Planners Perspective on Series Compensated Transmission Lines
|
|
- Charity Phelps
- 5 years ago
- Views:
Transcription
1 TOGETHER WE DELIVER Planners Perspective on Series Compensated Transmission Lines Kenneth A. Donohoo, PE Director, System Planning Distribution and Transmission Oncor Electric Delivery Company LLC
2 SERIES CAPACITOR COMPENSATION The use of capacitors connected inline with transmission lines to cancel a portion of the transmission line impedance. The percentage of compensation refers to the percentage of transmission line impedance offset or cancelled. X = X L (1-X C /X L ) = X L (1-k), where k = percent of compensation 1
3 WHY USE SERIES CAPACITOR COMPENSATION? Increase the power flow by reducing the line impedance Increase utilization of existing facilities Relieve transmission bottlenecks Improve the dynamic stability of the grid Increases capacity/capability Reduce voltage variation 2
4 BENEFIT OF SERIES COMPENSATION Scenario 1: Uncompensated Case [2] pg 114 of Bergen Vittal, Power System Analysis. 3
5 BENEFIT OF SERIES COMPENSATION Scenario 2: With Compensation 4
6 LIMITATIONS OF SERIES COMPENSATION The percent compensation limited to less than 70% Voltage profile across line changes Voltage may reach 1.10 pu requiring extra insulation May require additional capability in facilities on each end of line Technically difficult to tie new generators into a seriescompensated line Complicates System Protection requirements Adverse effects on the generator units due to subsynchronous oscillation phenomena 5
7 SUB-SYNCHRONOUS RESONANCE (SSR) Resonance: The tendency of a system under excitation to oscillate at certain frequencies. Good Resonance Bad Resonance Subsynchronous Oscillations*: A phenomena where growing quantities of power are exchanged between equipment at frequencies lower than 60 Hz. Has the potential to break generator shafts, damage generator protection and series capacitor banks. Adding Series Compensation to a power system introduces SSR concerns. * Some texts prefer subsynchronous oscillations as a general term instead of subsynchronous resonance. 6
8 Mohave SSR Incident (1970) An example of SSR Torsional Interaction Mohave generator: 1,580 MW coal-fired in NV Gradually growing vibration that eventually fractured a shaft section First investigations incorrectly determined cause. After 2nd failure in 1971 cause was identified as Subsynchronous Resonance An electrical resonance at 30.5 Hz excited a mechanical resonance at 30.1 Hz Problem was cured by reducing compensation percentage and installing a torsional relay D. Baker, G. Boukarim, Subsynchronous Resonance Studies and Mitigation Methods for Series Capacitor Applications, IEEE D. Walker, D. Hodges, Results of Subsynchronous Resonance Test At Mohave, IEEE
9 SSR MANIFESTATIONS Different situations can cause SSR Torsional Interaction (TI) Electrical resonance frequency of system close to natural torsional resonance frequency of mechanical system. Can result in shaft failure. Usually takes several seconds. Transient Torque Electrical resonance frequency of system close to natural torsional resonance frequency of mechanical system, however adequate damping prevents growing oscillations. Can result in shaft fatigue. Induction Generator Effect (IGE) Purely electrical phenomenon; no mechanical component. Affects wind and fossil generators. Self excitation because synchronous motor circuit acts like an induction generator at subsynchronous frequencies. The effective slip can cause negative resistance, hence negative damping. Can result in rapidly growing currents or voltages. Subsynchronous Control Interaction (SSCI) Control system of power electronic device (e.g. HVDC, wind farms, or SVC) has an unintended resonant point close to the system electrical resonance. Result: Rapidly growing currents or voltages. P.M. Amderspm, B.L. Agrawal, Sybsynchronous Resonance in Power Systems. IEEE Press,
10 SOUTH TEXAS SSCI EVENT (2009) Series capacitors installed on long 345 kv lines to allow full loading. 1,000 MW of wind farms connected to Ajo. Many are Type III. 345 kv series compensated lines 9
11 SOUTH TEXAS SSCI EVENT (2009) A fault occurred on the Ajo to Nelson Sharpe line due to a downed static wire. Fault cleared in 2.5 cycles by opening this line. The wind farms were then radially connected to the Ajo to Rio Hondo series compensated transmission line. The Doubly-Fed Induction Generators (DFIG) controlled by a voltage source converter introduces negative damping. Undamped oscillations at 22 Hz. Voltages reacted approximately 2.0 pu in ~150 ms. The series capacitors bypassed approximately 1.5 seconds. Damage to wind generators and series capacitors occurred. From AEP presentation by Paul Hassink, Sub-synchronous Control Interaction, Utility Wind Integration Group Spring Workshop April 15, 2011 Also: 10
12 FAULT RECORDER, SOUTH TEXAS EVENT Slide from AEP presentation by Paul Hassink, Sub-synchronous Control Interaction, Utility Wind Integration Group Spring Workshop April 15,
13 EFFECT OF OUTAGES Can increase coupling between a series capacitor and generator. Two outages make the generator at Ogallala radial to the CTT series capacitors. Alibates Gray Windmill Ogallala 50% Compensation Oklaunion WillowCrk Long Draw 12
14 EFFECT OF OUTAGES Five double-circuit outages make Limestone radial to W.Shackelford Navarro series compensated line. Venus / Midlothian Watermill Navarro Wshackelford - Navarro Big Brown Limestone Twin Oak 13
15 EFFECT OF OUTAGES Can increase coupling between a series capacitor and generator Must consider planned and forced outages SSR studies are labor-intensive and do not lend towards being studied on-demand Therefore possible outage combinations must be studied ahead-of-time by Planning Any generator that is up to FIVE outages away from being radial to a series capacitor may be subject to SSR study 14
16 HOW STUDY FOR SSR? Frequency scans Impedance (ohms) EMT 1 Simulation Frequency (Hz) Resistance Reactance Graph resistance & reactance vs. frequency. Look for dips & crossovers. Less accurate so designed to be conservative. If frequency scan shows possible exposure risk, EMT simulation may be able to dismiss the exposure risk. EMT simulations are more accurate. 1 Electromagnetic Transient simulation: A time-domain analysis similar to a dynamic or stability analysis but capable of simulating off-nominal frequencies other than 60 Hz. Such simulations generally require more detailed models. 15
17 WHO S AT RISK? More Risk: Electrically close to series capacitors Type III wind farms Long shaft / multi-mass generators (Coal, NG Steam, Combined Cycle) Less Risk: Type IV wind farms Type III wind farms with special damping controls Hydro, CTs, reciprocating engines Solar inverters HVDC ties 16
18 Protection vs. Mitigation? Protection Involves forced tripping (removal of generator or series capacitor). Disruptive for a system that is already in a weakened state due to outages ( double blow ). Generally recommended as backup means of defense. Mitigation Involves reducing exposure to SSR risk. Generally allows the resource to continue operating, even when outages place the unit in stronger electrical coupling with a series capacitor. In many cases, may completely eliminate risk. E.g. Horse Hollow Energy Center installed mitigation which allowed the wind turbines to operate radially to the series-compensated transmission line owned by NextEra. Protection or Mitigation? Recommend Both! 17
19 PROTECTION & MITIGATION Location Responsibility Option Notes Torsional Relays IEEE Recommended, most widely used technique for addressing risk, reliable protection method PROTECTION Generation SSR Blocking Filter Supplemental exciter damping controls, (SEDC) Lack of adaptability/flexibility with changing system, may require multiple rebuilds as system changes Generation excitation controls to mitigate SS Transmission Automatic Bypass SC Operation Fiber/communications in place, sufficient coordination to operate before generation Torsional Relays Single Circuit Segmentation Needs study; No change to current SC configuration, only how it is operated MITIGATION Transmission SS Filters Segmentation Both Circuits Single vendor, partial mitigation, lack of adaptability/flexibility with changing system, may require multiple rebuilds as system changes First phase toward ultimate future TCSC should system needs change; TCSC would integrate segmented platform, not replace Thyristor Controlled Series Compensation (TCSC) Maximum adaptability to system changes, similar to SVC technology CONTINGENCY PLANNING Clearances/ Outages ERCOT & TSP s Develop procedures to short/bypass SC 18
20 Mitigating SSR Type Entity Cost Notes Outage coordination Outage Coordination Special Protection Schemes* Generator PSS tuning Special Protection Schemes Wind turbine controller adjustments Damping Filters Wind Control System Upgrades ERCOT (&TSP) Suggest 4-square chart: $ Involves avoiding certain outages or bypassing series gen capacitor vs TSP; when low they occur. Very effective, cost vs high cost. but only practical for mitigating rare conditions (e.g. N-4 or higher). Bypassing manually performed by operator via SCADA. TSP $ SPSs are effective but discouraged because they Thyristor-controlled series capacitors Fossil Generator PSS Tuning SSR Filters TSP / Generator Thyristor-Controlled Series Caps (TCSC) are difficult to model in studies and may operate unexpectedly with unintended consequences. Any proposals will undergo heavy scrutiny. Generator $ Upgraded control provides wide-band damping that does not need tuning Generator $ May only be effective in certain situations; would need restudy when grid changes $$$ Tuning may need adjustment as grid changes. Tuning can be expensive TSP $$$ Theoretically very effective Also: Wind developers may select a different turbine model; new fossil plants may modify generator masses or install amortisseur windings; SVCs outfitted with special control schemes. 19
21 Protecting Against SSR Type Entity Notes Torsional Relays that trip Fossil Generator Overvoltage / Overcurrent Relays that trip Generator SSR Current Relays that bypass series capacitor SSR Current Relays that trip generator Generator Generator TSP Generator Fossil generators only. Selective and effective protection. Period of adjustment where occasional nuisance tripping possible. Fast protection relays may protect against certain SSCI and IGE resonance. Low selectivity. Applicable to wind. Generally not fast enough to prevent damage to generators. Useful as backup protection. Selectivity? New technology. Not clear if fast enough to completely avoid damage. Applicable to both wind and fossil. 20
22 Role of ERCOT in SSR (Existing Generation Resources) ERCOT analyzed risk exposure of all existing power plants. For exposed plants, Contacted TSP and generator. Coordinated study. Facilitate resolution. Several thermal and wind plants are already moving towards resolution. 21
23 Role of ERCOT in SSR (New Generation Resources) New resources analyzed for risk in GINR screening study Screening study report indicates whether exposed for SSR. If exposed, then developer must either: Run a detailed study. Typically not performed by TSP. Contract out. Obtain letter from generator manufacturer. Explains why not at risk for SSR and substantiated with technical reasoning or a study simulation. New resources not allowed to synchronize until SSR issues resolved. 22
24 Questions/Discussion 23
Artificial Island Open Window Concerns re: Dominion Proposal 1A
Artificial Island Open Window Concerns re: Dominion Proposal 1A Esam A. Khadr Michael Kayes Robert Pollock Donald Shoup Managing Director PSE&G Electric Delivery Planning Director PSE&G Delivery Projects
More informationApplication for A Sub-harmonic Protection Relay. ERLPhase Power Technologies
Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic
More informationWind and Solar (PV) Sub harmonic Interactions with Power Systems
I PCGRID Workshop - 2017 Wind and Solar (PV) Sub harmonic Interactions with Power Systems Dr. Krish Narendra Chief Technology Officer ERLPhase Protection, Automation, Control & Smart Grid ERLPhase Power
More informationELEMENTS OF FACTS CONTROLLERS
1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are
More informationA New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated
More informationMitigation & Protection of Sub-Synchronous Controller Interactions (SSCI) in DFIG Wind Turbine Systems
Mitigation & Protection of Sub-Synchronous Controller Interactions (SSCI) in DFIG Wind Turbine Systems Krish Narendra, P.hD. CTO ERL Protection, Automation, Control & Smart Grid ERLPhase Power Technologies
More informationCOMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)
7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series
More information4 Series Capacitor Compensation Requirements
4 Series Capacitor Compensation Requirements 4.1 Purposes and Benefits of Series Capacitor Compensation As noted previously, transmission lines inherently have an inductive reactance that is in series
More informationProtection for Sub SSTI Conditions Using an Industrial Sub-harmonic Relay
Relay Conference 2018 Protection for Sub SSTI Conditions Using an Industrial Sub-harmonic Relay R. Midence ERLPhase Power Technologies Winnipeg, MB Canada 1 Outline Sub Synchronous Torsional Interactions
More informationISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS
ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS INDO-US Workshop October 2009, I.I.T. Kanpur INTRODUCTION Electric Power Systems are very large, spread over a wide geographical area
More informationA Comprehensive Approach for Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique
A Comprehensive Approach Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique Mahmoud Elfayoumy 1, Member, IEEE, and Carlos Grande Moran 2, Senior Member, IEEE Abstract: The
More informationABB Inc. April 1, 2016 Slide 1
Galina S. Antonova, ABB Inc., i-pcgrid Workshop - 2016 Combining subsynchronous oscillations detection and synchrophasor measurements to increase power system stability April 1, 2016 Slide 1 Sub synchronous
More informationIntegration of Wind Generation into Weak Grids
Integration of Wind Generation into Weak Grids Jason MacDowell GE Energy Consulting NERC ERSTF Atlanta, GA December 10-11, 2014 Outline Conventional and Power Electronic (PE) Sources Stability limitations
More informationDynamic Phasors for Small Signal Stability Analysis
for Small Signal Stability Analysis Chandana Karawita (Transgrid Solutions) for Small Signal Stability Analysis Outline Introduction 1 Introduction Simulation and Analysis Techniques Typical Outputs Modelling
More informationTransient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme
I J E E E C International Journal of Electrical, Electronics ISSN No. (Online) : 2277-2626 and Computer Engineering 2(1): 7-12(2013) Transient stability improvement by using shunt FACT device (STATCOM)
More informationUNDERSTANDING SUB-HARMONICS
UNDERSTANDING SUB-HARMONICS Joe Perez, P.E., SynchroGrid, College Station, TX 77845, jperez@synchrogrid.com Introduction: Over the years, engineers have employed fundamental principles of electrical engineering
More informationGSR018: Sub-Synchronous Oscillations (SSO) Workgroup Report
Stage 01: Workgroup National Electricity Transmission System Security and Quality of Supply Standards (NETS SQSS) GSR018: Sub-Synchronous Oscillations (SSO) Workgroup 01 02 03 Workgroup Industry Consultation
More informationPower Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)
Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,
More informationLARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS
LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS Giuseppe Di Marzio NTNU giuseppe.di.marzio@elkraft.ntnu.no Olav B. Fosso NTNU olav.fosso@elkraft.ntnu.no Kjetil Uhlen SINTEF
More informationStudy of Subsynchronous Resonance in Power Systems
Study of Subsynchronous Resonance in Power Systems 1 Oza Jaidev Suresh, 2 Prof. Shabbir Ghadiali 1 P.G Student, 2 Associate Professor Electrical Engineering Department, S.C.E.T, Surat, India 1 oza.jaidev@gmail.com,
More informationGrid Impact of Neutral Blocking for GIC Protection:
Report submitted to EMPRIMUS - Critical Infrastructure Protection Grid Impact of Neutral Blocking for GIC Protection: Impact of neutral grounding capacitors on network resonance Prepared By: Athula Rajapakse
More informationGSR018/GC0077: Sub-Synchronous Oscillations (SSO)
Stage 03: National Electricity Transmission System Security and Quality of Supply Standards (NETS SQSS) and Grid Code : Sub-Synchronous Oscillations (SSO) 01 Workgroup Report 02 Industry Consultation 03
More informationHarmonizing the Changing Resource Mix Keeping the Grid Together
Harmonizing the Changing Resource Mix Keeping the Grid Together Robert W. Cummings Senior Director of Engineering and Reliability Initiatives i-pcgrid March 30, 2017 NERC-IEEE Memorandum of Understanding
More informationA Direct Power Controlled and Series Compensated EHV Transmission Line
A Direct Power Controlled and Series Compensated EHV Transmission Line Andrew Dodson, IEEE Student Member, University of Arkansas, amdodson@uark.edu Roy McCann, IEEE Member, University of Arkansas, rmccann@uark.edu
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control
ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections
More informationCommissioning Process and Acceptance Test of a Sub-harmonic Protection Relay
Commissioning Process and Acceptance Test of a Sub-harmonic Protection Relay K. Narendra, R. Midence, A. Oliveira, N. Perera, N. Zhang - ERLPhase Power Technologies Ltd Abstract Numerous technical papers
More informationDamping of Sub synchronous Resonance Using SSSC Based PWM Hysteresis Controller
Damping of Sub synchronous Resonance Using SSSC Based PWM Hysteresis Controller E.Kumaresan*, S.Parthasarathy, B.Vidya Department of Electrical& Electronics Engineering Valliammai Engineering College,
More informationInternational Journal of Advance Engineering and Research Development
Scientific Journal of Impact Factor (SJIF): 4.72 International Journal of Advance Engineering and Research Development Volume 4, Issue 4, April -2017 e-issn (O): 2348-4470 p-issn (P): 2348-6406 Damping
More informationEH2741 Communication and Control in Electric Power Systems Lecture 2
KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment
More informationIDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)
IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone
More informationPOWER SYSTEM OSCILLATIONS
Chapter 2 POWER SYSTEM OSCILLATIONS 2.1 Introduction Oscillations in power systems are classified by the system components that they effect. Some of the major system collapses attributed to oscillations
More informationSimulations of open phase conditions on the high voltage side of YNd05-power plant transformers
Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Disclaimer: All information presented in the report, the results and the related computer program, data,
More informationESB National Grid Transmission Planning Criteria
ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and
More informationSub-synchronous Electrical Torque Frequencies Monitoring before the SSR Presence.
Sub-synchronous Electrical Torque Frequencies Monitoring before the SSR Presence. *José A Castillo J *David Sebastián B **Carlos A Rivera S *Daniel Olguín S * Programa de Postgrado en Ingeniería Eléctrica,
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationSubsynchronous oscillations aspects and experiences from Finland
Energiforsk seminar: Subsynchronous oscillations / 2016-11-24, Stockholm Subsynchronous oscillations aspects and experiences from Finland Tuomas 1 Rauhala Content of the presentation Subsynchronous oscillations
More informationENHANCEMENT OF POWER FLOW USING SSSC CONTROLLER
ENHANCEMENT OF POWER FLOW USING SSSC CONTROLLER 1 PRATIK RAO, 2 OMKAR PAWAR, 3 C. L. BHATTAR, 4 RUSHIKESH KHAMBE, 5 PRITHVIRAJ PATIL, 6 KEDAR KULKARNI 1,2,4,5,6 B. Tech Electrical, 3 M. Tech Electrical
More informationHow Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements
How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements Robert Nelson Senior Expert Engineering Manager and Manager of Codes, Standards, and Regulations Siemens Wind Turbines -
More informationITC Holdings Planning Criteria Below 100 kv. Category: Planning. Eff. Date/Rev. # 12/09/
ITC Holdings Planning Criteria Below 100 kv * Category: Planning Type: Policy Eff. Date/Rev. # 12/09/2015 000 Contents 1. Goal... 2 2. Steady State Voltage & Thermal Loading Criteria... 2 2.1. System Loading...
More informationNew HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations
New HVDC Interaction between AC networks 233 JPE 7-3-6 New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations Chan-Ki Kim, Young-Hun Kwon * and Gil-Soo Jang ** KEPRI,
More informationAnalysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar
Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:
More informationComparison of the Behaviour of Wind Farms and Conventional Power Stations during Grid Failure Conditions
May 4 Comparison of the Behaviour of Wind Farms and Conventional Power Dr. Martin Janßen APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT Overview Introduction Grid Faults Requirements for Grid Stability Fault
More informationNERC Protection Coordination Webinar Series June 30, Dr. Murty V.V.S. Yalla
Power Plant and Transmission System Protection ti Coordination Loss-of-Field (40) and Out-of of-step Protection (78) NERC Protection Coordination Webinar Series June 30, 2010 Dr. Murty V.V.S. Yalla Disclaimer
More informationDo Capacitor Switching Transients Still Cause Problems?
Do Capacitor Switching Transients Still Cause Problems? Mark McGranaghan We have been evaluating problems related to capacitor switching transients for many years. Capacitor banks have been used on distribution
More informationNERC Protection Coordination Webinar Series July 15, Jon Gardell
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationHarnessing of wind power in the present era system
International Journal of Scientific & Engineering Research Volume 3, Issue 1, January-2012 1 Harnessing of wind power in the present era system Raghunadha Sastry R, Deepthy N Abstract This paper deals
More informationArvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India
e t International Journal on Emerging Technologies 4(1): 10-16(2013) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Control of Synchronous Generator Excitation and Rotor Angle Stability by
More informationOverview of Actuation Thrust
Overview of Actuation Thrust Fred Wang Thrust Leader, UTK Professor ECE 620 CURENT Course September 13, 2017 Actuation in CURENT Wide Area Control of Power Power Grid Grid Measurement &Monitoring HVDC
More informationPower Quality Analysis in Power System with Non Linear Load
International Journal of Electrical Engineering. ISSN 0974-2158 Volume 10, Number 1 (2017), pp. 33-45 International Research Publication House http://www.irphouse.com Power Quality Analysis in Power System
More informationWind Power Facility Technical Requirements CHANGE HISTORY
CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical
More informationGrid Code Review Panel. Information Required to Evaluate Subsynchrononous Resonance on the Transmission System
Grid Code Review Panel Information Required to Evaluate Subsynchrononous Resonance on the Transmission System Summary of Issue A paper by National Grid Contact: Graham Stein 1. All electrical and electromechanical
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationDynamic Series Compensation for the Reinforcement of Network Connections with High Wind Penetration
Dynamic Series Compensation for the Reinforcement of Network Connections with High Wind Penetration Juan Carlos Nambo-Martinez Kamila Nieradzinska Olimpo Anaya-Lara EERA Deepwind 2014 23 January 2014,
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationMANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS. April 2009 Version 2
MANITOBA HYDRO TRANSMISSION SYSTEM INTERCONNECTION REQUIREMENTS April 2009 Version 2 LEGISLATIVE AUTHORITY Section 15(5) of The Manitoba Hydro Act authorizes Manitoba Hydro to set, coordinate and enforce
More informationAORC Technical meeting 2014
http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi
More informationEnhancement of Voltage Stability & reactive Power Control of Distribution System Using Facts Devices
Enhancement of Voltage Stability & reactive Power Control of Distribution System Using Facts Devices Aarti Rai Electrical & Electronics Engineering, Chhattisgarh Swami Vivekananda Technical University,
More informationUse of a Sub Harmonic Protection Relay to Detect SSO Conditions Associated with Type-III Windfarms and Series Compensated Transmission Systems
21, rue d Artois, F-75008 PARIS 095 DUBLIN 2017 http : //www.cigre.org Use of a Sub Harmonic Protection Relay to Detect SSO Conditions Associated with Type-III Windfarms and Series Compensated Transmission
More informationSetting and Verification of Generation Protection to Meet NERC Reliability Standards
1 Setting and Verification of Generation Protection to Meet NERC Reliability Standards Xiangmin Gao, Tom Ernst Douglas Rust, GE Energy Connections Dandsco LLC. Abstract NERC has recently published several
More informationVolume I Issue VI 2012 September-2012 ISSN
A 24-pulse STATCOM Simulation model to improve voltage sag due to starting of 1 HP Induction-Motor Mr. Ajay Kumar Bansal 1 Mr. Govind Lal Suthar 2 Mr. Rohan Sharma 3 1 Associate Professor, Department of
More informationATC s Mackinac Back to Back. Summary
ATC s Mackinac Back to Back HVDC Project Update Michael B. Marz American Transmission Company Summary The Need For Flow Control at Mackinac Mackinac Flow Control Requirements Available Flow Control Technologies
More informationGenerator Protection GENERATOR CONTROL AND PROTECTION
Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Volts Per Hertz (24), Undervoltage (27), Overvoltage (59), and Under/Overfrequency (81) Protection System Protection and Control Subcommittee
More informationTanu Sharma al. International Journal of Recent Research Aspects ISSN: , Vol. 1, Issue 3, Dec 2014, pp
Analysis and Mitigation of Sub-Synchronous Resonance using IEEE first benchmark model Tanu Sharma 1, Kamal Kumar Sharma 2, Himanshsu Gupta 3 1 Student, M. Tech, EMGOI, Ambala 2 Professor, Dept. of ECE,
More informationA NEW MONITORING SPECTRAL TECHNIQUE FOR SUB- SYNCHRONOUS ELECTRICAL TORQUE FREQUENCIES
A NEW MONITORING SPECTRAL TECHNIQUE FOR SUB- SYNCHRONOUS ELECTRICAL TORQUE FREQUENCIES *José A Castillo J *Daniel Olguín S **Carlos A Rivera S *David Sebastián B * Programa de Postgrado en Ingeniería Eléctrica,
More informationConnection Impact Assessment Application
Connection Impact Assessment Application This form is for generators applying for Connection Impact Assessment (CIA) and for generators with a project size >10 kw. Please return the completed form by email,
More informationFeasible Series Compensation Applications using Magnetic Energy Recovery Switch (MERS)
Feasible Series Compensation Applications using Magnetic Energy Recovery Switch (MERS) Jan A. Wiik, Takanori Isobe, *Taku Takaku, F. Danang Wijaya, Kazuhiro Usuki, Nobuyuki Arai and Ryuichi Shimada Tokyo
More informationProtection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin
Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad
More informationSynchrophasor Technology PMU Use Case Examples
1 IEEE Tutorial on Use of Synchrophasors in Grid Operations - Oscillation Source Detection and Operational Use of Synchrophasors Synchrophasor Technology PMU Use Case Examples Sarma (NDR) Nuthalapati,
More informationUProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy
UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected
More informationFacilitating Bulk Wind Power Integration Using LCC HVDC
21, rue d Artois, F-758 PARIS CIGRE US National Committee http : //www.cigre.org 213 Grid of the Future Symposium Facilitating Bulk Wind Power Integration Using LCC HVDC A. HERNANDEZ * R.MAJUMDER W. GALLI
More informationI. INTRODUCTION IJSRST Volume 3 Issue 2 Print ISSN: Online ISSN: X
2017 IJSRST Volume 3 Issue 2 Print ISSN: 2395-6011 Online ISSN: 2395-602X National Conference on Advances in Engineering and Applied Science (NCAEAS) 16 th February 2017 In association with International
More informationTECHNICAL BULLETIN 004a Ferroresonance
May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques
More informationSSE Offices, Glasgow and Teleconference
DRAFT Minutes Name NETS SQSS Sub-Synchronous Oscillations (SSO) Workgroup Number 3 Date of 28 November 2014 Time 10:00 14:00 Location SSE Offices, Glasgow and Teleconference Attendees Name Role Initials
More informationNERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June
More informationTransmission System Phase Backup Protection
Reliability Guideline Transmission System Phase Backup Protection NERC System Protection and Control Subcommittee Draft for Planning Committee Approval June 2011 Table of Contents 1. Introduction and Need
More informationDesign and Simulation of Passive Filter
Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt
More informationVSC Based HVDC Active Power Controller to Damp out Resonance Oscillation in Turbine Generator System
VSC Based HVDC Active Power Controller to Damp out Resonance Oscillation in Turbine Generator System Rajkumar Pal 1, Rajesh Kumar 2, Abhay Katyayan 3 1, 2, 3 Assistant Professor, Department of Electrical
More informationJoe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation
Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation Slide 1 Excerpt from the BoA BoA: Book of Acronyms MSC/MSR: Mechanically
More informationC1-207 TRANSMISSION CAPACITY INCREASE BY RETURNING POWER SYSTEM STABILIZERS
21, rue d'artois, F-75008 Paris http://www.cigre.org C1-207 Session 2004 CIGRÉ TRANSMISSION CAPACITY INCREASE BY RETURNING POWER SYSTEM STABILIZERS STEFAN ELENIUS* JUSSI JYRINSALO SIMO JOKI-KORPELA HELSINKI
More informationEE 742 Power System Components. Y. Baghzouz ECE Department UNLV
EE 742 Power System Components Y. Baghzouz ECE Department UNLV Desire to have a system with high reliability and power quality High reliability ensured by High quality of components High level of system
More informationMicrogrid Protection
Panel: Microgrid Research and Field Testing IEEE PES General Meeting, 4-8 June 7, Tampa, FL Microgrid Protection H. Nikkhajoei, Member, IEEE, R. H. Lasseter, Fellow, Abstract In general, a microgrid can
More informationNORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:
NORTH CAROLINA INTERCONNECTION REQUEST Utility: Designated Contact Person: Address: Telephone Number: Fax: E-Mail Address: An is considered complete when it provides all applicable and correct information
More informationSarma (NDR) Nuthalapati, PhD
SYNCHROPHASOR TECHNOLOGY PMU USE CASE EXAMPLES Sarma (NDR) Nuthalapati, PhD Research Scientist Texas A&M University, College Station, TX Control Room Solutions Task Team NASPI Work Group meeting and first
More informationSRI VIDYA COLLEGE OF ENGG AND TECH
EEE6603 PSOC Page 1 UNIT-III REACTIVE POWER VOLTAGE CONTROL 1. List the various components of AVR loop? The components of automatic voltage regulator loop are exciter, comparator, amplifier, rectifier
More informationPower System Stability. Course Notes PART-1
PHILADELPHIA UNIVERSITY ELECTRICAL ENGINEERING DEPARTMENT Power System Stability Course Notes PART-1 Dr. A.Professor Mohammed Tawfeeq Al-Zuhairi September 2012 1 Power System Stability Introduction Dr.Mohammed
More informationDamping of Sub-synchronous Resonance and Power Swing using TCSC and Series capacitor
Damping of Sub-synchronous Resonance and Power Swing using TCSC and Series capacitor Durga Prasad Ananthu Assistant Professor, EEE dept. Guru Nanak Dev Engg College, Bidar adp.ananthu@gmail.com Rami Reddy
More informationA Real-Time Platform for Teaching Power System Control Design
A Real-Time Platform for Teaching Power System Control Design G. Jackson, U.D. Annakkage, A. M. Gole, D. Lowe, and M.P. McShane Abstract This paper describes the development of a real-time digital simulation
More informationTask Force on Synchrophasor Protection Applications NASPI Engineering Analysis Task Team Matthew Rhodes 3/22/16
NASPI White Paper: Integrating Synchrophasor Technology into Power System Protection Applications Update Report Task Force on Synchrophasor Protection Applications NASPI Engineering Analysis Task Team
More informationConnection Impact Assessment Application Form
Connection Impact Assessment Application Form This Application Form is for Generators applying for a Connection Impact Assessment (CIA). In certain circumstances, London Hydro may require additional information
More informationForm B. Connection Impact Assessment Application Form Distribution System
Form B Connection Impact Assessment Application Form Distribution System This Application Form is for Generators applying for Connection Impact Assessment ( CIA ). It is important that the Generator provides
More informationAnalysis of Harmonic Distortion in Non-linear Loads
Analysis of Harmonic Distortion in Non-linear Loads Anne Ko Department of Electrical Power Engineering Mandalay Technological University, Mandalay, Myanmar.Phone:+95-09-2225761 anneko101082@gmail.com Wunna
More informationFundamental Concepts of Dynamic Reactive Compensation. Outline
1 Fundamental Concepts of Dynamic Reactive Compensation and HVDC Transmission Brian K. Johnson University of Idaho b.k.johnson@ieee.org 2 Outline Objectives for this panel session Introduce Basic Concepts
More informationChapter 10: Compensation of Power Transmission Systems
Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome
More information1
Guidelines and Technical Basis Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More informationPower Flow Control/Limiting Short Circuit Current Using TCSC
Power Flow Control/Limiting Short Circuit Current Using TCSC Gannavarapu Akhilesh 1 * D.Raju 2 1. ACTS, JNTU-H, PO box 500035, Hyderabad, Andhra Pradesh, India 2. M.Tech (NIT Nagpur), Hyderabad, Andhra
More informationHighgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES
Highgate Converter Overview Prepared by Joshua Burroughs & Jeff Carrara IEEE PES Highgate Converter Abstract Introduction to HVDC Background on Highgate Operation and Control schemes of Highgate 22 Why
More information