EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER
|
|
- Clifford Taylor
- 5 years ago
- Views:
Transcription
1 EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER Objective To analyse the differential protection scheme as applied to a three-phase power transformer To describe the operation and setting of differential protection. To explain the transformer supply voltage and current waveforms during the differential relay operation. To evaluate the differential protection performance. Introduction The differential protection scheme can be used to protect both the primary and secondary windings of a three-phase transformer against earth faults and phase-to-phase faults. This is possible because the efficiency of the power transformers is high and the magnetizing current is negligibly small. In a differential protection scheme a circuit compare the current entering the protective equipment to the current leaving the equipment, in each phase. Any difference of current of sufficient magnitude operates a relay, which in turn indicates fault clearance. Figure 1 shows a simplified diagram of a single-phase differential protection scheme. The currents entering and leaving the protected equipment (Ipin and lpout) are sensed through two identical current transformers. When there is no fault in the protected equipment, currents Ipin and Ipout are equal and the currents at the transformer secondaries are also equal (Isin = Isout) because the current transformers are identical. When the current transformers are connected with the polarities indicated in Figure 1, 1
2 the secondary currents flow round the circuit and no current flows in the coil of the protective relay (IR = 0), which can be an overcurrent relay. However, when a fault occurs in the protected equipment, currents lpin and lpout are no longer equal. Consequently, currents Isin and Isout are also no longer equal. The current resulting from the difference between these two currents (Isin Isout) flows in the protective relay coil. This trips the protective relay, there by, initiating fault clearance. Similar differential protection scheme can be employed for the protection of transformers. In this case, when the turns ratio of the protected transformer is not unity, the primary and secondary currents are different, and thereby, current transformers with different turns ratio are required for the CT secondary currents to be equal and the residual current IR to be zero under no fault condition. When protecting three-phase power transformers, some additional considerations must be taken into account: There is a 30 phase shift between the primary and secondary currents of a three-phase power transformer that is connected delta-wye or wye-delta and supplies a balanced load. When a three-phase power transformer is connected delta-wye or wye-delta, the zero sequence current on the wye side of the power transformer has no replica on the delta side. The 30 phase shift must be compensated and the zero sequence current on the wye side of the power transformer must be eliminated, for the CT secondary currents to be equal under no fault condition. This is achieved by proper connections of the current transformer secondary windings. A general rule for connecting the current transformers states that the CT secondary windings should be connected in delta when the power transformer windings are connected in wye, and vice versa. Figure 2 shows typical connections of the current transformers for three-phase power transformers connected delta-wye and delta-delta. Note that it is assumed that the ratios of the current transformers have been selected so that the secondary currents supplied by the two groups of current transformers are equal, thereby ensuring balance of the currents in the differential protection system. In practice, it is very difficult to maintain perfect balance of the currents in a differential protection system protecting a three-phase power transformer. This is mainly due to the following factors: Change in the power transformer turns ratio (on transformers with a tap-changing facility). Current transformer mismatch (difficulty in having current transformers with ratios that perfectly balances the differential protection system). Transformer magnetizing current. All these factors unbalance the differential protection system and produce a residual current IR in the differential relay coil. This residual current increases as the line currents flowing through the three-phase power transformer increase. Therefore, the current setting of the differential relay must be increased to prevent undesired relay tripping, thereby reducing the system sensitivity. Differential relays with bias coils are often used in transformer differential protection systems to reduce the negative effect of current 2
3 unbalance on the system sensitivity. Figure 3 shows the bias characteristic of a differential relay. This characteristic shows that the current required to trip the differential relay (differential operating current) increases as the current flowing through the transformer increases. Note that, in general, the sensitivity of transformer differential protection systems is less than that achieved in differential protection systems protecting the stator windings of a synchronous generator. 3
4 Figure 3: Typical bias characteristics of a differential relay Transformer magnetizing inrush, discussed in the first exercise of this unit, is another source of unbalance in transformer differential protection systems. This is because the magnetizing inrush current in the energized winding of a transformer is not replicated in the other windings of the transformer. This appears as a current unbalance to the differential protection system, which superficially, cannot be distinguished from a current unbalance caused by a fault in the transformer. When magnetizing inrush is severe, the current unbalance may easily exceed the current required to trip the differential relay and cause undesired disconnection of the power transformer. Fortunately, transformer magnetizing inrush is a transient phenomenon occurring on transformer energization. Undesired transformer disconnection can therefore be avoided by adding a short time delay to prevent the differential protection system from tripping on transformer magnetizing inrush. Note that after the magnetizing inrush, the magnetizing current stabilizes to a very low value. This current, however, causes a slight current unbalance that is stable under normal operating conditions. To preserve the system stability, this slight current unbalance must be taken into account when setting the differential relay operating current. To obtain additional information on transformer differential protection, refer to section 16.7, entitled "Differential protection", in the third edition of the Protective Relays Application Guide published by GEC Alsthom Measurements Limited. Procedure Summary In the first part of the exercise, set up the equipment in the EMS Workstation and the Protective Relaying Control Station. In the second part of the exercise, connect the equipment as shown in Figures 4 and 5. In this circuit, power transformers connected delta-wye are protected by a differential protection system which mainly consists of a current sensitive relay and line current transformers. When a fault occurs in the power transformers, the overcurrent) relay trips. This energizes time delay relay TD1. Once the time delay is elapsed, contact TD1- A closes to initiate a trip current in the coil of control relay CR1. Contact CR1-C closes to memorize the fault and light up the corresponding reset button. Contact CR1-B 4
5 opens to open contactor CR2, thereby disconnecting the power transformers from the three-phase power source. Open contactor CR3 to prevent operation of the differential protection system. Check whether or not the differential protection system is perfectly balanced when no load is applied to the power transformers. Adjust the current setpoint of the overcurrent relay. With the power transformers supplying power to a balanced three-phase load, initiate earth faults at the primary and secondary windings of the power transformers and observe what happens in the differential protection system. You will close contactor CR3 to allow operation of the differential protection system. You will verify whether or not the differential protection system is stable on transformer magnetizing inrush. You will initiate earth faults and a phase-to-phase fault in the power transformers, and observe the operation of the differential protection system. Equipment Required Protective Relaying Control Station: (record the equipment rating) 1. AC/DC current sensitive relay: 2. EMS: Workstation (record the equipment rating) 1. Power supply: 2. Interconnection module: 3. Universal fault module: 4. Faultable transformers: 5. Transmission grid A: 6. Current transformers: 7. Resistive loads: 8. AC ammeter: 9. AC voltmeter: PROCEDURE CAUTION! High voltages are present In this laboratory exercise! Do not make or modify any banana jack connections with the power on unless otherwise specified! Setting Up the Equipment 1.Ensure that the Protective Relaying Control Station is connected to a three-phase power source. Make sure the DC Power Supply of the Protective Relaying Control Station is turned off. Install AC/DC Current sensitive relay in the Protective Relaying Control Station. 2.Make the following settings on the Universal Fault Module: TD1 time delay s SST1 time interval ~5 s SS12 time interval ~ 1 0 s Note: The control knobs for adjusting the time delay and time intervals are located on time delay relay TD1 and solid-state timers SST1 and SST2 in the Universal Fault Module. 5
6 3.Install the Interconnection Module, Power, Supply, Universal Fault Module, Faultable Transformers, Transmission Grid "A", Current Transformers, Resistive Load, AC Ammeter, and AC Voltmeter in the EMS Workstation. Make sure the Power Supply is turned off and its voltage control knob is set to the O position. Connect the Power Supply to one of the three-phase power outlets on the back panel of the Protective Relaying Control Station. On the Current Transformers module, make sure that all switches are set to the I (close) position to short-circuit the secondary s of the current transformers. Differential Protection of a Three-Phase Power Transformer 4.Connect the Interconnection Module installed in the EMS Workstation to the Interconnection Panel of the Protective Relaying Control Station using the supplied cables. Connect the equipment as shown in Figures 4 and 5 Note: Since a single AC/DC Current Sensitive Belay is available, terminals A2 and A3 are connected to terminal A4 to avoid disturbing the operation of the differential protection system. 5.Make the following settings: On the Faultable Transformers Transformer T1 Fault Switches (FS1 to FS3)... O Transformer T3 Fault Switches (FS1 to FS3) O On Transmission Grid "A" Switch S I (close) Switch S2... O (open) 6
7 Figure 4 Connection diagram of the equipment in the EMS workstation Figure 5 Connection diagram of the equipment in the protective relaying control station On the AC/DC Current Sensitive Relay INPUT switch AC MODE switch OVER CURRENT 7
8 Current setpoint... minimum (fully CCW) Hysteresis ~7.5% On the Universal Fault Module INITIATE FAULT button released position FAULT DURATION switch s Make sure that the current transformers are connected as shown in Figures 4 and 5 then set the switches of current transformers CT1 to CT6 on the Current Transformers module to the O (open) position. 6.On Control Relays 2 of the Protective Relaying Control Station, set the time delay of control relay TD1 to approximately 2 s. Note: -Access to the time delay adjustment knob of control relay TD1 is through a panel on top of the Protective Relaying Control Station. Turn on the DC Power Supply of the Protective Relaying Control Station. On Transmission Grid "A", set switch S3 to the O (open) position to open contactor CR3. This will prevent operation of the differential protection system and allow the operation of the AC/DC Current Sensitive Relay to be observed. 7.On the Resistive Load module, set all toggle switches to the O (open) position to temporarily disconnect the load (resistors R1, R2, and R3) from the secondary windings of the power transformers. Turn on the Power Supply and set the voltage control knob so that the line-to-neutral voltage at the secondary windings of the power transformers Record the circuit voltages and currents in the following blank spaces. E1 = V I1 = A E2 = V I 2 = A E3 = V I3 = A Is the differential protection system perfectly balanced? Briefly explain? 8. Adjust the current setpoint of the AC/DC Current Sensitive Relay to approximately 110% of the residual current (I3) measured in the previous step. To do so, slowly turn the current setpoint adjustment knob clockwise until the tripping indicator (red LED) of the AC/DC Current Sensitive Relay turns OFF. On the Resistive Load module, set the resistance of resistors R1, R2, andr 3 to the value indicated in Figure 2. 9.On the Faultable Transformers, set fault switch FS1 of transformer T1 to the I position to insert an earth fault near the middle of the primary winding of transformer T1. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. 8
9 Record the circuit voltages and currents in the following blank spaces. E1 = V I1 = A E2 = V I2 = A E3 = V I3 = A Describe what happens when an earth fault occurs near the middle of one of the power transformer primary windings. On the Faultable Transformers, set fault switch FS1 of transformer T1 to the O position to remove the fault. 10. On the Faultable Transformers, set fault switch FS3 of transformer T1 to the I position to insert an earth fault near the neutral end of the secondary winding of transformer T1. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. Record the circuit voltages and currents in the following blank spaces E1 = V I1 = A E2 = V E3 = V I2 = A I3 = A Describe what happens when an earth fault occurs near the neutral end of one of the power transformer secondary windings. On the Faultable Transformers, set fault switch FS3 of transformer T1 to the O position to remove the fault. 11.On Transmission Grid "A", set switch S3 to the I (close) position to close contactor CR3. This will allow operation of the differential protection system. 12.On Transmission Grid "A", set switch S1 to the O (open) position to open contactor CR1 and remove power from the power transformers. Energize the power transformers by setting switch S1 on Transmission Grid "A" to the I (close) position. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. 13. Repeat the previous step at least ten times. Does the residual current (I3) sometimes exceed the current setpoint of the AC/DC Current Sensitive Relay on transformer energization? 9
10 EEL3086 SWITCHGEAR AND PROTECTION Ye No Is the differential protection system stable on transformer energization? Yes No Note: The AC/DC Current Sensitive Relay is fairly insensitive to the residual current resulting from the transformer magnetizing inrush. A time delay relay is, however, included in the differential protection system to prevent transformer disconnection in case a high magnetizing inrush would trip the AC/DC Current Sensitive Relay. 14.On Transmission Grid "A", set switch S1 to the I position to close contactor CR1 and energize the power transformers. On the Faultable Transformers, set fault switch FS3 of transformer T1 to the I position to insert an earth fault near the neutral end of the secondary winding of transformer T1. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. Describe what has happened. Has the fault been cleared by the differential protection system? Yes No On the Faultable Transformers, set fault switch FS3 of transformer T1 to the O position to remove the fault. 15.On the Faultable Transformers, set fault switch FS1 of transformer T1 to the I position to insert an earth fault near the middle of the primary winding of transformer T1. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. Describe what has happened. Has the fault been cleared by the differential protection system? Yes No On the Faultable Transformers, set fault switch FS1 of transformer T1 to the O position to remove the fault. 16.On Control Relays 1 of the Protective Relaying Control Station, press the RESET button of control relay CR1 to reset the differential protection system. On the Universal Fault Module, depress the INITIATE FAULT button to produce a phase-tophase fault at the secondary windings of the power transformers. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. Describe what has happened.
11 EEL3086 SWITCHGEAR AND PROTECTION Has the fault been cleared by the differential protection system? Yes No Does the differential protection system protect the power transformers against earth faults as well as phase-to-phase faults? Briefly explain. Turn off the Power Supply. 17. Turn off the DC Power Supply of the Protective Relaying Control Station. Remove all leads and cables. CONCLUSION In this exercise, you learned that differential protection can be used to protect the primary and secondary windings of a three-phase power transformer against earth faults and phase-to-phase faults. You also learned that the sensitivity of transformer differential protection is limited by several factors explained in the discussion of this exercise. You saw that transformer magnetizing inrush unbalances the circulating current circuit of a differential protection system, and may cause undesired transformer disconnection. You saw that transformer disconnection on a magnetizing inrush can be prevented by adding a time delay relay in the differential protection system. REVIEW QUESTIONS 1. A differential protection system protects a. Power transformers against magnetizing inrush. b. The primary and secondary windings of a power transformer against earth faults c. Power transformers against phase-to-phase faults d. Both b and c 2.In general, when using differential protection to protect a three-phase power transformer, the secondary windings of the line current transformers should be connected in.a Wye when the power transformer windings are connected in delta, and vice-versa. b. Wye on-both sides of the power transformer c. Delta on both sides of the power transformer d. None of the above. 3. In transformer differential protection systems, a time delay relay can be used to a. Increase the sensitivity to earth faults occurring on the secondary windings of power transformers b. Compensate the 30 phase shift of the line currents in power transformers connected delta-wye or wye-delta c. Prevent undesired transformer disconnection on transformer magnetizing inrush d. None of the above. CONCLUSIONS Write briefly your own conclusions about this experiment and the theory you have understood and concept learned.
12 EEL3086 SWITCHGEAR AND PROTECTION Preparation for Lab Report EEL 3086 Switchgear and Protection FACULTY OF ENGINEERING, MULTIMEDIA UNIVERSITY, CYBERJAYA LAB REPORT ID NAME: EXPERIMENT DATE: EXPERIMENT TITLE: OBJECTIVE: Instruments/Software required: (refer labsheet and lab equipment) NAME RATING/RANGE/DETAILS NUMBER Introduction: Circuit/Schematic Diagram: (draw a neat sketch of diagram and indicate ratings) EXPERIMENTAL PRECAUTIONS: (Precautions related to experiment alone) Experimental/Design Calculations: (show detailed calculations) EXPERIMENTAL RESULTS: (Refer labsheet) EXPERIMENTAL RESULTS ANALYSIS: (plot graph and analyze results) CONCLUSIONS: (Discuss whether experimental results met the objectives or not)
LVSIM-EMS Help Table of Contents
LVSIM-EMS Help Table of Contents LVSIM-EMS Help... 1 Overview of LVSIM-EMS... 7 LVSIM-EMS Toolbar... 8 LVSIM-EMS Menus... 10 File Menu Commands... 10 Virtual Laboratory File (filename.lvsimweb)... 10 New...
More informationDISCUSSION OF FUNDAMENTALS
Unit 4 AC s UNIT OBJECTIVE After completing this unit, you will be able to demonstrate and explain the operation of ac induction motors using the Squirrel-Cage module and the Capacitor-Start Motor module.
More informationExercise 3. Phase Sequence EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Phase sequence fundamentals
Exercise 3 Phase Sequence EXERCISE OBJECTIVE When you have completed this exercise, you will know what a phase sequence is and why it is important to know the phase sequence of a three-phase power system.
More informationUnit Protection Differential Relays
Unit Protection PROF. SHAHRAM MONTASER KOUHSARI Current, pu Current, pu Protection Relays - BASICS Note on CT polarity dots Through-current: must not operate Internal fault: must operate The CT currents
More informationEXPERIMENT 1 TITLE: SINGLE PHASE TRANSFORMERS - TRANSFORMER REGULATION
EXPERIMENT 1 TITLE: SINGLE PHASE TRANSFORMERS - TRANSFORMER REGULATION OBJECTIVES 1) To determine the voltage regulation of a transformer with varying loads and to discuss capacitive and inductive loading
More informationTransformer Protection
Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing
More informationGenerator Operation with Speed and Voltage Regulation
Exercise 3 Generator Operation with Speed and Voltage Regulation EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the speed governor and automatic voltage regulator used
More informationBusbars and lines are important elements
CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection
More informationCatastrophic Relay Misoperations and Successful Relay Operation
Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations
More informationTECHNICAL BULLETIN 004a Ferroresonance
May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques
More informationTransformer Protection
Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary
More informationThree Phase Transformers
EE/CME 392 Laboratory 6-1 Three Phase Transformers Safety The voltages used in this experiment are lethal. Assemble or modify a circuit only with the breakers off. Do not apply power until the wiring has
More informationwww. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay
Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:
More informationEarth Fault Protection
Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
More informationIntroduction to High-Speed Power Switching
Exercise 3 Introduction to High-Speed Power Switching EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the concept of voltage-type and current-type circuits. You will
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationExperiment 45. Three-Phase Circuits. G 1. a. Using your Power Supply and AC Voltmeter connect the circuit shown OBJECTIVE
Experiment 45 Three-Phase Circuits OBJECTIVE To study the relationship between voltage and current in three-phase circuits. To learn how to make delta and wye connections. To calculate the power in three-phase
More informationOvercurrent and Overload Protection of AC Machines and Power Transformers
Exercise 2 Overcurrent and Overload Protection of AC Machines and Power Transformers EXERCISE OBJECTIVE When you have completed this exercise, you will understand the relationship between the power rating
More informationg GE POWER MANAGEMENT
745 FREQUENTLY ASKED QUESTIONS 1 I get a communication error with the relay when I try to store a setpoint. This error can occur for several different reasons. First of all, verify that the address is
More informationMulti Differential Relay, MDR-2 DESCRIPTION OF OPTIONS
Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS Option C4 Block differential current protection Description of option Functional descriptions Parameter list Document no.: 4189340397C SW version:
More informationwww. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay
Generator Differential Relay The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3G relay offers the following
More informationShortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller
Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of
More informationHands On Relay School Open Lecture Transformer Differential Protection Scott Cooper
Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost
More informationBidirectional PWM DC Motor Drive with Regenerative Braking
Exercise 2 Bidirectional PWM DC Motor Drive with Regenerative Braking EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with two better types of PWM dc motor drives: the buck-boost
More informationA NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG
A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when
More informationHarmonic Reduction using Thyristor 12-Pulse Converters
Exercise 5 Harmonic Reduction using Thyristor 12-Pulse Converters EXERCISE OBJECTIVE When you have completed this exercise, you will understand what a thyristor 12- pulse converter is and how it operates.
More informationDynamic Power Factor Correction Using a STATCOM
Exercise 2 Dynamic Power Factor Correction Using a STATCOM EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the reasoning behind the usage of power factor correction
More informationVoltage-Versus-Speed Characteristic of a Wind Turbine Generator
Exercise 1 Voltage-Versus-Speed Characteristic of a Wind Turbine Generator EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the principle of electromagnetic induction.
More informationUSING SUPERIMPOSED PRINCIPLES (DELTA) IN PROTECTION TECHNIQUES IN AN INCREASINGLY CHALLENGING POWER NETWORK
USING SUPERIMPOSED PRINCIPLES (DELTA) IN PROTECTION TECHNIQUES IN AN INCREASINGLY CHALLENGING POWER NETWORK P Horton, S Swain patricia.horton@ge.com, simon.swain@ge.com UK INTRODUCTION Superimposed techniques
More informationThe measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms
Why Measure Winding Resistance? The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms Partial or dead short-circuited
More informationPOWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.
POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products
More informationHands On Relay School Open Lecture Transformer Differential Protection Scott Cooper
Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost
More informationSolving Series Circuits and Kirchhoff s Voltage Law
Exercise 6 Solving Series Circuits and Kirchhoff s Voltage Law EXERCISE OBJECTIVE When you have completed this exercise, you will be able to calculate the equivalent resistance of multiple resistors in
More informationExercise 6. Range and Angle Tracking Performance (Radar-Dependent Errors) EXERCISE OBJECTIVE
Exercise 6 Range and Angle Tracking Performance EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the radardependent sources of error which limit range and angle tracking
More informationELECTRICAL POWER ENGINEERING
Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation
More informationELECTRICAL POWER TRANSMISSION TRAINER
ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering
More informationExercise 10. Transformers EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to transformers
Exercise 10 Transformers EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the basic operating principles of transformers, as well as with the different ratios of transformers:
More informationXD1-T Transformer differential protection relay. Manual XD1-T (Revision A)
XD1-T Transformer differential protection relay Manual XD1-T (Revision A) Woodward Manual XD1-T GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information
More informationSpeed Feedback and Current Control in PWM DC Motor Drives
Exercise 3 Speed Feedback and Current Control in PWM DC Motor Drives EXERCISE OBJECTIVE When you have completed this exercise, you will know how to improve the regulation of speed in PWM dc motor drives.
More informationMcPherson Voltage Regulators 4501 NW 27 Ave Miami FL
McPherson Voltage Regulators 4501 NW 27 Ave Miami FL 33142 305-634-1511 To avoid of possible personal injury or equipment damage read and understand this manual before installation. (A.V.R) 208 / 380 /
More informationSection 6: System Grounding Bill Brown, P.E., Square D Engineering Services
Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Introduction The topic of system grounding is extremely important, as it affects the susceptibility of the system to voltage
More informationOvercurrent Elements
Exercise Objectives Hands-On Relay Testing Session Overcurrent Elements After completing this exercise, you should be able to do the following: Identify overcurrent element settings. Determine effective
More informationNERC Protection Coordination Webinar Series July 15, Jon Gardell
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationInternational Journal of Advance Engineering and Research Development ANALYSIS OF INTERNAL AND EXTERNAL FAULT FOR STAR DELTA TRANSFORMER USING PSCAD
Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 6, June -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 ANALYSIS OF
More informationExercise 7. The Buck/Boost Chopper EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. The Buck/Boost Chopper
Exercise 7 The Buck/Boost Chopper EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the operation of the buck/boost chopper. DISCUSSION OUTLINE The Discussion of this
More informationProblems connected with Commissioning of Power Transformers
Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.
More informationDifferential Protection with REF 542plus Feeder Terminal
Differential Protection with REF 542plus Application and Setting Guide kansikuva_bw 1MRS 756281 Issued: 09.01.2007 Version: A Differential Protection with REF 542plus Application and Setting Guide Contents:
More informationExercise 3. Doubly-Fed Induction Generators EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Doubly-fed induction generator operation
Exercise 3 Doubly-Fed Induction Generators EXERCISE OBJECTIVE hen you have completed this exercise, you will be familiar with the operation of three-phase wound-rotor induction machines used as doubly-fed
More informationPinhook 500kV Transformer Neutral CT Saturation
Russell W. Patterson Tennessee Valley Authority Presented to the 9th Annual Fault and Disturbance Analysis Conference May 1-2, 26 Abstract This paper discusses the saturation of a 5kV neutral CT upon energization
More informationNOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS
NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS Ljubomir KOJOVIC Cooper Power Systems - U.S.A. Lkojovic@cooperpower.com INTRODUCTION In steel facilities that use Electric Arc Furnaces (EAFs) to manufacture
More informationPMSM Control Using a Three-Phase, Six-Step 120 Modulation Inverter
Exercise 1 PMSM Control Using a Three-Phase, Six-Step 120 Modulation Inverter EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with six-step 120 modulation. You will know
More informationDEPARTMENT OF ELECTRICAL ENGINEERING BENGAL ENGINEERING AND SCIENCE UNIVERSITY, SHIBPUR
DEPARTMENT OF ELECTRICAL ENGINEERING BENGAL ENGINEERING AND SCIENCE UNIVERSITY, SHIBPUR Power system protection Laboratory (EE 852) 8 th Semester Electrical Expt. No. 852/1 BIFFI S METHOD FOR TESTING CURRENT
More informationg GE POWER MANAGEMENT
469 FREQUENTLY ASKED QUESTIONS 1 Can not communicate through the front port RS232 Check the following settings Communication port on your computer ( com1, com2 com3 etc ) Parity settings must match between
More informationVoltage Compensation of AC Transmission Lines Using a STATCOM
Exercise 1 Voltage Compensation of AC Transmission Lines Using a STATCOM EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the operating principles of STATCOMs used for
More informationExercise 3-3. Manual Reversing Starters EXERCISE OBJECTIVE DISCUSSION. Build manual reversing starters and understand how they work.
Exercise 3-3 Manual Reversing Starters EXERCISE OBJECTIVE Build manual reversing starters and understand how they work. DISCUSSION Reversing motor rotation direction is a common operation in industrial
More information6. List two possible arrangements of a Yconnection and give one application
OBJECTIVES PI 26.35-1 Electrical Equipment - Course PI 30.2 THREE PHASE SYSTEMS On completion of this module the student will be able to: 1. In a few sentences explain how three phase voltages are produced
More informationPower System Protection Manual
Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,
More informationNORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:
NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information
More informationCourse No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content
Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION Sr. No. Course Content 1.0 Fault Current Calculations 1.1 Introduction to per unit and percentage impedance 1.2
More informationGrid-Tied Home Energy Production Using a Solar or Wind Power Inverter without DC-to-DC Converter
Exercise 3 Grid-Tied Home Energy Production Using a Solar or Wind Power Inverter without DC-to-DC Converter EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with grid-tied
More informationElectricity Fundamentals Training System
Electricity Fundamentals Training System LabVolt Series Datasheet Festo Didactic en 120 V - 60 Hz 07/2018 Table of Contents General Description 2 Courseware 2 Topic Coverage 2 List of Available Training
More informationEASUN REYROLLE LIMITED
OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT
More informationThis document covers common questions concerning the design of an effectively grounded system.
This document covers common questions concerning the design of an effectively grounded system. To prevent against temporary overvoltage conditions when a line-to-ground fault occurs on the power grid.
More informationEE 340L Experiment 6: Synchronous Generator - Operation with the Grid
EE 340L Experiment 6: Synchronous Generator - Operation with the Grid The synchronous machine (see Fig. 1) is mechanically coupled to the Four-Quadrant Dynamometer/Power Supply (see Fig. 2) using a timing
More informationIssued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY
WN U-60 Attachment C to Schedule 152, Page 1 SCHEDULE 152 APPLICATION FOR INTERCONNECTING A GENERATING FACILITY TIER 2 OR TIER 3 This Application is considered complete when it provides all applicable
More informationUtility Interconnection and System Protection
Utility Interconnection and System Protection Alex Steselboim President, Advanced Power Technologies, Inc. Utility paralleling vs. isolated operation. Isochronous kw load sharing Reactive power (VAR) sharing
More information1. SQUIRREL CAGE AC MOTOR. NO LOAD TEST
1. SQUIRREL CAGE AC MOTOR. NO LOAD TEST 1.1 INTRODUCTION. DESCRIPTION OF THE EXPERIMENT The three-phase induction motor carries a three-phase winding on its stator. The rotor is either a wound type or
More informationClosed-Loop Position Control, Proportional Mode
Exercise 4 Closed-Loop Position Control, Proportional Mode EXERCISE OBJECTIVE To describe the proportional control mode; To describe the advantages and disadvantages of proportional control; To define
More information2015 Relay School Bus Protection Mike Kockott March, 2015
2015 Relay School Bus Protection Mike Kockott March, 2015 History of Bus Protection Circulating current differential (1900s) High impedance differential (1940s) Percentage restrained differential (1960s)
More informationSolving Parallel and Mixed Circuits, and Kirchhoff s Current Law
Exercise 7 Solving Parallel and Mixed Circuits, and Kirchhoff s Current Law EXERCISE OBJECTIVE When you have completed this exercise, you will be able to calculate the equivalent resistance of multiple
More informationEE 210: CIRCUITS AND DEVICES
EE 210: CIRCUITS AND DEVICES LAB #3: VOLTAGE AND CURRENT MEASUREMENTS This lab features a tutorial on the instrumentation that you will be using throughout the semester. More specifically, you will see
More informationPrimary Resistor Starters with Time Relays
Exercise 6-3 Primary Resistor Starters with Time Relays EXERCISE OBJECTIVE Understand how a time relay can be used jointly with primary resistor starters. DISCUSSION Primary resistor starters are used
More informationProtecting Large Machines for Arcing Faults
Protecting Large Machines for Arcing Faults March 2, 2010 INTRODUCTION Arcing faults occur due to dirty insulators or broken strands in the stator windings. Such faults if undetected can lead to overheating
More informationExercise 9. Electromagnetism and Inductors EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Magnetism, magnets, and magnetic field
Exercise 9 Electromagnetism and Inductors EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the concepts of magnetism, magnets, and magnetic field, as well as electromagnetism
More informationAlternator winding pitch and power system design
Our energy working for you. TM Power topic #5981 Technical information from Cummins Power Generation Alternator winding pitch and power system design White Paper Rich Scoggins Applications Engineering
More informationTransformer Fault Categories
Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)
More informationXD1-T - Transformer differential protection relay
XD1-T - Transformer differential protection relay Contents 1. Application and features 2. Design 3. Characteristics 3.1 Operating principle of the differential protection 3.2 Balancing of phases and current
More informationImpact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis
1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current
More informationPOWER SYSTEM II LAB MANUAL
POWER SYSTEM II LAB MANUAL (CODE : EE 692) JIS COLLEGE OF ENGINEERING (An Autonomous Institution) Electrical Engineering Department Kalyani, Nadia POWER SYSTEM II CODE : EE 692 Contacts :3P Credits : 2
More informationANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION
ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION R.Rahnavard 1, 2 M.Valizadeh 1 A.A.B.Sharifian 2 S.H.Hosseini 1 rerahnavard@gmail.com mj_valizad@yahoo.com hosseini@tabrizu.ac.ir
More informationImpact of Incipient Faults on Sensitive Protection
Impact of Incipient Faults on Sensitive Protection Paper Authors: Ilia Voloh GE Grid Solutions Zhihan Xu, Ilia Voloh GE Grid Solutions Leonardo Torelli CSE-Uniserve Presented by: Tom Ernst GE Grid Solutions
More informationSPAD 346 C. Stabilized Differential Relay. User s manual and Technical description SPAD 346 C V ~ V. f n SPCD 3D53 SPCJ 4D28
SPAD 6 C Stabilized Differential Relay User s manual and Technical description f n = 50Hz 60Hz I n = A 5A ( I ) I n = A 5A ( I ) I n = A 5A ( I 0 ) I n = A 5A ( I 0 ) 5 I I d L L I L I > IRF I 0 > I 0
More informationExtensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network
Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example
More informationCHAPTER 3 OVER CURRENT AND EARTH FAULT RELAY COORDINATION
18 CHAPTER 3 OVER CURRENT AND EARTH FAULT RELAY COORDINATION 3.1. OVERVIEW OF RELAY COORDINATION Relay coordination has to be carried out based on many other power system studies and Equipment Sizing calculation,
More informationAdvanced Test Equipment Rentals ATEC (2832)
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) The toolbox for substation 3-phase testing Three currents and four voltages Stand-alone functionality Rugged and reliable
More informationTesting Numerical Transformer Differential Relays
Feature Testing Numerical Transformer Differential Relays Steve Turner Beckwith Electric Co., nc. ntroduction Numerical transformer differential relays require careful consideration as to how to test properly.
More informationPower Station Electrical Protection A 2 B 2 C 2 Neutral C.T E M L } a 2 b 2 c 2 M M M CT Restricted E/F Relay L L L TO TRIP CIRCUIT Contents 1 The Need for Protection 2 1.1 Types of Faults............................
More informationResidual Current Operated Circuit-Breakers (RCCBs)
Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted
More informationThis transistor circuit has a voltage divider circuit with an emitter resistor for bias stability.
When you have completed this exercise, you will be able to describe the temperature effects on a voltage divider bias circuit by using a typical transistor circuit. You will verify your results with a
More informationLab 1: Basic Lab Equipment and Measurements
Abstract: Lab 1: Basic Lab Equipment and Measurements This lab exercise introduces the basic measurement instruments that will be used throughout the course. These instruments include multimeters, oscilloscopes,
More informationCapstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:
Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation
More informationDIGITAL EARTH FAULT RELAY
DIGITAL IDMT / DEFINITE TIME / INSTANTANEOUS Features Compact IDMT (4 IEC curves), Definite Time & Instantaneous Wide setting ranges Fully digital acquisition & processing of data Wide operating voltages
More informationExercise 1. Basic PWM DC Motor Drive EXERCISE OBJECTIVE DISCUSSION OUTLINE. Block diagram of a basic PWM dc motor drive DISCUSSION
Exercise 1 Basic PWM DC Motor Drive EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the most basic type of PWM dc motor drive: the buck chopper dc motor drive. You will
More informationENGINE GOVERNING SYSTEMS LSM200 SERIES LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER
ENGINE GOVERNING SYSTEMS LSM200 SERIES LOAD SHARING MODULE MEMBER GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA 01001-2907, USA LSM200 SERIES LOAD SHARING MODULE PRODUCT TECHNICAL INFORMATION PTI
More informationExercise 8. The Four-Quadrant Chopper EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. The Four-Quadrant Chopper
Exercise 8 The Four-Quadrant Chopper EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the operation of the four-quadrant chopper. DISCUSSION OUTLINE The Discussion of
More informationDistributed Generation Application Form (Generation of Greater than 20 kw to 15 MW)
Distributed Generation Application Form (Generation of Greater than 20 kw to 15 MW) PSC-6028 R(03-04-04) Name & Address Distributed By Name & Address Supplied By Public Service Commission of Wisconsin
More informationA NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *
Iranian Journal of Science & Technology, Transaction B, Engineering, Vol. 30, No. B6, pp 643-654 Printed in The Islamic Republic of Iran, 2006 Shiraz University A NEW DIFFERENTIAL PROTECTION ALGORITHM
More informationCourseware Sample F0
Electric Power / Controls Courseware Sample 85822-F0 A ELECTRIC POWER / CONTROLS COURSEWARE SAMPLE by the Staff of Lab-Volt Ltd. Copyright 2009 Lab-Volt Ltd. All rights reserved. No part of this publication
More informationCHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY
CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY LIST OF TOPICS 1 Electric Circuit Principles 2 Electronic Circuit Principles 3 Generation 4 Distribution 5 Utilisation The expected learning outcome is
More informationUNIVERSITY OF TECHNOLOGY, JAMAICA SCHOOL OF ENGENEERING. Electrical Engineering Science. Laboratory Manual
UNIVERSITY OF TECHNOLOGY, JAMAICA SCHOOL OF ENGENEERING Electrical Engineering Science Laboratory Manual Table of Contents Experiment #1 OHM S LAW... 3 Experiment # 2 SERIES AND PARALLEL CIRCUITS... 8
More information