EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER

Size: px
Start display at page:

Download "EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER"

Transcription

1 EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER Objective To analyse the differential protection scheme as applied to a three-phase power transformer To describe the operation and setting of differential protection. To explain the transformer supply voltage and current waveforms during the differential relay operation. To evaluate the differential protection performance. Introduction The differential protection scheme can be used to protect both the primary and secondary windings of a three-phase transformer against earth faults and phase-to-phase faults. This is possible because the efficiency of the power transformers is high and the magnetizing current is negligibly small. In a differential protection scheme a circuit compare the current entering the protective equipment to the current leaving the equipment, in each phase. Any difference of current of sufficient magnitude operates a relay, which in turn indicates fault clearance. Figure 1 shows a simplified diagram of a single-phase differential protection scheme. The currents entering and leaving the protected equipment (Ipin and lpout) are sensed through two identical current transformers. When there is no fault in the protected equipment, currents Ipin and Ipout are equal and the currents at the transformer secondaries are also equal (Isin = Isout) because the current transformers are identical. When the current transformers are connected with the polarities indicated in Figure 1, 1

2 the secondary currents flow round the circuit and no current flows in the coil of the protective relay (IR = 0), which can be an overcurrent relay. However, when a fault occurs in the protected equipment, currents lpin and lpout are no longer equal. Consequently, currents Isin and Isout are also no longer equal. The current resulting from the difference between these two currents (Isin Isout) flows in the protective relay coil. This trips the protective relay, there by, initiating fault clearance. Similar differential protection scheme can be employed for the protection of transformers. In this case, when the turns ratio of the protected transformer is not unity, the primary and secondary currents are different, and thereby, current transformers with different turns ratio are required for the CT secondary currents to be equal and the residual current IR to be zero under no fault condition. When protecting three-phase power transformers, some additional considerations must be taken into account: There is a 30 phase shift between the primary and secondary currents of a three-phase power transformer that is connected delta-wye or wye-delta and supplies a balanced load. When a three-phase power transformer is connected delta-wye or wye-delta, the zero sequence current on the wye side of the power transformer has no replica on the delta side. The 30 phase shift must be compensated and the zero sequence current on the wye side of the power transformer must be eliminated, for the CT secondary currents to be equal under no fault condition. This is achieved by proper connections of the current transformer secondary windings. A general rule for connecting the current transformers states that the CT secondary windings should be connected in delta when the power transformer windings are connected in wye, and vice versa. Figure 2 shows typical connections of the current transformers for three-phase power transformers connected delta-wye and delta-delta. Note that it is assumed that the ratios of the current transformers have been selected so that the secondary currents supplied by the two groups of current transformers are equal, thereby ensuring balance of the currents in the differential protection system. In practice, it is very difficult to maintain perfect balance of the currents in a differential protection system protecting a three-phase power transformer. This is mainly due to the following factors: Change in the power transformer turns ratio (on transformers with a tap-changing facility). Current transformer mismatch (difficulty in having current transformers with ratios that perfectly balances the differential protection system). Transformer magnetizing current. All these factors unbalance the differential protection system and produce a residual current IR in the differential relay coil. This residual current increases as the line currents flowing through the three-phase power transformer increase. Therefore, the current setting of the differential relay must be increased to prevent undesired relay tripping, thereby reducing the system sensitivity. Differential relays with bias coils are often used in transformer differential protection systems to reduce the negative effect of current 2

3 unbalance on the system sensitivity. Figure 3 shows the bias characteristic of a differential relay. This characteristic shows that the current required to trip the differential relay (differential operating current) increases as the current flowing through the transformer increases. Note that, in general, the sensitivity of transformer differential protection systems is less than that achieved in differential protection systems protecting the stator windings of a synchronous generator. 3

4 Figure 3: Typical bias characteristics of a differential relay Transformer magnetizing inrush, discussed in the first exercise of this unit, is another source of unbalance in transformer differential protection systems. This is because the magnetizing inrush current in the energized winding of a transformer is not replicated in the other windings of the transformer. This appears as a current unbalance to the differential protection system, which superficially, cannot be distinguished from a current unbalance caused by a fault in the transformer. When magnetizing inrush is severe, the current unbalance may easily exceed the current required to trip the differential relay and cause undesired disconnection of the power transformer. Fortunately, transformer magnetizing inrush is a transient phenomenon occurring on transformer energization. Undesired transformer disconnection can therefore be avoided by adding a short time delay to prevent the differential protection system from tripping on transformer magnetizing inrush. Note that after the magnetizing inrush, the magnetizing current stabilizes to a very low value. This current, however, causes a slight current unbalance that is stable under normal operating conditions. To preserve the system stability, this slight current unbalance must be taken into account when setting the differential relay operating current. To obtain additional information on transformer differential protection, refer to section 16.7, entitled "Differential protection", in the third edition of the Protective Relays Application Guide published by GEC Alsthom Measurements Limited. Procedure Summary In the first part of the exercise, set up the equipment in the EMS Workstation and the Protective Relaying Control Station. In the second part of the exercise, connect the equipment as shown in Figures 4 and 5. In this circuit, power transformers connected delta-wye are protected by a differential protection system which mainly consists of a current sensitive relay and line current transformers. When a fault occurs in the power transformers, the overcurrent) relay trips. This energizes time delay relay TD1. Once the time delay is elapsed, contact TD1- A closes to initiate a trip current in the coil of control relay CR1. Contact CR1-C closes to memorize the fault and light up the corresponding reset button. Contact CR1-B 4

5 opens to open contactor CR2, thereby disconnecting the power transformers from the three-phase power source. Open contactor CR3 to prevent operation of the differential protection system. Check whether or not the differential protection system is perfectly balanced when no load is applied to the power transformers. Adjust the current setpoint of the overcurrent relay. With the power transformers supplying power to a balanced three-phase load, initiate earth faults at the primary and secondary windings of the power transformers and observe what happens in the differential protection system. You will close contactor CR3 to allow operation of the differential protection system. You will verify whether or not the differential protection system is stable on transformer magnetizing inrush. You will initiate earth faults and a phase-to-phase fault in the power transformers, and observe the operation of the differential protection system. Equipment Required Protective Relaying Control Station: (record the equipment rating) 1. AC/DC current sensitive relay: 2. EMS: Workstation (record the equipment rating) 1. Power supply: 2. Interconnection module: 3. Universal fault module: 4. Faultable transformers: 5. Transmission grid A: 6. Current transformers: 7. Resistive loads: 8. AC ammeter: 9. AC voltmeter: PROCEDURE CAUTION! High voltages are present In this laboratory exercise! Do not make or modify any banana jack connections with the power on unless otherwise specified! Setting Up the Equipment 1.Ensure that the Protective Relaying Control Station is connected to a three-phase power source. Make sure the DC Power Supply of the Protective Relaying Control Station is turned off. Install AC/DC Current sensitive relay in the Protective Relaying Control Station. 2.Make the following settings on the Universal Fault Module: TD1 time delay s SST1 time interval ~5 s SS12 time interval ~ 1 0 s Note: The control knobs for adjusting the time delay and time intervals are located on time delay relay TD1 and solid-state timers SST1 and SST2 in the Universal Fault Module. 5

6 3.Install the Interconnection Module, Power, Supply, Universal Fault Module, Faultable Transformers, Transmission Grid "A", Current Transformers, Resistive Load, AC Ammeter, and AC Voltmeter in the EMS Workstation. Make sure the Power Supply is turned off and its voltage control knob is set to the O position. Connect the Power Supply to one of the three-phase power outlets on the back panel of the Protective Relaying Control Station. On the Current Transformers module, make sure that all switches are set to the I (close) position to short-circuit the secondary s of the current transformers. Differential Protection of a Three-Phase Power Transformer 4.Connect the Interconnection Module installed in the EMS Workstation to the Interconnection Panel of the Protective Relaying Control Station using the supplied cables. Connect the equipment as shown in Figures 4 and 5 Note: Since a single AC/DC Current Sensitive Belay is available, terminals A2 and A3 are connected to terminal A4 to avoid disturbing the operation of the differential protection system. 5.Make the following settings: On the Faultable Transformers Transformer T1 Fault Switches (FS1 to FS3)... O Transformer T3 Fault Switches (FS1 to FS3) O On Transmission Grid "A" Switch S I (close) Switch S2... O (open) 6

7 Figure 4 Connection diagram of the equipment in the EMS workstation Figure 5 Connection diagram of the equipment in the protective relaying control station On the AC/DC Current Sensitive Relay INPUT switch AC MODE switch OVER CURRENT 7

8 Current setpoint... minimum (fully CCW) Hysteresis ~7.5% On the Universal Fault Module INITIATE FAULT button released position FAULT DURATION switch s Make sure that the current transformers are connected as shown in Figures 4 and 5 then set the switches of current transformers CT1 to CT6 on the Current Transformers module to the O (open) position. 6.On Control Relays 2 of the Protective Relaying Control Station, set the time delay of control relay TD1 to approximately 2 s. Note: -Access to the time delay adjustment knob of control relay TD1 is through a panel on top of the Protective Relaying Control Station. Turn on the DC Power Supply of the Protective Relaying Control Station. On Transmission Grid "A", set switch S3 to the O (open) position to open contactor CR3. This will prevent operation of the differential protection system and allow the operation of the AC/DC Current Sensitive Relay to be observed. 7.On the Resistive Load module, set all toggle switches to the O (open) position to temporarily disconnect the load (resistors R1, R2, and R3) from the secondary windings of the power transformers. Turn on the Power Supply and set the voltage control knob so that the line-to-neutral voltage at the secondary windings of the power transformers Record the circuit voltages and currents in the following blank spaces. E1 = V I1 = A E2 = V I 2 = A E3 = V I3 = A Is the differential protection system perfectly balanced? Briefly explain? 8. Adjust the current setpoint of the AC/DC Current Sensitive Relay to approximately 110% of the residual current (I3) measured in the previous step. To do so, slowly turn the current setpoint adjustment knob clockwise until the tripping indicator (red LED) of the AC/DC Current Sensitive Relay turns OFF. On the Resistive Load module, set the resistance of resistors R1, R2, andr 3 to the value indicated in Figure 2. 9.On the Faultable Transformers, set fault switch FS1 of transformer T1 to the I position to insert an earth fault near the middle of the primary winding of transformer T1. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. 8

9 Record the circuit voltages and currents in the following blank spaces. E1 = V I1 = A E2 = V I2 = A E3 = V I3 = A Describe what happens when an earth fault occurs near the middle of one of the power transformer primary windings. On the Faultable Transformers, set fault switch FS1 of transformer T1 to the O position to remove the fault. 10. On the Faultable Transformers, set fault switch FS3 of transformer T1 to the I position to insert an earth fault near the neutral end of the secondary winding of transformer T1. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. Record the circuit voltages and currents in the following blank spaces E1 = V I1 = A E2 = V E3 = V I2 = A I3 = A Describe what happens when an earth fault occurs near the neutral end of one of the power transformer secondary windings. On the Faultable Transformers, set fault switch FS3 of transformer T1 to the O position to remove the fault. 11.On Transmission Grid "A", set switch S3 to the I (close) position to close contactor CR3. This will allow operation of the differential protection system. 12.On Transmission Grid "A", set switch S1 to the O (open) position to open contactor CR1 and remove power from the power transformers. Energize the power transformers by setting switch S1 on Transmission Grid "A" to the I (close) position. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. 13. Repeat the previous step at least ten times. Does the residual current (I3) sometimes exceed the current setpoint of the AC/DC Current Sensitive Relay on transformer energization? 9

10 EEL3086 SWITCHGEAR AND PROTECTION Ye No Is the differential protection system stable on transformer energization? Yes No Note: The AC/DC Current Sensitive Relay is fairly insensitive to the residual current resulting from the transformer magnetizing inrush. A time delay relay is, however, included in the differential protection system to prevent transformer disconnection in case a high magnetizing inrush would trip the AC/DC Current Sensitive Relay. 14.On Transmission Grid "A", set switch S1 to the I position to close contactor CR1 and energize the power transformers. On the Faultable Transformers, set fault switch FS3 of transformer T1 to the I position to insert an earth fault near the neutral end of the secondary winding of transformer T1. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. Describe what has happened. Has the fault been cleared by the differential protection system? Yes No On the Faultable Transformers, set fault switch FS3 of transformer T1 to the O position to remove the fault. 15.On the Faultable Transformers, set fault switch FS1 of transformer T1 to the I position to insert an earth fault near the middle of the primary winding of transformer T1. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. Describe what has happened. Has the fault been cleared by the differential protection system? Yes No On the Faultable Transformers, set fault switch FS1 of transformer T1 to the O position to remove the fault. 16.On Control Relays 1 of the Protective Relaying Control Station, press the RESET button of control relay CR1 to reset the differential protection system. On the Universal Fault Module, depress the INITIATE FAULT button to produce a phase-tophase fault at the secondary windings of the power transformers. While doing this, observe the circuit currents and the tripping indicator on the AC/DC Current Sensitive Relay. Describe what has happened.

11 EEL3086 SWITCHGEAR AND PROTECTION Has the fault been cleared by the differential protection system? Yes No Does the differential protection system protect the power transformers against earth faults as well as phase-to-phase faults? Briefly explain. Turn off the Power Supply. 17. Turn off the DC Power Supply of the Protective Relaying Control Station. Remove all leads and cables. CONCLUSION In this exercise, you learned that differential protection can be used to protect the primary and secondary windings of a three-phase power transformer against earth faults and phase-to-phase faults. You also learned that the sensitivity of transformer differential protection is limited by several factors explained in the discussion of this exercise. You saw that transformer magnetizing inrush unbalances the circulating current circuit of a differential protection system, and may cause undesired transformer disconnection. You saw that transformer disconnection on a magnetizing inrush can be prevented by adding a time delay relay in the differential protection system. REVIEW QUESTIONS 1. A differential protection system protects a. Power transformers against magnetizing inrush. b. The primary and secondary windings of a power transformer against earth faults c. Power transformers against phase-to-phase faults d. Both b and c 2.In general, when using differential protection to protect a three-phase power transformer, the secondary windings of the line current transformers should be connected in.a Wye when the power transformer windings are connected in delta, and vice-versa. b. Wye on-both sides of the power transformer c. Delta on both sides of the power transformer d. None of the above. 3. In transformer differential protection systems, a time delay relay can be used to a. Increase the sensitivity to earth faults occurring on the secondary windings of power transformers b. Compensate the 30 phase shift of the line currents in power transformers connected delta-wye or wye-delta c. Prevent undesired transformer disconnection on transformer magnetizing inrush d. None of the above. CONCLUSIONS Write briefly your own conclusions about this experiment and the theory you have understood and concept learned.

12 EEL3086 SWITCHGEAR AND PROTECTION Preparation for Lab Report EEL 3086 Switchgear and Protection FACULTY OF ENGINEERING, MULTIMEDIA UNIVERSITY, CYBERJAYA LAB REPORT ID NAME: EXPERIMENT DATE: EXPERIMENT TITLE: OBJECTIVE: Instruments/Software required: (refer labsheet and lab equipment) NAME RATING/RANGE/DETAILS NUMBER Introduction: Circuit/Schematic Diagram: (draw a neat sketch of diagram and indicate ratings) EXPERIMENTAL PRECAUTIONS: (Precautions related to experiment alone) Experimental/Design Calculations: (show detailed calculations) EXPERIMENTAL RESULTS: (Refer labsheet) EXPERIMENTAL RESULTS ANALYSIS: (plot graph and analyze results) CONCLUSIONS: (Discuss whether experimental results met the objectives or not)

LVSIM-EMS Help Table of Contents

LVSIM-EMS Help Table of Contents LVSIM-EMS Help Table of Contents LVSIM-EMS Help... 1 Overview of LVSIM-EMS... 7 LVSIM-EMS Toolbar... 8 LVSIM-EMS Menus... 10 File Menu Commands... 10 Virtual Laboratory File (filename.lvsimweb)... 10 New...

More information

DISCUSSION OF FUNDAMENTALS

DISCUSSION OF FUNDAMENTALS Unit 4 AC s UNIT OBJECTIVE After completing this unit, you will be able to demonstrate and explain the operation of ac induction motors using the Squirrel-Cage module and the Capacitor-Start Motor module.

More information

Exercise 3. Phase Sequence EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Phase sequence fundamentals

Exercise 3. Phase Sequence EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Phase sequence fundamentals Exercise 3 Phase Sequence EXERCISE OBJECTIVE When you have completed this exercise, you will know what a phase sequence is and why it is important to know the phase sequence of a three-phase power system.

More information

Unit Protection Differential Relays

Unit Protection Differential Relays Unit Protection PROF. SHAHRAM MONTASER KOUHSARI Current, pu Current, pu Protection Relays - BASICS Note on CT polarity dots Through-current: must not operate Internal fault: must operate The CT currents

More information

EXPERIMENT 1 TITLE: SINGLE PHASE TRANSFORMERS - TRANSFORMER REGULATION

EXPERIMENT 1 TITLE: SINGLE PHASE TRANSFORMERS - TRANSFORMER REGULATION EXPERIMENT 1 TITLE: SINGLE PHASE TRANSFORMERS - TRANSFORMER REGULATION OBJECTIVES 1) To determine the voltage regulation of a transformer with varying loads and to discuss capacitive and inductive loading

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

Generator Operation with Speed and Voltage Regulation

Generator Operation with Speed and Voltage Regulation Exercise 3 Generator Operation with Speed and Voltage Regulation EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the speed governor and automatic voltage regulator used

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Catastrophic Relay Misoperations and Successful Relay Operation

Catastrophic Relay Misoperations and Successful Relay Operation Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

Transformer Protection

Transformer Protection Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary

More information

Three Phase Transformers

Three Phase Transformers EE/CME 392 Laboratory 6-1 Three Phase Transformers Safety The voltages used in this experiment are lethal. Assemble or modify a circuit only with the breakers off. Do not apply power until the wiring has

More information

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

Introduction to High-Speed Power Switching

Introduction to High-Speed Power Switching Exercise 3 Introduction to High-Speed Power Switching EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the concept of voltage-type and current-type circuits. You will

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Experiment 45. Three-Phase Circuits. G 1. a. Using your Power Supply and AC Voltmeter connect the circuit shown OBJECTIVE

Experiment 45. Three-Phase Circuits. G 1. a. Using your Power Supply and AC Voltmeter connect the circuit shown OBJECTIVE Experiment 45 Three-Phase Circuits OBJECTIVE To study the relationship between voltage and current in three-phase circuits. To learn how to make delta and wye connections. To calculate the power in three-phase

More information

Overcurrent and Overload Protection of AC Machines and Power Transformers

Overcurrent and Overload Protection of AC Machines and Power Transformers Exercise 2 Overcurrent and Overload Protection of AC Machines and Power Transformers EXERCISE OBJECTIVE When you have completed this exercise, you will understand the relationship between the power rating

More information

g GE POWER MANAGEMENT

g GE POWER MANAGEMENT 745 FREQUENTLY ASKED QUESTIONS 1 I get a communication error with the relay when I try to store a setpoint. This error can occur for several different reasons. First of all, verify that the address is

More information

Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS

Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS Option C4 Block differential current protection Description of option Functional descriptions Parameter list Document no.: 4189340397C SW version:

More information

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay Generator Differential Relay The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3G relay offers the following

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost

More information

Bidirectional PWM DC Motor Drive with Regenerative Braking

Bidirectional PWM DC Motor Drive with Regenerative Braking Exercise 2 Bidirectional PWM DC Motor Drive with Regenerative Braking EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with two better types of PWM dc motor drives: the buck-boost

More information

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when

More information

Harmonic Reduction using Thyristor 12-Pulse Converters

Harmonic Reduction using Thyristor 12-Pulse Converters Exercise 5 Harmonic Reduction using Thyristor 12-Pulse Converters EXERCISE OBJECTIVE When you have completed this exercise, you will understand what a thyristor 12- pulse converter is and how it operates.

More information

Dynamic Power Factor Correction Using a STATCOM

Dynamic Power Factor Correction Using a STATCOM Exercise 2 Dynamic Power Factor Correction Using a STATCOM EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the reasoning behind the usage of power factor correction

More information

Voltage-Versus-Speed Characteristic of a Wind Turbine Generator

Voltage-Versus-Speed Characteristic of a Wind Turbine Generator Exercise 1 Voltage-Versus-Speed Characteristic of a Wind Turbine Generator EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the principle of electromagnetic induction.

More information

USING SUPERIMPOSED PRINCIPLES (DELTA) IN PROTECTION TECHNIQUES IN AN INCREASINGLY CHALLENGING POWER NETWORK

USING SUPERIMPOSED PRINCIPLES (DELTA) IN PROTECTION TECHNIQUES IN AN INCREASINGLY CHALLENGING POWER NETWORK USING SUPERIMPOSED PRINCIPLES (DELTA) IN PROTECTION TECHNIQUES IN AN INCREASINGLY CHALLENGING POWER NETWORK P Horton, S Swain patricia.horton@ge.com, simon.swain@ge.com UK INTRODUCTION Superimposed techniques

More information

The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms

The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms Why Measure Winding Resistance? The measurement of winding resistance is useful in detecting a number of types of fault in a transformer. Malfunctioning tap changer mechanisms Partial or dead short-circuited

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost

More information

Solving Series Circuits and Kirchhoff s Voltage Law

Solving Series Circuits and Kirchhoff s Voltage Law Exercise 6 Solving Series Circuits and Kirchhoff s Voltage Law EXERCISE OBJECTIVE When you have completed this exercise, you will be able to calculate the equivalent resistance of multiple resistors in

More information

Exercise 6. Range and Angle Tracking Performance (Radar-Dependent Errors) EXERCISE OBJECTIVE

Exercise 6. Range and Angle Tracking Performance (Radar-Dependent Errors) EXERCISE OBJECTIVE Exercise 6 Range and Angle Tracking Performance EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the radardependent sources of error which limit range and angle tracking

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Exercise 10. Transformers EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to transformers

Exercise 10. Transformers EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to transformers Exercise 10 Transformers EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the basic operating principles of transformers, as well as with the different ratios of transformers:

More information

XD1-T Transformer differential protection relay. Manual XD1-T (Revision A)

XD1-T Transformer differential protection relay. Manual XD1-T (Revision A) XD1-T Transformer differential protection relay Manual XD1-T (Revision A) Woodward Manual XD1-T GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

Speed Feedback and Current Control in PWM DC Motor Drives

Speed Feedback and Current Control in PWM DC Motor Drives Exercise 3 Speed Feedback and Current Control in PWM DC Motor Drives EXERCISE OBJECTIVE When you have completed this exercise, you will know how to improve the regulation of speed in PWM dc motor drives.

More information

McPherson Voltage Regulators 4501 NW 27 Ave Miami FL

McPherson Voltage Regulators 4501 NW 27 Ave Miami FL McPherson Voltage Regulators 4501 NW 27 Ave Miami FL 33142 305-634-1511 To avoid of possible personal injury or equipment damage read and understand this manual before installation. (A.V.R) 208 / 380 /

More information

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services Introduction The topic of system grounding is extremely important, as it affects the susceptibility of the system to voltage

More information

Overcurrent Elements

Overcurrent Elements Exercise Objectives Hands-On Relay Testing Session Overcurrent Elements After completing this exercise, you should be able to do the following: Identify overcurrent element settings. Determine effective

More information

NERC Protection Coordination Webinar Series July 15, Jon Gardell

NERC Protection Coordination Webinar Series July 15, Jon Gardell Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

International Journal of Advance Engineering and Research Development ANALYSIS OF INTERNAL AND EXTERNAL FAULT FOR STAR DELTA TRANSFORMER USING PSCAD

International Journal of Advance Engineering and Research Development ANALYSIS OF INTERNAL AND EXTERNAL FAULT FOR STAR DELTA TRANSFORMER USING PSCAD Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 6, June -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 ANALYSIS OF

More information

Exercise 7. The Buck/Boost Chopper EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. The Buck/Boost Chopper

Exercise 7. The Buck/Boost Chopper EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. The Buck/Boost Chopper Exercise 7 The Buck/Boost Chopper EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the operation of the buck/boost chopper. DISCUSSION OUTLINE The Discussion of this

More information

Problems connected with Commissioning of Power Transformers

Problems connected with Commissioning of Power Transformers Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.

More information

Differential Protection with REF 542plus Feeder Terminal

Differential Protection with REF 542plus Feeder Terminal Differential Protection with REF 542plus Application and Setting Guide kansikuva_bw 1MRS 756281 Issued: 09.01.2007 Version: A Differential Protection with REF 542plus Application and Setting Guide Contents:

More information

Exercise 3. Doubly-Fed Induction Generators EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Doubly-fed induction generator operation

Exercise 3. Doubly-Fed Induction Generators EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Doubly-fed induction generator operation Exercise 3 Doubly-Fed Induction Generators EXERCISE OBJECTIVE hen you have completed this exercise, you will be familiar with the operation of three-phase wound-rotor induction machines used as doubly-fed

More information

Pinhook 500kV Transformer Neutral CT Saturation

Pinhook 500kV Transformer Neutral CT Saturation Russell W. Patterson Tennessee Valley Authority Presented to the 9th Annual Fault and Disturbance Analysis Conference May 1-2, 26 Abstract This paper discusses the saturation of a 5kV neutral CT upon energization

More information

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS Ljubomir KOJOVIC Cooper Power Systems - U.S.A. Lkojovic@cooperpower.com INTRODUCTION In steel facilities that use Electric Arc Furnaces (EAFs) to manufacture

More information

PMSM Control Using a Three-Phase, Six-Step 120 Modulation Inverter

PMSM Control Using a Three-Phase, Six-Step 120 Modulation Inverter Exercise 1 PMSM Control Using a Three-Phase, Six-Step 120 Modulation Inverter EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with six-step 120 modulation. You will know

More information

DEPARTMENT OF ELECTRICAL ENGINEERING BENGAL ENGINEERING AND SCIENCE UNIVERSITY, SHIBPUR

DEPARTMENT OF ELECTRICAL ENGINEERING BENGAL ENGINEERING AND SCIENCE UNIVERSITY, SHIBPUR DEPARTMENT OF ELECTRICAL ENGINEERING BENGAL ENGINEERING AND SCIENCE UNIVERSITY, SHIBPUR Power system protection Laboratory (EE 852) 8 th Semester Electrical Expt. No. 852/1 BIFFI S METHOD FOR TESTING CURRENT

More information

g GE POWER MANAGEMENT

g GE POWER MANAGEMENT 469 FREQUENTLY ASKED QUESTIONS 1 Can not communicate through the front port RS232 Check the following settings Communication port on your computer ( com1, com2 com3 etc ) Parity settings must match between

More information

Voltage Compensation of AC Transmission Lines Using a STATCOM

Voltage Compensation of AC Transmission Lines Using a STATCOM Exercise 1 Voltage Compensation of AC Transmission Lines Using a STATCOM EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the operating principles of STATCOMs used for

More information

Exercise 3-3. Manual Reversing Starters EXERCISE OBJECTIVE DISCUSSION. Build manual reversing starters and understand how they work.

Exercise 3-3. Manual Reversing Starters EXERCISE OBJECTIVE DISCUSSION. Build manual reversing starters and understand how they work. Exercise 3-3 Manual Reversing Starters EXERCISE OBJECTIVE Build manual reversing starters and understand how they work. DISCUSSION Reversing motor rotation direction is a common operation in industrial

More information

6. List two possible arrangements of a Yconnection and give one application

6. List two possible arrangements of a Yconnection and give one application OBJECTIVES PI 26.35-1 Electrical Equipment - Course PI 30.2 THREE PHASE SYSTEMS On completion of this module the student will be able to: 1. In a few sentences explain how three phase voltages are produced

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number:  Address: NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information

More information

Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content

Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION Sr. No. Course Content 1.0 Fault Current Calculations 1.1 Introduction to per unit and percentage impedance 1.2

More information

Grid-Tied Home Energy Production Using a Solar or Wind Power Inverter without DC-to-DC Converter

Grid-Tied Home Energy Production Using a Solar or Wind Power Inverter without DC-to-DC Converter Exercise 3 Grid-Tied Home Energy Production Using a Solar or Wind Power Inverter without DC-to-DC Converter EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with grid-tied

More information

Electricity Fundamentals Training System

Electricity Fundamentals Training System Electricity Fundamentals Training System LabVolt Series Datasheet Festo Didactic en 120 V - 60 Hz 07/2018 Table of Contents General Description 2 Courseware 2 Topic Coverage 2 List of Available Training

More information

EASUN REYROLLE LIMITED

EASUN REYROLLE LIMITED OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT

More information

This document covers common questions concerning the design of an effectively grounded system.

This document covers common questions concerning the design of an effectively grounded system. This document covers common questions concerning the design of an effectively grounded system. To prevent against temporary overvoltage conditions when a line-to-ground fault occurs on the power grid.

More information

EE 340L Experiment 6: Synchronous Generator - Operation with the Grid

EE 340L Experiment 6: Synchronous Generator - Operation with the Grid EE 340L Experiment 6: Synchronous Generator - Operation with the Grid The synchronous machine (see Fig. 1) is mechanically coupled to the Four-Quadrant Dynamometer/Power Supply (see Fig. 2) using a timing

More information

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY WN U-60 Attachment C to Schedule 152, Page 1 SCHEDULE 152 APPLICATION FOR INTERCONNECTING A GENERATING FACILITY TIER 2 OR TIER 3 This Application is considered complete when it provides all applicable

More information

Utility Interconnection and System Protection

Utility Interconnection and System Protection Utility Interconnection and System Protection Alex Steselboim President, Advanced Power Technologies, Inc. Utility paralleling vs. isolated operation. Isochronous kw load sharing Reactive power (VAR) sharing

More information

1. SQUIRREL CAGE AC MOTOR. NO LOAD TEST

1. SQUIRREL CAGE AC MOTOR. NO LOAD TEST 1. SQUIRREL CAGE AC MOTOR. NO LOAD TEST 1.1 INTRODUCTION. DESCRIPTION OF THE EXPERIMENT The three-phase induction motor carries a three-phase winding on its stator. The rotor is either a wound type or

More information

Closed-Loop Position Control, Proportional Mode

Closed-Loop Position Control, Proportional Mode Exercise 4 Closed-Loop Position Control, Proportional Mode EXERCISE OBJECTIVE To describe the proportional control mode; To describe the advantages and disadvantages of proportional control; To define

More information

2015 Relay School Bus Protection Mike Kockott March, 2015

2015 Relay School Bus Protection Mike Kockott March, 2015 2015 Relay School Bus Protection Mike Kockott March, 2015 History of Bus Protection Circulating current differential (1900s) High impedance differential (1940s) Percentage restrained differential (1960s)

More information

Solving Parallel and Mixed Circuits, and Kirchhoff s Current Law

Solving Parallel and Mixed Circuits, and Kirchhoff s Current Law Exercise 7 Solving Parallel and Mixed Circuits, and Kirchhoff s Current Law EXERCISE OBJECTIVE When you have completed this exercise, you will be able to calculate the equivalent resistance of multiple

More information

EE 210: CIRCUITS AND DEVICES

EE 210: CIRCUITS AND DEVICES EE 210: CIRCUITS AND DEVICES LAB #3: VOLTAGE AND CURRENT MEASUREMENTS This lab features a tutorial on the instrumentation that you will be using throughout the semester. More specifically, you will see

More information

Primary Resistor Starters with Time Relays

Primary Resistor Starters with Time Relays Exercise 6-3 Primary Resistor Starters with Time Relays EXERCISE OBJECTIVE Understand how a time relay can be used jointly with primary resistor starters. DISCUSSION Primary resistor starters are used

More information

Protecting Large Machines for Arcing Faults

Protecting Large Machines for Arcing Faults Protecting Large Machines for Arcing Faults March 2, 2010 INTRODUCTION Arcing faults occur due to dirty insulators or broken strands in the stator windings. Such faults if undetected can lead to overheating

More information

Exercise 9. Electromagnetism and Inductors EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Magnetism, magnets, and magnetic field

Exercise 9. Electromagnetism and Inductors EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Magnetism, magnets, and magnetic field Exercise 9 Electromagnetism and Inductors EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the concepts of magnetism, magnets, and magnetic field, as well as electromagnetism

More information

Alternator winding pitch and power system design

Alternator winding pitch and power system design Our energy working for you. TM Power topic #5981 Technical information from Cummins Power Generation Alternator winding pitch and power system design White Paper Rich Scoggins Applications Engineering

More information

Transformer Fault Categories

Transformer Fault Categories Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)

More information

XD1-T - Transformer differential protection relay

XD1-T - Transformer differential protection relay XD1-T - Transformer differential protection relay Contents 1. Application and features 2. Design 3. Characteristics 3.1 Operating principle of the differential protection 3.2 Balancing of phases and current

More information

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis 1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current

More information

POWER SYSTEM II LAB MANUAL

POWER SYSTEM II LAB MANUAL POWER SYSTEM II LAB MANUAL (CODE : EE 692) JIS COLLEGE OF ENGINEERING (An Autonomous Institution) Electrical Engineering Department Kalyani, Nadia POWER SYSTEM II CODE : EE 692 Contacts :3P Credits : 2

More information

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION R.Rahnavard 1, 2 M.Valizadeh 1 A.A.B.Sharifian 2 S.H.Hosseini 1 rerahnavard@gmail.com mj_valizad@yahoo.com hosseini@tabrizu.ac.ir

More information

Impact of Incipient Faults on Sensitive Protection

Impact of Incipient Faults on Sensitive Protection Impact of Incipient Faults on Sensitive Protection Paper Authors: Ilia Voloh GE Grid Solutions Zhihan Xu, Ilia Voloh GE Grid Solutions Leonardo Torelli CSE-Uniserve Presented by: Tom Ernst GE Grid Solutions

More information

SPAD 346 C. Stabilized Differential Relay. User s manual and Technical description SPAD 346 C V ~ V. f n SPCD 3D53 SPCJ 4D28

SPAD 346 C. Stabilized Differential Relay. User s manual and Technical description SPAD 346 C V ~ V. f n SPCD 3D53 SPCJ 4D28 SPAD 6 C Stabilized Differential Relay User s manual and Technical description f n = 50Hz 60Hz I n = A 5A ( I ) I n = A 5A ( I ) I n = A 5A ( I 0 ) I n = A 5A ( I 0 ) 5 I I d L L I L I > IRF I 0 > I 0

More information

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example

More information

CHAPTER 3 OVER CURRENT AND EARTH FAULT RELAY COORDINATION

CHAPTER 3 OVER CURRENT AND EARTH FAULT RELAY COORDINATION 18 CHAPTER 3 OVER CURRENT AND EARTH FAULT RELAY COORDINATION 3.1. OVERVIEW OF RELAY COORDINATION Relay coordination has to be carried out based on many other power system studies and Equipment Sizing calculation,

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) The toolbox for substation 3-phase testing Three currents and four voltages Stand-alone functionality Rugged and reliable

More information

Testing Numerical Transformer Differential Relays

Testing Numerical Transformer Differential Relays Feature Testing Numerical Transformer Differential Relays Steve Turner Beckwith Electric Co., nc. ntroduction Numerical transformer differential relays require careful consideration as to how to test properly.

More information

Power Station Electrical Protection A 2 B 2 C 2 Neutral C.T E M L } a 2 b 2 c 2 M M M CT Restricted E/F Relay L L L TO TRIP CIRCUIT Contents 1 The Need for Protection 2 1.1 Types of Faults............................

More information

Residual Current Operated Circuit-Breakers (RCCBs)

Residual Current Operated Circuit-Breakers (RCCBs) Product Overview Residual Current Operated Circuit-Breakers (RCCBs) Residual current operated circuit-breakers Number of poles Rated current A Rated residual current ma MW Auxiliary contacts can be mounted

More information

This transistor circuit has a voltage divider circuit with an emitter resistor for bias stability.

This transistor circuit has a voltage divider circuit with an emitter resistor for bias stability. When you have completed this exercise, you will be able to describe the temperature effects on a voltage divider bias circuit by using a typical transistor circuit. You will verify your results with a

More information

Lab 1: Basic Lab Equipment and Measurements

Lab 1: Basic Lab Equipment and Measurements Abstract: Lab 1: Basic Lab Equipment and Measurements This lab exercise introduces the basic measurement instruments that will be used throughout the course. These instruments include multimeters, oscilloscopes,

More information

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web: Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation

More information

DIGITAL EARTH FAULT RELAY

DIGITAL EARTH FAULT RELAY DIGITAL IDMT / DEFINITE TIME / INSTANTANEOUS Features Compact IDMT (4 IEC curves), Definite Time & Instantaneous Wide setting ranges Fully digital acquisition & processing of data Wide operating voltages

More information

Exercise 1. Basic PWM DC Motor Drive EXERCISE OBJECTIVE DISCUSSION OUTLINE. Block diagram of a basic PWM dc motor drive DISCUSSION

Exercise 1. Basic PWM DC Motor Drive EXERCISE OBJECTIVE DISCUSSION OUTLINE. Block diagram of a basic PWM dc motor drive DISCUSSION Exercise 1 Basic PWM DC Motor Drive EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the most basic type of PWM dc motor drive: the buck chopper dc motor drive. You will

More information

ENGINE GOVERNING SYSTEMS LSM200 SERIES LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

ENGINE GOVERNING SYSTEMS LSM200 SERIES LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER ENGINE GOVERNING SYSTEMS LSM200 SERIES LOAD SHARING MODULE MEMBER GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA 01001-2907, USA LSM200 SERIES LOAD SHARING MODULE PRODUCT TECHNICAL INFORMATION PTI

More information

Exercise 8. The Four-Quadrant Chopper EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. The Four-Quadrant Chopper

Exercise 8. The Four-Quadrant Chopper EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. The Four-Quadrant Chopper Exercise 8 The Four-Quadrant Chopper EXERCISE OBJECTIVE When you have completed this exercise, you will be familiar with the operation of the four-quadrant chopper. DISCUSSION OUTLINE The Discussion of

More information

Distributed Generation Application Form (Generation of Greater than 20 kw to 15 MW)

Distributed Generation Application Form (Generation of Greater than 20 kw to 15 MW) Distributed Generation Application Form (Generation of Greater than 20 kw to 15 MW) PSC-6028 R(03-04-04) Name & Address Distributed By Name & Address Supplied By Public Service Commission of Wisconsin

More information

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT * Iranian Journal of Science & Technology, Transaction B, Engineering, Vol. 30, No. B6, pp 643-654 Printed in The Islamic Republic of Iran, 2006 Shiraz University A NEW DIFFERENTIAL PROTECTION ALGORITHM

More information

Courseware Sample F0

Courseware Sample F0 Electric Power / Controls Courseware Sample 85822-F0 A ELECTRIC POWER / CONTROLS COURSEWARE SAMPLE by the Staff of Lab-Volt Ltd. Copyright 2009 Lab-Volt Ltd. All rights reserved. No part of this publication

More information

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY LIST OF TOPICS 1 Electric Circuit Principles 2 Electronic Circuit Principles 3 Generation 4 Distribution 5 Utilisation The expected learning outcome is

More information

UNIVERSITY OF TECHNOLOGY, JAMAICA SCHOOL OF ENGENEERING. Electrical Engineering Science. Laboratory Manual

UNIVERSITY OF TECHNOLOGY, JAMAICA SCHOOL OF ENGENEERING. Electrical Engineering Science. Laboratory Manual UNIVERSITY OF TECHNOLOGY, JAMAICA SCHOOL OF ENGENEERING Electrical Engineering Science Laboratory Manual Table of Contents Experiment #1 OHM S LAW... 3 Experiment # 2 SERIES AND PARALLEL CIRCUITS... 8

More information