Comparison of the Behaviour of Wind Farms and Conventional Power Stations during Grid Failure Conditions
|
|
- Jordan Russell
- 5 years ago
- Views:
Transcription
1 May 4 Comparison of the Behaviour of Wind Farms and Conventional Power Dr. Martin Janßen APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT
2 Overview Introduction Grid Faults Requirements for Grid Stability Fault Clearance Measurement Characteristics of Generating Units Synchronous Generator Fully Fed Synchronous Generator Doubly Fed Induction Generator Simulation Simulation Model Simulation Results Conclusion 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be
3 Introduction The effect of wind power cannot be neglected anymore Grid operators expect wind farms to behave like conventional synchronous generators: Fault Ride Trough Voltage Control Frequency Control New Grid Connection Conditions How do wind farms behave during grid faults? Does this behaviour cause any problems? 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 3
4 Grid Faults Requirements for Grid Stability High short circuit current for triggering of circuit breakers Delivery of reactive current during the fault Fast recovery of active power after fault clearance 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 4
5 Grid Faults Fault Clearance A fault on a transmission line is connected to the grid by the two ends of the line The circuit breakers nearest to the fault open within 1 ms The circuit breakers at the other end open 4 ms after the first The individual phases of the circuit breakers open sequentially, typically 5 ms apart 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 5
6 Grid Faults Measurement Tree phase fault on a 75 kv transmission line Phase Voltage [kv] Fault Duration 33.5 kv (15.8 % of V nom ) 5 Phase A Phases B and C see similar voltage depressions to Phase A Phase B Phase C 8 ms 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 6
7 Characteristics of Generating Units Synchronous Generator High short circuit current Reactive current provided during grid faults Fast recovery of active power, but high oscillations Danger of tripping if fault lasts too long 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 7
8 Characteristics of Generating Units Fully Fed Synchronous Generator Variable speed generator Generator decoupled from grid, behaviour determined by the converter Low transients Limited short circuit current Reactive current provided by converter Fast recovery of active power possible Turbine High voltage High voltage Transformer ~ ~ SG 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 8
9 Characteristics of Generating Units Doubly Fed Induction Generator Most common variable speed wind turbine design High voltage dynamic leads to over current of the generator High short circuit current but low a.c. component Reactive power provided by generator and converter Fast recovery of active power possible Transformer DFIG High voltage High voltage ~ ~ 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 9
10 Simulation model Transformer HV - MV Transformer MV - LV ~ = Pro Wind = ~ Z G 11 % u k 6 % u k Generator u Grid ~ Z F u PCC u Gen M Turbine n Crowbar 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 1
11 Simulation 3-Phase Fault with U PCC = 15 % U N Synchronous Generator U Gen / U N U / U N U PCC / U N i a, i r I Grid / I N t [s] 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 11
12 Simulation 3-Phase Fault with U PCC = 15 % U N Synchronous Generator U Gen / U N U / U N U PCC / U N t [s] 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 1
13 Simulation 3-Phase Fault with U PCC = 15 % U N Fully Fed Synchronous Generator U Gen / U N U PCC / U N U / U N i a, i r I Grid / I N t [s] 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 13
14 Simulation 3-Phase Fault with U PCC = 15 % U N Doubly Fed Induction Generator U Gen / U N U PCC / U N U / U N i a, i r I Grid / I N t [s] 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 14
15 Simulation 3-Phase Fault with U PCC = 15 % U N DFIG + Fully Fed SG U Gen / U N U PCC / U N U / U N i a, i r I Grid / I N t [s] 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 15
16 Conclusion Wind farms can have a similar characteristic as conventional synchronous generators All types of generators have different advantages / drawbacks regarding short circuit current / reactive power / active power With an appropriate design and control wind farms can help to stabilize the grid 5.4 APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT/ Dr.JANSSEN / Be 16
17
Netzkurzschlussverhalten von umrichterbetriebenen regenerativen Energieerzeugern und -speichern
October 25 Netzkurzschlussverhalten von umrichterbetriebenen regenerativen Energieerzeugern und -speichern Dr. Georg Möhlenkamp 5MOP8_EN-(Netzkurzschlussverhalten-Energieerzeuger).PPT / Dr.MÖHLENKAMP Overview
More informationInfluence of Wind Generators in Voltage Dips
Influence of Wind Generators in Voltage Dips E. Belenguer, N. Aparicio, J.L. Gandía, S. Añó 2 Department of Industrial Engineering and Design Universitat Jaume I Campus de Riu Sec, E-27 Castelló (Spain)
More informationWIND FARM Flexible AC Transmission Systems
WIND FARM Flexible AC Transmission Systems WIND ENERGY AND GRID INTEGRATION Madrid 24-25 January 2006 Jacques COURAULT Assumption: Wind farm is with Fixed Speed Induction Generator (FSIG) SUMMARY 1/ Wind
More informationIMPROVED SYNCHRONISM IN DFIG WIND ENERGY CONVERSION SYSTEM USING SMES ENERGY STORAGE
IMPROVED SYNCHRONISM IN DFIG WIND ENERGY CONVERSION SYSTEM USING SMES ENERGY STORAGE 1 PALLAVI DATE, 2 SUJAY KULKARNI, 3 SAKSHI PORJE, 4 JOYDEEP SARKAR 1 Electrical Power System, MCOERC, Nashik 2,3.4 Electrical
More informationSystem for Better Synchronism in DFIG Wind Energy Conversion System Using SMES Energy Storage
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 1 Ver. IV (Jan Feb. 2015), PP 23-29 www.iosrjournals.org System for Better Synchronism
More informationAnalysis of the Effectiveness of Grid Codes for Offshore Wind Farms Connected to Onshore Grid via VSC-Based HVDC
Conference of the Wind Power Engineering Community Analysis of the Effectiveness of Grid Codes for Offshore Wind Farms Connected to Onshore Grid via VSC-Based HVDC Moritz Mittelstaedt, Andreas Roehder,.Hendrik
More informationDevelopment of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine
Development of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine T. Neumann, C. Feltes, I. Erlich University Duisburg-Essen Institute of Electrical Power Systems Bismarckstr. 81,
More informationHarnessing of wind power in the present era system
International Journal of Scientific & Engineering Research Volume 3, Issue 1, January-2012 1 Harnessing of wind power in the present era system Raghunadha Sastry R, Deepthy N Abstract This paper deals
More informationNeutral Grounding in Wind Farm Medium Voltage Collector Grids
Neutral Grounding in Wind Farm Medium Voltage Collector Grids C. Feltes, Student Member, IEEE, R. van de Sandt, Member, IEEE, F. Koch, F. Shewarega, Member, IEEE, I. Erlich, Senior Member, IEEE Abstract
More informationRequirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH
Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 5th October 2010 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT
More informationDESIGN OF A MODE DECOUPLING FOR VOLTAGE CONTROL OF WIND-DRIVEN IG SYSTEM
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 8, Issue 5 (Nov. - Dec. 2013), PP 41-45 DESIGN OF A MODE DECOUPLING FOR VOLTAGE CONTROL OF
More informationWind and Solar (PV) Sub harmonic Interactions with Power Systems
I PCGRID Workshop - 2017 Wind and Solar (PV) Sub harmonic Interactions with Power Systems Dr. Krish Narendra Chief Technology Officer ERLPhase Protection, Automation, Control & Smart Grid ERLPhase Power
More informationWFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS
WFPS1 WIND FARM POWER STATION GRID CODE PROVISIONS WFPS1.1 INTRODUCTION 2 WFPS1.2 OBJECTIVE 2 WFPS1.3 SCOPE 3 WFPS1.4 FAULT RIDE THROUGH REQUIREMENTS 4 WFPS1.5 FREQUENCY REQUIREMENTS 5 WFPS1.6 VOLTAGE
More informationControl Strategy of a Dc-Link Brake Chopper for Low-Voltage-Ride-Through in Doubly Fed Induction Generator
AENSI Journals Australian Journal of Basic and Applied Sciences ISSN:1991-8178 Journal home page: www.ajbasweb.com Control Strategy of a Dc-Link Brake Chopper for Low-Voltage-Ride-Through in Doubly Fed
More informationControl of Wind Power Plant for Cooperation with Conventional Power Generation Unit and HVDC Classic Link
Control of Wind Power Plant for Cooperation with Conventional Power Generation Unit and HVDC Classic Link Li-Jun Cai*, Simon Jensen **, Vincenz Dinkhauser***, István Erlich**** REpower Systems SE,. Albert-Betz-Strasse,
More informationQUESTIONNAIRE for Wind Farm Power Stations only
TRANSMISSION SYSTEM OPERATOR QUESTIONNAIRE for Wind Farm Power Stations only To be submitted by the Generation Licensees together with the Application for Connection Certificate according to IEC 61400-21
More informationMitigation & Protection of Sub-Synchronous Controller Interactions (SSCI) in DFIG Wind Turbine Systems
Mitigation & Protection of Sub-Synchronous Controller Interactions (SSCI) in DFIG Wind Turbine Systems Krish Narendra, P.hD. CTO ERL Protection, Automation, Control & Smart Grid ERLPhase Power Technologies
More informationUProtection Requirements. Ufor a Large scale Wind Park. Shyam Musunuri Siemens Energy
UProtection Requirements Ufor a Large scale Wind Park Shyam Musunuri Siemens Energy Abstract: In the past wind power plants typically had a small power rating when compared to the strength of the connected
More informationLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
Scientific Journal Impact Factor (SJIF): 1.711 e-issn: 2349-9745 p-issn: 2393-8161 International Journal of Modern Trends in Engineering and Research www.ijmter.com LOW VOLTAGE RIDE - THROUGH CAPABILITY
More informationOffshore AC Grid Management for an AC Integrated VSC-HVDC Scheme with Large WPPs
Offshore AC Grid Management for an AC Integrated VSC-HVDC Scheme with Large WPPs Rakibuzzaman Shah, Member, IEEE, Mike Barnes, Senior Member, IEEE, and Robin Preece, Member, IEEE School of Electrical and
More informationETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents
Page: 1 Electrical Transient Analyzer Program Short Circuit Analysis ANSI Standard 3-Phase Fault Currents Number of Buses: Swing Generator Load Total 1 0 4 5 Number of Branches: XFMR2 XFMR3 Reactor Line/Cable
More informationImproved Transient Compensation Using PI-SRF Control Scheme Based UHVDC For Offshore Wind Power Plant
Improved Transient Compensation Using PI-SRF Control Scheme Based UHVDC For Offshore Wind Power Plant Sangeetha M 1, Arivoli R 2, Karthikeyan B 3 1 Assistant Professor, Department of EEE, Imayam College
More informationSynchrophasor Technology PMU Use Case Examples
1 IEEE Tutorial on Use of Synchrophasors in Grid Operations - Oscillation Source Detection and Operational Use of Synchrophasors Synchrophasor Technology PMU Use Case Examples Sarma (NDR) Nuthalapati,
More informationHow Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements
How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements Robert Nelson Senior Expert Engineering Manager and Manager of Codes, Standards, and Regulations Siemens Wind Turbines -
More informationControl of a Three Phase Inverter Mimicking Synchronous Machine with Fault Ridethrough
2017 Ninth Annual IEEE Green Technologies Conference Control of a Three Phase Inverter Mimicking Synchronous Machine with Fault Ridethrough Capability Vikram Roy Chowdhury, Subhajyoti Mukherjee, Pourya
More informationWind Power Facility Technical Requirements CHANGE HISTORY
CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical
More informationFacilitating Bulk Wind Power Integration Using LCC HVDC
21, rue d Artois, F-758 PARIS CIGRE US National Committee http : //www.cigre.org 213 Grid of the Future Symposium Facilitating Bulk Wind Power Integration Using LCC HVDC A. HERNANDEZ * R.MAJUMDER W. GALLI
More informationPlanners Perspective on Series Compensated Transmission Lines
TOGETHER WE DELIVER Planners Perspective on Series Compensated Transmission Lines Kenneth A. Donohoo, PE Director, System Planning Distribution and Transmission kenneth.donohoo@oncor.com Oncor Electric
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationSarma (NDR) Nuthalapati, PhD
SYNCHROPHASOR TECHNOLOGY PMU USE CASE EXAMPLES Sarma (NDR) Nuthalapati, PhD Research Scientist Texas A&M University, College Station, TX Control Room Solutions Task Team NASPI Work Group meeting and first
More informationAalborg Universitet. Design and Control of A DC Grid for Offshore Wind Farms Deng, Fujin. Publication date: 2012
Aalborg Universitet Design and Control of A DC Grid for Offshore Wind Farms Deng, Fujin Publication date: 2012 Document Version Publisher's PDF, also known as Version of record Link to publication from
More informationControl of Grid Side Inverter in a B2B Configuration for WT Applications. Master Thesis. by George Alin RADUCU
Control of Grid Side Inverter in a B2B Configuration for WT Applications Master Thesis by George Alin RADUCU PED10-1015b Aalborg University, 2008 Preface This present Master Thesis Control of Grid Side
More informationDC BUS VOLTAGE CONTROL OF PWM CONVERTERS IN PMSG IN WIND POWER SYSTEM Krishnamoorthy.M 1 Andal. S 2 M.Varatharaj 3
ISSN: 2349-2503 DC BUS VOLTAGE CONTROL OF PWM CONVERTERS IN PMSG IN WIND POWER SYSTEM Krishnamoorthy.M 1 Andal. S 2 M.Varatharaj 3 1 (Dept of EEE, Christ the king engineering college, Coimbatore, India,
More informationSimulations of open phase conditions on the high voltage side of YNd05-power plant transformers
Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Disclaimer: All information presented in the report, the results and the related computer program, data,
More informationADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION
23 rd International Conference on Electricity Distribution Lyon, 5-8 June 25 Paper 48 ADVANCED VECT SHIFT ALGITHM F ISLANDING DETECTION Murali KANDAKATLA Hannu LAAKSONEN Sudheer BONELA ABB GISL India ABB
More informationMITIGATION OF VOLTAGE SAG IN A DFIG BASED WIND TURBINE USING DVR
MITIGATION OF VOLTAGE SAG IN A DFIG BASED WIND TURBINE USING DVR M Venmathi*, Soumyadeep Chakraborti 1, Soham Ghosh 2, Abhirup Ray 3, Vidhya Nikam 4 * (Senior Lecturer, Dept. of Electrical and Electronics,
More informationFault Ride Through Technical Assessment Report Template
Fault Ride Through Technical Assessment Report Template Notes: 1. This template is intended to provide guidelines into the minimum content and scope of the technical studies required to demonstrate compliance
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements
Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system
More informationImprovement of Power Quality in PMSG Based Wind Integrated System Using FACTS Controller
Improvement of Power Quality in PMSG Based Wind Integrated System Using FACTS Controller Lekshmi M 1, Vishnu J 2 1PG Scholar, 2 Assistant Professor 1,2 Dept. of Electrical and Electronics Engineering Sree
More informationNOWADAYS, there is much interest in connecting various
IEEE TRANSACTIONS ON SMART GRID, VOL. 4, NO. 1, MARCH 2013 419 Modified Dynamic Phasor Estimation Algorithm for the Transient Signals of Distributed Generators Dong-Gyu Lee, Sang-Hee Kang, and Soon-Ryul
More informationFault current contribution from PPMS & HVDC
Fault current contribution from PPMS & HVDC ENTSO-E guidance document for national implementation for network codes on grid connection 16 November 2016 Table of Contents DESCRIPTION...3 Code(s) &...3 Introduction...3
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationImprovement of Power Quality Considering Voltage Stability in Grid Connected System by FACTS Devices
Improvement of Power Quality Considering Voltage Stability in Grid Connected System by FACTS Devices Sarika D. Patil Dept. of Electrical Engineering, Rajiv Gandhi College of Engineering & Research, Nagpur,
More informationFault Ride-through Capability Test Unit for Wind Turbines
WIND ENERGY Wind Energ. 2008; 11:3 12 Published online 7 November 2007 in Wiley Interscience (www.interscience.wiley.com).255 Research Article Fault Ride-through Capability Test Unit for Wind Turbines
More informationApplication for A Sub-harmonic Protection Relay. ERLPhase Power Technologies
Application for A Sub-harmonic Protection Relay ERLPhase Power Technologies 1 Outline Introduction System Event at Xcel Energy Event Analysis Microprocessor based relay hardware architecture Sub harmonic
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationIDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)
IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone
More informationImpact Assessment Generator Form
Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project
More informationAn Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing In Inverter-Based Islanded Micro grids
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331 PP 33-40 www.iosrjournals.org An Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing
More informationEnhancement of Reactive Power Capability of DFIG using Grid Side Converter
Enhancement of Reactive Power Capability of DFIG using Grid Side Converter V. Sumitha 1 R. Gnanadass 2 Abstract - In the new electricity grid code, reactive power generation by wind farms, which must operate
More informationNew Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage
1 New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage B. B. Pimple, V. Y. Vekhande and B. G. Fernandes Department of Electrical Engineering, Indian Institute of Technology Bombay,
More informationThe Open Access Institutional Repository at Robert Gordon University
OpenAIR@RGU The Open Access Institutional Repository at Robert Gordon University http://openair.rgu.ac.uk Citation Details Citation for the version of the work held in OpenAIR@RGU : TAN, S. F., 2010. Development
More informationVoltage Stability Improvement of Four Parallel Operated Offshore Wind Turbine Using Fuzzy Controller
2014 IJEDR Volume 2, Issue 1 ISSN: 2321-9939 Voltage Stability Improvement of Four Parallel Operated Offshore Wind Turbine Using Fuzzy Controller 1 R.Balamurugan, 2 R.Punitharaji 1 Student, 2 Assistant
More informationSystem Requirements for Wind Farms and Distributed Generation. Giuseppe Di Marzio
ystem Requirements for Wind Farms and Distributed Generation Giuseppe Di Marzio giuseppe.di.marzio@elraft.ntnu.no 1 Contents Grid interconnection schemes Power quality requirements Fault Level considerations
More informationSynchroPhasor use at OG&E. Austin D. White P.E. Steven E. Chisholm Oklahoma Gas & Electric
SynchroPhasor use at OG&E Austin D. White P.E. Steven E. Chisholm Oklahoma Gas & Electric Outline Hardware/Software Overview Current Deployment Status Use at OG&E Problems Solved & Interesting Findings
More informationFuzzy and Hysteresis Current Control Based SMES to Improve the Performance of DFIG for Wind Energy Systems
Fuzzy and Hysteresis Current Control Based SMES to Improve the Performance of DFIG for Wind Energy Systems A. Siva Prasad PG student, B.Sreenivasa Raju Assistant professor, K.V.Satheesh Babu Assistant
More informationCompany Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System
Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels
More informationCONVERTERS IN POWER VOLTAGE-SOURCED SYSTEMS. Modeling, Control, and Applications IEEE UNIVERSITATSBIBLIOTHEK HANNOVER. Amirnaser Yazdani.
VOLTAGE-SOURCED CONVERTERS IN POWER SYSTEMS Modeling, Control, and Applications Amirnaser Yazdani University of Western Ontario Reza Iravani University of Toronto r TECHNISCHE INFORMATIONSBIBLIOTHEK UNIVERSITATSBIBLIOTHEK
More informationLevel 6 Graduate Diploma in Engineering Electrical Energy Systems
9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,
More informationA New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2015 Grid of the Future Symposium A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated
More information1. An Introduction to Transient Stability
University of Technology, Jamaica School of Engineering Electrical Power Systems 1. An Introduction to Transient Stability Aims To give an appreciation of the data required for transient stability studies
More informationGrid Code Violation during Fault Triggered Islanding of Hybrid Micro-grid
Grid Code Violation during Fault Triggered Islanding of Hybrid Micro-grid Mazheruddin H. Syed, Student Member, IEEE, H.H. Zeineldin and M.S. El Moursi, Member, IEEE Department of Electrical Power Engineering
More informationInternational White Book on DER Protection: Review and Testing Procedures
European Distributed Energy Resources Laboratories International White Book on DER Protection: Review and Testing Procedures Ibrahim Abdulhadi Xinyao Li Federico Coffele Paul Crolla Adam Dyśko Campbell
More informationAORC Technical meeting 2014
http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi
More informationTexas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event
Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event
More informationPRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75
PRC-025-1 Introduction The document, Power Plant and Transmission System Protection Coordination, published by the NERC System Protection and Control Subcommittee (SPCS) provides extensive general discussion
More informationGrid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017
Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the
More informationInertial Response from Remote Offshore Wind Farms Connected Through VSC-HVDC Links: A Communication-less Scheme
1 Inertial Response from Remote Offshore Wind Farms Connected Through VSCHVDC Links: A Communicationless Scheme Yousef Pipelzadeh, Student Member, IEEE, Balarko Chaudhuri, Senior Member, IEEE, Tim C. Green,
More informationThe Implementation of the Low Voltage Ride-Through Curve on the Protection System of a Wind Power Plant
European Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ) International Conference on Renewable Energies and Power Quality (ICREPQ ) Las Palmas de Gran Canaria
More informationSwitching Induced Transients:
Switching Induced Transients: Transformer switching is the most commonly performed operation in any power delivery system and most of the times this operation can be performed without any undesirable consequences.
More informationShortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller
Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of
More informationSimulation of Steady-State and Transient Operational Behaviour of Variable-Speed Motor-Generators of Hydro Power Plants
11 IEEE International Electric Machines & Drives Conference (IEM Simulation of Steady-State and Transient Operational Behaviour of Variable-Speed Motor-Generators of Hydro Power Plants Erich Schmidt, Member,
More informationTarget Mchunu and Themba Khoza Eskom Transmission Division, System Operator Grid Code Management
GRID CONNECTION CODE FOR RENEWABLE POWER PLANTS (RPPs) CONNECTED TO THE ELECTRICITY TRANSMISSION SYSTEM (TS) OR THE DISTRIBUTION SYSTEM (DS) IN SOUTH AFRICA Target Mchunu and Themba Khoza Eskom Transmission
More informationMarkus Abplanalp, 7. Braunschweiger Supraleiterseminar, Strombegrenzerkonzepte im Vergleich
Markus Abplanalp, 7. Braunschweiger Supraleiterseminar, 6.6.2013 Strombegrenzerkonzepte im Vergleich Motivation Why fault current Limiter? Compromise in Power Systems High short-circuit capacity during
More informationReactive Power Control of DFIG Wind Turbines for Power Oscillation Damping under a Wide Range of Operating Conditions
Reactive Power Control of DFIG Wind Turbines for Power Oscillation Damping under a Wide Range of Operating Conditions Mohamed Edrah, K.L. Lo, Olimpo Anaya-Lara Department of Electrical and Electronic Engineering,
More informationIntermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV)
Intermittent Renewable Resources (Wind and PV) Distribution Connection Code (DCC) At Medium Voltage (MV) IRR-DCC-MV 1. Introduction 1 IRR-DCC-MV 2. Scope 1 IRR-DCC-MV 2.1. General 1 IRR-DCC-MV 2.2. Affected
More informationIntelligent Passive Anti-Islanding Protection for Doubly Fed Induction Generators
Research Journal of Recent Sciences ISSN 2277-2502 Res.J.Recent Sci. Intelligent Passive Anti-Islanding Protection for Doubly Fed Induction Generators Abstract Madani S.S., Abbaspour A., Rezaie Benam M.
More informationAppendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS
Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS S1. Standard Interconnection Methods with Typical Circuit Configuration for Single or Multiple Units Note: The protection requirements
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationPOWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.
POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products
More informationIntegration of Variable Renewable Energy
Integration of Variable Renewable Energy PRAMOD JAIN, Ph.D. Consultant, USAID Power the Future October 1, 2018 Almaty, Republic of Kazakhstan Venue: Almaty University of Power Engineering and Telecommunications
More informationActive Power Sharing and Frequency Control of Multiple Distributed Generators in A Microgrid
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, PP 01-07 www.iosrjournals.org Active Power Sharing and Frequency Control of Multiple Distributed
More informationHow to maximize reliability using an alternative distribution system for critical loads
White Paper WP024001EN How to maximize reliability using an alternative distribution system for critical loads Executive summary The electric power industry has several different distribution topologies
More informationFuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)
Dynamics and Control of Distributed Power Systems Fuel cell power system connection Ian A. Hiskens University of Wisconsin-Madison ACC Workshop June 12, 2006 This topology is fairly standard, though there
More informationWide Area Control Systems (1.4) Mani V. Venkatasubramanian Washington State University (
Wide Area Control Systems (1.4) Mani V. Venkatasubramanian Washington State University (email: mani@eecs.wsu.edu) PSERC Future Grid Initiative May 29, 2013 Task Objectives Wide-area control designs for
More informationMODELLING AND CONTROL OF A VARIABLE-SPEED SWITCHED RELUCTANCE GENERATOR BASED WIND TURBINE
MODELLING AND CONTROL OF A VARIABLE-SPEED SWITCHED RELUCTANCE GENERATOR BASED WIND TURBINE D. McSwiggan (1), L. Xu (1), T. Littler (1) (1) Queen s University Belfast, UK ABSTRACT This paper studies the
More informationADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS
ADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS R. A. Walling, K. Clark, N. W. Miller, J. J. Sanchez-Gasca GE Energy USA reigh.walling@ge.com ABSTRACT
More informationIEEE sion/1547revision_index.html
IEEE 1547 IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces http://grouper.ieee.org/groups/scc21/1547_revi sion/1547revision_index.html
More informationB.Tech Academic Projects EEE (Simulation)
B.Tech Academic Projects EEE (Simulation) Head office: 2 nd floor, Solitaire plaza, beside Image Hospital, Ameerpet Ameerpet : 040-44433434, email id : info@kresttechnology.com Dilsukhnagar : 9000404181,
More informationStandards Developments for Fault Current Limiters
tandards Developments for Fault Current Limiters Dr. Michael Mischa teurer steurer@caps.fsu.edu Center for Advanced Power ystems (CAP) Florida tate University 2000 Levy Avenue, Building A, Tallahassee,
More informationStrathprints Institutional Repository
Strathprints Institutional Repository Tzelepis, Dimitrios and Dysko, Adam and Booth, Campbell (6) Performance of loss-of-mains detection in multi-generator power islands. In: The th IET International Conference
More informationInternational Journal of Scientific & Engineering Research, Volume 4, Issue 7, July ISSN
International Journal of Scientific & Engineering Research, Volume 4, Issue 7, July-2013 866 Study of position of SFCL for maximum fault current limiter for power systems protection Sachin Trankatwar 1,
More informationCOMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)
7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series
More informationPHYSICAL PHENOMENA EXISTING IN THE TURBOGENERATOR DURING FAULTY SYNCHRONIZATION WITH INVERSE PHASE SEQUENCE*
Vol. 1(36), No. 1, 2016 POWER ELECTRONICS AND DRIVES DOI: 10.5277/PED160112 PHYSICAL PHENOMENA EXISTING IN THE TURBOGENERATOR DURING FAULTY SYNCHRONIZATION WITH INVERSE PHASE SEQUENCE* ADAM GOZDOWIAK,
More information5 Summary LOW VOLTAGE RIDE THROUGH WITH HIGH CURRENT INJECTION. Motivation. Future Requirements. Test results for symmetrical failures
LOW VOLTAGE RIDE THROUGH WITH HIGH CURRENT INJECTION 1 2 3 4 Motivation Future Requirements Test results for symmetrical failures Test results for asymmetrical failures 5 Summary 1 DYNAMIC VOLTAGE CONTROL:
More informationTable of Contents. Introduction... 1
Table of Contents Introduction... 1 1 Connection Impact Assessment Initial Review... 2 1.1 Facility Design Overview... 2 1.1.1 Single Line Diagram ( SLD )... 2 1.1.2 Point of Disconnection - Safety...
More informationQualitrol s PMU Technologies
Qualitrol s PMU Technologies IDM NASPI Conference June 2008 BEN 6000 Agenda 1. Qualitrol s experience 2. Recording functions that compliment Phasor Measurement 3. A Multi function PMU 4. PMU Case Study
More informationPower Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)
Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,
More informationHYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS
HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS Enrique PÉREZ Santiago REMENTERIA Aitor LAKA Arteche Spain Arteche Spain Ingeteam Power Technology-Spain ep@arteche.es sr@arteche.es Aitor.Laka@ingeteam.com
More informationMulti Differential Relay, MDR-2 DESCRIPTION OF OPTIONS
Multi Differential Relay, MDR-2 DESCRIPTION OF OPTIONS Option C4 Block differential current protection Description of option Functional descriptions Parameter list Document no.: 4189340397C SW version:
More information