Protective Relaying for DER
|
|
- Bruno Hamilton
- 5 years ago
- Views:
Transcription
1 Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ
2 Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed resource (DR) response to area electric power system (EPS) abnormal conditions
3 Overview Distributed generation (DG) impact on distribution feeders Real Life Operation of DR Interconnection Protection Introduction to Symmetrical Components
4 IEEE 1547 General Requirements to Be Met at PCC Voltage regulation Integration with area EPS grounding Synchronization Inadvertent energization of area EPS Monitoring provisions Isolation devices Interconnection integrity
5 DR Response to Area EPS Abnormal Conditions Faults Reclosing Voltage excursions Frequency excursions Loss of synchronism Reconnection to area EPS
6 DR Response to Area EPS Faults DR unit shall cease to energize area EPS for faults on area EPS circuit to which it is connected
7 DR Response to Area EPS Reclosing DR shall cease to energize area EPS circuit to which it is connected prior to reclosing by area EPS
8 DR Response to Voltage Excursions Voltage parameters are to be met at PCC Interconnection system responds to rms or fundamental voltage Phase to phase Phase to neutral Voltage Range (% of base voltage) Clearing Time (s) V < V V V
9 DR Response to Frequency Excursions DR shall cease to energize area EPS when system frequency is in particular range DR Size Frequency Range (Hz) Clearing Time (s) 30 kw > 30 kw > < > < 59.8 to 57.0 (adjustable) 0.16 to 300 (adjustable) <
10 DR Response to Loss of Synchronism In this case, DR response Applies only to synchronous generators Is primarily a risk to generators Standard addresses this condition as being of concern only if it results in voltage fluctuations that violate flicker limitations
11 DR Reconnection to Area EPS Reconnection is delayed up to 5 minutes after area EPS steady-state voltage and frequency are restored Ranges include Frequency 59.3 to 60.5 Hz Voltage see ANSI C , Table 1
12 Power Quality Limitation to dc injection Limitation of flicker induced by DR Harmonics
13 Islanding Unintentional Intentional
14 DG Impact on Distribution Feeders Increased fault duty Unintentional islanding Relay desensitization Nuisance tripping Automatic reclosing Voltage regulation and flicker Ferroresonance
15 Increased Fault Duty Is caused by addition of generating sources and rotating machinery of considerable size Affects capability of equipment to carry and interrupt fault currents Requires both local and area EPS equipment ratings to be reevaluated
16 Unintentional Islanding Occurs when portion of area EPS and DR become electrically isolated from rest of area EPS and DR continues to energize island Should be avoided for two major reasons There is potential for negative effects on voltage, frequency, and power quality Islanded generator complicates both automatic reclosing and manual switching
17 Relay Desensitization Available short-circuit current increases with addition of DR Short-circuit current splits between substation and DR Substation short-circuit contribution can be significantly reduced when compared with value before addition of DR
18 Relay Desensitization Fault Current Distribution Without DR Substation R1 R2 Three-Phase 3I A 198 A F1
19 Relay Desensitization Fault Current Distribution With DR Substation R1 R DR Substation Three-Phase 3I A 24 A DR 399 Three-Phase 3I A 246 A F1
20 Nuisance Tripping Without DR F2 Substation R1 R2 Three-Phase 3I A 616 A
21 Nuisance Tripping With DR Substation R F2 R DR Substation Three-Phase 3I A 616 A DR Three-Phase 3I 0 3E A 0 A pu 3E 0
22 Operation for Fault in Adjacent Zone I SYS + I FAULT SYS 1 I SYS I FAULT 2 3 I FAULT DR
23 Automatic Reclosing DR should be disconnected before open interval expires By interconnection protection (81U, 81O, 59, 27) By DTT Minimum open or dead time to allow arc deionization and to avoid restrike is
24 Automatic Reclosing If DR can form sustainable island when separated from system, restoration becomes issue Utility feeder breaker has to be equipped with synchronism-check element and / or live-bus and dead-line logic OR combination of both elements works as permissive for reclosing utility feeder breaker
25 Automatic Reclosing Close Permissives Utility Bus Feeder and bus are in synchronism Utility bus is hot and line is dead DR 3 C T 3 Live Bus / Dead Line or Synchronism 1 Temporary Fault Multifunction Relay
26 PV Array Real Life Operation of DR Interconnection Protection Isolation Transformer 380 Vac 13,800 Vac Neutral Grounding Reactor 51P 51G Pole-mounted Recloser T C I VY VZ G 27 Recloser Control Overhead Distribution Feeder Ø-G Fault Simplified Single-Line Diagram
27 Recloser Control Simplified Trip Logic OR G 51P 51G OR OR TRIP RECLOSER
28 Relay Settings Element Setting Delay Description % ms Definite time undervoltage level % s Definite time undervoltage level % 950 ms Definite time overvoltage level % ms Definite time overvoltage level Hz ms (@ 57 Hz) Definite time underfrequency level Hz s (@ 58.5 Hz) Definite time underfrequency level Hz ms (@ 60.5 Hz) Definite time overfrequency 59G 8,200 V 1.33 s Definite time residual ground overvoltage 51P 60 A NA Inverse time phase overcurrent 51G 19.8 A NA Inverse time residual ground overcurrent
29 Relay Underfrequency Settings
30 Feeder Fault (C-Ground)
31 Undervoltage Element Pickup Time ms
32 Undervoltage Element Time Delay ms
33 Recloser Interruption Time ms
34 ms Total Clearing Time
35 Introduction to Symmetrical Components The solution of balanced multi-phase systems can be accomplished using singlephase methods The method of symmetrical components allows unbalanced multi-phase systems to be solved using single-phase methods. Introduced in 1918 by C.L. Fortescue
36 Insight it is shown that unbalanced problems can be solved by the resolution of the currents and voltages into certain symmetrical relations. When the constants are symmetrical, that is, when the system viewed from any phase is similar, then the symmetrical components of currents do not react upon each other so that it becomes possible to eliminate the mutual relations with their attendant complication in the solution of the problems. C.L. Fortescue
37 Decomposition of an Unbalancedd System
38 Symmetrical Components as a Function of Phase Quantities
39 Phase Quantities as a Function of Symmetrical Components
40 Phase-to-Ground Fault Two-Terminal System
41 Zero Sequence Network During the Fault + - N 0 ΔV 0 = I 0R * (3 x Z N + Z 0TR ) Z 0S I 0DR = 0 Z 0DR 3 x Z N I 0S 0 V 0Z X H 0 Z 0TR ΔV 0 CB CLOSED I 0S + I 0R R CLOSED V 0Z before trip = 2400 V < 2,735 V (pick up) V 0Z after trip = 3200 V > 2,735 V (pick up) H
42 Residual Ground Overvoltage
43 Sample DER Interconnected Through PV Array a Delta/ Wye Transformer Isolation Transformer Pole-mounted Recloser T C I VY VZ Overhead Distribution Feeder Ø-G Fault 51P G 59G Recloser Control Simplified Single-Line Diagram
44 E What is the 3V0 at the Recloser Location After Utility Separation? Z 1S I 1S = 0 CB OPEN Z 2S I 2S = 0 CB OPEN Z 0S I 0S = 0 Z 1L Z 2L V 1 V 2 V 0 R CLOSED R CLOSED I 1DR = 0 I 2DR = 0 Z 0DR X Z 1DR Z 1TR Z 2DR Z 2TR I 0DR = 0 H 0 Z0TR H CB OPEN Z 0L R CLOSED I 0R = 0
45 Conclusions There are several requirements to be met by DR at PCC location DR has to respond to abnormal conditions of area EPS Addition of DR to distribution feeder affects its protection, voltage regulation, fault duty, reclosing scheme, and so on
46 Conclusions Event report analysis is a great tool to validate DER interconnection protection settings Unbalanced phasors can be broken down into their symmetrical components Symmetrical components allow the use of simple single-phase calculations for analysis of unbalanced systems The resultant symmetrical components can be recombined into the phase components
47 Questions?
48 Questions to the audience Please provide 3 examples of DR impacts on distribution feeders. Please provide 3 examples of area EPS abnormal conditions that the DR has to respond to. Can a DR immediately reconnect following a successful feeder restoration? If not, how long is the qualifying time delay? What are the quantities monitored during the qualifying time delay?
49 Questions to the audience According to the theory of Symmetrical Components, an unbalanced set of currents can be decomposed in three other components. What are these components? How are the sequence networks interconnected to represent a phase-toground fault?
ECE 528 Understanding Power Quality
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 22 1 Today Homework 5 questions Homework 6 discussion More on
More informationE N G I N E E R I N G M A N U A L
1 1 1.0 PURPOSE The purpose of this document is to define policy and provide engineering guidelines for the AP operating companies (Monongahela Power Company, The Potomac Edison Company, and West Penn
More informationBED INTERCONNECTION TECHNICAL REQUIREMENTS
BED INTERCONNECTION TECHNICAL REQUIREMENTS By Enis Šehović, P.E. 2/11/2016 Revised 5/19/2016 A. TABLE OF CONTENTS B. Interconnection Processes... 2 1. Vermont Public Service Board (PSB) Rule 5.500... 2
More informationBabak Enayati National Grid Thursday, April 17
2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April
More informationPhase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.
Summary Of Interconnection Technical Guidelines for Renewable Energy Systems 0-100 kw under Standard Offer Contract (Extract from JPS Guide to Interconnection of Distributed Generation) This document is
More informationImpacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering
Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Expo - Nov. 3, 2014 Index Normal Distribution System
More informationINTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs
INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES Technical Requirements for Grid-Tied DERs Projects Division 6/29/2017 Contents 1 Definitions and Acronyms... 1 2 Technical Interconnection
More informationDP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation
DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Single Phase
More informationTable of Contents. Introduction... 1
Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...
More informationFocused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection
Engineered Solutions for Power System Protection, Automaton and Control APPLICATION NOTE Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection 180622 Abstract This
More informationTECHNICAL GUIDELINE FOR THE INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES TO EPCOR DISTRIBUTION AND TRANSMISSION INC. S DISTRIBUTION SYSTEM
TECHNICAL GUIDELINE FOR THE INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES TO EPCOR DISTRIBUTION AND TRANSMISSION INC. S DISTRIBUTION SYSTEM January 5, 2017 Francesco Mannarino SVP, Electricity Operations
More informationGeneration Interconnection Requirements at Voltages 34.5 kv and Below
Generation Interconnection Requirements at Voltages 34.5 kv and Below 2005 March GENERATION INTERCONNECTION REQUIREMENTS AT 34.5 KV AND BELOW PAGE 1 OF 36 TABLE OF CONTENTS 1. INTRODUCTION 5 1.1. Intent
More informationThe Connecticut Light and Power Company
The Connecticut Light and Power Company and The United Illuminating Company Exhibit B - Generator Interconnection Technical Requirements May 12, 2010 Page 1 of 26 Table of Contents 1. SCOPE... 3 2. GENERAL
More informationUtility Interconnection and System Protection
Utility Interconnection and System Protection Alex Steselboim President, Advanced Power Technologies, Inc. Utility paralleling vs. isolated operation. Isochronous kw load sharing Reactive power (VAR) sharing
More informationTechnical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks
2014 Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks This document specifies the technical requirement for connecting sspv to the low voltage distribution
More informationSubstation applications
Substation applications To make it easy to choose the right for a protection application, the most typical applications are presented with the type of for them. Each sample application is presented by:
More informationSequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network
Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria
More informationIEEE sion/1547revision_index.html
IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html
More informationCOPYRIGHTED MATERIAL. Index
Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,
More informationGUIDE FOR GENERATOR INTERCONNECTION THE WIRES OWNER DISTRIBUTION SYSTEM
DATE: 200/06/2 PAGE 1 of GUIDE FOR GENERATOR INTERCONNECTION TO THE WIRES OWNER DISTRIBUTION SYSTEM The intent of this Guide is to establish the interconnection requirements of Distributed Resources with
More informationTransmission Protection Overview
Transmission Protection Overview 2017 Hands-On Relay School Daniel Henriod Schweitzer Engineering Laboratories Pullman, WA Transmission Line Protection Objective General knowledge and familiarity with
More informationGenerator Protection GENERATOR CONTROL AND PROTECTION
Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault
More informationExperiences in Integrating PV and Other DG to the Power System
Experiences in Integrating PV and Other DG to the Power System (Radial Distribution Systems) Prepared by: Philip Barker Founder and Principal Engineer Nova Energy Specialists, LLC Schenectady, NY Phone
More informationThis document covers common questions concerning the design of an effectively grounded system.
This document covers common questions concerning the design of an effectively grounded system. To prevent against temporary overvoltage conditions when a line-to-ground fault occurs on the power grid.
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements
Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system
More informationNERC Protection Coordination Webinar Series July 15, Jon Gardell
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationTransmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes
Transmission Line Protection Objective General knowledge and familiarity with transmission protection schemes Transmission Line Protection Topics Primary/backup protection Coordination Communication-based
More informationIEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces
IEEE PES Boston Chapter Technical Meeting IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces P1547 Chair David
More informationNew Methods for Detecting Unintentional Islanding for a Distributed-Generation Inverter
New Methods for Detecting Unintentional Islanding for a Distributed-Generation Inverter Daniel L. Ransom, PE Basler Electric Company Parsa Mirmobin Access Energy Abstract Since the first adoption of IEEE
More informationPJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016
PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 Prepared by System Planning Division Transmission Planning Department PJM 2016 Table of Contents Table of Contents Approval...6
More informationPower Quality Basics. Presented by. Scott Peele PE
Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement
More informationEducation & Training
Distribution System Operator Certificate This program provides you with a proficient working knowledge in modern electric power distribution systems. These four classes are designed to walk students through
More informationTexas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event
Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event
More informationCatastrophic Relay Misoperations and Successful Relay Operation
Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations
More informationPower Plant and Transmission System Protection Coordination Fundamentals
Power Plant and Transmission System Protection Coordination Fundamentals NERC Protection Coordination Webinar Series June 2, 2010 Jon Gardell Agenda 2 Objective Introduction to Protection Generator and
More informationGrid Converters for Photovoltaic
Grid Converters for Photovoltaic and Wind Power Systems by R. Teodorescu, M. Liserre and P. Rodriguez ISBN: 978 0 470 05751 3 Copyright Wiley 2011 Chapter 3 Grid Requirements for PV Grid connection requirements
More informationTECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION
TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION Document 9022 Puget Sound Energy, Inc. PSE-TC-160.70 December
More informationThe Effect of Various Types of DG Interconnection Transformer on Ferroresonance
The Effect of Various Types of DG Interconnection Transformer on Ferroresonance M. Esmaeili *, M. Rostami **, and G.B. Gharehpetian *** * MSc Student, Member, IEEE, Shahed University, Tehran, Iran, E mail:
More informationModelling Parameters. Affect on DER Impact Study Results
Modelling Parameters Affect on DER Impact Study Results Agenda Distributed Energy Resources (DER) Impact Studies DER Challenge Study Steps Lessons Learned Modeling Reverse Power Transformer Configuration
More informationReducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems
Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Alexander Apostolov AREVA T&D Automation I. INTRODUCTION The electric utilities industry is going through significant
More informationUPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS
UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS 1 B. RAMESH, 2 K. P. VITTAL Student Member, IEEE, EEE Department, National Institute of Technology Karnataka,
More informationPROTECTION SIGNALLING
PROTECTION SIGNALLING 1 Directional Comparison Distance Protection Schemes The importance of transmission system integrity necessitates high-speed fault clearing times and highspeed auto reclosing to avoid
More informationSection G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES
Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES Purpose This section specifies the requirements for protective relays and control devices for Generation Entities interconnecting
More informationDRAFT. City of Lethbridge Electric ENGINEERING STANDARDS GUIDELINE FOR GENERATOR INTERCONNECTION THE CITY OF LETHBRIDGE ELECTRIC DISTRIBUTION SYSTEM
City of Lethbridge Electric ENGINEERING STANDARDS DRAFT GUIDELINE FOR GENERATOR INTERCONNECTION TO THE CITY OF LETHBRIDGE ELECTRIC DISTRIBUTION SYSTEM Rev. 1 Rev. Date: 2003/01/24 Prepared by: Brent Smith
More informationANALYSIS OF LIGHTNING ARRESTER OVERLOADING IN FUTURE DISTRIBUTION SYSTEMS WITH DISTRIBUTED GENERATION. A Thesis JONATHAN MICHAEL SNODGRASS
ANALYSIS OF LIGHTNING ARRESTER OVERLOADING IN FUTURE DISTRIBUTION SYSTEMS WITH DISTRIBUTED GENERATION A Thesis by JONATHAN MICHAEL SNODGRASS Submitted to the Office of Graduate and Professional Studies
More informationProtection of Electrical Networks. Christophe Prévé
Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé
More informationRenewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA
Renewable Interconnection Standard & Experimental Tests Yahia Baghzouz UNLV Las Vegas, NV, USA Overview IEEE Std 1547 Voltage limitations Frequency limitations Harmonic limitations Expansion of IEEE Std
More informationWD series DIN Rail or Screw Mounted Protective Relays
WD series DIN Rail or Screw Mounted Protective Relays WD25 Paralleling (Synch Check) Relays WD2759 Over/undervoltage Relays WD32 Reverse Power Relays WD47 Phase Sequence Relays WD5051 Single- or Three-Phase
More informationADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION
23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB
More informationProtection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin
Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad
More informationWind Power Facility Technical Requirements CHANGE HISTORY
CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical
More informationInverter-Based Resource Disturbance Analysis
Inverter-Based Resource Disturbance Analysis Key Findings and Recommendations Informational Webinar February 15, 2018 August 16, 2016 Blue Cut Fire Disturbance Key Findings and Recommendations 2 Western
More informationWaterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology
Waterpower '97 August 5 8, 1997 Atlanta, GA Upgrading Hydroelectric Generator Protection Using Digital Technology Charles J. Beckwith Electric Company 6190-118th Avenue North Largo, FL 33773-3724 U.S.A.
More informationSEL-311C TRANSMISSION PROTECTION SYSTEM
SEL-3C TRANSMISSION PROTECTION SYSTEM ADVANCED TRANSMISSION LINE PROTECTION, AUTOMATION, AND CONTROL Bus ANSI NUMBERS/ACRONYMS AND FUNCTIONS 52 3 3 2 P G 8 O U 27 68 50BF 67 P G Q 50 P G Q 59 P G Q 5 P
More informationOPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS
OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS CONNECTED TO THE DISTRIBUTION SYSTEM ORANGE AND ROCKLAND
More informationDistribution/Substation Transformer
Distribution/Substation Transformer Type VFI, Vacuum Fault Interrupter Transformer Option Functional Specification Guide Functional specification for 15 kv, 25 kv, or 35 kv vacuum fault interrupter distribution/substation
More informationTABLE OF CONTENT
Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES
More informationAppendix C-1. Protection Requirements & Guidelines Non-Utility Generator Connection to Okanogan PUD
A. Introduction Appendix C-1 Protection Requirements & Guidelines to Okanogan PUD The protection requirements identified in this document apply to Non-Utility Generating (NUG) facilities, Independent Power
More informationDistributed Solar Integration Experiences
Distributed Solar Integration Experiences Prepared by: Philip Barker Founder and Principal Engineer Nova Energy Specialists, LLC Schenectady, NY Phone (518) 346 9770 Website: novaenergyspecialists.com
More information2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2012 Grid of the Future Symposium Impacts of the Decentralized Photovoltaic Energy Resources on the Grid B. ENAYATI, C.
More informationPower System Protection Where Are We Today?
1 Power System Protection Where Are We Today? Meliha B. Selak Power System Protection & Control IEEE PES Distinguished Lecturer Program Preceding IEEE PES Vice President for Chapters melihas@ieee.org PES
More informationPower Plant and Transmission System Protection Coordination
Technical Reference Document Power Plant and Transmission System Protection Coordination NERC System Protection and Control Subcommittee Revision 1 July 2010 Table of Contents 1. Introduction... 1 1.1.
More informationDER Ride-Through Performance Categories and Trip Settings Presentation at PJM Ride-Through Workshop, Philadelphia, PA, October 1-2, 2018
DER Ride-Through Performance Categories and Trip Settings Presentation at PJM Ride-Through Workshop, Philadelphia, PA, October 1-2, 2018 Dr. Jens C. Boemer, Principal Technical Leader, EPRI Reigh Walling,
More informationAdaptive Autoreclosure to Increase System Stability and Reduce Stress to Circuit Breakers
Adaptive Autoreclosure to Increase System Stability and Reduce Stress to Circuit Breakers 70 th Annual Conference for Protective Relay Engineers Siemens AG 2017 All rights reserved. siemens.com/energy-management
More informationSECTION AUTOMATIC TRANSFER SWITCH
SECTION 26 36 23 PART 1 - GENERAL 1.1 THE REQUIREMENT A. Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, withstand and close-on ratings as shown on the plans.
More informationRevised IEEE 1547 Standard for Interconnecting Distributed Energy Resources with Electric Power Systems- National Grid Solar Program
1 Revised IEEE 1547 Standard for Interconnecting Distributed Energy Resources with Electric Power Systems- National Grid Solar Program Babak Enayati, PhD, PE Lead Engineer, National Grid Waltham, MA Email:
More informationAdvantages and Disadvantages of EHV Automatic Reclosing
Technical Reference Document Advantages and Disadvantages of EHV Automatic Reclosing NERC System Protection and Control Subcommittee December 2009 Table of Contents 1. Introduction...1 2. Significant Autoreclosing
More informationPOWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.
POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products
More informationMicrogrid Protection Student Laboratory
Microgrid Protection Student Laboratory Ian Hellman-Wylie and Joey Navarro Senior Project California Polytechnic State University San Luis Obispo 2017 Abstract To better prepare students for careers in
More informationTechnical Requirements For Generation Connected to The ODEC System
Old Dominion Electric Cooperative Technical Requirements For Generation Connected to The ODEC System March 30, 2010 1 2 Table of Contents Topics Page Number Disclaimer.. 3 Perquisites.. 3 Applicability..
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements
Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission
More informationProtecting Feeders With Distributed Resource Scott Elling HDR Inc HDR, all rights reserved.
Protecting Feeders With Distributed Resource Scott Elling HDR Inc. 2015 HDR, all rights reserved. Background Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection
More informationSection G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES
Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES Purpose This section specifies the requirements for protective relays and control devices for Generation Entities interconnecting
More informationGeneration and Load Interconnection Standard
Generation and Load Interconnection Standard Rev. 0 DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5
More informationA proven distribution feeder solution with integrated protection, monitoring, and control
SEL-35 Protection System A proven distribution feeder solution with integrated protection, monitoring, and control Achieve sensitive and secure fault detection using comprehensive protection functions.
More informationBack to the Basics Event Analysis Using Symmetrical Components
Back to the Basics Event Analysis Using Symmetrical Components Amanvir Sudan Schweitzer Engineering Laboratories, Inc. 218 SEL Motivation Overview Back to Basics Introduction Symmetrical components refresher
More informationGuide and Requirements for Service. at 69,000 to 287,000 Volts R 0.2
Guide and Requirements for Service at 69,000 to 287,000 Volts R 0.2 September - 2011 Disclaimer This document is not intended as a design specification or as an instruction manual for the Load Customer
More informationPSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)
1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1
More informationDISTRIBUTION ENGINEERING PRACTICES
Interconnection Technical Requirements Handout PART C This document was excerpted from FirstEnergy Engineering Practice 02-280, approved for application throughout the FirstEnergy system on November 17,
More informationGeneration and Load Interconnection Standard
Generation and Load Interconnection Standard Rev. 0A DRAFT Name Signature Date Prepared: Approved: VP Acceptance APEGGA Permit to Practice P-08200 TABLE OF CONTENTS 1.0 INTRODUCTION...5 1.1 Purpose...5
More informationCommunications Assisted Islanding Detection
Communications Assisted Islanding Detection Contrasting Direct Transfer Trip and Methods Brian Dob and Craig Palmer Hubbell Power Systems, Inc. Boonton Twp NJ, USA Abstract A power system island is a part
More informationR10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)
R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between
More informationProtection of a 138/34.5 kv transformer using SEL relay
Scholars' Mine Masters Theses Student Theses and Dissertations Fall 2016 Protection of a 138/34.5 kv transformer using SEL 387-6 relay Aamani Lakkaraju Follow this and additional works at: http://scholarsmine.mst.edu/masters_theses
More informationHUTCHINSON UTILITIES COMMISSION TRANSMISSION INTERCONNECTION GUIDELINES
HUTCHINSON UTILITIES COMMISSION TRANSMISSION INTERCONNECTION GUIDELINES MAY 2013 I. INTRODUCTION A. OBJECTIVES The purpose of this handbook is to provide technical guidelines to assist the Applicant desiring
More informationCOPYRIGHTED MATERIAL. Introduction to protective relaying. 1.1 What is relaying?
1 Introduction to protective relaying 1.1 What is relaying? In order to understand the function of protective relaying systems, one must be familiar with the nature and the modes of operation of an electric
More informationA Novel Active Anti-Islanding Protection Scheme for Grid-Interactive Roof-Top Solar PV System
A Novel Active Anti-Islanding Protection Scheme for Grid-Interactive Roof-Top Solar PV System Rohith Varier, Student member, IEEE and Naran M. Pindoriya, Member, IEEE Electrical Engineering, Indian Institute
More informationTransmission Interconnection Requirements for Inverter-Based Generation
Transmission Requirements for Inverter-Based Generation June 25, 2018 Page 1 Overview: Every generator interconnecting to the transmission system must adhere to all applicable Federal and State jurisdictional
More informationIEEE Major Revision of Interconnection Standard
IEEE 1547-2018 - Major Revision of Interconnection Standard NRECA & APA s Emerging Priorities in Energy Research Day, Anchorage, AK Charlie Vartanian PE Secretary, IEEE 1547 Working Group October 31, 2018
More informationProtective Relays Digitrip 3000
New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer
More informationAnti-Islanding Today, Successful Islanding in the Future
Anti-Islanding Today, Successful Islanding in the Future John Mulhausen and Joe Schaefer Florida Power & Light Company Mangapathirao Mynam, Armando Guzmán, and Marcos Donolo Schweitzer Engineering Laboratories,
More informationElectrical Protection System Design and Operation
ELEC9713 Industrial and Commercial Power Systems Electrical Protection System Design and Operation 1. Function of Electrical Protection Systems The three primary aims of overcurrent electrical protection
More informationTable of Contents. 1.0 Intent and Limitations Intent Limitations Contact Information General Requirements...
Requirements for Interconnection Facilities Teck Metals Ltd. Transmission Assets: 1. Facility Connection Requirements 2. Technical Performance Requirements References: (Most recent version in each instance)
More informationBC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014
BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014 Expiry Year: 2018 APPROVED BY: Original signed by: Paul
More informationBE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2
BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY The BE1-67N Ground Directional Overcurrent Relay provides ground fault protection for transmission and distribution lines by sensing the direction and magnitude
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More informationNotes 1: Introduction to Distribution Systems
Notes 1: Introduction to Distribution Systems 1.0 Introduction Power systems are comprised of 3 basic electrical subsystems. Generation subsystem Transmission subsystem Distribution subsystem The subtransmission
More informationTECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS
TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS Puget Sound Energy, Inc. PSE-ET-160.60 October 30, 2007 TABLE OF CONTENTS 1. INTRODUCTION...1 1.1 GENERAL
More information1 INTRODUCTION 1.1 PRODUCT DESCRIPTION
GEK-00682D INTRODUCTION INTRODUCTION. PRODUCT DESCRIPTION The MDP Digital Time Overcurrent Relay is a digital, microprocessor based, nondirectional overcurrent relay that protects against phase-to-phase
More informationUsing a Multiple Analog Input Distance Relay as a DFR
Using a Multiple Analog Input Distance Relay as a DFR Dennis Denison Senior Transmission Specialist Entergy Rich Hunt, M.S., P.E. Senior Field Application Engineer NxtPhase T&D Corporation Presented at
More information