Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer
|
|
- Belinda Doyle
- 6 years ago
- Views:
Transcription
1 Negative-Sequence Based Scheme For Fault Protection in Twin Power Transformer Ms. Kanchan S.Patil PG, Student Prof.Ajit P. Chaudhari Associate Professor ABSTRACT A power transformer is a vital component in any power system network and any of its failure may cause disturbance in the proper operation of electrical power system network. Negative sequence current flows in transformers primary and secondary which can be computed by using digital relay along with their phase differences. Magnitude and phase information of negative sequence currents can be used to detect minor transformer windings fault. Negative sequence current and voltage based algorithms are very useful in the determination of faults in electrical power systems. Negative sequence algorithm becomes insensitive when current is not flowing through the secondary windings of transformer. A relay system for the protection of transformer using negative sequence current and voltage is introduced in this paper. The proposed protection scheme was evaluated with different cases, which included different numbers of shorted turns of the transformer, inrush currents. The experimental results presented in this paper indicate that the algorithm proposed in this paper is faster and more sensitive and is capable of detecting turn-to-turn faults occurring during transformer energization. Keywords Negative Sequence Algorithm, Power Transformer. 1. INTRODUCTION The faults occur in a transformer are classified in two types: external and internal faults. External faults are those that occur outside of the transformer: over voltage, over-fluxing, under frequency, and external System short circuits. Internal faults are those that occur Inside of the transformer: winding turn-to-turn, turn-to-ground, over-fluxing. From the last few decades a continuous growth has observed in the power system and the progress will continue in the upcoming years. A transformer, being an integrated part of the power system, is an important link between a generating power station and a point of power utilization.[1] Due to various kinds of intricate loads and their control systems, transformer is prone to faults. Internal winding faults in transformers can cause huge damages in a very short time, and in some cases the damages are repairable, and also about 70%-80% of transformer failures are caused by internal faults. Among these faults, Prof.Girish K. Mahajan Associate Professor girishmhajan_16@rediffmail.com Prof.Gaurav P. Tembhurnikar Asst.Professor tgaurav81@gmail.com Winding turn to turn fault is challenging to monitor and detect, especially at lower magnitude of the fault current. Internal faults involve a magnitude of fault current which is low relative to the power transformer base current. This indicates a need for high speed and high sensitivity to ensure good protection. According to the IEEE Standard documents, there is no one standard way to protect all power transformers against minor internal faults and at the same time to satisfy basic protection requirements: sensitivity, selectivity, and speed. The most difficult internal turn-to-turn fault is the fault which initially involves only a few turns [2]. Turn to turn faults can be calculated by numerous techniques. Fuzzy logic based techniques are also available to detect turn to turn faults which involves 16% of transformer windings [3]. To distinguish between healthy and faulted transformer, negative sequence algorithm having some assumptions such as the faults are unlikely to be three phase faults. Zero sequence current based schemes are also proposed to detect turn to turn faults [4]. The algorithms used in zero sequence current protection schemes are very sensitive to faults and is intended to be used in conjunction with current differential protection scheme during energization. During normal operations 1% turn to turn faults can be detected by using negative sequence current based algorithms [5]. Magnitude and phase difference of primary and secondary negative sequence current can be used by the algorithms to detect turn to turn faults. During energization, the transformer's secondary breaker is open. Inrush current flows on the primary side of the transformer while no current flows on the secondary side of the transformer. Therefore, the phase information of the negative-sequence current on the secondary side of the transformer is not useful during energization. [1]Voltage differential algorithms are used to protect the transformer from third harmonics voltage which is achieved by negative sequence algorithm. The transformer protection scheme is 166
2 based on the changes in flux linkages which occur due to turn to turn faults which is applied to both Y-Y winding arrangement and Y- winding arrangements. The algorithm described in [6] was found to operate during transformer energization and over excitation conditions. The algorithm's sensitivity was able to detect turn-to-turn faults comprised of 10% of the windings. Voltages as well as Currents also get affected by the turn to turn faults. The algorithms introduced in this paper compares primary and secondary voltage magnitude to detect the turn to turn faults.[5] Algorithm was developed in order to protect the transformer during energization and normal operation. Proposed algorithm was tested using real time simulator. Relay system is proposed in order to protect the transformer using real time simulator. The simulated transformer model was capable of simulating transformer energization current along with turn-to-turn faults[7]. To recognise value of inrush currents in constructed model was calculated using iterative process given in [8] and according to the example given in [9]. The calculations for inrush currents can be provided for the transformer under study. A brief discussion on the methods used to detect turn to turn faults in power transformer is given in section II. Proposed negative sequence based schemes are discussed in section III. Section IV describes the relay system and how it was tested. Section V provides the prototype test results. 2. TURN TO TURN FAULTS DETECTION For transformer protection, negative sequence current protection based relays are in use [10]. This relay makes use of a negative-sequence percentage differential current element which is calculated by the vector addition of all currents entering the protection zone. Sensitivity of algorithm is high which can detect faults involving 2% of the transformer's windings. The negative-sequence current differential element blocks the relay during inrush conditions. External fault region 180 o 90 o 270 o Internal fault 0 o region Fig:1 Detection of fault using negative sequence currents The primary and secondary negative-sequence currents along with their phase differences are used in the relay description [11]. Figure:1 describes the algorithm visually. Both primary and secondary negative-sequence current magnitude must be larger than in order for a phase comparison to occur. If either or both negative-sequence currents are less than, the phase is set to 120. This angle is outside the Relay Operating Angle (ROA) and ensures no trip signal is issued if the negativesequence current is too small to obtain an accurate phase angle. If the negative-sequence currents magnitudes are larger than, the phase difference between the primary and secondary negative-sequence currents is examined. This phase difference must fall within the region described by the ROA. 3. SCHEME BASED NEGATIVE SEQUENCE 3.1 Scheme based Negative sequence current A negative-sequence current-based algorithm (NSCA) for turn-to-turn faults sensing is proposed in [5]. First of all, the negative sequence current is calculated for both the primary side and secondary side of the transformer. Form this calculations we get, two negative-sequence current phasors. Let I p and I s denote the negative-sequence current phasors calculated for the primary and secondary side of the transformer. The next step of this algorithm is to check the magnitudes of I p and I s to ensure that they are both above a minimum threshold as shown in equation (1) and (2). This is important not only to prevent false tripping due to minor imbalances but also to ensure that the phase angle of the negative-sequence currents are reliable. I 2 p > Base current (Primary side) (1) I 2 s > Base current (Secondary side) (2) If the magnitude satisfy above equations then the phases of I p and I s are compared. I 2 p - I 2 s < 60 o (3) If equation (3) is satisfied, then there is trip. The current transformers (CT) are arranged such that negative-sequence current caused by external faults result in phase differences of 180. Ideally, an internal fault would results in a zero phase difference. Current Transformer saturation is the main cause of excursions from the ideal phase difference [5], making it necessary to allow for a range of angles from 0 to 60 o 3.2 Proposed Scheme By using advanced numerical technology, it is now possible to protect power transformers with new differential protection principle, which has much higher sensitivity than traditional transformer differential protection for low-level internal faults. The basic requirement of the algorithm is to satisfy phase comparison of equation (1) & (2). Negative sequence 167
3 current magnitudes of both primary and secondary currents must be greater than the threshold values given in equation (1) & (2). When current is flowing on the primary and secondary sides of the transformer inrush current can occur during the removal of a fault or the energization of transformer. When transformers primary is switch on by keeping secondary open, current will not flow in secondary windings while inrush current starts to flow in primary windings causing the negative-sequence current-based turn-to-turn fault detection method to block for any severity of fault. Currents as well as voltages will be affected by the turn to turn faults occurring in the transformer. Also the transformer s turn ratio would be affected by the turn to turn faults. Due to this voltages between all the phases gets disturbed causing imbalance between negative sequence current or voltages in three phase system. When transformer is loaded the current method of negative sequence fault detection is effective. But as there is no load current flowing during energization, this method is blind to turn-to-turn faults. manner similar to differential current protection. Equation (4), (5), (6), and (7) are valid for Y-Y connected transformers. = = Vp (5) V p (6) [ ] = [ ] [ ] (7) Similarly the secondary side turn-to-turn fault will change the effective turns ratio, from N s to N s. A fault on the primary side causes a decrease in secondary phase voltage while a fault on the secondary side causes an increase in phase voltage. Voltage exists on the load side of the transformer whether current is flowing or not. Inrush current affects the terminal voltages which allow negative sequence voltage algorithm to react faster than the current differential algorithm. the negative-sequence voltages for the primary and secondary side of the transformer can be calculated if the primary phase voltages and secondary phase voltages are available. The algorithm for comparing these two negative-sequence voltages is similar to the differential current algorithm. The pick-up negative-sequence voltage is set to 1% of the rated phase voltage. In order to illustrate how a voltage imbalance is detected, a single phase transformer with a turn-to-turn fault will be discussed in detail. It represents one phase of a 3-phase transformer experiencing a turn-to turn fault. Two scenarios will be discussed: a turn-to-turn fault on the primary side or a turn-to-turn fault on the secondary side. A small portion of the primary windings are shorted causing a small amount of additional current I 2 p to be drawn. This does not create a significant change in e p since the source resistance is assumed to be low. Therefore the negative- sequence voltage contributed by the primary side, given by V 2 p in (4), will be negligible [ ] = [ ] [ ] (4) The current travelling through the short circuit changes the mmf contribution of the faulted winding causing a change in the effective turns ratio from N p to N p. Therefore the secondary side contributes a large amount of negativesequence voltage, as given by in (6). The two negativesequence voltage magnitudes and are compared in a Fig:2 Algorithm for negative sequence current 4. NEGATIVE SEQUENCE ALGORITHMS First of all primary and secondary side negative sequence currents are considered. Figure 2 shows the algorithm for negative sequence currents. After that obtain primary and secondary side negative sequence current magnitude and also phase. If negative-sequence current exists only on the primary side of the transformer but not on secondary side, the primary side of the transformer is being energized. For transformer discrete Fourier transform and negative sequence transform on the primary and secondary side three phase currents was obtained. Here only the magnitude of the primary and secondary negative-sequence current is considered. Both the primary negative-sequence current and the secondary negative-sequence current, transformed to the primary side of the transformer, must be larger than 1% of the rated primary 168
4 current. This prevents erroneous tripping due to small imbalances. An energization on the secondary side of the transformer also results in the selection of the negative-sequence voltage algorithm. Figure 3 shows the algorithm for negative sequence voltages. the magnitude of the primary and secondary negative-sequence voltage is of interest in this case. Notice that the secondary negative-sequence voltage is transformed to the primary side of the transformer. Both the primary negative-sequence voltage and the secondary negative-sequence voltage, transformed to the primary side of the transformer, must be larger than 1% of the rated primary voltage which prevents erroneous tripping due to small imbalances in transformer. The restraining and differential voltages are calculated using (8) and (9). If the differential voltage exceeds the restraining voltage equation, a trip is warranted. V r = (Average of primary and secondary voltage magnitude) x (nominal turns ratio) (8) 5. SIMULATION RESULTS Fig:4 Voltage and current waveform of transformer on primary side when 2% windings are shorted V d = (Difference of of primary and secondary voltage magnitude) x (nominal turns ratio) (9) IEEE standard [13] requires that the transformer winding voltages, at no load, be within 0.5% of the nameplate voltage. If a 0.5% imbalance is introduced to the otherwise healthy system, it produces a negative-sequence voltage well below the threshold. Fig:5 Voltage and current waveform on secondary side of transformer Fig: 3 Algorithm for negative sequence voltages Fig:6 Pattern for inrush currents in three phases of 169
5 transformer when 2% windings are shorted on primary side Fig:7 Voltage and current waveform of transformer on primary side when 20% windings are shorted Fig.8 Voltage and current waveform on secondary side of transformer Fig:9 Pattern for inrush currents in three phases of transformer when 20% windings are shorted on primary side Figure 4 shows voltage and current waveforms of transformer when primary side of transformer is shorted by 2%. Voltage waveform are shown by upper part and lower part shows current waveform. Normal operation of transformer is seen till 1second, at the instant of 1 second fault occurs which causes disturbance in the operation of power transformer. But when only 2% turns are shorted during turn to turn faults, faults could not be detected properly and hence there is no trip at instant of 1second, it is clearly seen in figure 4, 5, 6. Figure 5 shows voltage and current waveform of transformer on secondary side. Pattern for inrush current is shown in figure 6 when 2% winding are shorted. Inrush currents for all three phases of transformer on primary side is shown in figure. Figure 7 shows Voltage and current waveform of transformer on primary side when 20% windings are shorted. Primary side of transformer is taken into consideration. Occurrence and clearance of fault during instant of 1 sec is clearly shown in figure 7. Fault is cleared within 0.02 seconds in power transformer when 20% windings are shorted on primary side. Voltage waveform are shown by upper part and lower part shows current waveform. The changes in magnitude of current during, after and before occurrence of fault is to be noted. Figure 8 shows voltage and current waveforms on the secondary side of power transformer. The voltage and current waveforms are shown during energization of power transformer. The waveforms can be seen before, after and during energization of the primary side of transformer. Pattern for inrush currents in all the three phases of transformer is shown in figure 9 when 20% windings are shorted on primary side. At the instant of one second fault occurs and cleared within a very short period of 0.02 seconds and after words pattern becomes uniform again. The working of transformer can be observed before occurrence of fault, during fault and after clearing the fault. 6. CONCLUSION In this paper, an efficient protection scheme based on negative sequence currents for detecting minor internal turn to-turn faults in power transformers was described. The proposed scheme is simple to implement The proposed protection scheme was evaluated with different cases, which included different numbers of shorted turns of the transformer, different values of the system parameters, different connections of the power transformer, and the inrush current. By using the proposed algorithm turn-to-turn faults involving 5% of the transformer's windings were detected. The negative-sequence-based algorithm was seen to be more sensitive and faster than the current differential algorithms. The reliability of protection system using negative sequence algorithm is increased. 170
6 REFERENCES [1] Daniel Zacharias and Ramakrishna Gokaraju Prototype of a Negative-Sequence Turn-to-Turn Fault Detection Scheme for Transformers, IEEE transactions on power delivery, VOL. 31, NO. 1, FEBRUARY [2] Mariya Babiy, Rama Gokaraju, Juan Carlos Garcia Turn-to Turn Fault Detection in Transformers Using Negative Sequence Current 2011 IEEE Electrical Power and Energy Conference /11/$ IEEE [3] B. Kasztenny, E. Rosolowski, M. Saha, and B. Hillstrom, A self-organizing fuzzy logic based protective relay-an application to power transformer protection, IEEE Trans. Power Del., vol. 12, no. 3, pp , Jul [4] A. Wiszniewski, W. Rebizant, and L. Schiel, Sensitive protection of power transformers for internal inter-turn faults, in Proc. IEEE PowerTech, Bucharest, Romania, Jul. 28 2, 2009, pp [5] Z. Gajic, I. Brncic, B. Hillstrom, and I. Ivankovic, Sensitive turn-to turn fault protection for power transformers, in CIGRE, Study Committee B5 Colloq., Calgary, AB, Canada, [6] Y. Kang, B. Lee, S. Kang, and P. Crossley, Transformer protection based on the increment of flux linkages, Proc. Inst. Elect. Eng., Gen., Transm. Distrib., vol. 151, no. 4, pp , [7] B. Kasztenny, E. Rosolowski, M. M. Saha, and B. Hillstrom, A power transformer model for investigation of protection schemes, presented at the Int. Conf. Power Syst. Transients, Lisbon, Portugal, Sep [8] T. R. Specht, Transformer magnetizing inrush current, Trans. Amer. Inst. Elect. Eng., vol. 70, no. 1, pp , Jul [9] S. Kulkarni and S. Khaparde, Transformer Engineering, Design and Practice. New York, USA: Marcel Dekker, [10] Schweitzer Engineering Laboratories, Pullman, WA, USA, SEL-487E transformer differential relay datasheet, Rep. no. PM487E-01, [11] Transformer Protection RET650 Technical Manual, 1st ed. ABB, [12] B. Kasztenny and A. Kulidjian, An improved transformer inrush restraint algorithm increases security while maintaining fault response performance, presented at the 53rd Annu. Conf. Protect. Relay Eng.,College Station, TX, USA, Apr [13] IEEE Standard General Requirements for Liquid- Immersed Distribution, Power, and Regulating Transformers, Std., Standard no. C ,
Turn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents
Turn-to-Turn Fault Detection in Transformers Using Negative Sequence Currents Mariya Babiy 1, Rama Gokaraju 1, Juan Carlos Garcia 2 1 University of Saskatchewan, Saskatoon, Canada 2 Manitoba HVDC Research
More informationAnalysis of Modern Digital Differential Protection for Power Transformer
Analysis of Modern Digital Differential Protection for Power Transformer Nikhil Paliwal (P.G. Scholar), Department of Electrical Engineering Jabalpur Engineering College, Jabalpur, India Dr. A. Trivedi
More informationKeywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer
Vol. 3 Issue 2, February-2014, pp: (69-75), Impact Factor: 1.252, Available online at: www.erpublications.com Modeling and Simulation of Modern Digital Differential Protection Scheme of Power Transformer
More informationENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES
ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES N. Perera 1, A. Dasgupta 2, K. Narendra 1, K. Ponram 3, R. Midence 1, A. Oliveira 1 ERLPhase Power Technologies Ltd. 1 74 Scurfield
More informationInternational Journal of Advance Engineering and Research Development ANALYSIS OF INTERNAL AND EXTERNAL FAULT FOR STAR DELTA TRANSFORMER USING PSCAD
Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 6, June -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 ANALYSIS OF
More informationA NEW DIFFERENTIAL PROTECTION ALGORITHM BASED ON RISING RATE VARIATION OF SECOND HARMONIC CURRENT *
Iranian Journal of Science & Technology, Transaction B, Engineering, Vol. 30, No. B6, pp 643-654 Printed in The Islamic Republic of Iran, 2006 Shiraz University A NEW DIFFERENTIAL PROTECTION ALGORITHM
More informationDetection and localization of internal turn-to-turn short circuits in transformer windings by means of negative sequence analysis
No. E-14-AAA-0000 Detection and localization of internal turn-to-turn short circuits in transformer windings by means of negative sequence analysis Malihe Abi, Mohammad Mirzaie Faculty of Electrical and
More informationII. DIFFERENTIAL PROTECTION
Differential Protection of Power Transformer Using Simulink Mandeep Singh 1, Harjit Singh Kainth 2 1 M. Tech Student, Arni University Kangra, India 2 Assistant Professor, Arni University Kangra, India
More informationPOWER TRANSFORMER PROTECTION USING ANN, FUZZY SYSTEM AND CLARKE S TRANSFORM
POWER TRANSFORMER PROTECTION USING ANN, FUZZY SYSTEM AND CLARKE S TRANSFORM 1 VIJAY KUMAR SAHU, 2 ANIL P. VAIDYA 1,2 Pg Student, Professor E-mail: 1 vijay25051991@gmail.com, 2 anil.vaidya@walchandsangli.ac.in
More informationSingle-Core Symmetrical Phase Shifting Transformer Protection Using Multi-Resolution Analysis
IJEEE, Volume 3, Spl. Issue (1) Single-Core Symmetrical Phase Shifting Transformer Protection Using Multi-Resolution Analysis Meenakshi Sahu 1, Mr. Rahul Rahangdale 1, Department of ECE, School of Engineering
More informationImproved differential relay for bus bar protection scheme with saturated current transformers based on second order harmonics
Journal of King Saud University Engineering Sciences (2016) xxx, xxx xxx King Saud University Journal of King Saud University Engineering Sciences www.ksu.edu.sa www.sciencedirect.com ORIGINAL ARTICLES
More informationSymmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines
Symmetrical Components in Analysis of Switching Event and Fault Condition for Overcurrent Protection in Electrical Machines Dhanashree Kotkar 1, N. B. Wagh 2 1 M.Tech.Research Scholar, PEPS, SDCOE, Wardha(M.S.),India
More informationFeature Extraction of Magnetizing Inrush Currents in Transformers by Discrete Wavelet Transform
Feature Extraction of Magnetizing Inrush Currents in Transformers by Discrete Wavelet Transform Patil Bhushan Prataprao 1, M. Mujtahid Ansari 2, and S. R. Parasakar 3 1 Dept of Electrical Engg., R.C.P.I.T.
More information1842 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 4, OCTOBER 2009
1842 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 4, OCTOBER 2009 Phasor Estimation in the Presence of DC Offset and CT Saturation Soon-Ryul Nam, Member, IEEE, Jong-Young Park, Sang-Hee Kang, Member,
More informationDiscrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component
International Journal Of Computational Engineering Research (ijceronline.com) Vol. 3 Issue. 3 Discrimination of Fault from Non-Fault Event in Transformer Using Concept of Symmetrical Component 1, Mr. R.V.KATRE,
More informationCURRENT-TRANSFORMER (CT) saturation leads to inaccurate
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 4, OCTOBER 2011 2531 Compensation of the Current-Transformer Saturation Effects for Digital Relays Firouz Badrkhani Ajaei, Majid Sanaye-Pasand, Senior
More informationData. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner
Digital Protective Relay Dr Murari Mohan Saha ABB AB KTH/EH2740 Lecture 3 Introduction to Modern Power System Protection A digital protective relay is an industrial microprocessor system operating in real
More informationAn Improved Algorithm for Variable Slope Differential Protection of Distribution Transformer using Harmonic Restraint
An Improved Algorithm for Variable Slope Differential Protection of Distribution Transformer using Harmonic Restraint B S Shruthi National Institute of Technology Karnataka, Surathkal, India Email: shruthibs123@gmail.com
More informationA Novel Fuzzy Neural Network Based Distance Relaying Scheme
902 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000 A Novel Fuzzy Neural Network Based Distance Relaying Scheme P. K. Dash, A. K. Pradhan, and G. Panda Abstract This paper presents a new
More informationwww. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay
Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:
More informationKeywords: Wavelet packet transform (WPT), Differential Protection, Inrush current, CT saturation.
IJESRT INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY Differential Protection of Three Phase Power Transformer Using Wavelet Packet Transform Jitendra Singh Chandra*, Amit Goswami
More informationDistance Relay Response to Transformer Energization: Problems and Solutions
1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering
More informationBus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero
Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic
More informationIdentification of Inrush and Internal Fault in Indirect Symmetrical Phase Shift Transformer Using Wavelet Transform
J Electr Eng Technol.2017; 12(5): 1697-1708 http://doi.org/10.5370/jeet.2017.12.5.1697 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 Identification of Inrush and Internal Fault in Indirect Symmetrical Phase
More informationof the improved scheme is presented. Index Terms Inrush current, power quality, transformer.
208 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 1, JANUARY 2007 A Sequential Phase Energization Method for Transformer Inrush Current Reduction Transient Performance and Practical Considerations
More informationInternational Journal of Digital Application & Contemporary research Website: (Volume 2, Issue 10, May 2014)
Digital Differential Protection of Power Transformer Gitanjali Kashyap M. Tech. Scholar, Dr. C. V. Raman Institute of Science and technology, Chhattisgarh (India) alisha88.ele@gmail.com Dharmendra Kumar
More informationPower System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)
Differential Protection (Unit protection) Differential Protection Differential protection is the best technique in protection. In this type of protection the electrical quantities entering and leaving
More informationAutomatic Transfer Switch (ATS) Using Programmable Logic Controller (PLC)
Automatic Transfer Switch (ATS) Using Programmable Logic Controller (PLC) Dr. Hamdy Ashour Arab Academy for Science &Technology Department of Electrical & Computer Control Engineering P.O. 1029 Miami,
More informationHands On Relay School Open Lecture Transformer Differential Protection Scott Cooper
Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost
More informationImproving Current and Voltage Transformers Accuracy Using Artificial Neural Network
Improving Current and Voltage Transformers Accuracy Using Artificial Neural Network Haidar Samet 1, Farshid Nasrfard Jahromi 1, Arash Dehghani 1, and Afsaneh Narimani 2 1 Shiraz University 2 Foolad Technic
More informationVerifying Transformer Differential Compensation Settings
Verifying Transformer Differential Compensation Settings Edsel Atienza and Marion Cooper Schweitzer Engineering Laboratories, Inc. Presented at the 6th International Conference on Large Power Transformers
More informationWavelet Based Transient Directional Method for Busbar Protection
Based Transient Directional Method for Busbar Protection N. Perera, A.D. Rajapakse, D. Muthumuni Abstract-- This paper investigates the applicability of transient based fault direction identification method
More informationInternational Journal of Digital Application & Contemporary research Website: (Volume 2, Issue 6, January 2014)
A New Method for Differential Protection in Power Transformer Harjit Singh Kainth* Gagandeep Sharma** *M.Tech Student, ** Assistant Professor (Electrical Engg. Department) Abstract: - This paper presents
More informationUHV TRANSFORMERS DIFFERENTIAL PROTECTION BASED ON THE SECOND HARMONIC SUPPRESSION
International Journal on Technical and Physical Problems of Engineering (IJTPE) Published by International Organization of IOTPE ISSN 2077-3528 IJTPE Journal www.iotpe.com ijtpe@iotpe.com March 2015 Issue
More informationOperation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software
Operation Analysis of Current Transformer with Transient Performance Analysis Using EMTP Software Govind Pandya 1, Rahul Umre 2, Aditya Pandey 3 Assistant professor, Dept. of Electrical & Electronics,
More informationSubstation Testing and Commissioning: Power Transformer Through Fault Test
1 Substation Testing and Commissioning: Power Transformer Through Fault Test M. Talebi, Member, IEEE, Power Grid Engineering Y. Unludag Electric Power System Abstract This paper reviews the advantage of
More informationDiscrimination between Inrush and Fault Current in Power Transformer by using Fuzzy Logic
Discrimination between Inrush and Fault Current in Power Transformer by using Fuzzy Logic Abdussalam 1, Mohammad Naseem 2, Akhaque Ahmad Khan 3 1 Department of Instrumentation & Control Engineering, Integral
More informationTransformer Protection
Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationSolution for Effect of Zero Sequence Currents on Y-Y Transformer Differential Protection
ABSTRACT National conference on Engineering Innovations and Solutions (NCEIS 2018) International Journal of Scientific Research in Computer Science, Engineering and Information Technology 2018 IJSRCSEIT
More informationImproving Transformer Protection
Omaha, NB October 12, 2017 Improving Transformer Protection Wayne Hartmann VP, Customer Excellence Senior Member, IEEE Wayne Hartmann Senior VP, Customer Excellence Speaker Bio whartmann@beckwithelectric.com
More informationPower System Protection Manual
Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,
More informationA New Network Proposal for Fault-Tolerant HVDC Transmission Systems
A New Network Proposal for Fault-Tolerant HVDC Transmission Systems Malothu Malliswari 1, M. Srinu 2 1 PG Scholar, Anurag Engineering College 2 Assistant Professor, Anurag Engineering College Abstract:
More informationMATHEMATICAL MODELING OF POWER TRANSFORMERS
MATHEMATICAL MODELING OF POWER TRANSFORMERS Mostafa S. NOAH Adel A. SHALTOUT Shaker Consultancy Group, Cairo University, Egypt Cairo, +545, mostafanoah88@gmail.com Abstract Single-phase and three-phase
More informationHands On Relay School Open Lecture Transformer Differential Protection Scott Cooper
Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost
More informationPROTECTIVE RELAY MISOPERATIONS AND ANALYSIS
PROTECTIVE RELAY MISOPERATIONS AND ANALYSIS BY STEVE TURNER, Beckwith Electric Company, Inc. This paper provides detailed technical analysis of two relay misoperations and demonstrates how to prevent them
More informationEnhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)
Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG) PATTI.RANADHEER Assistant Professor, E.E.E., PACE Institute
More informationProtecting power transformers from common adverse conditions
Protecting power transformers from common adverse conditions by Ali Kazemi, and Casper Labuschagne, Schweitzer Engineering Laboratories Power transformers of various size and configuration are used throughout
More informationGenerator Protection GENERATOR CONTROL AND PROTECTION
Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault
More informationProceedings of the 5th WSEAS Int. Conf. on SIMULATION, MODELING AND OPTIMIZATION, Corfu, Greece, August 17-19, 2005 (pp )
Proceedings of the 5th WSEAS Int. Conf. on SIMULATION, MODELING AND OPTIMIZATION, Corfu, Greece, August 7-9, 5 (pp567-57) Power differential relay for three phase transformer B.BAHMANI Marvdasht Islamic
More informationA DWT Approach for Detection and Classification of Transmission Line Faults
IJIRST International Journal for Innovative Research in Science & Technology Volume 3 Issue 02 July 2016 ISSN (online): 2349-6010 A DWT Approach for Detection and Classification of Transmission Line Faults
More informationCatastrophic Relay Misoperations and Successful Relay Operation
Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations
More informationAnalyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System
Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System Lalit Ghatpande, SynchroGrid, College Station, Texas, 77840 Naveen Ganta, SynchroGrid, College Station, Texas,
More informationISSN Vol.05,Issue.06, June-2017, Pages:
WWW.IJITECH.ORG ISSN 2321-8665 Vol.05,Issue.06, June-2017, Pages:1061-1066 Fuzzy Logic Based Fault Detection and Classification of Unsynchronized Faults in Three Phase Double Circuit Transmission Lines
More informationImpact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis
1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current
More informationPerformance of current transformer operate under harmonic condition and their effects on transformer differential protection
MTEC Web of Conferences 159, 02075 (2018) IJCET & ISMPE 2017 Performance of current transformer operate under harmonic condition and their effects on transformer differential protection Indra Nisja Department
More informationProtective Relaying of Power Systems Using Mathematical Morphology
Q.H. Wu Z. Lu T.Y. Ji Protective Relaying of Power Systems Using Mathematical Morphology Springer List of Figures List of Tables xiii xxi 1 Introduction 1 1.1 Introduction and Definitions 1 1.2 Historical
More informationOvercurrent relays coordination using MATLAB model
JEMT 6 (2018) 8-15 ISSN 2053-3535 Overcurrent relays coordination using MATLAB model A. Akhikpemelo 1 *, M. J. E. Evbogbai 2 and M. S. Okundamiya 3 1 Department of Electrical and Electronic Engineering,
More informationShortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller
Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of
More informationDistance Element Performance Under Conditions of CT Saturation
Distance Element Performance Under Conditions of CT Saturation Joe Mooney Schweitzer Engineering Laboratories, Inc. Published in the proceedings of the th Annual Georgia Tech Fault and Disturbance Analysis
More informationVisualization and Animation of Protective Relay Operation
Visualization and Animation of Protective Relay Operation A. P. Sakis Meliopoulos School of Electrical and Computer Engineering Georgia Institute of Technology Atlanta, Georgia 30332 George J. Cokkinides
More informationA Hybrid Method for Power System Frequency Estimation Jinfeng Ren, Student Member, IEEE, and Mladen Kezunovic, Fellow, IEEE
1252 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 3, JULY 2012 A Hybrid Method for Power System Frequency Estimation Jinfeng Ren, Student Member, IEEE, and Mladen Kezunovic, Fellow, IEEE Abstract
More informationTransformer Protection Principles
Transformer Protection Principles 1. Introduction Transformers are a critical and expensive component of the power system. Due to the long lead time for repair of and replacement of transformers, a major
More informationImplementation of Power Transformer Differential Protection Based on Clarke s Transform and Fuzzy Systems
Implementation of Power Transformer Differential Protection Based on Clarke s Transform and Fuzzy Systems Prasenjit Dey Prof. Priyanath Das Dr. Ajoy Kumar Chakrabothy (P.G Scholar) (Associate Prof.) (Associate
More informationProtection of a 138/34.5 kv transformer using SEL relay
Scholars' Mine Masters Theses Student Theses and Dissertations Fall 2016 Protection of a 138/34.5 kv transformer using SEL 387-6 relay Aamani Lakkaraju Follow this and additional works at: http://scholarsmine.mst.edu/masters_theses
More informationISSN: Page 298
Sizing Current Transformers Rating To Enhance Digital Relay Operations Using Advanced Saturation Voltage Model *J.O. Aibangbee 1 and S.O. Onohaebi 2 *Department of Electrical &Computer Engineering, Bells
More informationAFTER an overhead distribution feeder is de-energized for
1902 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011 A New Technique to Detect Faults in De-Energized Distribution Feeders Part II: Symmetrical Fault Detection Xun Long, Student Member,
More informationAnalysis of Microprocessor Based Protective Relay s (MBPR) Differential Equation Algorithms
WWWJOURNALOFCOMPUTINGORG 21 Analysis of Microprocessor Based Protective Relay s (MBPR) Differential Equation Algorithms Bruno Osorno Abstract This paper analyses and explains from the systems point of
More informationIMPLEMENTATION OF DIFFERENTIAL PROTECTION OF THREE PHASE TRANSFORMER USING MATLAB SIMULINK
Fourth International Conference on Control System and Power Electronics CSPE IMPLEMENTATION OF DIFFERENTIAL PROTECTION OF THREE PHASE TRANSFORMER USING MATLAB SIMULINK P.B.Thote * and Dr.M.B.Daigavane
More informationGenerator Turn-to-Turn Fault Protection Using a Stator-Rotor-Bound Differential Element
Generator Turn-to-Turn Protection Using a Stator-Rotor-Bound Differential Element Bogdan Kasztenny, Normann Fischer, Héctor J. Altuve, and Douglas Taylor Schweitzer Engineering Laboratories, Inc. Original
More informationImproved power transformer protection using numerical relays
Improved power transformer protection using numerical relays Bogdan Kasztenny* and Mladen Kezunovic Texas A&M University, USA Large power transformers belong to a class of very expensive and vital components
More informationApplication of Wavelet Transform in Power System Analysis and Protection
Application of Wavelet Transform in Power System Analysis and Protection Neha S. Dudhe PG Scholar Shri Sai College of Engineering & Technology, Bhadrawati-Chandrapur, India Abstract This paper gives a
More informationWavelet Transform Based Islanding Characterization Method for Distributed Generation
Fourth LACCEI International Latin American and Caribbean Conference for Engineering and Technology (LACCET 6) Wavelet Transform Based Islanding Characterization Method for Distributed Generation O. A.
More informationDetection of Fault in Fixed Series Compensated Transmission Line during Power Swing Using Wavelet Transform
International Journal of Scientific and Research Publications, Volume 4, Issue 5, May 24 Detection of Fault in Fixed Series Compensated Transmission Line during Power Swing Using Wavelet Transform Rohan
More informationExtensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network
Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example
More informationIntroduction. Principle of differential relay operation
nternational Journal of Enhanced Research in Science Technology & Engineering, SSN: 39-7463 Vol. 3 ssue, February-4, pp: (74-8), mpact Factor:.5, Available online at: www.erpublications.com Simulation
More informationCapacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices
Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices M. Sanaye-Pasand, R. Aghazadeh Applied Electromagnetics Research Excellence Center, Electrical & Computer Engineering
More information1392 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011
1392 IEEE TRANSACTIONS ON POWER DELIVERY, VOL 26, NO 3, JULY 2011 Real-Time Power System Frequency and Phasors Estimation Using Recursive Wavelet Transform Jinfeng Ren, Student Member, IEEE, and Mladen
More informationA NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG
A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when
More informationIJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN
A novel control strategy for Mitigation of Inrush currents in Load Transformers using Series Voltage source Converter Pulijala Pandu Ranga Rao *1, VenuGopal Reddy Bodha *2 #1 PG student, Power Electronics
More informationRelay-assisted commissioning
Relay-assisted commissioning by Casper Labuschagne and Normann Fischer, Schweitzer Engineering Laboratories (SEL) Power transformer differential relays were among the first protection relays to use digital
More informationPerformance Evaluation of Generator- Transformer Unit Overall Differential Protection in Large Power Plant
Performance Evaluation of Generator- Transformer Unit Overall Differential Protection in Large Power Plant Wael Yousef, IEEE Senior Member Mahmoud A. Elsadd Almoataz Y. Abdelaziz, IEEE Senior Member Mohamed
More informationANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION
ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION R.Rahnavard 1, 2 M.Valizadeh 1 A.A.B.Sharifian 2 S.H.Hosseini 1 rerahnavard@gmail.com mj_valizad@yahoo.com hosseini@tabrizu.ac.ir
More informationS1-3: New and re-discovered theories and practices in relay protection
(Cheboksary, September 9-13, 27) S1-3: New and re-discovered theories and practices in relay protection Practical experience from multiterminal line differential protection installations Z. GAJIĆ, I. BRNČIĆ,
More informationComprehensive Study on Magnetization Current Harmonics of Power Transformers due to GICs
Comprehensive Study on Magnetization Current Harmonics of Power Transformers due to GICs S. A. Mousavi, C. Carrander, G. Engdahl Abstract-- This paper studies the effect of DC magnetization of power transformers
More informationREGULATING TRANSFORMER (RT) is a generic term
568 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 23, NO. 2, APRIL 2008 Universal Adaptive Differential Protection for Regulating Transformers Tammam Hayder, Ulrich Schaerli, Kurt Feser, Fellow, IEEE, and
More informationReducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System
Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System M.S.B Subrahmanyam 1 T.Swamy Das 2 1 PG Scholar (EEE), RK College of Engineering, Kethanakonda,
More informationOnline Optimal Transmission Line Parameter Estimation for Relaying Applications Yuan Liao, Senior Member, IEEE, and Mladen Kezunovic, Fellow, IEEE
96 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 24, NO. 1, JANUARY 2009 Online Optimal Transmission Line Parameter Estimation for Relaying Applications Yuan Liao, Senior Member, IEEE, and Mladen Kezunovic,
More informationImplementation of Smart DFT-based PMU Model in the Real-Time Digital Simulator
Implementation of Smart DFT-based PMU Model in the Real-Time Digital Simulator Dinesh Rangana Gurusinghe, Dean Ouellette, and Athula D. Rajapakse Abstract-- Many commercial phasor measurement units (PMUs
More informationPerformance Analysis of Traditional and Improved Transformer Differential Protective Relays
Performance Analysis of Traditional and Improved Transformer Differential Protective Relays Armando Guzmán, Stan Zocholl, and Gabriel Benmouyal Schweitzer Engineering Laboratories, Inc. Hector J. Altuve
More informationElectromagnetic transient analysis of saturated iron-core superconducting fault current limiter and DVR
Electromagnetic transient analysis of saturated iron-core superconducting fault current limiter and DVR Y. Naga Vamsi Krishna 1, k.kamala devi 2 1Pg scholar, Department of EEE, Bapatla engineering college,
More informationSmart Busbar Protection Based ANFIS Technique for Substations and Power Plants
Smart Busbar Protection Based ANFIS Technique for Substations and Power Plants 1 Mohamed A. Ali, 2 Sayed A. Ward, 3 Mohamed S. Elkhalafy 123 Faculty of Engineering Shoubra, Benha University Email: 1 mohamed.mohamed02@feng.bu.edu.eg,
More informationImproving Transmission Line Performance using Transient Based Adaptive SPAR
Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON ), Cairo University, Egypt, December 19-21, 2, Paper ID 249. Improving Transmission Line Performance using Transient
More informationDISTANCE relay used for transmission line protection is
IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 25, NO. 1, JANUARY 2010 81 Detection of Symmetrical Faults by Distance Relays During Power Swings Saeed Lotfifard, Student Member, IEEE, Jawad Faiz, Senior Member,
More informationInternational Journal of Scientific & Engineering Research, Volume 4, Issue 7, July ISSN
International Journal of Scientific & Engineering Research, Volume 4, Issue 7, July-2013 377 Self-Healing Framework for Distribution Systems Fazil Haneef, S.Angalaeswari Abstract - The self healing framework
More informationVOLTAGE and current signals containing information
Impact of Instrument Transformers and Anti-Aliasing Filters on Fault Locators R. L. A. Reis, W. L. A. Neves, and D. Fernandes Jr. Abstract Butterworth and Chebyshev anti-aliasing filters assembled in instrument
More informationTransformer protection IED RET 670
Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth
More informationTransformer Differential Protection Lab
Montana Tech Library Digital Commons @ Montana Tech Proceedings of the Annual Montana Tech Electrical and General Engineering Symposium Student Scholarship 2016 Transformer Differential Protection Lab
More informationPower systems Protection course
Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and
More informationDesign Requirements for a Dynamic Voltage Restorer for Voltage Sags Mitigation in Low Voltage Distribution System
Design Requirements for a Dynamic Voltage Restorer for Voltage Sags Mitigation in Low Voltage Distribution System Rosli Omar, 1 N.A Rahim 2 1 aculty of Electrical Engineering, Universiti Teknikal Malaysia
More information