HV SHUNT REACTOR SECRETS FOR PROTECTION ENGINEERS

Size: px
Start display at page:

Download "HV SHUNT REACTOR SECRETS FOR PROTECTION ENGINEERS"

Transcription

1 HV SHUNT REACTOR SECRETS FOR PROTECTION ENGINEERS By Zoran Gajić ABB Sweden Västerås, Sweden Birger Hillström ABB Sweden Västerås, Sweden Fahrudin Mekić ABB Inc. Allentown, PA 1816 Presented to: 3 th Western Protective Relaying Conference Spokane, Washington October 1-3, 3

2 HV SHUNT REACTOR SECRETS FOR PROTECTION ENGINEERS Z. Gajić, B. Hillström F. Mekić ABB Sweden ABB Inc. Västerås, Sweden Allentown, PA 1816 Abstract: Viewed in the substation yard, an HV, oil immersed, shunt reactor does not differ much from a power transformer, but in reality it is not that simple. There are distinct differences between construction and operating characteristics of these two devices. In order to explain the properties of shunt reactors numerous current and voltage waveforms either captured as disturbance recordings in the field or simulated by ATP [7] will be presented. On all these figures the nomenclature for current and voltage signals, as shown in Figure 1 below, will always be used. A B C IA IB 3Io IC UA UB UC IaN IbN IcN IN Figure 1: Shunt Reactor Current & Voltage Signals All presented current and voltage signals will be expressed in per unit system with shunt reactor rated data as a base. 1

3 I. BASIS ABOUT HV SHUNT REACTORS 1.1 INTRODUCTION Shunt reactors are designed for connection to the ends of high voltage transmission lines or to high-voltage cables for the purpose of controlling the line voltage by absorbing reactive power. Let us look at the equivalent circuit of the transmission line and see shunt reactor effect on the line parameters. Is Z Ir Vs Y/ Y/ Vr Figure : Transmission line equivalent circuit (uncompensated line) In Figure, Vs and Is are the sending-end voltage and current, and Vr and Ir are the receivingend voltage and current. Writing Kirchoff Voltage Law equation for the circuit in Figure, Vr * Y Vs = Vr + Z( Ir + ) (1) Y * Z Vs = ( 1+ ) * Vr + Z * Ir () Also writing a Kirchoff Current Law equation at the sending end, Vr * Y Vs * Y Is = Ir + + (3) Y * Z Y * Z Is = Y ( 1+ ) * Vr + (1 + ) * Ir 4 (4) Vs AB Vr = Is CD Ir (5) where:

4 Y * Z A = D = 1+ ( perunit) (6) B = Z( Ω) (7) Y * Z C = Y ( 1+ )( S) (8) 4 Example 1: A three-phase line, completely transposed 345kV, 14 miles has the following positive sequence constants: z = j.563( Ω / mile) 6 y = j6.76*1 ( S / mile) From equations (6), (7) and (8) A = D = B = C = 8.77 * From (5), the no-load receiving-end voltage is Vs V = = = A.976 rnl kv LL Figure 3 summarizes these results, showing a high receiving-end voltage at no-load and a low receiving-end voltage at full load. This voltage regulation problem becomes more severe as the line length increase. 3

5 V(x) V RNL No-load Vs SIL V RSIL V S Full-load Short-circuit V RFL Sending end Receiving end V RSC Figure 3: Voltage profiles of an uncompensated line Assume that identical shunt reactors are connected from each phase to neutral at both ends of the same line during light load conditions, providing 75% compensation (the reactors are removed during heavy load conditions). In this case the line constants are: Z = z l = ( Ω) Y = 8.4*1 4 (1.75) =.1*1 From equations (6), (7) and (8) 4 9 ( S) A = D = From (5), the no-load receiving-end voltage is Vs VrNL = = = 348. kv LL A.993 It may be concluded from the previous example that reactors reduce overvoltages during light load conditions. However, shunt reactors can reduce line loadability if they are not removed under full-load conditions. There are two general types of shunt reactors. One is dry-type reactor of an air core or core-less design. These reactors are limited to voltages up to 34.5kV and are often installed on the tertiary of a transformer. 4

6 HV, oil immersed, shunt reactors are the most compact and cost-efficient means to compensate reactive power generation of long-distance, high-voltage power transmission lines, or extended cable systems during light load conditions. Two main application of the reactor can be identified, referring to Figure 4.: Shunt reactors that are continuously in service, generally used for EHV and long HV lines/cables Switched shunt reactors are applied in the underlying system and near load centers It is common for shunt reactors to be installed at both ends of EHV lines, and sized to prevent the line voltage from exceeding design value when energized from one end. Since there is usually some uncertainty as to which end of a line may be energized (or de-energized) first, shunt reactors are usually installed at both ends of line. G Z G Equivalent Pi of the Long Line Y/ Y/ Figure 4: One-line diagram of line-connected switched shunt reactors The shunt capacitance depends on type of transmission line, length of line and line voltage. A long distance 345kV transmission line will have a shunt capacitance around 3.14 µ F /mile (1.1Mvar/mile). The corresponding shunt capacitance for the 345kV cable is almost times as large as or about.4mvar/mile. The shunt capacitance will be increased by increasing the transmission voltage (proportional to the square of the transmission voltage). 5

7 1. SHUNT REACTOR GENERAL DESIGN CONCEPTS Two different ways are used in building reactors, commonly referred to as gapped core and coreless [1] & []. The gapped core reactor has a subdivided limb of core steel with air gaps inside the winding and no limb at all for the coreless concept. It is easy to verify that the gapped core concept becomes more advantageous as the loss evaluation rate increases and particularly at higher system voltages. This is due to the higher energy density that can be achieved in a gapped core reactor compared to a coreless reactor. SHUNT REACTOR OPERATING CHARACTERISTICS Linearity For normal operating voltages there is a linear relationship between applied voltage and reactor current (i.e. a small increase in voltage will result in a proportional increase in current). Magnetic fluxes and flux densities are also proportional to the time integral of the applied voltage. With a voltage of sinusoidal shape the fluxes and flux densities are also proportional to the voltage. The deviation from a true sinusoidal shape in line voltage is in general negligible for normal operating voltages. As the magnetic flux to a great extent has its path in magnetic core steel the core steel will get saturated for flux densities above a certain level, the saturation point. Below and up to the saturation point only a small current is needed to magnetize the core steel and the extra current needed to reach a marginal increase flux density is small. Once above the saturation point the extra current needed to further increase the flux density will be large. Harmonic content Steady state harmonics in reactor current arise from partial saturation in the magnetic circuit. These effects are in fact very small, and without practical importance for relaying and communication interference. Of all harmonics the third harmonic will be dominant. In the reactor neutral the third harmonics in the three phases add together and act like a zero sequence current. Asymmetry between phases The tolerances on asymmetry between phases of a three-phase reactor or between single-phase units forming a three-phase bank can be judged by the amount of residual harmonics. The result is a zero sequence current in the neutral connection. Standards are realistic, but better tolerances are possible to achieve. A usual figure is.5 %. 6

8 II. HV SHUNT REACTOR SWITCHING.1 SWITCHING IN OF REACTORS, INRUSH CURRENT The switching in of a reactor gives rise to inrush current a transient phenomenon related to saturation in the shunt reactor magnetic circuit. In principle, it is the same story as inrush current of a transformer, but there are differences. A reactor core keeps no remanence, because of the air gaps, which makes the whole thing easier. However, the damping of the asymmetric condition the dc component is slow, due to the inherent low losses in a shunt reactor. It is therefore necessary to keep this phenomenon in mind when designing the relay protection system for HV shunt reactors. The instantaneous current values during shunt reactor switching in can be visualized from the Figure 5. Input data for all figures in this chapter are obtained from actual disturbance recordings in the field. Depending on the switching instant the currents might have a dc component. The worst condition is when the reactor phase is closed in at zero voltage. The flux will increase with the voltage-time-area during the first half-cycle to a value twice the maximum flux in normal operation. The current is proportional to the flux density, until reactor core saturation occurs. Above the point of saturation the current will increase faster than the flux. 99,MVA, 44kV, 6Hz Reactor 4 Current [pu] IA IB IC Figure 5: Shunt Reactor Phase Currents during Asynchronized Switching Without saturation, the first peak of the current with full dc offset would be.8 = times rated current. The actual current peak might rise to a value in between 3 and 5.5 times depending on the particular shunt reactor design details. One of the time intervals when reactor core goes into saturation is clearly marked if Figure 5. For a three-phase reactor the different phases will experience different degrees of dc offset. The combination of the individual phase current offsets will give a neutral current rich in harmonics and also with possibly dc offset from the zero line as shown in Figure 6 or Figure 14. 7

9 ,MVA, 44kV, 6Hz Reactor.9 Current [pu] IN 3Io Figure 6: Shunt Reactor Neutral Currents during Asynchronized Switching The time to more or less fully balanced operation around zero flux in the core may be fairly long often in order of seconds, but such condition is of no harm for the shunt reactor itself. In recent years, so-called point on wave closing relays are available from switchgear manufacturers. By using these relays switching of different power system devices, including shunt reactors, can be performed without a disturbance to the rest of the power system. Typical current waveforms during the synchronized shunt reactor switching is shown in Figures 7, 8 & 9. 15MVAr, kv, 5Hz Reactor 1 Current [pu] IA IB IC Figure 7: Shunt Reactor Phase Currents during Synchronized Switching 8

10 1.5 15MVAr, kv, 5Hz Reactor.75 Current [pu] IN 3Io Figure 8: Shunt Reactor Neutral Currents during Synchronized Switching In order to obtain such disturbance free shunt reactor switching, circuit breaker poles must be precisely closed in three consecutive phase voltage peaks as shown in the following figure. 15MVAr, kv, 5Hz Reactor 1 Current & Voltage [pu] IA IB IC UA UB UC Figure 9: Shunt Reactor Phase Currents & Voltages during Synchronized Switching 9

11 . SHUNT REACTOR DISCONNECTION Disconnection of small reactive current was at one time regarded as a dangerous operation because of the risk of current chopping and resulting switching overvoltage. Modern surge arresters are fully capable of handling this condition, and besides, the tendency of the circuit breaker to chop reactor current is not so pronounced for typical HV shunt reactor rated current values [1], [3]. However, the primary current chopping causes another, and maybe less known, transient phenomenon, which appears in the CT secondary circuit. This phenomenon is manifested as an exponentially decaying dc current component in the CT secondary circuit (see Figure 16, for typical example). This secondary dc current has no corresponding primary current in the power system. The phenomenon can be simply explained as a discharge of the magnetic energy stored in the magnetic core of the current transformer. However these discharge secondary currents are typically very small for shunt reactors and pose no effect on the reactor protection schemes with numerical relays. 1

12 III. NUMERICAL PROTECTION RELAY RESPONSE DURING SHUNT REACTOR SWITCHING IN All numerical relays utilize so-called sampling technique of the input current and voltage signals. Typically 1 to 3 samples per fundamental power system cycle are used depending on the particular relay design. From these samples numerical relays calculates root-mean-square values of the input quantities by using different type of digital filters. These RMS values are then typically processed by different protective functions (i.e. phase and ground overcurrent) In order to apply correct relay settings for shunt reactor protection application, it is of outmost importance to understand the relay digital filter response to typical input current waveforms, which can be encountered. Figure 1 represents typical current waveform during reactor switching in. 5 99,MVA, 44kV, 6Hz Reactor 4 3 Current [pu] IC Figure 1: Typical Shunt Reactor current waveform during switching in Response of two different types of digital filters will be investigated. 1. TRMS (i.e. True RMS filter), which extracts equivalent RMS value from the input signal. Therefore this filter includes the dc component and higher harmonic components from the input quantity into its output result. DFT (i.e. digital Fourier filter), which extracts only RMS value of the fundamental component from the input signal. This filter effectively suppresses the dc component and higher harmonic components in the input quantity. 11

13 From Figure 11 it is obvious that the overcurrent relays which use DFT filtering technique can be set more sensitive than the relays which use TRMS filter for its operation. Similar results can be obtained if similar analysis is performed for the neutral point current as well. All setting recommendation in this document will be given for relays, which utilize DFT filtering technique (i.e. relays which effectively suppress the dc component and higher harmonic components in the input quantity)..5 IC RMS value 1.69 [pu] TRMS DFT Figure 11: Digital Filter Output for input signal shown in Figure 1 1

14 IV. POSSIBLE PROTECTION PROBLEMS DURING SHUNT REACTOR SWITCHING It is well known fact that one of the principal difficulties with shunt reactor protection scheme is false operation during reactor energizing and de-energizing [4]. As explained previously, during this period relatively high and long lasting dc current component typically causes most problems for protective relays. If the protection relays maloperate this typically happen some hundreds of millisecond or even 1 to seconds after circuit breaker closing. What is most difficult to understand is why this problem often happens randomly and not with every reactor switching attempt. Most problems are typically encountered with restricted ground fault protection, differential protection and ground fault protection during switching. Therefore performance of these three relays during switching in of the shunt reactor will be explained here in more details. 4.1 CURRENT TRANSFORMER PERFORMANCE DURING SWITCHING IN OF SHUNT REACTOR It should be noted that HV shunt reactors are typically switched in and out at least once per day or even more often depending on the power system loading patterns. As shown in Chapter II during switching in of shunt reactor relatively high and long lasting dc current component might appear in one or more phases. This current waveform moves the operating point of CT magnetic core on the hysteresis curve in one direction and when the dc component diminish it leaves the main CT with certain level of residual (i.e. remanent) flux. During normal operation reactor current is always around 1pu and therefore of a relatively low magnitude, which is never big enough to move the operating point towards the origin. Therefore when next switching attempt comes, depending on the moment of switching, residual flux in the CT core can increase or decrease. Thus this mechanism will sooner or later cause CT saturation during reactor switch in operation. This CT saturation then causes problems for protective relays, which lose the correct information about the primary current and therefore can maloperate. Such CT saturation event is captured by numerical relay disturbance recorder and it is shown in Figure MVAr, kv, 5Hz Reactor CT Saturation Instant Current [pu] IC Figure 1: Phase CT saturation during Shunt Reactor Switching in 13

15 1.5 15MVAr, kv, 5Hz Reactor 1 Current [pu] DFT IC Figure 13: Influence of Phase CT saturation on current DFT value calculation This type of CT saturation is reflected in the CT secondary side as: loss of information about primary dc component reduced current magnitude Figure 13 represents the DFT filter output value for the input current waveform as shown in Figure RESTRICTED GROUND FAULT RELAY PERFORMANCE DURING SWITCHING IN OF REACTOR Modern numerical relays typically offer restricted ground fault protection of a low impedance type. This gives the following benefits to the end user: this relay can be applied with different type of CTs at the reactor bushing and at reactor neutral point (i.e. CTs doesn t need to be identical) main CTs can be shared with other relays no galvanic connection is necessary between CTs at the reactor bushing and at reactor neutral point in case of an internal fault no high voltages will appear in the CT secondary wiring Typically these restricted ground fault relays of a low impedance type calculate the differential current as a difference between zero-sequence currents at the reactor bushings and the reactor neutral point. As additional operating criteria they often use directional principle (i.e. product type relays). However for shunt reactor protection these sometimes might not be enough to prevent maloperations. Let s have a look into the disturbance-recording file captured by numerical relay, which is shown in Figure

16 15MVAr, kv, 5Hz Reactor 1 Current [pu] IN 3Io Figure 14: Zero-sequence currents during Shunt Reactor Switching in The problem is that when one or more phase CTs saturate false 3Io current appears at the reactor bushings. Unfortunately this very often manifests as the current of opposite polarity in comparison with the neutral point current, which then causes the directional restricted ground fault relay (i.e. product type relay) to maloperate during reactor switching in. Calculated phase angle difference between neutral point current and zero-sequence current at the reactor bushing for the above event is shown in Figure 15: 1 Phase Angle Between IN & 3Io 8 6 Angle [deg] 4 3Io-IN Figure 15: Calculated phase angle difference between IN and 3Io currents Obviously it is necessary to have some additional means to restrain low impedance, restricted ground fault relay from maloperations during shunt reactor switching in. One very effective method is to check the amount of second harmonic component in the shunt reactor neutral point current and adaptively prevent relay operation if the preset limit is exceeded. 15

17 4.3 DIFFERENTIAL RELAY PERFORMANCE DURING SWITCHING IN OF REACTOR Modern numerical relays typically offer differential protection of a low impedance type. This gives the following benefits to the end user: this relay can be applied with different type of CTs at the reactor bushing and at reactor star point (i.e. CTs doesn t need to be identical) main CTs can be shared with other relays no galvanic connection is necessary between CTs at the reactor bushing and at reactor star point in case of an internal fault no high voltages will appear in the CT secondary wiring Here the situation is little bit easier because the relay measures essentially the same current on both ends of the protected winding. However again the long lasting dc component can cause uneven saturation of the two CTs and cause the relay maloperations. Let s have a look into the disturbance recording file captured by numerical relay, which is shown in Figure MVA, 44kV, 6Hz Reactor [pu] IC IcN Figure 16: Phase C winding currents during shunt reactor switching in As it can be seen in Figure 16 due to uneven CT saturation on the two winding ends differential protection had unwanted operation and it has disconnected the shunt reactor from the power system. Thus if sensitive setting is required for the differential protection (i.e. 1-15% of the reactor rated current) it might be necessary to have some additional means to restrain low impedance differential protection relay from maloperations during shunt reactor switching in. One effective method is to enable second harmonic blocking feature commonly readily available in numerical transformer differential relay. Second possibility is to delay the restraint differential protection operation only during reactor switching. In the same time in order to have secure operation for heavier internal fault, the unrestrained differential level can be typically set down to % and without any time delay. 16

18 4.4 GROUND OVERCURRENT RELAY PERFORMANCE DURING SWITCHING IN OF REACTOR Numerical ground overcurrent relay might maloperate during reactor switching if it is set too sensitive. Typically in such cases either pickup current value or time delay are increased. However, another very effective method for such type of problem is to enable second harmonic blocking feature for ground overcurrent relay, which is readily available in certain numerical protections. Then the relay will check the second harmonic component level in the measured input current and prevent relay operation if the preset limit is exceeded. V. SHUNT REACTOR BEHAVIOUR DURING EXTERNAL AND INTERNAL FAULTS Shunt reactors are connected in parallel with the rest of the power network. As shown in Appendix II shunt reactor can be treated as a device with the fixed impedance value. Therefore the individual phase current is directly proportional to the applied phase voltage (i.e. I=U/Z). Thus during external fault condition, when the faulty phase voltage is lower than the rated voltage, the current in the faulty phase will actually reduce its value from the rated value. Depending on the point on the voltage wave when external fault happens the reduce current might have superimposed dc component. Such behavior is verified by an ATP simulation and it is shown in Figure MVA, kv, 5Hz Reactor Current [pu] IA IB IC Figure 17: External Phase A to Ground Fault, Reactor Phase Currents As a result, shunt reactor unbalance current will appear in the neutral point as shown in Figure 18. However, this neutral point current will typically be less than 1 pu irrespective of the location and fault resistance of the external fault. 17

19 .5 15MVA, kv, 5Hz Reactor 1.17 Current [pu] IN 3Io Figure 18: External Phase A to Ground Fault, Reactor Zero-sequence Currents Similarly during an internal fault the value of the individual phase currents and neutral point current will depend very much on the position of the internal fault. Assuming that due to the construction details, internal shunt reactor phase-to-phase faults are not very likely, only two extreme cases of internal phase to ground fault scenarios will be presented here. In the first case the Phase A winding to ground fault, 1% from the neutral point has been simulated in ATP. As a result the phase currents on the HV side (i.e. in reactor bushings) will be practically the same as before the fault as shown in Figure MVA, kv, 5Hz Reactor Current [pu] IA IB IC Figure 19: Internal Phase A Winding to Ground Fault, Phase Currents 18

20 However phase A current at the shunt reactor star point and common neutral point current will have very big value due to so-called transformer effect. These currents can be so high to even cause CT saturation as shown in Figure for the common neutral point current MVA, kv, 5Hz Reactor 8.33 Current [pu] IN 3Io Figure : Internal Phase A Winding to Ground Fault, Zero-sequence Currents This type of the internal fault shall be easily detected and cleared by the differential, restricted ground fault or neutral point ground overcurrent protection, but not by reactor HV side overcurrent or HV residual ground fault protections. In the second case the Phase A to ground fault, just between the HV CTs and shunt reactor winding (i.e. shunt reactor bushing failure) has been investigated. In this case the currents have opposite properties. The phase A current on the HV side is very big (limited only by the power system source impedance and fault resistance), while the phase A current in reactor star point will have very small value due to a fact that phase A winding is practically short-circuited. As a result, shunt reactor unbalance current will appear in the neutral point. However, this neutral point current will typically have a value around 1 pu (i.e. similar value as during external ground fault). That type of the internal fault (i.e. shunt reactor bushing failure) shall be easily detected and cleared by the differential, restricted ground fault or HV side overcurrent or residual ground fault protections. Neutral point ground overcurrent protection can operate with the time delay. For internal ground fault in some other location in-between these two positions the shunt reactor currents will have values somewhere in the range limited by this two extreme cases. 19

21 VI. SHUNT REACTOR TURN-TO-TURN PROTECTION SCHEMES Turn-to-turn faults in shunt reactor present a formidable challenge to the protection engineer. The current and the voltage changes encountered during such fault are very small and therefore sensitive and reliable protection against turn-to-turn faults is difficult to achieve. At the same time the longitudinal differential protection offers no protection at all for such faults. Hence special protection schemes shall be employed. One such scheme, often used in certain countries, utilizes a fact that the HV shunt reactor winding is often made of two half-windings connected in parallel (i.e. the HV lead is brought out at the mid point of the winding, and the two neutral leads at the bottom and the top of the winding). This gives the opportunity to install two CTs in the winding star point (i.e. one in each winding part). Then so-called split phase differential protection can be utilized to detect turn-toturn faults. However this protection scheme have the following drawbacks: this special CT arrangement typically causes reactor manufacturing problems typically low CT ratio is required, which can cause longitudinal differential protection problems during reactor switching in, if the same CTs are used for both differential protections this scheme can be only used if the shunt reactor is specifically ordered with these CTs Second turn-to-turn protection scheme for shunt reactors, successfully used in some other counties, utilize the following facts: HV power system voltages are well balanced during normal load conditions Modern HV, oil immersed shunt reactors have very small manufacturing asymmetry between individual phases Shunt reactor winding impedance is approximately proportional to the square of the number of active turns Short circuit between some number of turns will cause the decrease of the winding impedance only in the faulty phase and corresponding small raise of the shunt reactor neutral point current Currents during turn-to-turn fault are of the small magnitude and they will not produce any sufficient unbalance voltage Any external cause of neutral point current (i.e. external phase to ground fault) will cause appearance of unbalance voltage which can be used to block the operation of turn-to-turn protection scheme In case of a bigger winding turn-to-turn fault which might cause the sufficient voltage unbalance, sensitive directional zero sequence relay connected on the shunt reactor HV side and set to look into the reactor shall be capable to detect such fault This protection scheme was developed even before multifunctional numerical relays were available. To implement such shunt reactor turn-to-turn protection scheme within multifunctional numerical relay utilizing its graphical configuration facilities, and readily available logical gates, timers etc. shall not be a big problem for a protection engineer.

22 In order to verify above statements, shunt reactor behavior, for phase A winding 1% turn-to-turn faults, is verified by an ATP simulation and it is shown in Figures 1 &. From these figures is obvious that the above-described scheme can be successfully implemented if the power system itself is well balanced MVA, kv, 5Hz Reactor Current [pu] IA IB IC Figure 1: Internal Phase A Winding turn-to-turn fault, Phase Currents.6 15MVA, kv, 5Hz Reactor Current & Voltage [pu] IN 3Io 3Uo Figure : Internal Phase A Winding turn-to-turn fault, Zero-sequence Quantities 1

23 VII. SHUNT REACTOR MECHANICAL FAULT DETECTION Similarly to the power transformers, HV oil immersed shunt reactors typically have build-in mechanical devices for internal fault or abnormal operating condition detection. Typically the following built-in mechanical fault detection devices can be encountered within shunt reactor: gas detection relay (i.e. Buchholz relay) with alarm and trip stage sudden pressure relay winding temperature contact thermometer with alarm and trip stage oil temperature contact thermometer with alarm and trip stage low oil level relay These mechanical relays are excellent compliment to the electrical measuring relays previously explained. Typically it is recommended to arrange that these mechanical relays trip reactor circuit breaker independently from electrical relays. However signals from mechanical devices shall be connected to binary inputs of numerical relays in order to get time tagging information, disturbance recording and event reporting in case of their operation. VIII. TYPICAL SHUNT REACTOR CONTROL SCHEMES The shunt reactors are generally designed for natural cooling with the radiators mounted directly on the tank. However sometimes it is required to have some control action in the cooling circuit depending on the status of the shunt reactor circuit breaker. The control action can be initiated by the circuit breaker auxiliary contact or by operation of an overcurrent relay set to 5% of the reactor rated current. By using overcurrent relay secure control action is obtained when reactor is energized regardless the circuit breaker auxiliary contact status. In order to improve power system performance, lately it is often required by the electrical utilities to perform automatic shunt reactor in and out switching, by monitoring the busbar voltage level. This functionality is quite easy to integrate into multifunctional, numerical relay. However user must carefully check relay performance regarding the following points: over/under voltage relay with reset ratio or 1% or better is required for such application typically more than one over/under voltage level with independently settable time delays are required within the relay over/under voltage relay shall be capable to operate only when all three voltages are above/below set operate level or relay must be capable to measure and operate on the value of the positive sequence voltage

24 IX. TRADITIONAL SHUNT REACTOR PROTECTION AND CONTROL SCHEMES Usually multifunctional numerical protection relays are used for both power transformer and shunt reactor protection. However, typically old protection schemes for shunt reactor protection, with just a few protection functions are still specified and applied today. Two such traditional protection arrangements are shown in the following two figures. IA IB IC 5/51 87N IN 5G/51G Figure 3: Typical Shunt Reactor Protection Scheme No1 The first protection scheme utilizes restricted ground fault protection (i.e. 87N) as reactor unit protection. This protection shall trip instantaneously for all internal phase to ground faults. For internal phase-to-phase fault detection, overcurrent protection (i.e. 5/51) is utilized. Ground overcurrent protection (i.e. 5G/51G) is used as backup protection for ground faults and as main protection for circuit breaker pole disagreement condition. 3

25 IA IB IC 5/51 5N/51N 87 IaN IbN IcN Figure 4: Typical Shunt Reactor Protection Scheme No The second protection scheme utilizes differential protection (i.e. 87) as reactor unit protection. This protection shall trip instantaneously for all internal phase to phase and phase to ground faults. Overcurrent protection (i.e. 5/51) is used as backup protection for internal phase-tophase faults. Residual overcurrent protection (i.e. 5N/51N) is used as backup protection for ground faults and as main protection for circuit breaker pole disagreement condition. Actually it shall be noted that the numerical multifunctional relays can offer much more functionality than shown on the above two figures. Please refer to the following chapter to see proposed shunt reactor protection scheme with multifunctional numerical protection relay. 4

26 X. CONCLUSIONS The paper has described a number of details regarding HV shunt reactors and their protection and control schemes. In order to help the end user to properly select and apply multifunctional numerical relays for HV shunt reactor protection and control, an example of possible application of such relay, which utilizes DFT filtering technique, is presented in Figure 5. IA IB IC 5/51 # 1 5N/51N 67N 87N UA UB UC N 87 IaN IbN IcN 5/ /51 # # 3 IN 5G/51G Figure 5: Example of complete HV shunt reactor protection and control scheme with multifunctional, numerical relay All proposed protection or control functions in Figure 5 are typically readily available in multifunctional numerical transformer protection relays. However suitability of a particular relay to be used for shunt reactor application shall be carefully evaluated. Table 1 gives the summary about each function from Figure 5 as well as some typical setting values [5]. The proposed settings shall be considered only as guidelines. It is hoped that this paper will provide some guidance to those seeking assistance in HV shunt reactor protection and control issues. 5

27 Function 87=low impedance differential protection 87N=low impedance, restricted ground fault protection #1-5/51=HV overcurrent protection #-5/51=HV overcurrent protection #3-5/51=HV overcurrent protection 49=thermal overload protection 5G/51G=ground fault protection in reactor neutral point 5N/51N=ground fault overcurrent protection in reactor HV side 59N=unbalance overvoltage 67=directional ground fault protection 7&59=under/over voltage Comment Check suitability for shunt reactor application with relay manufacturer. Check suitability for shunt reactor application with relay manufacturer. Backup protection, sensitive for internal faults close to the reactor bushings. Backup protection, sensitive for internal fault close to the reactor star point. Used as circuit breaker failure protection and indication that reactor is energized for the cooling control logic. Shall be used with great care. Shunt reactor overload can only be caused by overvoltage in a power system. That is the exact time when reactors are required to be energized. Thus it might come in conflict with shunt reactor voltage/reactive power control functionality in the power system. Backup protection, sensitive for internal fault close to the reactor star point. Used for turn-to-turn fault detection logic. Backup protection, sensitive for internal faults close to the reactor bushings. Used for turn-to-turn fault detection logic. Used for turn-to-turn fault detection logic. Used for automatic shunt reactor control. Often more than one stage required. Typical setting shown in percents of the shunt reactor rating Set restraint differential level to 1-15% with nd harmonic restrain set at 1%. Set unrestraint differential level %. Set differential level to 1%. Set operate angle for directional criteria to ±65 deg. Relay shall include adaptive nd harmonic restrain feature. Set low set to 13% with time delay in between.6s and 1s. Set high set to 5% with time delay of.1s. * Set low set to 13% with time delay in between.6s and 1s. Set high set to % with time delay of.1s. * Set low set to 3% with appropriate time delay as CBF protection. Set high set to 5% in order to indicate that shunt reactor is energized. * Specific manufacturing data are required in order to properly set this function. Possible to use winding/oil contact thermometer instead. Specific system data are required in order to properly set this function. Set low set to % with time delay in between.6s and 1s or even longer. Use nd harmonic blocking. Set high set to 175% with time delay of.1s. * Specific system data are required in order to properly set this function. Specific system data are required in order to properly set this function. Specific system data are required in order to properly set these functions. Table 1: List of functions for complete HV shunt reactor protection and control scheme * These settings are proposed for HV shunt reactors with own circuit breaker. In case that the HV shunt reactor is directly connected to the HV line without its own circuit breaker, these settings have to be revised in order to prevent unwanted operation, when: HV line is de-energized, due to low-frequency, long time constant transients which are determined by the combination of line capacitance and shunt reactor inductance [4]&[6] One HV line phase is open during dead time of single pole autoreclosing cycle 6

28 APPENDIX I Basic relationships between shunt reactor most important quantities are shown here: U Q = 3 * U * I = X * I = (App_I.1) X P Total.*Q (App_I.) P P.75* P.15 Q (App_I.3) Cu Total * Fe.5* PTotal.5* Q (App_I.4) where: Q is shunt reactor rated reactive power in VAr U is shunt reactor rated phase-to-phase voltage in V I is shunt reactor rated phase current in A X is shunt reactor rated reactance in Ω P total is total shunt reactor losses in W (typically total shunt reactor losses are in order of,% in accordance with references [1]&[]) P Cu is total shunt reactor copper losses in W (typically shunt reactor copper losses are in order of 75% of the total losses in accordance with reference [1]) P Fe is other shunt reactor losses (most of them are iron losses) in W Above data are important in order to properly simulate HV shunt reactors. 7

29 APPENDIX II Typical HV shunt reactor magnetizing characteristic is shown in Figure 6..5 Shunt Reactor Characteristic Voltage [pu] Current [pu] Figure 6: Typical magnetizing characteristic of a gapped core shunt reactor The relation between voltage and current peak value in a HV shunt reactor can be described by two lines, one below saturation and the other above saturation. The point where the two lines intersect is called knee point. The relation between voltage and current peak value is shown in Figure 6. The knee point usually corresponds from 15% to 135% of the rated voltage. The slope of the saturated part is % to 4% of the slope in the unsaturated region. Below the knee point the reactor current is sinusoidal (i.e. this means that the relation between the current peak value and the root-mean-square value of the current is fix and equal to ) and its magnitude is directly proportional to the applied sinusoidal voltage. Thus for normal operating voltages there is a linear relationship between applied voltage and reactor current (i.e. a small increase in voltage will result in a proportional increase in current). Magnetic fluxes and flux densities are also proportional to the time integral of the applied voltages. With a voltage of sinusoidal shape the fluxes and flux densities are also proportional to the voltage. The deviation from a true sinusoidal shape in phase voltage is generally negligible for normal operating conditions of the power system. For operation above the knee point the current peak value increases faster than the root-meansquare value, and the quotient between the peak value and the root-mean-square value exceeds value. 8

30 BIBLIOGRAPHY 1. Carlson, Å., Shunt Reactor Manual, ABB Power Technology Products/Transformers, Ludvika-Sweden, -8-. ABB Transformatori, Pamphlet Shunt Reactors, Roma-Italy 3. Switchgear Committee of the IEEE Power Engineering Society, IEEE Application Guide for Shunt Reactor Switching, IEEE Std C IEEE Power Systems Relaying Committee, IEEE Guide for the Protection of Shunt Reactors, ANSI/IEEE C Nylen, R., Shunt Reactor and SVC Protection Application Guide, ABB Relays, Västerås- Sweden, Elmore, W. A., editor, Protective Relaying: Theory and Applications, Marcel Dekker, Inc., ATP is the royalty-free version of the Electromagnetic Transients Program (EMTP). For more info please visit one of the following web sites: or BIOGRAPHICAL SKETCHES Zoran Gajić was born in former Yugoslavia in He received his BSEE with honors from University of Belgrade, Yugoslavia in 199 and GDE in Computer Engineering from Witwatersrand University, Johannesburg-RSA in Since 1993 he has been working in the area of power system protection and control within ABB Group of companies, where he had various engineering positions. Currently he has a position of Protection Application Specialist with ABB Automation Technologies, Substation Automation, Sweden. He is a member of IEEE and PES. Zoran has published several technical papers in the relay protection area. His main working areas are computer applications for protection and control of electrical power systems, protection and control algorithms for microprocessor based relays and power system simulation. Zoran is co-holder of two patents. Birger Hillström was born in Sweden He received his M.Sc.E.E degree from Chalmers Technical University in Goteborg Sweden, He was employed as development engineer at ASEA, Sweden, 197 and is currently working as development project manager at ABB Automation Technologies, Substation Automation, Sweden. During ten years he was relay laboratory manager and was then responsible for development of a digitally controlled, analogue power system simulator and was after that part of a specification group of a real time digital power system simulator. His special areas of interest are transient network analysis, development and testing of line and transformer static and numerical relays. Fahrudin Mekić was born in former Yugoslavia in He received his BSEE with honors from Sarajevo University, Bosnia and Herzegovina in 1991 where he also worked as research assistant. He received his MSEE degree from Istanbul Technical University, Turkey in Since 1996 he has been working in the area of power system protection and control within ABB, where he had various engineering positions. Currently he is Senior Application Engineer with the Substation Automation and Protection Division, ABB Inc, in Allentown, PA. Fahrudin has published several technical papers in the area of protection and reliability. He is currently responsible for the application and technical issues associated with ABB relays. He is a member of IEEE. 9

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System Lalit Ghatpande, SynchroGrid, College Station, Texas, 77840 Naveen Ganta, SynchroGrid, College Station, Texas,

More information

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS 1 STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS Z. GAJIĆ S. HOLST D. BONMANN D. BAARS ABB AB, SA Products ABB AB, SA Products ABB AG, Transformers ELEQ bv Sweden Sweden Germany Netherlands zoran.gajic@se.abb.com

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

Transformer Protection

Transformer Protection Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary

More information

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Jules Esztergalyos, Senior Member, IEEE Abstract--The measuring technique described in this paper is based on Electro Magnetic

More information

Pinhook 500kV Transformer Neutral CT Saturation

Pinhook 500kV Transformer Neutral CT Saturation Russell W. Patterson Tennessee Valley Authority Presented to the 9th Annual Fault and Disturbance Analysis Conference May 1-2, 26 Abstract This paper discusses the saturation of a 5kV neutral CT upon energization

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

COPYRIGHTED MATERIAL. Index

COPYRIGHTED MATERIAL. Index Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,

More information

Power Plant and Transmission System Protection Coordination Fundamentals

Power Plant and Transmission System Protection Coordination Fundamentals Power Plant and Transmission System Protection Coordination Fundamentals NERC Protection Coordination Webinar Series June 2, 2010 Jon Gardell Agenda 2 Objective Introduction to Protection Generator and

More information

Unit Protection Differential Relays

Unit Protection Differential Relays Unit Protection PROF. SHAHRAM MONTASER KOUHSARI Current, pu Current, pu Protection Relays - BASICS Note on CT polarity dots Through-current: must not operate Internal fault: must operate The CT currents

More information

1

1 Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Long lasting transients in power filter circuits

Long lasting transients in power filter circuits Computer Applications in Electrical Engineering Vol. 12 2014 Long lasting transients in power filter circuits Jurij Warecki, Michał Gajdzica AGH University of Science and Technology 30-059 Kraków, Al.

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum International Journal of Scientific & Engineering Research, Volume 7, Issue 4, April-216 628 REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD Abhilash.G.R Smitha K.S Vocational Teacher

More information

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria

More information

Beyond the Knee Point: A Practical Guide to CT Saturation

Beyond the Knee Point: A Practical Guide to CT Saturation Beyond the Knee Point: A Practical Guide to CT Saturation Ariana Hargrave, Michael J. Thompson, and Brad Heilman, Schweitzer Engineering Laboratories, Inc. Abstract Current transformer (CT) saturation,

More information

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved. Pomona, CA, May 24 & 25, 2016 Tertiary Winding Design in wye-wye Connected Transformers Scope of Presentation > Tertiary vs. Stabilizing Winding? Tertiary vs. Stabilizing Winding? Need for Stabilizing

More information

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers International Conference on Power System Transients IPST 23 in New Orleans, USA Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

ISSN: Page 298

ISSN: Page 298 Sizing Current Transformers Rating To Enhance Digital Relay Operations Using Advanced Saturation Voltage Model *J.O. Aibangbee 1 and S.O. Onohaebi 2 *Department of Electrical &Computer Engineering, Bells

More information

NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1

NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 NERC Requirements for Setting Load-Dependent Power Plant Protection: PRC-025-1 Charles J. Mozina, Consultant Beckwith Electric Co., Inc. www.beckwithelectric.com I. Introduction During the 2003 blackout,

More information

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic

More information

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

FGJTCFWPKPUVKVWVGQHVGEJPQNQI[ FGRCTVOGPVQHGNGEVTKECNGPIKPGGTKPI VGG246JKIJXQNVCIGGPIKPGGTKPI FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown

More information

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software

Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software Govind Pandya 1, Rahul Umre 2, Aditya Pandey 3 Assistant professor, Dept. of Electrical & Electronics,

More information

Importance of Transformer Demagnetization

Importance of Transformer Demagnetization Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia 4th International Colloquium "Transformer Research and Asset Management Importance

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

Transformer Protection Principles

Transformer Protection Principles Transformer Protection Principles 1. Introduction Transformers are a critical and expensive component of the power system. Due to the long lead time for repair of and replacement of transformers, a major

More information

Problems connected with Commissioning of Power Transformers

Problems connected with Commissioning of Power Transformers Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

Evaluating the Impact of Increasing System Fault Currents on Protection

Evaluating the Impact of Increasing System Fault Currents on Protection Evaluating the Impact of Increasing System Fault Currents on Protection Zhihan Xu, Ilia Voloh GE Grid Solutions, LLC Mohsen Khanbeigi Hydro One Abstract Every year the capacity of power systems is increasing,

More information

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer Vol. 3 Issue 2, February-2014, pp: (69-75), Impact Factor: 1.252, Available online at: www.erpublications.com Modeling and Simulation of Modern Digital Differential Protection Scheme of Power Transformer

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

Detecting and Managing Geomagnetically Induced Currents With Relays

Detecting and Managing Geomagnetically Induced Currents With Relays Detecting and Managing Geomagnetically Induced Currents With Relays Copyright SEL 2013 Transformer Relay Connections Voltage Current Control RTDs Transformer Protective Relay Measures differential current

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES U AJMAL, GE Grid Solutions UK Ltd, usman.ajmal@ge.com S SUBRAMANIAN, GE Grid Solutions UK Ltd, sankara.subramanian@ge.com H Ha GE Grid Solutions

More information

Study Committee B5 Colloquium 2005 September Calgary, CANADA

Study Committee B5 Colloquium 2005 September Calgary, CANADA 113 Study Committee B5 Colloquium 2005 September 14-16 Calgary, CANADA SENSITIVE TURN-TO-TURN FAULT PROTECTION FOR POWER TRANSFORMERS Zoran Gajić*, Ivo Brnčić, Birger Hillström ABB, Sweden E-mail: zoran.gajic@se.abb.com

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays

More information

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3

Power System Protection. Dr. Lionel R. Orama Exclusa, PE Week 3 Power System Protection Dr. Lionel R. Orama Exclusa, PE Week 3 Operating Principles: Electromagnetic Attraction Relays Readings-Mason Chapters & 3 Operating quantities Electromagnetic attraction Response

More information

Application of SVCs to Satisfy Reactive Power Needs of Power Systems

Application of SVCs to Satisfy Reactive Power Needs of Power Systems 1 Application of SVCs to Satisfy Reactive Power Needs of Power Systems H. K. Tyll, Senior Member, IEEE Abstract In the early days of power transmission problems like voltage deviation during load changes

More information

2015 Relay School Bus Protection Mike Kockott March, 2015

2015 Relay School Bus Protection Mike Kockott March, 2015 2015 Relay School Bus Protection Mike Kockott March, 2015 History of Bus Protection Circulating current differential (1900s) High impedance differential (1940s) Percentage restrained differential (1960s)

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

Testing Numerical Transformer Differential Relays

Testing Numerical Transformer Differential Relays Feature Testing Numerical Transformer Differential Relays Steve Turner Beckwith Electric Co., nc. ntroduction Numerical transformer differential relays require careful consideration as to how to test properly.

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

SHUNT CAPACITOR BANK DESIGN AND PROTECTION BASICS

SHUNT CAPACITOR BANK DESIGN AND PROTECTION BASICS SHUNT CAPACITOR BANK DESIGN AND PROTECTION BASICS Introduction Shunt capacitor units are typically used to deliver capacitive reactive compensation or power factor correction. The use of shunt capacitor

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis 1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current

More information

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power

More information

Differential Protection with REF 542plus Feeder Terminal

Differential Protection with REF 542plus Feeder Terminal Differential Protection with REF 542plus Application and Setting Guide kansikuva_bw 1MRS 756281 Issued: 09.01.2007 Version: A Differential Protection with REF 542plus Application and Setting Guide Contents:

More information

BUS2000 Busbar Differential Protection System

BUS2000 Busbar Differential Protection System BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection 1 Typical Busbar Arrangements Single Busbar Double Busbar with Coupler Breaker and a Half

More information

How Transformer DC Winding Resistance Testing Can Cause Generator Relays to Operate

How Transformer DC Winding Resistance Testing Can Cause Generator Relays to Operate How Transformer DC Winding Resistance Testing Can Cause Generator Relays to Operate Ritwik Chowdhury, Mircea Rusicior, Jakov Vico, and Jason Young Schweitzer Engineering Laboratories, Inc. 216 IEEE. Personal

More information

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Alexander Apostolov AREVA T&D Automation I. INTRODUCTION The electric utilities industry is going through significant

More information

Generator Protection GENERATOR CONTROL AND PROTECTION

Generator Protection GENERATOR CONTROL AND PROTECTION Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault

More information

Catastrophic Relay Misoperations and Successful Relay Operation

Catastrophic Relay Misoperations and Successful Relay Operation Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations

More information

Demagnetization of Power Transformers Following a DC Resistance Testing

Demagnetization of Power Transformers Following a DC Resistance Testing Demagnetization of Power Transformers Following a DC Resistance Testing Dr.ing. Raka Levi DV Power, Sweden Abstract This paper discusses several methods for removal of remanent magnetism from power transformers.

More information

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions 1 Transmission transformers are important links in the bulk power system. They allow transfer of power from generation centers, up to the high-voltage grid, and to bulk electric substations for distribution

More information

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium Assessment of the Impact of GMD on the TVA 500 kv Grid & Power Transformers Part II:

More information

(2) New Standard IEEE P (3) Core : (4) Windings :

(2) New Standard IEEE P (3) Core : (4) Windings : (d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.

More information

Conventional Paper-II-2011 Part-1A

Conventional Paper-II-2011 Part-1A Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance

More information

2. Current interruption transients

2. Current interruption transients 1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series

More information

S1-3: New and re-discovered theories and practices in relay protection

S1-3: New and re-discovered theories and practices in relay protection (Cheboksary, September 9-13, 27) S1-3: New and re-discovered theories and practices in relay protection Practical experience from multiterminal line differential protection installations Z. GAJIĆ, I. BRNČIĆ,

More information

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) 1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS DFFERENTAL PROTECTON METHODOLOGY FOR ARBTRARY THREE-PHASE POWER TRANSFORMERS Z. Gaji ABB AB-SA Products, Sweden; zoran.gajic@se.abb.com Keywords: power transformer, phase shifting transformer, converter

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission

More information

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections

More information

Distance Relay Response to Transformer Energization: Problems and Solutions

Distance Relay Response to Transformer Energization: Problems and Solutions 1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering

More information

Solution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection

Solution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection ABSTRACT National conference on Engineering Innovations and Solutions (NCEIS 2018) International Journal of Scientific Research in Computer Science, Engineering and Information Technology 2018 IJSRCSEIT

More information

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines

Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India

More information

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering) R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between

More information

Preventing transformer saturation in static transfer switches A Real Time Flux Control Method

Preventing transformer saturation in static transfer switches A Real Time Flux Control Method W H I T E PA P E R Preventing transformer saturation in static transfer switches A Real Time Flux Control Method TM 2 SUPERSWITCH 4 WITH REAL TIME FLUX CONTROL TM Preventing transformer saturation in static

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected

More information

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit

More information

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost

More information

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,

More information

Although shunt capacitors

Although shunt capacitors INSIDE PQ The Trouble With Capacitors Part 1 Switching capacitors seems like a simple proposition, but it can lead to some very interesting problems By R. Fehr, P.E., Engineering Consultant Although shunt

More information

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS 2-1. General but less than locked-rotor amperes and flows only Electrical power systems must be designed to serve in the normal circuit path. a variety of

More information

16 Transformer and Transformer-feeder Protection

16 Transformer and Transformer-feeder Protection Chap16-254-279 17/06/02 9:58 Page 254 Transformer and Transformer-feeder Protection Introduction 16.1 Winding faults 16.2 Magnetising inrush 16.3 Transformer overheating 16.4 Transformer protection overview

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

ARC FLASH HAZARD ANALYSIS AND MITIGATION

ARC FLASH HAZARD ANALYSIS AND MITIGATION ARC FLASH HAZARD ANALYSIS AND MITIGATION J.C. Das IEEE PRESS SERIES 0N POWER ENGINEERING Mohamed E. El-Hawary, Series Editor IEEE IEEE PRESS WILEY A JOHN WILEY & SONS, INC., PUBLICATION CONTENTS Foreword

More information

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES THE OLE OF SYNCHOPHASOS IN THE INTEGATION OF DISTIBUTED ENEGY ESOUCES Alexander APOSTOLOV OMICON electronics - USA alex.apostolov@omicronusa.com ABSTACT The introduction of M and P class Synchrophasors

More information

Substation applications

Substation applications Substation applications To make it easy to choose the right for a protection application, the most typical applications are presented with the type of for them. Each sample application is presented by:

More information

Generator Advanced Concepts

Generator Advanced Concepts Generator Advanced Concepts Common Topics, The Practical Side Machine Output Voltage Equation Pitch Harmonics Circulating Currents when Paralleling Reactances and Time Constants Three Generator Curves

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and

More information