Transient Recovery Voltage at Transformer Limited Fault Clearing

Size: px
Start display at page:

Download "Transient Recovery Voltage at Transformer Limited Fault Clearing"

Transcription

1 Transient Recovery Voltage at Transformer Limited Fault Clearing H. Kagawa (Tokyo Electric power Company, Japan) A. Janssen (Liander N.V., the Netherlands) D. Dufounet (Consultant, France) H. Kajino, H. Ito (Mitsubishi Electric Corporation, Japan) 216 CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada 1

2 Contents 1. Background and Introduction 2. TRV for Transformer limited fault (TLF) Voltage drop across the TLF First-pole-to-clear factors for TLF conditions TRV for TLF conditions 3. Transformer models 4. Detailes manufacture transformer models 5. Conclusions 216 CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada 2

3 Background and Introduction Severe Transient Recovery Voltage (TRV) after the current interruption may appear when a fault occurs in the immediate vicinity of a power transformer. These faults are called Transformer Limited Fault (TLF). Kaf: Amplitude factor of TRV, Kaf=Uc/Ep Uc: TRV peak, Ep: voltage peak TRV for TLF conditions TLF may cause higher Rate-of-Rise of TRV (RRRV) than the standard values specified for terminal fault test duties T1 and T3 of IEC and IEEE standard C37.6. TRV parameters, that include the voltage drop across the transformer, the 1st/2nd/3rd pole-to-clear-factors, the amplitude factor, the rate of rise of recovery voltage have been investigated. 216 CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada IUc Ep V 3

4 TRV for TLF HV side CB1 LV side CB2 HV side CB1 LV side CB2 Open Transformer Open Transformer HV side CB1 LV side CB2 HV side CB1 LV side CB2 Transformer Open Transformer secondary faults(tsf) Transformer Open Transformer fed faults(tff) Transformer Limited faults(tlf) The TRV frequency is generally determined by the inductance and the equivalent surge capacitance of the transformer. In such cases, the Rate-of-Rise of TRV (RRRV) may exceed the values specified in the standards for terminal fault test duties T1 and T CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada 4

5 Voltage drop across the transformer Voltage drop ratio of transformer(p.u) UHV primary (1kV) UHV Secondary (5kV) 5kV Primary (5kV) 5kV Secondary (275kV) 275kV Primary (275kV) Voltage drop ratio of transformer in TLF short-circuit current is determined by the back impedance and the impedance of transformer. In the IEC Standard, the voltage drop ratio is.9 in the voltage range from 1 to 8 kv. Japan These values can be given by the ratio of the system impedance to the impedance of transformer. The voltage drops across the transformers are confirmed almost less than CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada 5

6 Pole-to-clear factor[pu] Pole-to-clear factor[pu] First-pole-to-clear factors(kpp) for TLF conditions (1) Third-pole-to-clear factor: Ktp Second-pole-to-clear factor: Ksp First-pole-to-clear factor: Kpp Third-pole-to-clear factor: Ktp Second-pole-to-clear factor: Ksp First-pole-to-clear factor: Kpp Kpp< Kpp< kV/275kV/63kV-15MVA trans. 525kV/242kV/22kV-1MVA trans. 15kV/525kV/147kV-3MVA trans. 7kV/3kV/11.9kV-165MVA trans. 7kV/3kV/11.9kV-51MVA trans X/X1 [pu] Primary side 216 CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada kV/242kV/22kV-1MVA trans. 525kV/275kV/63kV-15MVA trans. 7kV/3kV/11.9kV-51MVA trans. 15kV/525kV/147kV-3MVA trans. 7kV/3kV/11.9kV-165MVA trans X/X1 [pu] Secondary side Typical calculated values of kpp by symmetrical coordinate methods using positive and zero-sequence impedance values for various power transformer used in different projects of the rated voltages from 55kV to 11 kv. Those transformers have a delta connection for a tertiary winding. 6

7 Pole-to-clear factor[pu] Pole-to-clear factor[pu] First-pole-to-clear factors(kpp) for TLF conditions (2) Third-pole-to-clear factor: Ktp Second-pole-to-clear factor: Ksp First-pole-to-clear factor: Kpp Third-pole-to-clear factor: Ktp Second-pole-to-clear factor: Ksp First-pole-to-clear factor: Kpp Kpp< Kpp< kV/275kV/63kV-15MVA trans. 525kV/242kV/22kV-1MVA trans. 15kV/525kV/147kV-3MVA trans. 7kV/3kV/11.9kV-165MVA trans. 7kV/3kV/11.9kV-51MVA trans X/X1 [pu] Primary side The kpp for TLF conditions for a primary side range from 1. to 1.15 and those for a secondary side is lower than.95. The kpp specified in IEC for terminal fault T1 and T3 (i.e. 1.2 for UHV and 1.3 up to 8 kv) are certainly higher than those commonly observed in real cases for TLF conditions kV/242kV/22kV-1MVA trans. 525kV/275kV/63kV-15MVA trans. 7kV/3kV/11.9kV-51MVA trans. 15kV/525kV/147kV-3MVA trans. 7kV/3kV/11.9kV-165MVA trans X/X1 [pu] Secondary side 216 CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada 7

8 TRV for TLF conditions at primary side TRV peak RRRV TRV peak and RRRV calculated with different systems and transformer parameters. The TRV peak can be covered by the specifications in the IEC standard for all cases. The RRRV can be covered by the new recommendation for UHV ratings, but exceed the existing specifications in the IEC standard for 8 kv and 55 kv ratings. 216 CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada 8

9 TRV TLF conditions at secondary side TRV peak RRRV The RRRV at the secondary side exceeds the existing specifications in the IEC standard for 525 kv, 3 kv and 242 kv ratings. The maximum RRRV at the secondary side is calculated as 17. kv/μs for 245 kv transformers for secondary side TFF. 216 CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada 9

10 Transformer models Rated voltage Rated capacity Short-circuit Impedance (measured values, based on 15 MVA) Primary 525 kv / 3 Secondary Tertiary 275 kv / 3 63 kv Primary / Secondary 15 MVA Tertiary 45 MVA Primary - Secondary 13.8 % Primary - Tertiary 7.3 % Secondary - Tertiary 44.8 % 525kV-15 MVA shell-type three-phase transformer Frequency responses were obtained by FRA measurements with 525 kv-15 MVA shell - type power transformer. The same circuit that was used for the TRV measurements was used for the FRA measurements. 216 CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada 1

11 Transformer models(primary side) C1 R1 L1 C1=494 pf, R1=2.89kW,L1=82.1 mh Frequency (Hz) Simplified transformer model Frequency response Primary side The simplified transformer model can be obtained by the response of the FRA measurement. The L 1, C 1, and R 1 values applicable to the simplified transformer model can be evaluated from the slope of the gain and the gain at the resonant points. The impedance response evaluated with the simplified transformer model agreed with the FRA measurement as well. 216 CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada Gain Z (db) Measurement R1=2.89kW L1=82.1 mh 26.4 db 7.9 khz=w1 C1=494 pf Calculation by simplified transformer model

12 Transformer models(secondary side) C1 R1 L1 C2 R2 L2 C1=28482 pf, R1=5.9 kw, L1=13.76 mh C2=2592 pf, R2=1.97 kw, L2= 4.2 mh Simplified transformer model Gain Z (db) Frequency (Hz) Frequency response Secondary side The result of FRA measurement has two resonant frequencies at 8.4 khz and 15.5 khz. It means that the simplified transformer model has a double stack of R-L-C parallel circuit. The impedance response evaluated with the simplified transformer model agreed with the FRA measurement as well Measurement L=L1+L2=17.96 mh L1=13.76 mh, L2= 4.2 mh R1=5.9kW R2=1.97kW 8.4 khz 14.1 db 5.89 db C=1334 pf 15.5 khz C=1/(1/C1+1/C2) C1=28482 pf C2=2592 pf Calculation by simplified transformer model CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada 12

13 Voltage (V) Voltage (V) TRV reproduced by the simplified model 3 15 Measurement Calculation Measurement Calculation Time (ms) Time (ms) Primary side Secondary side The TRV calculated with the simplified transformer model compared with the measurement of the TRV by the capacitor current injection method. The calculated TRV waveforms showed good agreement with the measured TRVs. The simplified transformer model obtained the FRA measurements can reproduce the TRV waveform for TLF conditions very precisely CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada 13

14 TRV reproduced with Manufacturer model CLM u L1 M2 M1 H H M1 M2 L2 U H : Series coil M : Common coil L : Tertiary coil L2 M2 M1 H H M1 M2 L1 DC source Charging resistor capacitor Switch I Diode M1 M2 U u H (CLM1) CLM (CLM2) L1 L2 Cross section of the coil Manufacture transformer model Each group has five separate coils consisting of a pair of primary (H) coils, two pair of secondary (M 1 and M 2 ) coils and two pair of tertiary (L 1 and L 2 ) coils. The capacitance from the tertiary coil to the ground is expressed as C LE, and that between the tertiary coil and secondary coil is expressed as C LM. CLM CLM CLM 216 CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada 14

15 TRV reproduced with Manufacturer model Voltage [V] Calculation Measurement Time [ms] Primary side TRV reproduced by the manufacturer model based on the transformer design shows good agreement with the measurements. TRV was also calculated with the capacitance (C LE ) which is reduced 1/1. Deformation of the TRV is caused by the capacitance between the tertiary winding and the ground. Voltage [V] CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada 5-5 Calculation conditions : x 1/1, Dividing CLM(usingCLM1,CLM2) Calculation Measurement Time [ms] Secondary side 15

16 Conclusion The voltage drop across the transformers in the UHV and EHV network in Japan are confirmed almost less than.9. Kpp for TLF conditions for a primary side ranges from 1. to 1.15 and those for a secondary side ranges from.95 to 1.. TRV for TLF conditions were investigated using different system and transformer parameters. Calculation results shows RRRV exceeds the standard values for T1 and T3 for 8/5kV. TRV waveforms were reproduced by the simplified transformer model and the transformer model based on the design. Calculations results shows good agreement with the measurements. 216 CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada 16

17 Thank you for your kind Attention. 216 CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada 17

18 First-pole-to-clear factors for TLF conditions Kpp : By symmetrical coordinate method Simplified circuit for primary fault Thevenin source E Xs1 Xs S Transformer with delta winding T P 3LG > Positive-sequence reactance Transformer Xs1 Xs Xp CB Simplified circuit for secondary fault CB 3LG S Transformer with delta winding > Positive-sequence reactance Xs Xp T P Thevenin source Xs1 Xs Xs1 E X > Zero-sequence reactance 1 p s s1 Transformer Xs Xs Xp X 1 s p s1 > Zero-sequence reactance Transformer Xs Xp Xs Xt Xt X K pp p Xt ( Xs s X ( X 3X 2X t s 1 ) ) s 216 CIGRE-IEC Colloquium, May 9-11, 216, Montréal, QC, Canada X K pp s Xt ( X p s) X ( X ) 3X 2X t p 1 s 18

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines Presenter Mark McVey C4/B5.41 INTERNATIONAL COUNCIL ON LARGE

More information

DC current interruption tests with HV mechanical DC circuit breaker

DC current interruption tests with HV mechanical DC circuit breaker http: //www.cigre.org CIGRÉ A3/B4-124 CIGRÉ Winnipeg 2017 Colloquium Study Committees A3, B4 & D1 Winnipeg, Canada September 30 October 6, 2017 DC current interruption tests with HV mechanical DC circuit

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Waruna Chandrasena, Bruno Bisewski, and Jeff Carrara Abstract-- This paper describes several system

More information

THREE-PHASE SHORT-CIRCUIT TESTING OF HIGH-VOLTAGE CIRCUIT-BREAKERS USING SYNTHETIC CIRCUITS

THREE-PHASE SHORT-CIRCUIT TESTING OF HIGH-VOLTAGE CIRCUIT-BREAKERS USING SYNTHETIC CIRCUITS Denis DUFOURNET Head of CERDA High Power and High Voltage Laboratories in Villeurbanne, France. Georges MONTILLET Dead Tank Circuit Breakers Product Manager Development, Charleroi, PA USA. Charleston,

More information

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR CIRCUIT BREAKER SF 6 ING. VÁCLAV JEŽEK PROF. ING. ZDENĚK VOSTRACKÝ, DRSC., DR.H.C. Abstract: This article describes the analysis of faults interrupted by generator

More information

Hours / 100 Marks Seat No.

Hours / 100 Marks Seat No. 17323 14115 3 Hours / 100 Seat No. Instructions (1) All Questions are Compulsory. (2) Illustrate your answers with neat sketches wherever necessary. (3) Figures to the right indicate full marks. (4) Assume

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

Question Paper Profile

Question Paper Profile I Scheme Question Paper Profile Program Name : Electrical Engineering Program Group Program Code : EE/EP/EU Semester : Third Course Title : Electrical Circuits Max. Marks : 70 Time: 3 Hrs. Instructions:

More information

TRV OVERVIEW FOR REACTANCE LIMITED FAULTS

TRV OVERVIEW FOR REACTANCE LIMITED FAULTS The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com TRV OVERVIEW FOR REACTANCE

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering) R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between

More information

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:

More information

148 Electric Machines

148 Electric Machines 148 Electric Machines 3.1 The emf per turn for a single-phase 2200/220- V, 50-Hz transformer is approximately 12 V. Calculate (a) the number of primary and secondary turns, and (b) the net cross-sectional

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY Dr. Karthik Reddy VENNA Hong URBANEK Nils ANGER Siemens AG Germany Siemens AG Germany Siemens AG Germany karthikreddy.venna@siemens.com

More information

Revision of TRV Requirements for the Application of Generator Circuit-Breakers

Revision of TRV Requirements for the Application of Generator Circuit-Breakers Revision of TRV Requirements for the Application of Generator Circuit-Breakers M. Palazzo, M. Popov, A. Marmolejo and M. Delfanti Abstract-- The requirements imposed on generator circuitbreakers greatly

More information

(2) New Standard IEEE P (3) Core : (4) Windings :

(2) New Standard IEEE P (3) Core : (4) Windings : (d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.

More information

Effects of Braking Resistor on Circuit Breaker Operations

Effects of Braking Resistor on Circuit Breaker Operations Effects of Braking Resistor on Circuit Breaker Operations Allahverdi Azadrou Department of Electrical Engineering, Salmas Branch, Islamic Azad University, Salmas, Iran Azadrou.elec@gmail.com Abstract This

More information

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24 LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should

More information

Chapter 7 Conclusion 7.1 General

Chapter 7 Conclusion 7.1 General Chapter 7 7.1 General The mechanical integrity of a transformer winding is challenged by several mechanisms. Many dielectric failures in transformers are direct results of reduced mechanical strength due

More information

High-Power Testing of Circuit Breakers

High-Power Testing of Circuit Breakers High-Power Testing of Circuit Breakers Prof. Dr. Rene Smeets KEMA T&D Testing The Netherlands rene.smeets@kema.com IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July 2008 1 categories

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

, ,54 A

, ,54 A AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate

More information

Effects of Harmonic Distortion I

Effects of Harmonic Distortion I Effects of Harmonic Distortion I Harmonic currents produced by nonlinear loads are injected back into the supply systems. These currents can interact adversely with a wide range of power system equipment,

More information

Conventional Paper-II-2011 Part-1A

Conventional Paper-II-2011 Part-1A Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance

More information

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Disclaimer: All information presented in the report, the results and the related computer program, data,

More information

Transient Recovery Voltage Analysis on a Series Power Flow Control Device

Transient Recovery Voltage Analysis on a Series Power Flow Control Device Transient Recovery Voltage Analysis on a Series Power Flow Control Device L. V. Trevisan, G. Cappai, G. Álvarez Cordero Abstract-- In the frame of the Seventh Framework Program, TWENTIES project [1], it

More information

Effects of Transient Recovery Voltages on Circuit Breaker Ratings

Effects of Transient Recovery Voltages on Circuit Breaker Ratings Effects of Transient Recovery Voltages on Circuit Breaker Ratings Term Project: - EE22 - Power System Transients. Spring 28 Instructor: - Dr. Bruce Mork Team: - Himanshu Bahirat Muhammad Ali Praveen KK

More information

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN Effectiveness of Surge Capacitors on Transformer Tertiary connected shunt reactors in preventing failures- Field measurements and comparison with Transient study results Pratap G. Mysore, P.E Pratap Consulting

More information

Analysis of Transient Recovery Voltage in Transmission Lines Compsensated with Tpcs-tcsc Considering Accurate Model of Transformer & Generator

Analysis of Transient Recovery Voltage in Transmission Lines Compsensated with Tpcs-tcsc Considering Accurate Model of Transformer & Generator Australian Journal of Basic and Applied Sciences, 5(5): 816-824, 2011 ISSN 1991-8178 Analysis of Transient Recovery Voltage in Transmission Lines Compsensated with Tpcs-tcsc Considering Accurate Model

More information

Fault Analysis. EE 340 Spring 2012

Fault Analysis. EE 340 Spring 2012 Fault Analysis EE 340 Spring 2012 Introduction A fault in a circuit is any failure that interferes with the normal system operation. Lighting strokes cause most faults on highvoltage transmission lines

More information

GUIDE FOR APPLICATION OF IEC AND IEC

GUIDE FOR APPLICATION OF IEC AND IEC 305 GUIDE FOR APPLICATION OF IEC 67-00 AND IEC 67- PART MAKING AND BREAKING TESTS Working Group A3. October 006 GUIDE FOR APPLICATION OF IEC 67-00 AND IEC 67- PART MAKING AND BREAKING TESTS Working Group

More information

Conventional Paper-II-2013

Conventional Paper-II-2013 1. All parts carry equal marks Conventional Paper-II-013 (a) (d) A 0V DC shunt motor takes 0A at full load running at 500 rpm. The armature resistance is 0.4Ω and shunt field resistance of 176Ω. The machine

More information

2. Current interruption transients

2. Current interruption transients 1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,

More information

Investigation about how to drive a double resonance Tesla coil

Investigation about how to drive a double resonance Tesla coil Investigation about how to drive a double resonance Tesla coil Antonio Carlos M. de Queiroz A double resonance Tesla coil can be designed for optimal efficiency in the way described in http://www.coe.ufrj.br/~acmq/tesla/drsstc.html

More information

Transient Recovery Voltages (TRVs) for High Voltage Circuit Breakers

Transient Recovery Voltages (TRVs) for High Voltage Circuit Breakers Transient Recovery Voltages (TRVs) for High Voltage Circuit Breakers Denis Dufournet IEEE Fellow Chairman IEC TC17 Senior Expert Areva T&D Calgary, October 16 th 2008 Introduction Importance of TRV The

More information

86 chapter 2 Transformers

86 chapter 2 Transformers 86 chapter 2 Transformers Wb 1.2x10 3 0 1/60 2/60 3/60 4/60 5/60 6/60 t (sec) 1.2x10 3 FIGURE P2.2 2.3 A single-phase transformer has 800 turns on the primary winding and 400 turns on the secondary winding.

More information

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of Hz zero sequence continuous voltage S. Nishiwaki, T. Nakamura, Y.Miyazaki Abstract When an one line grounding fault in a transmission

More information

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1 Post: Last Amended on - Page 1 of 6 LOCATION 1 I. TRANSFORMERS AND REACTORS 1. 500 MVA, 765 kv 500 MVA, 400 kv Ratio & Polarity Check Magnetic Balance & Magnetizing Current Measurement at Low Voltage Vector

More information

Chapter 2: Transformers

Chapter 2: Transformers Chapter 2: Transformers 2-1. The secondary winding of a transformer has a terminal voltage of v s (t) = 282.8 sin 377t V. The turns ratio of the transformer is 100:200 (a = 0.50). If the secondary current

More information

IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 50, NO. 5, SEPTEMBER/OCTOBER

IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 50, NO. 5, SEPTEMBER/OCTOBER IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 50, NO. 5, SEPTEMBER/OCTOBER 2014 2989 Circuit Breaker Transient Recovery Voltage Requirements for Medium-Voltage Systems With NRG Rasheek Rifaat, Senior

More information

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 17, NO. 4, OCTOBER 2002 969 Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies Taku Noda, Member, IEEE, Hiroshi Nakamoto,

More information

AP Physics C. Alternating Current. Chapter Problems. Sources of Alternating EMF

AP Physics C. Alternating Current. Chapter Problems. Sources of Alternating EMF AP Physics C Alternating Current Chapter Problems Sources of Alternating EMF 1. A 10 cm diameter loop of wire is oriented perpendicular to a 2.5 T magnetic field. What is the magnetic flux through the

More information

The Advantages and Application of Three Winding Transformers

The Advantages and Application of Three Winding Transformers The Advantages and Application of Three Winding Transformers MSc, CEng, FIEE, FIMechE, FIPENZ Principal, Sinclair Knight Merz Abstract Although seldom used in Australia and New Zealand, three winding transformers

More information

G. KOEPPL Koeppl Power Experts Switzerland

G. KOEPPL Koeppl Power Experts Switzerland PS3: Substation Design: New Solutions and Experiences Bus-Node Substation A Big Improvement in Short-Circuit and Switching Properties at Reduced Substation Costs G. KOEPPL Koeppl Power Experts Switzerland

More information

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions

More information

Medium voltage circuit breaker technical guide

Medium voltage circuit breaker technical guide IEC 56-1987 - ANSI C37-06 1987 COMPARISON CONTENTS page 1 - Rated voltage 3 2 - Rated isolating level 3 3 - Rated voltage during normal running 4 4 - Allowable short time current 4 5 - Allowable current

More information

International Journal of Engineering Technology and Scientific Innovation

International Journal of Engineering Technology and Scientific Innovation EFFECT OF BRAKING RESISTOR AND FAULT CURRENT LIMITER ON CIRCUIT BREAKER OPERATION Amir Ghorbani and Allahverdi Azadru Department of Electrical Engineering, Salmas Branch, Islamic Azad University, Salmas,

More information

Testing and Stabilizing Feedback Loops in Today s Power Supplies

Testing and Stabilizing Feedback Loops in Today s Power Supplies Keywords Venable, frequency response analyzer, impedance, injection transformer, oscillator, feedback loop, Bode Plot, power supply design, open loop transfer function, voltage loop gain, error amplifier,

More information

High Current Amplifier

High Current Amplifier High Current Amplifier - Introduction High Current Amplifier High current amplifier is often a very useful piece of instrument to have in the lab. It is very handy for increasing the current driving capability

More information

MV network design & devices selection EXERCISE BOOK

MV network design & devices selection EXERCISE BOOK MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester

More information

Matz Ohlen Director Transformer Test Systems. Megger Sweden

Matz Ohlen Director Transformer Test Systems. Megger Sweden Matz Ohlen Director Transformer Test Systems Megger Sweden Frequency response analysis of power transformers Measuring and analyzing data as function of frequency, variable frequency diagnostics Impedance

More information

Calsytech, # 38 North Mada Street Nandambakkam, Chennai, Tamil Nadu. Discipline Electro-Technical Calibration Issue Date

Calsytech, # 38 North Mada Street Nandambakkam, Chennai, Tamil Nadu. Discipline Electro-Technical Calibration Issue Date Last Amended on 23.11.2016 Page 1 of 7 SOURCE 1. DC VOLTAGE $ 1mV to 10 mv 10 mv to100 mv 100 mv to1000 V 0.43% to 0.05% 0.05% to 0.01% 0.01% to 0.004% Calibrator, Calibrator by DC VOLTAGE 1mV to 20 mv

More information

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved. Pomona, CA, May 24 & 25, 2016 Tertiary Winding Design in wye-wye Connected Transformers Scope of Presentation > Tertiary vs. Stabilizing Winding? Tertiary vs. Stabilizing Winding? Need for Stabilizing

More information

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg. Aligarh College of Engineering & Technology (College Code: 19) Electrical Engg. (EE-11/21) Unit-I DC Network Theory 1. Distinguish the following terms: (a) Active and passive elements (b) Linearity and

More information

Shunt Reactor Switching

Shunt Reactor Switching Shunt Reactor Switching Dielectric stresses produced by circuit-breakers to shunt reactors. Presentation made during the IEEE Transformers Committee meeting, Amsterdam, Netherlands, April 2001 Presented

More information

A Guide to the DC Decay of Fault Current and X/R Ratios

A Guide to the DC Decay of Fault Current and X/R Ratios A Guide to the DC Decay of Fault Current and X/R Ratios Introduction This guide presents a guide to the theory of DC decay of fault currents and X/R ratios and the calculation of these values in Ipsa.

More information

Ferroresonance Experience in UK: Simulations and Measurements

Ferroresonance Experience in UK: Simulations and Measurements Ferroresonance Experience in UK: Simulations and Measurements Zia Emin BSc MSc PhD AMIEE zia.emin@uk.ngrid.com Yu Kwong Tong PhD CEng MIEE kwong.tong@uk.ngrid.com National Grid Company Kelvin Avenue, Surrey

More information

PROBLEMS. Figure13.74 For Prob Figure13.72 For Prob Figure13.75 For Prob Figure13.73 For Prob Figure13.76 For Prob

PROBLEMS. Figure13.74 For Prob Figure13.72 For Prob Figure13.75 For Prob Figure13.73 For Prob Figure13.76 For Prob CHAPTER 13 Magnetically Coupled Circuits 571 13.9 In order to match a source with internal impedance of 500 to a 15- load, what is needed is: (a) step-up linear transformer (b) step-down linear transformer

More information

DC VACUUM CIRCUIT BREAKER

DC VACUUM CIRCUIT BREAKER DC VACUUM CIRCUIT BREAKER Lars LILJESTRAND Magnus BACKMAN Lars JONSSON ABB Sweden ABB Sweden ABB Sweden lars.liljestrand@se.abb.com magnus.backman@se.abb.com lars.e.jonsson@se.abb.com Marco RIVA ABB Italy

More information

PAPER-II (Subjective)

PAPER-II (Subjective) PAPER-II (Subjective) 1.(A) Choose and write the correct answer from among the four options given in each case for (a) to (j) below: (a) Improved commutation in d.c machines cannot be achieved by (i) Use

More information

Beckwith Electric Co., Inc.

Beckwith Electric Co., Inc. Report ID: PL-26363 REP1 Revision: Issued: 217-8-24 Beckwith Electric Co., Inc. IEEE C37.6 Recloser/Controller Tests The Power of Trust. The Future of Energy. REPORT OF PERFORMANCE CLIENT MANUFACTURER

More information

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad Day 2 - Session IV-A High Voltage 163 Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad B. Kondala Rao, Gopal Gajjar ABB Ltd., Maneja, Vadodara, India Introduction Circuit breakers play

More information

A Study on Ferroresonance Mitigation Techniques for Power Transformer

A Study on Ferroresonance Mitigation Techniques for Power Transformer A Study on Ferroresonance Mitigation Techniques for Power Transformer S. I. Kim, B. C. Sung, S. N. Kim, Y. C. Choi, H. J. Kim Abstract--This paper presents a comprehensive study on the ferroresonance mitigation

More information

DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers

DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers D. Jovcic*, M.H. Hedayati *University of Aberdeen,UK, d.jovcic@abdn.ac.uk University of Aberdeen,UK, mhh@abdn.ac.uk Keywords: High Voltage

More information

Field Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis

Field Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis Field Experience with Sweep Frequency Response Analysis for Power Transformer Diagnosis Ambuj Kumar, Sunil Kumar Singh, Shrikant Singh Abstract Sweep frequency response analysis has been turning out a

More information

Harmonic control devices

Harmonic control devices ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 24 1 Today Harmonic control devices In-line reactors (chokes)

More information

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar.

Technical Report. Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by. Dr. V. R. Kanetkar. Technical Report on Zero Reactive Power Passive Current Harmonic Filter (ZRPPCHF) (In House Case Study) Prepared by Dr. V. R. Kanetkar (February 2015) Shreem Electric Limited (Plot No. 43-46, L. K. Akiwate

More information

Chapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc.

Chapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc. Chapter 30 Inductance, Electromagnetic Oscillations, and AC Circuits 30-7 AC Circuits with AC Source Resistors, capacitors, and inductors have different phase relationships between current and voltage

More information

Voltage Source Converter Modelling

Voltage Source Converter Modelling Voltage Source Converter Modelling Introduction The AC/DC converters in Ipsa represent either voltage source converters (VSC) or line commutated converters (LCC). A single converter component is used to

More information

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels

More information

Code No: R Set No. 1

Code No: R Set No. 1 Code No: R05220204 Set No. 1 II B.Tech II Semester Supplimentary Examinations, Aug/Sep 2007 ELECTRICAL MACHINES-II (Electrical & Electronic Engineering) Time: 3 hours Max Marks: 80 Answer any FIVE Questions

More information

IOCL Electrical Engineering Technical Paper

IOCL Electrical Engineering Technical Paper IOCL Electrical Engineering Technical Paper 1. Which one of the following statements is NOT TRUE for a continuous time causal and stable LTI system? (A) All the poles of the system must lie on the left

More information

Modeling of the behavior of power electronic equipment to grid ripple control signal

Modeling of the behavior of power electronic equipment to grid ripple control signal Modeling of the behavior of power electronic equipment to grid ripple control signal X. Yang, S. Dennetière Abstract The paper presents time domain simulation for power electronic device equivalent impedance

More information

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor Module 2 : Current and Voltage Transformers Lecture 8 : Introduction to VT Objectives In this lecture we will learn the following: Derive the equivalent circuit of a CCVT. Application of CCVT in power

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits

QUESTION BANK ETE (17331) CM/IF. Chapter1: DC Circuits QUESTION BANK ETE (17331) CM/IF Chapter1: DC Circuits Q1. State & explain Ohms law. Also explain concept of series & parallel circuit with the help of diagram. 3M Q2. Find the value of resistor in fig.

More information

PROBLEMS on Transformers

PROBLEMS on Transformers PROBLEMS on Transformers (A) Simple Problems 1. A single-phase, 250-kVA, 11-kV/415-V, 50-Hz transformer has 80 turns on the secondary. Calculate (a) the approximate values of the primary and secondary

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits

Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits 1 Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits M. N. Moschakis, E. A. Leonidaki, Student Member, IEEE, N. D. Hatziargyriou, Senior

More information

5. Black box arc modelling

5. Black box arc modelling 1 5. Black box arc modelling Circuit-breaker s performance in power system is analysed by representing the circuit-breaker characteristics by a function of electrical parameters such as current/voltage,

More information

EN Assignment No.1 - TRANSFORMERS

EN Assignment No.1 - TRANSFORMERS EN-06 - Assignment No.1 - TRANSFORMERS Date : 13 th Jan 01 Q1) A 0kVA 00/0 Volts, 60Hz, single phase transformer is found to have the following equivalent circuit parameter referred to the high potential

More information

Questions Bank of Electrical Circuits

Questions Bank of Electrical Circuits Questions Bank of Electrical Circuits 1. If a 100 resistor and a 60 XL are in series with a 115V applied voltage, what is the circuit impedance? 2. A 50 XC and a 60 resistance are in series across a 110V

More information

Lecture 16 Date: Frequency Response (Contd.)

Lecture 16 Date: Frequency Response (Contd.) Lecture 16 Date: 03.10.2017 Frequency Response (Contd.) Bode Plot (contd.) Bode Plot (contd.) Bode Plot (contd.) not every transfer function has all seven factors. To sketch the Bode plots for a generic

More information

Lecture 4 ECEN 4517/5517

Lecture 4 ECEN 4517/5517 Lecture 4 ECEN 4517/5517 Experiment 3 weeks 2 and 3: interleaved flyback and feedback loop Battery 12 VDC HVDC: 120-200 VDC DC-DC converter Isolated flyback DC-AC inverter H-bridge v ac AC load 120 Vrms

More information

HARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus

HARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus 1592 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005 The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus Ahmed Faheem Zobaa, Senior Member, IEEE Abstract A

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

ELECTRICAL POWER ENGINEERING

ELECTRICAL POWER ENGINEERING Introduction This trainer has been designed to provide students with a fully comprehensive knowledge in Electrical Power Engineering systems. The trainer is composed of a set of modules for the simulation

More information

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India) ISSN: 2349-7637 (Online) RESEARCH HUB International Multidisciplinary Research Journal (RHIMRJ) Research Paper Available online at: www.rhimrj.com Modeling and Simulation of Distribution STATCOM Bhavin

More information

High voltage engineering

High voltage engineering High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency

More information

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit Validation of a Power Transformer Model for Ferroresonance with System Tests on a 4 kv Circuit Charalambos Charalambous 1, Z.D. Wang 1, Jie Li 1, Mark Osborne 2 and Paul Jarman 2 Abstract-- National Grid

More information

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Jules Esztergalyos, Senior Member, IEEE Abstract--The measuring technique described in this paper is based on Electro Magnetic

More information

Vallabh Vidyanagar, Anand, INDIA

Vallabh Vidyanagar, Anand, INDIA IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 1 Ver. V (Feb. 2014), PP 01-06 Interpretation of Sweep Frequency Response Analysis

More information

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation R. S. Al Abri, M. H. Albadi, M. H. Al Abri, U. K. Al Rasbi, M. H. Al Hasni, S. M. Al Shidi Abstract This paper presents an analysis

More information

Title ZnO device and resistor in parallel IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY (2006), 16(2): 65.

Title ZnO device and resistor in parallel IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY (2006), 16(2): 65. Title Current limiting characteristics of ZnO device and resistor in parallel Author(s) Shirai, Y; Morimoto, T; Furushiba, Baba, J; Nitta, T Citation IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY (2006),

More information

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS Shashi Kumar 1, Brajesh Kumar Prajapati 2, Vikramjeet Singh 3 1, 2 Students, Electrical Engineering Department Greater Noida

More information