Inertial Response from Remote Offshore Wind Farms Connected Through VSC-HVDC Links: A Communication-less Scheme
|
|
- Eugene Fletcher
- 5 years ago
- Views:
Transcription
1 1 Inertial Response from Remote Offshore Wind Farms Connected Through VSCHVDC Links: A Communicationless Scheme Yousef Pipelzadeh, Student Member, IEEE, Balarko Chaudhuri, Senior Member, IEEE, Tim C. Green, Senior Member, IEEE Abstract A communicationless scheme that allows remote offshore wind farms connected through HVDC links to participate in primary frequency control and contribute to system inertia is discussed in this paper. As a HVDC link decouples the offshore system from the onshore side, realtime communication of onshore frequency is normally required for the primary frequency control loop of the wind farms. Dependance on remote communication which could be unreliable at times is a problem. To obviate the need for communication, appropriate droop control on the offshore and onshore converters is used in this paper to translate the variation in onshore frequency to an equivalent variation on the offshore end. Thus the need for communicating onshore frequency to the offshore side is obviated which ensures reliable operation. Such a communicationless scheme is compared against the conventional approach involving remote communication of onshore grid frequency to the wind farm site. Along side physical and analytical justification, a case study is presented to demonstrate that the communicationless scheme performs similar to the conventional one in terms of reducing grid frequency variations. Index Terms Primary frequency control, inertial response, droop, offshore wind farms, VSCHVDC, communication I. INTRODUCTION FAST primary control of wind farms decouples their mechanical side from the electrical (network) side. Hence, the mechanical inertia effect of the wind turbines are not felt by the network. With large number of onshore and offshore farms set to displace decommissioned fossilfuel stations, the overall inertia of future systems would decrease significantly. As a result of this the variations in grid frequency would be more than before for a given disturbance. With significant penetration of wind, large reduction in overall inertia could result in unacceptable excursions of grid frequency outside the specified tolerance which is a cause of major concerns for utilities. With appropriate supplementary control around the primary control loops of wind farms, it is possible to force the wind farms to contribute to system inertia and thus participate in primary frequency control. Several methods for achieving this have been proposed and demonstrated [1], [2], [3], [4], [5], [6]. Although there are subtle differences each of these methods rely on measuring the grid frequency for adjusting the active Support from the EPSRC UK under grant EP/F (Power Networks Research Academy) is gratefully acknowledged. The authors are with the Control and Power Research group, Imperial College London, London, UK {y.pipelzadeh08,b.chaudhuri, t.green}@imperial.ac.uk /torque reference of the wind farms to counteract the variations in measured frequency. For onshore wind farms this is relatively straightforward as the grid frequency measured locally at the point of common coupling (PCC) can be readily used. The same is possible for nearby (less than 3040 kms into the sea) offshore wind farms with AC connection to the shore. For remote offshore wind farms, high voltage direct current (HVDC) is the only option for connection to main onshore grid. Voltage source converter (VSC) is arguably the only choice of HVDC technology in such cases [7]. An HVDC link is asynchronous which decouples the frequencies on the onshore and offshore end. Thus a variation in onshore grid frequency is not reflected on the offshore side. So the remote offshore wind farms cannot rely on frequency measured locally on the offshore side (at the PCC) to contribute to inertia (and participate in primary frequency control) like the onshore wind farms. One option is to remotely communicate the onshore grid frequency to the offshore wind farm site in real time as has been reported in [8], [9] in the context of line commutated converter (LCC) based HVDC link. However, the reliability of communication channels in terms of latency, reduced data rate or complete drop could pose difficulties. With large number of offshore wind farms envisaged especially, in Europe a reliable and effective solution to this problem is critical. In this paper, a technique is demonstrated which enables offshore wind farms connected through VSCHVDC link to contribute to system inertia and primary frequency control without having to rely on remote communications. The idea is based on using appropriate droop control on the offshore and onshore HVDC converters to translate the variation in onshore frequency to an equivalent variation an the offshore end. Thus the need for communicating onshore frequency to the offshore side is obviated which ensures reliable operation. The concept is illustrated with a case study on a multimachine onshore AC system with one large offshore wind farm connected through a VSCHVDC link. First the need for inertial response from wind farms in reducing the frequency variation is illustrated to set the context. Then the communicationless scheme is shown to perform very similar to a conventional scheme which relies on remote communication of onshore grid frequency. Finally, the challenges of the communicationless scheme in terms of potential variations in DC link voltage are highlighted.
2 2 II. ACTIVE POWER CONTROL FOR WIND FARMS Doublyfed induction generators (DFIG) are used for the wind farms throughout this paper. In particular, GE 1.5 MW wind turbine generator (WTG) model [10] is adopted and an aggregated model combining the WTGs within the wind farm as a single unit is used. A conceptual schematic of the active control for the WTGs is shown in Fig. 1 [2], [1], [10]. wind Fig. 1. angle wind model limits on compensation mech. i/p turbine control rotor model gen. o/p rotor torque control ref. rotor torque order rated Active control of WTGs rotor ref. rotor order limits gen. o/p Pord (from supplementary controller) Pord to converter control Using the angle and the tip ratio, the wind model calculates the mechanical extracted from wind. The mechanical input and the generator (electrical) output is used in the two mass (for turbine blades and generator shaft) rotor model to derive the turbine and the rotor. The deviation of this rotor from its reference value actuates the and torque control blocks. The compensation block generates a angle error signal depending on the deviation of actual order from the rated value. The torque order out of the torque control block and the rotor is used to derive the active order, P ord for the WTG which is passed on to the converter control block. III. INERTIAL RESPONSE FROM REMOTE OFFSHORE WIND FARMS Wind farms could participate in primary frequency control and contribute to system inertia by releasing the stored kinetic energy in response to a drop in grid frequency. The usual approach is to use the deviation in grid frequency from its nominal value to vary the active output of the wind farm as discussed below. A. Conventional scheme Several schemes have been proposed in the literature for deriving inertial response from wind farms. Although there are subtle differences between these approaches the basic philosophy is similar. The idea is to use the deviation in grid frequency to modulate the active output from the wind farms as shown in Fig. 2 [10]. The deviation in measured grid frequency (f meas ) from its nominal values (f nom ) is taken through a deadband block to f meas f ref deadband K w 1sT LP P ord min stw 1sT w P ord max Fig. 2. Control loop for modulation of wind farm output to participate in primary frequency control (i.e. provide inertial response) avoid responding to regular small variations in grid frequency. A gain and lowpass block is used to scale this frequency deviation appropriately. Rate limits and windup limits on the allowable range of change in order is used to derive the required change in order ( P ord ) which acts through the supplementary input (shown in Fig. 1) to modulate the active order (P ord ) of the wind farm. For remote offshore wind farms connected through a VSC HVDC link the grid frequency (f meas ) is communicated to the wind farm site for use in the control loop shown above. The modulation in active output of the wind farm is propagated onto the onshore main grid by having the offshore HVDC converter under AC voltagefrequency control while the onshore HVDC converter maintains the DC link voltage constant. With reliable and fast communication links in place, this scheme (termed conventional scheme ) works satisfactorily allowing remote offshore wind farms to participate in primary frequency control. B. Communicationless scheme For offshore wind farms connected to the main grid using VSCHVDC links the offshore converter is usually set to maintain a constant AC voltage at a given frequency so that coming from the wind farm side is transmitted on the DC side. The onshore converter is set to control the DC link voltage to a constant value so that the incoming is transferred on to the onshore AC system. The basic idea behind the communicationless scheme is to use appropriate droop characteristics on both the onshore and offshore converters to ensure that the frequency variation on the offshore side is proportional to that on the onshore side. The frequencyvoltage droop characteristics is used to derive the DC link voltage reference (Von) and frequency reference (foff ) settings for the onshore and offshore converters, respectively as shown in Fig. 3. The objective is to derive a variation in DC link voltage on the onshore end which is proportional to the onshore frequency variation (with respect to nominal value denoted by the superscript nom ) and translate that on the offshore end after compensating for the voltage drop across the DC cable (Fig. 3(b)). This voltage variation at the offshore end results in a proportional amount of variation in offshore frequency (Fig. 3(b)). The measured quantities (denoted by the superscript m ) used for the droop control schemes in Fig. 3 are all local. Thus without any need for remote communication the onshore frequency variation propagates on to the offshore side allowing communicationless primary frequency control from remote offshore wind farms. P ord
3 3 V off m f off nom K off f off * of the onshore AC system was increased to cause decrease of grid frequency from its nominal value of 60 Hz. V rated (a) Frequency reference for offshore HVDC converter f on m f on nom V rated K on R line I m (b) DC link voltage reference for onshore HVDC converter V on * Fig. 3. Droop control loops for offshore and onshore HVDC converters to achieve communicationless scheme A. Test System The wellknown 4machine, 2area system described in [11] was used for the case study. A number of modifications were made to the original system to suit the present case study. Three tielines as shown in Fig. 4 were considered. Each area consists of two coupled generation units, each having a rating of 600 MVA and 20 kv. Two scenarios were considered one with conventional generation and no wind farm and the other where one of the conventional plant was replaced by an equivalent offshore wind farm connected through VSCHVDC link as described below: 1) Scenario I: Conventional generation, no wind farm: All the units are equipped with steam turbinegovernor system [11]. Frequency dependent load models were considered. In steady state, each unit dispatch 500 MW with the loads Ld1 = 600 MW and Ld2 = 1358 MW resulting in a tieline flow of 380 MW. To analytically show the principle of operation of the above scheme, the droop control loops depicted in Fig. 3 are written as: (foff foff nom ) = K off (Voff m V rated ) (1) (Von V rated ) = K on (fon m fon nom ) R line I m (2) Assuming perfect control of onshore end DC link voltage i.e. Von m = Von and offshore frequency i.e. foff m = f off and using the fact that Voff m = V on m R line I m (where R line is the series resistance of the DC cable and I m is the measured current through the DC cable), (1) and (2) can be combined as: (f m off f nom off ) = K off K on (f m on f nom on ) (3) Thus the offshore frequency variation with respect to he nominal value foff m f off nom is proportional to the onshore frequency variation fon m fon nom. Hence, the local offshore frequency variation can be used for the primary frequency control loop of the wind farms. The values of K off and K on are to be chosen to ensure that the variation in DC link voltage is limited within the allowable range for expected levels of variation in onshore frequency. Otherwise, operational limits on DC link voltage would disrupt the proportionality between onshore and offshore frequency variations. The hard limit on onshore DC link voltage reference Von is usually set to ±10% of the rated value. From (3) it is clear that by setting K off K on = 1, it is possible, in principle to exactly replicate the onshore grid frequency variation on the offshore end provided the nominal frequencies are the same which is usually the case. IV. CASE STUDY A case study was carried out on the test system described next using the PowerFactory software. Loading G G Ld1 Fig. 4. 4machine, 2area test system. G1G4 represent conventional generators 2) Scenario II: One conventional plant displaced with an offshore wind farm: The base case described above was modified by replacing a conventional plant (G2) with an offshore wind farm radially connected to bus 6 via ±150 kv bipolar VSC HVDC link with length 100 km, as shown in Fig. 5. The wind farm comprises of 350 aggregated wind turbine generators (WTGs) individually rated at 1.5 MW, 0.69 kv. In steady state, the total wind farm output is 500 MW. The VSC HVDC converters are rated at 550 MVA. When considering the conventional scheme, the grid frequency is communicated from bus 6 to the offshore wind farm controls (see red trace). G1 Ld Ld1 Freq. at bus 6 Pi Qi VSC HVDC Pr Qr Vdci DC Chopper circuit Communication link Vdcr Ld2 AC Feeder (Collector) G4 G WF 3 Grid Freq. <Hz> DFIG (350 X 1.5 MVA) Fig. 5. 4machine, 2area test network with G2 replaced by an equivalent offshore windfarm (showing in blue). Grid frequency is conveyed to the windfarm site through a communication link (conventional scheme). G3 G3
4 4 B. Inertial Response from Wind farms Inertial control for wind s at 11 m/s and 14 m/s The impact of displacing conventional synchronous with wind farms is shown in this section. Fig. 6 (a), (b) compares these cases for two load events (7% and 14% increase in system load). The impact of these two events can be observed in Fig. 6. Synchronous machines inherently contribute to system inertia, whilst without additional control, wind farms do not participate in primary frequency control. Due to the reduction in net system inertia with wind farms, the grid frequency deviates more (first several seconds) from its nominal values. This phenomena is due to the facts that synchronous machine turbines rotate at system frequency with nearly constant rotating, whereas wind turbines are not synchronized to the grid but are controlled to provide maximum active. min. freq. : Hz grid frequency: Hz (without control) grid frequency: Hz (14 m/s) grid frequency: Hz (11m/s) Frequency recovery better with higher wind s Hz min. freq. : Hz Controlled inertial grid frequency: Hz (without WF) Grid frequency variation following 7% increase in load grid frequency: Hz (with WF) Scenario 1: without WF min. freq. : Hz Scenario 2: synch. generator (G2) displaced by an offshore WF min. freq. : Hz Grid frequency variation following 14% increase in load 57.5 grid frequency: Hz (without WF) grid frequency: Hz (with WF) min. freq. : 58.7 Hz min. freq.: 57.8 Hz Fig. 6. Variation in grid frequency when conventional generation (G2) is replaced by an equivalent offshore wind farm connected through HVDC links Fig WF Active Power: MW (14 m/s) WF Active Power: MW (11 m/s) At higher wind s no inertial energy recovery needed Inertial energy recovery Inertial energy recovery at different wind s C. Effect of Latency on Conventional scheme Inertial control from offshore wind farm using remote communication scheme is demonstrated here. Fig. 8. shows that inertial control significantly reduces the deviation of grid frequency from its nominal value by increasing the output of the wind plants by up to a maximum of 10% of the rated turbine. Latency in communicating the grid frequency to the wind farm site could be in the range of 150 to 500 ms in the worst case. Although pessimistic, those high values of latencies were considered to demonstrate the effect of latency on frequency control from remote offshore wind farms. Even with latencies as high as 500 ms the deterioration in performance is found to be very little. The deterioration is caused due to violation of the 10% limit on top of the rated. The wind turbines contribute to primary frequency control by releasing the kinetic energy stored in the rotating mass. The stored kinetic energy is larger at higher wind s. Once the stored energy is exhausted, the wind turbines would have to recover that by producing less than rated which is termed the recovery phase. As shown in Fig. 7, for higher wind of 14 m/s due to larger stored kinetic energy, the recovery phase is almost not there. But for a lower wind of 11 m/s the recovery phase is prominent. Although this has very little influence on the primary frequency control in terms of the maximum deviation in grid frequency from its nominal value, the frequency recovery phase beyond 78 s is affected as shown in Fig. 7. D. Communicationless scheme The primary frequency control with the communicationless scheme is compared against the conventional scheme in Fig. 9. The comparison is made in the backdrop of the frequency variation without any inertial control. For the conventional scheme, a latency of 150 ms (which is pessimistic but possible) is considered in communicating the onshore grid frequency to the remote wind farm site. It can be seen that the performance is quite similar with the two schemes which highlights the fact that it is possible to derive frequency control from remote offshore wind farms without requiring fast and reliable communication. The active output of the wind farm is also shown which is limited within 10% of the wind farm rating of 500
5 5 Fig. 8. Effect of latency on grid frequency with varying latency min. freq. : 8 Hz min. freq.: Hz grid frequency: Hz (no control) grid frequency: Hz (with wind farm) grid frequency: Hz (150ms latency) grid frequency: Hz (500ms latency) WF output Output limited to 10% of WF rating WF Active Power: MW (no latency) WF Active Power: MW (500ms latency) 59.9 With 150 ms latency With 500 ms latency 59.7 no latency 59.5 slight deterioration with larger latency [s] 10 Measured grid frequency: Hz (no latency) Measured grid frequency: Hz (150 ms latency) Measured grid frequency: Hz (500 ms latency) Effect of latency on performance of conventional scheme Comparison of conventional and communicationless schemes grid frequency: Hz (without control) grid frequency: Hz (conventional scheme) grid frequency: Hz (communicationless scheme) WF output WF Active Power: MW (conventional scheme) WF Active Power: MW (communicationless scheme) The variation in DC link voltage at the onshore end for the communicationless scheme is shown in the lower subplot. This is caused due to the frequencyvoltage droop control loop on the onshore converter which reacts to variation in onshore grid frequency. The conventional scheme do not rely on frequencyvoltage droop and hence, the onshore end DC link voltage remains constant. Here we have chosen K on K off =1 and the nominal frequencies on the onshore and offshore ends are the same. Hence, as explained in SectionIIIB, the variation in offshore frequency is almost identical to that of onshore frequency and is therefore, not shown separately. The performance of the communicationless scheme for different values of onshore converter droop coefficient K on is shown in Fig. 10. grid frequency: Hz (Kon = 25) Influence of droop coefficient (Kon) grid frequency: Hz (Kon = 25 with Vdc limits) grid frequency: Hz (Kon = 10) grid frequency: Hz (Kon = 6) DC Link Voltage (onshore converter end) Droop gain 'Kon' = 25 min. voltage: kv 120 Vdc onshore (): kv (Kon = 25) Vdc onshore (): kv (Kon = 25 with Vdc limits) Vdc onshore (): kv (Kon = 10) Vdc onshore (): kv (Kon = 6) min. voltage: kv min. voltage: kv DC link voltage limited min. voltage: 135 kv DC link voltage (onshore end) conventional scheme communicationless scheme 142 Vdc onshore (): kv (conventional scheme) Vdc onshore (): kv (communicationless scheme) Fig. 9. Performance comparison of communicationless scheme against conventional scheme MW. As a result of latency, there is slight violation of this limit for the conventional scheme which causes the frequency deviation to be a little more than the communicationless scheme. Fig. 10. Primary frequency control with communicationless scheme for different values of onshore converter droop coefficient K on As K on is increased from 6 to 25, the dip in grid frequency reduces for an ideal situation with no lower limit on DC link voltage. However in practice, for K on =25, the DC link voltage is clipped at its allowable minimum (from converter modulation index point of view) resulting in significant deviation in grid frequency from its nominal value. Better frequency control (i.e. lesser variation from nominal value) for higher values of K on is due to increased sensitivity of propagation of onshore frequency variation on to the offshore end. However, this is achieved at the expense of larger variation in DC link voltage which is not allowable beyond a certain range (see hard limits on Von in Fig. 2) from cable over voltage and converter modulation index considerations [7].
6 6 V. CONCLUSION A communicationless scheme is demonstrated that allows remote offshore wind farms connected through HVDC links to participate in primary frequency control. Fast and realtime communication of onshore grid frequency is required for the primary frequency control loop of the remote offshore wind farms. Appropriate droop control on the offshore and onshore converters is shown to translate the variation in onshore frequency to an equivalent variation on the offshore end. Thus the need for fast and reliable communication is obviated which ensures reliable operation. Such a communicationless scheme is compared against the conventional approach involving remote communication of onshore grid frequency to the wind farm site. Along side physical and analytical justification, a case study is presented to demonstrate that the communicationless scheme work similar to the conventional one in terms of reducing grid frequency variations. One challenge with the communicationless scheme is it relies on DC link voltage variation as a means of obtaining a offshore frequency variation proportional to that on the onshore side. Depending the chosen droop gains, limits on DC link voltage could disrupt the proportionality between onshore and offshore frequency variations. Further work is necessary to address these issues properly with a more realistic case study. REFERENCES [1] D. Gautam, L. Goel, R. Ayyanar, V. Vittal, and T. Harbour, Control strategy to mitigate the impact of reduced inertia due to doubly fed induction generators on large systems, IEEE Transactions on Power Systems, vol. 26, no. 1, pp , feb [2] N. Miller and P. Marken, Facts on grid friendly wind plants, in Power and Energy Society General Meeting, 2010 IEEE, july 2010, pp [3] G. Lalor, A. Mullane, and M. O Malley, Frequency control and wind turbine technologies, IEEE Transactions on Power Systems, vol. 20, no. 4, pp , [4] J. Morren, S. de Haan, W. Kling, and J. Ferreira, Wind turbines emulating inertia and supporting primary frequency control, IEEE Transactions on Power Systems, vol. 21, no. 1, pp , [5] G. Ramtharan, J. Ekanayake, and N. Jenkins, Frequency support from doubly fed induction generator wind turbines, IET Renewable Power Generation, vol. 1, no. 1, pp. 3 9, [6] J. Ekanayake and N. Jenkins, Comparison of the response of doubly fed and fixed induction generator wind turbines to changes in network frequency, IEEE Transactions on Energy conversion, vol. 19, no. 4, pp , [7] J. Arrillaga, N. Watson, and Y. Liu, Flexible transmission. Wiley Online Library, [8] Z. Miao, L. Fan, D. Osborn, and S. Yuvarajan, Wind farms with hvdc delivery in inertial response and primary frequency control, IEEE Transactions on Energy Conversion, vol. 25, no. 4, pp , [9] L. Fan, Z. Miao, and D. Osborn, Wind farms with hvdc delivery in load frequency control, IEEE Transactions on Power Systems, vol. 24, no. 4, pp , [10] J. MacDowell, K. Clark, N. Miller, and J. SanchezGasca, Validation of ge wind plant models for system planning simulations, in Power and Energy Society General Meeting, 2011 IEEE, july 2011, pp [11] P. Kundur, Power system stability and control, ser. The EPRI system engineering series. New York; London: McGrawHill, 1994.
Wind Farms with HVDC Delivery in Inertia Response and Load Frequency Control
Wind Farms with HVDC Delivery in Inertia Response and Load Frequency Control Zhixin Miao, Senior Member, IEEE, Lingling Fan, Senior Member, IEEE, Dale Osborn, Member, IEEE, Subbaraya Yuvarajan, Senior
More informationAuthors and affiliations. Introduction. Approach
Abstract title Provision of primary frequency support and inertia emulation by offshore wind farms connected through multi-terminal VSC-HVDC links. Authors and affiliations Sotirios Nanou *, Argiris Spetsiotis,
More informationWIND power is likely to replace a significant proportion
1 Inertial Response from Offshore Wind Farms Connected through DC Grids Inmaculada Martínez Sanz, Student Member, IEEE, Balarko Chaudhuri, Senior Member, IEEE, and Goran Strbac, Member, IEEE Abstract Inertial
More informationFast frequency support from wind power plant
Fast frequency support from wind power plant Harshank Agarwal and Zakir Rather Department of Energy Science and Engineering Indian Institute of Technology, Bombay Mumbai, India Abstract Energy penetration
More informationHow Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements
How Full-Converter Wind Turbine Generators Satisfy Interconnection Requirements Robert Nelson Senior Expert Engineering Manager and Manager of Codes, Standards, and Regulations Siemens Wind Turbines -
More informationOffshore AC Grid Management for an AC Integrated VSC-HVDC Scheme with Large WPPs
Offshore AC Grid Management for an AC Integrated VSC-HVDC Scheme with Large WPPs Rakibuzzaman Shah, Member, IEEE, Mike Barnes, Senior Member, IEEE, and Robin Preece, Member, IEEE School of Electrical and
More informationControl of multiple VSC-HVDC converters within an offshore AC-hub
Control of multiple VSC-HVDC converters within an offshore AC-hub Jonathan Stevens, Student Member, IEEE, Daniel Rogers, Member, IEEE, Institute of Energy Cardiff University Cardiff, UK AbstractThe offshore
More informationStudy of Frequency Response in Power System with Renewable Generation and Energy Storage
Study of Frequency Response in Power System with Renewable Generation and Energy Storage Atia Adrees, Member, IEEE and Jovica V. Milanović, Fellow, IEEE School of Electrical and Electronic Engineering
More informationCombined active and reactive power control strategy to improve power system frequency stability with DFIGs
The 6th International Conference on Renewable Power Generation (RPG) 19 20 October 2017 Combined active and reactive power control strategy to improve power system frequency stability with DFIGs Congwei
More informationFacilitating Bulk Wind Power Integration Using LCC HVDC
21, rue d Artois, F-758 PARIS CIGRE US National Committee http : //www.cigre.org 213 Grid of the Future Symposium Facilitating Bulk Wind Power Integration Using LCC HVDC A. HERNANDEZ * R.MAJUMDER W. GALLI
More informationADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS
ADVANCED CONTROLS FOR MITIGATION OF FLICKER USING DOUBLY-FED ASYNCHRONOUS WIND TURBINE-GENERATORS R. A. Walling, K. Clark, N. W. Miller, J. J. Sanchez-Gasca GE Energy USA reigh.walling@ge.com ABSTRACT
More informationFast Frequency Support Control in the GB Power System using VSC-HVDC Technology
Fast Frequency Support Control in the GB Power System using VSC-HVDC Technology Luis Orellana, Víctor Matilla, Sheng Wang, Oluwole D. Adeuyi, and Carlos E. Ugalde-Loo School of Engineering, Cardiff University
More informationCoordinated Control Scheme for Ancillary Services from Offshore Wind Power Plants to AC and DC Grids
Downloaded from orbit.dtu.dk on: Nov 07, 2018 Coordinated Control Scheme for Ancillary Services from Offshore Wind Power Plants to AC and DC Grids Sakamuri, Jayachandra Naidu; Altin, Müfit; Hansen, Anca
More informationAnalysis of the Effectiveness of Grid Codes for Offshore Wind Farms Connected to Onshore Grid via VSC-Based HVDC
Conference of the Wind Power Engineering Community Analysis of the Effectiveness of Grid Codes for Offshore Wind Farms Connected to Onshore Grid via VSC-Based HVDC Moritz Mittelstaedt, Andreas Roehder,.Hendrik
More informationChalmers Publication Library
Chalmers Publication Library Frequency Support by Wind Farms in Islanded Power Systems with High Wind Power Penetration This document has been downloaded from Chalmers Publication Library (CPL). It is
More informationA Fundamental Study of Applying Wind Turbines for Power System Frequency Control
A Fundamental Study of Applying Wind Turbines for Power System Frequency Control CFES Annual Conference February 26, 2015 Felipe Wilches-Bernal and Joe H. Chow Rensselaer Polytechnic Institute 2/26/2015
More informationFrequency Stability Enhancement for Low Inertia Systems using Synthetic Inertia of Wind Power
Downloaded from orbit.u.dk on: Mar 17, 2019 Frequency Stability Enhancement for Low Inertia Systems using Synthetic Inertia of Wind Power Nguyen, Ha Thi; Yang, Guangya; Nielsen, Arne Hejde; Jensen, Peter
More informationMODELLING AND CONTROL OF A VARIABLE-SPEED SWITCHED RELUCTANCE GENERATOR BASED WIND TURBINE
MODELLING AND CONTROL OF A VARIABLE-SPEED SWITCHED RELUCTANCE GENERATOR BASED WIND TURBINE D. McSwiggan (1), L. Xu (1), T. Littler (1) (1) Queen s University Belfast, UK ABSTRACT This paper studies the
More informationEE 742 Chapter 9: Frequency Stability and Control. Fall 2011
EE 742 Chapter 9: Frequency Stability and Control Fall 2011 Meeting demand with generation Large and slow changes (24 hr) in power demand are met by unit commitment Medium and relatively fast changes (30
More informationMULTI-TERMINAL DC (MTDC) grids could form the
Adaptive Droop Control for Effective Power Sharing in Multi-terminal DC (MTDC) Grids Nilanan Ray Chaudhuri, Member, IEEE, and Balarko Chaudhuri, Senior Member, IEEE Abstract Following a converter outage
More informationProvision of Inertial and Primary Frequency Control Services using Offshore Multi-terminal HVDC Networks
1 Provision of Inertial and Primary Frequency Control Services using Offshore Multi-terminal HVDC Networks B. Silva, Student Member, IEEE, C. L. Moreira, L. Seca, Y. Phulpin, and J. A. Peças Lopes, Senior
More informationA generic inertia emulation controller for multi-terminal VSC-HVDC systems
Downloaded from vbn.aau.dk on: marts, 019 Aalborg Universitet A generic inertia emulation controller for multi-terminal VSC-HVDC systems Zhu, Jiebei; Guerrero, Josep M.; Booth, Campbell; Zhang, Haotian;
More informationCOMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)
7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series
More informationELEMENTS OF FACTS CONTROLLERS
1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are
More informationSTUDY OF FREQUENCY RESPONSE IN POWER SYSTEM WITH RENEWABLE GENERATION AND ENERGY STORAGE
STUDY OF FREQUENCY RESPONSE IN POWER SYSTEM WITH RENEWABLE GENERATION AND ENERGY STORAGE Atia Adrees and J. V. Milanović University of Manchester Manchester, UK atia.adrees@manchester.ac.uk, milanovic@manchester.ac.uk
More informationPowerFactory model for multi-terminal HVDC network with DC voltage droop control
Downloaded from orbit.dtu.dk on: Oct 24, 2018 PowerFactory model for multi-terminal HVDC network with DC voltage droop control Korompili, Asimenia; Wu, Qiuwei Publication date: 2014 Document Version Publisher's
More informationSimplified Wind Turbine Model for the Simulation of Frequency Support Mode of Operation
Simplified Wind Turbine Model for the Simulation of Frequency Support Mode of Operation F. D. KANELLOS Hellenic Transmission System Operator Kastoros 72, Piraeus GREECE kanellos@mail.ntua.gr G. J. TSEKOURAS
More informationTransient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme
I J E E E C International Journal of Electrical, Electronics ISSN No. (Online) : 2277-2626 and Computer Engineering 2(1): 7-12(2013) Transient stability improvement by using shunt FACT device (STATCOM)
More informationComparison of the Behaviour of Wind Farms and Conventional Power Stations during Grid Failure Conditions
May 4 Comparison of the Behaviour of Wind Farms and Conventional Power Dr. Martin Janßen APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT Overview Introduction Grid Faults Requirements for Grid Stability Fault
More informationControl of a Three Phase Inverter Mimicking Synchronous Machine with Fault Ridethrough
2017 Ninth Annual IEEE Green Technologies Conference Control of a Three Phase Inverter Mimicking Synchronous Machine with Fault Ridethrough Capability Vikram Roy Chowdhury, Subhajyoti Mukherjee, Pourya
More informationEndorsed Assignments from ERS Framework
ERSTF Completion Endorsed Assignments from ERS Framework Ref Number Title ERS Recommendatio n Ongoing Responsibility 1 Synch Inertia at Interconnection Level Measure 2 Initial Frequency Deviation Measure
More informationA Comprehensive Approach for Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique
A Comprehensive Approach Sub-Synchronous Resonance Screening Analysis Using Frequency scanning Technique Mahmoud Elfayoumy 1, Member, IEEE, and Carlos Grande Moran 2, Senior Member, IEEE Abstract: The
More informationImproved Transient Compensation Using PI-SRF Control Scheme Based UHVDC For Offshore Wind Power Plant
Improved Transient Compensation Using PI-SRF Control Scheme Based UHVDC For Offshore Wind Power Plant Sangeetha M 1, Arivoli R 2, Karthikeyan B 3 1 Assistant Professor, Department of EEE, Imayam College
More informationHarmonizing the Changing Resource Mix Keeping the Grid Together
Harmonizing the Changing Resource Mix Keeping the Grid Together Robert W. Cummings Senior Director of Engineering and Reliability Initiatives i-pcgrid March 30, 2017 NERC-IEEE Memorandum of Understanding
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control
ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections
More informationNew Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage
1 New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage B. B. Pimple, V. Y. Vekhande and B. G. Fernandes Department of Electrical Engineering, Indian Institute of Technology Bombay,
More informationActive Power Sharing and Frequency Control of Multiple Distributed Generators in A Microgrid
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, PP 01-07 www.iosrjournals.org Active Power Sharing and Frequency Control of Multiple Distributed
More informationCombination of Adaptive and Intelligent Load Shedding Techniques for Distribution Network
Combination of Adaptive and Intelligent Load Shedding Techniques for Distribution Network M. Karimi, Student Member, IEEE, H. Mokhlis, Member, IEEE, A. H. A. Bakar, Member, IEEE, J. A. Laghari, A. Shahriari,
More informationHarnessing of wind power in the present era system
International Journal of Scientific & Engineering Research Volume 3, Issue 1, January-2012 1 Harnessing of wind power in the present era system Raghunadha Sastry R, Deepthy N Abstract This paper deals
More informationeach time the Frequency is above 51Hz. Continuous operation is required
GC0101 EXTRACT OF EUROPEAN CONNECTION CONDITIONS LEGAL TEXT DATED 08/01/2018. ECC.6 ECC.6.1 ECC.6.1.1 ECC.6.1.2 ECC.6.1.2.1 ECC.6.1.2.1.1 ECC.6.1.2.1.2 ECC.6.1.2.1.3 TECHNICAL, DESIGN AND OPERATIONAL CRITERIA
More informationLARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS
LARGE-SCALE WIND POWER INTEGRATION, VOLTAGE STABILITY LIMITS AND MODAL ANALYSIS Giuseppe Di Marzio NTNU giuseppe.di.marzio@elkraft.ntnu.no Olav B. Fosso NTNU olav.fosso@elkraft.ntnu.no Kjetil Uhlen SINTEF
More informationReduction of flicker effect in wind power plants with doubly fed machines
Reduction of flicker effect in wind power plants with doubly fed machines J. Bendl, M. Chomat and L. Schreier Institute of Electrical Engineering Academy of Sciences of the Czech Republic Dolejskova 5,
More informationIMPROVED SYNCHRONISM IN DFIG WIND ENERGY CONVERSION SYSTEM USING SMES ENERGY STORAGE
IMPROVED SYNCHRONISM IN DFIG WIND ENERGY CONVERSION SYSTEM USING SMES ENERGY STORAGE 1 PALLAVI DATE, 2 SUJAY KULKARNI, 3 SAKSHI PORJE, 4 JOYDEEP SARKAR 1 Electrical Power System, MCOERC, Nashik 2,3.4 Electrical
More informationCONVERTERS IN POWER VOLTAGE-SOURCED SYSTEMS. Modeling, Control, and Applications IEEE UNIVERSITATSBIBLIOTHEK HANNOVER. Amirnaser Yazdani.
VOLTAGE-SOURCED CONVERTERS IN POWER SYSTEMS Modeling, Control, and Applications Amirnaser Yazdani University of Western Ontario Reza Iravani University of Toronto r TECHNISCHE INFORMATIONSBIBLIOTHEK UNIVERSITATSBIBLIOTHEK
More informationMITIGATION OF VOLTAGE SAG IN A DFIG BASED WIND TURBINE USING DVR
MITIGATION OF VOLTAGE SAG IN A DFIG BASED WIND TURBINE USING DVR M Venmathi*, Soumyadeep Chakraborti 1, Soham Ghosh 2, Abhirup Ray 3, Vidhya Nikam 4 * (Senior Lecturer, Dept. of Electrical and Electronics,
More informationDetermination of Smart Inverter Power Factor Control Settings for Distributed Energy Resources
21, rue d Artois, F-758 PARIS CIGRE US National Committee http : //www.cigre.org 216 Grid of the Future Symposium Determination of Smart Inverter Power Factor Control Settings for Distributed Energy Resources
More informationWind Power Plant Voltage Control Optimization with Embedded Application of Wind Turbines and Statcom
Downloaded from orbit.dtu.dk on: Aug 3, 018 Wind Power Plant Voltage Control Optimization with Embedded Application of Wind Turbines and Statcom Wu, Qiuwei; Solanas, Jose Ignacio Busca; Zhao, Haoran; Kocewiak,
More informationReactive Power Control of DFIG Wind Turbines for Power Oscillation Damping under a Wide Range of Operating Conditions
Reactive Power Control of DFIG Wind Turbines for Power Oscillation Damping under a Wide Range of Operating Conditions Mohamed Edrah, K.L. Lo, Olimpo Anaya-Lara Department of Electrical and Electronic Engineering,
More informationGrid codes and wind farm interconnections CNY Engineering Expo. Syracuse, NY November 13, 2017
Grid codes and wind farm interconnections CNY Engineering Expo Syracuse, NY November 13, 2017 Purposes of grid codes Grid codes are designed to ensure stable operating conditions and to coordinate the
More informationControl of a Back-to-Back VSC from Grid Connection to Islanded Modes in Microgrids
1 Control of a Back-to-Back VSC from Grid Connection to Islanded Modes in Microgrids Ling Xu, Student Member, IEEE, Zhixin Miao, Senior Member, IEEE, and Linglnig Fan, Senior Member, IEEE Abstract VSC
More informationPower Quality enhancement of a distribution line with DSTATCOM
ower Quality enhancement of a distribution line with DSTATCOM Divya arashar 1 Department of Electrical Engineering BSACET Mathura INDIA Aseem Chandel 2 SMIEEE,Deepak arashar 3 Department of Electrical
More informationOpen Access Simulation Toolbox for Wind Power Transmission using High Voltage Direct Current Technology
Open Access Simulation Toolbox for Wind Power Transmission using High Voltage Direct Current Technology Daniel Adeuyi (Cardiff University, Wales) Sheng WANG, Carlos UGALDE-LOO (Cardiff University, Wales);
More informationState-of-the-art review on frequency response of wind power plants in power systems
J. Mod. Power Syst. Clean Energy (2018) 6(1):1 16 https://doi.org/10.1007/s40565-017-0315-y State-of-the-art review on frequency response of wind power plants in power systems Ziping WU 1, Wenzhong GAO
More informationNetwork Code for HVDC Connections and DC-connected Power Park Modules Requirement Outlines
Network Code for HVDC Connections and DC-connected Power Park Modules Requirement Outlines 30 April 2014 Disclaimer: This document is not legally binding. It only aims at clarifying the content of the
More informationSystem for Better Synchronism in DFIG Wind Energy Conversion System Using SMES Energy Storage
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 10, Issue 1 Ver. IV (Jan Feb. 2015), PP 23-29 www.iosrjournals.org System for Better Synchronism
More informationPower System Reliability and Transfer Capability Improvement by VSC- HVDC (HVDC Light )
21, rue d Artois, F-75008 PARIS SECURITY AND RELIABILITY OF ELECTRIC POWER SYSTEMS http : //www.cigre.org CIGRÉ Regional Meeting June 18-20, 2007, Tallinn, Estonia Power System Reliability and Transfer
More informationHarmonic analysis of collection grid in offshore wind installations
Harmonic analysis of collection grid in offshore wind installations Chan Shan Wind Energy Submission date: August 2016 Supervisor: Ole-Morten Midtgård, IEL Co-supervisor: Salvatore D'Arco, SINTEF Energy
More informationLoad Frequency Control of a Multi-area Power System Incorporating Variable-speed Wind Turbines
Load Frequency Control of a Multi-area Power System Incorporating Variable-speed Wind Turbines Semaria Ruiz Alvarez Julián Patiño Jairo Espinosa Universidad Nacional de Colombia, Medellín, Colombia (e-mail:
More informationAvailable online at ScienceDirect. Energy Procedia 53 (2014 ) 86 94
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 53 (2014 ) 86 94 EERA DeepWind 2014, 11th Deep Sea Offshore Wind R&D Conference Dynamic Series Compensation for the Reinforcement
More informationA new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant alternating voltage
21, rue d Artois, F-758 PARIS B4_16_212 CIGRE 212 http : //www.cigre.org A new control scheme for an HVDC transmission link with capacitorcommutated converters having the inverter operating with constant
More informationDevelopment of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine
Development of an Experimental Rig for Doubly-Fed Induction Generator based Wind Turbine T. Neumann, C. Feltes, I. Erlich University Duisburg-Essen Institute of Electrical Power Systems Bismarckstr. 81,
More informationVoltage Stability Improvement of Four Parallel Operated Offshore Wind Turbine Using Fuzzy Controller
2014 IJEDR Volume 2, Issue 1 ISSN: 2321-9939 Voltage Stability Improvement of Four Parallel Operated Offshore Wind Turbine Using Fuzzy Controller 1 R.Balamurugan, 2 R.Punitharaji 1 Student, 2 Assistant
More informationA DC Voltage Control Strategy for MMC MTDC Grids incorporating Multiple Master Stations
A DC Voltage Control Strategy for MMC MTDC Grids incorporating Multiple Master Stations C. E. Spallarossa T. C. Green Imperial College London London, UK claudia.spallarossa10@ic.ac.uk Chang Lin Xueguang
More informationPartial Power Operation of Multi-level Modular Converters under Subsystem Faults
Partial Power Operation of Multi-level Modular Converters under Subsystem Faults Philip Clemow Email: philipclemow@imperialacuk Timothy C Green Email: tgreen@imperialacuk Michael M C Merlin Email: michaelmerlin7@imperialacuk
More informationWind Power Facility Technical Requirements CHANGE HISTORY
CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical
More informationRequirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH
Requirements for Offshore Grid Connections in the Grid of TenneT TSO GmbH Bernecker Straße 70, 95448 Bayreuth Updated: 5th October 2010 1/10 Requirements for Offshore Grid Connections in the Grid of TenneT
More informationDynamic Phasors for Small Signal Stability Analysis
for Small Signal Stability Analysis Chandana Karawita (Transgrid Solutions) for Small Signal Stability Analysis Outline Introduction 1 Introduction Simulation and Analysis Techniques Typical Outputs Modelling
More informationHigh Voltage DC Transmission 2
High Voltage DC Transmission 2 1.0 Introduction Interconnecting HVDC within an AC system requires conversion from AC to DC and inversion from DC to AC. We refer to the circuits which provide conversion
More informationControl and Operation of Multiterminal
Control and Operation of Multiterminal HVDC (MTDC) and its application for offshore wind energy integration in the North Sea Temesgen Haileselassie, Kjetil Uhlen Department of Electrical Power Engineering,
More informationIslanding Detection Method Based On Impedance Measurement
Islanding Detection Method Based On Impedance Measurement Chandra Shekhar Chandrakar 1, Bharti Dewani 2 Department of Electrical and Electronics Engineering Chhattisgarh Swami Vivekananda Technical University
More informationEXCITATION SYSTEM MODELS OF GENERATORS OF BALTI AND EESTI POWER PLANTS
Oil Shale, 2007, Vol. 24, No. 2 Special ISSN 0208-189X pp. 285 295 2007 Estonian Academy Publishers EXCITATION SYSTEM MODELS OF GENERATORS OF BALTI AND EESTI POWER PLANTS R. ATTIKAS *, H.TAMMOJA Department
More informationFUZZY BASED SMART LOAD PRIMARY FREQUENCY CONTROL CONTRIBUTION USING REACTIVE COMPENSATION
FUZZY BASED SMART LOAD PRIMARY FREQUENCY CONTROL CONTRIBUTION USING REACTIVE COMPENSATION G.HARI PRASAD 1, Dr. K.JITHENDRA GOWD 2 1 Student, dept. of Electrical and Electronics Engineering, JNTUA Anantapur,
More informationNew HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations
New HVDC Interaction between AC networks 233 JPE 7-3-6 New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations Chan-Ki Kim, Young-Hun Kwon * and Gil-Soo Jang ** KEPRI,
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements
Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system
More informationFeeder Protection Challenges with High Penetration of Inverter Based Distributed Generation
Feeder Protection Challenges with High Penetration of Inverter Based Distributed Generation Harag Margossian 1, Florin Capitanescu 2, Juergen Sachau 3 Interdisciplinary Centre for Security, Reliability
More informationWind and Solar (PV) Sub harmonic Interactions with Power Systems
I PCGRID Workshop - 2017 Wind and Solar (PV) Sub harmonic Interactions with Power Systems Dr. Krish Narendra Chief Technology Officer ERLPhase Protection, Automation, Control & Smart Grid ERLPhase Power
More informationArvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India
e t International Journal on Emerging Technologies 4(1): 10-16(2013) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Control of Synchronous Generator Excitation and Rotor Angle Stability by
More informationDC-GRID PHYSICAL MODELING PLATFORM DESIGN AND SIMULATION*
-GRID PHYSICAL MODELING PLATFORM DESIGN AND SIMLATION* Minxiao Han 1, Xiaoling Su** 1, Xiao Chen 1, Wenli Yan 1, Zhengkui Zhao 1 State Key Laboratory of Alternate Electrical Power System with Renewable
More informationAlternatives for Primary Frequency Control Contribution from Wind Power Plants Connected to VSC-HVDC Intertie
Downloaded from orbit.dtu.dk on: Dec 20, 2018 Alternatives for Primary Frequency Control Contribution from Wind Power Plants Connected to VSC-HVDC Intertie Laukhamar, Andreas Grøsvik ; Zeni, Lorenzo; Sørensen,
More informationACTIVE POWER CONTROL WITH UNDEAD-BAND VOLTAGE & FREQUENCY DROOP APPLIED TO A MESHED DC GRID TEST SYSTEM
ACTIVE POWER CONTROL WITH UNDEAD-BAND VOLTAGE & FREQUENCY DROOP APPLIED TO A MESHED DC GRID TEST SYSTEM Til Kristian Vrana a, Lorenzo Zeni b, Olav Bjarte Fosso a a Norwegian University of Science and Technology,
More informationRfG Implementation Fault Ride Through
RfG Implementation Fault Ride Through Place your chosen image here. The four corners must just cover the arrow tips. For covers, the three pictures should be the same size and in a straight line. Antony
More informationAnalysis of Hybrid Renewable Energy System using NPC Inverter
Analysis of Hybrid Renewable Energy System using NPC Inverter Reema Manavalan PG Scholar Power Electronics and Drives Anna University reemamanavalan87@gmail.com Abstract: In a variable-speed wind energy
More informationMultilink DC Transmission for Offshore Wind Power Integration
Department of Energy Technology - Pontoppidanstræde Aalborg University, Denmark Multilink DC Transmission for Offshore Wind Power Integration Master thesis - th Semester, 2- Title: Multilink DC Transmission
More informationPak. J. Biotechnol. Vol. 13 (special issue on Innovations in information Embedded and communication Systems) Pp (2016)
COORDINATED CONTROL OF DFIG SYSTEM DURING UNBALANCED GRID VOLTAGE CONDITIONS USING REDUCED ORDER GENERALIZED INTEGRATORS Sudhanandhi, K. 1 and Bharath S 2 Department of EEE, SNS college of Technology,
More informationIntroduction to HVDC in GB. Ian Cowan Simulation Engineer 12 March 2018
Introduction to HVDC in GB Ian Cowan Simulation Engineer 12 March 2018 Contents 1) History of Electricity Networks 2) Overview of HVDC 3) Existing Schemes 4) Future Schemes 5) Regulation and Ownership
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements
Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission
More informationPlanners Perspective on Series Compensated Transmission Lines
TOGETHER WE DELIVER Planners Perspective on Series Compensated Transmission Lines Kenneth A. Donohoo, PE Director, System Planning Distribution and Transmission kenneth.donohoo@oncor.com Oncor Electric
More informationChapter 10: Compensation of Power Transmission Systems
Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome
More informationFault Ride Through Technical Assessment Report Template
Fault Ride Through Technical Assessment Report Template Notes: 1. This template is intended to provide guidelines into the minimum content and scope of the technical studies required to demonstrate compliance
More informationIDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)
IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone
More informationImpact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing Methods
Proceedings of the th WSEAS International Conference on Power Systems, Beijing, China, September -, 200 Impact of Distributed Generation on Voltage Regulation by ULTC Transformer using Various Existing
More informationImpacts of DC Circuit Breakers on AC/DC System Stability Subject to DC Faults
216 International High Voltage Direct Current Conference (HVDC 216) Impacts of DC Circuit Breakers on AC/DC System Stability Subject to DC Faults Gen Li 1, Jun Liang 1, Carlos E Ugalde-Loo 1, Paul Coventry
More informationMasterthesis. Variable Speed Wind Turbine equipped with a Synchronous Generator. by Christian Freitag
Masterthesis Variable Speed Wind Turbine equipped with a Synchronous Generator by Christian Freitag Title: Variable Speed Wind Turbines equipped with a Synchronous Generator Semester: 4 th Semester theme:
More informationTable of Contents Error! Bookmark not defined.
Table of Contents Table of Contents... 1 Introduction... 2 Background... 2 Rationale by Requirement... 204 Requirement 1... 204 Background and Rationale... 204 Requirement 2... 268 Background and Rationale...
More informationAnalysis of Hybrid Renewable Energy System using NPC Inverter
Research Inventy: International Journal Of Engineering And Science Issn: 2278-4721, Vol.2, Issue 7 (March 2013), Pp 26-30 Www.Researchinventy.Com Analysis of Hybrid Renewable Energy System using NPC Inverter
More informationAalborg Universitet. Design and Control of A DC Grid for Offshore Wind Farms Deng, Fujin. Publication date: 2012
Aalborg Universitet Design and Control of A DC Grid for Offshore Wind Farms Deng, Fujin Publication date: 2012 Document Version Publisher's PDF, also known as Version of record Link to publication from
More informationIntegration of Wind Generation into Weak Grids
Integration of Wind Generation into Weak Grids Jason MacDowell GE Energy Consulting NERC ERSTF Atlanta, GA December 10-11, 2014 Outline Conventional and Power Electronic (PE) Sources Stability limitations
More informationWILEY CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION. Qing-Chang Zhong. Tomas Hornik IEEE PRESS
CONTROL OF POWER INVERTERS IN RENEWABLE ENERGY AND SMART GRID INTEGRATION Qing-Chang Zhong The University of Sheffield, UK Tomas Hornik Turbo Power Systems Ltd., UK WILEY A John Wiley & Sons, Ltd., Publication
More informationLOW VOLTAGE RIDE - THROUGH CAPABILITY OF WIND FARMS
Scientific Journal Impact Factor (SJIF): 1.711 e-issn: 2349-9745 p-issn: 2393-8161 International Journal of Modern Trends in Engineering and Research www.ijmter.com LOW VOLTAGE RIDE - THROUGH CAPABILITY
More informationDiscussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation
Discussion on the Deterministic Approaches for Evaluating the Voltage Deviation due to Distributed Generation TSAI-HSIANG CHEN a NIEN-CHE YANG b Department of Electrical Engineering National Taiwan University
More information