Comparison of the Behaviour of Wind Farms and Conventional Power Stations during Grid Failure Conditions

Size: px
Start display at page:

Download "Comparison of the Behaviour of Wind Farms and Conventional Power Stations during Grid Failure Conditions"

Transcription

1 May 4 Comparison of the Behaviour of Wind Farms and Conventional Power Dr. Martin Janßen APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT

2 Overview Introduction Grid Faults Requirements for Grid Stability Fault Clearance Measurement Characteristics of Generating Units Synchronous Generator Fully Fed Synchronous Generator Doubly Fed Induction Generator Simulation Simulation Model Simulation Results Conclusion 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be

3 Introduction The effect of wind power cannot be neglected anymore Grid operators expect wind farms to behave like conventional synchronous generators: Fault Ride Trough Voltage Control Frequency Control New Grid Connection Conditions How do wind farms behave during grid faults? Does this behaviour cause any problems? 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 3

4 Grid Faults Requirements for Grid Stability High short circuit current for triggering of circuit breakers Delivery of reactive current during the fault Fast recovery of active power after fault clearance 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 4

5 Grid Faults Fault Clearance A fault on a transmission line is connected to the grid by the two ends of the line The circuit breakers nearest to the fault open within 1 ms The circuit breakers at the other end open 4 ms after the first The individual phases of the circuit breakers open sequentially, typically 5 ms apart 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 5

6 Grid Faults Measurement Tree phase fault on a 75 kv transmission line Phase Voltage [kv] Fault Duration 33.5 kv (15.8 % of V nom ) 5 Phase A Phases B and C see similar voltage depressions to Phase A Phase B Phase C 8 ms 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 6

7 Characteristics of Generating Units Synchronous Generator High short circuit current Reactive current provided during grid faults Fast recovery of active power, but high oscillations Danger of tripping if fault lasts too long 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 7

8 Characteristics of Generating Units Fully Fed Synchronous Generator Variable speed generator Generator decoupled from grid, behaviour determined by the converter Low transients Limited short circuit current Reactive current provided by converter Fast recovery of active power possible Turbine High voltage High voltage Transformer ~ ~ SG 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 8

9 Characteristics of Generating Units Doubly Fed Induction Generator Most common variable speed wind turbine design High voltage dynamic leads to over current of the generator High short circuit current but low a.c. component Reactive power provided by generator and converter Fast recovery of active power possible Transformer DFIG High voltage High voltage ~ ~ 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 9

10 Simulation model Transformer HV - MV Transformer MV - LV ~ = Pro Wind = ~ Z G 11 % u k 6 % u k Generator u Grid ~ Z F u PCC u Gen M Turbine n Crowbar 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 1

11 Simulation 3-Phase Fault with U PCC = 15 % U N Synchronous Generator U Gen / U N U / U N U PCC / U N i a, i r I Grid / I N t [s] 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 11

12 Simulation 3-Phase Fault with U PCC = 15 % U N Synchronous Generator U Gen / U N U / U N U PCC / U N t [s] 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 1

13 Simulation 3-Phase Fault with U PCC = 15 % U N Fully Fed Synchronous Generator U Gen / U N U PCC / U N U / U N i a, i r I Grid / I N t [s] 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 13

14 Simulation 3-Phase Fault with U PCC = 15 % U N Doubly Fed Induction Generator U Gen / U N U PCC / U N U / U N i a, i r I Grid / I N t [s] 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 14

15 Simulation 3-Phase Fault with U PCC = 15 % U N DFIG + Fully Fed SG U Gen / U N U PCC / U N U / U N i a, i r I Grid / I N t [s] 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 15

16 Conclusion Wind farms can have a similar characteristic as conventional synchronous generators All types of generators have different advantages / drawbacks regarding short circuit current / reactive power / active power With an appropriate design and control wind farms can help to stabilize the grid 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 16

17

Netzkurzschlussverhalten von umrichterbetriebenen regenerativen Energieerzeugern und -speichern

Netzkurzschlussverhalten von umrichterbetriebenen regenerativen Energieerzeugern und -speichern October 25 Netzkurzschlussverhalten von umrichterbetriebenen regenerativen Energieerzeugern und -speichern Dr. Georg Möhlenkamp 5MOP8_EN-(Netzkurzschlussverhalten-Energieerzeuger).PPT / Dr.MÖHLENKAMP Overview

More information

Influence of Wind Generators in Voltage Dips

Influence of Wind Generators in Voltage Dips Influence of Wind Generators in Voltage Dips E. Belenguer, N. Aparicio, J.L. Gandía, S. Añó 2 Department of Industrial Engineering and Design Universitat Jaume I Campus de Riu Sec, E-27 Castelló (Spain)

More information

WIND FARM Flexible AC Transmission Systems

WIND FARM Flexible AC Transmission Systems WIND FARM Flexible AC Transmission Systems WIND ENERGY AND GRID INTEGRATION Madrid 24-25 January 2006 Jacques COURAULT Assumption: Wind farm is with Fixed Speed Induction Generator (FSIG) SUMMARY 1/ Wind

More information

IMPROVED SYNCHRONISM IN DFIG WIND ENERGY CONVERSION SYSTEM USING SMES ENERGY STORAGE

IMPROVED SYNCHRONISM IN DFIG WIND ENERGY CONVERSION SYSTEM USING SMES ENERGY STORAGE IMPROVED SYNCHRONISM IN DFIG WIND ENERGY CONVERSION SYSTEM USING SMES ENERGY STORAGE 1 PALLAVI DATE, 2 SUJAY KULKARNI, 3 SAKSHI PORJE, 4 JOYDEEP SARKAR 1 Electrical Power System, MCOERC, Nashik 2,3.4 Electrical

More information

System for Better Synchronism in DFIG Wind Energy Conversion System Using SMES Energy Storage

System for Better Synchronism in DFIG Wind Energy Conversion System Using SMES Energy Storage IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 1 Ver. IV (Jan Feb. 2015), PP 23-29 www.iosrjournals.org System for Better Synchronism

More information

Analysis of the Effectiveness of Grid Codes for Offshore Wind Farms Connected to Onshore Grid via VSC-Based HVDC

Analysis of the Effectiveness of Grid Codes for Offshore Wind Farms Connected to Onshore Grid via VSC-Based HVDC Conference of the Wind Power Engineering Community Analysis of the Effectiveness of Grid Codes for Offshore Wind Farms Connected to Onshore Grid via VSC-Based HVDC Moritz Mittelstaedt, Andreas Roehder,.Hendrik

More information

Development of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine

Development of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine Development of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine T. Neumann, C. Feltes, I. Erlich University Duisburg-Essen Institute of Electrical Power Systems Bismarckstr. 81,

More information

Harnessing of wind power in the present era system

Harnessing of wind power in the present era system International Journal of Scientific & Engineering Research Volume 3, Issue 1, January-2012 1 Harnessing of wind power in the present era system Raghunadha Sastry R, Deepthy N Abstract This paper deals

More information

Neutral Grounding in Wind Farm Medium Voltage Collector Grids

Neutral Grounding in Wind Farm Medium Voltage Collector Grids Neutral Grounding in Wind Farm Medium Voltage Collector Grids C. Feltes, Student Member, IEEE, R. van de Sandt, Member, IEEE, F. Koch, F. Shewarega, Member, IEEE, I. Erlich, Senior Member, IEEE Abstract

More information

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 5th October 2010 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT

More information

DESIGN OF A MODE DECOUPLING FOR VOLTAGE CONTROL OF WIND-DRIVEN IG SYSTEM

DESIGN OF A MODE DECOUPLING FOR VOLTAGE CONTROL OF WIND-DRIVEN IG SYSTEM IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 8, Issue 5 (Nov. - Dec. 2013), PP 41-45 DESIGN OF A MODE DECOUPLING FOR VOLTAGE CONTROL OF

More information

Wind and Solar (PV) Sub harmonic Interactions with Power Systems

Wind and Solar (PV) Sub harmonic Interactions with Power Systems I PCGRID Workshop - 2017 Wind and Solar (PV) Sub harmonic Interactions with Power Systems Dr. Krish Narendra Chief Technology Officer ERLPhase Protection, Automation, Control & Smart Grid ERLPhase Power

More information

WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS

WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS WFPS1.1 INTRODUCTION 2 WFPS1.2 OBJECTIVE 2 WFPS1.3 SCOPE 3 WFPS1.4 FAULT RIDE THROUGH REQUIREMENTS 4 WFPS1.5 FREQUENCY REQUIREMENTS 5 WFPS1.6 VOLTAGE

More information

Control Strategy of a Dc-Link Brake Chopper for Low-Voltage-Ride-Through in Doubly Fed Induction Generator

Control Strategy of a Dc-Link Brake Chopper for Low-Voltage-Ride-Through in Doubly Fed Induction Generator AENSI Journals Australian Journal of Basic and Applied Sciences ISSN:1991-8178 Journal home page: www.ajbasweb.com Control Strategy of a Dc-Link Brake Chopper for Low-Voltage-Ride-Through in Doubly Fed

More information

Control of Wind Power Plant for Cooperation with Conventional Power Generation Unit and HVDC Classic Link

Control of Wind Power Plant for Cooperation with Conventional Power Generation Unit and HVDC Classic Link Control of Wind Power Plant for Cooperation with Conventional Power Generation Unit and HVDC Classic Link Li-Jun Cai*, Simon Jensen **, Vincenz Dinkhauser***, István Erlich**** REpower Systems SE,. Albert-Betz-Strasse,

More information

QUESTIONNAIRE for Wind Farm Power Stations only

QUESTIONNAIRE for Wind Farm Power Stations only TRANSMISSION SYSTEM OPERATOR QUESTIONNAIRE for Wind Farm Power Stations only To be submitted by the Generation Licensees together with the Application for Connection Certificate according to IEC 61400-21

More information

Mitigation & Protection of Sub-Synchronous Controller Interactions (SSCI) in DFIG Wind Turbine Systems

Mitigation & Protection of Sub-Synchronous Controller Interactions (SSCI) in DFIG Wind Turbine Systems Mitigation & Protection of Sub-Synchronous Controller Interactions (SSCI) in DFIG Wind Turbine Systems Krish Narendra, P.hD. CTO ERL Protection, Automation, Control & Smart Grid ERLPhase Power Technologies

More information

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy

UProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected

More information

LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS

LOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS Scientific Journal Impact Factor (SJIF): 1.711 e-issn: 2349-9745 p-issn: 2393-8161 International Journal of Modern Trends in Engineering and Research www.ijmter.com LOW VOLTAGE RIDE - THROUGH CAPABILITY

More information

Offshore AC Grid Management for an AC Integrated VSC-HVDC Scheme with Large WPPs

Offshore AC Grid Management for an AC Integrated VSC-HVDC Scheme with Large WPPs Offshore AC Grid Management for an AC Integrated VSC-HVDC Scheme with Large WPPs Rakibuzzaman Shah, Member, IEEE, Mike Barnes, Senior Member, IEEE, and Robin Preece, Member, IEEE School of Electrical and

More information

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents Page: 1 Electrical Transient Analyzer Program Short Circuit Analysis ANSI Standard 3-Phase Fault Currents Number of Buses: Swing Generator Load Total 1 0 4 5 Number of Branches: XFMR2 XFMR3 Reactor Line/Cable

More information

Improved Transient Compensation Using PI-SRF Control Scheme Based UHVDC For Offshore Wind Power Plant

Improved Transient Compensation Using PI-SRF Control Scheme Based UHVDC For Offshore Wind Power Plant Improved Transient Compensation Using PI-SRF Control Scheme Based UHVDC For Offshore Wind Power Plant Sangeetha M 1, Arivoli R 2, Karthikeyan B 3 1 Assistant Professor, Department of EEE, Imayam College

More information

Synchrophasor Technology PMU Use Case Examples

Synchrophasor Technology PMU Use Case Examples 1 IEEE Tutorial on Use of Synchrophasors in Grid Operations - Oscillation Source Detection and Operational Use of Synchrophasors Synchrophasor Technology PMU Use Case Examples Sarma (NDR) Nuthalapati,

More information

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements

How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements Robert Nelson Senior Expert Engineering Manager and Manager of Codes, Standards, and Regulations Siemens Wind Turbines -

More information

Control of a Three Phase Inverter Mimicking Synchronous Machine with Fault Ridethrough

Control of a Three Phase Inverter Mimicking Synchronous Machine with Fault Ridethrough 2017 Ninth Annual IEEE Green Technologies Conference Control of a Three Phase Inverter Mimicking Synchronous Machine with Fault Ridethrough Capability Vikram Roy Chowdhury, Subhajyoti Mukherjee, Pourya

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

Facilitating Bulk Wind Power Integration Using LCC HVDC

Facilitating Bulk Wind Power Integration Using LCC HVDC 21, rue d Artois, F-758 PARIS CIGRE US National Committee http : //www.cigre.org 213 Grid of the Future Symposium Facilitating Bulk Wind Power Integration Using LCC HVDC A. HERNANDEZ * R.MAJUMDER W. GALLI

More information

Planners Perspective on Series Compensated Transmission Lines

Planners Perspective on Series Compensated Transmission Lines TOGETHER WE DELIVER Planners Perspective on Series Compensated Transmission Lines Kenneth A. Donohoo, PE Director, System Planning Distribution and Transmission kenneth.donohoo@oncor.com Oncor Electric

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Sarma (NDR) Nuthalapati, PhD

Sarma (NDR) Nuthalapati, PhD SYNCHROPHASOR TECHNOLOGY PMU USE CASE EXAMPLES Sarma (NDR) Nuthalapati, PhD Research Scientist Texas A&M University, College Station, TX Control Room Solutions Task Team NASPI Work Group meeting and first

More information

Aalborg Universitet. Design and Control of A DC Grid for Offshore Wind Farms Deng, Fujin. Publication date: 2012

Aalborg Universitet. Design and Control of A DC Grid for Offshore Wind Farms Deng, Fujin. Publication date: 2012 Aalborg Universitet Design and Control of A DC Grid for Offshore Wind Farms Deng, Fujin Publication date: 2012 Document Version Publisher's PDF, also known as Version of record Link to publication from

More information

Control of Grid Side Inverter in a B2B Configuration for WT Applications. Master Thesis. by George Alin RADUCU

Control of Grid Side Inverter in a B2B Configuration for WT Applications. Master Thesis. by George Alin RADUCU Control of Grid Side Inverter in a B2B Configuration for WT Applications Master Thesis by George Alin RADUCU PED10-1015b Aalborg University, 2008 Preface This present Master Thesis Control of Grid Side

More information

DC BUS VOLTAGE CONTROL OF PWM CONVERTERS IN PMSG IN WIND POWER SYSTEM Krishnamoorthy.M 1 Andal. S 2 M.Varatharaj 3

DC BUS VOLTAGE CONTROL OF PWM CONVERTERS IN PMSG IN WIND POWER SYSTEM Krishnamoorthy.M 1 Andal. S 2 M.Varatharaj 3 ISSN: 2349-2503 DC BUS VOLTAGE CONTROL OF PWM CONVERTERS IN PMSG IN WIND POWER SYSTEM Krishnamoorthy.M 1 Andal. S 2 M.Varatharaj 3 1 (Dept of EEE, Christ the king engineering college, Coimbatore, India,

More information

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Disclaimer: All information presented in the report, the results and the related computer program, data,

More information

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION 23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB

More information

MITIGATION OF VOLTAGE SAG IN A DFIG BASED WIND TURBINE USING DVR

MITIGATION OF VOLTAGE SAG IN A DFIG BASED WIND TURBINE USING DVR MITIGATION OF VOLTAGE SAG IN A DFIG BASED WIND TURBINE USING DVR M Venmathi*, Soumyadeep Chakraborti 1, Soham Ghosh 2, Abhirup Ray 3, Vidhya Nikam 4 * (Senior Lecturer, Dept. of Electrical and Electronics,

More information

Fault Ride Through Technical Assessment Report Template

Fault Ride Through Technical Assessment Report Template Fault Ride Through Technical Assessment Report Template Notes: 1. This template is intended to provide guidelines into the minimum content and scope of the technical studies required to demonstrate compliance

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Improvement of Power Quality in PMSG Based Wind Integrated System Using FACTS Controller

Improvement of Power Quality in PMSG Based Wind Integrated System Using FACTS Controller Improvement of Power Quality in PMSG Based Wind Integrated System Using FACTS Controller Lekshmi M 1, Vishnu J 2 1PG Scholar, 2 Assistant Professor 1,2 Dept. of Electrical and Electronics Engineering Sree

More information

NOWADAYS, there is much interest in connecting various

NOWADAYS, there is much interest in connecting various IEEE TRANSACTIONS ON SMART GRID, VOL. 4, NO. 1, MARCH 2013 419 Modified Dynamic Phasor Estimation Algorithm for the Transient Signals of Distributed Generators Dong-Gyu Lee, Sang-Hee Kang, and Soon-Ryul

More information

Fault current contribution from PPMS & HVDC

Fault current contribution from PPMS & HVDC Fault current contribution from PPMS & HVDC ENTSO-E guidance document for national implementation for network codes on grid connection 16 November 2016 Table of Contents DESCRIPTION...3 Code(s) &...3 Introduction...3

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Improvement of Power Quality Considering Voltage Stability in Grid Connected System by FACTS Devices

Improvement of Power Quality Considering Voltage Stability in Grid Connected System by FACTS Devices Improvement of Power Quality Considering Voltage Stability in Grid Connected System by FACTS Devices Sarika D. Patil Dept. of Electrical Engineering, Rajiv Gandhi College of Engineering & Research, Nagpur,

More information

Fault Ride-through Capability Test Unit for Wind Turbines

Fault Ride-through Capability Test Unit for Wind Turbines WIND ENERGY Wind Energ. 2008; 11:3 12 Published online 7 November 2007 in Wiley Interscience (www.interscience.wiley.com).255 Research Article Fault Ride-through Capability Test Unit for Wind Turbines

More information

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

An Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing In Inverter-Based Islanded Micro grids

An Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing In Inverter-Based Islanded Micro grids IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331 PP 33-40 www.iosrjournals.org An Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing

More information

Enhancement of Reactive Power Capability of DFIG using Grid Side Converter

Enhancement of Reactive Power Capability of DFIG using Grid Side Converter Enhancement of Reactive Power Capability of DFIG using Grid Side Converter V. Sumitha 1 R. Gnanadass 2 Abstract - In the new electricity grid code, reactive power generation by wind farms, which must operate

More information

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage 1 New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage B. B. Pimple, V. Y. Vekhande and B. G. Fernandes Department of Electrical Engineering, Indian Institute of Technology Bombay,

More information

The Open Access Institutional Repository at Robert Gordon University

The Open Access Institutional Repository at Robert Gordon University OpenAIR@RGU The Open Access Institutional Repository at Robert Gordon University http://openair.rgu.ac.uk Citation Details Citation for the version of the work held in OpenAIR@RGU : TAN, S. F., 2010. Development

More information

Voltage Stability Improvement of Four Parallel Operated Offshore Wind Turbine Using Fuzzy Controller

Voltage Stability Improvement of Four Parallel Operated Offshore Wind Turbine Using Fuzzy Controller 2014 IJEDR Volume 2, Issue 1 ISSN: 2321-9939 Voltage Stability Improvement of Four Parallel Operated Offshore Wind Turbine Using Fuzzy Controller 1 R.Balamurugan, 2 R.Punitharaji 1 Student, 2 Assistant

More information

System Requirements for Wind Farms and Distributed Generation. Giuseppe Di Marzio

System Requirements for Wind Farms and Distributed Generation. Giuseppe Di Marzio ystem Requirements for Wind Farms and Distributed Generation Giuseppe Di Marzio giuseppe.di.marzio@elraft.ntnu.no 1 Contents Grid interconnection schemes Power quality requirements Fault Level considerations

More information

SynchroPhasor use at OG&E. Austin D. White P.E. Steven E. Chisholm Oklahoma Gas & Electric

SynchroPhasor use at OG&E. Austin D. White P.E. Steven E. Chisholm Oklahoma Gas & Electric SynchroPhasor use at OG&E Austin D. White P.E. Steven E. Chisholm Oklahoma Gas & Electric Outline Hardware/Software Overview Current Deployment Status Use at OG&E Problems Solved & Interesting Findings

More information

Fuzzy and Hysteresis Current Control Based SMES to Improve the Performance of DFIG for Wind Energy Systems

Fuzzy and Hysteresis Current Control Based SMES to Improve the Performance of DFIG for Wind Energy Systems Fuzzy and Hysteresis Current Control Based SMES to Improve the Performance of DFIG for Wind Energy Systems A. Siva Prasad PG student, B.Sreenivasa Raju Assistant professor, K.V.Satheesh Babu Assistant

More information

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels

More information

CONVERTERS IN POWER VOLTAGE-SOURCED SYSTEMS. Modeling, Control, and Applications IEEE UNIVERSITATSBIBLIOTHEK HANNOVER. Amirnaser Yazdani.

CONVERTERS IN POWER VOLTAGE-SOURCED SYSTEMS. Modeling, Control, and Applications IEEE UNIVERSITATSBIBLIOTHEK HANNOVER. Amirnaser Yazdani. VOLTAGE-SOURCED CONVERTERS IN POWER SYSTEMS Modeling, Control, and Applications Amirnaser Yazdani University of Western Ontario Reza Iravani University of Toronto r TECHNISCHE INFORMATIONSBIBLIOTHEK UNIVERSITATSBIBLIOTHEK

More information

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Level 6 Graduate Diploma in Engineering Electrical Energy Systems 9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,

More information

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated

More information

1. An Introduction to Transient Stability

1. An Introduction to Transient Stability University of Technology, Jamaica School of Engineering Electrical Power Systems 1. An Introduction to Transient Stability Aims To give an appreciation of the data required for transient stability studies

More information

Grid Code Violation during Fault Triggered Islanding of Hybrid Micro-grid

Grid Code Violation during Fault Triggered Islanding of Hybrid Micro-grid Grid Code Violation during Fault Triggered Islanding of Hybrid Micro-grid Mazheruddin H. Syed, Student Member, IEEE, H.H. Zeineldin and M.S. El Moursi, Member, IEEE Department of Electrical Power Engineering

More information

International White Book on DER Protection: Review and Testing Procedures

International White Book on DER Protection: Review and Testing Procedures European Distributed Energy Resources Laboratories International White Book on DER Protection: Review and Testing Procedures Ibrahim Abdulhadi Xinyao Li Federico Coffele Paul Crolla Adam Dyśko Campbell

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi

More information

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event

More information

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75 PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion

More information

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017

Grid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017 Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the

More information

Inertial Response from Remote Offshore Wind Farms Connected Through VSC-HVDC Links: A Communication-less Scheme

Inertial Response from Remote Offshore Wind Farms Connected Through VSC-HVDC Links: A Communication-less Scheme 1 Inertial Response from Remote Offshore Wind Farms Connected Through VSCHVDC Links: A Communicationless Scheme Yousef Pipelzadeh, Student Member, IEEE, Balarko Chaudhuri, Senior Member, IEEE, Tim C. Green,

More information

The Implementation of the Low Voltage Ride-Through Curve on the Protection System of a Wind Power Plant

The Implementation of the Low Voltage Ride-Through Curve on the Protection System of a Wind Power Plant European Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ) International Conference on Renewable Energies and Power Quality (ICREPQ ) Las Palmas de Gran Canaria

More information

Switching Induced Transients:

Switching Induced Transients: Switching Induced Transients: Transformer switching is the most commonly performed operation in any power delivery system and most of the times this operation can be performed without any undesirable consequences.

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Simulation of Steady-State and Transient Operational Behaviour of Variable-Speed Motor-Generators of Hydro Power Plants

Simulation of Steady-State and Transient Operational Behaviour of Variable-Speed Motor-Generators of Hydro Power Plants 11 IEEE International Electric Machines & Drives Conference (IEM Simulation of Steady-State and Transient Operational Behaviour of Variable-Speed Motor-Generators of Hydro Power Plants Erich Schmidt, Member,

More information

Target Mchunu and Themba Khoza Eskom Transmission Division, System Operator Grid Code Management

Target Mchunu and Themba Khoza Eskom Transmission Division, System Operator Grid Code Management GRID CONNECTION CODE FOR RENEWABLE POWER PLANTS (RPPs) CONNECTED TO THE ELECTRICITY TRANSMISSION SYSTEM (TS) OR THE DISTRIBUTION SYSTEM (DS) IN SOUTH AFRICA Target Mchunu and Themba Khoza Eskom Transmission

More information

Markus Abplanalp, 7. Braunschweiger Supraleiterseminar, Strombegrenzerkonzepte im Vergleich

Markus Abplanalp, 7. Braunschweiger Supraleiterseminar, Strombegrenzerkonzepte im Vergleich Markus Abplanalp, 7. Braunschweiger Supraleiterseminar, 6.6.2013 Strombegrenzerkonzepte im Vergleich Motivation Why fault current Limiter? Compromise in Power Systems High short-circuit capacity during

More information

Reactive Power Control of DFIG Wind Turbines for Power Oscillation Damping under a Wide Range of Operating Conditions

Reactive Power Control of DFIG Wind Turbines for Power Oscillation Damping under a Wide Range of Operating Conditions Reactive Power Control of DFIG Wind Turbines for Power Oscillation Damping under a Wide Range of Operating Conditions Mohamed Edrah, K.L. Lo, Olimpo Anaya-Lara Department of Electrical and Electronic Engineering,

More information

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)

Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) IRR-DCC-MV 1. Introduction 1 IRR-DCC-MV 2. Scope 1 IRR-DCC-MV 2.1. General 1 IRR-DCC-MV 2.2. Affected

More information

Intelligent Passive Anti-Islanding Protection for Doubly Fed Induction Generators

Intelligent Passive Anti-Islanding Protection for Doubly Fed Induction Generators Research Journal of Recent Sciences ISSN 2277-2502 Res.J.Recent Sci. Intelligent Passive Anti-Islanding Protection for Doubly Fed Induction Generators Abstract Madani S.S., Abbaspour A., Rezaie Benam M.

More information

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS S1. Standard Interconnection Methods with Typical Circuit Configuration for Single or Multiple Units Note: The protection requirements

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products

More information

Integration of Variable Renewable Energy

Integration of Variable Renewable Energy Integration of Variable Renewable Energy PRAMOD JAIN, Ph.D. Consultant, USAID Power the Future October 1, 2018 Almaty, Republic of Kazakhstan Venue: Almaty University of Power Engineering and Telecommunications

More information

Active Power Sharing and Frequency Control of Multiple Distributed Generators in A Microgrid

Active Power Sharing and Frequency Control of Multiple Distributed Generators in A Microgrid IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, PP 01-07 www.iosrjournals.org Active Power Sharing and Frequency Control of Multiple Distributed

More information

How to maximize reliability using an alternative distribution system for critical loads

How to maximize reliability using an alternative distribution system for critical loads White Paper WP024001EN How to maximize reliability using an alternative distribution system for critical loads Executive summary The electric power industry has several different distribution topologies

More information

Fuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)

Fuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1) Dynamics and Control of Distributed Power Systems Fuel cell power system connection Ian A. Hiskens University of Wisconsin-Madison ACC Workshop June 12, 2006 This topology is fairly standard, though there

More information

Wide Area Control Systems (1.4) Mani V. Venkatasubramanian Washington State University (

Wide Area Control Systems (1.4) Mani V. Venkatasubramanian Washington State University ( Wide Area Control Systems (1.4) Mani V. Venkatasubramanian Washington State University (email: mani@eecs.wsu.edu) PSERC Future Grid Initiative May 29, 2013 Task Objectives Wide-area control designs for

More information

MODELLING AND CONTROL OF A VARIABLE-SPEED SWITCHED RELUCTANCE GENERATOR BASED WIND TURBINE

MODELLING AND CONTROL OF A VARIABLE-SPEED SWITCHED RELUCTANCE GENERATOR BASED WIND TURBINE MODELLING AND CONTROL OF A VARIABLE-SPEED SWITCHED RELUCTANCE GENERATOR BASED WIND TURBINE D. McSwiggan (1), L. Xu (1), T. Littler (1) (1) Queen s University Belfast, UK ABSTRACT This paper studies the

More information

ADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS

ADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS ADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS R. A. Walling, K. Clark, N. W. Miller, J. J. Sanchez-Gasca GE Energy USA reigh.walling@ge.com ABSTRACT

More information

IEEE sion/1547revision_index.html

IEEE sion/1547revision_index.html IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html

More information

B.Tech Academic Projects EEE (Simulation)

B.Tech Academic Projects EEE (Simulation) B.Tech Academic Projects EEE (Simulation) Head office: 2 nd floor, Solitaire plaza, beside Image Hospital, Ameerpet Ameerpet : 040-44433434, email id : info@kresttechnology.com Dilsukhnagar : 9000404181,

More information

Standards Developments for Fault Current Limiters

Standards Developments for Fault Current Limiters tandards Developments for Fault Current Limiters Dr. Michael Mischa teurer steurer@caps.fsu.edu Center for Advanced Power ystems (CAP) Florida tate University 2000 Levy Avenue, Building A, Tallahassee,

More information

Strathprints Institutional Repository

Strathprints Institutional Repository Strathprints Institutional Repository Tzelepis, Dimitrios and Dysko, Adam and Booth, Campbell (6) Performance of loss-of-mains detection in multi-generator power islands. In: The th IET International Conference

More information

International Journal of Scientific & Engineering Research, Volume 4, Issue 7, July ISSN

International Journal of Scientific & Engineering Research, Volume 4, Issue 7, July ISSN International Journal of Scientific & Engineering Research, Volume 4, Issue 7, July-2013 866 Study of position of SFCL for maximum fault current limiter for power systems protection Sachin Trankatwar 1,

More information

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) 7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series

More information

PHYSICAL PHENOMENA EXISTING IN THE TURBOGENERATOR DURING FAULTY SYNCHRONIZATION WITH INVERSE PHASE SEQUENCE*

PHYSICAL PHENOMENA EXISTING IN THE TURBOGENERATOR DURING FAULTY SYNCHRONIZATION WITH INVERSE PHASE SEQUENCE* Vol. 1(36), No. 1, 2016 POWER ELECTRONICS AND DRIVES DOI: 10.5277/PED160112 PHYSICAL PHENOMENA EXISTING IN THE TURBOGENERATOR DURING FAULTY SYNCHRONIZATION WITH INVERSE PHASE SEQUENCE* ADAM GOZDOWIAK,

More information

5 Summary LOW VOLTAGE RIDE THROUGH WITH HIGH CURRENT INJECTION. Motivation. Future Requirements. Test results for symmetrical failures

5 Summary LOW VOLTAGE RIDE THROUGH WITH HIGH CURRENT INJECTION. Motivation. Future Requirements. Test results for symmetrical failures LOW VOLTAGE RIDE THROUGH WITH HIGH CURRENT INJECTION 1 2 3 4 Motivation Future Requirements Test results for symmetrical failures Test results for asymmetrical failures 5 Summary 1 DYNAMIC VOLTAGE CONTROL:

More information

Table of Contents. Introduction... 1

Table of Contents. Introduction... 1 Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...

More information

Qualitrol s PMU Technologies

Qualitrol s PMU Technologies Qualitrol s PMU Technologies IDM NASPI Conference June 2008 BEN 6000 Agenda 1. Qualitrol s experience 2. Recording functions that compliment Phasor Measurement 3. A Multi function PMU 4. PMU Case Study

More information

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78) Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,

More information

HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS

HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS Enrique PÉREZ Santiago REMENTERIA Aitor LAKA Arteche Spain Arteche Spain Ingeteam Power Technology-Spain ep@arteche.es sr@arteche.es Aitor.Laka@ingeteam.com

More information

Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS

Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS Option C4 Block differential current protection Description of option Functional descriptions Parameter list Document no.: 4189340397C SW version:

More information