OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

Size: px
Start display at page:

Download "OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES"

Transcription

1 OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES U AJMAL, GE Grid Solutions UK Ltd, usman.ajmal@ge.com S SUBRAMANIAN, GE Grid Solutions UK Ltd, sankara.subramanian@ge.com H Ha GE Grid Solutions UK Ltd, hengxu.ha@ge.com G LLOYD, GE Grid Solutions UK Ltd, graeme.lloyd@ge.com S HOSSEINI, GE Grid Solutions UK Ltd, sharaf.hosseini@ge.com Dr.J BLAKE, GE Grid Solutions US, jim.blake@ge.com C.F.CHOW, GE Grid Solutions Singapore, chin-fei.chow@ge.com 1 ABSTRACT Open-phase Detection (OPD) is of prime concern in the nuclear industry [1]. Events at several nuclear power plants have shown that the open-phases on the HV side of a transformer may be difficult to detect by existing plant instrumentation and electrical protection schemes. If an open-phase condition is not quickly detected and the transformer not isolated from the system, tripping of critical motor driven loads and loss of plant safety systems can occur. Breaker poles failing to close, a broken conductor, failure of a transformer bushing or line insulator, a loose connection or a blown fuse can all lead to an open-phase condition. Two methods of implementing OPD are described in the paper. The first method uses simple undercurrent detectors and relay logic which is being site trialled in the USA. The second method is a new method proposed for OPD using sequence components and phase identification using total energy flow per phase which has been tested in Matlab (Simulink). Both methods provide a fast, simple and cost effective solution to detect an openphase on the HV side of a transformer. An open-phase condition on heavily loaded to moderately loaded transformers can however be reliably detected and protected against with conventional protection relay schemes. Conversely, reliable open-phase detection for all transformer connections which are lightly loaded or unloaded is challenging. An unloaded power transformer with its primary winding energized, draws a magnetization current in each phase in the range 50 to 750 ma with a significant harmonic content. In addition, an open-phase condition on the HV side of a transformer can be very difficult to detect from the LV side only as the current magnitude and phase angle measured on the LV side depend on the transformer s core and winding configuration as well as the loading level. This paper describes the issues from loss of a phase for nuclear power station auxiliary transformers and proposes a new universal protection scheme applicable to most power transformer configurations. The new scheme uses optical CTs to reliably and accurately measure the very small currents during an open-phase condition using a protection relay with an IEC LE process bus input. KEYWORDS: Nuclear, Open-phase, Auxiliary, Generation 1

2 2 INTRODUCTION An open-phase condition on the HV side of a transformer can be very difficult to be detected from the LV side as the current and voltage response depends on the transformer s core and winding configuration. Commonly used core and winding configurations of power transformers include: Core design: Three limbed core (core type), five limbed core (shell type) and five limbed core with buried delta. Winding configuration: YNd, Dyn, YNyn, Yyn and YNynd Transformer primary-side currents can be an effective indication of an open-phase condition. Extensive simulation studies, have established that with an open-phase on the HV side of a transformer, in some cases the three phase voltages and currents on the LV side could be fairly balanced, particularly under low transformer loading conditions. The severity of the current and voltage imbalance on the LV side depends on the winding configuration as well as the core construction. An unbalance on the LV side of a standby auxiliary transformer for a nuclear power plant can lead to the following: Unbalanced voltage conditions at redundant safety buses. Tripping of equipment such as essential service water pumps, centrifugal charging pumps and component cooling water pumps. Preventing the onsite electric power system from supporting plant safety systems. A lightly loaded or unloaded transformer may continue normal operation for days with acceptable balanced voltages and currents on the LV side even when there is an open-phase condition on the HV. The condition may be detected either during visual inspection, or when the loading of the transformer has increased substantially. The protection relay, monitoring the LV side, can only detect the condition when the load has increased substantially and this will mainly be via the overcurrent element (negative phase sequence or sensitive earth fault) protecting the LV side. A universal protection scheme for HV side open-phase condition of Standby Auxiliary Transformer (SAT) is described in this paper. This scheme is based on a very sensitive, highly accurate and reliable current measurement system that uses optical CTs, where the open-phase condition is automatically detected and alarmed. There is consensus among all parties involved that an alarm rather than a trip command may be more beneficial as the condition can be investigated and remediated in a controlled manner without loss of safety functions. This scheme is universal in the sense that it applies to all transformer winding and core configurations and to a wide range of transformer loadings from no-load to full-load. The OPD scheme discussed in this paper has been used in the field trial of a particular nuclear power plant. All OPD schemes used for automatic and reliable detection of open-phase conditions must be calibrated and tuned to the plant distribution system during the commissioning stage because it depends on the design and configuration of the onsite and offsite power system. 3 TRANSFORMER RESPONSE An open-phase fault, for the purpose of this paper, is defined as a series single phase open fault between the source and the transformer HV winding. The measuring point is at the HV bushings of the transformer. Transformer responses to open-phase faults depend on several factors with the following four being dominant: 1. Source grounding type 2. HV/Primary Winding Configuration 3. LV/Secondary Winding Configuration 4. Core type (3-5 legged) The above criteria affect the presence and level of sequence currents in the transformer. The ratio of these currents to the positive sequence current can be used to detect the presence of an HV open-phase fault. During development of the OPD scheme, various transformer types were modelled to study their open-phase responses. For open-phase faults on the HV side, grounding of the primary winding will determine the ratio of zero sequence to positive sequence currents (I 0 /I 1 ) and the ratio of negative sequence to positive sequence currents (I 2 /I 1 ). This is discussed below. 2

3 3.1 Grounded Primary (Yn) Transformers with a grounded primary winding exhibit a significant increase in I o /I 1 (close to 0.9pu) current ratio during an open-phase fault. This is mainly attributed to current re-routing through the transformer earth connection. Simulation results are shown in Figure 1. In addition to the current response, for Y n - transformers, flux interaction between the primary and secondary windings will result in the voltage in the primary faulted winding being regenerated. However, no power will be transferred via the faulted primary phase winding to the secondary phase winding. Hence, current response is used for OPD in this case. Figure.1 Open-phase response for grounded primary transformer; Positive (Red), Negative (Green) and Zero (Blue) sequence components shown. 3.2 Ungrounded Primary (Y or ) Transformers with an ungrounded primary side will carry a high I 2 /I 1 ratio (close to 0.8pu) as shown in Figure 2. This is due to change in current direction in one of the un-faulted phases. Voltages in healthy primary windings will drop to approximately 0.5pu of the pre-fault voltage. In this case, both the current and voltage can be used for an OPD scheme. Time (s) Time (s) Figure.2 Open-phase response for ungrounded-primary transformer; Positive (Red), Negative (Green) and Zero (Blue) sequence components shown. 3

4 3.3 Loaded versus Unloaded Transformers The current and voltage behaviour described above can be detected by traditional protection schemes when a transformer is carrying significant (>5% rated) load. However, detecting an open-phase fault when the transformer is unloaded or lightly loaded (<5% rated) is not possible with traditional protection schemes. In such cases, optical CTs with digital filtering (to eliminate noise at such low current levels) can be used to provide accurate primary current measurements on the transformer HV side. Typical primary current measurements would be between 50mA to 750mA for unloaded transformers. This current will mainly consist of the transformer magnetising current and any mutual inductance current caused by the HV line. 3.4 System Balance Even though it may initially seem that an open-phase condition on the HV side of a power transformer will result in imbalances on the LV side with enough significance that can be detected by monitoring the LV side, there have been extensive simulation studies that all have confirmed that the impact not only depends on the transformer core design but also on the winding configuration as well as the loading of the transformer. System Balance HV side Phase A Open (Unloaded Transformer ) Configuration and core Primary Voltage (pu) Secondary Voltage (pu) design Phase A Phase B Phase C Phase A Phase B Phase C YNyn (Shell type) Dyn (Core type) YNd (Core type) YNynd (Shell type with Tertiary Delta) Simulation results above indicate that under no-load condition and when there is an open-phase condition on Phase A of the HV side, if the secondary or the tertiary is delta, regardless of the core design the system voltage remains balanced. For example in the case of YNd (core type) the system is balanced because the flux in the three limbs are balanced on the LV side, resulting in the voltage being re-created to 1 pu in the HV phase that has become opened. From the table above it can be concluded that: YNd - lost phase is always re-created irrespective of the core design. Primary Delta or un-earthed Y - the lost voltage is not re-created. YNyn - System balance depends on the core construction. 3.5 Magnetizing current Transformer primary side current magnitude can be an effective indication of an open-phase condition. Transformers that are normally unloaded such as SAT, detection of an open-phase condition via conventional current transformers (CTs)is difficult due to the low magnitude of magnetising currents. CTs are adapted for significantly higher currents than those under unloaded or lightly loaded conditions. A possible solution is by monitoring of the magnetization currents on the HV side of the transformers using Optical CTs together with an adequate numerical relay. Generally, an unloaded SAT with the HV side energized draws magnetization current which is rich in harmonics and is in the range of ma. Figure below depicts a typical SAT magnetizing current. Figure.3 Transformer magnetising and excitation current 4

5 The figure below depicts the magnetization current of unloaded SAT before and after HV side phase A opened. Figure 4: Before phase A (L1) being opened (left), After phase A (L1) being opened (right) 4 OPD SCHEMES 4.1 Use of Undercurrent Elements with Relay Logic (Technique-1) Figure 5: Depicts the relay logic used covering both unloaded as well as loaded transformers. The relay logic employs the measurement of the individual phase currents together with a zero sequence check for the case when the transformer is unloaded. In the case of long incoming lines and an open-phase condition at a long distance away from the measurement point, line charging should also be taken into account which could mask the effect of an open-phase condition if the detection is merely based on low current measurement. In this case a negative sequence test should also be incorporated into the relay logic for the unloaded case. 5

6 4.2 Use of Sequence Components and Summation of Energy (Technique-2) This technique is based on three design modules. When combined with the versatility of configurable logic of a numerical relay, the scheme can be used to detect open-phase faults in several different transformer construction types. An overview of the scheme is shown in Figure 1. The OPD design model takes primary (HV) current and primary (HV) voltage as inputs. Symmetrical components of these currents and voltages are derived in design module 1 - discrete Fourier transform (DFT) and sequence calculation. In design module 2 - open-phase fault detection, input current and voltage components are compared against set criteria. This is the criteria for OPD and for elimination of non-open-phase fault types. Finally, design module 3 - fault detection, calculates the sum of real energy flow per phase for phase selection. Figure.6 OPD Technique-2 Scheme block diagram 4.3 Design Module 1 - Discrete Fourier Transform (DFT) & Sequence Calculation This module, shown in Figure 6, converts measured voltages and currents into sequence components via a Fourier transform. In Matlab, the DFT algorithm is implemented by the following equation: N 1 2 k 2 j N X ( n) x( n N k 1) e N k 0 (1) Where N is number of samples per cycle (N=T0/Ts), T0 is the cycle period of the fundamental frequency, Ts is the sampling interval, x is the input signal, k is the integral variable, and n is the time of the present cycle. The DFT algorithm is the preferred method of sampling measured analogue values as it is feasible to implement in protection relays. Figure.7 DFT and sequence components derivation block diagram representation 6

7 4.4 Design Module 2 - Open-phase Fault Detection The voltage and current sequence components output by module 1 are analysed in module 2 to detect an openphase condition, as shown in Figure 5. The criteria used for detection can be divided into the following: Fault Detection Block: Ratios used for comparison are I 2 /I 1, I 0 /I 1, V 0 /V 1, V 2 /V 1, where I 2 is the negative sequence current, I 1 is the positive sequence current, and I 0 is the zero sequence current. The same notation applies to voltage components. The criteria are based on the tested behaviour of sequence currents and voltages during open-phase conditions on the HV side of various transformer construction types. In an actual application of the scheme, apart from the fault type and transformer construction type, operating values of these ratios will be affected by the system standing imbalance, capacitive charging currents and mutual inductance with adjacent conductors. Figure 3 shows the criteria used for a Y- or Y-Y n type transformer. Non-Open-Phase Fault Detection: To provide selectivity, the algorithm includes functions for detecting several types of non-open-phase faults both on the LV and HV side. These faults will normally be picked up by either the transformer protection scheme or the HV line protection scheme. Figure.8 OPD criteria Technique-2 5 CASE STUDY (TECHNIQUE-1) GE Grid Solutions has carried out three field trials in collaboration with Florida Power and Light (FPL). In the first field trial the GE Grid Solutions OPD system was installed at FPL s Alexander substation in May, 2013 on a 230 kv, 55 MVA wye-wye power transformer. The second field trial of the GE Grid Solutions OPD system was done at the EFACEC Transformer factory in Savannah, GA in April, Three phase testing was done on a 138 kv Delta-Wye transformer and included both open-phase and grounded phase tests, with excitation voltages ranging from 0.9 pu to 1.1 pu. A third OPD trial system was permanently installed at the FPL Martin plant (fossil plant) in July 2014 on a 238 /6.9/6.9 kv three winding Y-Y-Y power transformer. The GE/FPL OPD systems together with Real Time Digital Simulation (RTDS) testing have all demonstrated that the GE OPD system can reliably detect the presence of open, grounded, and high impedance grounded phase faults on the HV side of both loaded and unloaded power transformers. The third field trial is discussed here in detail. 5.1 GE Grid Solutions/FPL Martin plant field trial GE Grid s solution is to install COSI (compact optical sensor intelligence) non-conventional current transformers on the HV bushings of the off-site 3 winding 238/6.9/6.9kV Y-Y-Y power transformer. The photo below shows the COSI optical current transformer installed at the site. 7

8 Figure.9 Photos of field trial GE Grid Solutions s COSI optical CT measures small currents with high resolution and excellent stability. The ring, as shown on the photo above, is not required to be centred on the current carrying conductor because the measurement and the data transmission are carried out optically making the system immune to electromagnetic noise/pickup. A GE Grid Solutions transformer protection relay (P645) with IEC LE Process Bus capability is used to measure the current. The relay is programmed to detect open-phase conditions, including grounded phase and high impedance grounded phase conditions. This relay can be set to be picked up as low as 2 ma with a 2 ma resolution and as fast as 55 ms. 5.2 Data processing algorithm The OPD system is designed to detect the open-phase condition when the transformer is either loaded or unloaded. In the case when the transformer is unloaded, current measured by the relay is typically in the range of 50 ma to 750 ma in which case the response time required can be several seconds. However in the case when the transformer is loaded, current measured by the relay is higher than 1A and the response time needs to be much faster. In order to implement the OPD system to operate in both loaded and unloaded conditions, a dual stream digital signal processing approach has been designed within the same relay. To do so the raw digital data from the COSI current transformer is split into two separate digital streams. One stream is heavily filtered using a frequency tracking comb filter with narrow pass bands located at the fundamental power frequency and several higher harmonics to provide a low noise signal. This allows for the measurement of currents down to 2 ma to be used for when the transformer is unloaded. An input signal from a local conventional voltage transformer is used to provide a frequency reference for the comb filter while redundancy is taken care of in case of a lost or corrupted signal. The second stream is lightly filtered using a weak band pass filter at around 60 Hz and the data from this stream is used for determining the open-phase condition when the transformer is loaded. The objectives of the OPD system were: Test 1 To detect HV side grounded phase condition (phase A, B and C) when the transformer is unloaded. Test 2 To detect healthy condition on the HV side when the transformer is unloaded. Test 3 To detect healthy condition on the HV side when the transformer loaded. Test 4 To detect single phase OPC on HV side (phase C at approximately 120 meters away from the measurement point) when the transformer is unloaded. Test 5 To detect double phase OPC on HV side (phase B and phase C at approximately 120 meters away from the measurement point) when the transformer is unloaded. 8

9 The results of the tests are shown in the table below. Test Transformer Phase A State/Current A Phase B State/Current A Phase C State/Current A Neutral Current A 1 Unloaded Grounded / Grounded / Grounded / Unloaded Healthy / Healthy / Healthy / Loaded Healthy / Healthy / Healthy / Unloaded Healthy / 1.41 Healthy / Opened / Unloaded Healthy / 1.07 Opened / Opened / It is concluded from the above test results that under all conditions the current magnitude is above 2 ma (the accuracy limit of the relay). Also note that the neutral current increases under open-phase condition compared to healthy condition. This is due to the fact that capacitive currents are not cancelled out while under healthy condition the capacitive currents cancel each other out resulting in a small neutral current. 6 CONCLUSION The proposed OPD techniques uses a combination of phase current, sequence components and energy summation to detect and identify an open phase. The requirement for a fast trip is not compromised, as in lightly loaded conditions; the HV side can safely trip after several seconds. The scheme however, is dependent on an accurate measurement of primary phase current down to 5% of transformer rating. This is provided by GE s COSI Optical CTs. Site trials have established that GE Grid Solutions optical fibre measurement technology has excellent potential to improve present power system protection systems and to enable novel protection schemes that will meet the demands of future networks. 7 BIBLIOGRAPHY [1] United States Nuclear Regulatory Commission Advisory Committee on Reactor Safeguards Washington, DC Branch Technical Porition 8-9 on Open Phase Conditions in Electrical Power Systems (ML14057A433, May 2014,1-4 ) 9

Solving old problems with new technology: How to monitor and measure GIC and OPD currents

Solving old problems with new technology: How to monitor and measure GIC and OPD currents Solving old problems with new technology: How to monitor and measure GIC and OPD currents Marcelo Zapella (GE Grid Solutions), Lucas Oliveira (GE Grid Solutions), Rich Hunt (GE Grid Solutions), Dylan Stewart

More information

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved. Pomona, CA, May 24 & 25, 2016 Tertiary Winding Design in wye-wye Connected Transformers Scope of Presentation > Tertiary vs. Stabilizing Winding? Tertiary vs. Stabilizing Winding? Need for Stabilizing

More information

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

Alternative Approaches and Dynamic Analysis Considerations for Detecting Open Phase Conductors in Three Phase Power Systems

Alternative Approaches and Dynamic Analysis Considerations for Detecting Open Phase Conductors in Three Phase Power Systems Alternative Approaches and Dynamic Analysis Considerations for Detecting Open Phase Conductors in Three Phase Power Systems Robert M. Carritte, Kawa Cheung, Mohit Malik Abstract-- Open phase conductors

More information

Transformer Protection

Transformer Protection Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

Transformer Protection Principles

Transformer Protection Principles Transformer Protection Principles 1. Introduction Transformers are a critical and expensive component of the power system. Due to the long lead time for repair of and replacement of transformers, a major

More information

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS 1 STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS Z. GAJIĆ S. HOLST D. BONMANN D. BAARS ABB AB, SA Products ABB AB, SA Products ABB AG, Transformers ELEQ bv Sweden Sweden Germany Netherlands zoran.gajic@se.abb.com

More information

Catastrophic Relay Misoperations and Successful Relay Operation

Catastrophic Relay Misoperations and Successful Relay Operation Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations

More information

EASUN REYROLLE LIMITED

EASUN REYROLLE LIMITED OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Table of Contents. Introduction... 1

Table of Contents. Introduction... 1 Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...

More information

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Disclaimer: All information presented in the report, the results and the related computer program, data,

More information

Power systems 2: Transformation

Power systems 2: Transformation Power systems 2: Transformation Introduction In this series of articles, we will be looking at each of the main stages of the electrical power system in turn. s you will recall from our Introduction to

More information

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

thepower to protect  the power to protect i-gard LITERATURE Low and medium voltage thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors

More information

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd. Functional Range - Earth Fault Relay C&S Protection & Control Ltd. 2 Contents Page No. 1. Application 2. Operating Principle. Current Transformer Connections 5. Connections, Contact Arrangement and Setting

More information

This document covers common questions concerning the design of an effectively grounded system.

This document covers common questions concerning the design of an effectively grounded system. This document covers common questions concerning the design of an effectively grounded system. To prevent against temporary overvoltage conditions when a line-to-ground fault occurs on the power grid.

More information

2 Grounding of power supply system neutral

2 Grounding of power supply system neutral 2 Grounding of power supply system neutral 2.1 Introduction As we had seen in the previous chapter, grounding of supply system neutral fulfills two important functions. 1. It provides a reference for the

More information

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected

More information

Problems connected with Commissioning of Power Transformers

Problems connected with Commissioning of Power Transformers Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.

More information

COPYRIGHTED MATERIAL. Index

COPYRIGHTED MATERIAL. Index Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,

More information

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

Ground Fault Detection using Zigzag Grounding Transformer in Ungrounded System

Ground Fault Detection using Zigzag Grounding Transformer in Ungrounded System Ground Fault Detection using Zigzag Grounding Transformer in Ungrounded System Dhruvita Mandaliya 1, Ajay M. Patel 2, Tarang Thakkar 3 1 PG Student, Electrical Engineering Department, Birla Vishvakarma

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic

More information

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS DFFERENTAL PROTECTON METHODOLOGY FOR ARBTRARY THREE-PHASE POWER TRANSFORMERS Z. Gaji ABB AB-SA Products, Sweden; zoran.gajic@se.abb.com Keywords: power transformer, phase shifting transformer, converter

More information

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

ACS 1000 Transformer Failure Investigation. Nathan Schachter, Peng

ACS 1000 Transformer Failure Investigation. Nathan Schachter, Peng Investigation Nathan Schachter, Peng Objectives Learn what happened Explain why it happened Discuss solutions Suggest remedies so it does not happen again Prevention is the key to success 2 ACS 1000 VFD

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

Relay-assisted commissioning

Relay-assisted commissioning Relay-assisted commissioning by Casper Labuschagne and Normann Fischer, Schweitzer Engineering Laboratories (SEL) Power transformer differential relays were among the first protection relays to use digital

More information

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web: Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation

More information

22.0 Harmonics in Industrial Power Systems

22.0 Harmonics in Industrial Power Systems 1.0 Harmonics in Industrial Power Systems Harmonic frequencies are multiples of the line (fundamental) frequency, which in North America is usually 60 Hz, while it is 50 Hz elsewhere. Figure 1 shows a

More information

ON-SITE TESTING OF SPECIAL TRANSFORMERS

ON-SITE TESTING OF SPECIAL TRANSFORMERS ON-SITE TESTING OF SPECIAL TRANSFORMERS Simanand GANDHI JEYARAJ, Megger Ltd, UK, Simanand.gandhi@megger.com, Robert MILNE, UK Power Networks, UK, robert.milne83@googlemail.com Grant MITCHELL, Transmag

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES

More information

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design

Need for grounding Codes and Standards for grounding Wind Turbine Generator grounding design Foundation + Horizontal Electrode grounding design IEEE PES Transmission and Distribution Conference 2008 Panel Session Large Wind Plant Collector Design Wind Farm Collector System Grounding by Steven W. Saylors, P.E. Chief Electrical Engineer Vestas Americas

More information

Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC)

Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC) Name: Course 11 Distribution Transformer Applications Instructor: David R. Smith, PE Due: April 24, 2017 (EV), April 25, 2017 (LC) 1. T F In three-phase four-wire delta systems rated 240/120 volts, sometimes

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions 1 Transmission transformers are important links in the bulk power system. They allow transfer of power from generation centers, up to the high-voltage grid, and to bulk electric substations for distribution

More information

Long lasting transients in power filter circuits

Long lasting transients in power filter circuits Computer Applications in Electrical Engineering Vol. 12 2014 Long lasting transients in power filter circuits Jurij Warecki, Michał Gajdzica AGH University of Science and Technology 30-059 Kraków, Al.

More information

(2) New Standard IEEE P (3) Core : (4) Windings :

(2) New Standard IEEE P (3) Core : (4) Windings : (d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.

More information

Substation applications

Substation applications Substation applications To make it easy to choose the right for a protection application, the most typical applications are presented with the type of for them. Each sample application is presented by:

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example

More information

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device ABB AG - EPDS The worldʼs fastest limiting and switching device Agenda The world s fastest limiting and switching device Customers Function: Insert-holder with insert Comparison: I S -limiter Circuit-breaker

More information

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP Kiran V. Natkar 1, Naveen Kumar 2 1 Student, M.E., Electrical Power System, MSS CET/ Dr. B.A.M. University, (India) 2 Electrical Power System,

More information

CONTENTS. 1. Introduction Generating Stations 9 40

CONTENTS. 1. Introduction Generating Stations 9 40 CONTENTS 1. Introduction 1 8 Importance of Electrical Energy Generation of Electrical Energy Sources of Energy Comparison of Energy Sources Units of Energy Relationship among Energy Units Efficiency Calorific

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Tripping of circuit breakers in PV installations due to zero sequence field impedance

Tripping of circuit breakers in PV installations due to zero sequence field impedance Tripping of circuit breakers in PV installations due to zero sequence field impedance B. Verhelst 1,2, C. Debruyne 1,2, J. Desmet 1,2 1 dept. Electrical Engineering - Lemcko HoWest Kortrijk, Belgium bart.verhelst@howest.be

More information

R Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data

R Distribution Transformers. Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections. Reference Data Distribution Transformers Mineral Oil-Immersed, Self-Cooled, 60 Hertz Voltages and Connections R201-90-2 Reference Data CONTENTS POPULAR DlSTRIBUTlON TRANSFORMER AND CIRCUIT VOLTAGES... 1 2400-Volt Systems

More information

GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED POWER-DISTRIBUTION SYSTEMS WITH ADJUSTABLE-SPEED DRIVES 1. Modified_103007

GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED POWER-DISTRIBUTION SYSTEMS WITH ADJUSTABLE-SPEED DRIVES 1. Modified_103007 GROUND-FAULT PROTECTION ON RESISTANCE-GROUNDED POWER-DISTRIBUTION SYSTEMS WITH ADJUSTABLE-SPEED DRIVES 1 TWO BASIC PROBLEMS 1. Prevent nuisance or false trips because of noise on loads or feeders without

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and

More information

Transformer Trainer. Electrical Power Systems PSL20. Learning Outcomes. Key Features. Key Specifications

Transformer Trainer. Electrical Power Systems PSL20. Learning Outcomes. Key Features. Key Specifications Electrical Power Systems PSL2 Investigates the principles and operating characteristics of single-phase and three-phase power and distribution transformers Key Features Educational transformers with fully

More information

CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES

CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES 3.1. Introduction Power Transformer is the nerve centre of any power distribution system. The capacity of power transformers is generally decided

More information

BUS2000 Busbar Differential Protection System

BUS2000 Busbar Differential Protection System BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection 1 Typical Busbar Arrangements Single Busbar Double Busbar with Coupler Breaker and a Half

More information

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority S. Songsiri * and S. Sirisumrannukul Abstract This paper presents an application

More information

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E. HP Critical Facility Services delivered by EYP MCF What is VOLTAGE? Difference of Electric Potential

More information

Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL)

Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL) Report on investigation of failure of 315 MVA Auto transformer at 400 kv Bawana Substation of Delhi Transco Ltd.(DTL) 1.0 Introduction: 1.1 DTL vide letter No. F.DTL/206/F.06/2015-16/Mgr(Bawana)/353 dated

More information

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER. Power Voltage Transformers for Air Insulated Substations THE PROVEN POWER. Introduction Trench Power Voltage Transformers (Power VTs) combine the attributes of an inductive voltage transformer with the

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit Validation of a Power Transformer Model for Ferroresonance with System Tests on a 4 kv Circuit Charalambos Charalambous 1, Z.D. Wang 1, Jie Li 1, Mark Osborne 2 and Paul Jarman 2 Abstract-- National Grid

More information

7SG14 Duobias-M Transformer Protection

7SG14 Duobias-M Transformer Protection 7SG14 Duobias-M Transformer Protection Document Release History This document is issue 2010/02. The list of revisions up to and including this issue is: Pre release Revision Date Change 2010/02 Document

More information

Industrial Electrician Level 3

Industrial Electrician Level 3 Industrial Electrician Level 3 Industrial Electrician Unit: C1 Industrial Electrical Code I Level: Three Duration: 77 hours Theory: Practical: 77 hours 0 hours Overview: This unit is designed to provide

More information

SIPROTEC 5 Application. SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT inside the delta connection of the compensation side

SIPROTEC 5 Application. SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT inside the delta connection of the compensation side www.siemens.com/protection SIPROTEC 5 Application SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT in the delta connection of the compensation Answers for infrastructure and cities. Autotransformer

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com ARC FLASH PPE GUIDELINES FOR

More information

Bus Protection Fundamentals

Bus Protection Fundamentals Bus Protection Fundamentals Terrence Smith GE Grid Solutions 2017 Texas A&M Protective Relay Conference Bus Protection Requirements High bus fault currents due to large number of circuits connected: CT

More information

Chapter 7 Conclusion 7.1 General

Chapter 7 Conclusion 7.1 General Chapter 7 7.1 General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due

More information

7. INSPECTION AND TEST PROCEDURES

7. INSPECTION AND TEST PROCEDURES 7.1 Switchgear and Switchboard Assemblies A. Visual and Mechanical Inspection 1. Compare equipment nameplate data with drawings and specifications. 2. Inspect physical and mechanical condition. 3. Inspect

More information

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2 BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY The BE1-67N Ground Directional Overcurrent Relay provides ground fault protection for transmission and distribution lines by sensing the direction and magnitude

More information

Power Station Electrical Protection A 2 B 2 C 2 Neutral C.T E M L } a 2 b 2 c 2 M M M CT Restricted E/F Relay L L L TO TRIP CIRCUIT Contents 1 The Need for Protection 2 1.1 Types of Faults............................

More information

NERC Protection Coordination Webinar Series July 15, Jon Gardell

NERC Protection Coordination Webinar Series July 15, Jon Gardell Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Improving High Voltage Power System Performance. Using Arc Suppression Coils

Improving High Voltage Power System Performance. Using Arc Suppression Coils Improving High Voltage Power System Performance Using Arc Suppression Coils by Robert Thomas Burgess B Com MIEAust CPEng RPEQ A Dissertation Submitted in Fulfilment of the Requirements for the degree of

More information

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS Juan Manuel Gers, PhD Protection coordination principles Relay coordination is the process of selecting settings that will assure that the relays

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

Protective Relaying for DER

Protective Relaying for DER Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum International Journal of Scientific & Engineering Research, Volume 7, Issue 4, April-216 628 REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD Abhilash.G.R Smitha K.S Vocational Teacher

More information

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21 Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive

More information

Differential Protection with REF 542plus Feeder Terminal

Differential Protection with REF 542plus Feeder Terminal Differential Protection with REF 542plus Application and Setting Guide kansikuva_bw 1MRS 756281 Issued: 09.01.2007 Version: A Differential Protection with REF 542plus Application and Setting Guide Contents:

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

ISSN: [IDSTM-18] Impact Factor: 5.164

ISSN: [IDSTM-18] Impact Factor: 5.164 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY A REVIEW OF ROUTINE TESTING ON DISTRIBUTION TRANSFORMER Sukhbir Singh 1, Parul Jangra 2, Anoop Bhagat 3, Vipin Saini 4 1 Assistant

More information

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when

More information

Preface...x Chapter 1 Electrical Fundamentals

Preface...x Chapter 1 Electrical Fundamentals Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5

More information

IOCL Electrical Engineering Technical Paper

IOCL Electrical Engineering Technical Paper IOCL Electrical Engineering Technical Paper 1. Which one of the following statements is NOT TRUE for a continuous time causal and stable LTI system? (A) All the poles of the system must lie on the left

More information

Notes 1: Introduction to Distribution Systems

Notes 1: Introduction to Distribution Systems Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Power Systems Modelling and Fault Analysis

Power Systems Modelling and Fault Analysis Power Systems Modelling and Fault Analysis Theory and Practice Nasser D. Tleis BSc, MSc, PhD, CEng, FIEE AMSTERDAM BOSTON HEIDELBERG LONDON NEW YORK OXFORD PARIS SAN DIEGO SAN FRANCISCO SINGAPORE SYDNEY

More information

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre. General PQ: Power Quality has multiple issues involved. Thus, need to have some benchmarking standards. Very little is spoken about the LT supply installation within an industry. There is need to understand

More information

Rarely used, problems with unbalanced loads.

Rarely used, problems with unbalanced loads. THREE-PHASE TRANSFORMERS Transformers used in three-phase systems may consist of a bank of three single-phase transformers or a single three-phase transformer which is wound on a common magnetic core.

More information

Generator Protection GENERATOR CONTROL AND PROTECTION

Generator Protection GENERATOR CONTROL AND PROTECTION Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault

More information

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM BY MR. H. C. MEHTA AT 1 ST INDIA DOBLE PROTECTION AND AUTOMATION CONFERENCE, NOV 2008 POWER-LINKER Wisdom is not Virtue but Necessity hcmehta@powerlinker.org

More information

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,

More information