Grid Impact of Neutral Blocking for GIC Protection:

Size: px
Start display at page:

Download "Grid Impact of Neutral Blocking for GIC Protection:"

Transcription

1 Report submitted to EMPRIMUS - Critical Infrastructure Protection Grid Impact of Neutral Blocking for GIC Protection: Impact of neutral grounding capacitors on network resonance Prepared By: Athula Rajapakse Date: 29 June, 2013 Electresearch

2 Third Party Disclaimer: The content of this document is not intended for the use of, nor is it intended to be relied upon by any person, firm or corporation, other than the authors of the report and EMPRIMUS LLC. Authors of this report deny any liability whatsoever to any parties for damages or injury suffered by such third party arising from the use of this document by the third party. Confidentiality: This document is restricted to the confidential use of the authors and EMPRIMUS LLC. Any retention, reproduction, distribution or disclosure to third parties is prohibited without written authorization of EMPRIMUS LLC. Electresearch Page i

3 Table of Contents 1.0 Introduction Study Methodology Results Scenario-1: System intact conditions Scenario-2: One of the 660 MVA, 22/500 kv transformers out of service Scenario-3: One of the 500 kv circuits between bus-1 and bus-2 out of service Scenario-4: 750 MVA, 500/345 kv autotransformer between bus-1 and bus-4 out of service Scenario-5: One of the 500 kv circuits between bus-1 and bus-3 out of service Scenario-6: System intact, with autotransformer neutral grounding capacitors bypassed Scenario-7: System intact, with 2 winding transformer neutral grounding capacitors bypassed Concluding Remarks References Electresearch Page ii

4 1.0 Introduction A commonly proposed solution to block the flowing of geomagnetically induced currents (GIC) in power transmission lines during solar storms is to ground the transformer neutrals through capacitors. This report details the impact of neutral blocking capacitors used for GIC blocking on network resonance at both (ii) harmonic and (ii) subsynchronous frequencies. Harmonic resonance in a power transmission network is caused by the energy exchange between capacitive elements and inductive elements in the system at one or more of the natural frequencies. Thus the harmonic resonance characteristics are mainly determined by the shunt capacitances of transmission lines, cables, and shunt capacitor banks, and the inductances of the network elements such as transmission lines, cables, transformers, generators, and reactors. Problems due to harmonic resonance are commonly manifested as significant distortion of supply voltage waveforms due to high harmonic impedance (parallel resonance) at harmonic source locations. However, series resonance conditions can also exist and lead to problems. Subsynchronous resonance is an electric power system condition where the electric network exchange energy with a turbine generator at one or more of the natural frequencies of the combined system below the nominal frequency of the system. This definition include what might be considered natural modes of oscillation that are due to inherent system characteristics as well as forced modes of oscillations driven by a particular device or control system [1]. Relevant to this study are the natural modes of oscillation, and we focus on examining the existence of natural modes of oscillation in the network that could interact with the natural torsional modes of a turbine generator shaft, setting up conditions for energy exchange at a subsynchronous frequency. The neutral blocking capacitor can introduce changes to the resonance characteristics of a transmission network, especially of the zero sequence impedances. This is because the capacitive reactance that is in series with the inductive zero sequence impedance of the transformer and other network devices can form a series or parallel resonance circuit depending on the network topology. Frequency scan analysis is the most widely used technique at present to identify the potential harmonic problems in power networks. This method is adopted in this study to identify the resonance conditions that exist in a 500/345 kv test network. All studies and analyses are conducted with the objective of understanding the impact of the neutral blocking capacitor, and thus involve comparison of frequency scans with and without the neutral grounding capacitors. In the following sections methodologies used and the results are presented. 2.0 Study Methodology The influence of the neutral grounding capacitors on the resonance characteristics of an interconnected network was investigated using frequency scan studies. Frequency scans gives the impedance seen from a specific point in the network at different frequencies. Frequency scan results can be used as screening level information to identify potential network resonance problems. In order to identify potential subsynchronous resonance issues, the calculated frequency scans should cover the frequencies below the power frequency. Harmonic resonance issues are typically due to lower order harmonics of power frequency. Thus, frequency scans presented in this report considered the frequency range from Hz (up to the 12 th harmonic of a 60 Hz system). The network used for studies is shown in Figure 1. The simulations presented in this report consider neutral grounding circuits of the two 22/500 kv two winding transformers connected between bus-7 and bus-2 (T 1, T 2 ), and the two 500/345 kv autotransformers connected between bus-1 and bus-4 (T 3 ), and bus-3 and bus-5 (T 4 ). Electresearch Page 1

5 Figure 1: Test network The main purpose of this study is to identify the influence of the neutral grounding capacitor on the overall network characteristics. Thus the frequency scan studies considered simulations with solidly grounded transformer neutrals and capacitor grounded transformer neutrals. In order to examine the effects of the value of the grounding capacitance, three different capacitor values (265 μf, 1000 μf, and 2650 μf) were considered. Moreover, different system conditions resulting from prior outages of various elements in the test circuit are also considered. Frequency scans were repeated at two locations, at bus-1 and at bus-2. In order to study the influence of the location of neutral grounding capacitors, selected cases were repeated with some of the neutral grounding capacitors bypassed. A list of simulation cases and the corresponding system conditions are given in Table 1. Simulations were carried out in PSCAD/EMTDC. The Harmonic Impedance Solution module available in PSCAD/EMTDC software, shown in Figure 2, was used to obtain the frequency scan results. This module can be used to directly obtain the frequency characteristics of the sequence impedances at the test location by selecting the proper option as shown in Figure 3. The following characteristics are presented under each of the conditions listed above. 1. Positive sequence impedance characteristics The neutral grounding capacitor is not expected to influence the positive sequence characteristics 2. Zero sequence impedance characteristics The influence of the neutral grounding capacitor is expected to appear in zero sequence impedance characteristics. Electresearch Page 2

6 Table 1 Scenarios, test locations, and test conditions Scenario Condition Location Neutral grounding Case No. Scenario-1 System intact bus-1 Solidly grounded Capacitor grounded, C = 265 μf Capacitor grounded, C = 1000 μf Capacitor grounded, C = 2650 μf Case (1) Case (2) Case (3) Case (4) Scenario-2 One of the 660 MVA, 22/500 kv transformers out of service Scenario-3 Scenario-4 Scenario-5 One of the 500 kv circuits between bus-1 and bus-2 out of service 750 MVA, 500/345 kv autotransformer between bus-1 and bus-4 out of service One of 500 kv circuits between bus-1 and bus-3 out of service bus-2 bus-1 bus-2 bus-1 bus-2 bus-1 bus-2 bus-1 bus-2 Solidly grounded Capacitor grounded, C = 265 μf Capacitor grounded, C = 1000 μf Capacitor grounded, C = 2650 μf Solidly grounded Capacitor grounded, C = 265 μf Capacitor grounded, C = 1000 μf Capacitor grounded, C = 2650 μf Solidly grounded Capacitor grounded, C = 265 μf Capacitor grounded, C = 1000 μf Capacitor grounded, C = 2650 μf Solidly grounded Capacitor grounded, C = 265 μf Capacitor grounded, C = 1000 μf Capacitor grounded, C = 2650 μf Solidly grounded Capacitor grounded, C = 265 μf Capacitor grounded, C = 1000 μf Capacitor grounded, C = 2650 μf Solidly grounded Capacitor grounded, C = 265 μf Capacitor grounded, C = 1000 μf Capacitor grounded, C = 2650 μf Solidly grounded Capacitor grounded, C = 265 μf Capacitor grounded, C = 1000 μf Capacitor grounded, C = 2650 μf Solidly grounded Capacitor grounded, C = 265 μf Capacitor grounded, C = 1000 μf Capacitor grounded, C = 2650 μf Solidly grounded Capacitor grounded, C = 265 μf Capacitor grounded, C = 1000 μf Capacitor grounded, C = 2650 μf Case (5) Case (6) Case (7) Case (8) Case (9) Case (10) Case (11) Case (12) Case (13) Case (14) Case (15) Case (16) Case (17) Case (18) Case (19) Case (20) Case (21) Case (22) Case (23) Case (24) Case (25) Case (26) Case (27) Case (28) Case (29) Case (30) Case (31) Case (32) Case (33) Case (34) Case (35) Case (36) Case (37) Case (38) Case (39) Case (40) Electresearch Page 3

7 Table 1 continued Scenario Condition Location Neutral grounding Case No. Scenario-6 System intact, autotransformer bus-1 T 3, T 4 solidly grounded, T 1,T 2 capacitor grounded, C=265 μf T 3, T 4 solidly grounded, T 1,T 2 Capacitor Case (41) Case (42) neutral grounding capacitors bypassed bus-2 grounded, C=2650 μf T 3, T 4 solidly grounded, T 1,T 2 capacitor grounded, C=265 μf T 3, T 4 solidly grounded, T 1,T 2 Capacitor grounded, C=2650 μf Case (43) Case (44) Scenario-7 System intact, two winding transformer neutral grounding capacitors bypassed bus-1 bus-2 T 1,T 2 solidly grounded, T 3, T 4 capacitor grounded, C=265 μf T 1,T 2 solidly grounded, T 3, T 4 capacitor grounded, C=2650 μf T 1,T 2 solidly grounded, T 3, T 4 capacitor grounded, C=265 μf T 1,T 2 solidly grounded, T 3, T 4 capacitor grounded, C=2650 μf Case (45) Case (46) Case (47) Case (48) Electresearch Page 4

8 150 A V TL500D1 500 kv, 2 cct, 250 km A V [MVAR] [MVAR] 1.0 [ohm] 265 [uf] 'Harmonic Impedance Solution' module Z(f) A V A V BUS 1 Figure 2 Harmonic Impedance Solution module connected to calculate the frequency characteristics at BUS 1. Figure 3 Harmonic Impedance Solution module parameter options Electresearch Page 5

9 3.0 Results 3.1 Scenario-1: System intact conditions Figure 4: Frequency characteristics of the zero sequence impedance at bus-1 Figure 5: Frequency characteristics of the positive sequence impedance at bus-1 Electresearch Page 6

10 Figure 6: Frequency characteristics of the zero sequence impedance at bus-2 Figure 7: Frequency characteristics of the positive sequence impedance at bus-2 Electresearch Page 7

11 3.2 Scenario-2: One of the 660 MVA, 22/500 kv transformers out of service Figure 8: Frequency characteristics of the zero sequence impedance at bus-1 Figure 9: Frequency characteristics of the positive sequence impedance at bus-1 Electresearch Page 8

12 Figure 10: Frequency characteristics of the zero sequence impedance at bus-2 Figure 11: Frequency characteristics of the positive sequence impedance at bus-2 Electresearch Page 9

13 3.3 Scenario-3: One of the 500 kv circuits between bus-1 and bus-2 out of service Figure 12: Frequency characteristics of the zero sequence impedance at bus-1 Figure 13: Frequency characteristics of the positive sequence impedance at bus-1 Electresearch Page 10

14 Figure 14: Frequency characteristics of the zero sequence impedance at bus-2 Figure 15: Frequency characteristics of the positive sequence impedance at bus-2 Electresearch Page 11

15 3.4 Scenario-4: 750 MVA, 500/345 kv autotransformer between bus-1 and bus-4 out of service Figure 16: Frequency characteristics of the zero sequence impedance at bus-1 Figure 17: Frequency characteristics of the positive sequence impedance at bus-1 Electresearch Page 12

16 Figure 18: Frequency characteristics of the zero sequence impedance at bus-2 Figure 19: Frequency characteristics of the positive sequence impedance at bus-2 Electresearch Page 13

17 3.5 Scenario-5: One of the 500 kv circuits between bus-1 and bus-3 out of service Figure 20: Frequency characteristics of the zero sequence impedance at bus-1 Figure 21: Frequency characteristics of the positive sequence impedance at bus-1 Electresearch Page 14

18 Figure 22: Frequency characteristics of the zero sequence impedance at bus-2 Figure 23: Frequency characteristics of the positive sequence impedance at bus-2 Electresearch Page 15

19 3.6 Scenario-6: System intact, with autotransformer neutral grounding capacitors bypassed Figure 24: Frequency characteristics of the zero sequence impedance at bus-1 Figure 25: Frequency characteristics of the positive sequence impedance at bus-1 Electresearch Page 16

20 Figure 26: Frequency characteristics of the zero sequence impedance at bus-2 Figure 27: Frequency characteristics of the positive sequence impedance at bus-2 Electresearch Page 17

21 3.7 Scenario-7: System intact, with 2 winding transformer neutral grounding capacitors bypassed Figure 28: Frequency characteristics of the zero sequence impedance at bus-1 Figure 29: Frequency characteristics of the positive sequence impedance at bus-1 Electresearch Page 18

22 Figure 30: Frequency characteristics of the zero sequence impedance at bus-2 Figure 31: Frequency characteristics of the positive sequence impedance at bus-2 Electresearch Page 19

23 4.0 Concluding Remarks As expected, frequency scans show that neutral grounding capacitors has no impact on the positive sequence impedance frequency characteristics (see Figures 5, 7, 9, 11, 23). However, the impact of neutral grounding capacitors is visible on some frequency scans of zero sequence impedance, as described below. Frequency scans show that at harmonic frequencies (f > 60 Hz), the impact of neutral grounding capacitors on the zero sequence impedance is negligible when the grounding capacitance is larger than 1000 μf (see Figures 4, 6, 8, 10, 12, 22). However, at subsynchronous frequencies (f < 60 Hz), zero sequence impedance characteristics are affected by the neutral grounding capacitors. Parallel resonance conditions exist even when the capacitance is 2650 μf (see Figures 4, 8, and 12), depending on the system conditions and the location of frequency scan. However, when the value of grounding capacitance is large (i.e. in the order of 2,650 μf), peaks of the impedance plots at the resonance frequency are small and therefore, less likely to have significant impact on the system operation. Since subsynchronous resonance issues are dependent on the specific network being considered, this potential resonance issue will need to be analyzed on a case by case basis. Frequency scan results of scenarios-6 and -7 show that the effect of capacitance is local, even when the capacitance is as low as 265 μf, as described below. In scenario-6, the neutrals of the transformers T 1 and T 2 (connected at bus-2) are grounded through capacitors while the neutrals of the transformers T 3 and T 4 are solidly grounded. Frequency scans of the zero sequence impedance at bus-2 show parallel resonance conditions at subsynchronous frequencies (Figure 26). However, the zero sequence impedance measured at the remotely located bus-1 (Figure 24) is not affected at all by the neutral grounding capacitors of the transformers T 1 and T 2, for capacitances of 265 μf and larger. Similarly, in scenario-7, the neutrals of the transformers T 3 and T 4 (connected at bus-1 and bus-3 respectively) are grounded through capacitors while the neutrals of the transformers T 1 and T 2 are solidly grounded. Although the frequency scans of the zero sequence impedance at bus-1 (Figure 28) show parallel resonance conditions at subsynchronous frequencies, the zero sequence impedance measured at the remotely located bus-2 (Figure 30) is not affected by the neutral grounding capacitors of the autotransformers T 3 and T 4. The study shows that conditions for parallel resonance in the zero sequence impedance can be created at subsynchronous frequencies, when the neutrals are grounded through capacitors. Although it is less likely to have a significant impact at higher capacitor values (~2650 μf), it is recommended to conduct a through analysis to determine whether there are undue electromechanical interactions between the network and turbine generators when applying neutral grounding capacitors to a particular system. 5.0 References [1] Paul M. Anderson, B. L. Agrawal, J. E. Van Ness, Subsynchronous Resonance in Power Systems, IEEE Press, New York, NY, USA, Electresearch Page 20

A Comprehensive Approach for Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique

A Comprehensive Approach for Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique A Comprehensive Approach Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique Mahmoud Elfayoumy 1, Member, IEEE, and Carlos Grande Moran 2, Senior Member, IEEE Abstract: The

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Disclaimer: All information presented in the report, the results and the related computer program, data,

More information

Grounding Resistance

Grounding Resistance Grounding Resistance Substation grounding resistance is the resistance in ohms between the substation neutral and earth ground (zeropotential reference) An actual fall of potential test is the best way

More information

UNDERSTANDING SUB-HARMONICS

UNDERSTANDING SUB-HARMONICS UNDERSTANDING SUB-HARMONICS Joe Perez, P.E., SynchroGrid, College Station, TX 77845, jperez@synchrogrid.com Introduction: Over the years, engineers have employed fundamental principles of electrical engineering

More information

Harmonic control devices

Harmonic control devices ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 24 1 Today Harmonic control devices In-line reactors (chokes)

More information

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) 7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series

More information

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation R. S. Al Abri, M. H. Albadi, M. H. Al Abri, U. K. Al Rasbi, M. H. Al Hasni, S. M. Al Shidi Abstract This paper presents an analysis

More information

Harmonic resonances due to transmission-system cables

Harmonic resonances due to transmission-system cables International Conference on Renewable Energies and Power Quality (ICREPQ 14) Cordoba (Spain), 8 th to 1 th April, 214 Renewable Energy and Power Quality Journal (RE&PQJ) ISSN 2172-38 X, No.12, April 214

More information

ELEMENTS OF FACTS CONTROLLERS

ELEMENTS OF FACTS CONTROLLERS 1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are

More information

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits WREF 01 Paper # 048 Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits Ketut Dartawan Ricardo Austria, Le Hui and Mark Suehiro* Pterra Consulting Maui Electric Company*

More information

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7

Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 White Paper Multi-Pulse Rectifier Solutions for Input Harmonics Mitigation Applicable Product: F7, G7, P7 and E7 Dr. Jun-koo Kang, Yaskawa Electric America Doc#: WP.AFD.02 Copyright Yaskawa Electric America,

More information

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India e t International Journal on Emerging Technologies 4(1): 10-16(2013) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Control of Synchronous Generator Excitation and Rotor Angle Stability by

More information

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme I J E E E C International Journal of Electrical, Electronics ISSN No. (Online) : 2277-2626 and Computer Engineering 2(1): 7-12(2013) Transient stability improvement by using shunt FACT device (STATCOM)

More information

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic

More information

Power Quality enhancement of a distribution line with DSTATCOM

Power Quality enhancement of a distribution line with DSTATCOM ower Quality enhancement of a distribution line with DSTATCOM Divya arashar 1 Department of Electrical Engineering BSACET Mathura INDIA Aseem Chandel 2 SMIEEE,Deepak arashar 3 Department of Electrical

More information

New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations

New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations New HVDC Interaction between AC networks 233 JPE 7-3-6 New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations Chan-Ki Kim, Young-Hun Kwon * and Gil-Soo Jang ** KEPRI,

More information

Long lasting transients in power filter circuits

Long lasting transients in power filter circuits Computer Applications in Electrical Engineering Vol. 12 2014 Long lasting transients in power filter circuits Jurij Warecki, Michał Gajdzica AGH University of Science and Technology 30-059 Kraków, Al.

More information

Protection for Sub SSTI Conditions Using an Industrial Sub-harmonic Relay

Protection for Sub SSTI Conditions Using an Industrial Sub-harmonic Relay Relay Conference 2018 Protection for Sub SSTI Conditions Using an Industrial Sub-harmonic Relay R. Midence ERLPhase Power Technologies Winnipeg, MB Canada 1 Outline Sub Synchronous Torsional Interactions

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

Power Quality Requirements for Connection to the Transmission System

Power Quality Requirements for Connection to the Transmission System Power Quality Requirements for Connection to the Transmission System Revision: 1.0 Date: September 2015 Introduction and Purpose of this Document The purpose of this document is to provide clarity to Customers

More information

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION David TOPOLANEK Petr TOMAN Michal PTACEK Jaromir DVORAK Brno University of Technology - Czech

More information

The Engineering Problem. Calculating GIC Flow through the EHV System

The Engineering Problem. Calculating GIC Flow through the EHV System The Engineering Problem Calculating GIC Flow through the EHV System 1 Creating the GIC System Model Since the EHV system is a three-phase balanced network, it is only necessary to model a single-phase

More information

Harmonic control devices. ECE 528 Understanding Power Quality

Harmonic control devices. ECE 528 Understanding Power Quality ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 12 1 Today Harmonic control devices In-line reactors (chokes)

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at   Modeling and Analysis of Transformer ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering

More information

Performance Improvement of Power System Using Static Synchronous Compensator (STATCOM) Priya Naikwad, Mayuri Kalmegh, Poonam Bhonge

Performance Improvement of Power System Using Static Synchronous Compensator (STATCOM) Priya Naikwad, Mayuri Kalmegh, Poonam Bhonge 2017 IJSRST Volume 3 Issue 2 Print ISSN: 235-6011 Online ISSN: 235-602X National Conference on Advances in Engineering and Applied Science (NCAEAS) 16 th February 2017 In association with International

More information

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Ishwar Lal Yadav Department of Electrical Engineering Rungta College of Engineering and Technology Bhilai, India

More information

MITIGATING GEOMAGNETIC INDUCED CURRENTS USING SURGE ARRESTERS. Alberto Ramirez Orquin Vanessa Ramirez Resilient Grids, LLC.

MITIGATING GEOMAGNETIC INDUCED CURRENTS USING SURGE ARRESTERS. Alberto Ramirez Orquin Vanessa Ramirez Resilient Grids, LLC. MITIGATING GEOMAGNETIC INDUCED CURRENTS USING SURGE ARRESTERS Alberto Ramirez Orquin Vanessa Ramirez Resilient Grids, LLC. September, 2015 General Introducing a simple, cost-effective, means to deal with

More information

Planners Perspective on Series Compensated Transmission Lines

Planners Perspective on Series Compensated Transmission Lines TOGETHER WE DELIVER Planners Perspective on Series Compensated Transmission Lines Kenneth A. Donohoo, PE Director, System Planning Distribution and Transmission kenneth.donohoo@oncor.com Oncor Electric

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

Low-Frequency Protection Concepts for the Electric Power Grid: Geomagnetically Induced Current (GIC) and E3 HEMP Mitigation

Low-Frequency Protection Concepts for the Electric Power Grid: Geomagnetically Induced Current (GIC) and E3 HEMP Mitigation Meta-R-322 Low-Frequency Protection Concepts for the Electric Power Grid: Geomagnetically Induced Current (GIC) and E3 HEMP Mitigation John Kappenman Metatech Corporation 358 S. Fairview Ave., Suite E

More information

Digital Fault Recorder Deployment at HVDC Converter Stations

Digital Fault Recorder Deployment at HVDC Converter Stations Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic

More information

Exercises. 6 Exercises

Exercises. 6 Exercises 6 Exercises The following five computer exercises accompany the course. Alternative Transients Program (ATP-EMTP) will be used to compute electrical transients. First electrical network should be created

More information

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium Assessment of the Impact of GMD on the TVA 500 kv Grid & Power Transformers Part II:

More information

Harmonic Distortion Evaluations

Harmonic Distortion Evaluations Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion

More information

Geomagnetic Disturbances. IEEE PES Chicago Chapter Technical Presentation March 12, Alan Engelmann Transmission Planning ComEd.

Geomagnetic Disturbances. IEEE PES Chicago Chapter Technical Presentation March 12, Alan Engelmann Transmission Planning ComEd. Geomagnetic Disturbances IEEE PES Chicago Chapter Technical Presentation March 12, 2014 Alan Engelmann Transmission Planning ComEd GMD Background Solar Disturbances Impacts Monitoring Events 2 Solar Disturbances

More information

Effect of Geomagnetically Induced Currents on Protection Systems

Effect of Geomagnetically Induced Currents on Protection Systems Effect of Geomagnetically Induced Currents on Protection Systems Sture Lindahl 2004-01-23 Industrial Electrical Engineering and Automation sture.lindahl@iea.lth.se Effect of GIC on Protective Relays Activity

More information

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Waruna Chandrasena, Bruno Bisewski, and Jeff Carrara Abstract-- This paper describes several system

More information

Aspects of Network Harmonic Impedance Modelling in High Voltage Distribution Networks

Aspects of Network Harmonic Impedance Modelling in High Voltage Distribution Networks Aspects of Network Harmonic Impedance Modelling in High Voltage Distribution Networks Diptargha Chakravorty Indian Institute of Technology Delhi (CES) New Delhi, India diptarghachakravorty@gmail.com Jan

More information

Resonances in Collection Grids of Offshore Wind Farms

Resonances in Collection Grids of Offshore Wind Farms Downloaded from orbit.dtu.dk on: Dec 20, 2017 Resonances in Collection Grids of Offshore Wind Farms Holdyk, Andrzej Publication date: 2013 Link back to DTU Orbit Citation (APA): Holdyk, A. (2013). Resonances

More information

WILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS

WILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION Qing-Chang Zhong The University of Sheffield, UK Tomas Hornik Turbo Power Systems Ltd., UK WILEY A John Wiley & Sons, Ltd., Publication

More information

Chapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc.

Chapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc. Chapter 30 Inductance, Electromagnetic Oscillations, and AC Circuits 30-7 AC Circuits with AC Source Resistors, capacitors, and inductors have different phase relationships between current and voltage

More information

LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS

LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS Giuseppe Di Marzio NTNU giuseppe.di.marzio@elkraft.ntnu.no Olav B. Fosso NTNU olav.fosso@elkraft.ntnu.no Kjetil Uhlen SINTEF

More information

GMD Impacts on Generators

GMD Impacts on Generators Walling Energy Systems Consulting, LLC GMD Impacts on Generators Reigh Walling 1 CME interacts with earth magnetic field Large solar flare - Coronal Mass Ejection (CME) Protons and electrons in solar wind

More information

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Level 6 Graduate Diploma in Engineering Electrical Energy Systems 9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,

More information

Prepared By Pierre Archambault, PEng Power Survey International Inc Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA

Prepared By Pierre Archambault, PEng Power Survey International Inc Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA ATCO Electric Hangingstone Substation HARMONIC STUDY Prepared By Pierre Archambault, PEng Power Survey International Inc. 8025 Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA Rev.: 6 March 2007 TABLE OF

More information

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated

More information

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk.

Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces. H.A. Khalik, M. A. Aziz, and E. Farouk. , 2011;4(12) Improvement of Power System Distribution Quality Due to Using Dc-Converter Loads and Electric Arc Furnaces H.A. Khalik, M. A. Aziz, and E. Farouk. Electrical power and Machines Engineering

More information

In power system, transients have bad impact on its

In power system, transients have bad impact on its Analysis and Mitigation of Shunt Capacitor Bank Switching Transients on 132 kv Grid Station, Qasimabad Hyderabad SUNNY KATYARA*, ASHFAQUE AHMED HASHMANI**, AND BHAWANI SHANKAR CHOWDHRY*** RECEIVED ON 1811.2014

More information

Design and Simulation of Passive Filter

Design and Simulation of Passive Filter Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt

More information

Transients under energizing multiple power filter circuits

Transients under energizing multiple power filter circuits Computer Applications in Electrical Engineering Vol. 14 2016 DOI 10.21008/j.1508-4248.2016.0008 Transients under energizing multiple power filter circuits Jurij Warecki, Michał Gajdzica AGH University

More information

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection SolidGround TM GIC grid stability and harmonics mitigation

More information

ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS

ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS INDO-US Workshop October 2009, I.I.T. Kanpur INTRODUCTION Electric Power Systems are very large, spread over a wide geographical area

More information

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative:  Address: Fax Number: Interconnection of a Customer-Owned Renewable Generation System of Greater than 100 KW and Less than or Equal to 1 MW to the LCEC Electric Grid Tier 3 Application and Compliance Form Instructions: Complete

More information

Harmonic filter design for electrified railways

Harmonic filter design for electrified railways filter design for electrified railways DIgSILENT USER GROUP Sydney 5 September 2013 M Jansen, S Hagaman, T George Railway electrification project Adds significant unbalanced non-linear load to the grid

More information

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,

More information

Operational Experiences of an HV Transformer Neutral Blocking Device

Operational Experiences of an HV Transformer Neutral Blocking Device MIPSYCON NOVEMBER 7, 2017 Operational Experiences of an HV Transformer Neutral Blocking Device Fred R. Faxvog, Emprimus Michael B. Marz, American Transmission Co. SolidGround GIC Neutral Blocker Fully

More information

, ,54 A

, ,54 A AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Power System Impacts of Geomagnetic Disturbances

Power System Impacts of Geomagnetic Disturbances 1 Power System Impacts of Geomagnetic Disturbances Thomas J. Overbye Fox Family Professor of Electrical l and Computer Engineering i University of Illinois at Urbana Champaign overbye@illinois.edu September

More information

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Phanikumar.Ch, M.Tech Dept of Electrical and Electronics Engineering Bapatla Engineering College, Bapatla,

More information

Sub-synchronous Electrical Torque Frequencies Monitoring before the SSR Presence.

Sub-synchronous Electrical Torque Frequencies Monitoring before the SSR Presence. Sub-synchronous Electrical Torque Frequencies Monitoring before the SSR Presence. *José A Castillo J *David Sebastián B **Carlos A Rivera S *Daniel Olguín S * Programa de Postgrado en Ingeniería Eléctrica,

More information

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone

More information

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit

More information

HVDC High Voltage Direct Current

HVDC High Voltage Direct Current HVDC High Voltage Direct Current Typical HVDC Station BACK TO BACK CONVERTER STATION MONO POLAR WITH GROUND RETURN PA Back to Back Converters indicates that the Rectifiers & Inverters are located in the

More information

In Class Examples (ICE)

In Class Examples (ICE) In Class Examples (ICE) 1 1. A 3φ 765kV, 60Hz, 300km, completely transposed line has the following positive-sequence impedance and admittance: z = 0.0165 + j0.3306 = 0.3310 87.14 o Ω/km y = j4.67 410-6

More information

Fault Ride Through Technical Assessment Report Template

Fault Ride Through Technical Assessment Report Template Fault Ride Through Technical Assessment Report Template Notes: 1. This template is intended to provide guidelines into the minimum content and scope of the technical studies required to demonstrate compliance

More information

Some aspects regarding harmonic s distortions propagation in large medium voltage distribution system

Some aspects regarding harmonic s distortions propagation in large medium voltage distribution system Some aspects regarding harmonic s distortions propagation in large medium voltage distribution system L. E. PETREAN 1, D. C. PETER 1, M. HORGOŞ 1, A. BUCHMANN 1, L. PETREAN 2 1 Electrical Engineering Department,

More information

P2 Power Solutions Pvt. Ltd.

P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Active Current Conditioners P2 Power Solutions Pvt. Ltd. P2 Power Solutions works to deliver Innovative Engineering solutions with specific focus on

More information

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: ; e-issn:

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER  CSEA2012 ISSN: ; e-issn: POWER FLOW CONTROL BY USING OPTIMAL LOCATION OF STATCOM S.B. ARUNA Assistant Professor, Dept. of EEE, Sree Vidyanikethan Engineering College, Tirupati aruna_ee@hotmail.com 305 ABSTRACT In present scenario,

More information

ANALYSIS OF THE MITIGATION METHODS OF GEOMAGNETICALLY INDUCED CURRENT

ANALYSIS OF THE MITIGATION METHODS OF GEOMAGNETICALLY INDUCED CURRENT ANALYSIS OF THE MITIGATION METHODS OF GEOMAGNETICALLY INDUCED CURRENT AnkitNimje 1, Nikhil Bhagadkar 2, Shubham Marsinge 3, Prof. C.S.Hiwarkar 4 1 Ankit Nimje, Electrical Department, K.D.K.C.E, Maharashtra,

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

Analysis of Single and Multi Resonance Point in Reactance Characteristics of TCSC Device

Analysis of Single and Multi Resonance Point in Reactance Characteristics of TCSC Device Analysis of Single and Multi Resonance Point in Reactance Characteristics of TCSC Device Manojkumar Patil 1, Santosh Kompeli 2 1 Student (M.E.) Electrical Engineering Department, MSS S COE, Jalna, Maharashtra,

More information

A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer

A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer IJIRST International Journal for Innovative Research in Science & Technology Volume 3 Issue 07 December 2016 ISSN (online): 2349-6010 A Novel Method to Analyse the Effects of Geomagnetic Induced Current

More information

Modeling and Evaluation of Geomagnetic Storms in the Electric Power System

Modeling and Evaluation of Geomagnetic Storms in the Electric Power System 21, rue d Artois, F-75008 PARIS C4-306 CIGRE 2014 http : //www.cigre.org Modeling and Evaluation of Geomagnetic Storms in the Electric Power System K. PATIL Siemens Power Technologies International, Siemens

More information

Analysis of a 405 km transmission line with series compensation

Analysis of a 405 km transmission line with series compensation Analysis of a 405 km transmission line with series compensation by Dr. Rupert Gouws, North-West University This paper presents an investigative case study and energy efficiency analysis of the 405 km,

More information

Harmonic Design Considerations for Wind Farms

Harmonic Design Considerations for Wind Farms Harmonic Design Considerations for Wind Farms To Ensure Grid Code Compliance Liam Breathnach Power System Studies Group ESB International Agenda Introduction Harmonic Theory and Concepts Grid Code Requirements

More information

FINNISH EXPERIENCES ON GRID EFFECTS OF GIC'S

FINNISH EXPERIENCES ON GRID EFFECTS OF GIC'S FINNISH EXPERIENCES ON GRID EFFECTS OF GIC'S ESA-SPACE WEATHER WORKSHOP The Netherlands 17. November, 2005 by J. Elovaara 1 Jarmo Elovaara Oct. 25, 2005 Content: 1. About the potential effects of GIC's

More information

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance The Effect of Various Types of DG Interconnection Transformer on Ferroresonance M. Esmaeili *, M. Rostami **, and G.B. Gharehpetian *** * MSc Student, Member, IEEE, Shahed University, Tehran, Iran, E mail:

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

Voltage and Current Waveforms Enhancement using Harmonic Filters

Voltage and Current Waveforms Enhancement using Harmonic Filters Voltage and Current Waveforms Enhancement using Harmonic Filters Rajeb Ibsaim rabsaim@yahoo.com, Azzawia University, Libya Amer Daeri ibnjubair1@yahoo.co.uk Azzawia University, Libya Abstract The demand

More information

Power Factor & Harmonics

Power Factor & Harmonics Power Factor & Harmonics Andy Angrick 2014 Harmonic Distortion Harmonic problems are becoming more apparent because more equipment that produce harmonics are being applied to power systems Grounding Harmonics

More information

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY POWER QUALITY IMPROVEMENT OF GRID CONNECTED WIND ENERGY SYSTEM BY USING STATCOM Mr.Mukund S. Mahagaonkar*, Prof.D.S.Chavan * M.Tech

More information

Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation

Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation TSAI-HSIANG CHEN a NIEN-CHE YANG b Department of Electrical Engineering National Taiwan University

More information

Power Quality Enhancement and Mitigation of Voltage Sag using DPFC

Power Quality Enhancement and Mitigation of Voltage Sag using DPFC Power Quality Enhancement and Mitigation of Voltage Sag using DPFC M. Bindu Sahithi 1, Y. Vishnu Murthulu 2 1 (EEE Department, Prasad V Potluri Siddhartha Institute of Technology, A.p, India) 2 (Assistant

More information

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies

Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies Analysis of Temporary Over-Voltages from Self-Excited Large Induction Motors in the Presence of Resonance - Case Studies T.G. Martinich, M. Nagpal, A. Bimbhra Abstract-- Technological advancements in high-power

More information

Do Capacitor Switching Transients Still Cause Problems?

Do Capacitor Switching Transients Still Cause Problems? Do Capacitor Switching Transients Still Cause Problems? Mark McGranaghan We have been evaluating problems related to capacitor switching transients for many years. Capacitor banks have been used on distribution

More information

Dynamic Modeling of Thyristor Controlled Series Capacitor in PSCAD and RTDS Environments

Dynamic Modeling of Thyristor Controlled Series Capacitor in PSCAD and RTDS Environments Dynamic Modeling of Thyristor Controlled Series Capacitor in PSCAD and RTDS Environments 1 Pasi Vuorenpää and Pertti Järventausta, Tampere University of Technology Jari Lavapuro, Areva T&D Ltd Abstract

More information

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar. Technical Report on Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by Dr. V. R. Kanetkar (February 2015) Shreem Electric Limited (Plot No. 43-46, L. K. Akiwate

More information

ANFIS based 48-Pulse STATCOM Controller for Enhancement of Power System Stability

ANFIS based 48-Pulse STATCOM Controller for Enhancement of Power System Stability ANFIS based 48-Pulse STATCOM Controller for Enhancement of Power System Stility Subir Datta and Anjan Kumar Roy Abstract The paper presents a new ANFIS-based controller for enhancement of voltage stility

More information

Grid Code Review Panel. Information Required to Evaluate Subsynchrononous Resonance on the Transmission System

Grid Code Review Panel. Information Required to Evaluate Subsynchrononous Resonance on the Transmission System Grid Code Review Panel Information Required to Evaluate Subsynchrononous Resonance on the Transmission System Summary of Issue A paper by National Grid Contact: Graham Stein 1. All electrical and electromechanical

More information

I. INTRODUCTION IJSRST Volume 3 Issue 2 Print ISSN: Online ISSN: X

I. INTRODUCTION IJSRST Volume 3 Issue 2 Print ISSN: Online ISSN: X 2017 IJSRST Volume 3 Issue 2 Print ISSN: 2395-6011 Online ISSN: 2395-602X National Conference on Advances in Engineering and Applied Science (NCAEAS) 16 th February 2017 In association with International

More information

CHAPTER 1 INTRODUCTION

CHAPTER 1 INTRODUCTION CHAPTER 1 INTRODUCTION 1.1 Introduction Power semiconductor devices constitute the heart of the modern power electronics, and are being extensively used in power electronic converters in the form of a

More information

Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System

Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System Performance Analysis of Passive Filter for Harmonics Due to Non-Linear Load in Power System Engr.Kavitha Vasantha 1 Lecturer, BSIE, College of Engineering, Salmabad, Kingdom of Bahrain 1 Abstract: As end

More information

A Process for Evaluating the Degree of Susceptibility of a fleet of Power Transformers to Effects of GIC

A Process for Evaluating the Degree of Susceptibility of a fleet of Power Transformers to Effects of GIC 1 A Process for Evaluating the Degree of Susceptibility of a fleet of Power Transformers to Effects of GIC Ramsis Girgis, Kiran Vedante, and Gary Burden ABB Power Transformers Abstract: There has been

More information

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 3, Issue 03, 2015 ISSN (online): 2321-0613 Mitigating the Harmonic Distortion in Power System using SVC With AI Technique Mr. Sanjay

More information

Connection Impact Assessment Application Form

Connection Impact Assessment Application Form Connection Impact Assessment Application Form This Application Form is for Generators applying for a Connection Impact Assessment (CIA). In certain circumstances, London Hydro may require additional information

More information

GMD Voltage Collapse Study

GMD Voltage Collapse Study GMD Voltage Collapse Study Terry Volkmann 2016 Fall Reliability Conference November 2, 2016 1 GMD Voltage Collapse Studies in Wisconsin and Maine Overview: Modeling shows GMD Voltage Collapse Issues: Power

More information

Solving Customer Power Quality Problems Due to Voltage Magnification

Solving Customer Power Quality Problems Due to Voltage Magnification PE-384-PWRD-0-11-1997 Solving Customer Power Quality Problems Due to Voltage Magnification R. A. Adams, Senior Member S. W. Middlekauff, Member Duke Power Company Charlotte, NC 28201 USA E. H. Camm, Member

More information