Overcurrent Elements
|
|
- Delphia Poole
- 6 years ago
- Views:
Transcription
1 Exercise Objectives Hands-On Relay Testing Session Overcurrent Elements After completing this exercise, you should be able to do the following: Identify overcurrent element settings. Determine effective overcurrent protection settings. Validate relay settings. In this exercise, the instructor will introduce the SEL-387A Current Differential and Overcurrent Relay overcurrent elements, determine how to set the elements for transformer backup protection, and demonstrate how to enter the settings. You will then enter the overcurrent settings into ACSELERATOR QuickSet SEL-5030 Software. After sending your settings to the relay, you will validate the settings and verify the protection scheme. SEL-387A Time-Overcurrent Elements The SEL-387A provides numerous overcurrent elements, as many as 11 per winding and 5 per neutral input. Four levels of phase instantaneous or definite-time elements are available for overcurrent protection, breaker failure protection, overcurrent phase selection for targeting, transformer backup protection, and so on. Two levels of negative-sequence and residual instantaneous elements provide protection against unbalanced conditions and ground faults. Phase, negative-sequence, and residual timeovercurrent elements are available for system backup protection. The SEL-387A also has neutral instantaneous or definite-time elements available. For a more detailed description of each of the overcurrent elements, refer to the SEL-387A Instruction Manual (available at Hands-On Activity 1: Enable Overcurrent Elements In this hands-on activity, you will enable the element for a particular winding and enter settings for backup overcurrent protection. Write your answers in the space provided. Transformer Data Rated 50 MVA Rated high side 161 kv (DAB) Rated low side 14.4 kv (wye) High-side bushing current transformer (CT) ratio (wye connected) Low-side bushing CT ratio (wye connected) Neutral bushing CT ratio Overcurrent Elements Page 1 of
2 Step 1 In ACSELERATOR QuickSet, select Group 1 > Set 1 > Winding 1 Elements. Figure 1 Phase Time-Overcurrent Element Settings Determine the Winding 1 Max Phase Time Overcurrent Trip Level setting. 51P1P = The transformer maximum expected load equals MVA 1000 kv 3 Set the 51P1 pickup to 150 percent of expected maximum load. Step 3 Select Group 1 > Set 1 > Neutral 2 Elements. Figure 2 Neutral Instantaneous Overcurrent Element Settings Overcurrent Elements Page 2 of
3 Step 4 Determine the Neutral Inst Overcurrent Trip Level setting. 50NN21P = Set the 50N element to 50 percent of the maximum ground fault current. Obtain the maximum value from a system fault study. For this example, assume a 5,000 A ground fault current. Step 5 Verify that the Neutral Inst Overcurrent Trip Delay (50NN1D) is set at minimum value of Step 6 Select Group 1 > Set 1 > Winding 2 Elements. Figure 3 Phase Time-Overcurrent Element Settings Step 7 Determine the Winding 2 Phase Time Overcurrent Trip Level setting. 51P2P = Set the phase time-overcurrent element to 150 percent of the continuous rated amperes. Step 8 Set the Winding 2 Phase TOC Curve Selection to coordinate with the downstream time-overcurrent protection. 51P2C = Overcurrent Elements Page 3 of
4 Step 9 Set the Winding 2 Phase TOC Time Dial. 51P2TD = For this exercise, set the time dial to 3 to provide time coordination with downstream devices. You can determine the time dial setting based on a fault coordination study. Step 10 Verify that the following settings are at the default values: 51P2RS = Y 51P2TC = 1 Step 11 Save your settings, and then send them to the relay. Hands-On Activity 2: Validate Overcurrent Elements In this hands-on activity, you will validate the phase and neutral instantaneous overcurrent elements and the phase time-overcurrent elements. Validation Functional Description Figure 4 illustrates the location of Fault F1. The relay should operate when the fault magnitude exceeds the overcurrent relay setting and the time-delay elements time out. Figure 4 Overcurrent Validation Fault Location Overcurrent Elements Page 4 of
5 Validation Pickup Test Values The instructor will use the SEL-AMS (Adaptive Multichannel Source) to inject secondary quantities into the relay terminals to simulate faults (as indicated in Table 1). Table 1 Input (Fault Applied at F1 Location) IAW1 IAW2 IAWn (n = 2 in this example) Simulated F1 Values for Element Pickup Test Element 51P1P 51P2P 50NN21P The instructor will apply the test values to the relay using the SEL-5401 Test System Software front-panel function. Apply a value slightly less than the pickup setting, and slowly increase the current magnitude until the applicable Relay Word bit asserts. Fault Step 1 Reset relay targets by pushing the {TARGET RESET} pushbutton located on the relay front panel. Clear the Sequential Events Recorder (SER) entries. You can perform this task by using either the SER C serial port command or the ACSELERATOR QuickSet human-machine interface (HMI). The instructor will apply the fault current. Step 3 Use the TARn serial port command (n = the Relay Word bit for the element under test) or the ACSELERATOR QuickSet HMI to verify the overcurrent element pickup. Step 4 Verify the following ACSELERATOR QuickSet HMI user-defined target light-emitting diode (LED) indicators: Phase time-overcurrent element 51P1P asserts. Phase time-overcurrent element 51P2P asserts. Neutral instantaneous overcurrent element 50NN21P asserts. Record the element in the Fault column of Table 1. Overcurrent Elements Page 5 of
6 Hands-On Activity 3: Validate Time-Overcurrent Element In this hands-on activity, you will validate the Winding 2 time-overcurrent element. Validate Time-Overcurrent Test Values The instructor will use the SEL-AMS to inject secondary quantities into the relay terminals to simulate faults (as indicated in Table 1). Step 1 Calculate the expected operate time using the equations from Figure 5, and record your answers in Table 2. Figure 5 Time-Overcurrent Operation Equations Element Name 51P1T 51P2T 50NN2T Table 2 Simulated F1 Values for Element Pickup Test Calculated Operate Time at Three Times Pickup Test Time Percentage Difference Clear the SER entries. You can perform this task by using either the SER C serial port command or the ACSELERATOR QuickSet HMI. Overcurrent Elements Page 6 of
7 Winding 2 Time-Overcurrent Timing Test The instructor will apply the test values to the relay at three times the element pickup. Step 1 Reset relay targets by pushing the {TARGET RESET} pushbutton located on the relay front panel. Clear the SER entries. You can perform this task by using either the SER C serial port command or the ACSELERATOR QuickSet HMI. Step 3 After the instructor applies the fault current, use the TARn serial port command (n = the Relay Word bit for the element under test) or the ACSELERATOR QuickSet HMI to verify the overcurrent element pickup. Step 4 Verify that the relay indicator for the Winding 2 phase time-overcurrent element 51P2T asserts at the calculated test time. Step 5 Calculate the error percentage using the following formula: % error = (recorded calculated)/calculated Step 6 Ensure the error percentage is within ±5 percent for this timing test. Overcurrent Elements Page 7 of
EE Lecture 14 Wed Feb 8, 2017
EE 5223 - Lecture 14 Wed Feb 8, 2017 Ongoing List of Topics: URL: http://www.ece.mtu.edu/faculty/bamork/ee5223/index.htm Labs - EE5224 Lab 3 - begins on Tues Feb 14th Term Project - details posted. Limit
More informationTransformer Protection
Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing
More informationProtective Relays Digitrip 3000
New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer
More informationNERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series
More informationDIFFERENTIAL TRANSFORMER PROTECTION USING THE SEL 387 AND SEL 587 MICROPROCESSOR RELAYS
DIFFERENTIAL TRANSFORMER PROTECTION USING THE SEL 387 AND SEL 587 MICROPROCESSOR RELAYS Ryan Chun Senior Project Electrical Engineering Department California Polytechnic State University San Luis Obispo
More informationVerifying Transformer Differential Compensation Settings
Verifying Transformer Differential Compensation Settings Edsel Atienza and Marion Cooper Schweitzer Engineering Laboratories, Inc. Presented at the 6th International Conference on Large Power Transformers
More informationMicrogrid Protection Student Laboratory
Microgrid Protection Student Laboratory Ian Hellman-Wylie and Joey Navarro Senior Project California Polytechnic State University San Luis Obispo 2017 Abstract To better prepare students for careers in
More informationPOWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS
POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS Juan Manuel Gers, PhD Example - Single Line Example 1 - Data Calculate the following: 1. The three phase short circuit levels on busbars
More informationEE Lecture 15 (recorded Feb 9, 2011) Fri Feb 15, 2013
EE 5223 - Lecture 15 (recorded Feb 9, 2011) Fri Feb 15, 2013 Ongoing List of Topics: URL: http://www.ece.mtu.edu/faculty/bamork/ee5223/index.htm Term Project - structuring, details Exercises posted Today:
More informationForward to the Basics: Selected Topics in Distribution Protection
Forward to the Basics: Selected Topics in Distribution Protection Lee Underwood and David Costello Schweitzer Engineering Laboratories, Inc. Presented at the IEEE Rural Electric Power Conference Orlando,
More informationGenerator Protection GENERATOR CONTROL AND PROTECTION
Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault
More informationHands On Relay School Open Lecture Transformer Differential Protection Scott Cooper
Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost
More informationCatastrophic Relay Misoperations and Successful Relay Operation
Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations
More informationPower Distribution: Protection Analysis
Power Distribution: Protection Analysis By: Avneet Singh Samra Senior Project ELECTRICAL ENGINEERING DEPARTMENT California Polytechnic State University San Luis Obispo 2016 1 Abstract The objective of
More informationSEL-787-3, -4 Transformer Protection Relay
SEL-787-3, -4 Transformer Protection Relay SEL-787-3E Model SEL-787-3S Model SEL-787-4X Model Major Features and Benefits The SEL-787 Transformer Protection Relay provides unsurpassed protection, integration,
More informationShortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller
Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of
More informationBus Protection Fundamentals
Bus Protection Fundamentals Terrence Smith GE Grid Solutions 2017 Texas A&M Protective Relay Conference Bus Protection Requirements High bus fault currents due to large number of circuits connected: CT
More informationSetting Generic Distance Relay UTP-100#WPSC1. in the. Computer-Aided Protection Engineering System (CAPE)
Setting Generic Distance Relay UTP-100#WPSC1 in the Computer-Aided Protection Engineering System (CAPE) Prepared for CAPE Users' Group August 6, 1998 Revised August 24, 1998 Electrocon International, Inc.
More informationProtection of a 138/34.5 kv transformer using SEL relay
Scholars' Mine Masters Theses Student Theses and Dissertations Fall 2016 Protection of a 138/34.5 kv transformer using SEL 387-6 relay Aamani Lakkaraju Follow this and additional works at: http://scholarsmine.mst.edu/masters_theses
More informationA proven distribution feeder solution with integrated protection, monitoring, and control
SEL-35 Protection System A proven distribution feeder solution with integrated protection, monitoring, and control Achieve sensitive and secure fault detection using comprehensive protection functions.
More informationU I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525.
Time Overcurrent Relays More or less approximates thermal fuse» Allow coordination with fuses Direction of Current nduced Torque Restraining Spring Reset Position Time Dial Setting Disk Basic equation
More informationTutorial on Symmetrical Components
Tutorial on Symmetrical Components Part : Examples Ariana Amberg and Alex Rangel, Schweitzer Engineering Laboratories, nc. Abstract Symmetrical components and the per-unit system are two of the most fundamental
More informationARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS
The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com ARC FLASH PPE GUIDELINES FOR
More informationHands On Relay School Open Lecture Transformer Differential Protection Scott Cooper
Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost
More informationTESTING PROCEDURE for SEL 311L DISTANCE and DIFFERENTIAL RELAY
1 TESTING PROCEDURE for SEL 311L DISTANCE and DIFFERENTIAL RELAY 2 CONTENTS 1. Launching COMMUNICATION and GETTING Setting Parameters from RELAY 2. MEASUREMENT 3. DIFFERENTIAL TEST 4. OVERCURRENT TEST
More informationBE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2
BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY The BE1-67N Ground Directional Overcurrent Relay provides ground fault protection for transmission and distribution lines by sensing the direction and magnitude
More informationTesting Numerical Transformer Differential Relays
Feature Testing Numerical Transformer Differential Relays Steve Turner Beckwith Electric Co., nc. ntroduction Numerical transformer differential relays require careful consideration as to how to test properly.
More informationProtecting Large Machines for Arcing Faults
Protecting Large Machines for Arcing Faults March 2, 2010 INTRODUCTION Arcing faults occur due to dirty insulators or broken strands in the stator windings. Such faults if undetected can lead to overheating
More information1 INTRODUCTION 1.1 PRODUCT DESCRIPTION
GEK-00682D INTRODUCTION INTRODUCTION. PRODUCT DESCRIPTION The MDP Digital Time Overcurrent Relay is a digital, microprocessor based, nondirectional overcurrent relay that protects against phase-to-phase
More informationDISTRIBUTION DEVICE COORDINATION
DISTRIBUTION DEVICE COORDINATION Kevin Damron & Calvin Howard Avista Utilities Presented March th, 08 At the 5 th Annual Hands-On Relay School Washington State University Pullman, Washington TABLE OF CONTENTS
More informationPD300. Transformer, generator and motor protection Data sheet
PD300 Transformer, generator and motor protection Data sheet DSE_PD300_eng_AO No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam T&D. One of
More informationTransformer Differential Protection Lab
Montana Tech Library Digital Commons @ Montana Tech Proceedings of the Annual Montana Tech Electrical and General Engineering Symposium Student Scholarship 2016 Transformer Differential Protection Lab
More informationwww. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay
Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:
More informationOvercurrent and Overload Protection of AC Machines and Power Transformers
Exercise 2 Overcurrent and Overload Protection of AC Machines and Power Transformers EXERCISE OBJECTIVE When you have completed this exercise, you will understand the relationship between the power rating
More informationSEL-311C TRANSMISSION PROTECTION SYSTEM
SEL-3C TRANSMISSION PROTECTION SYSTEM ADVANCED TRANSMISSION LINE PROTECTION, AUTOMATION, AND CONTROL Bus ANSI NUMBERS/ACRONYMS AND FUNCTIONS 52 3 3 2 P G 8 O U 27 68 50BF 67 P G Q 50 P G Q 59 P G Q 5 P
More informationHeight: inches Width: inches Depth: inches, inches. Listings/Certification UL 1053 ANSI C37-90 IEC 255. General Description
1rcJll Cutler-Hammer New nformation Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer protection Backup
More informationTime-current Coordination
269 5.2.3.1 Time-current Coordination Time that is controlled by current magnitude permits discriminating faults at one location from another. There are three variables available to discriminate faults,
More informationProtection Introduction
1.0 Introduction Protection 2 There are five basic classes of protective relays: Magnitude relays Directional relays Ratio (impedance) relays Differential relays Pilot relays We will study each of these.
More informationEvent Analysis Tutorial
1 Event Analysis Tutorial Part 1: Problem Statements David Costello, Schweitzer Engineering Laboratories, Inc. Abstract Event reports have been an invaluable feature in microprocessor-based relays since
More informationBabak Enayati National Grid Thursday, April 17
2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April
More informationGround Fault Isolation with Loads Fed from Separately Derived Grounded Sources
Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources Introduction Ground fault sensing detects current that flows between a source and a (faulted) load traveling on other than
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationDESIGN OF A DIFFERENTIAL PROTECTION SCHEME FOR A 345 KV TRANSMISSION LINE USING SEL 311L RELAYS TARANGINI KAROOR SUBRAHMANYAM
DESIGN OF A DIFFERENTIAL PROTECTION SCHEME FOR A 345 KV TRANSMISSION LINE USING SEL 311L RELAYS by TARANGINI KAROOR SUBRAHMANYAM B.E., OSMANIA UNIVERSITY, 2011 A REPORT submitted in partial fulfillment
More informationBE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY
BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY The BE1-87G is a single or three-phase solid-state variable percentage differential relay designed to provide selective, high-speed, differential protection
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More informationPower System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3
Power System Protection Dr. Lionel R. Orama Exclusa, PE Week 3 Operating Principles: Electromagnetic Attraction Relays Readings-Mason Chapters & 3 Operating quantities Electromagnetic attraction Response
More informationHarmonic Distortion Evaluations
Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion
More informationOptimizing HV Capacitor Bank Design, Protection, and Testing Benton Vandiver III ABB Inc.
Optimizing HV Capacitor Bank Design, Protection, and Testing Benton Vandiver III ABB Inc. Abstract - This paper will discuss in detail a capacitor bank protection and control scheme for >100kV systems
More informationPinhook 500kV Transformer Neutral CT Saturation
Russell W. Patterson Tennessee Valley Authority Presented to the 9th Annual Fault and Disturbance Analysis Conference May 1-2, 26 Abstract This paper discusses the saturation of a 5kV neutral CT upon energization
More informationOVERCURRENT PROTECTION RELAY GRD110
INSTRUCTION MANUAL OVERCURRENT PROTECTION RELAY GRD110 TOSHIBA Corporation 2002 All Rights Reserved. ( Ver. 3.1) Safety Precautions Before using this product, please read this chapter carefully. 1 This
More informationSubstation Testing and Commissioning: Power Transformer Through Fault Test
1 Substation Testing and Commissioning: Power Transformer Through Fault Test M. Talebi, Member, IEEE, Power Grid Engineering Y. Unludag Electric Power System Abstract This paper reviews the advantage of
More informationDirectional STANDARDS: Overcurrent Relaying
A CABLE Technicians TESTING Approach to Directional STANDARDS: Overcurrent Relaying Understanding O V E R V I E W and O F Testing T H E Directional Relays 1 Moderator n Ron Spataro AVO Training Institute
More informationTransformer protection IED RET 670
Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth
More informationMV network design & devices selection EXERCISE BOOK
MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester
More informationSEL-351R-4 Recloser Control
-4 Recloser Control Take Control of Your Recloser Major Features and Benefits The -4 Recloser Control is the replacement for the legacy Recloser Control. Throughout the rest of this data sheet, the -4
More informationOptimizing HV Capacitor-Bank Design Protection & Testing
Optimizing HV Capacitor-Bank Design Protection & Testing Benton Vandiver III ABB Inc. 71st Annual Conference for Protective Relay Engineers Texas A&M University Introduction Shunt Capacitor Bank Considerations
More informationAUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME
AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME Donald M. MACGREGOR Electrocon Int l, Inc. USA eii@electrocon.com Venkat TIRUPATI Electrocon Int l, Inc. USA eii@electrocon.com Russell
More informationPhase and neutral overcurrent protection
Phase and neutral overcurrent protection Page 1 ssued June 1999 Changed since July 1998 Data subject to change without notice (SE970165) Features Two-phase or three-phase time-overcurrent and earth fault
More informationTransmission Line Applications of Directional Ground Overcurrent Relays. Working Group D24 Report to the Line Protection Subcommittee January 2014
Transmission Line Applications of Directional Ground Overcurrent Relays Working Group D24 Report to the Line Protection Subcommittee January 2014 Working Group Members: Don Lukach (Chairman), Rick Taylor
More informationImpacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering
Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Expo - Nov. 3, 2014 Index Normal Distribution System
More informationINSTRUCTIONS. SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays. GE Power Management
g INSTRUCTIONS SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays Manual Part Number: GEK-86069J Copyright 2002 215 Anderson Avenue Markham, Ontario L6E 1B3 Canada Telephone: (905) 294-6222 Fax:
More informationBack to the Basics Event Analysis Using Symmetrical Components
Back to the Basics Event Analysis Using Symmetrical Components Amanvir Sudan Schweitzer Engineering Laboratories, Inc. 218 SEL Motivation Overview Back to Basics Introduction Symmetrical components refresher
More informationUsing a Multiple Analog Input Distance Relay as a DFR
Using a Multiple Analog Input Distance Relay as a DFR Dennis Denison Senior Transmission Specialist Entergy Rich Hunt, M.S., P.E. Senior Field Application Engineer NxtPhase T&D Corporation Presented at
More informationConsiderations and Experiences in Implementing Ground Differential Protection for Transformer Protection at TVA
Considerations and Experiences in Implementing Ground Differential Protection for Transformer Protection at TVA Meyer Kao - Consultant, Gary Kobet - Tennessee Valley Authority George Pitts -Tennessee Valley
More informationENOSERV 2014 Relay & Protection Training Conference Course Descriptions
ENOSERV 2014 Relay & Protection Training Conference Course Descriptions Day 1 Generation Protection/Motor Bus Transfer Generator Protection: 4 hours This session highlights MV generator protection and
More informationEEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER
EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER Objective To analyse the differential protection scheme as applied to a three-phase power transformer
More informationwww. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay
Generator Differential Relay The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3G relay offers the following
More informationRelay-assisted commissioning
Relay-assisted commissioning by Casper Labuschagne and Normann Fischer, Schweitzer Engineering Laboratories (SEL) Power transformer differential relays were among the first protection relays to use digital
More informationRestricted earth-fault protection function block description
function block description Document ID: PRELIMINARY VERSION User s manual version information Version Date Modification Compiled by Preliminary 30.10.2009. Preliminary version, without technical information
More informationg GE POWER MANAGEMENT
745 FREQUENTLY ASKED QUESTIONS 1 I get a communication error with the relay when I try to store a setpoint. This error can occur for several different reasons. First of all, verify that the address is
More informationPower System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)
Differential Protection (Unit protection) Differential Protection Differential protection is the best technique in protection. In this type of protection the electrical quantities entering and leaving
More informationA Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants
A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants Martin Best and Stephanie Mercer, UC Synergetic, LLC Abstract Wind generating plants employ several
More informationWaterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology
Waterpower '97 August 5 8, 1997 Atlanta, GA Upgrading Hydroelectric Generator Protection Using Digital Technology Charles J. Beckwith Electric Company 6190-118th Avenue North Largo, FL 33773-3724 U.S.A.
More informationNERC Protection Coordination Webinar Series July 15, Jon Gardell
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationRAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements
RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying
More informationAPPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges.
APPLICATION: Basler Electric offers a New Line of digitally controlled brush (static) or brushless excitation systems designed for use with existing Hydro, Gas as well as Diesel driven generators requiring
More informationTransmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection
Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed
More informationUnit Protection Differential Relays
Unit Protection PROF. SHAHRAM MONTASER KOUHSARI Current, pu Current, pu Protection Relays - BASICS Note on CT polarity dots Through-current: must not operate Internal fault: must operate The CT currents
More informationINVESTIGATING THE CAPABILITIES OF SEL 787 TRANSFORMER PROTECTION RELAY USING LOW LEVEL SIMULATORS.
INVESTIGATING THE CAPABILITIES OF SEL 787 TRANSFORMER PROTECTION RELAY USING LOW LEVEL SIMULATORS. Thesis submitted to the School of Engineering and Information Technology, Murdoch University in partial
More informationTransmission Protection Overview
Transmission Protection Overview 2017 Hands-On Relay School Daniel Henriod Schweitzer Engineering Laboratories Pullman, WA Transmission Line Protection Objective General knowledge and familiarity with
More informationo9oo INSTRUCTIONS SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays GE Power Management
0 INSTRUCTIONS SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays Manual Part Number: GEK-86069J Copyright 22 215 Anderson Avenue Markham, Ontario L6E 1B3 Canada Telephone: (905) 294-6222 Fax:
More informationResidual instantaneous overcurrent protection function block description
Residual instantaneous overcurrent block description Document ID: PRELIMINARY VERSION User s manual version information Version Date Modification Compiled by Preliminary 30.10.2009. Preliminary version,
More informationUnit Auxiliary Transformer (UAT) Relay Loadability Report
Background and Objective Reliability Standard, PRC 025 1 Generator Relay Loadability (standard), developed under NERC Project 2010 13.2 Phase 2 of Relay Loadability: Generation, was adopted by the NERC
More informationProtection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin
Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad
More informationTurn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents
Turn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents Mariya Babiy 1, Rama Gokaraju 1, Juan Carlos Garcia 2 1 University of Saskatchewan, Saskatoon, Canada 2 Manitoba HVDC Research
More informationSubstation Monitoring with TESLA
Substation Monitoring with TESLA Line 12 11 52-2 52-1 PT S1 21 22 PT S2 Line Protection Relay Current Module 2x 21 Voltage Module 9xAI 3xEI Application Note TESLA is a power system recorder used to monitor
More informationTEST PROCEDURE FOR THE RMS-2012AF PROGRAMMABLE LOGIC CONTROLLER USING AN AMPTECTOR SECONDARY TEST SET.
1 TEST PROCEDURE FOR THE RMS-2012AF PROGRAMMABLE LOGIC CONTROLLER USING AN AMPTECTOR SECONDARY TEST SET. The Amptector Adapter Plug, shown above, is available from WESTRIP to facilitate the testing of
More informationDistance Relay Response to Transformer Energization: Problems and Solutions
1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering
More information1960 Research Drive, Suite 100, Troy, Michigan with. REVISION: December 10, 2007 (Supersedes previous versions) Prepared by:
ENGINEERING SERVICES 1960 Research Drive, Suite 100, Troy, Michigan 48083 ARC FLASH REDUCTION with SEPAM RELAY ZONE SELECTIVE INTERLOCKING REVISION: December 10, 2007 (Supersedes previous versions) Prepared
More informationTransmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes
Transmission Line Protection Objective General knowledge and familiarity with transmission protection schemes Transmission Line Protection Topics Primary/backup protection Coordination Communication-based
More informationEASUN REYROLLE LIMITED
OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT
More informationA NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG
A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when
More informationProtection of Microgrids Using Differential Relays
1 Protection of Microgrids Using Differential Relays Manjula Dewadasa, Member, IEEE, Arindam Ghosh, Fellow, IEEE and Gerard Ledwich, Senior Member, IEEE Abstract A microgrid provides economical and reliable
More informationATP modeling of internal transformer faults for relay performance testing
Michigan Technological University Digital Commons @ Michigan Tech Dissertations, Master's Theses and Master's Reports - Open Dissertations, Master's Theses and Master's Reports 2011 ATP modeling of internal
More informationSEL-710 Motor Protection Relay
SEL-710 Motor Protection Relay Motor Protection Relay Major Features and Benefits The SEL-710 Motor Protection Relay provides an exceptional combination of protection, monitoring, control, and communication
More informationThree-phase instantaneous overcurrent protection function block description
Three-phase instantaneous overcurrent protection block description Document ID: PRELIMINARY VERSION User s manual version information Version Date Modification Compiled by Preliminary 30.10.2009 Preliminary
More informationNERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June
More informationT/3000 T/3000. Substation Maintenance and Commissioning Test Equipment
T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY
More informationFuseless Capacitor Bank Protection
Fuseless Bank Protection Minnesota Power Systems Conference St. Paul, MN. November 2, 1999 by: Tom Ernst, Minnesota Power Other Papers of Interest Presented at Western Protective Relay Conference, Oct.
More informationHands-On-Relay School 2015 Distribution Event Analysis. Randy Spacek Protection Engineer Manager
Hands-On-Relay School 2015 Distribution Event Analysis Randy Spacek Protection Engineer Manager OVERVIEW Available Tools Fault Type Identification: line and transformer Relay Event Record: Oscillography
More information