Catastrophic Relay Misoperations and Successful Relay Operation

Size: px
Start display at page:

Download "Catastrophic Relay Misoperations and Successful Relay Operation"

Transcription

1 Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations and demonstrates how to prevent them from occurring. It also provides an example of using data recorded by a relay during onerous conditions to implement a new protection scheme. An undesired overall differential relay operation occurred at a hydro power plant during an external fault on the low side of the auxiliary transformer. This was an extremely challenging case to analyze since there were no three-line diagrams and it was eventually discovered that one set of CTs was located inside the delta winding of the GSU. An unwanted breaker failure operation occurred that tripped a large generator during high load which resulted in an outage in the adjoining downtown area of a large city. A transformer differential trip protecting the step-up transformer at a process plant occurred due to sympathetic inrush when a large nearby GSU was energized via the interconnecting high voltage transmission line which resulted in an extended outage. An intermittent arcing ground fault on the stator windings of a large generator was not cleared and eventually led to flashover on all three phases; as a result, extensive damage occurred to the large generator. Another intermittent arcing ground fault on the stator windings of a large coal fired generator could not be detected by traditional stator ground fault protection. The ground was on a bushing at the terminals and had arced many times prior to the trip. The customer was able to determine the location of the fault and remedy the situation by implementing a high-speed arcing ground fault protection scheme. Each individual analysis ends with a conclusion which states why the relay misoperated and also provides a recommendation as to the best practice for the particular application. Case 1 Overall Differential Relay Operation at a Hydro Power Plant during External Fault on an Auxiliary Transformer Low Side Synopsis A phase-to-phase fault occurred within the 13.2 kv auxiliary system which was external to the overall differential scheme for generator 1 and resulted in a trip. This section shows why the protection operated and how to prevent it from re-occurring in the future.

2 Figure 1 shows the one-line diagram for this protection. Generator 1 is rated 200 MW. Note that the winding 1 CTs are internal to the delta-connected GSU transformer winding connected to the generator. 500 kv 10000:5 (wye) WDG1 16 kv Breaking Resistor G1 Zigzag 13.2 kv 10000:5 (wye) 10000:5 (wye) 300:5 (wye) WDG2 WDG3 WDG4 x Phase-to-Phase Fault Figure 1 Hydro Electric Plant Single Line Diagram (Generator 1) Existing Protection Settings

3 Fault Current Signals Figure 2A shows the oscillography captured by the relay at the time of the trip. Figure 2B shows the current phasors measured by the protective relay. Figure 2A Fault Event Oscillography

4 Figure 2B Fault Current Phasors Winding 1 CT Connections Figure 3 shows how it is believed that the CTs are connected to the winding 1 current inputs for the differential relay. This has not been confirmed by the customer. Zero-sequence current filtering is enabled to prevent unwanted operations since zerosequence current circulates inside the delta winding during external ground faults within the transmission grid. I C I A I B I C I A /2 A B C I A I B I A - I C I B - I A I C - I B Figure 3 Winding 1 Internal CT Connections Differential Operating Equations Figure 4A shows how the differential protection eliminates zero-sequence current from the winding 1 current inputs.

5 Figure 4A Winding 1 Zero-Sequence Current Elimination Figure 4B shows how the differential protection compensates for the 30 o phase shift across the GSU. Figure 4B Input Current Compensation Figure 4C shows how the differential protection calculates the differential and restraint current for each phase. Figure 4C Differential and Restraint Current Calculations Non-Fault Balanced Load Current Figure 5A shows balanced load current measured by the protective relay during a normal non-fault load condition.

6 Figure 5A Current Phasors during Normal Load Flow (amps secondary) Figure 5B shows the resultant differential and restraint currents calculated by the relay. Figure 5B Protective Relay Secondary Metering Figure 5C shows the corresponding current phasors measured by the relay.

7 Figure 5C Current Phasors measured by Protective Relay (amps secondary) Figure 5D shows the calculated differential and restraint currents which match the values displayed in the relay secondary metering. Note that these values are in per unit. Figure 5D Differential and Restraint Current Calculations (per unit) Fault Current and Trip Figure 6A shows the fault currents measured by the relay when the trip occurred due to the external phase-to-phase fault.

8 Figure 6A Fault Current Phasors (amps secondary) Figure 6B shows the calculated differential and restraint current when the trip occurred. Figure 6B Differential and Restraint Current (per unit) Figure 7 shows the operating points for each phase mapped onto the differential operating characteristic. All three phases are in the operate region A & C Bias (P.U.) Figure 7 Differential Operating Characteristic

9 Fault Current and Non-Trip The solution is to roll the winding 4 current inputs as shown in Figure 8. Figure 8 Correct Relay Setup Figure 9 shows the new fault current measurements for winding 4 due to the correction. Figure 9 Correct Winding 4 Current Measurements (amps secondary) Figure 10 shows the corrected calculated differential and restraint current when the trip occurred. There is now minimal differential current and the relay does not trip. Figure 10 Differential and Restraint Current (per unit) A & C 0.3 B Bias (P.U.) Figure 11 Corrected Differential Operating Characteristic

10 1 st Conclusion The differential protection tripped because of an incorrect CT phase compensation setting for winding 4 current inputs. The best practice is to not include the auxiliary transformer inside the zone of overall differential protection as shown in Figure 12. The auxiliary transformer should be protected by a separate differential relay as denoted by the green CTs that overlap with the overall differential protection. 500 kv 10000:5 (wye) WDG1 16 kv Breaking Resistor 10000:5 (wye) G1 Zigzag 13.2 kv 10000:5 (wye) 10000:5 (wye) WDG2 WDG3 WDG4 x Phase-to-Phase Fault Figure 12 Hydro Electric Plant Single Line Diagram (Generator 1) Case 2 Unwanted Breaker Failure Operation - Large Generator Tripped during High Load Period in Downtown Area of Large City Synopsis A large generator located in the downtown area of a large city was offline and a breaker failure trip occurred during a period of high load disrupting service. Figure 13 shows the system topology at the time of the trip. Note that the generator is connected to the transmission grid via an HV breaker. The low-side winding of the GSU drew excitation current since it was energized via the auxiliary station service.

11 0 Generator Transformer Excitation Current GSU High Side Breaker Auxiliary Station Service Original Breaker Failure Scheme Logic Figure 13 System Operating Conditions 50BF BFI (Input 4) 0 BF Trip Original Protection Settings Fault Current Signals Figure 14A shows the oscillography captured by the relay at the time of the trip. Figure 14B shows the current phasors measured by the protective relay.

12 Figure 14A Fault Event Oscillography Figure 14B Fault Current Phasors 2 nd Conclusion The breaker failure trip occurred because I C was above the current detector pickup setting and input 4 (BFI) was asserted. The breaker failure function may be used for a unit breaker rather than a generator breaker. It is limited in that it has no fault detector associated with the unit breaker.

13 Output contact operation would occur if any of the initiate contacts close and the 52b contact indicated a closed breaker after the set time delay. The corresponding logic is shown in Figure 15. t p 52a BF Trip BFI 0 Figure 15 Correct Breaker Failure Logic Case 3 Transformer Differential Trip due to Sympathetic Inrush when nearby Large GSU Energized via Interconnecting High-Voltage Transmission Line Synopsis The transformer differential relay protecting the step-up transformer at a processing plant tripped when a nearby large GSU at a power plant was energized from the high side. The trip was due to sympathetic inrush current flowing through the step-up transformer, as shown in Figure 16. GSU Generator Processing Plant GSU 87 Original Protection Settings Figure 16 System Operating Conditions (arrows indicate direction of Inrush Current)

14 Fault Current Signals Figure 17A shows the oscillography captured by the relay at the time of the trip. Note that current input IAW1 is almost completely offset and there is some distortion in other current inputs as well. Figure 17A Fault Event Oscillography (Raw waveforms) Figure 17B shows the 2 nd harmonic content of the current inputs at the time of the trip. Figure 17B Fault Event Oscillography (2 nd Harmonic Content)

15 The 2 nd harmonic differential current present when the trip occurred was as follows: A-Phase = 17% B-Phase = 13% C-Phase = 13% The ratio of harmonic to fundamental differential current used to restrain the transformer differential protection is calculated as follows: If the ratio is greater than the restraint setting, then the transformer differential protection is blocked. The original 2 nd harmonic restraint setting was 20% for the electro-mechanical transformer differential relay. The customer used the same setting for the multifunction numerical relay that replaced the original electro-mechanical relay. We can see from Figure 17B that a setting of 20% was not sensitive enough to detect the sympathetic inrush current flowing through the step-up transformer. 3 rd Conclusion Electro-mechanical relays had a fixed harmonic inhibit level of 20% for several decades. This worked well for many years; then transformer manufacturers started making better transformers that used less material and were designed with smaller tolerances. Therefore, modern laminated steel core transformers will not reliably produce 20% 2 nd harmonic current during inrush. A setting of 11% for the 2 nd harmonic restraint would be the most reliable based upon this particular event. Note that the multifunction numerical relay actually uses the RMS of the 2 nd and 4 th harmonic differential current but that still was not enough to restrain the protection. Case 4 Intermittent Arcing Ground Fault Leads to Flashover on All Three Phases of Large Generator - Extensive Damage Occurred Synopsis An intermittent arcing ground fault on a large machine stator winding was undetected for a long time and eventually evolved into a three-phase fault which caused extensive damage to the generator as shown in Figures 18A and 18B.

16 Figure 18A Initial Arc Figure 18B Ground Fault Evolving into Three-Phase Fault

17 4 th Conclusion Conventional protection methods are not reliable due to the intermittent nature of an arcing fault; that is any single arc may not last long enough to operate time-delayed neutral voltage protection such as 59N or 27TN. Case 5 Intermittent Arcing Ground Fault Quickly Cleared by High-Speed Arcing Ground Fault Protection Scheme Synopsis Another intermittent arcing ground fault on a large machine stator winding was quickly detected and cleared in less than 30 cycles as shown in Figure 19. The duration of the first arc was 8 cycles followed by another with duration of 10 cycles; then the high-speed ground fault trip occurred. Figure 19 High Speed Arcing Ground Fault Trip 5 th Conclusion 100% stator ground fault protection is provided by injecting a subharmonic 20 Hz voltage signal into the secondary of the generator neutral grounding transformer through a band-pass filter. The band-pass filter passes only the 20 Hz signal and rejects out-of-band signals. The main advantage of this protection is 100% protection of the stator windings for ground faults including when the machine is off-line (provided that the 20 Hz signal is present). Figure 20 illustrates a typical application. A 20 Hz voltage signal is impressed across the grounding resistor (R N ) by the 20 Hz signal generator. The band-pass filter only passes the 20 Hz signal and rejects out-of-band signals. The voltage across the grounding resistor is also connected across the voltage input (V N ) of the 64S relay. The current input (I N ) of the 64S relay measures the 20 Hz current flowing on the grounded side of the grounding transformer and is stepped down through a CT. It is important to note that the relay does not measure the 20 Hz current flowing through the grounding

18 resistor. The 20 Hz current increases during ground faults on the stator winding and an overcurrent element tuned to 20 Hz that operates on this current provides the protection. A short time delay on pickup is possible since the 20 Hz signal is decoupled from the fundamental power system (i.e., 50 or 60 Hz). Conventional stator ground fault protection requires a long delay to prevent unwanted tripping for external ground faults in the transmission grid due to capacitive coupling across the windings of the GSU as shown in Figure 21. The 64S protection has two overcurrent elements: one operates on the total current (I N ) and the other operates on the real component of the total current. The overcurrent element that operates on the real component sees a change in the insulation resistance of the stator windings and can detect when the insulation first starts to break down, thus preventing catastrophic damage as what occurred in the fourth case presented in this report. Neutral Grounding Transformer L l K k R N 20 Hz Band Pass Filter 1B1 1A1 1A3 1A4 1B4 Wiring Shielded 20 Hz Generator 4A1 4A3 Bl 1A1 1A2 1A3 2A1 2A3 3A2 3A3 3A1 Supply Voltage DC +V Aux -V Aux 20 Hz CT High Voltage 64S Relay Low Voltage 59N V N I N Figure Hz Injection Grounding Network

19 Figure 21 Neutral Voltage Induced due to Capacitive Coupling across GSU Another solution is the accelerated stator ground fault tripping scheme that uses sequence voltages V 2 and V 0 measured at the machine terminal, thus avoiding the long time delay required to coordinate with system protection because of the capacitive coupling across the generator step-up transformer (GSU). Figure 22 shows the scheme which is very easy to set. V N + Short Delay 59N1P (Setting) - AND 0 Accelerated Trip V 2 V2P (Setting) - + V 0 V2P (Setting) + - V N + 59N2P (Setting) - Long Delay 0 Delayed Trip 59N1P = 59N2P Figure 22 Accelerated Stator Ground Fault Tripping Scheme Logic Note that the relay must measure line-to-ground phase voltage in order for the relay to be able to calculate the zero-sequence voltage at the machine terminal. Therefore, the VTs must be connected wye - wye.

20 Figure 23A shows the recommended settings for the neutral overvoltage element 59N1. The pickup setting should cover at least 90 percent of the stator windings. The pickup settings for V 2 and V 0 inhibits are based upon observation of many simulations and real world case studies. Figure 23A 59N1 Settings Figure 23B shows the recommended settings for 59N2. The pickup is the same as 59N1 and uses the time delay required to coordinate with system protection for external ground faults in the transmission system. Figure 23B 59N2 Settings Figure 24 shows the symmetrical components short circuit diagram for a single phase-to-ground fault on the high side of the GSU (i.e., external). There is ample negative-sequence voltage at the machine terminal while no zero-sequence voltage present since there is an open circuit on the generator side of the GSU; therefore, the 59N1 is blocked from tripping.

21 E G + + F x Z 1G Z T Z 1S E S V 2 F x Z 2G Z T Z 2S V 0 F x Z 0G Z T Z 0S Figure 24 External Ground Fault Final Conclusions This paper provides detailed technical analysis of several catastrophic relay misoperations and demonstrates how to prevent them from occurring. It also provides an example of using data recorded by a relay during onerous conditions to implement a new protection scheme. Each individual analysis ends with a conclusion which states why the relay misoperated and also provides a recommendation as to the best practice for the particular application. As mistakes often occur at the design stage, it is necessary to carefully assess the initial settings. About the Author Steve Turner, IEEE Senior Member, is a Senior Applications Engineer at Beckwith Electric Company. His previous experience includes work as an application engineer with GEC Alstom, and an application engineer in the international market for SEL, focusing on transmission line protection applications. Steve worked for Duke Energy (formerly Progress Energy), where he developed a patent for double-ended fault location on overhead transmission lines. Steve has a BSEE and MSEE from Virginia Tech. He has presented at numerous conferences including Georgia Tech Protective Relay Conference, Western Protective Relay Conference, ECNE and Doble User Groups, as well as various international conferences.

PROTECTIVE RELAY MISOPERATIONS AND ANALYSIS

PROTECTIVE RELAY MISOPERATIONS AND ANALYSIS PROTECTIVE RELAY MISOPERATIONS AND ANALYSIS BY STEVE TURNER, Beckwith Electric Company, Inc. This paper provides detailed technical analysis of two relay misoperations and demonstrates how to prevent them

More information

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc. The InterNational Electrical Testing Association Journal FEATURE PROTECTION GUIDE 64S Theory, Application, and Commissioning of Generator 100 Percent Stator Ground Fault Protection Using Low Frequency

More information

Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security

Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security Steve Turner Senior Application Engineer Beckwith Electric Company Introduction Summarize conclusions from NERC

More information

Protecting Large Machines for Arcing Faults

Protecting Large Machines for Arcing Faults Protecting Large Machines for Arcing Faults March 2, 2010 INTRODUCTION Arcing faults occur due to dirty insulators or broken strands in the stator windings. Such faults if undetected can lead to overheating

More information

Testing Numerical Transformer Differential Relays

Testing Numerical Transformer Differential Relays Feature Testing Numerical Transformer Differential Relays Steve Turner Beckwith Electric Co., nc. ntroduction Numerical transformer differential relays require careful consideration as to how to test properly.

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost

More information

Generator Protection GENERATOR CONTROL AND PROTECTION

Generator Protection GENERATOR CONTROL AND PROTECTION Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault

More information

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost

More information

Improving Transformer Protection

Improving Transformer Protection Omaha, NB October 12, 2017 Improving Transformer Protection Wayne Hartmann VP, Customer Excellence Senior Member, IEEE Wayne Hartmann Senior VP, Customer Excellence Speaker Bio whartmann@beckwithelectric.com

More information

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS Ljubomir KOJOVIC Cooper Power Systems - U.S.A. Lkojovic@cooperpower.com INTRODUCTION In steel facilities that use Electric Arc Furnaces (EAFs) to manufacture

More information

Waterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology

Waterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology Waterpower '97 August 5 8, 1997 Atlanta, GA Upgrading Hydroelectric Generator Protection Using Digital Technology Charles J. Beckwith Electric Company 6190-118th Avenue North Largo, FL 33773-3724 U.S.A.

More information

Transformer Protection Principles

Transformer Protection Principles Transformer Protection Principles 1. Introduction Transformers are a critical and expensive component of the power system. Due to the long lead time for repair of and replacement of transformers, a major

More information

Pinhook 500kV Transformer Neutral CT Saturation

Pinhook 500kV Transformer Neutral CT Saturation Russell W. Patterson Tennessee Valley Authority Presented to the 9th Annual Fault and Disturbance Analysis Conference May 1-2, 26 Abstract This paper discusses the saturation of a 5kV neutral CT upon energization

More information

Impact of Incipient Faults on Sensitive Protection

Impact of Incipient Faults on Sensitive Protection Impact of Incipient Faults on Sensitive Protection Paper Authors: Ilia Voloh GE Grid Solutions Zhihan Xu, Ilia Voloh GE Grid Solutions Leonardo Torelli CSE-Uniserve Presented by: Tom Ernst GE Grid Solutions

More information

PROTECTION OF TRANSFORMERS M-3311A TEST PLAN

PROTECTION OF TRANSFORMERS M-3311A TEST PLAN PROTECTION OF TRANSFORMERS M-3311A TEST PLAN Chuck Mozina -- is a Consultant, Protection and Protection Systems for Beckwith Electric and resides in Palm Harbor (near Tampa), Florida.. He is a Life Fellow

More information

Substation Testing and Commissioning: Power Transformer Through Fault Test

Substation Testing and Commissioning: Power Transformer Through Fault Test 1 Substation Testing and Commissioning: Power Transformer Through Fault Test M. Talebi, Member, IEEE, Power Grid Engineering Y. Unludag Electric Power System Abstract This paper reviews the advantage of

More information

How Transformer DC Winding Resistance Testing Can Cause Generator Relays to Operate

How Transformer DC Winding Resistance Testing Can Cause Generator Relays to Operate How Transformer DC Winding Resistance Testing Can Cause Generator Relays to Operate Ritwik Chowdhury, Mircea Rusicior, Jakov Vico, and Jason Young Schweitzer Engineering Laboratories, Inc. 216 IEEE. Personal

More information

889 Advanced Generator Protection Technical Note

889 Advanced Generator Protection Technical Note GE Grid Solutions 8 Series 889 Advanced Generator Protection Technical Note GE Publication Number: GET-20056 Copyright 2017 GE Multilin Inc. Overview The Multilin 889 is part of the 8 Series platform that

More information

Relay-assisted commissioning

Relay-assisted commissioning Relay-assisted commissioning by Casper Labuschagne and Normann Fischer, Schweitzer Engineering Laboratories (SEL) Power transformer differential relays were among the first protection relays to use digital

More information

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions 1 Transmission transformers are important links in the bulk power system. They allow transfer of power from generation centers, up to the high-voltage grid, and to bulk electric substations for distribution

More information

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants Martin Best and Stephanie Mercer, UC Synergetic, LLC Abstract Wind generating plants employ several

More information

Verifying Transformer Differential Compensation Settings

Verifying Transformer Differential Compensation Settings Verifying Transformer Differential Compensation Settings Edsel Atienza and Marion Cooper Schweitzer Engineering Laboratories, Inc. Presented at the 6th International Conference on Large Power Transformers

More information

Performance Analysis of Traditional and Improved Transformer Differential Protective Relays

Performance Analysis of Traditional and Improved Transformer Differential Protective Relays Performance Analysis of Traditional and Improved Transformer Differential Protective Relays Armando Guzmán, Stan Zocholl, and Gabriel Benmouyal Schweitzer Engineering Laboratories, Inc. Hector J. Altuve

More information

Forward to the Basics: Selected Topics in Distribution Protection

Forward to the Basics: Selected Topics in Distribution Protection Forward to the Basics: Selected Topics in Distribution Protection Lee Underwood and David Costello Schweitzer Engineering Laboratories, Inc. Presented at the IEEE Rural Electric Power Conference Orlando,

More information

DOUBLE-ENDED FAULT LOCATORS

DOUBLE-ENDED FAULT LOCATORS The InterNational Electrical Testing Association Journal FEATURE END-TO-END TESTING OF DOUBLE-ENDED FAULT LOCATORS BY STEVE TURNER, Beckwith Electric Company, Inc.. www.netaworld.org FOR HIGH VOLTAGE,

More information

BUS2000 Busbar Differential Protection System

BUS2000 Busbar Differential Protection System BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection 1 Typical Busbar Arrangements Single Busbar Double Busbar with Coupler Breaker and a Half

More information

Using a Multiple Analog Input Distance Relay as a DFR

Using a Multiple Analog Input Distance Relay as a DFR Using a Multiple Analog Input Distance Relay as a DFR Dennis Denison Senior Transmission Specialist Entergy Rich Hunt, M.S., P.E. Senior Field Application Engineer NxtPhase T&D Corporation Presented at

More information

NERC Protection Coordination Webinar Series July 15, Jon Gardell

NERC Protection Coordination Webinar Series July 15, Jon Gardell Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Considerations and Experiences in Implementing Ground Differential Protection for Transformer Protection at TVA

Considerations and Experiences in Implementing Ground Differential Protection for Transformer Protection at TVA Considerations and Experiences in Implementing Ground Differential Protection for Transformer Protection at TVA Meyer Kao - Consultant, Gary Kobet - Tennessee Valley Authority George Pitts -Tennessee Valley

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:

More information

Overcurrent Elements

Overcurrent Elements Exercise Objectives Hands-On Relay Testing Session Overcurrent Elements After completing this exercise, you should be able to do the following: Identify overcurrent element settings. Determine effective

More information

Power Plant and Transmission System Protection Coordination

Power Plant and Transmission System Protection Coordination Agenda Item 5.h Attachment 1 A Technical Reference Document Power Plant and Transmission System Protection Coordination Draft 6.9 November 19, 2009 NERC System Protection and Control Subcommittee November

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering) R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between

More information

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System Lalit Ghatpande, SynchroGrid, College Station, Texas, 77840 Naveen Ganta, SynchroGrid, College Station, Texas,

More information

Visualization and Animation of Protective Relay Operation

Visualization and Animation of Protective Relay Operation Visualization and Animation of Protective Relay Operation A. P. Sakis Meliopoulos School of Electrical and Computer Engineering Georgia Institute of Technology Atlanta, Georgia 30332 George J. Cokkinides

More information

Transformer Protection

Transformer Protection 1 Presenter Contact Info Wayne Hartmann Senior VP, Customer Excellence Beckwith Electric Company whartmann@beckwithelectric.com 904 238 3844 Wayne is the top strategist for delivering innovative technology

More information

Protective Relaying for DER

Protective Relaying for DER Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed

More information

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays

More information

Power Plant and Transmission System Protection Coordination

Power Plant and Transmission System Protection Coordination Technical Reference Document Power Plant and Transmission System Protection Coordination NERC System Protection and Control Subcommittee Revision 1 July 2010 Table of Contents 1. Introduction... 1 1.1.

More information

Protection of a 138/34.5 kv transformer using SEL relay

Protection of a 138/34.5 kv transformer using SEL relay Scholars' Mine Masters Theses Student Theses and Dissertations Fall 2016 Protection of a 138/34.5 kv transformer using SEL 387-6 relay Aamani Lakkaraju Follow this and additional works at: http://scholarsmine.mst.edu/masters_theses

More information

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic

More information

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series

More information

Advanced Applications of Multifunction Digital Generator Protection

Advanced Applications of Multifunction Digital Generator Protection Advanced Applications of Multifunction Digital Generator Protection Charles J. Mozina Beckwith Electric Company 6190-118th Avenue North Largo, FL 33773-3724 U.S.A. Abstract: The protection of generators

More information

Impact of Incipient Faults on Sensitive Protection

Impact of Incipient Faults on Sensitive Protection Impact of Incipient Faults on Sensitive Protection Zhihan Xu GE Grid Solutions, LLC Ilia Voloh GE Grid Solutions, LLC Leonardo Torelli CSE-Uniserve Abstract Incipient faults first represent a challenge

More information

Distance Relay Response to Transformer Energization: Problems and Solutions

Distance Relay Response to Transformer Energization: Problems and Solutions 1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering

More information

Detecting and Managing Geomagnetically Induced Currents With Relays

Detecting and Managing Geomagnetically Induced Currents With Relays Detecting and Managing Geomagnetically Induced Currents With Relays Copyright SEL 2013 Transformer Relay Connections Voltage Current Control RTDs Transformer Protective Relay Measures differential current

More information

Power Plant and Transmission System Protection Coordination Fundamentals

Power Plant and Transmission System Protection Coordination Fundamentals Power Plant and Transmission System Protection Coordination Fundamentals NERC Protection Coordination Webinar Series June 2, 2010 Jon Gardell Agenda 2 Objective Introduction to Protection Generator and

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

Power System Protection

Power System Protection I Power System Protection Arun Phadke Virginia Polytechnic Institute 1 Transfor mer Protection Alexander Apostolov, John Apple yard, Ahmed Elneweihi, Robert Haas, and Glenn W Swift 1-1 Ty pes of Transformer

More information

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay Generator Differential Relay The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3G relay offers the following

More information

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS 1 STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS Z. GAJIĆ S. HOLST D. BONMANN D. BAARS ABB AB, SA Products ABB AB, SA Products ABB AG, Transformers ELEQ bv Sweden Sweden Germany Netherlands zoran.gajic@se.abb.com

More information

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Expo - Nov. 3, 2014 Index Normal Distribution System

More information

Transformer Fault Categories

Transformer Fault Categories Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Volts Per Hertz (24), Undervoltage (27), Overvoltage (59), and Under/Overfrequency (81) Protection System Protection and Control Subcommittee

More information

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3 Power System Protection Dr. Lionel R. Orama Exclusa, PE Week 3 Operating Principles: Electromagnetic Attraction Relays Readings-Mason Chapters & 3 Operating quantities Electromagnetic attraction Response

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES U AJMAL, GE Grid Solutions UK Ltd, usman.ajmal@ge.com S SUBRAMANIAN, GE Grid Solutions UK Ltd, sankara.subramanian@ge.com H Ha GE Grid Solutions

More information

Solution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection

Solution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection ABSTRACT National conference on Engineering Innovations and Solutions (NCEIS 2018) International Journal of Scientific Research in Computer Science, Engineering and Information Technology 2018 IJSRCSEIT

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

Babak Enayati National Grid Thursday, April 17

Babak Enayati National Grid Thursday, April 17 2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April

More information

ATP modeling of internal transformer faults for relay performance testing

ATP modeling of internal transformer faults for relay performance testing Michigan Technological University Digital Commons @ Michigan Tech Dissertations, Master's Theses and Master's Reports - Open Dissertations, Master's Theses and Master's Reports 2011 ATP modeling of internal

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Evaluating the Impact of Increasing System Fault Currents on Protection

Evaluating the Impact of Increasing System Fault Currents on Protection Evaluating the Impact of Increasing System Fault Currents on Protection Zhihan Xu, Ilia Voloh GE Grid Solutions, LLC Mohsen Khanbeigi Hydro One Abstract Every year the capacity of power systems is increasing,

More information

EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER

EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER Objective To analyse the differential protection scheme as applied to a three-phase power transformer

More information

Hands-On-Relay School 2015 Distribution Event Analysis. Randy Spacek Protection Engineer Manager

Hands-On-Relay School 2015 Distribution Event Analysis. Randy Spacek Protection Engineer Manager Hands-On-Relay School 2015 Distribution Event Analysis Randy Spacek Protection Engineer Manager OVERVIEW Available Tools Fault Type Identification: line and transformer Relay Event Record: Oscillography

More information

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME Donald M. MACGREGOR Electrocon Int l, Inc. USA eii@electrocon.com Venkat TIRUPATI Electrocon Int l, Inc. USA eii@electrocon.com Russell

More information

Optimizing HV Capacitor Bank Design, Protection, and Testing Benton Vandiver III ABB Inc.

Optimizing HV Capacitor Bank Design, Protection, and Testing Benton Vandiver III ABB Inc. Optimizing HV Capacitor Bank Design, Protection, and Testing Benton Vandiver III ABB Inc. Abstract - This paper will discuss in detail a capacitor bank protection and control scheme for >100kV systems

More information

Transformer Differential Protection Lab

Transformer Differential Protection Lab Montana Tech Library Digital Commons @ Montana Tech Proceedings of the Annual Montana Tech Electrical and General Engineering Symposium Student Scholarship 2016 Transformer Differential Protection Lab

More information

Utility Interconnection and System Protection

Utility Interconnection and System Protection Utility Interconnection and System Protection Alex Steselboim President, Advanced Power Technologies, Inc. Utility paralleling vs. isolated operation. Isochronous kw load sharing Reactive power (VAR) sharing

More information

IMPROVEMENTS IN PROTECTION AND COMMISSIONING OF DIGITAL TRANSFORMER RELAYS AT MEDIUM VOLTAGE INDUSTRIAL FACILITIES

IMPROVEMENTS IN PROTECTION AND COMMISSIONING OF DIGITAL TRANSFORMER RELAYS AT MEDIUM VOLTAGE INDUSTRIAL FACILITIES IMPOVEMENTS IN POTECTION AND COMMISSIONING OF DIGITAL TANSFOME ELAYS AT MEDIUM VOLTAGE INDUSTIAL FACILITIES Copyright Material IEEE Paper No. PCIC-AN84 Charles J. Mozina, P.E. Life Fellow Member, IEEE

More information

Event Analysis Tutorial

Event Analysis Tutorial 1 Event Analysis Tutorial Part 1: Problem Statements David Costello, Schweitzer Engineering Laboratories, Inc. Abstract Event reports have been an invaluable feature in microprocessor-based relays since

More information

COPYRIGHTED MATERIAL. Index

COPYRIGHTED MATERIAL. Index Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,

More information

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June

More information

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected

More information

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System WHO SHOULD FILE THIS SUBMITTAL: Anyone in the final stages of interconnecting a Generation System with Nodak Electric Cooperative, Inc. This submittal shall be completed and provided to Nodak Electric

More information

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT. MODBUS/BECO2200-M3425A Communication Data Base for M-3425A Integrated Protection System Device I.D. = 150 Specifications presented herein are thought to be accurate at the time of publication but are subject

More information

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

thepower to protect  the power to protect i-gard LITERATURE Low and medium voltage thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors

More information

Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS

Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS Option C4 Block differential current protection Description of option Functional descriptions Parameter list Document no.: 4189340397C SW version:

More information

Modern Protection of Three-Phase and Spare Transformer Banks

Modern Protection of Three-Phase and Spare Transformer Banks Modern Protection of Three-Phase and Spare Transformer Banks Michael Thompson, Faridul Katha Basha, and Craig Holt Schweitzer Engineering Laboratories, Inc. 2016 IEEE. Personal use of this material is

More information

ANALYSIS OF A DIFFERENTIAL AND OVERCURRENT OPERATION ON A 345KV HIGH VOLTAGE LINE REACTOR

ANALYSIS OF A DIFFERENTIAL AND OVERCURRENT OPERATION ON A 345KV HIGH VOLTAGE LINE REACTOR ANALYSIS OF A DIFFERENTIAL AND OVERCURRENT OPERATION ON A 345KV HIGH VOLTAGE LINE REACTOR Authors: Eric Schroeder P.E., Cross Texas Transmission, Amarillo, Texas Jerry Burton, Cross Texas Transmission,

More information

2015 Relay School Bus Protection Mike Kockott March, 2015

2015 Relay School Bus Protection Mike Kockott March, 2015 2015 Relay School Bus Protection Mike Kockott March, 2015 History of Bus Protection Circulating current differential (1900s) High impedance differential (1940s) Percentage restrained differential (1960s)

More information

NERC Protection Coordination Webinar Series June 23, Phil Tatro

NERC Protection Coordination Webinar Series June 23, Phil Tatro Power Plant and Transmission System Protection Coordination Volts Per Hertz (24), Undervoltage (27), Overvoltage (59), and Under/Overfrequency (81) Protection NERC Protection Coordination Webinar Series

More information

O V E R V I E W O F T H E

O V E R V I E W O F T H E A CABLE Technicians TESTING Approach to Generator STANDARDS: Protection O V E R V I E W O F T H E 1 Moderator n Ron Spataro AVO Training Institute Marketing Manager 2 Q&A n Send us your questions and comments

More information

Problems connected with Commissioning of Power Transformers

Problems connected with Commissioning of Power Transformers Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

Bus Protection Fundamentals

Bus Protection Fundamentals Bus Protection Fundamentals Terrence Smith GE Grid Solutions 2017 Texas A&M Protective Relay Conference Bus Protection Requirements High bus fault currents due to large number of circuits connected: CT

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event

More information

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,

More information

1

1 Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive

More information

GPM. Field and Stator Ground Fault Protection Modules. Instruction Manual AF1. GE Grid Solutions

GPM. Field and Stator Ground Fault Protection Modules. Instruction Manual AF1. GE Grid Solutions GE Grid Solutions GPM Field and Stator Ground Fault Protection Modules Instruction Manual Product version: 2.0x GE publication code: 1601-0256-AF1 (GEK-113231D) 1601-0256-AF1 Copyright 2017 GE Multilin

More information

SHUNT CAPACITOR BANK DESIGN AND PROTECTION BASICS

SHUNT CAPACITOR BANK DESIGN AND PROTECTION BASICS SHUNT CAPACITOR BANK DESIGN AND PROTECTION BASICS Introduction Shunt capacitor units are typically used to deliver capacitive reactive compensation or power factor correction. The use of shunt capacitor

More information

Generator Protection M 3425

Generator Protection M 3425 PROTECTION Generator Protection M 3425 Integrated Protection System for Generators of All Sizes Unit shown with optional M 3925 Target Module and M 3931 HMI (Human Machine Interface) Module Provides all

More information

Introduction to Harmonics and Power Quality

Introduction to Harmonics and Power Quality NWEMS Introduction to Harmonics and Power Quality August 20 24, 2018 Seattle, WA Track B Anaisha Jaykumar (SEL) Class Content» Definition of power quality (PQ)» Impact of PQ problems» Sources of poor PQ»

More information

Table of Contents. Introduction... 1

Table of Contents. Introduction... 1 Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...

More information