Digital Fault Recorder Deployment at HVDC Converter Stations
|
|
- Gwenda Craig
- 5 years ago
- Views:
Transcription
1 Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic tool when analyzing faults and unexpected behavior. Monitoring the AC supply, the secondary of the power transformers, the filter banks, the DC output, converter station control signals and the protection scheme provides an invaluable set of data showing the interaction of the DC system with disturbances and transients emanating from the AC supply. Modern Fault Recorders are multi-function devices incorporating power quality measurements to the IEC standard to class A accuracy. This allows continuous monitoring of the harmonics presented to the AC grid to ensure they remain compliant. Monitoring harmonic levels in the filter banks and secondary side of the power transformer will ensure currents do not exceed rated values. Furthermore it will be possible to incorporate travelling wave fault location into the scheme for monitoring the DC overhead line circuit. This will provide very accurate fault location thereby reducing downtime by dispatching crews to the right spot first time. A Multi-Function Fault Recorder The following functionality is applicable to HVDC stations: High Speed Fault Recording This is the traditional role of a fault recorder whereby analogue signals (both AC and DC) are sampled at a high rate (up to 512 samples / cycle) and a record in the order of 2 or 3 seconds triggered and stored when an abnormal event is detected. The resultant record consisting of pre and post trigger information allows post mortem analyses to be conducted. When combined with digital inputs from relays, circuit breakers and control equipment it is possible to analyse the response of any part of the Station to a transient event to assess performance. Slow Scan or Disturbance Monitoring Also known as Dynamic Disturbance Recording (DDR) this function logs calculated parameters such as system frequency, rms magnitude, phase angle, power (real, reactive and apparent) and sequence components at a selectable rate up to twice per cycle. DDR-C (continuous) stores the parameters in a circular buffer. The typical duration before data is overwritten is 15 days. There is also a triggered variant, DDR-T, where parameters are stored as a permanent record up to 30 minutes long with pre and post trigger segments. Slow scan monitoring is used to determine the response of the Converter Station during periods of instability on the AC grid such as power swing oscillations and frequency and voltage deviations. When digital input status is overlaid on the recordings it is possible to monitor relay and breaker activity as well. Power Quality Monitoring Power quality monitoring providing long term log data of frequency, rms magnitudes, harmonics, voltage dips and swells, unbalance and power must be done by a device
2 compliant with IEC Class A accuracy. The results obtained are then validated and can be compared with data from other equivalent devices on the network. Note that harmonic monitoring is particularly important at HVDC sites as the DC conversion process can inject harmonics into the AC grid if the filters are not designed correctly. Note that when measuring harmonics it is important to have a wide bandwidth signal from the instrument transformer. Protection or metering CTs have sufficient bandwidth for accurate current measurements but standard capacitor or inductive type voltage transformers do not. At transmission voltages it is normal to employ capacitor voltage instrument transformers. In such cases it is imperative to add a PQ Sensor device to provide a wide bandwidth output for accurate harmonic measurements. Travelling Wave Fault Location HVDC circuits tend to be long and fault location can be problematical as normal impedance methods cannot be applied for DC. A good alternative solution it to deploy a double ended travelling wave system where the fault induced travelling waves propagate to each end of the line and are detected and accurately time stamped. Distance to fault is calculated from the arrival time at each of the line ends, the total line length and the speed of propagation. Accuracies in the order of 100m are possible. Travelling wave fault location is possible on overhead lines where the travelling wave losses are relatively low. However, the technique is not viable on cable lengths over 50Km due to the much higher losses incurred. Typical Deployment on a +/- 500KV Converter Station The following example is from a project where a submarine cable was used for the HVDC transmission. As such there are no filter banks on the DC side of the Converter as the capacitance of the cable limits harmonics. (DC side filter banks are more common when the HVDC transmission is via overhead lines) The project utilized 2 x bipoles, pole 1 and pole 2 with a common return via the sea. The architecture used at each Converter Station is shown in Fig 1.Data Acquisition Units (DAUs) operate as standalone recording devices. All have Fault Recording and Slow Scan Monitoring as standard with some having a Power Quality capability. None of the devices have Travelling Wave functionality in this case as the losses on the long submarine cable are too great to support the technique. There is one AC transmission line at each Converter Station terminated on busbars. Two Converters are connected to the busbars, Pole 1 and Pole 2. Each Converter consists of one power transformer, filter banks, a series reactor and the AC/DC converter. The power transformers are single phase devices with two secondary windings separated by 30 degrees. In total 6 secondary windings connect to the AC/DC converter. All DAUs are installed in the relevant protection bay to reduce the amount of secondary wiring. All DAUs are connected to the IEC61850 station bus to exchange cross trigger signals, augment the hard wired digital inputs with digital status and messages from GOOSE messages and transfer data to the central analysis station. The central master station has a client server architecture. All data from the DAUs is stored on the central server with the aid of an SQL database. The server is housed in the Converter Station control room and clients can log on locally or remotely from the National Operations Center to view and analyse data and construct reports.
3 Fig 1 DFR deployment in a +/- 500KV HVDC Converter Station The quantities monitored for each asset type are listed below: DAU Function Incoming AC Line Bay AC Filter and Shunt reactor Bays Transformer Bay DC Pole 500KV and Neutral Common Device Signals Monitored 3 phase currents Residual current 3 phase voltages 3 phase currents to ground Residual current 3 phase voltages Single phase primary and residual currents Current on each secondary winding (12 current channels in total) 3 phase primary voltages Each secondary winding voltage (9 voltage channels in total DC pole current DC neutral current valve side DC neutral current electrode side 1 AC voltage channel to monitor ripple DC pole voltage DC midpoint voltage DC neutral voltage 14 DC voltage channels for control signals 4 DC currents in the common neutral circuit All DC channels had an input range of +/-12V. DC current signals were derived from transducers and DC voltages derived from RCD devices.
4 PQ Sensors were fitted to the transformer primary voltage CVTs to provide accurate wide bandwidth harmonic monitoring. Harmonic monitoring was also deployed on the AC filter and Shunt Reactor currents for diagnostic purposes. Clock Synchronisation It is possible for the fault recording system to incorporate an internal GPS receiver for accurate time synchronization but in this example an external master clock was available that generated an NTP signal ensuring a time of accuracy of 1 or 2ms for each device. It is very important for all recorded data to be time synchronized so that it is possible to directly compare events between one DAU and another and between each end of the HVDC link. Note that if Travelling Wave fault location is used then clock accuracies better than 1µs is required. End to End Communications Each converter station has an independent monitoring system but there is a communication channel to the converter station at the other end of the link such that data can be downloaded from both sides and compared when necessary. The architecture drawing below shows this. Summary Using a multi-function fault recording monitoring system is an essential tool for on line monitoring of an HVDC Converter Station. Diagnostics are required when a fast acting, complex control system interacting with a dynamic AC grid experiences problems. Some DC
5 Converter stations have some internal monitoring but it does not substitute for comparing external AC influences with DC response. Adding the Power Quality and Fault Locating functionality adds value to the installation and provides an increased return on investment.
ELECTRICAL POWER ENGINEERING
Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation
More informationHVDC High Voltage Direct Current
HVDC High Voltage Direct Current Typical HVDC Station BACK TO BACK CONVERTER STATION MONO POLAR WITH GROUND RETURN PA Back to Back Converters indicates that the Rectifiers & Inverters are located in the
More informationThis webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB
This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays
More informationApplication for A Sub-harmonic Protection Relay. ERLPhase Power Technologies
Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationFundamental Concepts of Dynamic Reactive Compensation. Outline
1 Fundamental Concepts of Dynamic Reactive Compensation and HVDC Transmission Brian K. Johnson University of Idaho b.k.johnson@ieee.org 2 Outline Objectives for this panel session Introduce Basic Concepts
More informationELECTRICAL POWER TRANSMISSION TRAINER
ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering
More informationChapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two
Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead
More informationUNIT-4 POWER QUALITY MONITORING
UNIT-4 POWER QUALITY MONITORING Terms and Definitions Spectrum analyzer Swept heterodyne technique FFT (or) digital technique tracking generator harmonic analyzer An instrument used for the analysis and
More informationHV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point
2010 MAP Range HV / MV / LV electrical network quality analyzers Class A > Network quality Analyzers PRODUCT ADVANTAGES COMPLIANT with the EN 61000-4-30 standard, Class A DETECTION of the fault LOCATION
More informationUProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy
UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected
More informationISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS
ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS INDO-US Workshop October 2009, I.I.T. Kanpur INTRODUCTION Electric Power Systems are very large, spread over a wide geographical area
More informationCHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS
84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial
More informationSmart Energy & Power Quality Solutions. Portable energy measurement devices COMPACT FLEXIBLE PRECISE
Portable energy measurement devices COMPACT FLEXIBLE PRECISE Portable energy measurement devices COMPACT FLEXIBLE PRECISE The portable energy measurement devices from Janitza Stay flexible with the portable
More informationPRC Compliance Using Bitronics 70 Series Recorders
PRC-002-2 Compliance Using Bitronics 70 Series Recorders Introduction The North American Electric Reliability Council (NERC) has defined standards for disturbance monitoring and reporting requirements
More informationDesign, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter
1 Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter Nee, Staffan Norrga, Remus Teodorescu ISBN-10: 1118851560
More informationCOMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)
7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series
More informationConventional Paper-II-2011 Part-1A
Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance
More informationFixed Series Compensation
Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and
More informationPOWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.
POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products
More informationPOWER QUALITY AND SAFETY
POWER QUALITY AND SAFETY Date : November 27, 2015 Venue : 40 th IIEE Annual National Convention and 3E XPO 2015 PRESENTATION OUTLINE Power Quality I. INTRODUCTION II. GRID CODE REQUIREMENTS III. ERC RESOLUTION
More informationSHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP
SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP Kiran V. Natkar 1, Naveen Kumar 2 1 Student, M.E., Electrical Power System, MSS CET/ Dr. B.A.M. University, (India) 2 Electrical Power System,
More informationPower quality Harmonics up to 40th harmonic Rotary field components Distortion factor THD-U / THD-I
Memory 256 MB Alarm management Residual current measurement Homepage Ethernet-Modbus gateway BACnet (optional) UMG 96 RM-E Power analyser with Ethernet and RCM Communication Modbus (RTU, TCP, Gateway)
More informationQualitrol s PMU Technologies
Qualitrol s PMU Technologies IDM NASPI Conference June 2008 BEN 6000 Agenda 1. Qualitrol s experience 2. Recording functions that compliment Phasor Measurement 3. A Multi function PMU 4. PMU Case Study
More informationChoosing your power quality analyzer
Choosing your power quality analyzer > Based on its specifications > Power Quality Analyzers Single-phase Permanent analyzers > page 89 > page 88 > page 91 Three-phase Non-intrusive analyzers MAP 607 MAP
More informationLevel 6 Graduate Diploma in Engineering Electrical Energy Systems
9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,
More informationELEMENTS OF FACTS CONTROLLERS
1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are
More informationCHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS
86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the
More informationZambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years
21, rue d Artois, F-758 PARIS B4-18 CIGRE 216 http : //www.cigre.org Zambezi (previously Caprivi) Link HVDC Interconnector: Review of Operational Performance in the First Five Years T G MAGG, Power System
More informationPowerMonitor 5000 Family Advanced Metering Functionality
PowerMonitor 5000 Family Advanced Metering Functionality Steve Lombardi, Rockwell Automation The PowerMonitor 5000 is the new generation of high-end electrical power metering products from Rockwell Automation.
More informationCourse ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation
Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission
More informationCurso de Transmissão em Corrente Continua Rio de Janeiro, de Junho, 2007
Curso de Transmissão em Corrente Continua Rio de Janeiro, 13 15 de Junho, 2007 DC Harmonic Filters Page 1 of 9 1 Function of the DC-Side Harmonic Filters Harmonic voltages which occur on the dc-side of
More informationESB National Grid Transmission Planning Criteria
ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and
More informationA Power Quality Interface for Low and Medium Voltage Smart Grids
Technical Data Power Quality Interface for Low and Medium Voltage Smart Grids Model PQI-D smart 1 Wall-mounted housing 1 DIN-Rail housing 1 Panel mounting housing 1. pplication Solving all measurement
More informationDeep Data from Optical Sensors
1 Deep Data from Optical Sensors Farnoosh Rahmatian NuGrid Power Corp August 7, 2018 IEEE PES GM, Portland, OR 2018 NuGrid Power Corp 2 Outline What is a deep data sensor? Optical Voltage/Current Sensors
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control
ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections
More information[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY POWER QUALITY IMPROVEMENT OF GRID CONNECTED WIND ENERGY SYSTEM BY USING STATCOM Mr.Mukund S. Mahagaonkar*, Prof.D.S.Chavan * M.Tech
More informationCoil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900
Coil Products Coil Products Customer partnership around the globe More than 250,000 coil products delivered to more than 170 countries. More than 60 years of operational experience. 35,000 in Europe 13,000
More informationINTEGRATED TRANSMISSION PLAN Glossary
INTEGRATED TRANSMISSION PLAN Glossary SEPTEMBER 2017 GLOSSARY Term AC ACM asset health and asset health index (AHI) automatic underfrequency load shedding (AUFLS) availability bus cable capacitor bank
More informationUsing smart grid sensors and advanced software applications as an asset management tool at Hydro Ottawa
24th International Conference & Exhibition on Electricity Distribution (CIRED) 12-15 June 2017 Session 1: Network components Using smart grid sensors and advanced software applications as an asset management
More informationSequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network
Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria
More informationHVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN
HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN Summary Capacitor Commutated Converters (CCC) were introduced to the HVDC market
More informationp. 1 p. 6 p. 22 p. 46 p. 58
Comparing power factor and displacement power factor corrections based on IEEE Std. 18-2002 Harmonic problems produced from the use of adjustable speed drives in industrial plants : case study Theory for
More informationCork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)
Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:
More informationPower quality report. A Manufacturing Plant
Power quality report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION... 5 2.1 SITE MONITORED...
More informationPower System Stability. Course Notes PART-1
PHILADELPHIA UNIVERSITY ELECTRICAL ENGINEERING DEPARTMENT Power System Stability Course Notes PART-1 Dr. A.Professor Mohammed Tawfeeq Al-Zuhairi September 2012 1 Power System Stability Introduction Dr.Mohammed
More informationPQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.
General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand
More informationHigh Voltage DC Transmission 2
High Voltage DC Transmission 2 1.0 Introduction Interconnecting HVDC within an AC system requires conversion from AC to DC and inversion from DC to AC. We refer to the circuits which provide conversion
More informationGrid Impact of Neutral Blocking for GIC Protection:
Report submitted to EMPRIMUS - Critical Infrastructure Protection Grid Impact of Neutral Blocking for GIC Protection: Impact of neutral grounding capacitors on network resonance Prepared By: Athula Rajapakse
More informationABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device
ABB AG - EPDS The worldʼs fastest limiting and switching device Agenda The world s fastest limiting and switching device Customers Function: Insert-holder with insert Comparison: I S -limiter Circuit-breaker
More informationPQM3000R Class A network analyzer according to EN for power quality monitoring
Class A network analyzer according to EN 50160 for power quality monitoring Possibility to carry out parameter recording according to EN 50160 Integrated web server for complete device management 4 GB
More informationPRC Disturbance Monitoring and Reporting Requirements
Standard Development Timeline This section is maintained by the drafting team during the development of the standard and will be removed when the standard becomes effective. Development Steps Completed
More informationMICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2
PART 1 PART 2 PRODUCTS 2.01 MANUFACTURERS A. Eaton products B.. C.. The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features
More informationU I. HVDC Control. LCC Reactive power characteristics
Lecture 29 HVDC Control Series Compensation 1 Fall 2017 LCC Reactive power characteristics LCC HVDC Reactive compensation by switched filters and shunt capacitor banks Operates at lagging power factor
More informationPAPER-II (Subjective)
PAPER-II (Subjective) 1.(A) Choose and write the correct answer from among the four options given in each case for (a) to (j) below: (a) Improved commutation in d.c machines cannot be achieved by (i) Use
More informationMITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)
VOL. 4, NO. 4, JUNE 9 ISSN 89-668 6-9 Asian Research Publishing Network (ARPN). All rights reserved. MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) Rosli Omar and Nasrudin Abd Rahim
More informationFERRORESONANCE SIMULATION STUDIES USING EMTP
FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements
Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system
More informationAORC Technical meeting 2014
http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi
More informationExperiences on using gapless waveform data & synchronized harmonic phasors
1 Panel Session: New Techniques for Power Quality Measurement and Field Experiences 15PESGM3040 Experiences on using gapless waveform data & synchronized harmonic phasors Wilsun Xu University of Alberta
More informationPower Quality and Reliablity Centre
Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview
More informationPower Quality Measurements the Importance of Traceable Calibration
Power Quality Measurements the Importance of Traceable Calibration H.E. van den Brom and D. Hoogenboom VSL Dutch Metrology Institute, Delft, the Netherlands, hvdbrom@vsl.nl Summary: Standardization has
More informationInsights in the impact of special projects on voltage quality in the HV/EHV networks
Authors: Vladimir Ćuk Konstantinos Tzanakakis Department of Electrical Engineering, Electrical Energy Systems Checked by: prof. J.F.G. (Sjef) Cobben Frans van Erp (Tennet) Date: 05.12.2014. Version: 0.0
More informationAC Power Transmission Training System Add- On to ( )
AC Power Transmission Training System Add- On to 8006 587433 (89252-00) LabVolt Series Datasheet Festo Didactic en 120 V - 60 Hz 03/2019 Table of Contents General Description 2 List of Equipment 2 List
More informationExtensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network
Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example
More informationAnalysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 3 Ver. I (May Jun. 2014), PP 36-41 Analysis, Modeling and Simulation of Dynamic Voltage
More informationASPECTS OF REAL-TIME DIGITAL SIMULATIONS OF ELECTRICAL NETWORKS
23 rd International Conference on Electricity Distribution Lyon, 58 June 25 ASPECTS OF REAL-TIME DIGITAL SIMULATIONS OF ELECTRICAL ABSTRACT Ambrož BOŽIČEK ambroz.bozicek@fe.uni-lj.si Boštjan BLAŽIČ bostjan.blazic@fe.uni-lj.si
More information3 Phase Power Quality Analy er
3 Phase Power Quality Analy er BlackBox G4500 The 3 Phases Portable Power Quality Analyzers Discover Outstanding Features The BlackBox portable series power quality analyzer takes power quality monitoring
More informationMODEL POWER SYSTEM TESTING GUIDE October 25, 2006
October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More informationPower Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)
Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,
More informationProtection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin
Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad
More informationLecture 4 Power System Instrumentation. Course map
Lecture 4 Power System Instrumentation 1 Course map 2 1 Outline of the Lecture Instrument Transformers Voltage Transformer Current Transformers Measurement Setups Instrumentation 3 The Current Transformer
More informationPower Quality Solutions PQSine P-Series of Active Harmonic Filters and Power Optimizers
EPCOS Product Brief 2017 Power Quality Solutions of Active Harmonic Filters and Power Optimizers EPCOS has been offering a comprehensive range of key components for power factor correction (PFC) and power
More informationUnit-II----Analysis of HVDC Converters
Unit-II----Analysis of HVDC Converters Introduction: HVDC converters converts AC to DC and transfer the DC power, then DC is again converted to AC by using inverter station. HVDC system mainly consists
More informationSizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks
Sizing the neutral wire cross-section and minimization of neutral currents using microgeneration in low voltage networks André Braga Instituto Superior Técnico Av. Rovisco Pais, 1049-001 Lisbon, Portugal
More informationUsing a Multiple Analog Input Distance Relay as a DFR
Using a Multiple Analog Input Distance Relay as a DFR Dennis Denison Senior Transmission Specialist Entergy Rich Hunt, M.S., P.E. Senior Field Application Engineer NxtPhase T&D Corporation Presented at
More informationAnalysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar
Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements
Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission
More informationIntroduction: TAS PowerTek Ltd. MAVROS
Introduction: Electrical supply system in today s scenario faces a major challenge due to Power Quality issues. Harmonics on supply system due to Electronics type of loads that are used extensively. Power
More informationNew HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations
New HVDC Interaction between AC networks 233 JPE 7-3-6 New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations Chan-Ki Kim, Young-Hun Kwon * and Gil-Soo Jang ** KEPRI,
More informationEH2741 Communication and Control in Electric Power Systems Lecture 2
KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment
More informationPQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks
GB Technical data Issue 06/2009 PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks Fault detection Evaluation of voltage quality according to EN50160 and IEC61000-2-2 Fault recorder
More informationDimension diagrams All dimensions in mm. Typical connection UMG 604-PRO. Power Analyser UMG 604-PRO. Front view. Side view. Versorgungsspannung
Dimension diagrams All dimensions in mm 73 mm 10 mm 35 mm 44 mm 90 mm 90 mm 107,5 mm 50 mm 76 mm 82 mm Front view Side view Typical connection An. In R32 RS485 Dig. I/O Versorgungsspannung Auxiliary Supply
More informationEnhancement of Voltage Stability & reactive Power Control of Distribution System Using Facts Devices
Enhancement of Voltage Stability & reactive Power Control of Distribution System Using Facts Devices Aarti Rai Electrical & Electronics Engineering, Chhattisgarh Swami Vivekananda Technical University,
More informationAn Introduction to Power Quality
1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger
More informationSouthern Company Interconnection Requirements for Inverter-Based Generation
Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection
More informationPower Quality Report. A Manufacturing Plant
Power Quality Report Prepared for A Manufacturing Plant 6 May 2016 by Dr Angelo De Francesco Power Quality Consultant CHK Power Quality Pty Ltd Page 1 Contents 1 EXECUTIVE SUMMARY... 4 2 INTRODUCTION...
More informationRequirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH
Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 5th October 2010 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT
More informationDIFFERENTIAL CURRENT GENERATOR «POCDIF» (AC/DC - 32A - 50V - 12 ranges)
PERFORMANCES 12 ranges of AC current from 16 ma to 128 A peak AC permanent current up to 26 ARMS Nine ranges of DC permanent current from 16 ma to 12 A DC current ± 6mA or ± 10 ma stackable to AC current
More informationCHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES
86 CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES 5.1 INTRODUCTION Distribution systems face severe power quality problems like current unbalance, current harmonics, and voltage unbalance,
More informationHigh Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur
High Voltage DC Transmission Prof. Dr. S. N. Singh Department of Electrical Engineering Indian Institute of Technology, Kanpur Module No. # 01 Lecture No. # 02 Comparison of HVAC and HVDC Systems Welcome
More informationC.A Complete electrical network analysis at the tips of your fingers! Power Quality Monitor. Keeping up with the standards
Keeping up with the standards C.A 8352 Power Quality Monitor Complete electrical network analysis at the tips of your fingers! All measurements for complete analysis: powers, harmonics, flicker, symmetry,
More informationEnhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)
Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) PATTI.RANADHEER Assistant Professor, E.E.E., PACE Institute
More informationApplication Of Artificial Neural Network In Fault Detection Of Hvdc Converter
Application Of Artificial Neural Network In Fault Detection Of Hvdc Converter Madhuri S Shastrakar Department of Electrical Engineering, Shree Ramdeobaba College of Engineering and Management, Nagpur,
More informationReliabilityFirst Regional Criteria 1. Disturbance Monitoring and Reporting Criteria
ReliabilityFirst Regional Criteria 1 Disturbance Monitoring and Reporting Criteria 1 A ReliabilityFirst Board of Directors approved good utility practice document which are not reliability standards. ReliabilityFirst
More informationNetwork Analyzer for Low-, Medium- and High-Voltage Networks
Technical data Network nalyzer for Low-, Medium- and High-Voltage Networks Model PQ-Box 150 1 Fault detection 1 Evaluation of voltage quality according to EN50160 and IEC61000-2-2 (2-4) 1 FFT nalysis up
More informationDIFFERENTIAL CURRENT GENERATOR «POCDIF» (AC/DC - 32A - 50V - 12 ranges)
PERFORMANCES 12 ranges of AC current from 16 ma to 128 A peak AC permanent current up to 26 ARMS Nine ranges of DC permanent current from 16 ma to 12 A DC current ± 6mA or ± 10 ma stackable to AC current
More informationAutomated Fault Detection With PQ Monitors
Automated Fault Detection With PQ Monitors Theo Laughner, PE Sr. Program Manager of Power Quality Acknowledgements: Anthony Murphy, PE October 12, 2015 Background Case Studies (5) Needs Tools Conclusion
More informationPower quality Harmonics up to 40th harmonic Unbalance, rotary field indication Distortion factor THD-U / THD-I
Harmonics Temperature input Measurement accuracy 0.5 Memory 4 MByte UMG 104 Energy measurement device for DIN rails Communication Profibus (DP / V0 optional) Modbus RTU Power quality Harmonics up to 40th
More information