A Revolution in. Transformer EQUIVALENT CIRCUIT DIAGRAM OF A REAL CURRENT TRANSFORMER 1. by Benton Vandiver, Omicron
|
|
- Cleopatra Short
- 6 years ago
- Views:
Transcription
1 by Benton Vandiver, Omicron A Revolution in D ifferent test devices and methods are used in the market to verify the performance of current transformers during development, production, installation and maintenance. An innovative solution exists to test current transformers at all life cycle stages by using the modeling concept. Current transformers are used in electrical power systems for relaying and metering purposes. Depending on the application they are used for, the current transformers are designed differently. Transformer Testing Applications Areas The current transformers for metering and protection applications basically work the same way: translating highpower primary signals to secondary readable values. While current transformers used for protection applications operate to well above the nominal current, however, the current transformers for metering purposes must go into saturation directly above the nominal current level to protect the connected metering equipment. Protection current transformers. Current transformers EQUIVALENT CIRCUIT DIAGRAM OF A REAL CURRENT TRANSFORMER 1 P1 lp P2 Np : Ns lxm Xm le lrm Rm EMF S1 ls Rb Us Xb S2 le ls lp Xm Rm Np, Ns Rct EMF Us Rb Xb Excitation current Secondary current Primary current Main inductivity of the core Magnetic losses of the core Amount of turns of the ideal core Ohmic resistance of secondary turns Electro-Motive Force secondary core voltage Secondary terminal voltage Ohmic part of complex burden Inductive part of complex burden
2
3 CONNECTION EXAMPLE FOR A 6-TAP CURRENT TRANSFORMER 2 CTA PC X6 X5 X4 X3 X2 X1 play an important role in the protection of electrical power systems. They provide the protection relay with a ratio of the primary current so it can operate according to its settings. The transformation of the current values from primary to secondary must be accurate during normal and especially during fault conditions on the primary side (when currents up to 30 times the nominal current are not an exception). Metering current transformers. Energy is supplied by many sources, including alternative energy sources such as solar and wind power. To guarantee accurate billing in this competitive electricity market, additional metering points are necessary. It is important to have the entire metering chain calibrated because the meter is only as accurate as the instrument transformers sourcing it. This makes the testing and calibration of current transformers up to the 0.1 accuracy class essential. However, on-site testing of CTs of the 0.1 accuracy class is particularly critical because disturbances from power lines can influence measurement results. signals on the secondary side can be measured and analyzed. This method, however, is time-consuming and material-intensive. Sometimes it is not even feasible because very high currents are required (e.g., for on-site testing of current transformers designed for transient behavior (TP types) as they have very high knee-points values). 2. Another common testing scenario for current transformers is injecting a defined testing voltage on the secondary side and reading signals on the primary side. Unfortunately, using this scenario, some parameters such as accuracy and knee point (excitation curve) can be tested only with limitations. This is because of the scenario s restrictions in accuracy caused by the very low signals in use and the maximum voltage of approximately 2 kv, which can be applied to the secondary side of current transformers. Other important parameters such as the transient dimensioning factor, the accuracy limit factor, the safety factor, composite errors, time constancies and many others cannot be tested at all. Because both methods have limitations, a new method of testing CTs was needed. CT Analyzer With CT SB2 Attached 3 Testing of current transformers Conventional testing methods apply a signal on one side and read the output signal on the other side. Several ways of conventional testing are possible. 1. The traditional way of testing a current transformer is to apply a high current to the primary side and read the signals on the secondary side. By using different burdens or injecting over-currents, situations can be simulated and the New Modeling Concept Omicron developed the CT Analyzer test device. The concept of modeling a current transformer allows for a detailed view of the transformer s design and its physical behavior. The test device builds a model of the current transformer automatically by using nameplate data and data measured
4 HYSTERESIS CURVE AT MAXIMUM SATURATION POINT SHOWING THE POSSIBLE AREA FOR RESIDUAL MAGNETISM Flux Density (B) Ψ r-max Ψ r-max Field Strength (H) during the test. Based on this model, the test device can calculate additional parameters such as the Vb (secondary terminal voltage acc. IEEE) or the accuracy limiting factor (ALF) and the safety factor (FS acc. to IEC) and simulate the CT s behavior, for example, under different burdens or with various primary currents. Since its introduction in 2005, the analyzer has gained acceptance with more than 1,000 units operating in every corner of the globe, including the U.S. and Canada. The analyzer is small, lightweight and conducts fully automated tests of current transformers within the shortest times possible. It measures the current transformer s copper and iron losses according to its equivalent circuit diagram (see Figure 1). While copper losses are described as the winding resistance R CT, iron losses are described as the eddy losses or eddy resistance R eddy, and hysteresis losses as hysteresis resistance R H. With this detailed information about the core s total losses, the analyzer can model the current transformer and calculate the current ratio error, as well as the phase displacement for any primary current and secondary burden. All operating points described in the relevant international standards for current transformers can be determined. The model also allows important parameters such as the residual magnetism, the saturated and unsaturated inductance, the symmetrical short-current factor (over-current factor) and the transient dimensioning factor (according to the IEC standard for transient fault current calculations) to be assessed. With all of the relevant modeling data known, it can be used directly in power system simulation programs to give that CT or group of CTs actual response to modeled system conditions. 4 This provides the power system engineer with improved fault simulations, making performance testing and trouble shooting of protection systems much more accurate. Within seconds a test report, including an automatic assessment according to IEEE C57.13 or C (Standard for High Accuracy Instrument Transformers), is generated. The analyzer offers a very high testing accuracy of 0.05 percent (0.02 percent typical) for current ratio and 3 minutes (1 minute typical) for phase displacement. The accuracy of the analyzer is verified by several metrological institutes including the PTB in Germany, KEMA in the Netherlands and the Wuhan HV Research Institute in China. (Traceability is to national standards administered by EURAMET and ILAC members (e.g. ÖKD, DKD, NIST, NATA, NPL, PTB, BNM etc.) Innovations For automated testing of multiratio CTs with up to six tap connections (X1 to X6), the analyzer was improved with the addition of the CT SB2 Switch-Box as an accessory. The CT l DEMAGNETIZATION PRINCIPLE OF IRON CORES B H Demagnetization t 5
5 SB2 is connected to all taps of a multiratio CT, as well as to the analyzer (see Figure 2). Every ratio combination can be tested automatically without the need for rewiring. An integrated connection check feature tests the secondary connection to the CT and indicates wiring mistakes before the measurement cycle begins. In addition, the analyzer checks the different ratios of the current transformer under test. The testing signal will then be adjusted to limit test voltages below 200 V, ensuring a high level of worker safety during the operation. The SB2 can be attached to the back of the analyzer (see Figure 3) with all wiring connections made. As a new measurement option for the analyzer, RemAlyzer allows current transformers to be tested for residual magnetism after a system fault or local event where core saturation is suspected. Residual magnetism might occur if a current transformer is driven into saturation. This can happen as a consequence of high fault currents containing transient components or direct currents applied to the current transformer during winding resistance tests or during a polarity check (wiring check). Depending on the level of remaining flux density, residual magnetism dramatically influences the response characteristic of a current transformer (see Figure 4). Because remanence effects in protective current transformers are not predictable and barely recognizable during normal operation, these effects are even more critical. Unwanted operation of the differential protection may be caused. Protective relays also might show a failure to operate in case of real over-current as the current transformer s signal is distorted because of the residual magnetism in the CT core. Once the current transformer is magnetized, a demagnetization process is necessary to remove residual magnetism. This can be achieved, for example, by applying an AC current with similar strength as the current which caused the remanence. In a second step, the current transformer is demagnetized by reducing the voltage gradually to zero (see Figures 5 and 6). The analyzer performs the residual magnetism measurements prior to the usual CT testing cycle as it automatically removes residual magnetism after testing. To determine the residual magnetism, the analyzer drives the core into positive and negative saturation alternately until a stable symmetric hysteresis loop is reached. The analyzer then calculates the initial remanence condition to determine whether the core was affected by residual TEST CARD OF CT ANALYZER SHOWING MEASUREMENT RESULTS OF A RESIDUAL MAGNETISM TEST CT-0 Res. Magnetism Resist Excita I-sn: 1.0A Residual Flux: 6.750mVs Residual Magnetism: 3% Remanence Factor Kr: 90% Ready Main magnetism. The results are displayed as absolute values in voltage per second, as well as in percent relative to the saturation flux (Ψs: defined in the IEC ) on the residual magnetism test card. In addition, the remanence factor Kr is shown on the test card (see Figure 7). The analyzer automatically demagnetizes the current transformer when the test is complete. Conclusion After installation, current transformers are typically used for 30 years. To guarantee a reliable and safe operation over the life of the CTs, a high level of quality during design phase, manufacturing process and installation is essential. Several quality tests are performed from development to installation. After installation, CTs should be tested regularly to ensure correct functioning over the entire life. Benton Vandiver III is technical director at Omicron electronics and has more than 32 years experience in power systems protection. He is a registered professional engineer in Texas and a member of IEEE/PES/SPRC, IEEE-SA and USNC/CIGRE. Benton holds a U.S. patent for Communication-based Testing of IEDs and has authored or co-authored more than 80 technical papers and articles in the U.S. and internationally. Reprinted with revisions to format, from the August 2012 edition of PowerGrid International Copyright 2012 by PennWell Corporation 6
6 My dad tests multi ratio CT s...and with the CT Analyzer and the new CT SB2 it s all automated! The new CT SB2 Switch Box has been designed for OMICRON s CT Analyzer to enable automated testing of multiratio CTs with up to 6 taps. Dad especially likes the wiring check to ensure that the correct taps are connected. The accuracy of the Contact us for an on-site demo! CT Analyzer allows Dad to test even metering class CTs up to 0.15 class that s pretty impressive. My Dad is even able to attach the CT SB2 to the CT Analyzer. With a combined weight of only 24 lbs, the CT Analyzer together with the CT SB2 Switch Box is the most lightweight and automated testing solution for multi-ratio protection or metering class CTs. Come and check it out for yourself on the OMICRON Roadshow Bus or contact us for an on-site demo! OMICRON
CT Analyzer. Revolution in current transformer testing and calibration
CT Analyzer Revolution in current transformer testing and calibration Revolutionary way of CT testing Current transformers are used for relaying and metering purposes in electrical power systems. They
More informationAdvanced Test Equipment Rentals ATEC (2832)
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CT Analyzer Revolution in Current Transformer Testing and Calibration Revolutionary Way of CT Testing Current transformers
More informationCT Analyzer. Current transformer testing, calibration and assessment
CT Analyzer Current transformer testing, calibration and assessment Analyze your current transformer (CT) with the push of a button How CT Analyzer works > > Injects low test signals into secondary side
More informationEUROPE S LARGEST SELECTION OF TEST & MEASUREMENT EQUIPMENT FOR HIRE INLEC.COM. Nationwide Low Call
EUROPE S LARGEST SELECTION OF TEST & MEASUREMENT EQUIPMENT FOR HIRE INLEC.COM Nationwide Low Call 0333 6000 600 WHY BUY WHEN YOU CAN HIRE CT Analyzer Revolution in Current Transformer Testing and Calibration
More informationCT Analyzer. Test Set for Analysis of Metering Current Transformers According to IEEE C57.13 Standard
CT Analyzer Test Set for Analysis of Metering Current Transformers According to IEEE C57.13 Standard The New Standard in Metering CT Testing In today s competitive electricity market, it is important to
More informationPCT200 SERIES CT/PT TEST SYSTEM USER MANUAL
PONOVO POWER CO., LTD 2F, 4Cell, Tower C, In.Do Mansion No.48A Zhichun Road, Haidian District Beijing, China (Post Code 100098) TEL. +86 (10) 82755151 ext. 8887 Office FAX +86 (10) 82755257 E-Mail Info@ponovo.com.cn
More informationAlternative Testing Techniques for Current Transformers. Dinesh Chhajer, PE Technical Support Group MEGGER
Alternative Testing Techniques for Current Transformers Dinesh Chhajer, PE Technical Support Group MEGGER Agenda Current Transformer Definition and Fundamentals Current Transformer Applications o Metering
More informationImpact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis
1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current
More informationMVCT. Megger VT & CT Analyzer. MVCT Megger VT & CT Analyzer
MVCT Ability to test both VT and CT Easy to use one-button automated test plans Industry leading test duration using patented simultaneous tap measurements Smallest and lightest unit on the market CT Kneepoints
More informationHYVA404 CTPT Analyzer instruction manual (V1.3.19) CT/PT Analyzer. User Manual (V1.3.19)
CT/PT Analyzer User Manual (V1.3.19) Content Warning...3 1 Application and Technical Index of CT/PT Analyzer... 4 1.1 Application... 4 1.2 CT Technical Index... 4 2 Hardware... 6 2.1 Introduction... 6
More informationPCT200 Series User Manual
PONOVO POWER CO., LTD No. 139 Jinghai Third Road, BDA, Beijing, China, 100176 Office TEL. +86 (10) 59089666 E-Mail Website Info@relaytest.com www.relaytest.com / www.ponovo.com.cn PCT200 Series User Manual
More informationContent. 1. Dimensiong of CT s. 2. Error definitions. 3. General design aspects. 4. Linear cores. Certified acc. to ISO 9001/14001, SN EN 45001
Content 1. Dimensiong of CT s 2. Error definitions 3. General design aspects 4. Linear cores Certified acc. to ISO 9001/14001, SN EN 45001 Dimensioning of CT s N P x I P = N S x I S N S = ( I P x N P )
More informationBurdens & Current Transformer Requirements of MiCOM Relays. Application Notes B&CT/EN AP/B11. www. ElectricalPartManuals. com
Burdens & Current Transformer Requirements of MiCOM Relays Application Notes B&CT/EN AP/B11 Application Notes B&CT/EN AP/B11 Burdens & CT Req. of MiCOM Relays Page 1/46 CONTENTS 1. ABBREVIATIONS & SYMBOLS
More informationOutdoor Instrument Transformers. Application Guide
Outdoor Instrument Transformers Application Guide Introduction Edited by Knut Sjövall, knut.sjovall@se.abb.com ABB Power Technologies AB Department: PTHV/HV/MT SE-771 80 LUDVIKA, Sweden 2 1HSE 9543 40-00en
More informationDiagnostic measurements on instrument transformers
Diagnostic measurements on instrument transformers A classification and overview of diagnostic measurements ABSTRACT The article presents the most common diagnostic measurements on instrument transformers
More informationBack to the Basics Current Transformer (CT) Testing
Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of
More informationCT Analyzer instruction manual (V1.0.5)
Warning... 3 1 Application and technical index of CT analyzer... 4 1.1 Application... 4 1.2 CT Technical index... 4 2 Hardware... 6 2.1 Introduction... 6 2.2 Power supply... 6 2.3 Test connection terminals...
More informationBeyond the Knee Point: A Practical Guide to CT Saturation
Beyond the Knee Point: A Practical Guide to CT Saturation Ariana Hargrave, Michael J. Thompson, and Brad Heilman, Schweitzer Engineering Laboratories, Inc. Abstract Current transformer (CT) saturation,
More informationTap Changer Analyzer & Winding Ohmmeter RMO60TD
Tap Changer Analyzer & Winding Ohmmeter RMO60TD Test current 5 ma 60 A DC Rapid automatic demagnetization AC Current monitoring channel Lightweight 13 kg Measuring range 0,1-2 k Two voltage sense channels
More informationTap Changer Analyzer & Winding Ohmmeter RMO25TD
Tap Changer Analyzer & Winding Ohmmeter RMO25TD Test current 5 ma 25 A DC Rapid automatic demagnetization AC Current monitoring channel Lightweight 9,5 kg Measuring range 0,1-2 k Two voltage sense channels
More informationACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH
ACCURACY OF VOLTAGE TRANSFORMERS DESIGN CRITERIA AND A SURVEY ON THE PRECISION AND REPRODUCIBILITY OF A NEW MODEL-BASED CALIBRATION APPROACH Michael Freiburg Erik Sperling Michael Krueger OMICRON Austria
More informationTap Changer Analyzer & Winding Ohmmeter RMO60TD
Tap Changer Analyzer & Winding Ohmmeter RMO60TD Test current 5 ma 60 A DC Rapid automatic demagnetization AC Current monitoring channel Lightweight 13 kg Measuring range 0,1-2 k Two voltage sense channels
More informationAdvanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) CP RC Resonance circuit for GIS testing A new approach to testing gas-insulated switchgear Testing gas-insulated switchgear
More informationVOLTECHNOTES. Transformer Basics VPN /1
Transformer Basics VPN 104-039/1 TRANSFORMER BASICS Introduction Transformer design and test are sometimes viewed as an art rather than a science. Transformers are imperfect devices, and there will be
More informationWinding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer
Winding Ohmmeter & Tap Changer Test Set RMO40TD with Demagnetizer Lightweight 9,5 kg Test current 5 ma 40 A DC Measuring range 0,1-2 k Two voltage sense channels Extremely quick measurement Rapid automatic
More informationThree-Phase Transformer Demagnetizer DEM60
Three-Phase Transformer Demagnetizer DEM60 Fully automatic demagnetization Demagnetization currents 5 ma 60 A DC Automatic discharging circuit Lightweight 13,1 kg High DC Current Source for Automatic Transformers
More informationIn-circuit Measurements of Inductors and Transformers in Switch Mode Power Supplies APPLICATION NOTE
In-circuit Measurements of Inductors and Transformers in Switch Mode Power Supplies FIGURE 1. Inductors and transformers serve key roles in switch mode power supplies, including filters, step-up/step-down,
More informationSTRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS
1 STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS Z. GAJIĆ S. HOLST D. BONMANN D. BAARS ABB AB, SA Products ABB AB, SA Products ABB AG, Transformers ELEQ bv Sweden Sweden Germany Netherlands zoran.gajic@se.abb.com
More informationTable of Contents. Table of Figures. Table of Tables
Abstract The aim of this report is to investigate and test a transformer and check if it is good to use by doing the following tests continuity test, insulation test, polarity test, open circuit test,
More informationVOLTECHNOTES. Turns Ratio iss 4 Page 1 of 7
VOLTECHNOTES Turns Ratio 104-113 iss 4 Page 1 of 7 Introduction Transformers are used in a wide array of electrical or electronic applications, providing functions that range from isolation and stepping
More informationTRAX Transformer and Substation Test System
TRAX Replaces need for multiple test sets Saves time by eliminating need for multiple instruments learning User-friendly interface reduces training and testing time Portable and compact system components
More informationOutcomes from this session
Outcomes from this session At the end of this session you should be able to Understand what is meant by the term losses. Iron Losses There are three types of iron losses Eddy current losses Hysteresis
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities
More informationMATHEMATICAL MODELING OF POWER TRANSFORMERS
MATHEMATICAL MODELING OF POWER TRANSFORMERS Mostafa S. NOAH Adel A. SHALTOUT Shaker Consultancy Group, Cairo University, Egypt Cairo, +545, mostafanoah88@gmail.com Abstract Single-phase and three-phase
More informationTRAX Transformer and Substation Test System
TRAX Replaces need for multiple test sets Saves time by eliminating need for multiple instruments learning User-friendly interface reduces training and testing time Portable and compact system components
More informationAMH-DC-TB-S SOFT MAGNETIC MATERIALS: RINGS, BARS, STRIPS
LABORATORIO ELETTROFISICO AMH-DC-TB-S SOFT MAGNETIC MATERIALS: RINGS, BARS, STRIPS AMH-DC-TB-S Permeameter AMH-DC-TB-S Permeameter is a variation of the model AMH-DC-T-S Permeameter and provides additional
More informationTRAX Transformer and Substation Test System
Replaces need for multiple test sets Saves time by eliminating need for multiple instruments learning User-friendly interface reduces training and testing time Portable and compact system components for
More informationCurrent Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...
TECHNICAL REPORT APPLICATION GUIDE TITLE: Current Transformer Requirements for VA TECH Reyrolle ACP Relays PREPARED BY:- A Allen... APPROVED :- B Watson... REPORT NO:- 990/TIR/005/02 DATE :- 24 Jan 2000
More informationProfessional Provider of Power Testing Instrument PCT200 Series CT/PT Test System
Professional Provider of Power Testing Instrument PCT200 Series CT/PT Test System TP YCT Bushing type CT PT Bushing Type CT M type CT GIS CT PT PONOO POWER CO., LTD. No.139 Jinghai Third Road, BD, Beijing,
More informationDemagnetization of Power Transformers Following a DC Resistance Testing
Demagnetization of Power Transformers Following a DC Resistance Testing Dr.ing. Raka Levi DV Power, Sweden Abstract This paper discusses several methods for removal of remanent magnetism from power transformers.
More informationApplication Guide High Impedance Differential Protection Using SIEMENS 7SJ602
Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602 1 / 12 1 INTRODUCTION This document provides guidelines for the performance calculations required for high impedance differential
More informationShortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller
Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of
More informationMaintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems
Maintaining Voltage-Current Phase Relationships in Power Quality Monitoring Systems Brian Kingham, Utility Market Manager, Schneider Electric, PMC Division Abstract: Historical power quality measurement
More information~=E.i!=h. Pre-certification Transformers
7 Transformers Section 26 of the electrical code governs the use and installations of transformers. A transformer is a static device used to transfer energy from one alternating current circuit to another.
More informationInnovative Science and Technology Publications
Innovative Science and Technology Publications Manuscript Title SATURATION ANALYSIS ON CURRENT TRANSFORMER Thilepa R 1, Yogaraj J 2, Vinoth kumar C S 3, Santhosh P K 4, 1 Department of Electrical and Electronics
More informationApprentice Electrical Technician Test (ETT) Preparation Guide
Apprentice Electrical Technician Test (ETT) Preparation Guide APPRENTICE ELECTRICAL TECHNICIAN TEST (ETT) About the Test There are 40 questions with a maximum time limit of three hours. This is a closed
More informationOperation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software
Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software Govind Pandya 1, Rahul Umre 2, Aditya Pandey 3 Assistant professor, Dept. of Electrical & Electronics,
More informationTMS 580. Transformer Loss Measuring System FEATURES BENEFITS APPLICATIONS
TMS 580 Transformer Loss Measuring System The measurement of the losses in power transformers is an indispensable quality-verification process. Due to the fact that normally the transformer user puts a
More informationSpecialists in HV and MV test and diagnostics. Testing in Substations
Specialists in HV and MV test and diagnostics Testing in Substations Testing in Substations Testing in Substations At 4fores we specialize in the diagnosis and measurement of all types of existing technologies
More informationImportance of Transformer Demagnetization
Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia 4th International Colloquium "Transformer Research and Asset Management Importance
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities
More informationISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer
ISSN: 2454-132X Impact factor: 4.295 (Volume 3, Issue 6) Available online at www.ijariit.com Modeling and Analysis of Transformer Divyapradeepa.T Department of Electrical and Electronics, Rajalakshmi Engineering
More informationProposal for instrumentation to calibrate DCCT s up to 24 ka
Klaus. Unser 16. 03.1994 SL-I, CERN Draft: Controlled Circulation personal copy for:... The items marked with this sign ( ) are possibly new ideas which should not be disclosed before they are protected
More informationAustralian Standard. Instrument transformers. Part 1: Current transformers (IEC Ed.1.2 (2003) MOD) AS AS
AS 60044.1 2007 AS 60044.1 2007 Australian Standard Instrument transformers Part 1: Current transformers (IEC 60044-1 Ed.1.2 (2003) MOD) This Australian Standard was prepared by Committee EL-013, Measurement
More information148 Electric Machines
148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional
More informationCP CU1. Coupling unit for line and ground testing
CP CU1 Coupling unit for line and ground testing Line and ground test system CPC 100 The CPC 100 is a multifunctional test set for primary assets. When combined with the CP CU1 it covers the following
More informationSATURATION OF CURRENT TRANSFORMERS AND ITS IMPACT ON DIGITAL OVERCURRENT RELAYS NABIL H. AL-ABBAS
SATURATION OF CURRENT TRANSFORMERS AND ITS IMPACT ON DIGITAL OVERCURRENT RELAYS by NABIL H. AL-ABBAS A Thesis Presented to the DEANSHIP OF GRADUATE STUDIES In Partial Fulfillment of the Requirements for
More informationMedium Voltage Products. KECA 80 C85 Indoor current sensor
Medium Voltage Products KECA 80 C85 Indoor current sensor Parameters for Application Value Rated primary current of application up to 2 500 A Sensor Parameters Value Highest voltage for equipment, U m
More informationEvaluating the Impact of Increasing System Fault Currents on Protection
Evaluating the Impact of Increasing System Fault Currents on Protection Zhihan Xu, Ilia Voloh GE Grid Solutions, LLC Mohsen Khanbeigi Hydro One Abstract Every year the capacity of power systems is increasing,
More informationThis is a preview - click here to buy the full publication
TECHNICAL REPORT IEC TR 61869-100 Edition 1.0 2017-01 colour inside Instrument transformers Part 100: Guidance for application of current transformers in power system protection INTERNATIONAL ELECTROTECHNICAL
More informationREQUIRED SKILLS AND KNOWLEDGE UEENEEG101A. Electromagnetic devices and circuits. Topic and Description NIDA Lesson CARD # Magnetism encompassing:
REQUIRED SKILLS AND KNOWLEDGE UEENEEG101A KS01-EG101A Electromagnetic devices and circuits T1 Magnetism encompassing: Topic and Description NIDA Lesson CARD # magnetic field pattern of bar and horse-shoe
More informationVOTANO 100. Accurate and mobile voltage transformer testing and calibration system
VOTANO 100 Accurate and mobile voltage transformer testing and calibration system Sophisticated testing of inductive and capacitive voltage transformers VOTANO 100: accuracy and portability At only 15
More informationUnderstanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques
Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Charles Sweetser, Services Manager, PRIM Engineering, Waltham, Mass. Topics of Discussion
More information2C73 Setting Guide. High Impedance Differential Relay. relay monitoring systems pty ltd Advanced Protection Devices
2C73 Setting Guide High Impedance Differential Relay relay monitoring systems pty ltd Advanced Protection Devices 1. INTRODUCTION This document provides guidelines for the performance calculations required
More informationCHAPTER 3 SOFTWARE DEVELOPMENT. communications, control design, test and measurement, financial modeling and analysis,
CHAPTER 3 SOFTWARE DEVELOPMENT 3.1 Introduction MATLAB has a wide range of applications, including signal and image processing, communications, control design, test and measurement, financial modeling
More informationAC Excitation. AC Excitation 1. Introduction
AC Excitation 1 AC Excitation Introduction Transformers are foundational elements in all power distribution systems. A transformer couples two (or more) coils to the same flux. As long as the flux is changing
More informationAutomatic Transformer Winding Analyser
2293 Automatic Transformer Winding Analyser The 2293 is an automatic winding analyser, optimized for three phase power and distribution transformer measurements. It uniquely combines winding resistance
More informationDemagnetization of instrument transformers before calibration
sciendo COMMUNICATIONS Journal of ELECTRICAL ENGINEERING, VOL 69 (2018), NO6, 426 430 Demagnetization of instrument transformers before calibration Karel Draxler, Renata Styblíková This paper describes
More informationSATURATION ANALYSIS ON CURRENT TRANSFORMER
Volume 118 No. 18 2018, 2169-2176 ISSN: 1311-8080 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu SATURATION ANALYSIS ON CURRENT TRANSFORMER MANIVASAGAM RAJENDRAN
More informationBus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero
Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic
More informationMoving Test - MT3000
Moving Test - MT3000 Three-Phase Portable Test System Keep ahead with Modular Design The Modular Concept The MT3000 is based on a real modular design concept to provide the greatest possible flexibility
More informationINSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad
INSTITUTE OF AERONAUTICAL ENGINEERING (Autonomous) Dundigal, Hyderabad - 00 03 ELECTRICAL AND ELECTRONICS ENGINEERING ASSIGNMENT Course Name : ELECRICAL MACHINES - II Course Code : A0 Class : II B.TECH-II
More informationSolutions to Consider in Current Transformer Selection for APR1400 Nuclear Power Plant Medium Voltage Switchgears
Journal of Energy and Power Engineering 11 (2017) 670-678 doi: 10.17265/1934-8975/2017.10.008 D DAVID PUBLISHING Solutions to Consider in Current Transformer Selection for APR1400 Nuclear Power Plant Medium
More informationA Laboratory Investigation into the use of MV Current Transformers for Transient Based Protection.
International Conference on Power Systems Transients IPST 3 in New Orleans, USA A Laboratory Investigation into the use of MV Current Transformers for Transient Based Protection. M A Redfern, S C Terry,
More informationNon-conventional instrument transformers and power quality aspects an overview
Representative Meeting / Switzerland June 7 th. 2017 Non-conventional instrument transformers and power quality aspects an overview Erik P. Sperling Presentation overview 1. History 2. Instrument transformer
More informationAnalyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System
Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System Lalit Ghatpande, SynchroGrid, College Station, Texas, 77840 Naveen Ganta, SynchroGrid, College Station, Texas,
More informationImpact of Incipient Faults on Sensitive Protection
Impact of Incipient Faults on Sensitive Protection Paper Authors: Ilia Voloh GE Grid Solutions Zhihan Xu, Ilia Voloh GE Grid Solutions Leonardo Torelli CSE-Uniserve Presented by: Tom Ernst GE Grid Solutions
More informationIJRASET: All Rights are Reserved
Analysis and Simulation of Current Transformer Aalakh Devari 1, Pritam Thomke 2, Devendra Sutar 3 1 Electronics and Telecommunication Dept., Goa College of Engineering, Farmagudi, Ponda Goa, India- 403401
More informationThree Phase Power Transformer Modeling Using FEM for Accurate Prediction of Core and Winding Loss
Kalpa Publications in Engineering Volume 1, 2017, Pages 75 80 ICRISET2017. International Conference on Research and Innovations in Science, Engineering &Technology. Selected Papers in Engineering Three
More informationPower systems 2: Transformation
Power systems 2: Transformation Introduction In this series of articles, we will be looking at each of the main stages of the electrical power system in turn. s you will recall from our Introduction to
More information2C73 Setting Guide. High Impedance Differential Relay. Advanced Protection Devices. relay monitoring systems pty ltd
2C73 Setting Guide High Impedance Differential Relay relay monitoring systems pty ltd Advanced Protection Devices 1. INTRODUCTION This document provides guidelines for the performance calculations required
More informationConnection Impact Assessment Application
Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,
More information1 K Hinds 2012 TRANSFORMERS
1 K Hinds 2012 TRANSFORMERS A transformer changes electrical energy of a given voltage into electrical energy at a different voltage level. It consists of two coils which are not electrically connected,
More informationKNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers
KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.
More informationFRAX Series Sweep Frequency Response Analyzers
FRAX Series Highest dynamic range and accuracy in the industry Fulfills international standards for SFRA measurements Advanced analysis and decision support built into the software. FRAX 150 with built
More informationHow Transformer DC Winding Resistance Testing Can Cause Generator Relays to Operate
How Transformer DC Winding Resistance Testing Can Cause Generator Relays to Operate Ritwik Chowdhury, Mircea Rusicior, Jakov Vico, and Jason Young Schweitzer Engineering Laboratories, Inc. 216 IEEE. Personal
More informationCURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS ADVANCED MATERIALS THE KEY TO PROGRESS
CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS ADVANCED MATERIALS THE KEY TO PROGRESS CURRENT TRANSFORMERS FOR ELECTRONIC WATTHOUR METERS VACUUMSCHMELZE GmbH & Co. KG (VAC) is one of the worldwide
More informationCPC 100. Multi-functional primary test system for substation commissioning and maintenance
CPC 100 Multi-functional primary test system for substation commissioning and maintenance CPC 100 The revolutionary all-in-one test system The patented test system replaces numerous individual testing
More informationCurrent Transformer Performance study Using Software Tools.
Current Transformer Performance study Using Software Tools. A. Mechraoui, A. Draou, A. Akkouche, and S. AL Ahmadi Department of Electronics Technology Madinah College of Technology, Madinah Council of
More informationCatastrophic Relay Misoperations and Successful Relay Operation
Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations
More informationSubstation Test Equipment Guidebook
Substation Test Equipment Guidebook CONTENTS TRANSFORMER TURNS RATIO TESTERS CURRENT TRANSFORMER TESTERS CIRCUIT BREAKER ANALYZERS CIRCUIT BREAKER POWER SUPPLIES BREAKER ANALYZER ACCESSORIES 4 5 6 7 8
More informationEffects of Harmonic Distortion I
Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,
More informationCPC 100. Multi-functional Primary Test System for Substation Commissioning and Maintenance
CPC 100 Multi-functional Primary Test System for Substation Commissioning and Maintenance CPC 100 - The Revolutionary All-in-One Test System The patented test system replaces numerous individual testing
More informationMFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work
GE Grid Solutions MFAC High Impedance Differential Relay MFAC relays provide high speed differential protection for various types of power systems plants including generators, reactors, busbars, motors
More informationChapter 2-1 Transformers
Principles of Electric Machines and Power Electronics Chapter 2-1 Transformers Third Edition P. C. Sen Transformer application 1: power transmission Ideal Transformer Assumptions: 1. Negligible winding
More informationOptimizing HV Capacitor-Bank Design Protection & Testing
Optimizing HV Capacitor-Bank Design Protection & Testing Benton Vandiver III ABB Inc. 71st Annual Conference for Protective Relay Engineers Texas A&M University Introduction Shunt Capacitor Bank Considerations
More informationSubstation Testing and Commissioning: Power Transformer Through Fault Test
1 Substation Testing and Commissioning: Power Transformer Through Fault Test M. Talebi, Member, IEEE, Power Grid Engineering Y. Unludag Electric Power System Abstract This paper reviews the advantage of
More informationMEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly
MEDIUM VOLTAGE PRODUCT PARAMETERS GUIDE How to specify the indoor instrument transformers correctly The range of electric values in the power supply systems is very extensive. This is why it is necessary
More informationEffect of Geomagnetically Induced Currents on Protection Systems
Effect of Geomagnetically Induced Currents on Protection Systems Sture Lindahl 2004-01-23 Industrial Electrical Engineering and Automation sture.lindahl@iea.lth.se Effect of GIC on Protective Relays Activity
More informationGenerator Advanced Concepts
Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves
More information