Effect of Geomagnetically Induced Currents on Protection Systems

Size: px
Start display at page:

Download "Effect of Geomagnetically Induced Currents on Protection Systems"

Transcription

1 Effect of Geomagnetically Induced Currents on Protection Systems Sture Lindahl Industrial Electrical Engineering and Automation

2 Effect of GIC on Protective Relays Activity of the Sun Propagation of the Solar Wind Magnetospheric Processes Ionospheric Processes Earth Surface Potential Geomagnetically Induced Currents Saturation of Power Transformers Performance of Protective Relays Sture Lindahl, LTH/IEA 2

3 Solar Flare Effects Sture Lindahl, LTH/IEA 3

4 Geomagnetically Induced Currents Electrojet GIC GIC GIC + Earth Surface Potential Gradient - GIC Sture Lindahl, LTH/IEA 4

5 Conclusions The risk is that protective relays operate unwantedly during a geomagnetic storm and causes a severe power system disturbance or even a nationwide blackout A less obvious risk is that the current transformers operates so far into saturation that the secondary current is too low for proper operation of the protection equipment at internal faults during geomagnetic storms. Sture Lindahl, LTH/IEA 5

6 Protective Relays at Risk The most important class of relays is the non-directional low set residual overcurrent relays commonly applied on shunt capacitors, power transformers, shunt reactors, and transmission lines Sture Lindahl, LTH/IEA 6

7 Shunt Capacitors International operational experience shows very clearly that low-set residual overcurrent relays for shunt capacitors with directly earthed neutral point are very vulnerable. So far, protective relays for shunt capacitors is Sweden have not maloperated during geomagnetic storms. It is recommended that the setting and the harmonic restraint of the (1) residual overcurrent and(2) neutral-point overcurrent relay are reviewed and tested. Sture Lindahl, LTH/IEA 7

8 Power Transformers Security of transformer protection There are some protective relays for power transformers that should be reviewed and tested. The candidates are: (1) the low-set residual overcurrent relay, (2) the low-set neutral-point overcurrent relay, and (3) the restricted earth-fault relay. The same holds true for similar protective relays applied on directly earthed shunt reactors. Sture Lindahl, LTH/IEA 8

9 Power Transformers Dependability of transformer protection Are the power transformers sufficiently protected in case of GIC? Power transformers and shunt reactors are in general equipped with mechanical and thermal fault detectors. These fault detectors operate independently of the instrument transformers and may keep up the dependability Sture Lindahl, LTH/IEA 9

10 Transformer Damage Sture Lindahl, LTH/IEA 10

11 and 130-kV Power Lines Operational experience shows that the lowset residual overcurrent relays are vulnerable to GICs. In 1986, all such relays on the 400- and 220- kv network were replaced by modern dependent time overcurrent relays with logarithmic characteristic and second harmonic restraint. There are, however, a number of residual over-current relays applied on power lines that have inadequate performance. Sture Lindahl, LTH/IEA 11

12 Residual Overcurrent Relays Future low-set residual overcurrent relays should preferably just measure the fundamental frequency component of the current. How to justify that the dependent time residual overcurrent relay must operate at 150 Hz? (SNDR-requirement) It should also be possible to restrain the relay not only from the second harmonic but also from other harmonics. Sture Lindahl, LTH/IEA 12

13 GIC Disturbance kV Hemsjö-Karlshamnsverket with the HVDC converter for SwePo Link 400 MW import from Poland interrupted The residual overcurrent dependent time relay operated unexpectedly. Sture Lindahl, LTH/IEA 13

14 GIC Disturbance Recordings Hemsjö RMS(Ires) RMS(3I0) Current [A] Time [ms] Sture Lindahl, LTH/IEA 14

15 GIC Disturbance Recordings Hemsjö , Harm(3I0) 1E+1 Relative Magnitude 1E+0 1E-1 1E-2 1E E-4 Fund 2nd 3rd 4th 5th 6th 7th 8th 9th Sture Lindahl, LTH/IEA 15

16 GIC Disturbance Recordings Hemsjö , Harm(Ires) 1E+1 Relative Magnitude 1E+0 1E-1 1E-2 1E E-4 Fund 2nd 3rd 4th 5th 6th 7th 8th 9th Sture Lindahl, LTH/IEA 16

17 GIC Disturbance Recordings Hemsjö (3i0) Current [A] Time [ms] Sture Lindahl, LTH/IEA 17

18 GIC Disturbance Recordings Hemsjö , ires Current [A] Time [ms] Sture Lindahl, LTH/IEA 18

19 GIC Disturbance Recordings Hemsjö , Harm(Ures) 1E+1 Relative Magnitude 1E+0 1E-1 1E-2 1E E-4 Fund 2nd 3rd 4th 5th 6th 7th 8th 9th Sture Lindahl, LTH/IEA 19

20 GIC Disturbance Recordings Hemsjö , ures Voltage [kv] Time [ms] Sture Lindahl, LTH/IEA 20

21 GIC Disturbance The relay operation is caused by the 3 rd and 6 th harmonic current and not by the fundamental frequency current The stabilising 2 nd harmonic in the residual current is very low SNDR has requested that the residual current dependent time relay must operate for the 3 rd harmonic Sture Lindahl, LTH/IEA 21

22 Three-Phase System Model (Ch 5) AC Source DC Source Transformer Load Shunt Capacitor Sture Lindahl, LTH/IEA 22

23 Magnetising Inductance Relative Incremental Magnetising Inductance 1.5 Magnetising Inductance Saturated Region Non-Saturated Region Saturated Region (Magnetising Current)/Is Sture Lindahl, LTH/IEA 23

24 Magnetising Inductance Incremental Magnetising Reactance ms= 6 ms= 10 ms= Magnetising Reactance Relative Magnetising Current Sture Lindahl, LTH/IEA 24

25 Analytical or Dynamic Simulation RMS-Value of Magnetising Current (RMS-Value)/Is (DC Current)/Is Sture Lindahl, LTH/IEA 25

26 Analytical or Dynamic Simulation Peak-Value of Magnetising Current (Peak-Value)/Is (DC Current)/Is Sture Lindahl, LTH/IEA 26

27 Analytical or Dynamic Simulation Fundamental Frequency Current 500 (Fundamental)/Is (DC Current)/Is Sture Lindahl, LTH/IEA 27

28 Analytical or Dynamic Simulation Second Harmonic Current 60 (Second Harmonic)/Is (DC Current)/Is Sture Lindahl, LTH/IEA 28

29 Analytical or Dynamic Simulation Third Harmonic Current 60 (Third Harmonic)/Is (DC Current)/Is Sture Lindahl, LTH/IEA 29

30 Analytical or Dynamic Simulation Both methods give similar results Saturating power transformers cause a reduction of the busbar voltage Saturating power transformers cause both even and odd harmonics (k=1 to 9) Higher order harmonics not accurate The analytical method gives upper limit Sture Lindahl, LTH/IEA 30

31 Busbar Voltages (Ch 7) Busbar Voltage Voltage [kv] (Direct Current per Phase)/Is Sture Lindahl, LTH/IEA 31

32 Busbar Voltages Total Harmonic Distortion 5 4 THD [%] (Direct Current per Phase)/Is Sture Lindahl, LTH/IEA 32

33 Busbar Voltages Magnitude and Phase Angle of Second Harmonic Magnitude Phase Angle Magnitude V2/V Angle [degrees] (Direct Current per Phase)/Is -180 Sture Lindahl, LTH/IEA 33

34 Busbar Voltages Magnitude and Phase Angle of Third Harmonic Magnitude Phase Angle Magnitude V3/V Angle [degrees] (Direct Current per Phase)/Is -180 Sture Lindahl, LTH/IEA 34

35 Busbar Voltages Saturating transformers cause harmonic distortion of the busbar voltages Busbar voltage drops by about 3% Total harmonic distortion is about 3% Individual harmonics is lower than 3% Sture Lindahl, LTH/IEA 35

36 GIC Disturbance Recordings Hemsjö , Harm(Ures) 1E+1 Relative Magnitude 1E+0 1E-1 1E-2 1E E-4 Fund 2nd 3rd 4th 5th 6th 7th 8th 9th Sture Lindahl, LTH/IEA 36

37 Earthed Shunt Capacitors (Ch 9) Phase Currents at 200 Mvar (Idc/Is=5.94) Phase a Phase b Phase c Current [A] Time [ms] Sture Lindahl, LTH/IEA 37

38 Earthed Shunt Capacitors Total Harmonic Distortion of the Phase Currents THD [%] (Direct Current per Phase)/Is Sture Lindahl, LTH/IEA 38

39 Earthed Shunt Capacitors Magnitude and Phase Angle of Third Harmonic Magnitude Phase Angle Magnitude I3/I Angle [degrees] (Direct Current per Phase)/Is -180 Sture Lindahl, LTH/IEA 39

40 Earthed Shunt Capacitors Magnitude and Phase Angle of 6th Harmonic Magnitude Phase Angle Magnitude I6/I Angle [degrees] (Direct Current per Phase)/Is -180 Sture Lindahl, LTH/IEA 40

41 Earthed Shunt Capacitors RMS-value of Residual Current 0.5 (Residual Current)/In (Direct Current per Phase)/Is Sture Lindahl, LTH/IEA 41

42 Earthed Shunt Capacitors Magnitude and Phase Angle of Second Harmonic Magnitude Phase Angle I2/In Angle [degrees] (Direct Current per Phase)/Is -180 Sture Lindahl, LTH/IEA 42

43 Earthed Shunt Capacitors Magnitude and Phase Angle of Third Harmonic Magnitude Phase Angle I3/In Angle [degrees] (Direct Current per Phase)/Is -180 Sture Lindahl, LTH/IEA 43

44 Earthed Shunt Capacitors Magnitude and Phase Angle of 6th Harmonic Magnitude Phase Angle I6/In Angle [degrees] (Direct Current per Phase)/Is -180 Sture Lindahl, LTH/IEA 44

45 Earthed Shunt Capacitors The fundamental frequency phase current decreases because of the busbar voltage The total harmonic distortion in the phase current is higher than 10% The 3rd harmonic of the phase current is higher than 6% of the phase current while the 6th harmonic is higher than 10% The RMS value of the residual current is about 40% while the 6 th harmonic is higher than 20%. Sture Lindahl, LTH/IEA 45

46 Current Transformers (Ch 12) I : I :1 pn sn L λ R w Lb i p i p e s i s R b Ψ s Sture Lindahl, LTH/IEA 46

47 Instrument Transformers (Ch 10) How to determine the B-H characteristic from the V-I characteristic? Sture Lindahl, LTH/IEA 47

48 Experimental Data Magnetising Curve U [V] U [V] I [ma] Sture Lindahl, LTH/IEA 48

49 Instrument Transformers RMS Characteristics of a Saturating CT Sinusoidal Current Sinusoidal Voltage 2.0 Voltage [pu] Current [pu] Sture Lindahl, LTH/IEA 49

50 Instrument Transformers It seems reasonable to use the RMS value of the magnetising current at the knee point and use that value to determine when the magnetising inductance drops from the nonsaturated value to the saturated value Sture Lindahl, LTH/IEA 50

51 Current Transformers Harmonic Content of Secondary Current Fundamental 2nd 3rd 4th 5th 6th Amplitude [A] Magnitude of Direct Current, IDC [A] Sture Lindahl, LTH/IEA 51

52 Future Work Requirements on the dependent time residual overcurrent relay for power lines and power transformers Protection for earthed shunt capacitors How to protect power transformers against GIC? Sture Lindahl, LTH/IEA 52

ANALYSIS OF THE MITIGATION METHODS OF GEOMAGNETICALLY INDUCED CURRENT

ANALYSIS OF THE MITIGATION METHODS OF GEOMAGNETICALLY INDUCED CURRENT ANALYSIS OF THE MITIGATION METHODS OF GEOMAGNETICALLY INDUCED CURRENT AnkitNimje 1, Nikhil Bhagadkar 2, Shubham Marsinge 3, Prof. C.S.Hiwarkar 4 1 Ankit Nimje, Electrical Department, K.D.K.C.E, Maharashtra,

More information

Comparative Study of Various Filtering Techniques to Reduce Harmonics in HVDC Converter Transfomer Due to GIC

Comparative Study of Various Filtering Techniques to Reduce Harmonics in HVDC Converter Transfomer Due to GIC International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn: 2278-800X, www.ijerd.com Volume 13, Issue 6 (June 2017), PP.21-25 Comparative Study of Various Filtering Techniques

More information

Grid Impact of Neutral Blocking for GIC Protection:

Grid Impact of Neutral Blocking for GIC Protection: Report submitted to EMPRIMUS - Critical Infrastructure Protection Grid Impact of Neutral Blocking for GIC Protection: Impact of neutral grounding capacitors on network resonance Prepared By: Athula Rajapakse

More information

2013 Grid of the Future Symposium. Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765 kv Power Transformer Design

2013 Grid of the Future Symposium. Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765 kv Power Transformer Design 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2013 Grid of the Future Symposium Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765

More information

High-Level Harmonic Distortion During Geomagnetic Disturbances - a Hidden Threat to Grid Security

High-Level Harmonic Distortion During Geomagnetic Disturbances - a Hidden Threat to Grid Security 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2014 Grid of the Future Symposium High-Level Harmonic Distortion During Geomagnetic Disturbances - a Hidden Threat to

More information

Pinhook 500kV Transformer Neutral CT Saturation

Pinhook 500kV Transformer Neutral CT Saturation Russell W. Patterson Tennessee Valley Authority Presented to the 9th Annual Fault and Disturbance Analysis Conference May 1-2, 26 Abstract This paper discusses the saturation of a 5kV neutral CT upon energization

More information

Interfacing Power System Simulators with Geomagnetically Induced Currents (GIC) Simulation Programs. Luis Marti Hydro One, Canada

Interfacing Power System Simulators with Geomagnetically Induced Currents (GIC) Simulation Programs. Luis Marti Hydro One, Canada 1 Interfacing Power System Simulators with Geomagnetically Induced Currents (GIC) Simulation Programs Luis Marti Hydro One, Canada 2 GMD 101 Background. What is a GMD event. Effects on the power system

More information

DISTURBANCES IN THE SOUTHERN AFRICAN POWER NETWORK DUE TO GEOMAGNETICALLY INDUCED CURRENTS

DISTURBANCES IN THE SOUTHERN AFRICAN POWER NETWORK DUE TO GEOMAGNETICALLY INDUCED CURRENTS Cigré Session, Paris, Paper 36-26 August 22 DISTURBANCES IN THE SOUTHERN AFRICAN POWER NETWORK DUE TO GEOMAGNETICALLY INDUCED CURRENTS J. Koen *, C.T. Gaunt University of Cape Town, South Africa 1. INTRODUCTION

More information

IEEE PES/IAS Joint Chapter July Technical Presentation Meeting Basics of solar phenomena & How transformers react and handle events

IEEE PES/IAS Joint Chapter July Technical Presentation Meeting Basics of solar phenomena & How transformers react and handle events Topic and abstract Geomagnetic disturbances Events associated with GMD have been known and studied in power systems since the 1960 s. Early events pre dating the AC power have been recorded to the 1850

More information

Geomagnetic Disturbances. IEEE PES Chicago Chapter Technical Presentation March 12, Alan Engelmann Transmission Planning ComEd.

Geomagnetic Disturbances. IEEE PES Chicago Chapter Technical Presentation March 12, Alan Engelmann Transmission Planning ComEd. Geomagnetic Disturbances IEEE PES Chicago Chapter Technical Presentation March 12, 2014 Alan Engelmann Transmission Planning ComEd GMD Background Solar Disturbances Impacts Monitoring Events 2 Solar Disturbances

More information

Impact of Solar Storms on the Swiss Transmission Network

Impact of Solar Storms on the Swiss Transmission Network Impact of Solar Storms on the Swiss Transmission Network Research Center for Energy Networks - ETH Zurich Giovanni Beccuti Impact of Solar Storms on the Swiss Transmission Network 1/25 Contents 1 Introduction

More information

Detecting and Managing Geomagnetically Induced Currents With Relays

Detecting and Managing Geomagnetically Induced Currents With Relays Detecting and Managing Geomagnetically Induced Currents With Relays Copyright SEL 2013 Transformer Relay Connections Voltage Current Control RTDs Transformer Protective Relay Measures differential current

More information

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection SolidGround TM GIC grid stability and harmonics mitigation

More information

FERRORESONANCE SIMULATION STUDIES USING EMTP

FERRORESONANCE SIMULATION STUDIES USING EMTP FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in

More information

MFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work

MFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work GE Grid Solutions MFAC High Impedance Differential Relay MFAC relays provide high speed differential protection for various types of power systems plants including generators, reactors, busbars, motors

More information

Digital Fault Recorder Deployment at HVDC Converter Stations

Digital Fault Recorder Deployment at HVDC Converter Stations Digital Fault Recorder Deployment at HVDC Converter Stations On line continuous monitoring at HVDC Converter Stations is an important asset in determining overall system performance and an essential diagnostic

More information

Investigation of Geomagnetic Induced Current Effects on Power Transformer

Investigation of Geomagnetic Induced Current Effects on Power Transformer International Research Journal of Engineering and Technology (IRJET) e-issn: 2395-56 Investigation of Geomagnetic Induced Current Effects on Power Transformer Roshni.R.Jethani 1, Dr.Harikumar Naidu 2,

More information

Voltage and Current Waveforms Enhancement using Harmonic Filters

Voltage and Current Waveforms Enhancement using Harmonic Filters Voltage and Current Waveforms Enhancement using Harmonic Filters Rajeb Ibsaim rabsaim@yahoo.com, Azzawia University, Libya Amer Daeri ibnjubair1@yahoo.co.uk Azzawia University, Libya Abstract The demand

More information

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at   Modeling and Analysis of Transformer ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering

More information

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System Lalit Ghatpande, SynchroGrid, College Station, Texas, 77840 Naveen Ganta, SynchroGrid, College Station, Texas,

More information

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Level 6 Graduate Diploma in Engineering Electrical Energy Systems 9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,

More information

GMD Impacts on Generators

GMD Impacts on Generators Walling Energy Systems Consulting, LLC GMD Impacts on Generators Reigh Walling 1 CME interacts with earth magnetic field Large solar flare - Coronal Mass Ejection (CME) Protons and electrons in solar wind

More information

FINNISH EXPERIENCES ON GRID EFFECTS OF GIC'S

FINNISH EXPERIENCES ON GRID EFFECTS OF GIC'S FINNISH EXPERIENCES ON GRID EFFECTS OF GIC'S ESA-SPACE WEATHER WORKSHOP The Netherlands 17. November, 2005 by J. Elovaara 1 Jarmo Elovaara Oct. 25, 2005 Content: 1. About the potential effects of GIC's

More information

Transformer Fault Categories

Transformer Fault Categories Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer

A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer IJIRST International Journal for Innovative Research in Science & Technology Volume 3 Issue 07 December 2016 ISSN (online): 2349-6010 A Novel Method to Analyse the Effects of Geomagnetic Induced Current

More information

FAQ for SIMOREG 6RA70 and Control Module

FAQ for SIMOREG 6RA70 and Control Module I DT LD CS 28 / February / 2011 FAQ for SIMOREG 6RA70 and Control Module Question: What requirements apply for line quality and what line interference can occur? Answer: Line requirements: Voltage: rated

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example

More information

HV SHUNT REACTOR SECRETS FOR PROTECTION ENGINEERS

HV SHUNT REACTOR SECRETS FOR PROTECTION ENGINEERS HV SHUNT REACTOR SECRETS FOR PROTECTION ENGINEERS By Zoran Gajić ABB Sweden Västerås, Sweden Birger Hillström ABB Sweden Västerås, Sweden Fahrudin Mekić ABB Inc. Allentown, PA 1816 Presented to: 3 th Western

More information

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd. Functional Range - Earth Fault Relay C&S Protection & Control Ltd. 2 Contents Page No. 1. Application 2. Operating Principle. Current Transformer Connections 5. Connections, Contact Arrangement and Setting

More information

Content. 1. Dimensiong of CT s. 2. Error definitions. 3. General design aspects. 4. Linear cores. Certified acc. to ISO 9001/14001, SN EN 45001

Content. 1. Dimensiong of CT s. 2. Error definitions. 3. General design aspects. 4. Linear cores. Certified acc. to ISO 9001/14001, SN EN 45001 Content 1. Dimensiong of CT s 2. Error definitions 3. General design aspects 4. Linear cores Certified acc. to ISO 9001/14001, SN EN 45001 Dimensioning of CT s N P x I P = N S x I S N S = ( I P x N P )

More information

Dietrich Bonmann, ABB AG Bad Honnef, March 15, Impact of GIC on transformers and the transmission network

Dietrich Bonmann, ABB AG Bad Honnef, March 15, Impact of GIC on transformers and the transmission network Dietrich Bonmann, ABB AG Bad Honnef, March 15, 2016 Impact of GIC on transformers and the transmission network Impact of GIC on transformers and the transmission network : From GIC to black-out Main network

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 5th October 2010 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT

More information

BUS2000 Busbar Differential Protection System

BUS2000 Busbar Differential Protection System BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection 1 Typical Busbar Arrangements Single Busbar Double Busbar with Coupler Breaker and a Half

More information

Effects of GIC on Power Transformers and Power Systems

Effects of GIC on Power Transformers and Power Systems Effects of GIC on Power Transformers and Power Systems Prepared by Dr. Ramsis Girgis and Kiran Vedante (USA) in the name of CIGRE SC A2 Background There has been some misconception in the electric power

More information

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic

More information

Protective Relaying of Power Systems Using Mathematical Morphology

Protective Relaying of Power Systems Using Mathematical Morphology Q.H. Wu Z. Lu T.Y. Ji Protective Relaying of Power Systems Using Mathematical Morphology Springer List of Figures List of Tables xiii xxi 1 Introduction 1 1.1 Introduction and Definitions 1 1.2 Historical

More information

The Engineering Problem. Calculating GIC Flow through the EHV System

The Engineering Problem. Calculating GIC Flow through the EHV System The Engineering Problem Calculating GIC Flow through the EHV System 1 Creating the GIC System Model Since the EHV system is a three-phase balanced network, it is only necessary to model a single-phase

More information

Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602

Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602 Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602 1 / 12 1 INTRODUCTION This document provides guidelines for the performance calculations required for high impedance differential

More information

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium Assessment of the Impact of GMD on the TVA 500 kv Grid & Power Transformers Part II:

More information

Hydro One GMD Preparedness Plan for Cycle 24

Hydro One GMD Preparedness Plan for Cycle 24 Hydro One GMD Preparedness Plan for Cycle 24 Presented to: Critical Infrastructure Protection and Space Weather Workshop March 28-29, 2012, Ottawa, Ontario, Canada L. Marti Hydro One Networks Inc. 483

More information

GIC Analysis using PSS E. K.V. PATIL Siemens Power Technologies International Schenectady, New York, USA

GIC Analysis using PSS E. K.V. PATIL Siemens Power Technologies International Schenectady, New York, USA CIGRÉ-697 2015 CIGRÉ Canada Conference 21, rue d Artois, F-75008 PARIS http : //www.cigre.org Winnipeg, Manitoba, August 31-September 2, 2015 GIC Analysis using PSS E K.V. PATIL Siemens Power Technologies

More information

22.0 Harmonics in Industrial Power Systems

22.0 Harmonics in Industrial Power Systems 1.0 Harmonics in Industrial Power Systems Harmonic frequencies are multiples of the line (fundamental) frequency, which in North America is usually 60 Hz, while it is 50 Hz elsewhere. Figure 1 shows a

More information

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum International Journal of Scientific & Engineering Research, Volume 7, Issue 4, April-216 628 REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD Abhilash.G.R Smitha K.S Vocational Teacher

More information

2015 Relay School Bus Protection Mike Kockott March, 2015

2015 Relay School Bus Protection Mike Kockott March, 2015 2015 Relay School Bus Protection Mike Kockott March, 2015 History of Bus Protection Circulating current differential (1900s) High impedance differential (1940s) Percentage restrained differential (1960s)

More information

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power

More information

GMD Voltage Collapse Study

GMD Voltage Collapse Study GMD Voltage Collapse Study Terry Volkmann 2016 Fall Reliability Conference November 2, 2016 1 GMD Voltage Collapse Studies in Wisconsin and Maine Overview: Modeling shows GMD Voltage Collapse Issues: Power

More information

Modeling and Evaluation of Geomagnetic Storms in the Electric Power System

Modeling and Evaluation of Geomagnetic Storms in the Electric Power System 21, rue d Artois, F-75008 PARIS C4-306 CIGRE 2014 http : //www.cigre.org Modeling and Evaluation of Geomagnetic Storms in the Electric Power System K. PATIL Siemens Power Technologies International, Siemens

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

GIC Distribution. Carlos David Fernández Barroso. Division of Industrial Electrical Engineering and Automation Faculty of Engineering, Lund University

GIC Distribution. Carlos David Fernández Barroso. Division of Industrial Electrical Engineering and Automation Faculty of Engineering, Lund University CODEN:LUTEDX/(TEIE-5328)/1-062/(2014) GIC Distribution Carlos David Fernández Barroso Division of Industrial Electrical Engineering and Automation Faculty of Engineering, Lund University Table of contents

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

Conventional Paper-II-2013

Conventional Paper-II-2013 1. All parts carry equal marks Conventional Paper-II-013 (a) (d) A 0V DC shunt motor takes 0A at full load running at 500 rpm. The armature resistance is 0.4Ω and shunt field resistance of 176Ω. The machine

More information

Analysis of a 405 km transmission line with series compensation

Analysis of a 405 km transmission line with series compensation Analysis of a 405 km transmission line with series compensation by Dr. Rupert Gouws, North-West University This paper presents an investigative case study and energy efficiency analysis of the 405 km,

More information

Conventional Paper-II-2011 Part-1A

Conventional Paper-II-2011 Part-1A Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance

More information

An Introduction to Power Quality

An Introduction to Power Quality 1 An Introduction to Power Quality Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments during the presentation 3 Today s Presenter n Andy Sagl Megger

More information

Harmonic resonances due to transmission-system cables

Harmonic resonances due to transmission-system cables International Conference on Renewable Energies and Power Quality (ICREPQ 14) Cordoba (Spain), 8 th to 1 th April, 214 Renewable Energy and Power Quality Journal (RE&PQJ) ISSN 2172-38 X, No.12, April 214

More information

Burdens & Current Transformer Requirements of MiCOM Relays. Application Notes B&CT/EN AP/B11. www. ElectricalPartManuals. com

Burdens & Current Transformer Requirements of MiCOM Relays. Application Notes B&CT/EN AP/B11. www. ElectricalPartManuals. com Burdens & Current Transformer Requirements of MiCOM Relays Application Notes B&CT/EN AP/B11 Application Notes B&CT/EN AP/B11 Burdens & CT Req. of MiCOM Relays Page 1/46 CONTENTS 1. ABBREVIATIONS & SYMBOLS

More information

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:

More information

concerning the risks to the electric power grid from geomagnetic storms,

concerning the risks to the electric power grid from geomagnetic storms, Description of document: Requested date: Released date: Posted date: Source of document: Idaho Public Utilities Commission (PUC) records concerning the risks to the electric power grid from geomagnetic

More information

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections

More information

p. 1 p. 6 p. 22 p. 46 p. 58

p. 1 p. 6 p. 22 p. 46 p. 58 Comparing power factor and displacement power factor corrections based on IEEE Std. 18-2002 Harmonic problems produced from the use of adjustable speed drives in industrial plants : case study Theory for

More information

Mitigation of an Inrush Current of Power Transformer by using PWM-Inverter based Series Voltage Compensator

Mitigation of an Inrush Current of Power Transformer by using PWM-Inverter based Series Voltage Compensator Mitigation of an Inrush Current of Power Transformer by using PWM-Inverter based Series Voltage Compensator Apurva Kulkarni, Priyadarshani engg college,nagpur apookul@gmailcom Vinesh Choudhari, Faculty

More information

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8] Code No: RR320205 Set No. 1 1. (a) Explain about Bewley s Lattice diagrams and also mention the uses of these diagrams. [6+2] (b) A line of surge impedance of 400 ohms is charged from a battery of constant

More information

Evaluating Transformer Heating due to Geomagnetic Disturbances

Evaluating Transformer Heating due to Geomagnetic Disturbances Evaluating Transformer Heating due to Geomagnetic Disturbances Presented by: Brian Penny, American Transmission Company 53 rd Annual Minnesota Power Systems Conference November 7, 2017 atcllc.com Presentation

More information

Vulnerability Assessment and Planning

Vulnerability Assessment and Planning Vulnerability Assessment and Planning Project 2013-03 (GMD Mitigation) Standard Drafting Team GMD Task Force In-person meeting March 18-19, 2014 Topics Application of the Benchmark GMD Event in System

More information

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) PATTI.RANADHEER Assistant Professor, E.E.E., PACE Institute

More information

Type MCAG 14, 34 T&D. High Stability Circulating Current Relay

Type MCAG 14, 34 T&D. High Stability Circulating Current Relay PROTETION Type MAG, 3 High Stability irculating urrent Relay The MAG relay, used with a stabilising resistor, is designed for applications where sensitive settings with stability on heavy through faults

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

Consolidated Edison s Experience with On-line Monitoring and Mitigation of Geomagnetic Disturbances

Consolidated Edison s Experience with On-line Monitoring and Mitigation of Geomagnetic Disturbances Consolidated Edison s Experience with On-line Monitoring and Mitigation of Geomagnetic Disturbances Gary R. Hoffman, Advanced Power Technologies Sam Sambasivan, Consolidated Edison Vincenzo Panuccio, Consolidated

More information

Transformer Protection

Transformer Protection Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary

More information

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Jules Esztergalyos, Senior Member, IEEE Abstract--The measuring technique described in this paper is based on Electro Magnetic

More information

The power transformer

The power transformer ELEC0014 - Introduction to power and energy systems The power transformer Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 35 Power transformers are used: to transmit

More information

Long lasting transients in power filter circuits

Long lasting transients in power filter circuits Computer Applications in Electrical Engineering Vol. 12 2014 Long lasting transients in power filter circuits Jurij Warecki, Michał Gajdzica AGH University of Science and Technology 30-059 Kraków, Al.

More information

Unit Protection Differential Relays

Unit Protection Differential Relays Unit Protection PROF. SHAHRAM MONTASER KOUHSARI Current, pu Current, pu Protection Relays - BASICS Note on CT polarity dots Through-current: must not operate Internal fault: must operate The CT currents

More information

In Class Examples (ICE)

In Class Examples (ICE) In Class Examples (ICE) 1 1. A 3φ 765kV, 60Hz, 300km, completely transposed line has the following positive-sequence impedance and admittance: z = 0.0165 + j0.3306 = 0.3310 87.14 o Ω/km y = j4.67 410-6

More information

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected

More information

Keywords: Transformer modeling, saturation, hysteresis, MATLAB. Introduction

Keywords: Transformer modeling, saturation, hysteresis, MATLAB. Introduction Modeling and analysis of 100 KVA distribution transformer including the core saturation effect Neelam Choudhary 1, Ranjana Nigam Singh 2 1,2 Electrical Engineering department, Jabalpur Engineering College,

More information

Impact of Incipient Faults on Sensitive Protection

Impact of Incipient Faults on Sensitive Protection Impact of Incipient Faults on Sensitive Protection Paper Authors: Ilia Voloh GE Grid Solutions Zhihan Xu, Ilia Voloh GE Grid Solutions Leonardo Torelli CSE-Uniserve Presented by: Tom Ernst GE Grid Solutions

More information

IMPACT OF INRUSH CURRENTS AND GEOMAGNETICALLY INDUCED CURRENTS ON TRANSFORMER BEHAVIOR

IMPACT OF INRUSH CURRENTS AND GEOMAGNETICALLY INDUCED CURRENTS ON TRANSFORMER BEHAVIOR Michigan Technological University Digital Commons @ Michigan Tech Dissertations, Master's Theses and Master's Reports 2018 IMPACT OF INRUSH CURRENTS AND GEOMAGNETICALLY INDUCED CURRENTS ON TRANSFORMER

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

3 Pole high impedance differential relay 7VH83

3 Pole high impedance differential relay 7VH83 Fig 1. High impedance differential protection relay 7VH83 Features l Integral CT shorting relay. l Robust solid state design. l Inrush stabilisation through filtering. l Fast operating time. l LED indicator.

More information

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax: POWER CORPORATION Power Quality Specifications and Guidelines for Customers Phone: 403-514-3700 Fax: 403-514-3719 1 GENERAL OVERVIEW........................................ 1.1 WHAT DOES THIS SPECIFICATION

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering) R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between

More information

Relaying 101. by: Tom Ernst GE Grid Solutions

Relaying 101. by: Tom Ernst GE Grid Solutions Relaying 101 by: Tom Ernst GE Grid Solutions Thomas.ernst@ge.com Relaying 101 The abridged edition Too Much to Cover Power system theory review Phasor domain representation of sinusoidal waveforms 1-phase

More information

Outdoor Instrument Transformers. Application Guide

Outdoor Instrument Transformers. Application Guide Outdoor Instrument Transformers Application Guide Introduction Edited by Knut Sjövall, knut.sjovall@se.abb.com ABB Power Technologies AB Department: PTHV/HV/MT SE-771 80 LUDVIKA, Sweden 2 1HSE 9543 40-00en

More information

A Revolution in. Transformer EQUIVALENT CIRCUIT DIAGRAM OF A REAL CURRENT TRANSFORMER 1. by Benton Vandiver, Omicron

A Revolution in. Transformer EQUIVALENT CIRCUIT DIAGRAM OF A REAL CURRENT TRANSFORMER 1. by Benton Vandiver, Omicron by Benton Vandiver, Omicron A Revolution in D ifferent test devices and methods are used in the market to verify the performance of current transformers during development, production, installation and

More information

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India

More information

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM BY MR. H. C. MEHTA AT 1 ST INDIA DOBLE PROTECTION AND AUTOMATION CONFERENCE, NOV 2008 POWER-LINKER Wisdom is not Virtue but Necessity hcmehta@powerlinker.org

More information

Substation applications

Substation applications Substation applications To make it easy to choose the right for a protection application, the most typical applications are presented with the type of for them. Each sample application is presented by:

More information

Making VSC-HVDC Control Robust to Geomagnetically Induced Current

Making VSC-HVDC Control Robust to Geomagnetically Induced Current Making VSC-HVDC Control Robust to Geomagnetically Induced Current Siyu Gao Elia Grid International, Brussels, Belgium Mike Barnes University of Manchester, Manchester, UK Mike.barnes@manchester.ac.uk Abstract

More information

Innovative Science and Technology Publications

Innovative Science and Technology Publications Innovative Science and Technology Publications Manuscript Title SATURATION ANALYSIS ON CURRENT TRANSFORMER Thilepa R 1, Yogaraj J 2, Vinoth kumar C S 3, Santhosh P K 4, 1 Department of Electrical and Electronics

More information

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection) Differential Protection (Unit protection) Differential Protection Differential protection is the best technique in protection. In this type of protection the electrical quantities entering and leaving

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

Geo-Magnetic Disturbance Analysis of HV and EHV Grids

Geo-Magnetic Disturbance Analysis of HV and EHV Grids Engineering Conferences International ECI Digital Archives Modeling, Simulation, And Optimization for the 21st Century Electric Power Grid Proceedings Fall 10-22-2012 Geo-Magnetic Disturbance Analysis

More information

SPACE WEATHER, VOL. 3, S08C03, doi: /2004sw000123, 2005

SPACE WEATHER, VOL. 3, S08C03, doi: /2004sw000123, 2005 Geomagnetic storm of 29--31 October 2003: Geomagnetically induced currents and their relation to problems in the Swedish high-voltage power transmission system Antti Pulkkinen NASA Goddard Space Flight

More information

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC CITY OF LETHBRIDGE ELECTRIC ENGINEERING STANDARDS POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS The City of Lethbridge acknowledges the use of other utility industry and industry committee

More information

Catastrophic Relay Misoperations and Successful Relay Operation

Catastrophic Relay Misoperations and Successful Relay Operation Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations

More information

2C73 Setting Guide. High Impedance Differential Relay. relay monitoring systems pty ltd Advanced Protection Devices

2C73 Setting Guide. High Impedance Differential Relay. relay monitoring systems pty ltd Advanced Protection Devices 2C73 Setting Guide High Impedance Differential Relay relay monitoring systems pty ltd Advanced Protection Devices 1. INTRODUCTION This document provides guidelines for the performance calculations required

More information