times base current at a power factor of 0. (lagging) at start-up under 600 V. The motor can be represented by a series R-L combination. Assume a base power of 5 kva. Give results in real quantities (Ω, V, A). Vbase=600; Sbase=5e3; xf=0.; xc=3; pf=0.; (a) Find the equivalent series R-L combination of the motor in Ω. Taking into account the feeder impedance, compute the line current and the voltage across the motor. Ibase=Sbase/Vbase; %Find the phasor current teta=acos(pf); Im=8*Ibase*exp(-j*teta); %Ohms law to find the impedance zm=vbase/im; zbase=vbase^/sbase; %Voltage divider to find the voltage across the impedance vm=vbase*zm/(zm+j*xf*zbase); %Ohms law to find the line current Iline=Vbase/(zm+j*xf*zbase); R= 1.8 X= 8.81 Iline= 5.76A Vm= 31.8V (b) A series capacitor is used to cancel 75 % of the feeder inductance. Compute the voltage across the motor and the line current. vm_series_compensation=vbase*zm/(zm+j*(xf-0.75*xf)); Iline_series_compensation=Vbase/(zm+j*(xf-0.75*xf)); Iline= 47.81A Vm= 430V (c)

5 A capacitor, of 3 pu reactance, is connected in parallel with the motor. Compute the voltage across the motor and the line current. Compare with the previous case and explain the difference. zm_parallel_xc=zm*(-j*xc)/(zm-j*xc); vm_parallel_compensation=vbase*zm_parallel_xc/(zm_parallel_xc+j*xf); Iline_parallel_compensation=Vbase/(zm_parallel_xc+j*xf); Iline= 5.36A Vm= 37.9V The system seems to be adequately compensated in series. However, the high current and the over voltages in the parallel shows that the system is overcompensated with the parallel capacitor. QUESTION (0 points) A three-phase 13.8 kv/138 kv, 00 MVA, 60 Hz transformer, with a series equivalent impedance of j0.08 pu (on the transformer base) is connected to a transmission line of impedance + j0 Ω. The line feeds a 00 MVA load, with a power factor of Vt_high=138; Vt_low=13.8; St=00; zt=0.0+j*0.08; zl_ohms=+j*0; Pl=00; pf=0.85; (a) Give the transformer and line equivalent circuits, in real and pu values. Draw the single line diagram of the system, showing impedances and voltages in pu and in Ω, V. Vbase=Vt_high; Sbase=St; Zbase=Vbase^/Sbase; zt_high_ohms=zt*zbase; zl_pu=zl_ohms/zbase; Rtr(pu)= 0.0 Xtr(pu)= 0.08 Rtr(ohm)= 1.9 Xtr(ohm)= 7.61 Rl(pu)= 0.01 Xl(pu)= 0.1 Rl(ohm)= Xl(ohm)= /138kV 00MVA 0.0+j0.08 p.u 1.9+j7.61ohm from the high voltage side Line: +j0homs 0.01+j0.1pu Load 00MVA pf 0.85 lagging

6 (b) The sending-end voltage is adjusted so that the load voltage is 138 kv. Compute the current flowing in the transmission line. Use pu values. Find the amplitude in V and angle of the voltage on the low voltage side of the transformer. Compute the voltage regulation. %Compute the current Iline=conj(pf+j*sin(acos(pf))); %voltage in the secondary of the transformer Vtransf_pu=1+Iline*(zl_pu+zt); Vtransf_volts=Vtransf_pu*Vt_low; Vtransf_volts_amplitude=abs(Vtransf_volts)*sqrt(); delta=angle(vtransf_pu)*180/pi; %voltage regulation VR_no=(abs(Vtransf_pu)-1)*100; Iline(pu)= 1 Vt_low= 16.7kV Delta= 10.7 VR= 0.87 (c) Series compensation, equal to 75 % of the line reactance, is added to the transmission line. The sending-end voltage is adjusted so that the load voltage is 138 kv. Find the amplitude and angle of the voltage on the low voltage side of the transformer. Compute the voltage regulation and compare to the uncompensated case. Vtransf_comp=1+Iline*(zl_pu-0.75*zl_pu+zt); Vtransf_comp_amplitude=abs(Vtransf_comp)*Vt_low*sqrt(); delta_compensated=angle(vtransf_comp)*180/pi; VR=(abs(Vtransf_comp)-1)*100; Vt_low= 15.11kV Delta= 5. VR= 9.58 Series compensation improves voltage regulation since reduces the reactance and therefore the voltage drop across the line. QUESTION 3 (0 points) A three-phase 600 V, 60 Hz feeder supplies two three-phase loads: (a) a Y connected inductor, of per phase impedance of 0 Ω and (b) a Δ connected capacitor, of per phase impedance of 0 Ω. V=600; xi=0; xc=0; (a) Compute the current in each capacitor and inductor. Compute the total current drawn by the loads. Draw the phasor diagram showing the phase voltage and inductor, capacitor and total current per leg, based on a Y equivalent. %current in the individual elements Iind=V/sqrt(3)/(j*xi); Icap=V/(-j*xc); %total current Itot=Iind+Icap*sqrt(3);

7 Ic= 30 Iind= 17.3 Iload= Icapacitor phase=j51.96a Itotal=34.64A Vphase=346V Iinductor phase=-j17.3a (b) Compute the power associated with each load, real and reactive component. Find the total power. Sind=3*(Iind)^*j*xi; Scap=3*(Icap)^*(-j*xc); Scap 54000Var Sind Var Stot 36000Var (c) One of the capacitors becomes an open circuit. Find the total line current flowing in each of the three lines. Ic Iind Icap Phase c Iind Iind Icap Ib Phase b Ia Phase a %the voltage is not affected then, one of the currents is the same Va=600/sqrt(3); Vb=Va*exp(-j**pi/3); Vc=Va*exp(j**pi/3);

8 Ia=Va/(j*xi)+(Va-Vb)/(-j*xc)+(Va-Vc)/(-j*xc); Ib=Vb/(j*xi)+(Vb-Va)/(-j*xc); Ic=Vc/(j*xi)+(Vc-Va)/(-j*xc); I_a= j34.64 I_b= -j17.3 I_c= -j17.3 QUESTION 4 (0 points) A 400 km, 765 kv, 60 Hz transmission line has the following distributed parameters: x = 0.30 Ω/km, y = j5.0 x 10-6 S/km. Losses are neglected. L=400; V=765000; x=0.3; y=5e-6; (a) Compute the nominal π equivalent circuit parameters and draw the circuit. Compute the corresponding ABCD parameters. Find the surge impedance and surge impedance loading. X=x*L*j; Y=y*L*j; Api=1+Y*X/; Bpi=X; Cpi=Y*(1+Y*X/4); Zc=sqrt(x/y); SIL=V^/Zc; beta=sqrt(x*y); Api= 0.88 Cpi= i Zc= 45 Bpi= 10i Dpi= 0.88 SIL= 389 X=j10 Vs Is Ir Vr Y/=j.001 Y/ (b) The line delivers 000 MW at 735 kv with a power factor of 0.95 lagging. Using the ABCD parameters, compute the sending end voltage, current and δ angle. Confirm using the nominal π equivalent circuit, and the short line equivalent. P=000e6; Vr=735000; pf=0.95; A=cos(beta*L);

9 B=Zc*sin(beta*L)*j; C=1/Zc*sin(beta*L)*j; Vrl=Vr/sqrt(3); Srec=P/pf; Ir=Srec/3/Vrl*(pf-j*sin(acos(pf))); Vs=A*Vrl+B*Ir; Vspi=Api*Vrl+Bpi*Ir; Vs_short=Vrl+X*Ir; Is=C*Vrl+A*Ir; Ispi=Cpi*Vrl+Api*Ir; Is_short=Ir; Vs= Vs_pi= Vs_short= Is== 143 Is_pi= 144 Is_short= 1653 (c) Series compensation of 70 % is introduced. Using the short line equivalent, compute the new load angle and maximum steady state power transfer capability. Compare with the uncompensated line. Xnew=0.3*X; Vs_new=Vrl+Ir*X; delta_new=asin(abs(xnew)*p/3/(abs(vs_new)*abs(vrl))); Pmax=V^/abs(Xnew)*3; delta_new= 6. Pmax= QUESTION 5 (0 points) A two-bus transmission system consists of the following: (i) a voltage regulated generator bus (1.0 pu), the swing bus; (ii) a voltage regulated bus (1.0 pu), with a generator supplying real power (0.5 pu) and reactive power, and a load of power (1.0 + j0.5) pu. The transmission line impedance is (j0.5). xl=0.5; (a) Draw the single line diagram. Identify the type of buses. Compute the Y bus matrix. Write the current equation and the power equation. Swing bus P=? Q=? V=1 delta=0 j0.5 PV bus P=-0.75 Q=? V=1 delta=? G=0.5 Load=1+j0.5 y=1/(j*xl); Y=[y -y; -y y];

10 (1 δ 1 ) I = xl sin( δ ) P = xl δ =.0 o Y= -i i i -i (b) Formulate the Newton Raphson solution. Compute the first iteration. X = δ ; Y = P X(0)=0; Calculate the Jacobian: P = VV Y sin( δ ) 1 1, P = = cos( ) = = J VV 1 Y1, δ Y1, δ Jacobian= Δy= Δx= x1= (c) Indicate the changes required to the formulation above if a load bus replaces the voltage controlled bus. Compute the first iteration. The number of variables changes and the formulation as follows: X δ P ; Y = ; Q = V Calculate the Jacobian: 0 X(0)= 1

11 P = VV Y sin( δ ) 1 1, Q = VV Y (1 cos( δ )) 1 1, P J = = VV Y = Y = 1 1 1, cos( δ ) 1, δ P J = = V Y δ = Y = 0 1 1, sin( ) 1, V Q J = = VV Y δ = Y = , sin( ) 1, δ Q J = = V Y δ = Y = 4 1 1, (1 cos( )) 1, V Jacobian= Δy= Δx= x1= QUESTION 6 (0 points) A three-phase generator has a Y connected winding, with a neutral grounded through an impedance of j0. pu. The generator positive (transient), negative and zero sequence components are respectively, j0.4, j0.5, j0.0. The transmission line impedance is j0.4 pu, with a zero sequence component of 0. The generator prefault voltage is assumed to be regulated at 1 pu. Ignore all prefault currents. xl=0.4; xg1=0.4; xg=0.5; xg0=0.; xn=0.; xf=0.1; (a) A three-phase symmetrical short circuit occurs at the end of the transmission line, with a 0.1 pu impedance. Give the sequence impedance matrix for the fault current. Draw the sequence networks corresponding to the fault. Compute the sequence components of the fault currents. Convert into phase quantities. Y11=-j*(1/xg1+1/xl); Y1=j/xl; Y1=Y1; Y=-j*(1/xl); Y=[Y11 Y1; Y1 Y]; Z=inv(Y); Ifault=1/(Z(,)+j*xf); I0=0; I=0; I1=Ifault;

12 a=-0.5+j*sqrt(3)/; A=[1 1 1; 1 a^ a; 1 a a^]; I=A*[I0 I1 I]'; j0.8pu + Zero sequence network V0 - j0.8pu If=I1 + Positive sequence network 1p.u V1 Zf=0.1 - j0.65pu + Negative sequence network V - I 0 =0 I 1 =1.11 I =0 I a = I b = I b = (b) A single line-to-ground fault occurs on phase a with an impedance of 0.1 pu. Calculate the sequence components of the fault current. Draw the sequence networks corresponding to the fault. Compute the value of the sequence components of the fault currents. Convert into phase quantities.

13 j0.8pu + Zero sequence network V0 - j0.8pu If=I0=I1=I + Positive sequence network 1p.u V1 3xZf=j0.3 - j0.65pu + Negative sequence network V - z0=j*(3*xn+xg0); z1=j*(xg1+xl); z=j*(xg+xl); I0=1/(z0+z1+z+3*j*xf); Ifsingle=A*[I0 I0 I0]'; I 0 =0.39 I 1 =0.39 I =0.39 I a = I b =0 I b =0 (c) For the symmetrical three-phase fault and the single line-to-ground fault, compute the symmetrical components of the voltage at the fault, and convert to abc values. Draw conclusions as to the severity and impact of those two types of faults on the voltages at the load. V0=-I0*z0; V1=1-I0*z1; V=-I0*z; Vfault=A*[V0 V1 V]'; Three V0= 0 V1= 0.11 V= 0 phase Va= 0.11 Vb= Vc= Single V0= V1= V= phase Va= 0.11 Vb= Vc=.97 13

14 QUESTION 7 (0 points) A three-phase. 60 Hz, round rotor hydroelectric generator has an H constant of 4 s. It delivers P m = 1.0 pu power at a power factor of 0.85 lagging to an infinite bus through a transmission line of reactance X = 0.7. The voltage at the infinite bus is 1.0 pu with an angle of 0 deg. The machine transient reactance X d = 0.35 pu. H=4; xg=0.35; xl=0.7; pf=0.85; f=60; clearing=5; (a) Compute the transient machine internal voltage and angle δ. Give the corresponding equation for the electric power. Write the pu swing equation. I=1/pf*(pf-j*sin(acos(pf))); E=1+j*(xg+xl)*I; ESin( δ ) P = xg+ xl H d ωpu() t δ() t = P m, pu() t Pe, pu() t ωsyn dt Integrating swing equation twice, assuming pm remains constant we obtain ωsync δ () t = t + δ0 4H E= 1.95 δ= 3.46 (b) A three-phase bolted short occurs midway along the transmission line. Determine the power angle 5 cycles after the initiation of the short circuit. Assume the mechanical input power remains constant at the initial value. Draw the pre-fault and post-fault P- δ curves. Indicate the initial conditions, and the fault clearing point. Explain the application of the equal area criterion to this case. wsync=60**pi; delta_new=wsync/(4*h)*(clearing/f)^+angle(e); Pmax=abs(E)/(xg+xl); delta_max=pi-angle(e);

15 1.86 sin(x) Pmax=1.86 pu A A delta= delta=6.8 x delta= delta=3.46 δ_new In order to have transient stability the kinetic energy accumulated in the machine during the fault (A1) has to be less than the energy the generator can return to the system before losing synchronism (A). Then: A1 A δ max δ δ ( Pmax.sin( δ) 1) dδ ; new δ new A1=delta_new-angle(E); A=Pmax*(cos(delta_new)-cos(delta_max))-(delta_max-delta_new); In this case stability is kept (c) The fault is cleared after 5 cycles. Find the maximum δ angle. Indicate if the system recovers from the fault. To find the maximum angle we have to solve the following non-linear equation: A1=A delta_new-angle(e)= Pmax*(cos(delta_new)-cos(delta_max))-(delta_max-delta_new); which is equal to: 1.95 = 1.86 cos( δ max) + δ max Which can be solved graphically as:

16 x δ_max= rad = 6.8degrees

In Class Examples (ICE)

In Class Examples (ICE) In Class Examples (ICE) 1 1. A 3φ 765kV, 60Hz, 300km, completely transposed line has the following positive-sequence impedance and admittance: z = 0.0165 + j0.3306 = 0.3310 87.14 o Ω/km y = j4.67 410-6

More information

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Level 6 Graduate Diploma in Engineering Electrical Energy Systems 9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,

More information

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

COURSE PLANNER SUBJECT: ELECTRICAL POWER SYSTEM II

COURSE PLANNER SUBJECT: ELECTRICAL POWER SYSTEM II COURSE PLANNER SUBJECT: ELECTRICAL POWER SYSTEM II [260908] B.E. Third Year Class Electrical 204 Term: 6/2 (DEC-6 to APR-7) Faculty: PROF. J. I. JARIWALA PROF. A. S. SHAH PROF. T. M. PANCHAL PROF. N. B.

More information

PAPER-II (Subjective)

PAPER-II (Subjective) PAPER-II (Subjective) 1.(A) Choose and write the correct answer from among the four options given in each case for (a) to (j) below: (a) Improved commutation in d.c machines cannot be achieved by (i) Use

More information

Transmission Line Models Part 1

Transmission Line Models Part 1 Transmission Line Models Part 1 Unlike the electric machines studied so far, transmission lines are characterized by their distributed parameters: distributed resistance, inductance, and capacitance. The

More information

Conventional Paper-II-2013

Conventional Paper-II-2013 1. All parts carry equal marks Conventional Paper-II-013 (a) (d) A 0V DC shunt motor takes 0A at full load running at 500 rpm. The armature resistance is 0.4Ω and shunt field resistance of 176Ω. The machine

More information

UNIVERSITY OF SWAZILAND MAIN EXAMINATION, DECEMBER 2016

UNIVERSITY OF SWAZILAND MAIN EXAMINATION, DECEMBER 2016 UNIVERSITY OF SWAZILAND MAIN EXAMINATION, DECEMBER 2016 FACULTY OF SCIENCE AND ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONIC ENGINEERING TITLE OF PAPER: POWER SYSTEM ANALYSIS AND OPERATION COURSE

More information

AC Power Instructor Notes

AC Power Instructor Notes Chapter 7: AC Power Instructor Notes Chapter 7 surveys important aspects of electric power. Coverage of Chapter 7 can take place immediately following Chapter 4, or as part of a later course on energy

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING. MIDTERM EXAMINATION, February Forth Year Electrical and Computer Engineering

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING. MIDTERM EXAMINATION, February Forth Year Electrical and Computer Engineering NAME: LAST UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENINEERIN MIDTERM EXAMINATION, February 017 Forth Year Electrical and Computer Engineering ECE413 Energy Systems and Distribution eneration

More information

Conventional Paper-II-2011 Part-1A

Conventional Paper-II-2011 Part-1A Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance

More information

Lab 1. Objectives. Single Line Diagram. Methodology. Observations. Jon Jawnsy Yu 26 October 2009

Lab 1. Objectives. Single Line Diagram. Methodology. Observations. Jon Jawnsy Yu 26 October 2009 Lab 1 Objectives In this lab, our objective is to simulate a simple single machine infinite bus configuration using the PowerWorld Simulator software. We design a local generator system (a synchronous

More information

Chapter 10: Compensation of Power Transmission Systems

Chapter 10: Compensation of Power Transmission Systems Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur Lecture - 10 Transmission Line Steady State Operation Voltage Control (Contd.) Welcome

More information

Chapter 2-1 Transformers

Chapter 2-1 Transformers Principles of Electric Machines and Power Electronics Chapter 2-1 Transformers Third Edition P. C. Sen Transformer application 1: power transmission Ideal Transformer Assumptions: 1. Negligible winding

More information

Chapter 2: Transformers

Chapter 2: Transformers Chapter 2: Transformers 2-1. The secondary winding of a transformer has a terminal voltage of v s (t) = 282.8 sin 377t V. The turns ratio of the transformer is 100:200 (a = 0.50). If the secondary current

More information

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS) SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS) SLIDE In this video, we will cover a sample exam problem for the Power PE Exam. This exam problem falls under the topic of Protection, which accounts for

More information

Spring 2000 EE361: MIDTERM EXAM 1

Spring 2000 EE361: MIDTERM EXAM 1 NAME: STUDENT NUMBER: Spring 2000 EE361: MIDTERM EXAM 1 This exam is open book and closed notes. Assume f=60 hz and use the constant µ o =4π 10-7 wherever necessary. Be sure to show all work clearly. 1.

More information

148 Electric Machines

148 Electric Machines 148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional

More information

ECG 741 Power Distribution Transformers. Y. Baghzouz Spring 2014

ECG 741 Power Distribution Transformers. Y. Baghzouz Spring 2014 ECG 741 Power Distribution Transformers Y. Baghzouz Spring 2014 Preliminary Considerations A transformer is a device that converts one AC voltage to another AC voltage at the same frequency. The windings

More information

EN Assignment No.1 - TRANSFORMERS

EN Assignment No.1 - TRANSFORMERS EN-06 - Assignment No.1 - TRANSFORMERS Date : 13 th Jan 01 Q1) A 0kVA 00/0 Volts, 60Hz, single phase transformer is found to have the following equivalent circuit parameter referred to the high potential

More information

, ,54 A

, ,54 A AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

Electric Circuits II Three-Phase Circuits. Dr. Firas Obeidat

Electric Circuits II Three-Phase Circuits. Dr. Firas Obeidat Electric Circuits II Three-Phase Circuits Dr. Firas Obeidat 1 Table of Contents 1 Balanced Three-Phase Voltages 2 Balanced Wye-Wye Connection 3 Balanced Wye-Delta Connection 4 Balanced Delta-Delta Connection

More information

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit CHAPTER 2 Basic Concepts, Three-Phase Review, and Per Unit 1 AC power versus DC power DC system: - Power delivered to the load does not fluctuate. - If the transmission line is long power is lost in the

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Ishwar Lal Yadav Department of Electrical Engineering Rungta College of Engineering and Technology Bhilai, India

More information

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Short-Circuit Analysis IEC Standard 1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Purpose of Short-Circuit Studies A Short-Circuit Study can be used to determine any or all of

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Hours / 100 Marks Seat No.

Hours / 100 Marks Seat No. 17323 14115 3 Hours / 100 Seat No. Instructions (1) All Questions are Compulsory. (2) Illustrate your answers with neat sketches wherever necessary. (3) Figures to the right indicate full marks. (4) Assume

More information

Grounding Resistance

Grounding Resistance Grounding Resistance Substation grounding resistance is the resistance in ohms between the substation neutral and earth ground (zeropotential reference) An actual fall of potential test is the best way

More information

Rajasthan Technical University, Kota

Rajasthan Technical University, Kota COURSE - FILE Name : Dr. Dinesh Birla Branch : Electrical Engineering Session : 2014-15, Odd Semester Semester : M. Tech I st Semester Specialization : Power System Index: Course File Sr. No. Content/

More information

Electrical Power Systems

Electrical Power Systems Electrical Power Systems CONCEPT, THEORY AND PRACTICE SECOND EDITION SUBIR RAY Professor MVJ College of Engineering Bangalore PHI Learning Pfcte tofm Delhi-110092 2014 Preface xv Preface to the First Edition

More information

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits QUESTION BANK ETE (17331) CM/IF Chapter1: DC Circuits Q1. State & explain Ohms law. Also explain concept of series & parallel circuit with the help of diagram. 3M Q2. Find the value of resistor in fig.

More information

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM 3.1 INTRODUCTION Static synchronous compensator is a shunt connected reactive power compensation device that is capable of generating or

More information

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone

More information

Form B. Connection Impact Assessment Application Form Distribution System

Form B. Connection Impact Assessment Application Form Distribution System Form B Connection Impact Assessment Application Form Distribution System This Application Form is for Generators applying for Connection Impact Assessment ( CIA ). It is important that the Generator provides

More information

not to be republished NCERT ALTERNATING CURRENT Chapter Seven MCQ 1

not to be republished NCERT ALTERNATING CURRENT Chapter Seven MCQ 1 hapter Seven ALTERNATING URRENT MQ 1 7.1 If the rms current in a 50 Hz ac circuit is 5 A, the value of the current 1/300 seconds after its value becomes zero is (a) 5 2 A (b) 5 3/2 A (c) 5/6 A (d) 5/ 2

More information

PROTECTION APPLICATION HANDBOOK

PROTECTION APPLICATION HANDBOOK BOOK No 6 Revision 0 Global Organization Innovative Solutions Product & Substation System Business Business PROTECTION APPLICATION HANDBOOK BA THS / BU Transmission Systems and Substations LEC Support

More information

GRADE 12 SEPTEMBER 2012 ELECTRICAL TECHNOLOGY

GRADE 12 SEPTEMBER 2012 ELECTRICAL TECHNOLOGY Province of the EASTERN CAPE EDUCATION NATIONAL SENIOR CERTIFICATE GRADE 12 SEPTEMBER 2012 ELECTRICAL TECHNOLOGY MARKS: 200 TIME: 3 hours This question paper consists of 11 pages and a formula sheet. 2

More information

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS 40 CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS 3.1 INTRODUCTION The low power factor effects on transmission line, switchgear, transformers etc. It is observed that if the power

More information

EE 740 Transmission Lines

EE 740 Transmission Lines EE 740 Transmission Lines 1 High Voltage Power Lines (overhead) Common voltages in north America: 138, 230, 345, 500, 765 kv Bundled conductors are used in extra-high voltage lines Stranded instead of

More information

Exercises on overhead power lines (and underground cables)

Exercises on overhead power lines (and underground cables) Exercises on overhead power lines (and underground cables) 1 From the laws of Electromagnetism it can be shown that l c = 1 v 2 where v is the speed of propagation of electromagnetic waves in the environment

More information

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW

GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 2 MW Electric Utility Contact Information DTE Energy Interconnection Coordinator One Energy Plaza, SB

More information

Connection Impact Assessment Application Form

Connection Impact Assessment Application Form Connection Impact Assessment Application Form This Application Form is for Generators applying for a Connection Impact Assessment (CIA). In certain circumstances, London Hydro may require additional information

More information

Connection Impact Assessment Application

Connection Impact Assessment Application Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,

More information

Questions Bank of Electrical Circuits

Questions Bank of Electrical Circuits Questions Bank of Electrical Circuits 1. If a 100 resistor and a 60 XL are in series with a 115V applied voltage, what is the circuit impedance? 2. A 50 XC and a 60 resistance are in series across a 110V

More information

Class XII Chapter 7 Alternating Current Physics

Class XII Chapter 7 Alternating Current Physics Question 7.1: A 100 Ω resistor is connected to a 220 V, 50 Hz ac supply. (a) What is the rms value of current in the circuit? (b) What is the net power consumed over a full cycle? Resistance of the resistor,

More information

Investigation of D-Statcom Operation in Electric Distribution System

Investigation of D-Statcom Operation in Electric Distribution System J. Basic. Appl. Sci. Res., (2)29-297, 2 2, TextRoad Publication ISSN 29-434 Journal of Basic and Applied Scientific Research www.textroad.com Investigation of D-Statcom Operation in Electric Distribution

More information

Electricity & Optics

Electricity & Optics Physics 24100 Electricity & Optics Lecture 19 Chapter 29 sec. 1,2,5 Fall 2017 Semester Professor Koltick Series and Parallel R and L Resistors and inductors in series: R series = R 1 + R 2 L series = L

More information

Exercise 2: Parallel RLC Circuits

Exercise 2: Parallel RLC Circuits RLC Circuits AC 2 Fundamentals Exercise 2: Parallel RLC Circuits EXERCSE OBJECTVE When you have completed this exercise, you will be able to analyze parallel RLC circuits by using calculations and measurements.

More information

Downloaded from / 1

Downloaded from   / 1 PURWANCHAL UNIVERSITY II SEMESTER FINAL EXAMINATION-2008 LEVEL : B. E. (Computer/Electronics & Comm.) SUBJECT: BEG123EL, Electrical Engineering-I Full Marks: 80 TIME: 03:00 hrs Pass marks: 32 Candidates

More information

Chapter 31 Alternating Current

Chapter 31 Alternating Current Chapter 31 Alternating Current In this chapter we will learn how resistors, inductors, and capacitors behave in circuits with sinusoidally vary voltages and currents. We will define the relationship between

More information

Application and features

Application and features Power Measurement Unit PM 2214 Power Measurement Unit PM 2214 Application and features PM 2214 Power supervision / SCADA system Feeder automation / Customized 0.05% high accuracy Cost saving for 4 feeder

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

Chapter 33. Alternating Current Circuits

Chapter 33. Alternating Current Circuits Chapter 33 Alternating Current Circuits Alternating Current Circuits Electrical appliances in the house use alternating current (AC) circuits. If an AC source applies an alternating voltage to a series

More information

Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC)

Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC) Increasing Dynamic Stability of the Network Using Unified Power Flow Controller (UPFC) K. Manoz Kumar Reddy (Associate professor, Electrical and Electronics Department, Sriaditya Engineering College, India)

More information

Power Factor & Harmonics

Power Factor & Harmonics Power Factor & Harmonics Andy Angrick 2014 Harmonic Distortion Harmonic problems are becoming more apparent because more equipment that produce harmonics are being applied to power systems Grounding Harmonics

More information

EE6201 CIRCUIT THEORY QUESTION BANK PART A

EE6201 CIRCUIT THEORY QUESTION BANK PART A EE6201 CIRCUIT THEORY 1. State ohm s law. 2. State kirchoff s law. QUESTION BANK PART A 3. Which law is applicable for branch current method? 4. What is the matrix formation equation for mesh and nodal

More information

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg. Aligarh College of Engineering & Technology (College Code: 19) Electrical Engg. (EE-11/21) Unit-I DC Network Theory 1. Distinguish the following terms: (a) Active and passive elements (b) Linearity and

More information

ELEMENTS OF FACTS CONTROLLERS

ELEMENTS OF FACTS CONTROLLERS 1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are

More information

Modle 6 : Preventive, Emergency and Restorative Control. Lecture 29 : Emergency Control : An example. Objectives. A simple 2 machine example

Modle 6 : Preventive, Emergency and Restorative Control. Lecture 29 : Emergency Control : An example. Objectives. A simple 2 machine example Modle 6 : Preventive, Emergency and Restorative Control Lecture 29 : Emergency Control : An example Objectives In this lecture you will learn the following An example to illustrate the system angular instability

More information

Rajasthan Technical University, Kota

Rajasthan Technical University, Kota COURSE FILE POWER SYSTEM ENGINEERING Name Branch Session Semester : Dr. Dinesh Birla : Electrical Engineering : 2012-13, Odd Semester : B. Tech VII Semester Index: Course File Sr. No. 1 Students Detail

More information

Resonance. Resonance curve.

Resonance. Resonance curve. Resonance This chapter will introduce the very important resonant (or tuned) circuit, which is fundamental to the operation of a wide variety of electrical and electronic systems in use today. The resonant

More information

University of Rajshahi Department of Electrical & Electronic Engineering B.Sc. Engineering Part-IV Odd Semester Examination- 2017

University of Rajshahi Department of Electrical & Electronic Engineering B.Sc. Engineering Part-IV Odd Semester Examination- 2017 Course Code: EEE 4141 Course Title: Power System i. Answer to all parts (a), (b), (c) etc. of a question must be contiguous. ii. Use separate answer script for each Section (A/B). iii. Right margin indicates

More information

Tutorial on Symmetrical Components

Tutorial on Symmetrical Components Tutorial on Symmetrical Components Part : Examples Ariana Amberg and Alex Rangel, Schweitzer Engineering Laboratories, nc. Abstract Symmetrical components and the per-unit system are two of the most fundamental

More information

KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK UNIT I BASIC CIRCUITS ANALYSIS PART A (2-MARKS)

KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK UNIT I BASIC CIRCUITS ANALYSIS PART A (2-MARKS) KINGS COLLEGE OF ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK YEAR / SEM : I / II SUBJECT CODE & NAME : EE 1151 CIRCUIT THEORY UNIT I BASIC CIRCUITS ANALYSIS PART A (2-MARKS)

More information

GATE 2000 Electrical Engineering

GATE 2000 Electrical Engineering GATE 2000 Electrical Engineering SECTION A (TOTAL MARKS=75) 1. This question consists of 25 (TWENTTY FIVE) sub-questions. Each sub-question carries ONE mark. The answers to these sub-questions MUST be

More information

The power transformer

The power transformer ELEC0014 - Introduction to power and energy systems The power transformer Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 35 Power transformers are used: to transmit

More information

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945

More information

86 chapter 2 Transformers

86 chapter 2 Transformers 86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.

More information

Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC)

Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC) International Journal of Scientific and Research Publications, Volume 2, Issue 5, May 2012 1 Improving the Transient and Dynamic stability of the Network by Unified Power Flow Controller (UPFC) K. Manoz

More information

Enhancement of Power System Voltage Stability Using SVC and TCSC

Enhancement of Power System Voltage Stability Using SVC and TCSC International Journal of Scientific & Engineering Research Volume 4, Issue 1, January-2013 1 Enhancement of Power System Voltage Stability Using SVC and TCSC Deepa Choudhary Department of electrical engineering

More information

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) VOL. 4, NO. 4, JUNE 9 ISSN 89-668 6-9 Asian Research Publishing Network (ARPN). All rights reserved. MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) Rosli Omar and Nasrudin Abd Rahim

More information

EE Branch GATE Paper 2006

EE Branch GATE Paper 2006 Q. 1 Q. 20 carry one mark each 1. The following is true (A) A finite signal is always bounded (B) A bounded signal always possesses finite energy (C) A bounded signal is always zero outside the interval

More information

Voltage Sag Index Calculation Using an Electromagnetic Transients Program

Voltage Sag Index Calculation Using an Electromagnetic Transients Program International Conference on Power Systems Transients IPST 3 in New Orleans, USA Voltage Sag Index Calculation Using an Electromagnetic Transients Program Juan A. Martinez-Velasco, Jacinto Martin-Arnedo

More information

Sample Question Paper

Sample Question Paper Scheme G Sample Question Paper Course Name : Electrical Engineering Group Course Code : EE/EP Semester : Third Subject Title : Electrical Circuit and Network 17323 Marks : 100 Time: 3 hrs Instructions:

More information

Grounding Examples. MVA 1000kW. pu 1 A a 2

Grounding Examples. MVA 1000kW. pu 1 A a 2 Session 2; Page 1/7 Fall 216 Grounding Examples 1 1 1 a 1e j12deg MVA 1kW pu 1 A 12 1 a 2 a 1 a a 2 A 416 V feeder is supplied by the WYE connected side of a 75 MVA transformer. The system MVA sc supplying

More information

Transient Stability Improvement Of Power System With Phase Shifting Transformer

Transient Stability Improvement Of Power System With Phase Shifting Transformer INTERNATIONAL JOURNAL OF TECHNOLOGY ENHANCEMENTS AND EMERGING ENGINEERING RESEARCH, VOL 3, ISSUE 3 19 Transient Stability Improvement Of Power System With Phase Shifting Transformer Jyothi Varanasi, Aditya

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

Code No: R Set No. 1

Code No: R Set No. 1 Code No: R05310204 Set No. 1 III B.Tech I Semester Regular Examinations, November 2007 ELECTRICAL MACHINES-III (Electrical & Electronic Engineering) Time: 3 hours Max Marks: 80 Answer any FIVE Questions

More information

Chapter 2 Shunt Active Power Filter

Chapter 2 Shunt Active Power Filter Chapter 2 Shunt Active Power Filter In the recent years of development the requirement of harmonic and reactive power has developed, causing power quality problems. Many power electronic converters are

More information

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections

More information

PROBLEMS on Transformers

PROBLEMS on Transformers PROBLEMS on Transformers (A) Simple Problems 1. A single-phase, 250-kVA, 11-kV/415-V, 50-Hz transformer has 80 turns on the secondary. Calculate (a) the approximate values of the primary and secondary

More information

POWER SYSTEM II LAB MANUAL

POWER SYSTEM II LAB MANUAL POWER SYSTEM II LAB MANUAL (CODE : EE 692) JIS COLLEGE OF ENGINEERING (An Autonomous Institution) Electrical Engineering Department Kalyani, Nadia POWER SYSTEM II CODE : EE 692 Contacts :3P Credits : 2

More information

GATE 2009 Electrical Engineering

GATE 2009 Electrical Engineering Q. No. 1 20 Carry One Mark Each GATE 2009 Electrical Engineering 1. The pressure coil of a dynamometer type wattmeter is (A) highly inductive (B) highly resistive (C) purely resistive (D) purely inductive

More information

Figure Derive the transient response of RLC series circuit with sinusoidal input. [15]

Figure Derive the transient response of RLC series circuit with sinusoidal input. [15] COURTESY IARE Code No: R09220205 R09 SET-1 B.Tech II Year - II Semester Examinations, December-2011 / January-2012 NETWORK THEORY (ELECTRICAL AND ELECTRONICS ENGINEERING) Time: 3 hours Max. Marks: 80 Answer

More information

Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK

Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK Omar G. Mrehel Hassan B. Elfetori AbdAllah O. Hawal Electrical and Electronic Dept. Operation Department Electrical

More information

Question Paper Profile

Question Paper Profile I Scheme Question Paper Profile Program Name : Electrical Engineering Program Group Program Code : EE/EP/EU Semester : Third Course Title : Electrical Circuits Max. Marks : 70 Time: 3 Hrs. Instructions:

More information

Transient Stability Improvement Of IEEE 9 Bus System With Shunt FACTS Device STATCOM

Transient Stability Improvement Of IEEE 9 Bus System With Shunt FACTS Device STATCOM Transient Stability Improvement Of IEEE 9 Bus System With Shunt FACTS Device STATCOM P.P. Panchbhai 1, P.S.Vaidya 2 1Pratiksha P Panchbhai, Dept. of Electrical Engineering, G H Raisoni College of Engineering

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Incorporation of Self-Commutating CSC Transmission in Power System Load-Flow

Incorporation of Self-Commutating CSC Transmission in Power System Load-Flow Queensland University of Technology From the SelectedWorks of Lasantha Bernard Perera Spring September 25, 2005 Incorporation of Self-Commutating CSC Transmission in Power System Load-Flow Lasantha B Perera,

More information

CHAPTER 9. Sinusoidal Steady-State Analysis

CHAPTER 9. Sinusoidal Steady-State Analysis CHAPTER 9 Sinusoidal Steady-State Analysis 9.1 The Sinusoidal Source A sinusoidal voltage source (independent or dependent) produces a voltage that varies sinusoidally with time. A sinusoidal current source

More information