Grounding Examples. MVA 1000kW. pu 1 A a 2
|
|
- Kerry York
- 6 years ago
- Views:
Transcription
1 Session 2; Page 1/7 Fall 216 Grounding Examples a 1e j12deg MVA 1kW pu 1 A 12 1 a 2 a 1 a a 2 A 416 V feeder is supplied by the WYE connected side of a 75 MVA transformer. The system MVA sc supplying the delta side of the transformer is 65 MVA. The transformer has a leakage reactance of 1%. A ground impedance will be connected in the neutral of 4.16kV side of the transformer to limit fault currents. A Sketch the per unit diagram for the system 1MVA Srated 75MVA V_LL 4.16kV V_LL V_ln V_ln 2.42kV MVAsc 65MVA 1. 2 _pu _pu.154pu MVAsc X_xfmr.1 X_xfmr 416V 416V.1pu 2 Srated V src j.154pu j.1pu
2 Session 2; Page 2/7 Fall 216 B Determine sequence networks for the system Positive Sequence: Negative Sequence: j.154pu j.1pu j.154pu j.1 pu V src Zero Sequence: j.154pu j.1pu Z gnd Note that this is a -Y grounded transformer. Also, assuming that zero sequence leakage impedance equal to positive and negative sequence values. C Assume that the feeder is all overhead lines with negligable capacitance. Determine the ground reactance needed to limit the single line to ground fault current to 6A. If_slgmax 6A Ibase Ibase 1.88kA V_LL If_slgmax Ifpu Ifpu.42pu Ibase Zbase V_LL 2 For a SLG fault we have (connect positive, negative and zero sequence circuits in series): I = Z1 Z2 Z j Xgnd where 1. e j9 deg Ifpu and we know for a SLG fault: I Solve for Zgnd Z1 j_pu jx_xfmr Z2 Z1 Z jx_xfmr 1 Zgnd ( Z1 Z2 Z) I Zgnd 2.772i per unit
3 Session 2; Page /7 Fall 216 Xgndpu Im( Zgnd) Xgndpu 2.77 per unit Xgnd XgndpuZbase Xgnd.59 Ω Xgnd Lgnd 2π6Hz Lgnd.954 mh at 6Hz D If the feeder is largely underground, the capacitance cannot be neglected. If the total per phase capacitance to ground is 1.5 F, determine the grounding resistance needed to limit the single line to ground fault current to 2 A. Cparasitic 1.5μF 1 Xc 2π6Hz Cparasitic Xc kω Xc Xc_pu Xc_pu pu Zbase Islg_max 2A Islg_max Islgpu Islgpu pu Ibase The sequence networks will now change with the addition of the capacitance as shown. j.154 pu j.1pu Positive Sequence -j1218.6pu j.154 pu j.1pu I Negative Sequence -j1218.6pu j.154 pu j.1pu Zero Sequence R gnd -j1218.6pu
4 Session 2; Page 4/7 Fall 216 I = Z1 Z2 [( Z Rg) ( jxc) ] Z Rg jxc Note that Z1+Z2 will be much much smaller than the parallel combination of R and -jxc, to that Z1 and Z2 can be neglected, as can Z We also, only care about the magnitude of the reduced current, not the angle. So we are actually solving: I = [( ZRg) ( jxc) ] ZRgjXc which requires an iterative solution. I Islgpu Initial Guess: Rg 1 MathCAD solve block: Given I = ( Rg Z) ( jxc_pu) ( Rg Z) jxc_pu Rgnd_pu Find( Rg) Rgnd_pu Rgnd Rgnd_puZbase Rgnd Ω
5 Session 2; Page 5/7 Fall 216 E Calculate the line to ground voltages on the unfaulted phases in parts C and D and calculate the zero sequence voltages and currents. Part C: I_partC Z jxgndpu Z1 Z2 I_partC.144 I1_partC I_partC I2_partC I_partC as a check: Ia_partC I_partC Ia_partC.42 pu Ia_partC Ibase 6kA V1_partC I1_partCZ1 V1_partC.959i V2_partC I2_partCZ2 V2_partC.41i V_partC I_partC( Z jxgndpu) V_partC.917i V_partC Vabc_partC A 12 V1_partC V2_partC Vabc_partC i i Vabc_partC arg( Vabc_partC) deg V_ln Vabc_partC kv Part D: ZgndD ( Rgnd_pu Z) ( jxc_pu) ( Rgnd_pu Z) jxc_pu I_partD ZgndD Z1 Z2 I_partD i 1 4 I1_partD I_partD I2_partD I_partD I_partD
6 Session 2; Page 6/7 Fall 216 as a check: Ia_partD I_partD Ia_partD pu Ia_partD Ibase 2.1A V1_partD I1_partDZ1 V1_partD 1 V2_partD I2_partDZ2 V2_partD V_partD I_partD( ZgndD) V_partD 1 V_partD Vabc_partD A 12 V1_partD V2_partD Vabc_partD i i Vabc_partD V_ln Vabc_partD kv arg( Vabc_partD) deg F Compute the single line to ground fault current and the voltage on the unfaulted phases if the transformer is solidly grounded. Calculate the zero sequence voltages and currents. I_gnd Z Z1 Z2 I_gnd 1.41 I1_gnd I_gnd I2_gnd I_gnd Ia_gnd I_gnd Ia_gnd 4.29 per unit Ia_gndIbase 58.8kA V1_gnd I1_gndZ1 V1_gnd.594i V2_gnd I2_gndZ2 V2_gnd.46i V_gnd I_gndZ V_gnd.18841i
7 Session 2; Page 7/7 Fall 216 V_gnd 1 16 Vabc A 12 V1_gnd V2_gnd Vabc i i Vabc arg( Vabc) deg Note that Vb and Vc are nearly 1. per unit, and are slightly depressed. If Z=Z1=Z2 then they would be 1. and offset from each other by 12 degrees. V_LL Vabc kv G For the different grounded cases described above, discuss the available quantities to measure for ground fault protection and suggest a scheme to consider (based on voltage, current, etc). For the high resistance grounded case, there isn't enough current available for doing ground fault protection, but V is 1pu, so there is enough voltage available to use that to identify the presense of a ground fault. For the case with the low inductance grounded, there is sufficient I for detecting a fault, although any fault impedance (resistance) may make this too difficult. There is also probably sufficient V to use that to detect the fault. For the solidly grounded case, V is pretty small, and it might be hard to discriminate sufficiently to identify a fault. On the other hand, I is large.
Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)
Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:
More informationCourse ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation
Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission
More informationBE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %
BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and
More informationEN Assignment No.1 - TRANSFORMERS
EN-06 - Assignment No.1 - TRANSFORMERS Date : 13 th Jan 01 Q1) A 0kVA 00/0 Volts, 60Hz, single phase transformer is found to have the following equivalent circuit parameter referred to the high potential
More informationIn Class Examples (ICE)
In Class Examples (ICE) 1 1. A 3φ 765kV, 60Hz, 300km, completely transposed line has the following positive-sequence impedance and admittance: z = 0.0165 + j0.3306 = 0.3310 87.14 o Ω/km y = j4.67 410-6
More information148 Electric Machines
148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional
More informationSpring 2000 EE361: MIDTERM EXAM 1
NAME: STUDENT NUMBER: Spring 2000 EE361: MIDTERM EXAM 1 This exam is open book and closed notes. Assume f=60 hz and use the constant µ o =4π 10-7 wherever necessary. Be sure to show all work clearly. 1.
More informationLevel 6 Graduate Diploma in Engineering Electrical Energy Systems
9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,
More informationUNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENGINEERING. MIDTERM EXAMINATION, February Forth Year Electrical and Computer Engineering
NAME: LAST UNIVERSITY OF TORONTO FACULTY OF APPLIED SCIENCE AND ENINEERIN MIDTERM EXAMINATION, February 017 Forth Year Electrical and Computer Engineering ECE413 Energy Systems and Distribution eneration
More informationIGEE 402 Power System Analysis. FINAL EXAMINATION Fall 2004
IGEE 40 Power System Analysis FINAL EXAMINATION Fall 004 Special instructions: - Duration: 150 minutes. - Material allowed: a crib sheet (double sided 8.5 x 11), calculator. - Attempt 4 out of 7 questions.
More information, ,54 A
AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate
More informationR10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)
R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between
More informationSAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)
SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS) SLIDE In this video, we will cover a sample exam problem for the Power PE Exam. This exam problem falls under the topic of Protection, which accounts for
More information86 chapter 2 Transformers
86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.
More informationTopic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017
Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length
More informationHours / 100 Marks Seat No.
17323 14115 3 Hours / 100 Seat No. Instructions (1) All Questions are Compulsory. (2) Illustrate your answers with neat sketches wherever necessary. (3) Figures to the right indicate full marks. (4) Assume
More informationSafety through proper system Grounding and Ground Fault Protection
Safety through proper system Grounding and Ground Fault Protection November 4 th, 2015 Presenter: Mr. John Nelson, PE, FIEEE, NEI Electric Power Engineering, Inc. Event to start shortly Scheduled time:
More informationIV. Three-Phase Transfomers
I. Three-Phase Transfomers Three-Phase Transfomers The majority of the power generation/distribution systems in the world are 3- phase systems. The transformers for such circuits can be constructed either
More informationFerroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions
Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit
More informationChapter 2: Transformers
Chapter 2: Transformers 2-1. The secondary winding of a transformer has a terminal voltage of v s (t) = 282.8 sin 377t V. The turns ratio of the transformer is 100:200 (a = 0.50). If the secondary current
More informationQuestions Bank of Electrical Circuits
Questions Bank of Electrical Circuits 1. If a 100 resistor and a 60 XL are in series with a 115V applied voltage, what is the circuit impedance? 2. A 50 XC and a 60 resistance are in series across a 110V
More informationCode No: R Set No. 1
Code No: R05310204 Set No. 1 III B.Tech I Semester Regular Examinations, November 2007 ELECTRICAL MACHINES-III (Electrical & Electronic Engineering) Time: 3 hours Max Marks: 80 Answer any FIVE Questions
More informationELECTRICAL POWER TRANSMISSION TRAINER
ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering
More informationQuestion Paper Profile
I Scheme Question Paper Profile Program Name : Electrical Engineering Program Group Program Code : EE/EP/EU Semester : Third Course Title : Electrical Circuits Max. Marks : 70 Time: 3 Hrs. Instructions:
More informationChapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc.
Chapter 30 Inductance, Electromagnetic Oscillations, and AC Circuits 30-7 AC Circuits with AC Source Resistors, capacitors, and inductors have different phase relationships between current and voltage
More informationFault Analysis. EE 340 Spring 2012
Fault Analysis EE 340 Spring 2012 Introduction A fault in a circuit is any failure that interferes with the normal system operation. Lighting strokes cause most faults on highvoltage transmission lines
More informationImplementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK
Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK Omar G. Mrehel Hassan B. Elfetori AbdAllah O. Hawal Electrical and Electronic Dept. Operation Department Electrical
More informationLecture 16 Date: Frequency Response (Contd.)
Lecture 16 Date: 03.10.2017 Frequency Response (Contd.) Bode Plot (contd.) Bode Plot (contd.) Bode Plot (contd.) not every transfer function has all seven factors. To sketch the Bode plots for a generic
More informationModeling of Three-phase or Bank of Three Single Phase Three Winding Transformers Zero-phase-sequence Leakage Impedance in PSS E Short Circuit Module
Siemens Industry, Inc. Power Technology Issue 125 Modeling of Three-phase or Bank of Three Single Phase Three Winding Transformers Zero-phase-sequence Leakage Impedance in PSS E Short Circuit Module Carlos
More informationUNIVERSITY OF SWAZILAND MAIN EXAMINATION, DECEMBER 2016
UNIVERSITY OF SWAZILAND MAIN EXAMINATION, DECEMBER 2016 FACULTY OF SCIENCE AND ENGINEERING DEPARTMENT OF ELECTRICAL AND ELECTRONIC ENGINEERING TITLE OF PAPER: POWER SYSTEM ANALYSIS AND OPERATION COURSE
More informationLOW-RESISTANCE grounding resistors (LRGs) appear
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 44, NO. 5, SEPTEMBER/OCTOBER 2008 1311 Grounding the Neutral of Electrical Systems Through Low-Resistance Grounding Resistors: An Application Case Massimo
More informationConventional Paper-II-2011 Part-1A
Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance
More informationResonance. A resonant circuit (series or parallel) must have an inductive and a capacitive element.
1. Series Resonant: Resonance A resonant circuit (series or parallel) must have an inductive and a capacitive element. The total impedance of this network is: The circuit will reach its maximum Voltage
More informationUNIVERSITY OF NORTH CAROLINA AT CHARLOTTE Department of Electrical and Computer Engineering
UNIVERSITY OF NORTH CAROLINA AT CHARLOTTE Department of Electrical and Computer Engineering EXPERIMENT 10 BALANCED THREE-PHASE NETWORKS OBJECTIVES In this experiment the student will explore balanced three-phase
More informationR10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours
Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions
More informationEE Branch GATE Paper 2001 SECTION A (TOTAL MARKS = 75)
SECTION A (TOTAL MARKS = 75) 1. This question consists of 25 (TWENTY-FIVE) sub-questions (1.1-1.25) of ONE mark each. (25 1 = 25 ) 1.1 In a series RLC circuit at resonance, the magnitude of the voltage
More informationAnalysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies
Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies T.G. Martinich, M. Nagpal, A. Bimbhra Abstract-- Technological advancements in high-power
More informationGRADE 12 SEPTEMBER 2012 ELECTRICAL TECHNOLOGY
Province of the EASTERN CAPE EDUCATION NATIONAL SENIOR CERTIFICATE GRADE 12 SEPTEMBER 2012 ELECTRICAL TECHNOLOGY MARKS: 200 TIME: 3 hours This question paper consists of 11 pages and a formula sheet. 2
More informationTutorial on Symmetrical Components
Tutorial on Symmetrical Components Part : Examples Ariana Amberg and Alex Rangel, Schweitzer Engineering Laboratories, nc. Abstract Symmetrical components and the per-unit system are two of the most fundamental
More informationSYNCHRONOUS MACHINES
SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical
More informationAP Physics C. Alternating Current. Chapter Problems. Sources of Alternating EMF
AP Physics C Alternating Current Chapter Problems Sources of Alternating EMF 1. A 10 cm diameter loop of wire is oriented perpendicular to a 2.5 T magnetic field. What is the magnetic flux through the
More informationFatima Michael college of Engineering and Technology
Fatima Michael college of Engineering and Technology DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING EE2303 TRANSMISSION AND DISTRIBUTION SEM: V Question bank UNIT I INTRODUCTION 1. What is the electric
More informationUniversity of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab
University of Jordan School of Engineering Electrical Engineering Department EE 219 Electrical Circuits Lab EXPERIMENT 7 RESONANCE Prepared by: Dr. Mohammed Hawa EXPERIMENT 7 RESONANCE OBJECTIVE This experiment
More informationImpact Assessment Generator Form
Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project
More informationCode No: R Set No. 1
Code No: R05220204 Set No. 1 II B.Tech II Semester Supplimentary Examinations, Aug/Sep 2007 ELECTRICAL MACHINES-II (Electrical & Electronic Engineering) Time: 3 hours Max Marks: 80 Answer any FIVE Questions
More informationForm B. Connection Impact Assessment Application Form Distribution System
Form B Connection Impact Assessment Application Form Distribution System This Application Form is for Generators applying for Connection Impact Assessment ( CIA ). It is important that the Generator provides
More informationDISTRIBUTION DEVICE COORDINATION
DISTRIBUTION DEVICE COORDINATION Kevin Damron & Calvin Howard Avista Utilities Presented March th, 08 At the 5 th Annual Hands-On Relay School Washington State University Pullman, Washington TABLE OF CONTENTS
More informationDownloaded from / 1
PURWANCHAL UNIVERSITY II SEMESTER FINAL EXAMINATION-2008 LEVEL : B. E. (Computer/Electronics & Comm.) SUBJECT: BEG123EL, Electrical Engineering-I Full Marks: 80 TIME: 03:00 hrs Pass marks: 32 Candidates
More informationChapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two
Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead
More informationBus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero
Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic
More information2 Grounding of power supply system neutral
2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the
More informationUniversity of Rajshahi Department of Electrical & Electronic Engineering B.Sc. Engineering Part-IV Odd Semester Examination- 2017
Course Code: EEE 4141 Course Title: Power System i. Answer to all parts (a), (b), (c) etc. of a question must be contiguous. ii. Use separate answer script for each Section (A/B). iii. Right margin indicates
More informationShort-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC
Short-Circuit Analysis IEC Standard 1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Purpose of Short-Circuit Studies A Short-Circuit Study can be used to determine any or all of
More informationTechnical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.
Technical Report on Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by Dr. V. R. Kanetkar (February 2015) Shreem Electric Limited (Plot No. 43-46, L. K. Akiwate
More informationCHAPTER 6: ALTERNATING CURRENT
CHAPTER 6: ALTERNATING CURRENT PSPM II 2005/2006 NO. 12(C) 12. (c) An ac generator with rms voltage 240 V is connected to a RC circuit. The rms current in the circuit is 1.5 A and leads the voltage by
More informationThe Effect of Various Types of DG Interconnection Transformer on Ferroresonance
The Effect of Various Types of DG Interconnection Transformer on Ferroresonance M. Esmaeili *, M. Rostami **, and G.B. Gharehpetian *** * MSc Student, Member, IEEE, Shahed University, Tehran, Iran, E mail:
More informationBabak Enayati National Grid Thursday, April 17
2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April
More informationConventional Paper-II-2013
1. All parts carry equal marks Conventional Paper-II-013 (a) (d) A 0V DC shunt motor takes 0A at full load running at 500 rpm. The armature resistance is 0.4Ω and shunt field resistance of 176Ω. The machine
More informationPOWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University
POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE Professor Akhtar Kalam Victoria University The Problem Calculate & sketch the ZPS, NPS & PPS impedance networks. Calculate feeder faults. Calculate
More informationGrid Impact of Neutral Blocking for GIC Protection:
Report submitted to EMPRIMUS - Critical Infrastructure Protection Grid Impact of Neutral Blocking for GIC Protection: Impact of neutral grounding capacitors on network resonance Prepared By: Athula Rajapakse
More informationCHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit
CHAPTER 2 Basic Concepts, Three-Phase Review, and Per Unit 1 AC power versus DC power DC system: - Power delivered to the load does not fluctuate. - If the transmission line is long power is lost in the
More informationShortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller
Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of
More informationReg. No. : BASIC ELECTRICAL TECHNOLOGY (ELE 101)
Department of Electrical and Electronics Engineering Reg. No. : MNIPL INSTITUTE OF TECHNOLOGY, MNIPL ( Constituent Institute of Manipal University, Manipal) FIRST SEMESTER B.E. DEGREE MKEUP EXMINTION (REVISED
More informationBAKISS HIYANA BT ABU BAKAR JKE,POLISAS
BAKISS HIYANA BT ABU BAKAR JKE,POLISAS 1 1. Explain AC circuit concept and their analysis using AC circuit law. 2. Apply the knowledge of AC circuit in solving problem related to AC electrical circuit.
More informationSCHEME OF COURSE WORK ( ) Electrical & Electronics Engineering. Electrical machines-i, II and power transmission engineering
SCHEME OF COURSE WORK (2015-2016) COURSE DETAILS: Course Title Course Code Program Branch Semester Prerequisites Course to which it is prerequisite Switchgear and Protection 15EE1116 B.Tech Electrical
More informationSimulations of open phase conditions on the high voltage side of YNd05-power plant transformers
Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Disclaimer: All information presented in the report, the results and the related computer program, data,
More informationTransmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection
Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed
More informationCOURSE PLANNER SUBJECT: ELECTRICAL POWER SYSTEM II
COURSE PLANNER SUBJECT: ELECTRICAL POWER SYSTEM II [260908] B.E. Third Year Class Electrical 204 Term: 6/2 (DEC-6 to APR-7) Faculty: PROF. J. I. JARIWALA PROF. A. S. SHAH PROF. T. M. PANCHAL PROF. N. B.
More informationThree-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method
Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method Calculation of Isc by the impedance method In a 3-phase installation Isc at any point is
More informationThree-Phase/Six-Phase Conversion Autotransformers
1554 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 4, OCTOBER 2003 Three-Phase/Six-Phase Conversion Autotransformers Xusheng Chen, Member, IEEE Abstract The first commercial demonstration of six-phase
More informationTRANSMISSION LINE 1. Instructed by: Miss. R T Gunasekara
TRANSMISSION LINE 1 Instructed by: Miss. R T Gunasekara Name :- D.K.Pathirana Index No :- 080332P Group :- EE9 Date of Per. :- 24/01/2011 Instructed by :- R.T.Gunasekara OBSEVATION SHEET Name :- D.K.Pathirana
More informationQUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits
QUESTION BANK ETE (17331) CM/IF Chapter1: DC Circuits Q1. State & explain Ohms law. Also explain concept of series & parallel circuit with the help of diagram. 3M Q2. Find the value of resistor in fig.
More informationPROBLEMS on Transformers
PROBLEMS on Transformers (A) Simple Problems 1. A single-phase, 250-kVA, 11-kV/415-V, 50-Hz transformer has 80 turns on the secondary. Calculate (a) the approximate values of the primary and secondary
More informationBeskrivelse av simuleringsmodell ==> Description of simulation model
Infrastruktur Elkraft / Energy Side / Page: 1 av / of 6 Beskrivelse av simuleringsmodell ==> Description of simulation model General The modelled system consists of one rotary converter (synchronous-synchronous
More informationConnection Impact Assessment Application
Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,
More informationGround Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations
Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations A.R. Sultan, M.W. Mustafa, M.Saini Faculty of Electrical Engineering Universiti Teknologi Malaysia (UTM)
More informationCHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS
40 CHAPTER 3 IMPROVEMENT OF LOAD POWER FACTOR USING FACTS CONTROLLERS 3.1 INTRODUCTION The low power factor effects on transmission line, switchgear, transformers etc. It is observed that if the power
More informationExtensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network
Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example
More informationImpacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering
Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Expo - Nov. 3, 2014 Index Normal Distribution System
More informationModeling and Performance Analysis of Mho-Relay in Matlab
Modeling and Performance Analysis of Mho-Relay in Matlab Purra Sai Kiran M.Tech Student, Padmasri Dr. B V Raju Institute of Technology, Narsapur, Medak, Telangana. ABSTRACT: This paper describes the opportunity
More informationMITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)
VOL. 4, NO. 4, JUNE 9 ISSN 89-668 6-9 Asian Research Publishing Network (ARPN). All rights reserved. MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) Rosli Omar and Nasrudin Abd Rahim
More informationHarmonic control devices
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 24 1 Today Harmonic control devices In-line reactors (chokes)
More informationExercises on overhead power lines (and underground cables)
Exercises on overhead power lines (and underground cables) 1 From the laws of Electromagnetism it can be shown that l c = 1 v 2 where v is the speed of propagation of electromagnetic waves in the environment
More informationImpedance protection on power transformer.
Impedance protection on power transformer www.siemens.com/siprotec5 SIPROTEC 5 Application Impedance Protection on Power Transformer APN-045, Edition 1 Content 1...3 1.1 Introduction...3 1.2 Application
More informationTransient Recovery Voltage at Transformer Limited Fault Clearing
Transient Recovery Voltage at Transformer Limited Fault Clearing H. Kagawa (Tokyo Electric power Company, Japan) A. Janssen (Liander N.V., the Netherlands) D. Dufounet (Consultant, France) H. Kajino, H.
More informationSeries and Parallel Resonant Circuits
Series and Parallel Resonant Circuits Aim: To obtain the characteristics of series and parallel resonant circuits. Apparatus required: Decade resistance box, Decade inductance box, Decade capacitance box
More informationSample Question Paper
Scheme G Sample Question Paper Course Name : Electrical Engineering Group Course Code : EE/EP Semester : Third Subject Title : Electrical Circuit and Network 17323 Marks : 100 Time: 3 hrs Instructions:
More informationAny wave shape can be reproduced by the sum of sine waves of the appropriate magnitude and frequency.
How do we use an oscilloscope? Measure signals with unknown wave shapes and frequency other than 60 Hz sine waves and dc. To get a picture of the waveform. Distortion? Phase duration? Magnitude Any wave
More informationClass XII Chapter 7 Alternating Current Physics
Question 7.1: A 100 Ω resistor is connected to a 220 V, 50 Hz ac supply. (a) What is the rms value of current in the circuit? (b) What is the net power consumed over a full cycle? Resistance of the resistor,
More informationOptimal neutral ground resistor rating of the medium voltage systems in power generating stations
Journal of International Council on Electrical Engineering ISSN: (Print) 2234-8972 (Online) Journal homepage: http://www.tandfonline.com/loi/tjee20 Optimal neutral ground resistor rating of the medium
More informationRAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements
RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying
More informationConnection Impact Assessment Application Form
Connection Impact Assessment Application Form This Application Form is for Generators applying for a Connection Impact Assessment (CIA). In certain circumstances, London Hydro may require additional information
More informationInitial Application Form for Connection of Distributed Generation (>10kW)
Please complete the following information and forward to Vector Contact Details Primary Contact (who we should contact for additional information) Contact person Company name Contact numbers Daytime: Cell
More informationLab 4. Transistor as an amplifier, part 2
Lab 4 Transistor as an amplifier, part 2 INTRODUCTION We continue the bi-polar transistor experiments begun in the preceding experiment. In the common emitter amplifier experiment, you will learn techniques
More informationSmart Ground Test Report. Springfield Energy - Springfield Power Station Grounding System Evaluation
Smart Ground Test Report Springfield Energy - Springfield Power Station Grounding System Evaluation Prepared for *C.M. Burns *Springfield Energy Springfield Power Station U.S.A. Prepared by A. P. Sakis
More informationThe development of the SA grid code on Power Quality emission. Dr. Gerhard Botha 2017/08/08
The development of the SA grid code on Power Quality emission Dr. Gerhard Botha 2017/08/08 Overview What is the Grid Code? What is Power Quality? Power Quality Management Principles Differences Challenges
More informationPOWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics
POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics EE589-Power System Quality & Harmonics Electrical Engineering Department School of Engineering University of Jordan 1 Control of Harmonics
More informationTeaching Distance Relay Using Matlab/Simulink Graphical User Interface
Available online at www.sciencedirect.com Procedia Engineering 53 ( 2013 ) 264 270 Malaysian Technical Universities Conference on Engineering & Technology 2012, MUCET 2012 Part 1 - Electronic and Electrical
More informationFAULT LOCATING USING VOLTAGE AND CURRENT MEASUREMENTS
The BEST Group THE BUFFALO ENERGY SCIENCE AND TECHNOLOGY GROUP -Winter Lecture Series FAULT LOCATING USING VOLTAGE AND CURRENT MEASUREMENTS Presented by: Syed Khundmir T Department of Electrical Engineering
More informationEE 340 Transmission Lines. Spring 2012
EE 340 Transmission Lines Spring 2012 Physical Characteristics Overhead lines An overhead transmission line usually consists of three conductors or bundles of conductors containing the three phases of
More information