Three-Phase/Six-Phase Conversion Autotransformers
|
|
- Gwendolyn Carpenter
- 6 years ago
- Views:
Transcription
1 1554 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 4, OCTOBER 2003 Three-Phase/Six-Phase Conversion Autotransformers Xusheng Chen, Member, IEEE Abstract The first commercial demonstration of six-phase transmission, the Goudey-Oakdale three-phase/six-phase project, used two delta wye-grounded three-phase transformers to realize the required phase/voltage conversion. This paper proposes the usage of autotransformers for phase/voltage conversion for the actual three-phase/six-phase systems to be built in the future. The design considerations of the three-phase/six-phase conversion autotransformers are described. Topology-based, nonlinear, core-type conversion autotransformer EMTP models are developed. The behavior of the conversion autotransformers in a practical three-phase/six-phase system is simulated. These include transformer energization, short circuits, voltage regulation, open conductor, and ferroresonance. The simulation results show that the autotransformer is a viable choice for the conversion transformer. Since the cost ratio of the proposed conversion autotransformers with respect to the three-winding conversion transformers is approximately 64%, the new design is superior economically to other transformer designs, and will help push the HPO technology. Index Terms Autotransformer, six-phase, transmission. I. INTRODUCTION CONSIDERATION of the fundamental limits on power transfer in a restricted right-of-way led to the concept of increasing the number of phases in a circuit from three to six or twelve. This is called high phase order power transmission (HPO). At first as an idea, it gained credibility with a feasibility analysis published in the late 1970s [1]. As a laboratory prototype demonstration, an 80-kV phase-to-ground six-phase line and a 138-kV phase-to-ground twelve-phase line were built at the Malta test facility of Power Technologies Inc., Schenectady, NY, with support from the Department of Energy [2]. As the initial application on an operating utility transmission system, the Goudey-Oakdale line near Binghamton, NY, operated as a six-phase, 93-kV phase-to-ground line for two years [3]. Two delta/wye-grounded three-phase transformers were used to realize the required phase/voltage conversion. Possible reuse of the existing three-phase transformers and the isolation of the zero-sequence networks of the three-phase/six-phase systems resulted in the above choice. However, in a panel discussion of the 1994 IEEE Transmission and Distribution Conference, Chicago, IL, Guyker from Allegheny Power Service Corporation pointed out that What is needed today to help push HPO technology is not a cobbling of wye and delta banks, but an autotransformer that provides a balanced set of voltages and currents at a cost comparable to the wye-delta combination currently used. This statement motivated the author to conduct the research reported in this paper. Step-up and step-down three-phase/six-phase conversion autotransformers were conceptually designed. It is well known that the weight and cost of transformers of similar voltage ratings are proportional to the total megavolt ampere (MVA) of parts. The cost ratios of the proposed step-up and step-down autotransformers with respect to three-winding conversion transformers are 64.3% and 64.1%, respectively. Clearly, the autotransformers are superior economically to other transformer designs. Considering that for the same line-to-neutral voltage the six-phase transmission line could double the power flow capability this is why the six-phase transmission system is being actively researched, and that the installation costs of the two delta-wye three-phase transformers used in the Goudey-Oakdale project account for 60% of the total terminal costs [4], the proposed autotransformers will definitely help push the HPO technology. II. CONCEPTUAL DESIGN OF THE STEP-UP CONVERSION AUTOTRANSFORMER AND DETERMINATION OF ITS EMTP MODEL PARAMETERS Fig. 1 shows the three-phase/six-phase transmission system similar to the Goudey-Oakdale system described in [3]. The line-to-neutral voltages for the three-phase and the six-phase lines are kv and 93 kv, respectively. This conversion autotransformer is termed as the step-up autotransformer (the six-phase side has a higher line-to-neutral voltage than that of the three-phase side). Note that the polarities of the dfb three-phase windings (called tertiary windings in this paper) are reversed. The neutrals of the transformer are grounded. The autotransformer is assumed to be 250/125/125-MVA, 66.4/93/93-kV line-to-neutral, 60 Hz, five-legged, and wyegrounded. Its characteristics are summarized in Table I, and its one-phase schematic diagram is shown in Fig. 2. The design of the conversion autotransformer and the preparation of ATP data file proceed as follows: To have the autotransformer provide a balanced set of voltages and currents, it is required that the short-circuit impedances from the three-phase side to the two sets (ace and dfb) of the six phase side be equal. Redefine the autotransformer as a three-winding transformer with series, common, and tertiary windings as I, II, and III windings, respectively (Fig. 2). Assume that cylindrical windings are used and that the layout of one phase of the windings and iron is as shown in Fig. 3. The short-circuit impedances between the three windings I, II, and III are calculated as follows [5]: Manuscript received March 24, The author is with Seattle University, Seattle, WA USA Digital Object Identifier /TPWRD (1) /03$ IEEE
2 CHEN: THREE-PHASE/SIX-PHASE CONVERSION AUTOTRANSFORMERS 1555 TABLE I CHARACTERISTICS OF THE 250-MVA AUTOTRANSFORMER (10) (11) (2) It should be noted that the base current for the six-phase side is twice that of its rated current. The leakage and zero-sequence inductances referred to winding III are calculated as (12) (13) (14) (15) where is the zero sequence leakage inductance through the air and the tank. Usually, transformer winding resistances are calculated from short-circuit test data. Since no conversion autotransformers have yet been built, their values are assumed to be kv kv kv The core loss resistances are connected to the six-phase side for the left side transformer and the three-phase side for the right side transformer (Fig. 1). Their values are k (16) The reason for can be found in [6]. Assuming that the short-circuit reactances are equal to the short-circuit impedances, and noting that inductance is equal to reactance in per unit, the values of the leakage inductances of the model can be determined [6] Choosing 250 MVA, kv and kv as the power and voltage bases, respectively, the base currents, impedances, and inductances for the transformer are calculated as (3) (4) (5) (6) A (7) A (8) (9) k (17) A transformer data file was prepared for ATP supporting routine SPR.FOR [6]. SPR.FOR scales the curve of the transformer to match the specified excitation current, and generates curves for each nonlinear segment of the core. Nine ideal transformers are used to connect the autotransformer model to the system. The turns ratios of the ideal transformers are 0.29:1, 0.71:1, and 1:1, for windings I, II, and III, respectively. ATP input data for the conversion autotransformer are summarized in Table II. The 1.51-mile six-phase transmission line is modeled by ATP branch cards for PI-Equivalents (coupled R-L-C circuits) with the following constants: F F for and The power system external to the three-phase/six-phase system is represented by two three-phase voltage sources,, and, and,, and. The rated voltage of the two sources is 66.4 kv line-to-neutral. III. SIMULATION RESULTS The system of Fig. 1 was simulated comprehensively using ATP. Rated source voltage was assumed for all of the simulation cases if not otherwise specified.
3 1556 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 4, OCTOBER 2003 Fig. 1. Three-phase/six-phase transmission system. TABLE II ATP INPUT DATA FOR THE 250-MVA AUTOTRANSFORMER Fig. 2. One phase of the step-up conversion autotransformer. Fig. 3. Layout of phase A windings and iron of the step-up conversion autotransformer. A. Energization From the Three-Phase Side (Breaker is Closed, and Breaker is Open) Fig. 4 shows the simulated three-phase side excitation current waveforms,, and, and the six-phase side line-to-neutral voltage waveforms,,,,, and. The rms current is A or p.u., and the core loss is 600 kw or p.u. These should be accurate, because the supporting routine SPR.FOR matches the excitation current and the core loss. The voltages on the six-phase side are balanced.
4 CHEN: THREE-PHASE/SIX-PHASE CONVERSION AUTOTRANSFORMERS 1557 (a) (a) (b) (b) Fig. 4. Simulated excitation current and voltage waveforms. (a) Three-phase side excitation currents. (b) Six-phase side line-to-neutral voltages. B. Short-Circuit Performance Breaker is closed, and the rest breakers are open for all the short-circuit simulations (see Fig. 1) 1) Six-phase short-circuit. Fig. 5(a) shows the six-phase side short-circuit current waveforms. The rms currents for phases,,,,, and are 11.84, 11.91, 11.87, 11.69, 11.74, and ka, respectively. The average short-circuit current for phases ace is ka or p.u., for phases dfb is ka or p.u., and for phases ABC (the three-phase side) is ka, or p.u. The transformer s short-circuit equivalent circuit is shown in Fig. 5(b). The rms short-circuit current can be calculated as p.u. which is seen to be almost the same as the computed value of p.u. The astute readers must have noticed that the conventional star-circuit of a three-winding transformer was used to calculate the six-phase short-circuit currents. A simple reasoning is offered here. If complete balance of the system can be assumed, then and, which suggest that a six-phase short-circuit can be treated as two simultaneous three-phase (ace and dfb) short-circuits. The currents on the three-phase side can be determined by the balance of the magnetomotive forces (mmfs) per phase. The inversion of polarity of one set of the voltages on the six-phase side will not change the short-circuit currents on the three-phase side. 2) Phases and short-circuit. Fig. 5. Six-phase short-circuit (a c e d f b) of the autotransformer. (a) Simulated six-phase side short-circuit current waveforms. (b) Short-circuit equivalent circuit. Fig. 6. Current waveforms for a d short-circuit. Fig. 6 shows the current waveforms for both sides of the transformer. The rms currents are ka or p.u., A, A, and ka or p.u. It is observed that the short-circuit currents of the -ground short-circuit are the same as that of the short-circuit. 3) Phases a and ground short-circuit. Fig. 7 shows the current waveforms for both sides of the transformer. The rms currents are ka or p.u., A, A, and ka or p.u. It is gratifying to note that the results of the short-circuit analysis of the transformer are in excellent agreement with that of the theoretical analysis presented in [7]. C. Voltage Regulation For convenience of simulation, the voltage regulation (VR) is defined as (18)
5 1558 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 4, OCTOBER 2003 Fig. 7. Current waveforms for a g short-circuit. (a) (b) Fig. 8. Left-side transformer six-phase side voltage waveforms when it carries a rated pure inductive load. where no load voltage rated voltage; full load voltage. Fig. 8 shows the six-phase side voltage waveforms when the left side transformer carries a rated six-phase pure inductive load. The six-phase side voltages are balanced. The voltage regulation is. Knowing p.u. and p.u., the voltage regulation can be easily calculated [see Fig. 5(b)] (c) Since resistances are small comparing to the reactances in the system of Fig. 1, 3.66% is approximately the maximum voltage regulation under rated conditions of the transformer. D. Energization of the Right-Side Transformer after the Left-Side Transformer Has Been Energized Fig. 9 shows the six-phase side inrush and excitation current waveforms. It is observed that the inrush and excitation current waveforms are quite different when the right-side transformer is energized from a six-phase infinite bus. E. Open Conductor Performance The voltage for the two sources is fixed at 106% of the rated voltage. The angles of the source voltages are then adjusted so that the current of the six-phase side of the right-side transformer is at its rated current of 1255 A. In this operating condition, the right side transformer receives 265 MW, with a power (d) Fig. 9. Energization of the right-side transformer after the left-side transformer has been energized. (a) Phases a, c, and e inrush current waveforms. (b) Phases d, f, and b inrush current waveforms. (c) Phases a, c, and e excitation current waveforms. (d) Phases d, f, and b excitation current waveforms. factor of unity. The three-phase/six-phase system is balanced before the line outage.
6 CHEN: THREE-PHASE/SIX-PHASE CONVERSION AUTOTRANSFORMERS 1559 Fig. 11. Three-phase side voltage waveforms. Fig. 10. Simulated voltage and current waveforms of the six-phase transmission line when phase a is disconnected. (a) Voltages on the six-phase transmission line. (b) Currents on the six-phase transmission line. TABLE III VOLTAGE,CURRENT AND POWER ON THE SIX-PHASE LINE (ALL PHASES CONNECTED AND PHASE A DISCONNECTED) Fig. 10 shows the voltage and current waveforms of the sixphase transmission line when phase a is disconnected (breakers and are open). Simulation results for the two operating conditions are summarized in Table III. As shown in Table III, disconnecting phase a drops the current on phase a to zero and voltage on phase a to kv which is a result of both capacitive and inductive coupling from the other phases. The power received by the right-side transformer is MW, a reduction of 18% (compare: ). It is encouraging to observe that the voltages and currents on the reremaining phases are only slightly changed. F. Ferroresonance Transformer ferroresonance is a complicated nonlinear phenomenon. For three-winding, multiphase, multilegged transformers to develop fetroresonance overvoltages, the following four conditions must be met: 1) there is no load on the transformer; 2) one or more phases are disconnected from the source; 3) adequate capacitance to ground is connected to open terminals; 4) no source is connected directly or through small or medium impedances to the other windings on the leg with open terminals. Conditions 1 to 3 are well known for two-winding transformers. Condition 4 is unique to three-winding transformers. The reason is that connection of the source to the windings reduces dramatically the input inductance looking into the open terminals. Since the position of the breakers on both sides of the transformer is under supervision, the chances for ferroresonance are extremely rare. One case study is reported here. Breakers and are switched on to energize the left-side transformer which carries the 1.51-mile six-phase transmission line (breaker is closed and breaker is open). The winding capacitances to the ground of the autotransformer are assumed to be F/phase and F/phase for the three-phase and six-phase sides, respectively. There are no ferroresonance overvoltages when breakers and are closed with rated source voltages of 66.4 kv rms. However, when the length of the transmission line is increased to 10 mi, ferroresonance overvoltages do occur. Fig. 11 shows the three-phase side voltage waveforms when the six-phase line is 15.1 mi long. The aperiodic phase A voltage waveform has a peak value of 146 kv, which is kv kv of the rated peak line-to-neutral voltage. Phase and phase voltages are proportional to phase A voltage. IV. STEP-DOWN CONVERSION AUTOTRANSFORMER Fig. 12 shows the schematic diagram of one phase of the step-down conversion autotransformer. It is found that the layout of the windings and iron of Fig. 3 is unable to make the step-down conversion autotransformer to supply a balanced six-phase voltage at load. Fortunately, a simple change of the layout of the windings and iron such as the one shown in Fig. 13 will solve the problem. The conversion autotransformer is assumed to be 400-MVA, kv line-to-neutral, 60-Hz, five-legged, and
7 1560 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 4, OCTOBER 2003 Fig. 12. One phase of the step-down conversion autotransformer. Fig. 14. Step-down conversion autotransformer six-phase side voltage waveforms when it carries a rated pure inductive load. of the apparent power ratings of the windings of a given transformer construction. The cost ratios for the conversion autotransformers with respect to the three-winding conversion transformers are determined as follows: 1) Cost ratio for the step-up autotransformer (Fig. 2). (19) Fig. 13. Layout of phase A windings and iron of the step-down conversion autotransformer. wye-grounded. The short circuit impedances are assumed as follows: and Following the same procedure as for the step-up autotransformer discussed in Section II, the following results are obtained: and Note that the constraint of for the layout of windings and iron of Fig. 3 is lifted for that of Fig. 13. The base inductance for winding III, and the leakage and zero-sequence inductances referred to it are The other ATP data are omitted for simplicity. Fig. 14 shows the six-phase side voltage waveforms when the transformer carries a rated pure inductive load. The voltages of the six phases are completely balanced with a voltage regulation of, which can be calculated as. V. ADVANTAGES OF AUTOTRANSFORMERS The weight and cost of transformers of similar voltage ratings are proportional to the total MVA of parts which is the sum full load condition (20) where is the voltage ratio of the primary and second sides;,, and, are rated currents of the common winding, series and tertiary windings, and the three-phase side, respectively. MVA of parts step-up autotransformer MVA of parts step-up three-winding transformer (21) (22) Cost ratio (23) 2) Cost ratio for the step-down autotransformer (Fig. 12). The current rating for the common winding is determined by lines ace open if, and lines dfb open if if if (24a) (24b) Cost ratio if (25a) if (25b) The cost ratios for the 250-MVA step-up and 400-MVA step-down conversion autotransformers with respect to the three-winding conversion transformers are 64.3% and 64.1%, respectively. The savings of cost in using conversion autotransformers are considerable. The autotransformers also have lower per unit losses (higher efficiency) and lower excitation current. The disadvantages include the loss of electrical isolation between the three-phase and the six-phase sides.
8 CHEN: THREE-PHASE/SIX-PHASE CONVERSION AUTOTRANSFORMERS 1561 VI. CONCLUSION Conceptual designs for step-up and step-down threephase/six-phase conversion autotransformers are presented. The proposed autotransformers are placed in a practical three-phase/six-phase system and simulated comprehensively. The conceptual design shows signs of desirable performace and is superior economically to other transformer designs for conversion purposes. Further work is definitely needed to verify other performance measures such as lightning and switching performance, corona behavior, and other important ones. It is suggested that conversion autotransformers be used in the commercial three-phase/six-phase transmission systems to be built in the future. ACKNOWLEDGMENT The author wishes to express his sincere appreciation to Dr. S. S. Venkata of Iowa State University, who initiated this research project and whose advice and experience on HPO technology have been invaluable. REFERENCES [1] S. S. Venkata, W. C. Guyker, and W. H. Booth, 138-kV, six-phase electrical power transmission system, in Proc. Amer. Power Conf., vol. 40, Chicago, IL, Apr. 1978, pp [2] J. R. Stewart and I. S. Grant, High phase order Ready for application, in Proc IEEE Power Eng. Soc. Transmission and Distribution Conf., Minneapolis, Minnesota, Sept , 1981, Paper 81 TD [3] J. R. Stewart et al., Transformer winding selection associated with re-configuration of existing double-circuit line to six-phase operation, IEEE Trans. Power Delivery, vol. 7, pp , Apr [4] T. L. Landis et al., High phase order economics: Constructing a new transmission line, IEEE Trans. Power Delivery, vol. 13, pp , Oct [5] H. W. Dommel, Electromagnetic Transients Programs Reference Manual. Porland, OR: BPA, [6] X. Chen and S. S. Venkata, A three-phase, three-winding core-type transformer model for low-frequency transient studies, IEEE Trans. Power Delivery, vol. 12, pp , Apr [7] S. S. Venkata et al., 138-kV, six-phase transmission system: Fault analysis, IEEE Trans. Power Apparat. Syst., vol. PAS-101, pp , May Xusheng Chen (M 88) was born in Shanghai, China. He received the M.S.E.E. degree in power systems from Jiao Tong University, Shanghai, China, in He received the Ph.D. degree in electrical and computer engineering from Washington State University, Pullman, in Currently, he is a Professor at Seattle University, WA. His areas of interest include power system transients and protection, electrical machine modeling, six-phase nonlinear circuit analysis, power transmission, and wind generation. Dr. Chen is a member of Tau Beta Pi.
Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices
Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices M. Sanaye-Pasand, R. Aghazadeh Applied Electromagnetics Research Excellence Center, Electrical & Computer Engineering
More informationANEW, simple and low cost scheme to reduce transformer
950 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005 A Sequential Phase Energization Technique for Transformer Inrush Current Reduction Part II: Theoretical Analysis and Design Guide Wilsun
More informationof the improved scheme is presented. Index Terms Inrush current, power quality, transformer.
208 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007 A Sequential Phase Energization Method for Transformer Inrush Current Reduction Transient Performance and Practical Considerations
More informationFERRORESONANCE SIMULATION STUDIES USING EMTP
FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in
More informationIEEE Power Engineering Society 2001 Winter Meeting Columbus, OH. Panel Session. Data for Modeling System Transients
IEEE Power Engineering Society 2001 Winter Meeting Columbus, OH Panel Session Data for Modeling System Transients Parameters for Modeling Transmission Lines and Transformers in Transient Studies Bruce
More informationAS the power distribution networks become more and more
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 21, NO. 1, FEBRUARY 2006 153 A Unified Three-Phase Transformer Model for Distribution Load Flow Calculations Peng Xiao, Student Member, IEEE, David C. Yu, Member,
More informationAccurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 4, OCTOBER 2002 969 Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies Taku Noda, Member, IEEE, Hiroshi Nakamoto,
More informationA Study on Ferroresonance Mitigation Techniques for Power Transformer
A Study on Ferroresonance Mitigation Techniques for Power Transformer S. I. Kim, B. C. Sung, S. N. Kim, Y. C. Choi, H. J. Kim Abstract--This paper presents a comprehensive study on the ferroresonance mitigation
More informationA Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage
A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of Hz zero sequence continuous voltage S. Nishiwaki, T. Nakamura, Y.Miyazaki Abstract When an one line grounding fault in a transmission
More informationFerroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions
Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit
More informationTECHNICAL BULLETIN 004a Ferroresonance
May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques
More informationEffects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages
Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Waruna Chandrasena, Bruno Bisewski, and Jeff Carrara Abstract-- This paper describes several system
More informationISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer
ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering
More informationImpact Assessment Generator Form
Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project
More informationBE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %
BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and
More informationFerroresonance Experience in UK: Simulations and Measurements
Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey
More informationValidation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit
Validation of a Power Transformer Model for Ferroresonance with System Tests on a 4 kv Circuit Charalambos Charalambous 1, Z.D. Wang 1, Jie Li 1, Mark Osborne 2 and Paul Jarman 2 Abstract-- National Grid
More information160 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 1, JANUARY /$ IEEE
160 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 1, JANUARY 2009 Dual Three-Winding Transformer Equivalent Circuit Matching Leakage Measurements Francisco de León, Senior Member, IEEE, and Juan A.
More informationSimulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models
International Journal of Electrical & Computer Sciences IJECS-IJENS Vol:15 No:03 39 Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models Shen-Wen Hsiao, Shen-Jen
More informationThe Effect of Various Types of DG Interconnection Transformer on Ferroresonance
The Effect of Various Types of DG Interconnection Transformer on Ferroresonance M. Esmaeili *, M. Rostami **, and G.B. Gharehpetian *** * MSc Student, Member, IEEE, Shahed University, Tehran, Iran, E mail:
More informationImproving Passive Filter Compensation Performance With Active Techniques
IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 50, NO. 1, FEBRUARY 2003 161 Improving Passive Filter Compensation Performance With Active Techniques Darwin Rivas, Luis Morán, Senior Member, IEEE, Juan
More informationCOMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)
7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series
More informationFerroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy
Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy W. Piasecki, M. Stosur, T. Kuczek, M. Kuniewski, R. Javora Abstract-- Evaluation
More informationA Novel Single-Stage Push Pull Electronic Ballast With High Input Power Factor
770 IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, VOL. 48, NO. 4, AUGUST 2001 A Novel Single-Stage Push Pull Electronic Ballast With High Input Power Factor Chang-Shiarn Lin, Member, IEEE, and Chern-Lin
More informationSECTION 4 TRANSFORMERS. Yilu (Ellen) Liu. Associate Professor Electrical Engineering Department Virginia Tech University
SECTION 4 TRANSFORMERS Yilu (Ellen) Liu Associate Professor Electrical Engineering Department Virginia Tech University Analysis of Transformer Turns Ratio......................... 4.2 Analysis of a Step-Up
More informationEffect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 2, APRIL 2002 569 Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System Li-Ming Zhou, Senior Member, IEEE,
More informationCork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)
Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:
More informationTO LIMIT degradation in power quality caused by nonlinear
1152 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 13, NO. 6, NOVEMBER 1998 Optimal Current Programming in Three-Phase High-Power-Factor Rectifier Based on Two Boost Converters Predrag Pejović, Member,
More informationA Comprehensive Approach for Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique
A Comprehensive Approach Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique Mahmoud Elfayoumy 1, Member, IEEE, and Carlos Grande Moran 2, Senior Member, IEEE Abstract: The
More informationCOMMON mode current due to modulation in power
982 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 14, NO. 5, SEPTEMBER 1999 Elimination of Common-Mode Voltage in Three-Phase Sinusoidal Power Converters Alexander L. Julian, Member, IEEE, Giovanna Oriti,
More informationA NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *
Iranian Journal of Science & Technology, Transaction B, Engineering, Vol. 30, No. B6, pp 643-654 Printed in The Islamic Republic of Iran, 2006 Shiraz University A NEW DIFFERENTIAL PROTECTION ALGORITHM
More informationLong lasting transients in power filter circuits
Computer Applications in Electrical Engineering Vol. 12 2014 Long lasting transients in power filter circuits Jurij Warecki, Michał Gajdzica AGH University of Science and Technology 30-059 Kraków, Al.
More informationSolving Customer Power Quality Problems Due to Voltage Magnification
PE-384-PWRD-0-11-1997 Solving Customer Power Quality Problems Due to Voltage Magnification R. A. Adams, Senior Member S. W. Middlekauff, Member Duke Power Company Charlotte, NC 28201 USA E. H. Camm, Member
More informationIn Class Examples (ICE)
In Class Examples (ICE) 1 1. A 3φ 765kV, 60Hz, 300km, completely transposed line has the following positive-sequence impedance and admittance: z = 0.0165 + j0.3306 = 0.3310 87.14 o Ω/km y = j4.67 410-6
More informationA Resonant Tertiary Winding-Based Novel Air-Core Transformer Concept Pooya Bagheri, Wilsun Xu, Fellow, IEEE, and Walmir Freitas, Member, IEEE
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 3, JULY 2012 1519 A Resonant Tertiary Winding-Based Novel Air-Core Transformer Concept Pooya Bagheri, Wilsun Xu, Fellow, IEEE, and Walmir Freitas, Member,
More informationNew Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 38, NO. 1, JANUARY/FEBRUARY 2002 131 New Pulse Multiplication Technique Based on Six-Pulse Thyristor Converters for High-Power Applications Sewan Choi,
More informationCHAPTER 4. Distribution Transformers
CHAPTER 4 Distribution Transformers Introduction A transformer is an electrical device that transfers energy from one circuit to another purely by magnetic coupling. Relative motion of the parts of the
More information86 chapter 2 Transformers
86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.
More informationSIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS
SIMUATION OF D-STATCOM AND DVR IN POWER SYSTEMS S.V Ravi Kumar 1 and S. Siva Nagaraju 1 1 J.N.T.U. College of Engineering, KAKINADA, A.P, India E-mail: ravijntu@gmail.com ABSTRACT A Power quality problem
More informationLightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise
Lightning Overvoltages on Low Voltage Circuit Caused by Ground Potential Rise S. Sekioka, K. Aiba, S. Okabe Abstract-- The lightning overvoltages incoming from an overhead line such as a power distribution
More informationEMERGING distributed generation technologies make it
IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 20, NO. 4, NOVEMBER 2005 1757 Fault Analysis on Distribution Feeders With Distributed Generators Mesut E. Baran, Member, IEEE, and Ismail El-Markaby, Student Member,
More informationDownloaded from / 1
PURWANCHAL UNIVERSITY II SEMESTER FINAL EXAMINATION-2008 LEVEL : B. E. (Computer/Electronics & Comm.) SUBJECT: BEG123EL, Electrical Engineering-I Full Marks: 80 TIME: 03:00 hrs Pass marks: 32 Candidates
More informationGENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW
GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW ELECTRIC UTILITY CONTACT INFORMATION Consumers Energy Interconnection Coordinator 1945
More informationImprovement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller
Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Phanikumar.Ch, M.Tech Dept of Electrical and Electronics Engineering Bapatla Engineering College, Bapatla,
More informationEVALUATION OF REACTANCES AND TIME CONSTANTS OF SYNCHRONOUS GENERATOR
EVALUATION OF REACTANCES AND TIME CONSTANTS OF SYNCHRONOUS GENERATOR Shaheena Khanum 1, K.L Ratnakar 2, Ramesh K.N 3, Ravi.R 4 1 PG Student, Department of Electrical and Electronics Engineering, Sri Siddhartha
More informationA REVIEW ON THREE-PHASE TO SEVEN-PHASE POWER CONVERTER USING TRANSFORMER
A REVIEW ON THREE-PHASE TO SEVEN-PHASE POWER CONVERTER USING TRANSFORMER Seema Dhill 1, Rahul Baghel 2 1,2Dept. of Electrical Engineering, Shri Shankaracharya Engineering College, Durg, C.G., India -------------------------------------------------------------------------***------------------------------------------------------------------------
More informationModeling and electromagnetic transients study of two 1800MVA phase shifting transformers in the Italian transmission network
Modeling and electromagnetic transients study of two 18MVA phase shifting transformers in the Italian transmission network Luigi Colla, Vincenzo Iuliani, Francesco Palone, Massimo Rebolini, Stefano Zunino
More informationCourse ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation
Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission
More informationSERIES ACTIVE power filters have proved to be an interesting
928 IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 14, NO. 5, SEPTEMBER 1999 A Fault Protection Scheme for Series Active Power Filters Luis A. Morán, Senior Member, IEEE, Ivar Pastorini, Juan Dixon, Senior
More informationELECTRICAL POWER ENGINEERING
Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation
More informationVisualization and Animation of Protective Relay Operation
Visualization and Animation of Protective Relay Operation A. P. Sakis Meliopoulos School of Electrical and Computer Engineering Georgia Institute of Technology Atlanta, Georgia 30332 George J. Cokkinides
More informationIDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)
IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone
More information148 Electric Machines
148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional
More informationAdi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN
Effectiveness of Surge Capacitors on Transformer Tertiary connected shunt reactors in preventing failures- Field measurements and comparison with Transient study results Pratap G. Mysore, P.E Pratap Consulting
More informationReducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers
International Conference on Power System Transients IPST 23 in New Orleans, USA Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers
More informationAFTER an overhead distribution feeder is de-energized for
1902 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011 A New Technique to Detect Faults in De-Energized Distribution Feeders Part II: Symmetrical Fault Detection Xun Long, Student Member,
More informationHARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus
1592 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005 The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus Ahmed Faheem Zobaa, Senior Member, IEEE Abstract A
More information2. Current interruption transients
1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,
More informationR10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)
R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between
More informationDISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS
DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS Le Tang, Jeff Lamoree, Mark McGranaghan Members, IEEE Electrotek Concepts, Inc. Knoxville, Tennessee Abstract - Several papers have
More informationTab 2 Voltage Stresses Switching Transients
Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles
More informationUnit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21
Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive
More informationSimulation of HTS saturable core-type FCLs for MV distribution systems
University of Wollongong Research Online Faculty of Informatics - Papers (Archive) Faculty of Engineering and Information Sciences 2006 Simulation of HTS saturable core-type FCLs for MV distribution systems
More informationGround Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations
Ground Fault Currents in Unit Generator-Transformer at Various NGR and Transformer Configurations A.R. Sultan, M.W. Mustafa, M.Saini Faculty of Electrical Engineering Universiti Teknologi Malaysia (UTM)
More informationPreface...x Chapter 1 Electrical Fundamentals
Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5
More informationA Guide to the DC Decay of Fault Current and X/R Ratios
A Guide to the DC Decay of Fault Current and X/R Ratios Introduction This guide presents a guide to the theory of DC decay of fault currents and X/R ratios and the calculation of these values in Ipsa.
More informationCHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit
CHAPTER 2 Basic Concepts, Three-Phase Review, and Per Unit 1 AC power versus DC power DC system: - Power delivered to the load does not fluctuate. - If the transmission line is long power is lost in the
More informationInnovative Science and Technology Publications
Innovative Science and Technology Publications Manuscript Title SATURATION ANALYSIS ON CURRENT TRANSFORMER Thilepa R 1, Yogaraj J 2, Vinoth kumar C S 3, Santhosh P K 4, 1 Department of Electrical and Electronics
More informationGIS Disconnector Switching Operation VFTO Study
GIS Disconnector Switching Operation VFTO Study Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki, Marek Florkowski, Marek Fulczyk ABB Corporate Research Center in Krakow Starowislna 13A, 31-038 Krakow,
More informationELECTRICAL POWER TRANSMISSION TRAINER
ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering
More informationOnline Optimal Transmission Line Parameter Estimation for Relaying Applications Yuan Liao, Senior Member, IEEE, and Mladen Kezunovic, Fellow, IEEE
96 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 1, JANUARY 2009 Online Optimal Transmission Line Parameter Estimation for Relaying Applications Yuan Liao, Senior Member, IEEE, and Mladen Kezunovic,
More informationHybrid Transformer Model for Transient Simulation: Part II Laboratory Measurements and Benchmarking
1 Hybrid Transformer Model for Transient Simulation: Part II Laboratory Measurements and Benchmarking B. A. Mork, Member, IEEE, F. Gonzalez, Member, IEEE, D. Ishchenko, Member, IEEE, D. L. Stuehm, Member,
More informationTABLE OF CONTENT
Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES
More informationPower Quality Improvement in Distribution System Using D-STATCOM
Power Quality Improvement in Distribution System Using D-STATCOM 1 K.L.Sireesha, 2 K.Bhushana Kumar 1 K L University, AP, India 2 Sasi Institute of Technology, Tadepalligudem, AP, India Abstract This paper
More informationCHAPTER 2. Transformers. Dr Gamal Sowilam
CHAPTER Transformers Dr Gamal Sowilam Introduction A transformer is a static machine. It is not an energy conversion device, it is indispensable in many energy conversion systems. A transformer essentially
More informationA1-101 INFLUENCE OF SPECIAL SHORT CIRCUIT ON ELECTRICAL GENERATOR DESIGN. Ding Zhong MENG (HONG KONG, CHINA)
1, rue d'artois, F-758 Paris http://www.cigre.org A1-11 Session 4 CIGRÉ INFLUENCE OF SPECIAL SHORT CIRCUIT ON ELECTRICAL GENERATOR DESIGN Ding Zhong MENG (HONG KONG, CHINA) SUMMARY Refer to the IEC Standard
More informationOperation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software
Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software Govind Pandya 1, Rahul Umre 2, Aditya Pandey 3 Assistant professor, Dept. of Electrical & Electronics,
More informationIn power system, transients have bad impact on its
Analysis and Mitigation of Shunt Capacitor Bank Switching Transients on 132 kv Grid Station, Qasimabad Hyderabad SUNNY KATYARA*, ASHFAQUE AHMED HASHMANI**, AND BHAWANI SHANKAR CHOWDHRY*** RECEIVED ON 1811.2014
More informationTHREE-PHASE TO SEVEN-PHASE POWER CONVERTER USING PI CONTROLLER AND TRANSFORMER
THREE-PHASE TO SEVEN-PHASE POWER CONVERTER USING PI CONTROLLER AND TRANSFORMER Seema Dhill 1, Rahul Baghel 2 1,2Dept. of Electrical Engineering, Shri Shankaracharya Engineering College, Durg, C.G., India
More informationSimulation and Analysis of Power System Transients using EMTP-RV
5-Day course Montréal - CANADA October 1-5, 2012 Simulation and Analysis of Power System Transients using EMTP-RV This course is organized by POWERSYS. Place: DELTA MONTREAL http://www.deltahotels.com/en/hotels/quebec/delta-montreal/
More informationResonances in Collection Grids of Offshore Wind Farms
Downloaded from orbit.dtu.dk on: Dec 20, 2017 Resonances in Collection Grids of Offshore Wind Farms Holdyk, Andrzej Publication date: 2013 Link back to DTU Orbit Citation (APA): Holdyk, A. (2013). Resonances
More informationEnhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)
Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) PATTI.RANADHEER Assistant Professor, E.E.E., PACE Institute
More informationMATHEMATICAL MODELING OF POWER TRANSFORMERS
MATHEMATICAL MODELING OF POWER TRANSFORMERS Mostafa S. NOAH Adel A. SHALTOUT Shaker Consultancy Group, Cairo University, Egypt Cairo, +545, mostafanoah88@gmail.com Abstract Single-phase and three-phase
More informationElectrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018
Electrical Theory Power Principles and Phase Angle PJM State & Member Training Dept. PJM 2018 Objectives At the end of this presentation the learner will be able to: Identify the characteristics of Sine
More informationA Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions
IEEE TRANSACTIONS ON POWER ELECTRONICS, VOL. 16, NO. 5, SEPTEMBER 2001 603 A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions
More informationSTRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS
1 STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS Z. GAJIĆ S. HOLST D. BONMANN D. BAARS ABB AB, SA Products ABB AB, SA Products ABB AG, Transformers ELEQ bv Sweden Sweden Germany Netherlands zoran.gajic@se.abb.com
More informationEnhancement of Power Quality in Distribution System Using D-Statcom for Different Faults
Enhancement of Power Quality in Distribution System Using D-Statcom for Different s Dr. B. Sure Kumar 1, B. Shravanya 2 1 Assistant Professor, CBIT, HYD 2 M.E (P.S & P.E), CBIT, HYD Abstract: The main
More informationIssued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY
WN U-60 Attachment C to Schedule 152, Page 1 SCHEDULE 152 APPLICATION FOR INTERCONNECTING A GENERATING FACILITY TIER 2 OR TIER 3 This Application is considered complete when it provides all applicable
More informationCurrent Transformer Performance study Using Software Tools.
Current Transformer Performance study Using Software Tools. A. Mechraoui, A. Draou, A. Akkouche, and S. AL Ahmadi Department of Electronics Technology Madinah College of Technology, Madinah Council of
More informationAORC Technical meeting 2014
http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationDemagnetization of Power Transformers Following a DC Resistance Testing
Demagnetization of Power Transformers Following a DC Resistance Testing Dr.ing. Raka Levi DV Power, Sweden Abstract This paper discusses several methods for removal of remanent magnetism from power transformers.
More information(2) New Standard IEEE P (3) Core : (4) Windings :
(d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.
More informationR Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data
Distribution Transformers Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections R201-90-2 Reference Data CONTENTS POPULAR DlSTRIBUTlON TRANSFORMER AND CIRCUIT VOLTAGES... 1 2400-Volt Systems
More informationIT HAS LONG been recognized that bearing damage can be
1042 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 34, NO. 5, SEPTEMBER/OCTOBER 1998 Bearing Currents and Shaft Voltages of an Induction Motor Under Hard- and Soft-Switching Inverter Excitation Shaotang
More informationNew 24-Pulse Diode Rectifier Systems for Utility Interface of High-Power AC Motor Drives
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 33, NO. 2, MARCH/APRIL 1997 531 New 24-Pulse Diode Rectifier Systems for Utility Interface of High-Power AC Motor Drives Sewan Choi, Member, IEEE, Bang
More informationModule 1. Introduction. Version 2 EE IIT, Kharagpur
Module 1 Introduction Lesson 1 Introducing the Course on Basic Electrical Contents 1 Introducing the course (Lesson-1) 4 Introduction... 4 Module-1 Introduction... 4 Module-2 D.C. circuits.. 4 Module-3
More informationChapter 2: Transformers
Chapter 2: Transformers 2-1. The secondary winding of a transformer has a terminal voltage of v s (t) = 282.8 sin 377t V. The turns ratio of the transformer is 100:200 (a = 0.50). If the secondary current
More informationModule 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor
Module 2 : Current and Voltage Transformers Lecture 8 : Introduction to VT Objectives In this lecture we will learn the following: Derive the equivalent circuit of a CCVT. Application of CCVT in power
More informationSimulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid
5th International Conference on Computer Sciences and Automation Engineering (ICCSAE 2015) Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault
More information