Grounding Examples. MVA 1000kW. pu 1 A a 2

Size: px
Start display at page:

Download "Grounding Examples. MVA 1000kW. pu 1 A a 2"

Transcription

1 Session 2; Page 1/7 Fall 216 Grounding Examples a 1e j12deg MVA 1kW pu 1 A 12 1 a 2 a 1 a a 2 A 416 V feeder is supplied by the WYE connected side of a 75 MVA transformer. The system MVA sc supplying the delta side of the transformer is 65 MVA. The transformer has a leakage reactance of 1%. A ground impedance will be connected in the neutral of 4.16kV side of the transformer to limit fault currents. A Sketch the per unit diagram for the system 1MVA Srated 75MVA V_LL 4.16kV V_LL V_ln V_ln 2.42kV MVAsc 65MVA 1. 2 _pu _pu.154pu MVAsc X_xfmr.1 X_xfmr 416V 416V.1pu 2 Srated V src j.154pu j.1pu

2 Session 2; Page 2/7 Fall 216 B Determine sequence networks for the system Positive Sequence: Negative Sequence: j.154pu j.1pu j.154pu j.1 pu V src Zero Sequence: j.154pu j.1pu Z gnd Note that this is a -Y grounded transformer. Also, assuming that zero sequence leakage impedance equal to positive and negative sequence values. C Assume that the feeder is all overhead lines with negligable capacitance. Determine the ground reactance needed to limit the single line to ground fault current to 6A. If_slgmax 6A Ibase Ibase 1.88kA V_LL If_slgmax Ifpu Ifpu.42pu Ibase Zbase V_LL 2 For a SLG fault we have (connect positive, negative and zero sequence circuits in series): I = Z1 Z2 Z j Xgnd where 1. e j9 deg Ifpu and we know for a SLG fault: I Solve for Zgnd Z1 j_pu jx_xfmr Z2 Z1 Z jx_xfmr 1 Zgnd ( Z1 Z2 Z) I Zgnd 2.772i per unit

3 Session 2; Page /7 Fall 216 Xgndpu Im( Zgnd) Xgndpu 2.77 per unit Xgnd XgndpuZbase Xgnd.59 Ω Xgnd Lgnd 2π6Hz Lgnd.954 mh at 6Hz D If the feeder is largely underground, the capacitance cannot be neglected. If the total per phase capacitance to ground is 1.5 F, determine the grounding resistance needed to limit the single line to ground fault current to 2 A. Cparasitic 1.5μF 1 Xc 2π6Hz Cparasitic Xc kω Xc Xc_pu Xc_pu pu Zbase Islg_max 2A Islg_max Islgpu Islgpu pu Ibase The sequence networks will now change with the addition of the capacitance as shown. j.154 pu j.1pu Positive Sequence -j1218.6pu j.154 pu j.1pu I Negative Sequence -j1218.6pu j.154 pu j.1pu Zero Sequence R gnd -j1218.6pu

4 Session 2; Page 4/7 Fall 216 I = Z1 Z2 [( Z Rg) ( jxc) ] Z Rg jxc Note that Z1+Z2 will be much much smaller than the parallel combination of R and -jxc, to that Z1 and Z2 can be neglected, as can Z We also, only care about the magnitude of the reduced current, not the angle. So we are actually solving: I = [( ZRg) ( jxc) ] ZRgjXc which requires an iterative solution. I Islgpu Initial Guess: Rg 1 MathCAD solve block: Given I = ( Rg Z) ( jxc_pu) ( Rg Z) jxc_pu Rgnd_pu Find( Rg) Rgnd_pu Rgnd Rgnd_puZbase Rgnd Ω

5 Session 2; Page 5/7 Fall 216 E Calculate the line to ground voltages on the unfaulted phases in parts C and D and calculate the zero sequence voltages and currents. Part C: I_partC Z jxgndpu Z1 Z2 I_partC.144 I1_partC I_partC I2_partC I_partC as a check: Ia_partC I_partC Ia_partC.42 pu Ia_partC Ibase 6kA V1_partC I1_partCZ1 V1_partC.959i V2_partC I2_partCZ2 V2_partC.41i V_partC I_partC( Z jxgndpu) V_partC.917i V_partC Vabc_partC A 12 V1_partC V2_partC Vabc_partC i i Vabc_partC arg( Vabc_partC) deg V_ln Vabc_partC kv Part D: ZgndD ( Rgnd_pu Z) ( jxc_pu) ( Rgnd_pu Z) jxc_pu I_partD ZgndD Z1 Z2 I_partD i 1 4 I1_partD I_partD I2_partD I_partD I_partD

6 Session 2; Page 6/7 Fall 216 as a check: Ia_partD I_partD Ia_partD pu Ia_partD Ibase 2.1A V1_partD I1_partDZ1 V1_partD 1 V2_partD I2_partDZ2 V2_partD V_partD I_partD( ZgndD) V_partD 1 V_partD Vabc_partD A 12 V1_partD V2_partD Vabc_partD i i Vabc_partD V_ln Vabc_partD kv arg( Vabc_partD) deg F Compute the single line to ground fault current and the voltage on the unfaulted phases if the transformer is solidly grounded. Calculate the zero sequence voltages and currents. I_gnd Z Z1 Z2 I_gnd 1.41 I1_gnd I_gnd I2_gnd I_gnd Ia_gnd I_gnd Ia_gnd 4.29 per unit Ia_gndIbase 58.8kA V1_gnd I1_gndZ1 V1_gnd.594i V2_gnd I2_gndZ2 V2_gnd.46i V_gnd I_gndZ V_gnd.18841i

7 Session 2; Page 7/7 Fall 216 V_gnd 1 16 Vabc A 12 V1_gnd V2_gnd Vabc i i Vabc arg( Vabc) deg Note that Vb and Vc are nearly 1. per unit, and are slightly depressed. If Z=Z1=Z2 then they would be 1. and offset from each other by 12 degrees. V_LL Vabc kv G For the different grounded cases described above, discuss the available quantities to measure for ground fault protection and suggest a scheme to consider (based on voltage, current, etc). For the high resistance grounded case, there isn't enough current available for doing ground fault protection, but V is 1pu, so there is enough voltage available to use that to identify the presense of a ground fault. For the case with the low inductance grounded, there is sufficient I for detecting a fault, although any fault impedance (resistance) may make this too difficult. There is also probably sufficient V to use that to detect the fault. For the solidly grounded case, V is pretty small, and it might be hard to discriminate sufficiently to identify a fault. On the other hand, I is large.

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

EN Assignment No.1 - TRANSFORMERS

EN Assignment No.1 - TRANSFORMERS EN-06 - Assignment No.1 - TRANSFORMERS Date : 13 th Jan 01 Q1) A 0kVA 00/0 Volts, 60Hz, single phase transformer is found to have the following equivalent circuit parameter referred to the high potential

More information

In Class Examples (ICE)

In Class Examples (ICE) In Class Examples (ICE) 1 1. A 3φ 765kV, 60Hz, 300km, completely transposed line has the following positive-sequence impedance and admittance: z = 0.0165 + j0.3306 = 0.3310 87.14 o Ω/km y = j4.67 410-6

More information

148 Electric Machines

148 Electric Machines 148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional

More information

Spring 2000 EE361: MIDTERM EXAM 1

Spring 2000 EE361: MIDTERM EXAM 1 NAME: STUDENT NUMBER: Spring 2000 EE361: MIDTERM EXAM 1 This exam is open book and closed notes. Assume f=60 hz and use the constant µ o =4π 10-7 wherever necessary. Be sure to show all work clearly. 1.

More information

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Level 6 Graduate Diploma in Engineering Electrical Energy Systems 9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,

More information

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING. MIDTERM EXAMINATION, February Forth Year Electrical and Computer Engineering

UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING. MIDTERM EXAMINATION, February Forth Year Electrical and Computer Engineering NAME: LAST UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENINEERIN MIDTERM EXAMINATION, February 017 Forth Year Electrical and Computer Engineering ECE413 Energy Systems and Distribution eneration

More information

IGEE 402 Power System Analysis. FINAL EXAMINATION Fall 2004

IGEE 402 Power System Analysis. FINAL EXAMINATION Fall 2004 IGEE 40 Power System Analysis FINAL EXAMINATION Fall 004 Special instructions: - Duration: 150 minutes. - Material allowed: a crib sheet (double sided 8.5 x 11), calculator. - Attempt 4 out of 7 questions.

More information

, ,54 A

, ,54 A AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering) R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between

More information

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS) SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS) SLIDE In this video, we will cover a sample exam problem for the Power PE Exam. This exam problem falls under the topic of Protection, which accounts for

More information

86 chapter 2 Transformers

86 chapter 2 Transformers 86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

Hours / 100 Marks Seat No.

Hours / 100 Marks Seat No. 17323 14115 3 Hours / 100 Seat No. Instructions (1) All Questions are Compulsory. (2) Illustrate your answers with neat sketches wherever necessary. (3) Figures to the right indicate full marks. (4) Assume

More information

Safety through proper system Grounding and Ground Fault Protection

Safety through proper system Grounding and Ground Fault Protection Safety through proper system Grounding and Ground Fault Protection November 4 th, 2015 Presenter: Mr. John Nelson, PE, FIEEE, NEI Electric Power Engineering, Inc. Event to start shortly Scheduled time:

More information

IV. Three-Phase Transfomers

IV. Three-Phase Transfomers I. Three-Phase Transfomers Three-Phase Transfomers The majority of the power generation/distribution systems in the world are 3- phase systems. The transformers for such circuits can be constructed either

More information

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit

More information

Chapter 2: Transformers

Chapter 2: Transformers Chapter 2: Transformers 2-1. The secondary winding of a transformer has a terminal voltage of v s (t) = 282.8 sin 377t V. The turns ratio of the transformer is 100:200 (a = 0.50). If the secondary current

More information

Questions Bank of Electrical Circuits

Questions Bank of Electrical Circuits Questions Bank of Electrical Circuits 1. If a 100 resistor and a 60 XL are in series with a 115V applied voltage, what is the circuit impedance? 2. A 50 XC and a 60 resistance are in series across a 110V

More information

Code No: R Set No. 1

Code No: R Set No. 1 Code No: R05310204 Set No. 1 III B.Tech I Semester Regular Examinations, November 2007 ELECTRICAL MACHINES-III (Electrical & Electronic Engineering) Time: 3 hours Max Marks: 80 Answer any FIVE Questions

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Question Paper Profile

Question Paper Profile I Scheme Question Paper Profile Program Name : Electrical Engineering Program Group Program Code : EE/EP/EU Semester : Third Course Title : Electrical Circuits Max. Marks : 70 Time: 3 Hrs. Instructions:

More information

Chapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc.

Chapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc. Chapter 30 Inductance, Electromagnetic Oscillations, and AC Circuits 30-7 AC Circuits with AC Source Resistors, capacitors, and inductors have different phase relationships between current and voltage

More information

Fault Analysis. EE 340 Spring 2012

Fault Analysis. EE 340 Spring 2012 Fault Analysis EE 340 Spring 2012 Introduction A fault in a circuit is any failure that interferes with the normal system operation. Lighting strokes cause most faults on highvoltage transmission lines

More information

Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK

Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK Omar G. Mrehel Hassan B. Elfetori AbdAllah O. Hawal Electrical and Electronic Dept. Operation Department Electrical

More information

Lecture 16 Date: Frequency Response (Contd.)

Lecture 16 Date: Frequency Response (Contd.) Lecture 16 Date: 03.10.2017 Frequency Response (Contd.) Bode Plot (contd.) Bode Plot (contd.) Bode Plot (contd.) not every transfer function has all seven factors. To sketch the Bode plots for a generic

More information

Modeling of Three-phase or Bank of Three Single Phase Three Winding Transformers Zero-phase-sequence Leakage Impedance in PSS E Short Circuit Module

Modeling of Three-phase or Bank of Three Single Phase Three Winding Transformers Zero-phase-sequence Leakage Impedance in PSS E Short Circuit Module Siemens Industry, Inc. Power Technology Issue 125 Modeling of Three-phase or Bank of Three Single Phase Three Winding Transformers Zero-phase-sequence Leakage Impedance in PSS E Short Circuit Module Carlos

More information

UNIVERSITY OF SWAZILAND MAIN EXAMINATION, DECEMBER 2016

UNIVERSITY OF SWAZILAND MAIN EXAMINATION, DECEMBER 2016 UNIVERSITY OF SWAZILAND MAIN EXAMINATION, DECEMBER 2016 FACULTY OF SCIENCE AND ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONIC ENGINEERING TITLE OF PAPER: POWER SYSTEM ANALYSIS AND OPERATION COURSE

More information

LOW-RESISTANCE grounding resistors (LRGs) appear

LOW-RESISTANCE grounding resistors (LRGs) appear IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 44, NO. 5, SEPTEMBER/OCTOBER 2008 1311 Grounding the Neutral of Electrical Systems Through Low-Resistance Grounding Resistors: An Application Case Massimo

More information

Conventional Paper-II-2011 Part-1A

Conventional Paper-II-2011 Part-1A Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance

More information

Resonance. A resonant circuit (series or parallel) must have an inductive and a capacitive element.

Resonance. A resonant circuit (series or parallel) must have an inductive and a capacitive element. 1. Series Resonant: Resonance A resonant circuit (series or parallel) must have an inductive and a capacitive element. The total impedance of this network is: The circuit will reach its maximum Voltage

More information

UNIVERSITY OF NORTH CAROLINA AT CHARLOTTE Department of Electrical and Computer Engineering

UNIVERSITY OF NORTH CAROLINA AT CHARLOTTE Department of Electrical and Computer Engineering UNIVERSITY OF NORTH CAROLINA AT CHARLOTTE Department of Electrical and Computer Engineering EXPERIMENT 10 BALANCED THREE-PHASE NETWORKS OBJECTIVES In this experiment the student will explore balanced three-phase

More information

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions

More information

EE Branch GATE Paper 2001 SECTION A (TOTAL MARKS = 75)

EE Branch GATE Paper 2001 SECTION A (TOTAL MARKS = 75) SECTION A (TOTAL MARKS = 75) 1. This question consists of 25 (TWENTY-FIVE) sub-questions (1.1-1.25) of ONE mark each. (25 1 = 25 ) 1.1 In a series RLC circuit at resonance, the magnitude of the voltage

More information

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies T.G. Martinich, M. Nagpal, A. Bimbhra Abstract-- Technological advancements in high-power

More information

GRADE 12 SEPTEMBER 2012 ELECTRICAL TECHNOLOGY

GRADE 12 SEPTEMBER 2012 ELECTRICAL TECHNOLOGY Province of the EASTERN CAPE EDUCATION NATIONAL SENIOR CERTIFICATE GRADE 12 SEPTEMBER 2012 ELECTRICAL TECHNOLOGY MARKS: 200 TIME: 3 hours This question paper consists of 11 pages and a formula sheet. 2

More information

Tutorial on Symmetrical Components

Tutorial on Symmetrical Components Tutorial on Symmetrical Components Part : Examples Ariana Amberg and Alex Rangel, Schweitzer Engineering Laboratories, nc. Abstract Symmetrical components and the per-unit system are two of the most fundamental

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

AP Physics C. Alternating Current. Chapter Problems. Sources of Alternating EMF

AP Physics C. Alternating Current. Chapter Problems. Sources of Alternating EMF AP Physics C Alternating Current Chapter Problems Sources of Alternating EMF 1. A 10 cm diameter loop of wire is oriented perpendicular to a 2.5 T magnetic field. What is the magnetic flux through the

More information

Fatima Michael college of Engineering and Technology

Fatima Michael college of Engineering and Technology Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric

More information

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab University of Jordan School of Engineering Electrical Engineering Department EE 219 Electrical Circuits Lab EXPERIMENT 7 RESONANCE Prepared by: Dr. Mohammed Hawa EXPERIMENT 7 RESONANCE OBJECTIVE This experiment

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

Code No: R Set No. 1

Code No: R Set No. 1 Code No: R05220204 Set No. 1 II B.Tech II Semester Supplimentary Examinations, Aug/Sep 2007 ELECTRICAL MACHINES-II (Electrical & Electronic Engineering) Time: 3 hours Max Marks: 80 Answer any FIVE Questions

More information

Form B. Connection Impact Assessment Application Form Distribution System

Form B. Connection Impact Assessment Application Form Distribution System Form B Connection Impact Assessment Application Form Distribution System This Application Form is for Generators applying for Connection Impact Assessment ( CIA ). It is important that the Generator provides

More information

DISTRIBUTION DEVICE COORDINATION

DISTRIBUTION DEVICE COORDINATION DISTRIBUTION DEVICE COORDINATION Kevin Damron & Calvin Howard Avista Utilities Presented March th, 08 At the 5 th Annual Hands-On Relay School Washington State University Pullman, Washington TABLE OF CONTENTS

More information

Downloaded from / 1

Downloaded from   / 1 PURWANCHAL UNIVERSITY II SEMESTER FINAL EXAMINATION-2008 LEVEL : B. E. (Computer/Electronics & Comm.) SUBJECT: BEG123EL, Electrical Engineering-I Full Marks: 80 TIME: 03:00 hrs Pass marks: 32 Candidates

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic

More information

2 Grounding of power supply system neutral

2 Grounding of power supply system neutral 2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the

More information

University of Rajshahi Department of Electrical & Electronic Engineering B.Sc. Engineering Part-IV Odd Semester Examination- 2017

University of Rajshahi Department of Electrical & Electronic Engineering B.Sc. Engineering Part-IV Odd Semester Examination- 2017 Course Code: EEE 4141 Course Title: Power System i. Answer to all parts (a), (b), (c) etc. of a question must be contiguous. ii. Use separate answer script for each Section (A/B). iii. Right margin indicates

More information

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Short-Circuit Analysis IEC Standard 1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Purpose of Short-Circuit Studies A Short-Circuit Study can be used to determine any or all of

More information

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar. Technical Report on Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by Dr. V. R. Kanetkar (February 2015) Shreem Electric Limited (Plot No. 43-46, L. K. Akiwate

More information

CHAPTER 6: ALTERNATING CURRENT

CHAPTER 6: ALTERNATING CURRENT CHAPTER 6: ALTERNATING CURRENT PSPM II 2005/2006 NO. 12(C) 12. (c) An ac generator with rms voltage 240 V is connected to a RC circuit. The rms current in the circuit is 1.5 A and leads the voltage by

More information

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance The Effect of Various Types of DG Interconnection Transformer on Ferroresonance M. Esmaeili *, M. Rostami **, and G.B. Gharehpetian *** * MSc Student, Member, IEEE, Shahed University, Tehran, Iran, E mail:

More information

Babak Enayati National Grid Thursday, April 17

Babak Enayati National Grid Thursday, April 17 2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April

More information

Conventional Paper-II-2013

Conventional Paper-II-2013 1. All parts carry equal marks Conventional Paper-II-013 (a) (d) A 0V DC shunt motor takes 0A at full load running at 500 rpm. The armature resistance is 0.4Ω and shunt field resistance of 176Ω. The machine

More information

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE Professor Akhtar Kalam Victoria University The Problem Calculate & sketch the ZPS, NPS & PPS impedance networks. Calculate feeder faults. Calculate

More information

Grid Impact of Neutral Blocking for GIC Protection:

Grid Impact of Neutral Blocking for GIC Protection: Report submitted to EMPRIMUS - Critical Infrastructure Protection Grid Impact of Neutral Blocking for GIC Protection: Impact of neutral grounding capacitors on network resonance Prepared By: Athula Rajapakse

More information

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit CHAPTER 2 Basic Concepts, Three-Phase Review, and Per Unit 1 AC power versus DC power DC system: - Power delivered to the load does not fluctuate. - If the transmission line is long power is lost in the

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Reg. No. : BASIC ELECTRICAL TECHNOLOGY (ELE 101)

Reg. No. : BASIC ELECTRICAL TECHNOLOGY (ELE 101) Department of Electrical and Electronics Engineering Reg. No. : MNIPL INSTITUTE OF TECHNOLOGY, MNIPL ( Constituent Institute of Manipal University, Manipal) FIRST SEMESTER B.E. DEGREE MKEUP EXMINTION (REVISED

More information

BAKISS HIYANA BT ABU BAKAR JKE,POLISAS

BAKISS HIYANA BT ABU BAKAR JKE,POLISAS BAKISS HIYANA BT ABU BAKAR JKE,POLISAS 1 1. Explain AC circuit concept and their analysis using AC circuit law. 2. Apply the knowledge of AC circuit in solving problem related to AC electrical circuit.

More information

SCHEME OF COURSE WORK ( ) Electrical & Electronics Engineering. Electrical machines-i, II and power transmission engineering

SCHEME OF COURSE WORK ( ) Electrical & Electronics Engineering. Electrical machines-i, II and power transmission engineering SCHEME OF COURSE WORK (2015-2016) COURSE DETAILS: Course Title Course Code Program Branch Semester Prerequisites Course to which it is prerequisite Switchgear and Protection 15EE1116 B.Tech Electrical

More information

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Disclaimer: All information presented in the report, the results and the related computer program, data,

More information

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed

More information

COURSE PLANNER SUBJECT: ELECTRICAL POWER SYSTEM II

COURSE PLANNER SUBJECT: ELECTRICAL POWER SYSTEM II COURSE PLANNER SUBJECT: ELECTRICAL POWER SYSTEM II [260908] B.E. Third Year Class Electrical 204 Term: 6/2 (DEC-6 to APR-7) Faculty: PROF. J. I. JARIWALA PROF. A. S. SHAH PROF. T. M. PANCHAL PROF. N. B.

More information

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Calculation of Isc by the impedance method In a 3-phase installation Isc at any point is

More information

Three-Phase/Six-Phase Conversion Autotransformers

Three-Phase/Six-Phase Conversion Autotransformers 1554 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 4, OCTOBER 2003 Three-Phase/Six-Phase Conversion Autotransformers Xusheng Chen, Member, IEEE Abstract The first commercial demonstration of six-phase

More information

TRANSMISSION LINE 1. Instructed by: Miss. R T Gunasekara

TRANSMISSION LINE 1. Instructed by: Miss. R T Gunasekara TRANSMISSION LINE 1 Instructed by: Miss. R T Gunasekara Name :- D.K.Pathirana Index No :- 080332P Group :- EE9 Date of Per. :- 24/01/2011 Instructed by :- R.T.Gunasekara OBSEVATION SHEET Name :- D.K.Pathirana

More information

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits QUESTION BANK ETE (17331) CM/IF Chapter1: DC Circuits Q1. State & explain Ohms law. Also explain concept of series & parallel circuit with the help of diagram. 3M Q2. Find the value of resistor in fig.

More information

PROBLEMS on Transformers

PROBLEMS on Transformers PROBLEMS on Transformers (A) Simple Problems 1. A single-phase, 250-kVA, 11-kV/415-V, 50-Hz transformer has 80 turns on the secondary. Calculate (a) the approximate values of the primary and secondary

More information

Beskrivelse av simuleringsmodell ==> Description of simulation model

Beskrivelse av simuleringsmodell ==> Description of simulation model Infrastruktur Elkraft / Energy Side / Page: 1 av / of 6 Beskrivelse av simuleringsmodell ==> Description of simulation model General The modelled system consists of one rotary converter (synchronous-synchronous

More information

Connection Impact Assessment Application

Connection Impact Assessment Application Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,

More information

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations

Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations A.R. Sultan, M.W. Mustafa, M.Saini Faculty of Electrical Engineering Universiti Teknologi Malaysia (UTM)

More information

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS

CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS 40 CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS 3.1 INTRODUCTION The low power factor effects on transmission line, switchgear, transformers etc. It is observed that if the power

More information

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example

More information

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Expo - Nov. 3, 2014 Index Normal Distribution System

More information

Modeling and Performance Analysis of Mho-Relay in Matlab

Modeling and Performance Analysis of Mho-Relay in Matlab Modeling and Performance Analysis of Mho-Relay in Matlab Purra Sai Kiran M.Tech Student, Padmasri Dr. B V Raju Institute of Technology, Narsapur, Medak, Telangana. ABSTRACT: This paper describes the opportunity

More information

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) VOL. 4, NO. 4, JUNE 9 ISSN 89-668 6-9 Asian Research Publishing Network (ARPN). All rights reserved. MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) Rosli Omar and Nasrudin Abd Rahim

More information

Harmonic control devices

Harmonic control devices ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 24 1 Today Harmonic control devices In-line reactors (chokes)

More information

Exercises on overhead power lines (and underground cables)

Exercises on overhead power lines (and underground cables) Exercises on overhead power lines (and underground cables) 1 From the laws of Electromagnetism it can be shown that l c = 1 v 2 where v is the speed of propagation of electromagnetic waves in the environment

More information

Impedance protection on power transformer.

Impedance protection on power transformer. Impedance protection on power transformer www.siemens.com/siprotec5 SIPROTEC 5 Application Impedance Protection on Power Transformer APN-045, Edition 1 Content 1...3 1.1 Introduction...3 1.2 Application

More information

Transient Recovery Voltage at Transformer Limited Fault Clearing

Transient Recovery Voltage at Transformer Limited Fault Clearing Transient Recovery Voltage at Transformer Limited Fault Clearing H. Kagawa (Tokyo Electric power Company, Japan) A. Janssen (Liander N.V., the Netherlands) D. Dufounet (Consultant, France) H. Kajino, H.

More information

Series and Parallel Resonant Circuits

Series and Parallel Resonant Circuits Series and Parallel Resonant Circuits Aim: To obtain the characteristics of series and parallel resonant circuits. Apparatus required: Decade resistance box, Decade inductance box, Decade capacitance box

More information

Sample Question Paper

Sample Question Paper Scheme G Sample Question Paper Course Name : Electrical Engineering Group Course Code : EE/EP Semester : Third Subject Title : Electrical Circuit and Network 17323 Marks : 100 Time: 3 hrs Instructions:

More information

Any wave shape can be reproduced by the sum of sine waves of the appropriate magnitude and frequency.

Any wave shape can be reproduced by the sum of sine waves of the appropriate magnitude and frequency. How do we use an oscilloscope? Measure signals with unknown wave shapes and frequency other than 60 Hz sine waves and dc. To get a picture of the waveform. Distortion? Phase duration? Magnitude Any wave

More information

Class XII Chapter 7 Alternating Current Physics

Class XII Chapter 7 Alternating Current Physics Question 7.1: A 100 Ω resistor is connected to a 220 V, 50 Hz ac supply. (a) What is the rms value of current in the circuit? (b) What is the net power consumed over a full cycle? Resistance of the resistor,

More information

Optimal neutral ground resistor rating of the medium voltage systems in power generating stations

Optimal neutral ground resistor rating of the medium voltage systems in power generating stations Journal of International Council on Electrical Engineering ISSN: (Print) 2234-8972 (Online) Journal homepage: http://www.tandfonline.com/loi/tjee20 Optimal neutral ground resistor rating of the medium

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

Connection Impact Assessment Application Form

Connection Impact Assessment Application Form Connection Impact Assessment Application Form This Application Form is for Generators applying for a Connection Impact Assessment (CIA). In certain circumstances, London Hydro may require additional information

More information

Initial Application Form for Connection of Distributed Generation (>10kW)

Initial Application Form for Connection of Distributed Generation (>10kW) Please complete the following information and forward to Vector Contact Details Primary Contact (who we should contact for additional information) Contact person Company name Contact numbers Daytime: Cell

More information

Lab 4. Transistor as an amplifier, part 2

Lab 4. Transistor as an amplifier, part 2 Lab 4 Transistor as an amplifier, part 2 INTRODUCTION We continue the bi-polar transistor experiments begun in the preceding experiment. In the common emitter amplifier experiment, you will learn techniques

More information

Smart Ground Test Report. Springfield Energy - Springfield Power Station Grounding System Evaluation

Smart Ground Test Report. Springfield Energy - Springfield Power Station Grounding System Evaluation Smart Ground Test Report Springfield Energy - Springfield Power Station Grounding System Evaluation Prepared for *C.M. Burns *Springfield Energy Springfield Power Station U.S.A. Prepared by A. P. Sakis

More information

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08

The development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08 The development of the SA grid code on Power Quality emission Dr. Gerhard Botha 2017/08/08 Overview What is the Grid Code? What is Power Quality? Power Quality Management Principles Differences Challenges

More information

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics EE589-Power System Quality & Harmonics Electrical Engineering Department School of Engineering University of Jordan 1 Control of Harmonics

More information

Teaching Distance Relay Using Matlab/Simulink Graphical User Interface

Teaching Distance Relay Using Matlab/Simulink Graphical User Interface Available online at www.sciencedirect.com Procedia Engineering 53 ( 2013 ) 264 270 Malaysian Technical Universities Conference on Engineering & Technology 2012, MUCET 2012 Part 1 - Electronic and Electrical

More information

FAULT LOCATING USING VOLTAGE AND CURRENT MEASUREMENTS

FAULT LOCATING USING VOLTAGE AND CURRENT MEASUREMENTS The BEST Group THE BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP -Winter Lecture Series FAULT LOCATING USING VOLTAGE AND CURRENT MEASUREMENTS Presented by: Syed Khundmir T Department of Electrical Engineering

More information

EE 340 Transmission Lines. Spring 2012

EE 340 Transmission Lines. Spring 2012 EE 340 Transmission Lines Spring 2012 Physical Characteristics Overhead lines An overhead transmission line usually consists of three conductors or bundles of conductors containing the three phases of

More information