Overcurrent Elements

Size: px
Start display at page:

Download "Overcurrent Elements"

Transcription

1 Exercise Objectives Hands-On Relay Testing Session Overcurrent Elements After completing this exercise, you should be able to do the following: Identify overcurrent element settings. Determine effective overcurrent protection settings. Validate relay settings. In this exercise, the instructor will introduce the SEL-387A Current Differential and Overcurrent Relay overcurrent elements, determine how to set the elements for transformer backup protection, and demonstrate how to enter the settings. You will then enter the overcurrent settings into ACSELERATOR QuickSet SEL-5030 Software. After sending your settings to the relay, you will validate the settings and verify the protection scheme. SEL-387A Time-Overcurrent Elements The SEL-387A provides numerous overcurrent elements, as many as 11 per winding and 5 per neutral input. Four levels of phase instantaneous or definite-time elements are available for overcurrent protection, breaker failure protection, overcurrent phase selection for targeting, transformer backup protection, and so on. Two levels of negative-sequence and residual instantaneous elements provide protection against unbalanced conditions and ground faults. Phase, negative-sequence, and residual timeovercurrent elements are available for system backup protection. The SEL-387A also has neutral instantaneous or definite-time elements available. For a more detailed description of each of the overcurrent elements, refer to the SEL-387A Instruction Manual (available at Hands-On Activity 1: Enable Overcurrent Elements In this hands-on activity, you will enable the element for a particular winding and enter settings for backup overcurrent protection. Write your answers in the space provided. Transformer Data Rated 50 MVA Rated high side 161 kv (DAB) Rated low side 14.4 kv (wye) High-side bushing current transformer (CT) ratio (wye connected) Low-side bushing CT ratio (wye connected) Neutral bushing CT ratio Overcurrent Elements Page 1 of

2 Step 1 In ACSELERATOR QuickSet, select Group 1 > Set 1 > Winding 1 Elements. Figure 1 Phase Time-Overcurrent Element Settings Determine the Winding 1 Max Phase Time Overcurrent Trip Level setting. 51P1P = The transformer maximum expected load equals MVA 1000 kv 3 Set the 51P1 pickup to 150 percent of expected maximum load. Step 3 Select Group 1 > Set 1 > Neutral 2 Elements. Figure 2 Neutral Instantaneous Overcurrent Element Settings Overcurrent Elements Page 2 of

3 Step 4 Determine the Neutral Inst Overcurrent Trip Level setting. 50NN21P = Set the 50N element to 50 percent of the maximum ground fault current. Obtain the maximum value from a system fault study. For this example, assume a 5,000 A ground fault current. Step 5 Verify that the Neutral Inst Overcurrent Trip Delay (50NN1D) is set at minimum value of Step 6 Select Group 1 > Set 1 > Winding 2 Elements. Figure 3 Phase Time-Overcurrent Element Settings Step 7 Determine the Winding 2 Phase Time Overcurrent Trip Level setting. 51P2P = Set the phase time-overcurrent element to 150 percent of the continuous rated amperes. Step 8 Set the Winding 2 Phase TOC Curve Selection to coordinate with the downstream time-overcurrent protection. 51P2C = Overcurrent Elements Page 3 of

4 Step 9 Set the Winding 2 Phase TOC Time Dial. 51P2TD = For this exercise, set the time dial to 3 to provide time coordination with downstream devices. You can determine the time dial setting based on a fault coordination study. Step 10 Verify that the following settings are at the default values: 51P2RS = Y 51P2TC = 1 Step 11 Save your settings, and then send them to the relay. Hands-On Activity 2: Validate Overcurrent Elements In this hands-on activity, you will validate the phase and neutral instantaneous overcurrent elements and the phase time-overcurrent elements. Validation Functional Description Figure 4 illustrates the location of Fault F1. The relay should operate when the fault magnitude exceeds the overcurrent relay setting and the time-delay elements time out. Figure 4 Overcurrent Validation Fault Location Overcurrent Elements Page 4 of

5 Validation Pickup Test Values The instructor will use the SEL-AMS (Adaptive Multichannel Source) to inject secondary quantities into the relay terminals to simulate faults (as indicated in Table 1). Table 1 Input (Fault Applied at F1 Location) IAW1 IAW2 IAWn (n = 2 in this example) Simulated F1 Values for Element Pickup Test Element 51P1P 51P2P 50NN21P The instructor will apply the test values to the relay using the SEL-5401 Test System Software front-panel function. Apply a value slightly less than the pickup setting, and slowly increase the current magnitude until the applicable Relay Word bit asserts. Fault Step 1 Reset relay targets by pushing the {TARGET RESET} pushbutton located on the relay front panel. Clear the Sequential Events Recorder (SER) entries. You can perform this task by using either the SER C serial port command or the ACSELERATOR QuickSet human-machine interface (HMI). The instructor will apply the fault current. Step 3 Use the TARn serial port command (n = the Relay Word bit for the element under test) or the ACSELERATOR QuickSet HMI to verify the overcurrent element pickup. Step 4 Verify the following ACSELERATOR QuickSet HMI user-defined target light-emitting diode (LED) indicators: Phase time-overcurrent element 51P1P asserts. Phase time-overcurrent element 51P2P asserts. Neutral instantaneous overcurrent element 50NN21P asserts. Record the element in the Fault column of Table 1. Overcurrent Elements Page 5 of

6 Hands-On Activity 3: Validate Time-Overcurrent Element In this hands-on activity, you will validate the Winding 2 time-overcurrent element. Validate Time-Overcurrent Test Values The instructor will use the SEL-AMS to inject secondary quantities into the relay terminals to simulate faults (as indicated in Table 1). Step 1 Calculate the expected operate time using the equations from Figure 5, and record your answers in Table 2. Figure 5 Time-Overcurrent Operation Equations Element Name 51P1T 51P2T 50NN2T Table 2 Simulated F1 Values for Element Pickup Test Calculated Operate Time at Three Times Pickup Test Time Percentage Difference Clear the SER entries. You can perform this task by using either the SER C serial port command or the ACSELERATOR QuickSet HMI. Overcurrent Elements Page 6 of

7 Winding 2 Time-Overcurrent Timing Test The instructor will apply the test values to the relay at three times the element pickup. Step 1 Reset relay targets by pushing the {TARGET RESET} pushbutton located on the relay front panel. Clear the SER entries. You can perform this task by using either the SER C serial port command or the ACSELERATOR QuickSet HMI. Step 3 After the instructor applies the fault current, use the TARn serial port command (n = the Relay Word bit for the element under test) or the ACSELERATOR QuickSet HMI to verify the overcurrent element pickup. Step 4 Verify that the relay indicator for the Winding 2 phase time-overcurrent element 51P2T asserts at the calculated test time. Step 5 Calculate the error percentage using the following formula: % error = (recorded calculated)/calculated Step 6 Ensure the error percentage is within ±5 percent for this timing test. Overcurrent Elements Page 7 of

EE Lecture 14 Wed Feb 8, 2017

EE Lecture 14 Wed Feb 8, 2017 EE 5223 - Lecture 14 Wed Feb 8, 2017 Ongoing List of Topics: URL: http://www.ece.mtu.edu/faculty/bamork/ee5223/index.htm Labs - EE5224 Lab 3 - begins on Tues Feb 14th Term Project - details posted. Limit

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series

More information

DIFFERENTIAL TRANSFORMER PROTECTION USING THE SEL 387 AND SEL 587 MICROPROCESSOR RELAYS

DIFFERENTIAL TRANSFORMER PROTECTION USING THE SEL 387 AND SEL 587 MICROPROCESSOR RELAYS DIFFERENTIAL TRANSFORMER PROTECTION USING THE SEL 387 AND SEL 587 MICROPROCESSOR RELAYS Ryan Chun Senior Project Electrical Engineering Department California Polytechnic State University San Luis Obispo

More information

Verifying Transformer Differential Compensation Settings

Verifying Transformer Differential Compensation Settings Verifying Transformer Differential Compensation Settings Edsel Atienza and Marion Cooper Schweitzer Engineering Laboratories, Inc. Presented at the 6th International Conference on Large Power Transformers

More information

Microgrid Protection Student Laboratory

Microgrid Protection Student Laboratory Microgrid Protection Student Laboratory Ian Hellman-Wylie and Joey Navarro Senior Project California Polytechnic State University San Luis Obispo 2017 Abstract To better prepare students for careers in

More information

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS Juan Manuel Gers, PhD Example - Single Line Example 1 - Data Calculate the following: 1. The three phase short circuit levels on busbars

More information

EE Lecture 15 (recorded Feb 9, 2011) Fri Feb 15, 2013

EE Lecture 15 (recorded Feb 9, 2011) Fri Feb 15, 2013 EE 5223 - Lecture 15 (recorded Feb 9, 2011) Fri Feb 15, 2013 Ongoing List of Topics: URL: http://www.ece.mtu.edu/faculty/bamork/ee5223/index.htm Term Project - structuring, details Exercises posted Today:

More information

Forward to the Basics: Selected Topics in Distribution Protection

Forward to the Basics: Selected Topics in Distribution Protection Forward to the Basics: Selected Topics in Distribution Protection Lee Underwood and David Costello Schweitzer Engineering Laboratories, Inc. Presented at the IEEE Rural Electric Power Conference Orlando,

More information

Generator Protection GENERATOR CONTROL AND PROTECTION

Generator Protection GENERATOR CONTROL AND PROTECTION Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault

More information

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost

More information

Catastrophic Relay Misoperations and Successful Relay Operation

Catastrophic Relay Misoperations and Successful Relay Operation Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations

More information

Power Distribution: Protection Analysis

Power Distribution: Protection Analysis Power Distribution: Protection Analysis By: Avneet Singh Samra Senior Project ELECTRICAL ENGINEERING DEPARTMENT California Polytechnic State University San Luis Obispo 2016 1 Abstract The objective of

More information

SEL-787-3, -4 Transformer Protection Relay

SEL-787-3, -4 Transformer Protection Relay SEL-787-3, -4 Transformer Protection Relay SEL-787-3E Model SEL-787-3S Model SEL-787-4X Model Major Features and Benefits The SEL-787 Transformer Protection Relay provides unsurpassed protection, integration,

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Bus Protection Fundamentals

Bus Protection Fundamentals Bus Protection Fundamentals Terrence Smith GE Grid Solutions 2017 Texas A&M Protective Relay Conference Bus Protection Requirements High bus fault currents due to large number of circuits connected: CT

More information

Setting Generic Distance Relay UTP-100#WPSC1. in the. Computer-Aided Protection Engineering System (CAPE)

Setting Generic Distance Relay UTP-100#WPSC1. in the. Computer-Aided Protection Engineering System (CAPE) Setting Generic Distance Relay UTP-100#WPSC1 in the Computer-Aided Protection Engineering System (CAPE) Prepared for CAPE Users' Group August 6, 1998 Revised August 24, 1998 Electrocon International, Inc.

More information

Protection of a 138/34.5 kv transformer using SEL relay

Protection of a 138/34.5 kv transformer using SEL relay Scholars' Mine Masters Theses Student Theses and Dissertations Fall 2016 Protection of a 138/34.5 kv transformer using SEL 387-6 relay Aamani Lakkaraju Follow this and additional works at: http://scholarsmine.mst.edu/masters_theses

More information

A proven distribution feeder solution with integrated protection, monitoring, and control

A proven distribution feeder solution with integrated protection, monitoring, and control SEL-35 Protection System A proven distribution feeder solution with integrated protection, monitoring, and control Achieve sensitive and secure fault detection using comprehensive protection functions.

More information

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525.

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525. Time Overcurrent Relays More or less approximates thermal fuse» Allow coordination with fuses Direction of Current nduced Torque Restraining Spring Reset Position Time Dial Setting Disk Basic equation

More information

Tutorial on Symmetrical Components

Tutorial on Symmetrical Components Tutorial on Symmetrical Components Part : Examples Ariana Amberg and Alex Rangel, Schweitzer Engineering Laboratories, nc. Abstract Symmetrical components and the per-unit system are two of the most fundamental

More information

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com ARC FLASH PPE GUIDELINES FOR

More information

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost

More information

TESTING PROCEDURE for SEL 311L DISTANCE and DIFFERENTIAL RELAY

TESTING PROCEDURE for SEL 311L DISTANCE and DIFFERENTIAL RELAY 1 TESTING PROCEDURE for SEL 311L DISTANCE and DIFFERENTIAL RELAY 2 CONTENTS 1. Launching COMMUNICATION and GETTING Setting Parameters from RELAY 2. MEASUREMENT 3. DIFFERENTIAL TEST 4. OVERCURRENT TEST

More information

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2 BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY The BE1-67N Ground Directional Overcurrent Relay provides ground fault protection for transmission and distribution lines by sensing the direction and magnitude

More information

Testing Numerical Transformer Differential Relays

Testing Numerical Transformer Differential Relays Feature Testing Numerical Transformer Differential Relays Steve Turner Beckwith Electric Co., nc. ntroduction Numerical transformer differential relays require careful consideration as to how to test properly.

More information

Protecting Large Machines for Arcing Faults

Protecting Large Machines for Arcing Faults Protecting Large Machines for Arcing Faults March 2, 2010 INTRODUCTION Arcing faults occur due to dirty insulators or broken strands in the stator windings. Such faults if undetected can lead to overheating

More information

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION GEK-00682D INTRODUCTION INTRODUCTION. PRODUCT DESCRIPTION The MDP Digital Time Overcurrent Relay is a digital, microprocessor based, nondirectional overcurrent relay that protects against phase-to-phase

More information

DISTRIBUTION DEVICE COORDINATION

DISTRIBUTION DEVICE COORDINATION DISTRIBUTION DEVICE COORDINATION Kevin Damron & Calvin Howard Avista Utilities Presented March th, 08 At the 5 th Annual Hands-On Relay School Washington State University Pullman, Washington TABLE OF CONTENTS

More information

PD300. Transformer, generator and motor protection Data sheet

PD300. Transformer, generator and motor protection Data sheet PD300 Transformer, generator and motor protection Data sheet DSE_PD300_eng_AO No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam T&D. One of

More information

Transformer Differential Protection Lab

Transformer Differential Protection Lab Montana Tech Library Digital Commons @ Montana Tech Proceedings of the Annual Montana Tech Electrical and General Engineering Symposium Student Scholarship 2016 Transformer Differential Protection Lab

More information

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:

More information

Overcurrent and Overload Protection of AC Machines and Power Transformers

Overcurrent and Overload Protection of AC Machines and Power Transformers Exercise 2 Overcurrent and Overload Protection of AC Machines and Power Transformers EXERCISE OBJECTIVE When you have completed this exercise, you will understand the relationship between the power rating

More information

SEL-311C TRANSMISSION PROTECTION SYSTEM

SEL-311C TRANSMISSION PROTECTION SYSTEM SEL-3C TRANSMISSION PROTECTION SYSTEM ADVANCED TRANSMISSION LINE PROTECTION, AUTOMATION, AND CONTROL Bus ANSI NUMBERS/ACRONYMS AND FUNCTIONS 52 3 3 2 P G 8 O U 27 68 50BF 67 P G Q 50 P G Q 59 P G Q 5 P

More information

Height: inches Width: inches Depth: inches, inches. Listings/Certification UL 1053 ANSI C37-90 IEC 255. General Description

Height: inches Width: inches Depth: inches, inches. Listings/Certification UL 1053 ANSI C37-90 IEC 255. General Description 1rcJll Cutler-Hammer New nformation Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer protection Backup

More information

Time-current Coordination

Time-current Coordination 269 5.2.3.1 Time-current Coordination Time that is controlled by current magnitude permits discriminating faults at one location from another. There are three variables available to discriminate faults,

More information

Protection Introduction

Protection Introduction 1.0 Introduction Protection 2 There are five basic classes of protective relays: Magnitude relays Directional relays Ratio (impedance) relays Differential relays Pilot relays We will study each of these.

More information

Event Analysis Tutorial

Event Analysis Tutorial 1 Event Analysis Tutorial Part 1: Problem Statements David Costello, Schweitzer Engineering Laboratories, Inc. Abstract Event reports have been an invaluable feature in microprocessor-based relays since

More information

Babak Enayati National Grid Thursday, April 17

Babak Enayati National Grid Thursday, April 17 2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April

More information

Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources

Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources Ground Fault Isolation with Loads Fed from Separately Derived Grounded Sources Introduction Ground fault sensing detects current that flows between a source and a (faulted) load traveling on other than

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

DESIGN OF A DIFFERENTIAL PROTECTION SCHEME FOR A 345 KV TRANSMISSION LINE USING SEL 311L RELAYS TARANGINI KAROOR SUBRAHMANYAM

DESIGN OF A DIFFERENTIAL PROTECTION SCHEME FOR A 345 KV TRANSMISSION LINE USING SEL 311L RELAYS TARANGINI KAROOR SUBRAHMANYAM DESIGN OF A DIFFERENTIAL PROTECTION SCHEME FOR A 345 KV TRANSMISSION LINE USING SEL 311L RELAYS by TARANGINI KAROOR SUBRAHMANYAM B.E., OSMANIA UNIVERSITY, 2011 A REPORT submitted in partial fulfillment

More information

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY The BE1-87G is a single or three-phase solid-state variable percentage differential relay designed to provide selective, high-speed, differential protection

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3 Power System Protection Dr. Lionel R. Orama Exclusa, PE Week 3 Operating Principles: Electromagnetic Attraction Relays Readings-Mason Chapters & 3 Operating quantities Electromagnetic attraction Response

More information

Harmonic Distortion Evaluations

Harmonic Distortion Evaluations Harmonic Distortion Evaluations Harmonic currents produced by nonlinear loads can interact adversely with the utility supply system. The interaction often gives rise to voltage and current harmonic distortion

More information

Optimizing HV Capacitor Bank Design, Protection, and Testing Benton Vandiver III ABB Inc.

Optimizing HV Capacitor Bank Design, Protection, and Testing Benton Vandiver III ABB Inc. Optimizing HV Capacitor Bank Design, Protection, and Testing Benton Vandiver III ABB Inc. Abstract - This paper will discuss in detail a capacitor bank protection and control scheme for >100kV systems

More information

Pinhook 500kV Transformer Neutral CT Saturation

Pinhook 500kV Transformer Neutral CT Saturation Russell W. Patterson Tennessee Valley Authority Presented to the 9th Annual Fault and Disturbance Analysis Conference May 1-2, 26 Abstract This paper discusses the saturation of a 5kV neutral CT upon energization

More information

OVERCURRENT PROTECTION RELAY GRD110

OVERCURRENT PROTECTION RELAY GRD110 INSTRUCTION MANUAL OVERCURRENT PROTECTION RELAY GRD110 TOSHIBA Corporation 2002 All Rights Reserved. ( Ver. 3.1) Safety Precautions Before using this product, please read this chapter carefully. 1 This

More information

Substation Testing and Commissioning: Power Transformer Through Fault Test

Substation Testing and Commissioning: Power Transformer Through Fault Test 1 Substation Testing and Commissioning: Power Transformer Through Fault Test M. Talebi, Member, IEEE, Power Grid Engineering Y. Unludag Electric Power System Abstract This paper reviews the advantage of

More information

Directional STANDARDS: Overcurrent Relaying

Directional STANDARDS: Overcurrent Relaying A CABLE Technicians TESTING Approach to Directional STANDARDS: Overcurrent Relaying Understanding O V E R V I E W and O F Testing T H E Directional Relays 1 Moderator n Ron Spataro AVO Training Institute

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

MV network design & devices selection EXERCISE BOOK

MV network design & devices selection EXERCISE BOOK MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester

More information

SEL-351R-4 Recloser Control

SEL-351R-4 Recloser Control -4 Recloser Control Take Control of Your Recloser Major Features and Benefits The -4 Recloser Control is the replacement for the legacy Recloser Control. Throughout the rest of this data sheet, the -4

More information

Optimizing HV Capacitor-Bank Design Protection & Testing

Optimizing HV Capacitor-Bank Design Protection & Testing Optimizing HV Capacitor-Bank Design Protection & Testing Benton Vandiver III ABB Inc. 71st Annual Conference for Protective Relay Engineers Texas A&M University Introduction Shunt Capacitor Bank Considerations

More information

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME Donald M. MACGREGOR Electrocon Int l, Inc. USA eii@electrocon.com Venkat TIRUPATI Electrocon Int l, Inc. USA eii@electrocon.com Russell

More information

Phase and neutral overcurrent protection

Phase and neutral overcurrent protection Phase and neutral overcurrent protection Page 1 ssued June 1999 Changed since July 1998 Data subject to change without notice (SE970165) Features Two-phase or three-phase time-overcurrent and earth fault

More information

Transmission Line Applications of Directional Ground Overcurrent Relays. Working Group D24 Report to the Line Protection Subcommittee January 2014

Transmission Line Applications of Directional Ground Overcurrent Relays. Working Group D24 Report to the Line Protection Subcommittee January 2014 Transmission Line Applications of Directional Ground Overcurrent Relays Working Group D24 Report to the Line Protection Subcommittee January 2014 Working Group Members: Don Lukach (Chairman), Rick Taylor

More information

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Expo - Nov. 3, 2014 Index Normal Distribution System

More information

INSTRUCTIONS. SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays. GE Power Management

INSTRUCTIONS. SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays. GE Power Management g INSTRUCTIONS SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays Manual Part Number: GEK-86069J Copyright 2002 215 Anderson Avenue Markham, Ontario L6E 1B3 Canada Telephone: (905) 294-6222 Fax:

More information

Back to the Basics Event Analysis Using Symmetrical Components

Back to the Basics Event Analysis Using Symmetrical Components Back to the Basics Event Analysis Using Symmetrical Components Amanvir Sudan Schweitzer Engineering Laboratories, Inc. 218 SEL Motivation Overview Back to Basics Introduction Symmetrical components refresher

More information

Using a Multiple Analog Input Distance Relay as a DFR

Using a Multiple Analog Input Distance Relay as a DFR Using a Multiple Analog Input Distance Relay as a DFR Dennis Denison Senior Transmission Specialist Entergy Rich Hunt, M.S., P.E. Senior Field Application Engineer NxtPhase T&D Corporation Presented at

More information

Considerations and Experiences in Implementing Ground Differential Protection for Transformer Protection at TVA

Considerations and Experiences in Implementing Ground Differential Protection for Transformer Protection at TVA Considerations and Experiences in Implementing Ground Differential Protection for Transformer Protection at TVA Meyer Kao - Consultant, Gary Kobet - Tennessee Valley Authority George Pitts -Tennessee Valley

More information

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions ENOSERV 2014 Relay & Protection Training Conference Course Descriptions Day 1 Generation Protection/Motor Bus Transfer Generator Protection: 4 hours This session highlights MV generator protection and

More information

EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER

EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER Objective To analyse the differential protection scheme as applied to a three-phase power transformer

More information

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay Generator Differential Relay The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3G relay offers the following

More information

Relay-assisted commissioning

Relay-assisted commissioning Relay-assisted commissioning by Casper Labuschagne and Normann Fischer, Schweitzer Engineering Laboratories (SEL) Power transformer differential relays were among the first protection relays to use digital

More information

Restricted earth-fault protection function block description

Restricted earth-fault protection function block description function block description Document ID: PRELIMINARY VERSION User s manual version information Version Date Modification Compiled by Preliminary 30.10.2009. Preliminary version, without technical information

More information

g GE POWER MANAGEMENT

g GE POWER MANAGEMENT 745 FREQUENTLY ASKED QUESTIONS 1 I get a communication error with the relay when I try to store a setpoint. This error can occur for several different reasons. First of all, verify that the address is

More information

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection) Differential Protection (Unit protection) Differential Protection Differential protection is the best technique in protection. In this type of protection the electrical quantities entering and leaving

More information

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants Martin Best and Stephanie Mercer, UC Synergetic, LLC Abstract Wind generating plants employ several

More information

Waterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology

Waterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology Waterpower '97 August 5 8, 1997 Atlanta, GA Upgrading Hydroelectric Generator Protection Using Digital Technology Charles J. Beckwith Electric Company 6190-118th Avenue North Largo, FL 33773-3724 U.S.A.

More information

NERC Protection Coordination Webinar Series July 15, Jon Gardell

NERC Protection Coordination Webinar Series July 15, Jon Gardell Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

APPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges.

APPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges. APPLICATION: Basler Electric offers a New Line of digitally controlled brush (static) or brushless excitation systems designed for use with existing Hydro, Gas as well as Diesel driven generators requiring

More information

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed

More information

Unit Protection Differential Relays

Unit Protection Differential Relays Unit Protection PROF. SHAHRAM MONTASER KOUHSARI Current, pu Current, pu Protection Relays - BASICS Note on CT polarity dots Through-current: must not operate Internal fault: must operate The CT currents

More information

INVESTIGATING THE CAPABILITIES OF SEL 787 TRANSFORMER PROTECTION RELAY USING LOW LEVEL SIMULATORS.

INVESTIGATING THE CAPABILITIES OF SEL 787 TRANSFORMER PROTECTION RELAY USING LOW LEVEL SIMULATORS. INVESTIGATING THE CAPABILITIES OF SEL 787 TRANSFORMER PROTECTION RELAY USING LOW LEVEL SIMULATORS. Thesis submitted to the School of Engineering and Information Technology, Murdoch University in partial

More information

Transmission Protection Overview

Transmission Protection Overview Transmission Protection Overview 2017 Hands-On Relay School Daniel Henriod Schweitzer Engineering Laboratories Pullman, WA Transmission Line Protection Objective General knowledge and familiarity with

More information

o9oo INSTRUCTIONS SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays GE Power Management

o9oo INSTRUCTIONS SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays GE Power Management 0 INSTRUCTIONS SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays Manual Part Number: GEK-86069J Copyright 22 215 Anderson Avenue Markham, Ontario L6E 1B3 Canada Telephone: (905) 294-6222 Fax:

More information

Residual instantaneous overcurrent protection function block description

Residual instantaneous overcurrent protection function block description Residual instantaneous overcurrent block description Document ID: PRELIMINARY VERSION User s manual version information Version Date Modification Compiled by Preliminary 30.10.2009. Preliminary version,

More information

Unit Auxiliary Transformer (UAT) Relay Loadability Report

Unit Auxiliary Transformer (UAT) Relay Loadability Report Background and Objective Reliability Standard, PRC 025 1 Generator Relay Loadability (standard), developed under NERC Project 2010 13.2 Phase 2 of Relay Loadability: Generation, was adopted by the NERC

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

Turn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents

Turn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents Turn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents Mariya Babiy 1, Rama Gokaraju 1, Juan Carlos Garcia 2 1 University of Saskatchewan, Saskatoon, Canada 2 Manitoba HVDC Research

More information

Substation Monitoring with TESLA

Substation Monitoring with TESLA Substation Monitoring with TESLA Line 12 11 52-2 52-1 PT S1 21 22 PT S2 Line Protection Relay Current Module 2x 21 Voltage Module 9xAI 3xEI Application Note TESLA is a power system recorder used to monitor

More information

TEST PROCEDURE FOR THE RMS-2012AF PROGRAMMABLE LOGIC CONTROLLER USING AN AMPTECTOR SECONDARY TEST SET.

TEST PROCEDURE FOR THE RMS-2012AF PROGRAMMABLE LOGIC CONTROLLER USING AN AMPTECTOR SECONDARY TEST SET. 1 TEST PROCEDURE FOR THE RMS-2012AF PROGRAMMABLE LOGIC CONTROLLER USING AN AMPTECTOR SECONDARY TEST SET. The Amptector Adapter Plug, shown above, is available from WESTRIP to facilitate the testing of

More information

Distance Relay Response to Transformer Energization: Problems and Solutions

Distance Relay Response to Transformer Energization: Problems and Solutions 1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering

More information

1960 Research Drive, Suite 100, Troy, Michigan with. REVISION: December 10, 2007 (Supersedes previous versions) Prepared by:

1960 Research Drive, Suite 100, Troy, Michigan with. REVISION: December 10, 2007 (Supersedes previous versions) Prepared by: ENGINEERING SERVICES 1960 Research Drive, Suite 100, Troy, Michigan 48083 ARC FLASH REDUCTION with SEPAM RELAY ZONE SELECTIVE INTERLOCKING REVISION: December 10, 2007 (Supersedes previous versions) Prepared

More information

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes Transmission Line Protection Objective General knowledge and familiarity with transmission protection schemes Transmission Line Protection Topics Primary/backup protection Coordination Communication-based

More information

EASUN REYROLLE LIMITED

EASUN REYROLLE LIMITED OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT

More information

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when

More information

Protection of Microgrids Using Differential Relays

Protection of Microgrids Using Differential Relays 1 Protection of Microgrids Using Differential Relays Manjula Dewadasa, Member, IEEE, Arindam Ghosh, Fellow, IEEE and Gerard Ledwich, Senior Member, IEEE Abstract A microgrid provides economical and reliable

More information

ATP modeling of internal transformer faults for relay performance testing

ATP modeling of internal transformer faults for relay performance testing Michigan Technological University Digital Commons @ Michigan Tech Dissertations, Master's Theses and Master's Reports - Open Dissertations, Master's Theses and Master's Reports 2011 ATP modeling of internal

More information

SEL-710 Motor Protection Relay

SEL-710 Motor Protection Relay SEL-710 Motor Protection Relay Motor Protection Relay Major Features and Benefits The SEL-710 Motor Protection Relay provides an exceptional combination of protection, monitoring, control, and communication

More information

Three-phase instantaneous overcurrent protection function block description

Three-phase instantaneous overcurrent protection function block description Three-phase instantaneous overcurrent protection block description Document ID: PRELIMINARY VERSION User s manual version information Version Date Modification Compiled by Preliminary 30.10.2009 Preliminary

More information

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

Fuseless Capacitor Bank Protection

Fuseless Capacitor Bank Protection Fuseless Bank Protection Minnesota Power Systems Conference St. Paul, MN. November 2, 1999 by: Tom Ernst, Minnesota Power Other Papers of Interest Presented at Western Protective Relay Conference, Oct.

More information

Hands-On-Relay School 2015 Distribution Event Analysis. Randy Spacek Protection Engineer Manager

Hands-On-Relay School 2015 Distribution Event Analysis. Randy Spacek Protection Engineer Manager Hands-On-Relay School 2015 Distribution Event Analysis Randy Spacek Protection Engineer Manager OVERVIEW Available Tools Fault Type Identification: line and transformer Relay Event Record: Oscillography

More information