Study Committee B5 Colloquium 2005 September Calgary, CANADA

Size: px
Start display at page:

Download "Study Committee B5 Colloquium 2005 September Calgary, CANADA"

Transcription

1 113 Study Committee B5 Colloquium 2005 September Calgary, CANADA SENSITIVE TURN-TO-TURN FAULT PROTECTION FOR POWER TRANSFORMERS Zoran Gajić*, Ivo Brnčić, Birger Hillström ABB, Sweden Igor Ivanković HEP, Croatia 1. INTRODUCTION Three most typical weaknesses of the analogue power transformer differential relays have been: 1. Long operating time in case of heavy internal s followed by main CT saturation 2. Unwanted operations for external s and transformer inrush 3. Bad sensitivity for low-level internal s, such as winding turn-to-turn s With the introduction of the numerical technology the first two problems could be handled in much better way [4]. However sensitivity for internal winding turn-to-turn s did not improve much. This paper introduces the new protection principle, which will improve differential relay sensitivity for minor internal turn-to-turn s. However, the first two classical disadvantages are as well efficiently removed by applying the solution described in the paper. A short circuit of a few turns of the winding will give rise to a heavy current in the shortcircuited turns, but changes in the transformer terminal currents will be very small, because of the high ratio of transformation between the whole winding and the short-circuited turns. For that reason, the traditional power transformer differential protection was typically not sensitive enough to detect such winding turn-to-turn s before they developed into more serious and costly to repair earths. Alternatively, such s can be as well detected by Buchholtz (i.e. gas) relays. However, these relays detect such low-level s with a delay typically 50 ms 100 ms that often allows the to evolve into a more serious one. The new protection principle is based on the theory of symmetrical components [1] and [2], or more exact, on the negative-sequence currents. The very existence of relatively high negative-sequence currents is in itself an indication of a disturbance, as the negative sequence currents are superimposed, pure- quantities. The negative-sequence quantities are particularly suitable for different kinds of directional tests. For specific applications they seem to be superior to the zero-sequence quantities, which so far have been more extensively used, mostly due to the fact that they were easy to measure. The new protection principle yields a very sensitive protection for low-level turn-to-turn s. All such s, which involve around 1% short-circuited turns, can be detected. This low value is limited downwards only by an eventual small amount of the false, steady-state negative-sequence currents. The new negative-sequence-current-based sensitive protection is a good complement to the traditional power transformer differential protection, which is based on the well-known bias differential characteristic. The paper presents the principle of this new protection, and concludes with a case study

2 2. PROBLEM STATEMENT A study of the records of modern transformer breakdowns, which occurred over a period of years, showed that between 70% and 80% of the total number of transformer failures are eventually traced to internal winding insulation failure. If not quickly detected, these turn-to-turn s usually develop into more serious and costly to repair earth-s involving power transformer iron core. Alternatively they cause arcing within the power transformer tank, which creates a lot of damage until it is tripped by Buchholtz relay. These winding s are mostly a result of the degradation of the insulation system due to thermal, electrical, and mechanical stress, moisture, and so on [8]. Degradation means reduced insulation quality, which will eventually cause a breakdown in the insulation, either leads to adjacent winding turns being shorted (turn-to-turn short circuit ), or directly to a winding being shorted to the earth (winding to earth failure). Most often the insulation undergoes a gradual aging process before such a happens. Ageing of the insulation reduces both the mechanical and dielectric-withstand strength. Under external conditions, power transformer windings are temporarily subjected to high radial and compressive forces. As the load increases with system growth, the operating stresses increase. In an ageing transformer the conductor insulation is weakened to the point where it can no longer sustain much additional stress. Under increased stress, for example due to some external, insulation between adjacent turns suffers a dielectric failure and a turn-to-turn develops. The problem of the classical transformer differential protection has been that just these low-level turnto-turn s could not be detected with the overall sensitivity represented by the differential protection operate restraint characteristic. Even the relatively high sensitivity in the first section of the differential relay operate restraint characteristic may not be enough. If, for example, the differential relay minimum pickup current e.g. parameter IdMin in the first section of the relay operate restraint characteristic has been set to 30% because of an uncompensated On-Load-Tap-Changer, and/or other reasons, then it is clear, that a minor turn-to-turn, which initially only causes a differential current of, say, 10%, cannot be felt until it evolves into a more severe with higher differential currents. The problem can be solved by the application of an analysis, based on the comparison of the negative sequence currents on both power transformer sides. Existence of relatively high negative-sequence currents is in itself a proof of a disturbance on the power system, possibly a in the power transformer. The negative-sequence currents are measurable indications of abnormal conditions, similar to the zero-sequence currents. One of the several advantages of the negative-sequence currents compared to the zero-sequence currents is however that they provide coverage for phase-to-phase and power transformer turn-to-turn s as well, not only for earth-s. Theoretically the negative sequence currents do not exist during symmetrical three-phase s, however they do appear during initial stage of such s for long enough time for the relay to make proper decision. Further, the negative sequence currents are not stopped at a power transformer of the Yd, or Dy connection. The negative sequence currents are always properly transformed to the other side of any power transformer for any external disturbance. Finally, the negative sequence currents are typically not affected by through-load currents. The main feature of the new sensitive protection, which is capable to detect minor s, is the negative-sequence-current-based internal/external discriminator. The internal/external discriminator is a very powerful and reliable device. It detects even minor s, with a high sensitivity and a high speed, and at the same time discriminates with a high degree of dependability between internal and external s. The algorithm of the internal/external discriminator is based on the theory of symmetrical components. Already in 1933, Wagner and Evans [1] stated that: 1. Source of the negative-sequence currents is at the point of, (E NS = -I NS * Z NS ) 2. Negative-sequence currents distribute through the negative-sequence network 3. Negative-sequence currents obey the first Kirchhoff's law Similar statements are as well re-confirmed in reference [2]

3 3. PRINCIPLES OF THE NEW SENSITIVE DIFFERENTIAL PROTECTION In order to avoid misunderstandings about what is meant by the same direction and opposite direction, an explanation of relay internally used CT reference directions is shown in Figure 1. I W1 I W2 Z1 S2 E1 S1 Z1 S1 E1 S2 I W1 I W2 Relay Figure 1: Used reference connections of CTs, and definition of positive direction of currents As shown in Figure 1 relay will always measure the primary currents on all sides of the power transformer with the same reference direction towards the power transformer windings. 3.1 Compensation for the power transformer phase displacement and turns ratio Imagine first a power transformer with a turns ratio equal to 1, and zero degree phase displacement, e.g. a power transformer of the connection group Yy0. For an external the fictitious negative sequence source will be located outside the differential protection zone at the point. Thus the negative sequence currents will enter the healthy power transformer on the side, and leave it on the other side, properly transformed. According to the current direction definitions in Figure 1, the negative sequence currents on the respective power transformer sides will have opposite directions. In other words, the internal/external discriminator sees these currents as having a relative phase displacement of exactly 180 electrical degrees, as shown in Figure 2. Yy0; 1:1 INS S2 ZNS S1 ZNS S2 E NS Negative Sequence Zero Potential Relay Figure 2. Flow of Negative Sequence Currents for power transformer external For an internal (with the fictitious negative sequence source within protected power transformer) the negative sequence currents will flow out of the y power transformer on both sides. According to the definitions in Figure 1, the negative sequence currents on the respective power transformer

4 sides will have the same direction. In other words, the internal/external discriminator sees these currents as having a relative phase displacement of zero electrical degrees, as shown in Figure 3. In reality, for an internal, there might be some small phase shift between these two currents due to possible different negative sequence impedance angles of the source equivalent circuits on the two power transformer sides. Yy0; 1:1 INS S2 ZNS S1 ZNS S2 E NS Negative Sequence Zero Potential INS S2 Relay Figure 3. Flow of Negative Sequence Currents for power transformer internal If, however, a power transformer has a non-zero phase displacement, such as, for example, an Yd5 power transformer, where the LV side terminal currents lag those of the HV side by 150 electrical degrees, and apart of that, a turns ratio other than 1, then any comparison of the negative sequence currents from the two power transformer sides is not relevant unless the protected power transformer turns ratio and its phase shift are first allowed for. In general, before any comparison of the negativesequence currents is made, the negative-sequence currents from power transformer sides must first be referred to the same side of the power transformer, which serves as the reference side. In principle, this can be any side of the power transformer. In this paper, it is always the HV side of the power transformer. Modern numerical transformer differential relays use matrix equations to automatically compensate for any power transformer vector group and turns ratio [6]. This compensation is done automatically in the on-line process of calculating the traditional differential currents. It can be shown, that the negative-sequence differential currents can be calculated by using exactly the same matrix equations, which are used to calculate the traditional differential currents. However, the same equation shall be fed by the negative-sequence currents from the two power transformer sides instead of individual phase currents, as shown in matrix equation (1.1) for a case of two-winding, Yd5 power transformer. Neg. Seq. Diff Currents Negative Sequence current contribution from HV side Negative Sequence current contribution from LV side Id _ L1_ NS IHV _ NS ILV _ NS 1 Ur _ LV 1 Id _ L2_ NS = a IHV _ NS a ILV _ NS 3 2 Ur _ HV 3 2 Id _ L3_ NS a IHV _ NS a ILV _ NS (1.1) where: Id_L1_NS is the negative sequence differential current in phase L1 (in HV side primary amperes) IHV_NS is HV side negative sequence current in HV side primary amperes (phase L1 reference) ILV_NS is LV side negative sequence current in LV side primary amperes (phase L1 reference) Ur_HV is transformer rated phase-to-phase voltage on HV side (setting parameter) Ur_LV is transformer rated phase-to-phase voltage on LV side (setting parameter)

5 o j a is the well-known complex operator for sequence quantities, e.g. a = e = + j 2 2 In reality only the first negative sequence differential current, e.g. Id_L1_NS, needs to be calculated, because the negative sequence currents always form the symmetrical three phase current system on each transformer side and three negative sequence differential currents will always have the same magnitude and be phase displaced for 120 electrical degrees from each other. As marked in equation (1.1), the first term on the right hand side of the equation, represents the total contribution of the negative sequence current from HV side compensated for eventual power transformer phase shift. The second term on the right hand side of the equation, represents the total contribution of the negative sequence current from LV side compensated for eventual power transformer phase shift and transferred to the power transformer HV side. When above compensation is made, then the degree rule is again valid between negative sequence current contributions from the two sides. For example, for any unsymmetrical external, the respective negative sequence current contributions from the HV and LV power transformer sides will be exactly 180 degrees apart and equal in magnitude, regardless the power transformer turns ratio and phase displacement, as in example shown in Figure 4. Figure 4 shows trajectories of the two separate phasors representing the negative-sequence current contributions from HV and LV sides of an Yd5 power transformer (e.g. after the compensation of the transformer turns ratio and phase displacement by using equation 1.1) for an unsymmetrical external. Observe that the relative phase angle between these two phasors is 180 electrical degrees at any point in time. There is not any current transformer saturation for this case. "steady state" for HV side neg. seq. phasor ms ka 0.2 ka 0.3 ka 0.4 ka 10 ms "steady state" for LV side neg. seq. phasor Contribution to neg. seq. differential current from HV side Contribution to neg. seq. differential current from LV side Figure 4. Trajectories of Negative Sequence Current Contributions from HV and LV sides of Yd5 power transformer during external 3.2 Internal/external discriminator The internal/external discriminator is based on the above-explained facts. Its operation is based on the relative position of the two phasors representing HV and LV negative-sequence current contributions, defined by expression (1.1). It practically performs directional comparison between

6 these two phasors. First, the LV side phasors is positioned along the zero degree line. After that the relevant position of the HV side phasor in the complex plain is determined. The overall directional characteristic of the internal/external discriminator is shown in Figure 5. The directional characteristic is defined by the settings: ****************** 1. IminNegSeq 2. NegSeqROA If one or the other of currents is too low, then no measurement is done, and 120 degrees is mapped 180 deg 120 deg 90 deg IminNegSeq Internal / external boundary. NegSeqROA (Relay Operate Angle) 0 deg External region Internal region 270 deg Figure 5. Operating characteristic of the internal/external discriminator In order to perform directional comparison of the two phasors their magnitudes must be high enough so that one can be sure that they are due to a. On the other hand, in order to guarantee a good sensitivity of the internal/external discriminator, the value of this minimum limit must not be too high. Therefore this limit value, called IminNegSeq, is settable in the range from 1% to 20% of the differential protection s base current, which is in our case the power transformer HV side rated current. The de value is 4%. Only if magnitudes of both negative sequence current contributions are above the set limit, the relative position between these two phasors is checked. If either of the negative sequence current contributions, which should be compared, is too small (less than the set value for IminNegSeq), no directional comparison is made in order to avoid the possibility to produce a wrong decision. This magnitude check, as well guarantee stability of the algorithm, when power transformer is energized. The setting NegSeqROA represents the so-called Relay Operate Angle, which determines the boundary between the internal and external regions. It can be selected in the range from ±30 degrees to ±90 degrees, with a step of 1 degree. The de value is ±60 degrees. The de setting somewhat favours security in comparison to dependability. If the above condition concerning magnitudes is fulfilled, the internal/external discriminator compares the relative phase angle between the negative sequence current contributions from the HV side and LV side of the power transformer using the following two rules: If the negative sequence currents contributions from HV and LV sides are in phase, the is internal (i.e. both phasors are within internal region) If the negative sequence currents contributions from HV and LV sides are 180 degrees out of phase, the is external (i.e. HV phasors is outside internal region)

7 Therefore, under all external condition, the relative angle is theoretically equal to 180 degrees. During internal, the angle shall ideally be 0 degrees, but due to possible different negative sequence source impedance angles on HV and LV side of power transformer, it may differ somewhat from the ideal zero value. However, during heavy s, CT saturation might cause the measured phase angle to differ from 180 degrees for external, and from about 0 degrees for internal. See Figure 6 for an example of a heavy internal with transient CT saturation. Directional Comparison Criterion: Internal as seen from the HV side ms 60 excursion from 0 degrees due to CT saturation definitely an internal external region ka 1.0 ka 1.5 ka HV side contribution to the total negative sequence differential current in ka Directional limit (within the region delimited by ± 60 degrees is internal ) trip command in 12 ms Internal declared 7 ms after internal occurred Figure 6. Operation of the internal/external discriminator for internal with CT saturation 3.3 Sensitive negative-sequence based turn-to-turn protection The sensitive, negative-sequence-current-based turn-to-turn protection detects the low-level s, which are not detected by the traditional differential protection. The sensitive protection is independent from the traditional differential protection and is a very good complement to it. The essential part of this sensitive protection is the internal/external discriminator previously described. In order to be activated, the sensitive protection requires no start signal from the traditional power transformer biased differential protection. If magnitudes of HV and LV negative sequence current contributions are above the set limit for IminNegSeq, then their relative positions are determined. If the disturbance is characterized as an internal, then a separate trip request will be placed. Any decision on the way to the final trip request must be confirmed several times in succession in order to cope with eventual CT transients. This causes a short additional operating time delay due to this security count. The trustworthy information on whether a is internal or external is typically obtained in about ten milliseconds after the inception, depending on the setting IminNegSeq, and the magnitudes of the currents. For very low-level turn-to-turn s the overall response time of this protection is about thirty milliseconds. At heavy s, approximately five milliseconds time-to-saturation of the main CT is sufficient in order to produce a correct discrimination between internal and external s

8 4. TEST CASE FROM RECORDING CAPTURED IN THE FIELD Zagreb, capital of Croatia is supplied via two 400/110kV substations. One of them is Tumbri substation where three, 300MVA autotransformers are used to supply the capital 110kV subtransmission network. In last two years Croatian utility had couple of incident with autotransformer Tr3. This autotransformer has the following rated data 300/300/100MVA; 400/115/10.5kV; YNautod5, in accordance with IEC terminology [3]. It shall be noted that the Tr3 autotransformer tertiary delta winding is not loaded and it is used as stabilizing delta winding. This autotransformer is protected with two numerical, two-winding differential protections from different manufacturers, in accordance with utility protection philosophy [7]. The differential relays minimum pickup current is set to 30% of the autotransformer rating (e.g. 300MVA). Within approximately one year the utility had four incidents with this autotransformer as stated below: 1) On 2003-April-27 at 09:39: hours, Tr3 autotransformer 400kV bushing in phase L3 has exploded causing heavy internal. Fault was cleared extremely quickly by unrestrained differential protection stage. The current from 400kV network was 2500% and the current contribution from 110kV network (i.e. current through the autotransformer windings) was up to 500% of the autotransformer rating. Due to fast tripping the autotransformer windings were not damaged. Therefore after on-site bushing replacement the autotransformer Tr3 was put back into service on 2003-May-08. 2) On 2004-January-04 at 00:35: hours, near-by external on 110kV side in phase L1 happened. The autotransformer through- current was around 280% of its rating. Both autotransformer differential protections were stable. 3) On 2004-May-04 at 05:10: hours, near-by external on 110kV side in phase L3 happened. The autotransformer through- current was around 310% of its rating. Both autotransformer differential protections were stable. 4) On 2004-May-04 at 05:28: hours, approximately eighteen minutes after the external mentioned above under point 3), autotransformer Tr3 was tripped by Buchholtz protection relay. Both numerical differential protections did not operate, neither any other current measuring or impedance measuring backup protection has started. By oil analyses it was confirmed that extensive and long-lasting electrical arcing within the autotransformer tank has caused Buchholtz relay operation. Thus, autotransformer Tr3 has been shipped to the factory for repair. During factory inspection, winding in phase L3 has been found. It was concluded that it was turn-toturn which has involved only four turns close to the autotransformer neutral point in the common winding of phase L3. Figure 7 shows affected common winding part in phase L3. Disturbance recording, from all above-mentioned cases for autotransformer Tr3, were available from the two numerical differential relays. The new algorithm was successfully tested for all of the above cases, but in this paper only its operation for case number four will be presented. By merging the disturbance recording files for above described cases three and four, one overall disturbance file has been made. This merged disturbance file was used to specifically test the new sensitive differential protection algorithm. The output results from the new differential protection algorithm during autotransformer Tr3 internal turn-to-turn are shown in Figures 8, 9 and 10. In Figure 8 relevant instantaneous currents are shown. During entire turn-to-turn all measured phase currents are smaller than 60% of the autotransformer rating. Therefore the traditional differential currents were smaller than pre-set differential minimum operational level and traditional differential protection could not operate for this, e.g. no start signal has been set in Figure 9. However, from Figure 10 it is obvious that the low-level turn-to-turn was definitely internal. Operation of internal/external discriminator consistently indicates internal. This independent but sensitive negative-sequence-current-based differential protection detects the, characterizes it as internal, and issues a trip request in 12ms. Trajectory of the HV side negative sequence current contribution reaches its steady-state point in approximately 20 ms after inception. Finally, the new differential function operates in 27 ms (the output relay contact closing time not included)

9 Obviously the new algorithm would detect and trip the autotransformer Tr3 for this turn-to-turn. Figure 7. Turn-to-turn at the end of the common winding of the Autotransformer Tr3 Currents in ka Currents in ka Currents in ka Power transformer HV side terminal currents turn-to-turn Power transformer LV side terminal currents turn-to-turn Calculated Instantaneous differential currents (referred to the HV side) normally, these currents are zero turn-to-turn Time in milliseconds with zero sequence removed idif-l1 idif-l2 idif-l3 ihv-l1 ihv-l2 ihv-l3 ilv-l1 ilv-l2 ilv-l3 Figure 8. Measured currents from HV and LV sides, and instantaneous differential currents as calculated by traditional differential protection, during Tr3 autotransformer internal turn-to-turn

10 Binary output signals. Case: Tumbri-Croatia-internal-inter-turn-.ascii inter-turn inter-turn no start signal! trip in 27 ms trip request in 26 ms detected in 12 ms STL1 STL2 STL3 TRIP TRIPRES TRIPUNRE TRNSUNRE TRNSSENS BLK2HL1 BLK2HL2 BLK2HL3 BLK5HL1 BLK5HL2 BLK5HL3 BLKWAVL1 BLKWAVL2 BLKWAVL3 INTFAULT EXTFAULT Time in milliseconds Figure 9. Output signals from new differential protection algorithm during Tr3 autotransformer internal turn-to-turn If one or the other of currents is too low, then no measurement is done External region Directional Comparison Criterion: Internal as seen from the HV side A A (negseqroa = ± 60 deg) steady-state position for this internal Internal declared 12 ms after A 50 A Contribution to total neg. seq. diff. current from HV side (in A) Directional limit (within ± negseqroa degrees is internal ) Figure 10. Operation of the internal/external discriminator during Tr3 autotransformer internal turn-to-turn

11 5. CONCLUSION The new, patent pending, sensitive turn-to-turn protection algorithm for power transformers and autotransformers has been presented. In the paper all theory and case study were done for the two winding power transformer. However, the same protection principle, with minor adjustments, can be applied for protection of two, three or multi winding power transformers and autotransformers. Operation of new internal/external discriminator for power transformers has been successfully tested, by using simulation files produced by ATP [9], disturbance recording files from independent transformer differential protection testing on the analogue network simulator [5] and finally from the disturbance recordings captured in the field. All these tests indicate excellent performance of internal/external discriminator for power transformers. It detects even minor s, with a high sensitivity and a high speed, and at the same time discriminates with a high degree of dependability between internal and external s. The only shortcomings of this new algorithm are that it only operates when power transformer is loaded and it does not provide indication of the y phase(s). However, for internal s power transformers are always tripped three-phase, while from the captured disturbance record at the moment of tripping the y phase(s) can be identified. This paper shows, that by using advanced numerical technology, it is now possible to protect power transformers with new differential protection principle, which has much higher sensitivity than traditional transformer differential protection for low-level internal s, for example winding turnto-turn s. This new protection principle only utilize transformer terminal currents, but it is capable to detect turn-to-turn which has involved only four turns (less than 1% of turns as shown in Figure 7) close to the neutral point in the common winding of phase L3 of the 300MVA, 400/110kV autotransformer. The same protection principle can be used for differential protection of other power system components like generators, shunt reactors, busbars etc. However, for all these applications where there are galvanical connections between all ends of the protected object, this new principle will only provide protection against internal multi-phase s and earth-s, i.e. it will not provide protection against turn-to-turn s as in case of power transformers. 6. REFERENCES [1] C.F. Wagner, R.D. Evans, Book: Symmetrical Components", McGraw-Hill, New York & London, 1933 [2] J.L. Blackburn, Book: Symmetrical Components for Power System Engineering, Marcel Dekker, New York, Basel, Hong Kong, 1993; ISBN: [3] International Standard IEC , "Power Transformers General", Edition 2.1, [4] B. Hillström, N. Ćosić, I. Brnčić, "Advances in Power System Protection", 11th International Conference on Power System Protection PSP98, 1998, Bled, Slovenia [5] Z. Gajić, G.Z. Shen, J.M. Chen, Z.F. Xiang," Verification of utility requirements on modern numerical transformer protection by dynamic simulation" presented at the IEE Conference on Developments in Power System Protection, Amsterdam, Netherlands, 2001 [6] F. Mekić, Z. Gajić and S. Ganesan, "Adaptive Features of Numerical Differential Relays," presented at the 29th Annual Conference for Protective Relay Engineers, Spokane, Washington, USA, October 2002 [7] Z. Gajić, I. Ivanković, B. Filipović-Grčić, Differential Protection Issues for Combined Autotransformer Phase Shifting Transformer, presented at the IEE Conference on Developments in Power System Protection, Amsterdam, Netherlands, 2004 [8] W. Bartley, Analysis of Transformer Failures, International Association of Engineering Insurers 36 th Annual Conference, Stockholm, Sweden, 2003 ( [9] ATP is the royalty-free version of the Electromagnetic Transients Program (EMTP). For more info please visit one of the following web sites: or

S1-3: New and re-discovered theories and practices in relay protection

S1-3: New and re-discovered theories and practices in relay protection (Cheboksary, September 9-13, 27) S1-3: New and re-discovered theories and practices in relay protection Practical experience from multiterminal line differential protection installations Z. GAJIĆ, I. BRNČIĆ,

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example

More information

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS 1 STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS Z. GAJIĆ S. HOLST D. BONMANN D. BAARS ABB AB, SA Products ABB AB, SA Products ABB AG, Transformers ELEQ bv Sweden Sweden Germany Netherlands zoran.gajic@se.abb.com

More information

Solution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection

Solution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection ABSTRACT National conference on Engineering Innovations and Solutions (NCEIS 2018) International Journal of Scientific Research in Computer Science, Engineering and Information Technology 2018 IJSRCSEIT

More information

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS

DIFFERENTIAL PROTECTION METHODOLOGY FOR ARBITRARY THREE-PHASE POWER TRANSFORMERS DFFERENTAL PROTECTON METHODOLOGY FOR ARBTRARY THREE-PHASE POWER TRANSFORMERS Z. Gaji ABB AB-SA Products, Sweden; zoran.gajic@se.abb.com Keywords: power transformer, phase shifting transformer, converter

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Differential Protection with REF 542plus Feeder Terminal

Differential Protection with REF 542plus Feeder Terminal Differential Protection with REF 542plus Application and Setting Guide kansikuva_bw 1MRS 756281 Issued: 09.01.2007 Version: A Differential Protection with REF 542plus Application and Setting Guide Contents:

More information

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,

More information

Unit Protection Differential Relays

Unit Protection Differential Relays Unit Protection PROF. SHAHRAM MONTASER KOUHSARI Current, pu Current, pu Protection Relays - BASICS Note on CT polarity dots Through-current: must not operate Internal fault: must operate The CT currents

More information

Transformer Protection

Transformer Protection Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary

More information

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved. Pomona, CA, May 24 & 25, 2016 Tertiary Winding Design in wye-wye Connected Transformers Scope of Presentation > Tertiary vs. Stabilizing Winding? Tertiary vs. Stabilizing Winding? Need for Stabilizing

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES

CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES CHAPTER 3 REVIEW OF POWER TRANSFORMER PROTECTION SCHEMES 3.1. Introduction Power Transformer is the nerve centre of any power distribution system. The capacity of power transformers is generally decided

More information

Transformer Protection Principles

Transformer Protection Principles Transformer Protection Principles 1. Introduction Transformers are a critical and expensive component of the power system. Due to the long lead time for repair of and replacement of transformers, a major

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

EASUN REYROLLE LIMITED

EASUN REYROLLE LIMITED OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

Differential Protection Optimal differential protection for phase shifter transformers and special transformers

Differential Protection Optimal differential protection for phase shifter transformers and special transformers Differential Protection Optimal differential protection for phase shifter transformers and special transformers Due to the energy transition, a demand for renewable energy sources integration into power

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Practical Experience with Differential Protection for Converter Transformers

Practical Experience with Differential Protection for Converter Transformers 315 Study Committee B5 Colloquium August 25-31, 213 Belo Horizonte, Brazil Practical Experience with Differential Protection for Converter Transformers Z. Gajić* ABB SA Products Sweden Summary The paper

More information

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications

Transformer Winding Design. The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications The Design and Performance of Circular Disc, Helical and Layer Windings for Power Transformer Applications Minnesota Power Systems Conference November 3 5, 2009 Earl Brown Heritage Center University of

More information

Chapter 7 Conclusion 7.1 General

Chapter 7 Conclusion 7.1 General Chapter 7 7.1 General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due

More information

Transformer Fault Categories

Transformer Fault Categories Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)

More information

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions 1 Transmission transformers are important links in the bulk power system. They allow transfer of power from generation centers, up to the high-voltage grid, and to bulk electric substations for distribution

More information

Keywords Differential Protection, FACTS, Phase Angle Regulating Transformers

Keywords Differential Protection, FACTS, Phase Angle Regulating Transformers 206 Study Committee B5 Colloquium October 19-24, 2009 Jeju sland, Korea Use of 87T Relay Principles for Overall Differential Protection of Phase Angle Regulating Transformers GAJĆ, Z. * HOLST, S. ABB AB,

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:

More information

Improving High Voltage Power System Performance. Using Arc Suppression Coils

Improving High Voltage Power System Performance. Using Arc Suppression Coils Improving High Voltage Power System Performance Using Arc Suppression Coils by Robert Thomas Burgess B Com MIEAust CPEng RPEQ A Dissertation Submitted in Fulfilment of the Requirements for the degree of

More information

HV SHUNT REACTOR SECRETS FOR PROTECTION ENGINEERS

HV SHUNT REACTOR SECRETS FOR PROTECTION ENGINEERS HV SHUNT REACTOR SECRETS FOR PROTECTION ENGINEERS By Zoran Gajić ABB Sweden Västerås, Sweden Birger Hillström ABB Sweden Västerås, Sweden Fahrudin Mekić ABB Inc. Allentown, PA 1816 Presented to: 3 th Western

More information

Bus Protection Fundamentals

Bus Protection Fundamentals Bus Protection Fundamentals Terrence Smith GE Grid Solutions 2017 Texas A&M Protective Relay Conference Bus Protection Requirements High bus fault currents due to large number of circuits connected: CT

More information

Problems connected with Commissioning of Power Transformers

Problems connected with Commissioning of Power Transformers Problems connected with Commissioning of Power Transformers ABSTRACT P Ramachandran ABB India Ltd, Vadodara, India While commissioning large Power Transformers, certain abnormal phenomena were noticed.

More information

Phase Shifting Transformers. Presented by

Phase Shifting Transformers. Presented by Phase Shifting Transformers Presented by Phase Shifting Transformers (PST s) (a.k.a. Phase Angle Regulators) VS φ S P V V S = X L L X L sin( φ φ ) L S VL φ L PST s are power flow control devices between

More information

2015 Relay School Bus Protection Mike Kockott March, 2015

2015 Relay School Bus Protection Mike Kockott March, 2015 2015 Relay School Bus Protection Mike Kockott March, 2015 History of Bus Protection Circulating current differential (1900s) High impedance differential (1940s) Percentage restrained differential (1960s)

More information

Application of Low-Impedance 7SS601 Busbar Differential Protection

Application of Low-Impedance 7SS601 Busbar Differential Protection Application of Low-Impedance 7SS601 Busbar Differential Protection 1. Introduction Utilities have to supply power to their customers with highest reliability and minimum down time. System disturbances,

More information

Substation Testing and Commissioning: Power Transformer Through Fault Test

Substation Testing and Commissioning: Power Transformer Through Fault Test 1 Substation Testing and Commissioning: Power Transformer Through Fault Test M. Talebi, Member, IEEE, Power Grid Engineering Y. Unludag Electric Power System Abstract This paper reviews the advantage of

More information

Centralized busbar differential and breaker failure protection function

Centralized busbar differential and breaker failure protection function Centralized busbar differential and breaker failure protection function Budapest, December 2015 Centralized busbar differential and breaker failure protection function Protecta provides two different types

More information

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

148 Electric Machines

148 Electric Machines 148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional

More information

function block description to the differential protection and restricted earth-fault protection functions for autotransformers

function block description to the differential protection and restricted earth-fault protection functions for autotransformers Circuit Application breaker guide control function block description to the differential protection and restricted earth-fault protection functions for autotransformers Document ID: Budapest, PRELIMINARY

More information

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System Lalit Ghatpande, SynchroGrid, College Station, Texas, 77840 Naveen Ganta, SynchroGrid, College Station, Texas,

More information

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) 1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1

More information

Testing Numerical Transformer Differential Relays

Testing Numerical Transformer Differential Relays Feature Testing Numerical Transformer Differential Relays Steve Turner Beckwith Electric Co., nc. ntroduction Numerical transformer differential relays require careful consideration as to how to test properly.

More information

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays

More information

SPAD 346 C Stabilized differential relay

SPAD 346 C Stabilized differential relay SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer

Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer Ms. Kanchan S.Patil PG, Student kanchanpatil2893@gmail.com Prof.Ajit P. Chaudhari Associate Professor ajitpc73@rediffmail.com

More information

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper

Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost

More information

Single-Core Symmetrical Phase Shifting Transformer Protection Using Multi-Resolution Analysis

Single-Core Symmetrical Phase Shifting Transformer Protection Using Multi-Resolution Analysis IJEEE, Volume 3, Spl. Issue (1) Single-Core Symmetrical Phase Shifting Transformer Protection Using Multi-Resolution Analysis Meenakshi Sahu 1, Mr. Rahul Rahangdale 1, Department of ECE, School of Engineering

More information

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers International Conference on Power System Transients IPST 23 in New Orleans, USA Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

More information

Turn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents

Turn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents Turn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents Mariya Babiy 1, Rama Gokaraju 1, Juan Carlos Garcia 2 1 University of Saskatchewan, Saskatoon, Canada 2 Manitoba HVDC Research

More information

Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching

Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching International Conference on Power Systems Transients IPST 3 in New Orleans, USA Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching Ivo Uglesic

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering) R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between

More information

Evaluating the Impact of Increasing System Fault Currents on Protection

Evaluating the Impact of Increasing System Fault Currents on Protection Evaluating the Impact of Increasing System Fault Currents on Protection Zhihan Xu, Ilia Voloh GE Grid Solutions, LLC Mohsen Khanbeigi Hydro One Abstract Every year the capacity of power systems is increasing,

More information

Detection and localization of internal turn-to-turn short circuits in transformer windings by means of negative sequence analysis

Detection and localization of internal turn-to-turn short circuits in transformer windings by means of negative sequence analysis No. E-14-AAA-0000 Detection and localization of internal turn-to-turn short circuits in transformer windings by means of negative sequence analysis Malihe Abi, Mohammad Mirzaie Faculty of Electrical and

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

Line protection with transformer in the protection zone

Line protection with transformer in the protection zone Line protection with transformer in the protection zone www.siemens.com/siprotec5 Three-end line protection with transformer in the protection range SIPROTEC 5 Application Three-end line protection with

More information

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION 18 CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION 2.1 INTRODUCTION Transformers are subjected to a variety of electrical, mechanical and thermal stresses during normal life time and they fail when these

More information

Protection of a 138/34.5 kv transformer using SEL relay

Protection of a 138/34.5 kv transformer using SEL relay Scholars' Mine Masters Theses Student Theses and Dissertations Fall 2016 Protection of a 138/34.5 kv transformer using SEL 387-6 relay Aamani Lakkaraju Follow this and additional works at: http://scholarsmine.mst.edu/masters_theses

More information

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES

OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES OPEN-PHASE DETECTION TECHNIQUES FOR CRITICAL STANDBY SUPPLIES U AJMAL, GE Grid Solutions UK Ltd, usman.ajmal@ge.com S SUBRAMANIAN, GE Grid Solutions UK Ltd, sankara.subramanian@ge.com H Ha GE Grid Solutions

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Benefits of SFRA - Case Studies

Benefits of SFRA - Case Studies 6 th International Conference on Large Power Transformers- Modern Trends Benefits of SFRA - Case Studies B B Ahir Gujarat Energy Transmission Corporation Limited 1 Outline Condition Monitoring in GETCO

More information

PIPSPC. Prepared by Eng: Ahmed Safie Eldin. And. Introduction. Protection Control. Practical. System. Power

PIPSPC. Prepared by Eng: Ahmed Safie Eldin. And. Introduction. Protection Control. Practical. System. Power PIPSPC Practical Introduction Power System Protection Control Practical Introduction To Power System Protection And Control Prepared by Eng: Ahmed Safie Eldin 2005 Contents POWER SYSTEMS PRINCIPALS. 1

More information

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *

A NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT * Iranian Journal of Science & Technology, Transaction B, Engineering, Vol. 30, No. B6, pp 643-654 Printed in The Islamic Republic of Iran, 2006 Shiraz University A NEW DIFFERENTIAL PROTECTION ALGORITHM

More information

7SG14 Duobias-M Transformer Protection

7SG14 Duobias-M Transformer Protection 7SG14 Duobias-M Transformer Protection Document Release History This document is issue 2010/02. The list of revisions up to and including this issue is: Pre release Revision Date Change 2010/02 Document

More information

16 Transformer and Transformer-feeder Protection

16 Transformer and Transformer-feeder Protection Chap16-254-279 17/06/02 9:58 Page 254 Transformer and Transformer-feeder Protection Introduction 16.1 Winding faults 16.2 Magnetising inrush 16.3 Transformer overheating 16.4 Transformer protection overview

More information

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES THE OLE OF SYNCHOPHASOS IN THE INTEGATION OF DISTIBUTED ENEGY ESOUCES Alexander APOSTOLOV OMICON electronics - USA alex.apostolov@omicronusa.com ABSTACT The introduction of M and P class Synchrophasors

More information

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016 Prepared by System Planning Division Transmission Planning Department PJM 2016 Table of Contents Table of Contents Approval...6

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS Ljubomir KOJOVIC Cooper Power Systems - U.S.A. Lkojovic@cooperpower.com INTRODUCTION In steel facilities that use Electric Arc Furnaces (EAFs) to manufacture

More information

ISSN: [IDSTM-18] Impact Factor: 5.164

ISSN: [IDSTM-18] Impact Factor: 5.164 IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY A REVIEW OF ROUTINE TESTING ON DISTRIBUTION TRANSFORMER Sukhbir Singh 1, Parul Jangra 2, Anoop Bhagat 3, Vipin Saini 4 1 Assistant

More information

IVE(TY) Department of Engineering. Electrical Machines 1. Electrical Machines 1. Hour 13. slide 1

IVE(TY) Department of Engineering. Electrical Machines 1. Electrical Machines 1. Hour 13. slide 1 Hour 3 slide Three Phase Transformer (sect. 2.6) A set of three similar single phase transformers may be connected to form a three-phase transformer (three-phase transformer bank). The primary and secondary

More information

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic

More information

System grounding of wind farm medium voltage cable grids

System grounding of wind farm medium voltage cable grids Downloaded from orbit.dtu.dk on: Apr 23, 2018 System grounding of wind farm medium voltage cable grids Hansen, Peter; Østergaard, Jacob; Christiansen, Jan S. Published in: NWPC 2007 Publication date: 2007

More information

DIRECTIONAL PROTECTION

DIRECTIONAL PROTECTION UNIVERSITY OF LJUBLJANA FACULTY OF ELECTRICAL ENGINEERING DIRECTIONAL PROTECTION Seminar work in the course Distribution and industrial networks Mentor: Prof. Grega Bizjak Author: Amar Zejnilović Ljubljana,

More information

Tom Ernst GE Digital Energy Craig Talbot Minnesota Power

Tom Ernst GE Digital Energy Craig Talbot Minnesota Power Tom Ernst GE Digital Energy Craig Talbot Minnesota Power Introduction Traditional 3-phase testing method Traditional 1-phase testing method Alternate 1-phase testing method Application examples 3-Phase

More information

Transformer differential protection

Transformer differential protection Transformer differential protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970883) Features Three phase differential protection with two, three, five or

More information

Phase Comparison Relaying

Phase Comparison Relaying MULTILIN GER-2681B GE Power Management Phase Comparison Relaying PHASE COMPARISON RELAYING INTRODUCTION Phase comparison relaying is a kind of differential relaying that compares the phase angles of the

More information

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner Digital Protective Relay Dr Murari Mohan Saha ABB AB KTH/EH2740 Lecture 3 Introduction to Modern Power System Protection A digital protective relay is an industrial microprocessor system operating in real

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

The power transformer

The power transformer ELEC0014 - Introduction to power and energy systems The power transformer Thierry Van Cutsem t.vancutsem@ulg.ac.be www.montefiore.ulg.ac.be/~vct November 2017 1 / 35 Power transformers are used: to transmit

More information

Power Station Electrical Protection A 2 B 2 C 2 Neutral C.T E M L } a 2 b 2 c 2 M M M CT Restricted E/F Relay L L L TO TRIP CIRCUIT Contents 1 The Need for Protection 2 1.1 Types of Faults............................

More information

CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS

CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS 38 CHAPTER 3 SHORT CIRCUIT WITHSTAND CAPABILITY OF POWER TRANSFORMERS 3.1 INTRODUCTION Addition of more generating capacity and interconnections to meet the ever increasing power demand are resulted in

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

Bruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc.

Bruce L. Graves /01/$ IEEE. IEEE Industry Applications Magazine PhotoDisc, Inc. Bruce L. Graves A Defining a Power System A power system is an assembly of generators, transformers, power lines, fuses, circuit breakers, protective devices, cables, and associated apparatus used to generate

More information

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch.

Training Fees 3,300$ per participant including Materials/Handouts, Tea/Coffee Refreshments & International Buffet Lunch. Training Title POWER TRANSFORMERS Training Duration 5 days Training Venue and Dates Power transformers 5 20-24 May $3,300 Abu Dhabi In any of the 5 star hotel. The exact venue will be informed soon. Training

More information

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques

Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Understanding and Extracting Valuable Information from Basic and Advanced Power Transformer Testing Techniques Charles Sweetser, Services Manager, PRIM Engineering, Waltham, Mass. Topics of Discussion

More information

Transformer differential protection RADSB

Transformer differential protection RADSB protection RADSB User s Guide 1MRK 504 002-UEN Replaces 1MDU04007-EN Features Three-phase differential protection with two, three, five or six through-current restraint inputs Complete phase and earth-fault

More information

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006 October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date

More information

S C Strength of Winding Exits and Leads : A critical area for Failure Prevention in Power Transformers

S C Strength of Winding Exits and Leads : A critical area for Failure Prevention in Power Transformers S C Strength of Winding Exits and Leads : A critical area for Failure Prevention in Power Transformers by MANAN PANDYA SIEMENS LTD. manan.pandya@siemens.com 1 Introduction Short circuit withstand capability

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Substation Preventive Maintenance

Substation Preventive Maintenance Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS

More information

Negative-Sequence Differential Protection Principles, Sensitivity, and Security

Negative-Sequence Differential Protection Principles, Sensitivity, and Security 1 Negative-Sequence Differential Protection Principles, Sensitivity, and Security Bogdan Kasztenny, Normann Fischer, and Héctor J. Altuve, Schweitzer Engineering Laboratories, Inc. Abstract This paper

More information

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis

Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis 1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current

More information