High-Power Testing of Circuit Breakers

Size: px
Start display at page:

Download "High-Power Testing of Circuit Breakers"

Transcription

1 High-Power Testing of Circuit Breakers Prof. Dr. Rene Smeets KEMA T&D Testing The Netherlands IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July categories of tests development tests type-tests (for certification) acceptance tests IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July

2 1 development tests product development testing of prototypes ordered by: standard: laboratory: manufacturer according clients instructions mostly at manufacturer's site IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July type tests provide confidence that a duly indentified product conforms with requirements of a specific standard ordered by: standard: aim: laboratory: manufacturer (Inter)national standard certification independent testing institute recognised group of manuf. labs IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July

3 3 acceptance tests verify that a certain product complies with a specific application specified by the user ordered by: standard: laboratory: user of the equipment agreement manufacturer - user independent testing institute recognised group of manuf. labs IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July test methods direct testing - on the grid - generator fed - capacitor bank fed synthetic testing IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July

4 direct testing pros laboratory supplied by power grid simple cheap representative high-power available cons poor flexibility difficult to adjust IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July EDF direct testing generator supplied laboratory pros adjustable flexible no influence on local grid con huge investment IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July

5 direct test lay-out slamecka 1966 making switch transformers test object generator master breaker current limiting coils TRV generating circuit current measurement voltage measurement IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July increase of capacity per break GVA / break highest labpower available electra 2003 IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July

6 synthetic testing example: short-circuit test of a CB (three-phase) 420 kv - 63 ka - 50 Hz necessary power: 420 x 63 x 3 = MVA this exceeds any laboratory's direct power (Max: 8400 MVA) other methods must be sought: - single phase test: necessary power 45830/3 = MVA - half-pole testing (if possible): 15277/2 = 7638 MVA this still does not match the power-voltage characteristics of the most powerful labs. IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July solution before interruption a sufficiently large power must be available to maintain the full (arc) current at moderate voltage (< 60 kv) - from generators contact separation reignition arcing time interruption after interruption there is only the need for a sufficiently high voltage - from precharged capacitor short-circuit current transient recovery voltage special circuit needed to reignite the arc IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July synthetic test

7 synthetic tests generator circuit capacitor circuit Lv aux Ls G G Ug Ig TO U TRV TO R C Ii Uh0 + - Ch Ig Ug Ii Ui UTRV IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July synthetic testing Synthetic circuit (parallel current injection) Lv aux Ls G G Ug Ig U TRV TO R C Ii + - Ch Ig+Ii Ui UTRV IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July

8 synthetic testing generator current current through test-cb injected current delayed current zero IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July three-phase synthetic testing first pole to clear last pole to clear last pole to clear IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July

9 synthetic testing in practice test methods: current injection voltage injection ratings to be tested synthetically: 1100 kv - 63 ka - 60 Hz - 1Ø (experimentally) 550 kv - 63 ka - 60 Hz - 1Ø (routine) 245 kv - 63 ka - 60 Hz - 3Ø 2 x cap. bank 720 kv MJ 17 IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July 2008 high-power test of 1100 kv CB test-breaker IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July

10 test station lay-out open-air test site high-power labs synthetic installation (720 kv) switchyard (245 kv) generator building (8400 MVA) new MV test lab (38 kv) on-board transformer testing IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July grey zones in testing Test-circuit should represent the service conditions of equipment as much as possible Standards prescribe inherent behaviour of test-circuits. Inherent means 'naked' circuit only, without test-object. This can be different when a real test-objects interacts with the test-circuit Then, the representation must still be realistic. But: test are possible with test-circuits that show inherently adequate behaviour in accordance with standards, but do not reflect realistic service conditions IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July

11 circuit breaker testing Many arcs in series: high total arc voltage counteracts source voltage (in 800 kv testing: 8 arcs in series) Especially with - synthetic testing (auxiliary breakers) - when testing breakers with multiple arcing chambers Current supply sources must have terminal voltage as high as possible to guarantee sufficient arcing stresses Risk is to apply too little energy into the fault current arc. Testing is too light in that case IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July influence of many series arcs on current arc energy in service situation Source voltage high enough arc energy with 14 kv s ource Source voltage too low amplitude arc voltage current in service situation current in synthetic test IEEE Tutorial on Design and Application of High-Voltage time [ms Circuit ] Breakers July

12 Immediately after interruption Immediately after interruption hot gases are still in the gap and feel fast rising voltage: thermal stresses A little later very high voltage is reached across the open gap: dielectric stresses IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July transient recovery voltage (TRV) Voltage immediately after current interruption (TRV) is of crucial importance for success or failure g e o l ta v t, u ren c short-line fault current terminal fault current interaction interval short-line fault TRV current zero terminal fault TRV circuit breaker arc strongly interacts with TRV circuit test-circuit topology very important microsecond scale time 5 us/div voltage 5 kv/div current 50 A/div time (us) IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July

13 high-frequency effects of circuits Seldomly specified in standards Will affect result of tests in which high-frequency behaviour is important Example: interruption tests with vacuum circuit breaker Such a breaker is very good in interruption of current of high-frequency IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July TRV (pu) re-ignition series damped TRV effect of TRV circuit parallel damped TRV time (us) current at re-ignition (A) 250 series damped + power freq. 150 parallel damped + pow er freq. 50 Research: cable systems have oscillatory TRV, so test should be performed with oscillatory TRV time 20 (us) IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July

14 half-pole tests for (U)HV test voltage application across full-pole half-pole testing quarter-pole testing non-full pole ("unit"-) testing should consider uneven voltage distribution across circuit breaker, especially when there are no grading capacitors full-pole testing eliminates doubts 800 kv breaker IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July half-pole testing of GIS 2U U 2U U 2 U hot exhaust gas from breaker 2 U 2 U Half-pole test: interrupter stress OK internal stress NOK Full-pole test: interrupter stress OK internal stress OK IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July

15 ultra high voltage testing For metal enclosed breakers, half-pole testing does not represent the conditions in service: dielectric stresses of half-pole tests equivalent to full-pole conditions - between phases - between phases and enclosure effects of exhaust gases equivalent mechanical stresses equivalent forces (electrodynamical stresses) equivalent IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July single phase testing of threephase circuit breaker Often practiced when power of test laboratory is insufficient In principle possible, but with care Not realistic when common mechanism is controlling contact movement (circuit breaker, earthing switch) Beware of three-phase interactions, that single phase circuits fail to represent IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July

16 three-phase testing of three-phase devices contact separation recovery voltage current three-phase test contact movement single-phase test contact movement voltage: 80 kv/div current: 111kA/div time: 10 ms/div no-load contact movement IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July conclusions Standards do not cover everything Grey zone exists between allowable but different stresses that make life easier/worse for a breaker Test-engineers knowledge and test-lab policies must ensure that realistic testing will prevail: - supply sufficient arc energy even for highest voltages - have knowledge of arc-circuit interactions - being aware of high-frequency pitfalls - test three-phase when necessary IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July

DEVELOPMENTS IN EHV/UHV CIRCUIT BREAKER TESTING

DEVELOPMENTS IN EHV/UHV CIRCUIT BREAKER TESTING DEVELOPMENTS IN EHV/HV CIRCIT BREAKER TESTING ABSTRACT R.P.P. Smeets, A.B. Hofstee, M. Dekker DNV GL, KEMA Laboratories trechtseweg 310, 6812 AR Arnhem, the Netherlands rene.smeets@dnvgl.com Nowadays,

More information

THREE-PHASE SHORT-CIRCUIT TESTING OF HIGH-VOLTAGE CIRCUIT-BREAKERS USING SYNTHETIC CIRCUITS

THREE-PHASE SHORT-CIRCUIT TESTING OF HIGH-VOLTAGE CIRCUIT-BREAKERS USING SYNTHETIC CIRCUITS Denis DUFOURNET Head of CERDA High Power and High Voltage Laboratories in Villeurbanne, France. Georges MONTILLET Dead Tank Circuit Breakers Product Manager Development, Charleroi, PA USA. Charleston,

More information

Shunt Reactor Switching

Shunt Reactor Switching Shunt Reactor Switching Dielectric stresses produced by circuit-breakers to shunt reactors. Presentation made during the IEEE Transformers Committee meeting, Amsterdam, Netherlands, April 2001 Presented

More information

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR CIRCUIT BREAKER SF 6 ING. VÁCLAV JEŽEK PROF. ING. ZDENĚK VOSTRACKÝ, DRSC., DR.H.C. Abstract: This article describes the analysis of faults interrupted by generator

More information

DC current interruption tests with HV mechanical DC circuit breaker

DC current interruption tests with HV mechanical DC circuit breaker http: //www.cigre.org CIGRÉ A3/B4-124 CIGRÉ Winnipeg 2017 Colloquium Study Committees A3, B4 & D1 Winnipeg, Canada September 30 October 6, 2017 DC current interruption tests with HV mechanical DC circuit

More information

Copyright 2008 IEEE.

Copyright 2008 IEEE. Copyright 2008 IEEE. Paper presented at IEEE PES 2008 T&D Chicago meeting, Apr. 21 24, 2008 This material is posted here with permission of the IEEE. Such permission of the IEEE does not in any way imply

More information

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad Day 2 - Session IV-A High Voltage 163 Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad B. Kondala Rao, Gopal Gajjar ABB Ltd., Maneja, Vadodara, India Introduction Circuit breakers play

More information

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY Dr. Karthik Reddy VENNA Hong URBANEK Nils ANGER Siemens AG Germany Siemens AG Germany Siemens AG Germany karthikreddy.venna@siemens.com

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS Shashi Kumar 1, Brajesh Kumar Prajapati 2, Vikramjeet Singh 3 1, 2 Students, Electrical Engineering Department Greater Noida

More information

Transient Recovery Voltage at Transformer Limited Fault Clearing

Transient Recovery Voltage at Transformer Limited Fault Clearing Transient Recovery Voltage at Transformer Limited Fault Clearing H. Kagawa (Tokyo Electric power Company, Japan) A. Janssen (Liander N.V., the Netherlands) D. Dufounet (Consultant, France) H. Kajino, H.

More information

TRV OVERVIEW FOR REACTANCE LIMITED FAULTS

TRV OVERVIEW FOR REACTANCE LIMITED FAULTS The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com TRV OVERVIEW FOR REACTANCE

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi

More information

2. Current interruption transients

2. Current interruption transients 1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,

More information

Interrupting Phenomena of High-Voltage

Interrupting Phenomena of High-Voltage Interrupting Phenomena of High-Voltage 3 Circuit Breaker Hiroki Ito and Denis Dufournet Contents 3.1 Introduction... 63 3.2 Definitions of Terminology... 64 3.3 Abbreviations... 67 3.4 Fundamental Interrupting

More information

Stress Analysis of HVDC Circuit Breakers for Defining Test Requirements and its Implementation

Stress Analysis of HVDC Circuit Breakers for Defining Test Requirements and its Implementation http: //www.cigre.org CIGRÉ A3/B4-009 CIGRÉ Winnipeg 2017 Colloquium Study Committees A3, B4 & D1 Winnipeg, Canada September 30 October 6, 2017 Stress Analysis of HVDC Circuit Breakers for Defining Test

More information

Medium voltage circuit breaker technical guide

Medium voltage circuit breaker technical guide IEC 56-1987 - ANSI C37-06 1987 COMPARISON CONTENTS page 1 - Rated voltage 3 2 - Rated isolating level 3 3 - Rated voltage during normal running 4 4 - Allowable short time current 4 5 - Allowable current

More information

The testing of generator circuit-breakers

The testing of generator circuit-breakers The testing of generator circuit-breakers Smeets, R.P.P.; Linden, van der, W.A. Published in: EEE Transactions on Power Delivery DO: 10.1109/61.714483 Published: 01/01/1998 Document Version Publisher s

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

G. KOEPPL Koeppl Power Experts Switzerland

G. KOEPPL Koeppl Power Experts Switzerland PS3: Substation Design: New Solutions and Experiences Bus-Node Substation A Big Improvement in Short-Circuit and Switching Properties at Reduced Substation Costs G. KOEPPL Koeppl Power Experts Switzerland

More information

DC VACUUM CIRCUIT BREAKER

DC VACUUM CIRCUIT BREAKER DC VACUUM CIRCUIT BREAKER Lars LILJESTRAND Magnus BACKMAN Lars JONSSON ABB Sweden ABB Sweden ABB Sweden lars.liljestrand@se.abb.com magnus.backman@se.abb.com lars.e.jonsson@se.abb.com Marco RIVA ABB Italy

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 62271-100 Edition 1.1 2003-05 Edition 1:2001 consolidated with amendment 1:2002 High-voltage switchgear and controlgear Part 100: High-voltage alternating-current circuit-breakers

More information

Weidong Zhang, May.9, 2016 Development of Pre-Insertion Resistor for an 800kV GIS Circuit Breaker. ABB Group May 11, 2016 Slide 1

Weidong Zhang, May.9, 2016 Development of Pre-Insertion Resistor for an 800kV GIS Circuit Breaker. ABB Group May 11, 2016 Slide 1 Weidong Zhang, May.9, 2016 Development of Pre-Insertion Resistor for an 800kV GIS Circuit Breaker Group Slide 1 Background & Objects EHV/UHV system: Widely application for long distance transmission from

More information

This is a preview - click here to buy the full publication

This is a preview - click here to buy the full publication CONSOLIDATED VERSION IEC TR 62271-306 Edition 1.1 2018-08 colour inside High-voltage switchgear and controlgear Part 306: Guide to IEC 62271-100, IEC 62271-1 and other IEC standards related to alternating

More information

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES 21, rue d'artois, F-75008 Paris http://www.cigre.org A3-308 Session 2004 CIGRÉ HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES G.E. Agafonov, I.V. Babkin, B.E. Berlin Y. F. Kaminsky, S. V. Tretiakov,

More information

DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers

DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers D. Jovcic*, M.H. Hedayati *University of Aberdeen,UK, d.jovcic@abdn.ac.uk University of Aberdeen,UK, mhh@abdn.ac.uk Keywords: High Voltage

More information

GUIDE FOR APPLICATION OF IEC AND IEC

GUIDE FOR APPLICATION OF IEC AND IEC 305 GUIDE FOR APPLICATION OF IEC 67-00 AND IEC 67- PART MAKING AND BREAKING TESTS Working Group A3. October 006 GUIDE FOR APPLICATION OF IEC 67-00 AND IEC 67- PART MAKING AND BREAKING TESTS Working Group

More information

Modelling of Restriking and Reignition Phenomena in Three-phase Capacitor and Shunt Reactor Switching

Modelling of Restriking and Reignition Phenomena in Three-phase Capacitor and Shunt Reactor Switching Modelling of Restriking and Reignition Phenomena in Three-phase Capacitor and Shunt Reactor Switching Shui-cheong Kam School of Engineering Systems Queensland University of Technology Brisbane, Australia

More information

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment

Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Alternative Coupling Method for Immunity Testing of Power Grid Protection Equipment Christian Suttner*, Stefan Tenbohlen Institute of Power Transmission and High Voltage Technology (IEH), University of

More information

FUNCTIONS OF CIRCUIT BREAKERS

FUNCTIONS OF CIRCUIT BREAKERS FUNCTIONS OF CIRCUIT BREAKERS Circuit breakers are designed to carry out the following functions: 1. They must be capable of closing on and carrying full-load currents at rated power factors continuously.

More information

5. Black box arc modelling

5. Black box arc modelling 1 5. Black box arc modelling Circuit-breaker s performance in power system is analysed by representing the circuit-breaker characteristics by a function of electrical parameters such as current/voltage,

More information

In power system, transients have bad impact on its

In power system, transients have bad impact on its Analysis and Mitigation of Shunt Capacitor Bank Switching Transients on 132 kv Grid Station, Qasimabad Hyderabad SUNNY KATYARA*, ASHFAQUE AHMED HASHMANI**, AND BHAWANI SHANKAR CHOWDHRY*** RECEIVED ON 1811.2014

More information

Documents and Addresses

Documents and Addresses Report No.: 14-041-MS Sheet: 2 Documents and Addresses Accreditation The Prüffeld der Schaltwerke, Berlin has been approved by the DAkkS (German accreditation body) according to EN ISO/IEC 17025 for tests

More information

POWER SYSTEM TRANSIENTS - Switching Overvoltages in Power Systems - Juan A. Martinez-Velasco, Jacinto Martin-Arnedo

POWER SYSTEM TRANSIENTS - Switching Overvoltages in Power Systems - Juan A. Martinez-Velasco, Jacinto Martin-Arnedo SWITCHING OVERVOLTAGES IN POWER SYSTEMS Juan A. Martinez-Velasco Universitat Politècnica de Catalunya, Barcelona, Spain Jacinto Martin-Arnedo Estabanell Energía, Granollers, Spain Keywords: Switching overvoltages,

More information

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS Introduction Where fuses are unsuitable or inadequate, protective relays and circuit breakers are used in combination to detect and isolate faults. Circuit breakers

More information

A Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks

A Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks A Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks C. D. TSIREKIS Hellenic Transmission System Operator Kastoros 72, Piraeus GREECE

More information

Current Interruption Phenomena in HV Disconnectors with High-Speed Opening Auxiliary Contacts

Current Interruption Phenomena in HV Disconnectors with High-Speed Opening Auxiliary Contacts 1 Current Interruption Phenomena in HV Disconnectors with High-Speed Opening Auxiliary Contacts Y. Chai, P.A.A.F. Wouters, S. Kuivenhoven, P. van der Wal, M. Vanis, R.P.P. Smeets, Fellow, IEEE Abstract--High-speed

More information

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Waruna Chandrasena, Bruno Bisewski, and Jeff Carrara Abstract-- This paper describes several system

More information

Effects of Transient Recovery Voltages on Circuit Breaker Ratings

Effects of Transient Recovery Voltages on Circuit Breaker Ratings Effects of Transient Recovery Voltages on Circuit Breaker Ratings Term Project: - EE22 - Power System Transients. Spring 28 Instructor: - Dr. Bruce Mork Team: - Himanshu Bahirat Muhammad Ali Praveen KK

More information

Power Quality and Reliablity Centre

Power Quality and Reliablity Centre Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview

More information

Substation Preventive Maintenance

Substation Preventive Maintenance Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS

More information

AC High-Voltage Circuit Breakers

AC High-Voltage Circuit Breakers AC High-Voltage Circuit Breakers Everything you wanted to know about ac highvoltage circuit breakers but were afraid to ask IEEE Switchgear Committee Portland (Maine, USA), October 2017 Denis Dufournet

More information

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines Presenter Mark McVey C4/B5.41 INTERNATIONAL COUNCIL ON LARGE

More information

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems T. C. Dias, B. D. Bonatto, J. M. C. Filho Abstract-- Isolated industrial power systems or with high selfgeneration,

More information

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009 Nkosinathi Buthelezi Senior Consultant: Power Transformers and Reactors Presentation Content Standardization of Power

More information

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN Effectiveness of Surge Capacitors on Transformer Tertiary connected shunt reactors in preventing failures- Field measurements and comparison with Transient study results Pratap G. Mysore, P.E Pratap Consulting

More information

Switching Induced Transients:

Switching Induced Transients: Switching Induced Transients: Transformer switching is the most commonly performed operation in any power delivery system and most of the times this operation can be performed without any undesirable consequences.

More information

System grounding of wind farm medium voltage cable grids

System grounding of wind farm medium voltage cable grids Downloaded from orbit.dtu.dk on: Apr 23, 2018 System grounding of wind farm medium voltage cable grids Hansen, Peter; Østergaard, Jacob; Christiansen, Jan S. Published in: NWPC 2007 Publication date: 2007

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD This is a preview - click here to buy the full publication INTERNATIONAL STANDARD IEC/IEEE 62271-37-013 Edition 1.0 2015-10 colour inside High-voltage switchgear and controlgear Part 37-013: Alternating-current

More information

High voltage engineering

High voltage engineering High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency

More information

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC DATA SHEET No. 1 December 2000 Issued by the French Lightning Protection Association Precautions to be considered for use of surge arresters tested according to Class 1 of IEC 61643-1 Foreword: The protection

More information

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers Disclaimer: All information presented in the report, the results and the related computer program, data,

More information

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral

More information

CURRENT interrupting tests constitute an important part. Medium Voltage Laboratory for Load Break Switch Development. Erik Jonsson and Magne Runde

CURRENT interrupting tests constitute an important part. Medium Voltage Laboratory for Load Break Switch Development. Erik Jonsson and Magne Runde 1 Medium Laboratory for Load Break Switch Development Erik Jonsson and Magne Runde Abstract A new, directly powered laboratory for studying current interruption in medium voltage load break switches has

More information

Revision of TRV Requirements for the Application of Generator Circuit-Breakers

Revision of TRV Requirements for the Application of Generator Circuit-Breakers Revision of TRV Requirements for the Application of Generator Circuit-Breakers M. Palazzo, M. Popov, A. Marmolejo and M. Delfanti Abstract-- The requirements imposed on generator circuitbreakers greatly

More information

Standards for MV switchgear rated for arc flash protection

Standards for MV switchgear rated for arc flash protection Standards for MV switchgear rated for arc flash protection by Bryan Johnson, ABB Switchgear standards historically considered the electrical capability of switchgear with little regard to the effects of

More information

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids Tarik Abdulahović #, Torbjörn Thiringer # # Division of Electric Power Engineering, Department of Energy

More information

HIGH VOLTAGE CIRCUIT BREAKERS

HIGH VOLTAGE CIRCUIT BREAKERS HIGH VOLTAGE CIRCUIT BREAKERS Design and Applications Second Edition, Revised and Expanded RUBEN D. GARZON Square D Co. Smyrna, Tennessee MARCEL Ш D E К К E R MARCEL DEKKER, INC. NEW YORK BASEL CONTENTS

More information

D6.2 Develop system level model for mechanical DCCB

D6.2 Develop system level model for mechanical DCCB D6.2 Develop system level model for mechanical DCCB PROMOTioN Progress on Meshed HVDC Offshore Transmission Networks Mail info@promotion-offshore.net Web www.promotion-offshore.net This result is part

More information

(2) New Standard IEEE P (3) Core : (4) Windings :

(2) New Standard IEEE P (3) Core : (4) Windings : (d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.

More information

Beckwith Electric Co., Inc.

Beckwith Electric Co., Inc. Report ID: PL-26363 REP1 Revision: Issued: 217-8-24 Beckwith Electric Co., Inc. IEEE C37.6 Recloser/Controller Tests The Power of Trust. The Future of Energy. REPORT OF PERFORMANCE CLIENT MANUFACTURER

More information

GPS Synchronized high voltage measuring system

GPS Synchronized high voltage measuring system Synchronized high voltage measuring system Leif S. Christensen 1), Morten J. Ulletved 1) Poul Sørensen 2), Troels Sørensen 3), Torben Olsen 4), Henny K. Nielsen 4) 1) DELTA Dansk Elektronik, Lys & Akustik,

More information

Transient Recovery Voltage at Series Compensated Transmission Lines in Piauí, Brazil

Transient Recovery Voltage at Series Compensated Transmission Lines in Piauí, Brazil Transient Recovery Voltage at Series Compensated Transmission Lines in Piauí, Brazil S. Henschel L. Kirschner M.C. Lima Abstract As a part of ongoing 500 kv power transmission enhancements in Brazil, several

More information

FACTORY AND FIELD VERIFICATION TESTS OF CONTROLLED SWITCHING SYSTEM

FACTORY AND FIELD VERIFICATION TESTS OF CONTROLLED SWITCHING SYSTEM FACTORY AND FIELD VERIFICATION TESTS OF CONTROLLED SWITCHING SYSTEM by H. Ito, H. Tsutada, H. Kohyama, H. Yamamoto Mitsubishi Electric Corp. H. Wilson, S. Billings Mitsubishi Electric Power Products, Inc.

More information

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer PART 1: GENERAL 1.01 Transformer A. This section includes liquid filled, pad mounted distribution transformers with primary voltage of 12kV or 4.16kV (The University will determine primary voltage), with

More information

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) 012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION) CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 8051 Fax: +94 11 232 5387 CONTENTS Page 1.0

More information

Although shunt capacitors

Although shunt capacitors INSIDE PQ The Trouble With Capacitors Part 1 Switching capacitors seems like a simple proposition, but it can lead to some very interesting problems By R. Fehr, P.E., Engineering Consultant Although shunt

More information

LOVAG GENERAL INSTRUCTION G2 MEASUREMENT UNCERTAINTY. This instruction of a general nature and does not relate to specific standards.

LOVAG GENERAL INSTRUCTION G2 MEASUREMENT UNCERTAINTY. This instruction of a general nature and does not relate to specific standards. LTI-G2 LOVAG GENERAL INSTRUCTION G2 MEASUREMENT UNCERTAINTY This instruction of a general nature and does not relate to specific standards. It provides additional information ensuring a suitable degree

More information

CO 2 Circuit Breaker Arc Model for EMTP Simulation of SLF Interrupting Performance

CO 2 Circuit Breaker Arc Model for EMTP Simulation of SLF Interrupting Performance CO Circuit Breaker Arc Model for EMTP Simulation of SLF Interrupting Performance K. Udagawa, T. Koshizuka, T. Uchii, T. Shinkai, H. Kawano Abstract-- This paper presents a CO circuit breaker arc model

More information

Analysis of Transient Recovery Voltage in Transmission Lines Compsensated with Tpcs-tcsc Considering Accurate Model of Transformer & Generator

Analysis of Transient Recovery Voltage in Transmission Lines Compsensated with Tpcs-tcsc Considering Accurate Model of Transformer & Generator Australian Journal of Basic and Applied Sciences, 5(5): 816-824, 2011 ISSN 1991-8178 Analysis of Transient Recovery Voltage in Transmission Lines Compsensated with Tpcs-tcsc Considering Accurate Model

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

TS RES - OUTSTANDING ISSUES

TS RES - OUTSTANDING ISSUES TS RES - OUTSTANDING ISSUES This document has been officially issued as DRAFT until the following outstanding issues have been resolved. At that time the document will be officially reissued as the next

More information

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event

More information

Fundamental Concepts of Dynamic Reactive Compensation. Outline

Fundamental Concepts of Dynamic Reactive Compensation. Outline 1 Fundamental Concepts of Dynamic Reactive Compensation and HVDC Transmission Brian K. Johnson University of Idaho b.k.johnson@ieee.org 2 Outline Objectives for this panel session Introduce Basic Concepts

More information

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION David TOPOLANEK Petr TOMAN Michal PTACEK Jaromir DVORAK Brno University of Technology - Czech

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

MATEFU Insulation co-ordination and high voltage testing of fusion magnets

MATEFU Insulation co-ordination and high voltage testing of fusion magnets Stefan Fink: MATEFU Insulation co-ordination and high voltage testing of fusion magnets Le Chateau CEA Cadarache, France April 7th, 29 Insulation co-ordination Some principle considerations of HV testing

More information

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8] Code No: RR320205 Set No. 1 1. (a) Explain about Bewley s Lattice diagrams and also mention the uses of these diagrams. [6+2] (b) A line of surge impedance of 400 ohms is charged from a battery of constant

More information

Contents. Reignition and Restrikes. Reactor Switching. Normal and Abnormal Transients. Normal and Abnormal Transients Reignition.

Contents. Reignition and Restrikes. Reactor Switching. Normal and Abnormal Transients. Normal and Abnormal Transients Reignition. Contents Reignition and Restrikes By :- Himanshu Bahirat EE5 : Power System Transients Date:- February, Normal and Abnormal Transients Reignition Reactor Switching Restrike Capacitor switching Three phase

More information

Transformer Factory Testing

Transformer Factory Testing Transformer Factory Testing John J. Foschia Test Engineer John.Foschia@spx.com September 2018 Reasons for Testing Compliance with user specifications Assessment of quality and reliability Verification

More information

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström EH27401 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsn@ics.kth.se 1 Course map 2 Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids

More information

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N S C I E N C E P A S S I O N T E C H N O L O G Y HVDC Transmission Michael Muhr Graz University of Technology Austria www.tugraz.at 1 Definition HV High Voltage AC Voltage > 60kV 220kV DC Voltage > 60kV

More information

IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 50, NO. 5, SEPTEMBER/OCTOBER

IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 50, NO. 5, SEPTEMBER/OCTOBER IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 50, NO. 5, SEPTEMBER/OCTOBER 2014 2989 Circuit Breaker Transient Recovery Voltage Requirements for Medium-Voltage Systems With NRG Rasheek Rifaat, Senior

More information

Real Time Monitoring of SF6 Gas Pressure for Optimization Point on Wave Switching of SF6 Circuit Breaker

Real Time Monitoring of SF6 Gas Pressure for Optimization Point on Wave Switching of SF6 Circuit Breaker Real Time Monitoring of SF6 Gas Pressure for Optimization Point on Wave Switching of SF6 Circuit Breaker Ashish Maheshwari 1, Sunil Kumar Singla 2 1 PG Scholar, EIE Department, Thapar University Patiala,

More information

Comparison of the Behaviour of Wind Farms and Conventional Power Stations during Grid Failure Conditions

Comparison of the Behaviour of Wind Farms and Conventional Power Stations during Grid Failure Conditions May 4 Comparison of the Behaviour of Wind Farms and Conventional Power Dr. Martin Janßen APCG / 4MJA5_Wind-Farms-IEEE_13-5-4_EN.PPT Overview Introduction Grid Faults Requirements for Grid Stability Fault

More information

A SEMINAR REPORT PRESENT ON AIR BLAST CIRCUIT BREAKER

A SEMINAR REPORT PRESENT ON AIR BLAST CIRCUIT BREAKER A SEMINAR REPORT PRESENT ON AIR BLAST CIRCUIT BREAKER Submitted by :- submitted to:- Tazinder singh E.E. 3 rd year (BBDNIIT) 1 Acknowledgement 2 content Topic Page no. Air blast circuit breaker 04 Principle

More information

Cahier technique no. 193

Cahier technique no. 193 Collection Technique... Cahier technique no. 193 MV breaking techniques S. Théoleyre "Cahiers Techniques" is a collection of documents intended for engineers and technicians, people in the industry who

More information

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH Giuseppe Cappai, Bernhard Heinrich, Giuseppe Simioli, Leonardo Trevisan Weidmann Electrical Technology AG, Switzerland Abstract: A large solar

More information

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Romeo C. Ciobanu, Cristina Schreiner, Ramona Burlacu, Cristina Bratescu Technical

More information

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering

More information

DEVELOPMENT OF A TEST PROTOCOL FOR A 15 KV CLASS SOLID-STATE CURRENT LIMITER

DEVELOPMENT OF A TEST PROTOCOL FOR A 15 KV CLASS SOLID-STATE CURRENT LIMITER DEVELOPMENT OF A TEST PROTOCOL FOR A 15 KV CLASS SOLID-STATE CURRENT LIMITER ABSTRACT Ashok Sundaram Electric Power Research Inc., USA asundara@epri.com The Solid-state Fault Current Limiter (SSFCL) is

More information

Load Current Interruption in Air for Medium Voltage Ratings

Load Current Interruption in Air for Medium Voltage Ratings Erik Jonsson Load Current Interruption in Air for Medium Voltage Ratings Thesis for the degree of Philosophiae Doctor Trondheim, March 2014 Norwegian University of Science and Technology Faculty of Information

More information

AIR LOAD BREAK SWITCH DESIGN PARAMETERS

AIR LOAD BREAK SWITCH DESIGN PARAMETERS Nina Sasaki Støa-Aanensen AIR LOAD BREAK SWITCH DESIGN PARAMETERS Thesis for the degree of Philosophiae Doctor Trondheim, October 2015 Norwegian University of Science and Technology Faculty of Information

More information

FAULT CURRENT LIMITER SURGE PROTECTION DEVICE FOR THE POWER GRID BASED UPON ZERO POWER CONSUMPTION CERAMIC FERRITE PERMANENT MAGNETS

FAULT CURRENT LIMITER SURGE PROTECTION DEVICE FOR THE POWER GRID BASED UPON ZERO POWER CONSUMPTION CERAMIC FERRITE PERMANENT MAGNETS FAULT CURRENT LIMITER SURGE PROTECTION DEVICE FOR THE POWER GRID BASED UPON ZERO POWER CONSUMPTION CERAMIC FERRITE PERMANENT MAGNETS Jeremy HALL Wolfson Centre for Magnetics, Cardiff University UK halljp@cf.ac.uk

More information

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice

More information

Z-Source Circuit Breaker Utilizing Ultra-Fast Mechanical Switch for High Efficiency DC Circuit Protection

Z-Source Circuit Breaker Utilizing Ultra-Fast Mechanical Switch for High Efficiency DC Circuit Protection Z-Source Circuit Breaker Utilizing Ultra-Fast Mechanical Switch for High Efficiency DC Circuit Protection Landon Mackey, Md Rifat Kaisar Rachi, Chang Peng, Iqbal Husain College of Electrical and Computer

More information

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION

LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION LIGHTNING OVERVOLTAGES AND THE QUALITY OF SUPPLY: A CASE STUDY OF A SUBSTATION Andreas SUMPER sumper@citcea.upc.es Antoni SUDRIÀ sudria@citcea.upc.es Samuel GALCERAN galceran@citcea.upc.es Joan RULL rull@citcea.upc.es

More information

page 2 of 86 Report reference No:

page 2 of 86 Report reference No: articulars: test item vs. test requirements 3. Classification 3.1. Utilization category: (A or B)... : A 3.2. Interruption medium: (air, vacuum, gas Break)... : Air 3.3. Design: (open construction, moulded

More information

Testing 320 kv HVDC XLPE Cable System

Testing 320 kv HVDC XLPE Cable System Testing 320 kv HVDC XLPE Cable System H. He, W. Sloot DNV GL, KEMA Laboratories Arnhem, The Netherlands Abstract Two unique test requirements in testing of a high- voltage direct- current (HVDC) cable

More information

Single Line Diagram of Substations

Single Line Diagram of Substations Single Line Diagram of Substations Substations Electric power is produced at the power generating stations, which are generally located far away from the load centers. High voltage transmission lines are

More information