Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Size: px
Start display at page:

Download "Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems"

Transcription

1 Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems Romeo C. Ciobanu, Cristina Schreiner, Ramona Burlacu, Cristina Bratescu Technical University Iasi Dept. of Electrical Measurements and Materials Bdul D. Mangeron no , IASI, , Romania Tel.: Fax: rciobanu@ee.tuiasi.ro Abstract The broadband Partial Discharge (PD) measurement technique may be considered more accurate than a simple breakdown test and admitted as a complementary method for characterizing the quality of porous/fibrous and composite insulating materials. It should be taken into account especially at higher frequencies, when the risk of breakdown occurrence becomes greater in time, due to the local thermal aspects. Keywords: Partial discharges, composite insulating systems, cable paper technology 1. Introduction Partial discharges usually occur, if in gas filled cavities within solid insulation or in air gaps between several layers within an insulation construction, respectively between insulating material and electrodes, the breakdown voltage of the enclosed gas (mostly air) is exceeded. In case of capacitive voltage distribution for a.c. voltages the cavities are usually stressed much higher and also the PD-impulse rate is by magnitudes higher. As regards the standardisation of PD-testing, we need to accept PD-testing as a general recognised tool to verify the integrity of high-voltage insulation systems. These specifications have been introduced in the international safety standard for insulation coordination of low-voltage equipment, as far as solid insulation is concerned [1]. For thin insulation systems (< 1 mm) and especially for safety-related applications, the verification of the non-existence of PD or the capability to withstand PD permanently should always be required. By performing PD-testing both requirements for minimum thickness through insulation and excessive amplitudes of the test voltage and duration of the test are substituted. There is no physical background for the values of minimum thickness through insulation, which are currently required and which vary between 0.4 and 2 mm. It is difficult to understand how such different thickness values can provide the same required degree of safety. The use of very high test voltages without measuring PDs always implies the risk of degradation of the solid insulation. Such tests even widely accepted - can only show the important defects within the insulation system and can be acceptable in case of type testing, but they are not appropriate for sample or routine testing. The PD-testing is not necessarily performed with high expenditure. This may be at very high voltage levels, when the achievement of low interference levels is a real problem. But for test voltages less than 10 kv and according to the simplified test procedures, the PD-test is comparable to the traditional power-frequency highvoltage test. Simple screening measures are sufficient to meet the required interference level and PD-test apparatus with inherent interference suppression are widely available nowadays. 2. PD-testing at higher frequency Requirements and guidance for PD-testing are contained in e.g. [2, 3]. In high-voltage engineering the requirement of PD-testing is recognised in general, as the existence of high field stress is obvious. However, due to very small insulating distances in recent low-voltage 4-307

2 equipment similar or even higher fields can occur. This is usually the case if increased stresses due to overvoltages or dielectric testing are applied. In the past, this aspect was only taken into account when very high reliability was required [2, 4]. But recent technologies with decreasing insulating distance require a reconsideration of this situation. As a lower physical limit for the occurrence of PD, a peak voltage of 300 V may be considered. According to practical experience PD can occur when peak voltages in excess of 500 V are applied. 1 Power generator 10 Hz khz 2 Wide band high-voltage transformer 3 Test specimen 4 High pass filter 5 High-voltage probe 6 Screened cabinet 7 High speed digital storage oscilloscope 8 Decoupling amplifier 9 PD-measuring instrument (narrow band) 10 Digital voltmeter 11 Analogue oscilloscope 12 Control computer Fig. 1. PD-test circuit for higher frequency voltage tests. With respect to any kind of high-voltage testing at frequencies which are much higher than the power frequency, the availability of appropriate test voltage sources with adjustable frequency is a fundamental problem. The PD-measurements with higher frequency test voltage, which are reported here, have been performed with the test circuit shown in figure 1. This circuit is based on a high-frequency resonance transformer (2), which is fed by a highfrequency power generator (1) [5]. A possible alternative is a high-frequency power oscillator, which allows the generation of significantly higher frequencies [6]. For measuring the PDintensity, a digital storage oscilloscope in combination with a rejection filter with steep characteristic in order to suppress the high-frequency test voltage was basically used

3 Additional hardware and software facilities were created in order outline the measured quantities: PD pulse peak value of inception and extinction voltage, apparent charge of individual PD pulses, instantaneous values of test voltage and frequency when PD pulse occurs, other statistical data related to PD distribution versus phase or charge value. 3. Experimental investigations A wide literature describes the negative role of ions upon dielectric properties of hygroscopic materials, especially upon breakdown strength. However it proved to be no simple task to appoint a fair mineral purity limit of a certain insulator, especially under the circumstances when divergent opinions are occurring, regarding the real dependence between this limit (imposed by producers, on economical reasons) and the values of some dielectric properties (strictly imposed by the insulation users, on service or reliability reasons). Our study relates the case of insulation based on cellulose pulps for electrical purposes. The investigations were purchased on laboratory made samples of paper for cable applications, from demineralised - unbleached softwood sulphate - pulps, industrially beaten till a refining degree of 40 SR. The demineralisation process followed and presumed a special industrial treatment with HCL-acid (an equivalent addition of 80 kg acid / tone of absolutely dried cellulose) under controlled demineralisation duration (till a maximum admitted value - 2 hours), as widely described in [7]. All paper samples were finally formed and adjusted to 70 g/m² (0.12 mm thin). The results were correlated directly with the mineral content in paper, c ash [%]. A direct comparison of PD characteristics with the standard breakdown test was provided. All measurement results are presented as RMS values. It was assumed that the analysis of broadband PD phenomena versus mineral content of papers could offer new information in order to improve the theory of cellulose dielectric failure. The need for such studies at fundamental level is without doubt nowadays [ V ] 400 Ud - 1% Ud % 200 Ui - 1% Ui % k 2 k 3 k 3.5 k 10 k 30 k 35 k 45 k 60 k 110 k Fig. 2. Comparative evolution of breakdown and PD inception voltages versus frequency, for 1% and respectively 0.42% mineral content in paper. U d - breakdown voltage / U i - PD inception voltage / U e - PD extinction voltage. After testing the PD-characteristics, it was found that the most significant variation versus mineral content was emphasised mainly by the inception and extinction voltages, U i and U e, in the whole frequency range. That is why only the evolution of these characteristics is presented herein. On the other hand, when comparing the PD and breakdown processes, there were found appreciable differences between the evolution versus frequency of breakdown and PD inception voltages. This observation occurred reproducible for all types of analysed 4-309

4 samples, having different mineral content. But in order to express more synthetically the influence of mineral content, only two reference values are presented below, respectively: 0.42 %, considered the optimum value in the whole frequency range, and 1%, the standard reference content for common papers for electrical purposes. Figure 2 shows the continuous decrease of the breakdown voltage, U d, with the increase of frequency homologue to the one described by literature, but also the peculiar unexpected evolution of U i, different from U d. This phenomenon appointed herein is considered new, emphasised for the first time by the authors. This aspect was proven to be reproducible in a more general matter, for a wide range of dielectric structures and technologies analysed elsewhere by authors, even under different stress parameters or related to other physical or chemical features. 4. Analysis of experimental data At industrial frequencies, the PD phenomena appear clearly for lower voltages, comparing to the homologue breakdown value and this aspect could be a good explanation for the premature ageing of dielectric material in certain applications of electrical drives. The decrease becomes even more important in the case of higher mineral content (herein 1%). Basically, at over 10 khz the evolution versus frequency of both PD and breakdown phenomena look concordant as described in literature. In this domain the mineral content seems to influence only the PD inception voltage, comparing to the breakdown behaviour. That is why new studies of PD phenomena are needed in future, in order to understand more accurately the intimate pre-breakdown processes and failure of dielectric structures [ % ] 50 Hz 150 Hz 1 khz 45 khz 110 khz 0-5 0,2 0,4 0,6 cash [ % ] 0,8 1 1,2 Fig. 3. PD - Inception voltage evolution versus mineral content in paper, for different frequencies [ % ] 50 Hz 150 Hz 1 khz 45 khz 110 khz 0,2 0,4 0,6 c ash [ % ] 0,8 1 1,2 Fig. 4. PD - Extinction voltage evolution versus mineral content in paper, for different frequencies. In order to account for the demineralisation process efficiency via broadband PD analysis, in figures 3 and 4 the evolution versus mineral content of the relative variation of the PD inception and extinction voltages is presented. It was noticed that a significant variation of these characteristics occurred within a relatively small domain of mineral content, with an optimum of about 0.42 %. The increase of U i and U e - values appears obviously due to the 4-310

5 diminishing of ions content in paper, reducing the effect of PD phenomena. These results are according to similar observations obtained for other insulations, as thin films or cast resins. Once the mineral content becomes less than 0.4%, the positive effect of demineralisation process is progressively lost, especially at higher frequencies. This expected behaviour could be explained by the presence of the residual Cl - ion and by the chemical ageing process consequent to the longer demineralisation process duration, needed to reach much lower mineral content values. In our study, the optimum value of mineral content seen as a technological demineralisation limit was found 0.42 %, instead of 0,35 %, recommended by literature by analysing the breakdown characteristic alone, [8]. It seems that by applying short-term high electrical stresses, the case of breakdown strength, a higher mineral purity should be needed to reach some theoretical recommended values. But exactly the chemical damages incurred by the obtaining of this purity limit favour the occurrence of PD phenomena during a long term exploitation process, leading finally to a reduced lifetime of insulation. This is a clear example of doubt in relation with breakdown test purpose and validity related to samples routine testing. We finally estimated that the optimum value of 0.42 % can be considered more accurate and closer to the reality of long term in-service stress of papers for electrical applications. This value, if admitted as valid for cable paper, would provide significant technological and financial advantages for paper producers, reflected in a diminished consume of reactives and /or in a reduced duration of demineralisation. 5. Conclusion The appreciable differences between the evolution versus frequency of the PD and breakdown phenomena, aspect reproducible for many types of insulating specimens, suggests that the breakdown analysis alone proves to have limits in accuracy and results interpretation. The PD occurrence is clearly influenced by the mineral content, and an optimum value of 0.42 % was appointed for cable paper, for the whole frequency range. Such values, validated via PD analysis, can provide significant technological advantages for the producers. The extended analysis versus frequency of PD phenomena is considered a valuable complementary method in quality assessment of insulating technologies, and even for sample testing, being more close to the real in service behaviour and ageing mechanism of insulation. References 1. IEC /1992. Insulation coordination for equipment within low-voltage systems Part 1: Principles, requirements and tests. 2. IEC 60270/1981. Partial discharge measurements. 3. IEC High-voltage test techniques for low-voltage equipment Part 1/1992: Definitions, test and procedure requirements; Part 2/1994: Test equipment. 4. IEC /1997. Insulation coordination within low-voltage systems Part 4: Considerations of high-frequency voltage stress. 5. W. Pfeiffer. Dielectric Testing of Solid Insulation with Respect to Insulation Coordination of Low-Voltage Equipment. IEEE Transactions on Electrical Insulation. 2001, vol. 17, No. 3, pp W. Pfeiffer. High frequency voltage stress of insulation - methods of testing. IEEE Transactions on Electrical Insulation. 1991, vol. 26, pp R. Ciobanu, W. Pfeiffer. Influence of mineral content on the behavior of electrical papers under high frequency partial discharges. European Trans. on Elec. Power Eng. ETEP. 1999, vol. 9, No. 3, pp R. Ciobanu, W. Pfeiffer, E. Poppel. A theoretical approach to the P.D. phenomena in composite dielectrics. Cellulose Chemistry and Technology. 1997, No. 5, pp

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento Sept. 22-24, 28, Florence, Italy EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS C. Ceretta, R. Gobbo, G. Pesavento Dept. of Electrical Engineering University of

More information

High-Voltage Test and

High-Voltage Test and Eberhard Wolfgang Hauschild Lemke High-Voltage Test and Measuring Techniques ^ Springer Contents 1 Introduction 1 1.1 Development of Power Systems and Required High-Voltage Test Systems 1 1.2 The International

More information

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer Scientific Journal of Impact Factor(SJIF): 3.134 International Journal of Advance Engineering and Research Development Volume 2,Issue 7, July -2015 e-issn(o): 2348-4470 p-issn(p): 2348-6406 Comparison

More information

Partial Discharge Patterns in High Voltage Insulation

Partial Discharge Patterns in High Voltage Insulation 22 IEEE International Conference on Power and Energy (PECon), 2-5 December 22, Kota Kinabalu Sabah, Malaysia Partial Discharge Patterns in High Voltage Insulation Hazlee Illias, Teo Soon Yuan, Ab Halim

More information

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES Gonzalo MAIZ, Iberdrola Distribución, (Spain), gmaiz@iberdrola.es Armando RODRIGO, Instituto

More information

Simulation Model of Partial Discharge in Power Equipment

Simulation Model of Partial Discharge in Power Equipment Simulation Model of Partial Discharge in Power Equipment Pragati Sharma 1, Arti Bhanddakkar 2 1 Research Scholar, Shri Ram Institute of Technology, Jabalpur, India 2 H.O.D. of Electrical Engineering Department,

More information

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 23 CHAPTER 2 v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES 2.1 INTRODUCTION For reliable design of power system, proper insulation coordination among the power system equipment is necessary. Insulation

More information

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 75 CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN 5.1 INTRODUCTION Partial Discharge (PD) detection is an important tool for monitoring insulation conditions in high voltage (HV) devices in power systems.

More information

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE Z.Liu, B.T.Phung, T.R.Blackburn and R.E.James School of Electrical Engineering and Telecommuniications University of New South Wales

More information

DIELECTRIC HEATING IN INSULATING MATERIALS AT HIGH DC AND AC VOLTAGES SUPERIMPOSED BY HIGH FREQUENCY HIGH VOLTAGES

DIELECTRIC HEATING IN INSULATING MATERIALS AT HIGH DC AND AC VOLTAGES SUPERIMPOSED BY HIGH FREQUENCY HIGH VOLTAGES DIELECTRIC HEATING IN INSULATING MATERIALS AT HIGH DC AND AC VOLTAGES SUPERIMPOSED BY HIGH FREQUENCY HIGH VOLTAGES Matthias Birle * and Carsten Leu Ilmenau University of technology, Centre for electrical

More information

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment First International Conference on Emerging Trends in Engineering, Management and Scineces December 28-3, 214 (ICETEMS-214)Peshawar,Pakistan Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

More information

Diagnostic testing of cast resin transformers

Diagnostic testing of cast resin transformers Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com

More information

PD Diagnostic Applications and TechImp solutions

PD Diagnostic Applications and TechImp solutions PD Diagnostic Applications and TechImp solutions Condition Assessment Solutions for Electrical Systems. PD based innovative tools for the Condition Based Maintenance. MD-04.05.004 - rev. 00-29/08/2006

More information

Coherence and time-frequency analysis of impulse voltage and current measurements

Coherence and time-frequency analysis of impulse voltage and current measurements Coherence and time-frequency analysis of impulse voltage and current measurements Jelena Dikun Electrical Engineering Department, Klaipeda University, Klaipeda, Lithuania Emel Onal Electrical Engineering

More information

INTERNATIONAL. High-voltage test techniques Partial discharge measurements

INTERNATIONAL. High-voltage test techniques Partial discharge measurements INTERNATIONAL STANDARD IEC 60270 Third edition 2000-12 High-voltage test techniques Partial discharge measurements This English-language version is derived from the original bilingual publication by leaving

More information

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May 26 2011 St Pete Beach, Fl HDW ELECTRONICS, INC. THE BEST IN CABLE FAULT LOCATING TECHNOLOGY by Henning Oetjen Frank

More information

Investigation of PD Detection on XLPE Cables

Investigation of PD Detection on XLPE Cables Investigation of PD Detection on XLPE Cables Hio Nam O, T.R. Blackburn and B.T. Phung School of Electrical Engineering and Telecommunications The University New South Wales, Australia Abstract- The insulation

More information

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015 Basics of Partial Discharge Prepared for 2015 Phenix RSM Meeting January 2015 Definitions and History Standard Definitions Fundamentally, what is a Partial Discharge An electric discharge which only partially

More information

L. B. Gordon Space Power Institute 231 Leach Center Auburn University, Alabama 36849

L. B. Gordon Space Power Institute 231 Leach Center Auburn University, Alabama 36849 FAILURE MODES OF LAMINATE STRUCTURES L. B. Gordon Space Power Institute 231 Leach Center Auburn University, Alabama 36849 Abstract Laminate structures composed of alternating thin layers of conductor and

More information

Why partial discharge testing makes good sense

Why partial discharge testing makes good sense Why partial discharge testing makes good sense PD measurement and analysis have proven to be reliable for detecting defects in the insulation system of electrical assets before major damage or a breakdown

More information

Partial Discharge Signal Detection by Piezoelectric Ceramic Sensor and The Signal Processing

Partial Discharge Signal Detection by Piezoelectric Ceramic Sensor and The Signal Processing Journal of Electroceramics, 13, 487 492, 2004 C 2004 Kluwer Academic Publishers. Manufactured in The Netherlands. Partial Discharge Signal Detection by Piezoelectric Ceramic Sensor and The Signal Processing

More information

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS

PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS PULSE-SEQUENCE ANALYSIS OF PARTIAL DISCHARGES IN POWER TRANSFORMERS Anne Pfeffer 1*, Stefan Tenbohlen 1 and Stefan Kornhuber 2 1 Institute of Power Transmission and High Voltage Technology, Pfaffenwaldring

More information

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS 1. Introduction 2. Classification of High Voltage Tests 3. Test Voltages 4. High Voltage Testing of Electrical Apparatus 1. INTRODUCTION Purpose

More information

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT Claus NEUMANN Darmstadt University of Technology Germany claus.neumann@amprion.net Klaus WINTER Swedish Neutral

More information

Corona noise on the 400 kv overhead power line - measurements and computer modeling

Corona noise on the 400 kv overhead power line - measurements and computer modeling Corona noise on the 400 kv overhead power line - measurements and computer modeling A. MUJČIĆ, N.SULJANOVIĆ, M. ZAJC, J.F. TASIČ University of Ljubljana, Faculty of Electrical Engineering, Digital Signal

More information

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces 1 Prediction of Transient Transfer Functions at Cable-Transformer Interfaces Joe Y. Zhou, Member, IEEE and Steven A. Boggs, Fellow, IEEE Joe Zhou participated in this work while completing his Ph.D. at

More information

Electric Stresses on Surge Arrester Insulation under Standard and

Electric Stresses on Surge Arrester Insulation under Standard and Chapter 5 Electric Stresses on Surge Arrester Insulation under Standard and Non-standard Impulse Voltages 5.1 Introduction Metal oxide surge arresters are used to protect medium and high voltage systems

More information

Verification Structures for Transmission Line Pulse Measurements

Verification Structures for Transmission Line Pulse Measurements Verification Structures for Transmission Line Pulse Measurements R.A. Ashton Agere Systems, 9333 South John Young Parkway, Orlando, Florida, 32819 USA Phone: 44-371-731; Fax: 47-371-777; e-mail: rashton@agere.com

More information

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to

More information

MAHALAKSHMI ENGINEERING COLLEGE

MAHALAKSHMI ENGINEERING COLLEGE MAHALAKSHMI ENGINEERING COLLEGE TIRUCHIRAPALLI 621213 QUESTION BANK -------------------------------------------------------------------------------------------------------------- Sub. Code : EE2353 Semester

More information

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR CIRCUIT BREAKER SF 6 ING. VÁCLAV JEŽEK PROF. ING. ZDENĚK VOSTRACKÝ, DRSC., DR.H.C. Abstract: This article describes the analysis of faults interrupted by generator

More information

Simulation of Partial Discharge in High Voltage Power Equipment

Simulation of Partial Discharge in High Voltage Power Equipment International Journal on Electrical Engineering and Informatics Volume 3, Number 2, 2011 Simulation of Partial Discharge in High Voltage Power Equipment Asima Sabat and S. Karmakar Department of Electrical

More information

High Frequency Voltage Stress. Presented by: Flore Chiang Date: March 30, 2012

High Frequency Voltage Stress. Presented by: Flore Chiang Date: March 30, 2012 High Frequency Voltage Stress Presented by: Flore Chiang Date: March 30, 2012 Now the additional data is available! ground rules: 1. intro to PD. 2. experimental results. 3. comparison with current practice.

More information

An Investigation into the Effects of Sampling on the Loop Response and Phase Noise in Phase Locked Loops

An Investigation into the Effects of Sampling on the Loop Response and Phase Noise in Phase Locked Loops An Investigation into the Effects of Sampling on the Loop Response and Phase oise in Phase Locked Loops Peter Beeson LA Techniques, Unit 5 Chancerygate Business Centre, Surbiton, Surrey Abstract. The majority

More information

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s Designed for Partial Discharge Analyzers (PDA s) monitoring rotating machinery or other medium-voltage equipment from 1 to 35 kvac RMS at power-line frequencies of 10 Hz to 1 khz, Mica Capacitor Type 297

More information

Partial discharge diagnostics on very long and branched cable circuits

Partial discharge diagnostics on very long and branched cable circuits 11 Nordic Insulation Symposium Stockholm, June 11-13, 2001 Partial discharge diagnostics on very long and branched cable circuits Nico van Schaik, E. Fred Steennis, Wim Boone and Dick M. van Aartrijk KEMA

More information

Comparison of capacitive and inductive sensors designed for partial discharges measurements in electrical power apparatus

Comparison of capacitive and inductive sensors designed for partial discharges measurements in electrical power apparatus Comparison of capacitive and inductive sensors designed for partial discharges measurements in electrical power apparatus Michał Kunicki 1,* 1 Opole University of Technology, ul. Prószkowska 76, 45-758

More information

FAULT IDENTIFICATION IN TRANSFORMER WINDING

FAULT IDENTIFICATION IN TRANSFORMER WINDING FAULT IDENTIFICATION IN TRANSFORMER WINDING S.Joshibha Ponmalar 1, S.Kavitha 2 1, 2 Department of Electrical and Electronics Engineering, Saveetha Engineering College, (Anna University), Chennai Abstract

More information

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings J Electr Eng Technol Vol. 9, No. 1: 280-285, 2014 http://dx.doi.org/10.5370/jeet.2014.9.1.280 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 Characteristics of Insulation Diagnosis and Failure in Gas Turbine

More information

Strathprints Institutional Repository

Strathprints Institutional Repository Strathprints Institutional Repository Given, M and Mason, Ronald and Judd, Martin and Mcglone, Phillip and Timoshkin, Igor and Wilson, Mark () Comparison between RF and electrical signals from the partial

More information

Evaluation and Limitations of Corona Discharge Measurements An Application Point of View

Evaluation and Limitations of Corona Discharge Measurements An Application Point of View Evaluation and Limitations of Corona Discharge Measurements An Application Point of View P. Mraz, P. Treyer, U. Hammer Haefely Hipotronics, Tettex Instruments Division 2016 International Conference on

More information

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP IJSTE - International Journal of Science Technology & Engineering Volume 3 Issue 2 August 216 ISSN (online): 2349-784X Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

More information

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY Dr. Karthik Reddy VENNA Hong URBANEK Nils ANGER Siemens AG Germany Siemens AG Germany Siemens AG Germany karthikreddy.venna@siemens.com

More information

PD Testing Considerations for MV Plant Cables

PD Testing Considerations for MV Plant Cables PD Testing Considerations for MV Plant Cables Cable Testing Philosophy Damage Mistake Aging Repair Manufacturing Transportation Installation Operation Power frequency 50/60 Hz Power frequency 50/60 Hz

More information

PARTIAL DISCHARGE MEASUREMENT

PARTIAL DISCHARGE MEASUREMENT PARTIAL DISCHARGE MEASUREMENT Partial Discharges are small electrical sparks which occur predominantly at insulation imperfection. It is the phenomenon which occurs in the insulation on application of

More information

Error vs. Uncertainty Historical Perspective

Error vs. Uncertainty Historical Perspective 1 Error vs. Uncertainty Historical Perspective Jim McBride Chairman PSIM Committee Vice-Chairman HVTT Subcommittee IEEE PES SPDC Fall 2017 Clearwater, FL Discussions on Uncertainty PSIM - HVTT Subcommittee

More information

The Synthesis and Analysis of Partial Discharges from Stator Winding Insulation of Hydro Generators

The Synthesis and Analysis of Partial Discharges from Stator Winding Insulation of Hydro Generators ANALELE UNIVERSITĂłII EFTIMIE MURGU REŞIłA ANUL XIV, NR. 1, 2007, ISSN 1453-7397 Mihaela Răduca, Ana-Maria Pittner, Eugen Răduca, Iancu Tătucu The Synthesis and Analysis of Partial Discharges from Stator

More information

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

FGJTCFWPKPUVKVWVGQHVGEJPQNQI[ FGRCTVOGPVQHGNGEVTKECNGPIKPGGTKPI VGG246JKIJXQNVCIGGPIKPGGTKPI FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown

More information

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power

More information

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements EMEL ONAL Electrical Engineering Department Istanbul Technical University 34469 Maslak-Istanbul TURKEY onal@elk.itu.edu.tr http://www.elk.itu.edu.tr/~onal

More information

Fault Detection in Transformer Using Frequency (Sweep) Response Analysis

Fault Detection in Transformer Using Frequency (Sweep) Response Analysis Fault Detection in Transformer Using Frequency (Sweep) Response Analysis Miss. Kajal R. Pachbhai PG Student at Ballarpur Institute of Technology, Ballarpur-442701 India kajalpachbhai86@gmail.com Mr. Sagar

More information

Diagnosis of Water Tree Aging in XLPE Cable by the Loss Current Harmonic Component Under Variable Frequency Power

Diagnosis of Water Tree Aging in XLPE Cable by the Loss Current Harmonic Component Under Variable Frequency Power Journal of Electrical and Electronic Engineering 2015; 3(6): 208-214 Published online January 9, 2016 (http://www.sciencepublishinggroup.com/j/jeee) doi: 10.11648/j.jeee.20150306.16 ISSN: 2329-1613 (Print);

More information

Modeling insulation in high-voltage substations

Modeling insulation in high-voltage substations 38 ABB REVIEW DESIGNED FOR SAFETY DESIGNED FOR SAFETY Modeling insulation in high-voltage substations The goal of insulation coordination is to determine the dielectric strength of transformers and other

More information

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS Authored by: Sanjay Srivastava, Chief Engineer (HE&RM), Rakesh Kumar, Director (HE&RM), R.K. Jayaswal, Dy. Director (HE&RM)

More information

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY Lorenzo PERETTO Luigi FODDAI Simone ORRU Luigi PUDDU Altea Switzerland ENEL Italy ENEL Italy REPL Italy lperetto@alteasolutions.com

More information

Improving CDM Measurements With Frequency Domain Specifications

Improving CDM Measurements With Frequency Domain Specifications Improving CDM Measurements With Frequency Domain Specifications Jon Barth (1), Leo G. Henry Ph.D (2), John Richner (1) (1) Barth Electronics, Inc, 1589 Foothill Drive, Boulder City, NV 89005 USA tel.:

More information

Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage Application

Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage Application IEEE Transactions on Dielectrics and Electrical Insulation Vol. 14, No. 1; February 27 39 Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage

More information

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink ISSN (Online) 2321 24 Vol. 4, Issue 6, June 2 Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink C Sunil kumar 1, Harisha K S 2, Gouthami N 3, Harshitha V 4, Madhu C Assistant Professor,

More information

3.2 Measurement of high voltages

3.2 Measurement of high voltages DEPT OF HIGH VOLTAGE AND INSULATION ENG, HONGQING UNIVERSITY Part I- hapter 3: Insulation test techniques 3. Measurement of high voltages Instructor: Dr. Jian Li Lecture 7- DEPT OF HIGH VOLTAGE AND INSULATION

More information

International Journal of Advance Engineering and Research Development. Analysis of Surge Arrester using FEM

International Journal of Advance Engineering and Research Development. Analysis of Surge Arrester using FEM Scientific Journal of Impact Factor(SJIF): 3.134 e-issn(o): 2348-4470 p-issn(p): 2348-6406 International Journal of Advance Engineering and Research Development Volume 2,Issue 5, May -2015 Analysis of

More information

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation W. Buesch 1) G. Palmieri M.Miesch J. Marmonier O. Chuniaud ALSTOM LTD 1) ALSTOM LTD High Voltage Equipment

More information

Study on Glow Discharge Plasma Used in Polyester. surface modification

Study on Glow Discharge Plasma Used in Polyester. surface modification Study on Glow Discharge Plasma Used in Polyester Surface Modification LIU Wenzheng ( ), LEI Xiao ( ), ZHAO Qiang ( ) School of Electrical Engineering, Beijing Jiaotong University, Beijing 100044, China

More information

Choosing the right Pico Technology active differential probe

Choosing the right Pico Technology active differential probe Pico Technology offers many active s covering a wide range of voltages, category (CAT) ratings and bandwidths. As the name suggests, these probes have two major features: Active: Active probes achieve

More information

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS

CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS 136 CONDITION MONITORING OF MEDIUM VOLTAGE ELECTRICAL CABLES BY MEANS OF PARTIAL DISCHARGE MEASUREMENTS H. van Jaarsveldt* and R. Gouws** School of Electrical, Electronic and Computer Engineering, North-West

More information

PD Solutions. On-Line PD Measurement Devices

PD Solutions. On-Line PD Measurement Devices On-Line PD Measurement Devices 1. Longshot Device (see Figure 1) The measurement system applied is based around the wideband (0-400 MHz) HVPD- Longshot partial discharge test unit which utilizes a high-speed

More information

FERRORESONANCE - its Occurrence and Control in Electricity Distribution Networks

FERRORESONANCE - its Occurrence and Control in Electricity Distribution Networks FERRORESONANCE - its Occurrence and Control in Electricity Distribution Networks by Alex Baitch FIEAust, CPEng Manager Network Capability, Integral Energy This paper was presented to the Annual Conference

More information

IEEE Transactions on Power Delivery. 15(2) P.467-P

IEEE Transactions on Power Delivery. 15(2) P.467-P Title Author(s) Citation Detection of wide-band E-M signals emitted from partial discharge occurring in GIS using wavelet transform Kawada, Masatake; Tungkanawanich, Ampol; 河崎, 善一郎 ; 松浦, 虔士 IEEE Transactions

More information

DISCRETE DIFFERENTIAL AMPLIFIER

DISCRETE DIFFERENTIAL AMPLIFIER DISCRETE DIFFERENTIAL AMPLIFIER This differential amplifier was specially designed for use in my VK-1 audio oscillator and VK-2 distortion meter where the requirements of ultra-low distortion and ultra-low

More information

Software System for Finding the Incipient Faults in Power Transformers

Software System for Finding the Incipient Faults in Power Transformers Software System for Finding the Incipient Faults in Power Transformers Nikolina Petkova Technical University of Sofia, Department of Theoretical Electrical Engineering, 1156 Sofia, Bulgaria Abstract In

More information

Importance of Transformer Demagnetization

Importance of Transformer Demagnetization Available online at www.sciencedirect.com ScienceDirect Procedia Engineering 00 (2017) 000 000 www.elsevier.com/locate/procedia 4th International Colloquium "Transformer Research and Asset Management Importance

More information

Techniques to reduce electromagnetic noise produced by wired electronic devices

Techniques to reduce electromagnetic noise produced by wired electronic devices Rok / Year: Svazek / Volume: Číslo / Number: Jazyk / Language 2016 18 5 EN Techniques to reduce electromagnetic noise produced by wired electronic devices - Tomáš Chvátal xchvat02@stud.feec.vutbr.cz Faculty

More information

G. KOEPPL Koeppl Power Experts Switzerland

G. KOEPPL Koeppl Power Experts Switzerland PS3: Substation Design: New Solutions and Experiences Bus-Node Substation A Big Improvement in Short-Circuit and Switching Properties at Reduced Substation Costs G. KOEPPL Koeppl Power Experts Switzerland

More information

Effect of Shielded Distribution Cable on Very Fast Transients

Effect of Shielded Distribution Cable on Very Fast Transients IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 15, NO. 3, JULY 2000 857 Effect of Shielded Distribution Cable on Very Fast Transients Li-Ming Zhou and Steven Boggs, Fellow, IEEE Abstract Fast transients in

More information

Electric Field Analysis of High Voltage Condenser Bushing

Electric Field Analysis of High Voltage Condenser Bushing Proc. of Int. Conf. on Current Trends in Eng., Science and Technology, ICCTEST Electric Field Analysis of High Voltage Condenser Bushing Anguraja.R 1 and Pradipkumar Dixit 2 1 Research Scholar, Jain University,

More information

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid.

All the standards referred to the most current issue, including all amendment supplements. as of the date of the bid. 1. Scope This specification defines the methods, the procedures and the requirements to verify the cables manufactured according to I.E.C. Specifications NPS361. 2. Standards All the standards referred

More information

C I R E D 21 st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011

C I R E D 21 st International Conference on Electricity Distribution Frankfurt, 6-9 June 2011 Use and Problems of On-line PD Measurement Technology on Switchgears in Guangzhou Distribution System XIONG Jun, WANG Yong, HUANG Huihong, HUANG Yanguang,LU Guojun,WU Bihua (Central Test and Researches

More information

Evaluation of Distribution Line Spacers through the Leakage Current Monitoring

Evaluation of Distribution Line Spacers through the Leakage Current Monitoring Tsinghua University, Beijing, China, August -9, H-6 Evaluation of Distribution Line Spacers through the Leakage Current Monitoring A. G. Kanashiro *, W. Pinheiro and G. F. Burani Institute of Electrotechnics

More information

PARTIAL DISCHARGE MEASUREMENT ON RING MAIN UNIT

PARTIAL DISCHARGE MEASUREMENT ON RING MAIN UNIT PARTIAL DISCHARGE MEASUREMENT ON RING MAIN UNIT Chaudhari Prashant P.*1, R. K. Jha *2 *1 (M.E Student SND College Of Engineering Yeola) *2 (Asst. Prof., S.N.D.C.O.E & RC, Yeola) Abstract As per IEC Standard

More information

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES

CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES CONTINUOUS ON-LINE MONITORING OF PARTIAL DICHARGES IN HV DISTRIBUTION CABLES Hao ZHANG, Transgrid, (Australia), hao.zhang@transgrid.com.au Zhao LIU, University of NSW, (Australia), z.liu@unsw.edu.au Toan

More information

A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints

A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints WETS D 15 2.4 Drapeau A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints Jean-François DRAPEAU Researcher Expertise Équipement électriques IREQ Jacques CÔTÉ, HQD Simon

More information

High Sensitivity Interferometric Detection of Partial Discharges for High Power Transformer Applications

High Sensitivity Interferometric Detection of Partial Discharges for High Power Transformer Applications High Sensitivity Interferometric Detection of Partial Discharges for High Power Transformer Applications Carlos Macià-Sanahuja and Horacio Lamela-Rivera Optoelectronics and Laser Technology group, Universidad

More information

Detection of Partial Discharges and its Effect on Solid Insulation used in High Voltage Cable

Detection of Partial Discharges and its Effect on Solid Insulation used in High Voltage Cable Detection of Partial Discharges and its Effect on Solid Insulation used in High Voltage Cable Subrata Karmakar and Soumya Mishra Department of Electrical Engineering National Institute of Technology Rourkela-769008

More information

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets Abstract: For decades it has been recognized that partial discharge assessment is an excellent method

More information

TD-100. HAEFELY HIPOTRONICS Technical Document

TD-100. HAEFELY HIPOTRONICS Technical Document HAEFELY HIPOTRONICS Technical Document Breaking the limit of power capacitor resonance frequency with help of PD pulse spectrum to check and setup PD measurement P. Treyer, P. Mraz, U. Hammer, S. Gonzalez

More information

High-Voltage Test Techniques

High-Voltage Test Techniques High-Voltage Test Techniques Dieter Kind Kurt Feser 2nd Revised and Enlarged Edition With 211 Figures and 12 Laboratory Experiments Translated from the German by Y. Narayana Rao Professor of Electrical

More information

Analogue Demo Multimeter ADM

Analogue Demo Multimeter ADM Analogue Demo Multimeter ADM 2 3820-0 PHYWE Systeme GmbH & Co. KG Robert-Bosch-Breite 0 D-37079 Göttingen Telefon +49 (0) 55 604-0 Fax +49 (0) 55 604-07 E-mail info@phywe.de Operating instructions The

More information

Partial Discharge Monitoring and Diagnosis of Power Generator

Partial Discharge Monitoring and Diagnosis of Power Generator Partial Discharge Monitoring and Diagnosis of Power Generator Gao Wensheng Institute of High Voltage & insulation tech. Electrical Eng. Dept., Tsinghua University Wsgao@tsinghua.edu.cn Currently preventive

More information

Prepared by Mick Maytum

Prepared by Mick Maytum IEC Technical Committee 109: Standards on insulation co-ordination for low-voltage equipment Warning Prepared by Mick Maytum mjmaytum@gmail.com The document content is of a general nature only and is not

More information

EE 1402 HIGH VOLTAGE ENGINEERING

EE 1402 HIGH VOLTAGE ENGINEERING EE 1402 HIGH VOLTAGE ENGINEERING Unit 5 TESTS OF INSULATORS Type Test To Check The Design Features Routine Test To Check The Quality Of The Individual Test Piece. High Voltage Tests Include (i) Power frequency

More information

GENERATOR TESTING APPLICATION GUIDE. reliable. precision.

GENERATOR TESTING APPLICATION GUIDE.  reliable. precision. GENERATOR TESTING APPLICATION GUIDE www.haefely-hipotronics.com reliable. precision. 2 GENERATOR TESTING CONTENTS Product Line Overview 3 AC Hipot Testing 4 Partial Discharge Measurement 5 DC Hipot Testing

More information

ELEC3242 Communications Engineering Laboratory Amplitude Modulation (AM)

ELEC3242 Communications Engineering Laboratory Amplitude Modulation (AM) ELEC3242 Communications Engineering Laboratory 1 ---- Amplitude Modulation (AM) 1. Objectives 1.1 Through this the laboratory experiment, you will investigate demodulation of an amplitude modulated (AM)

More information

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage Journal of Energy and Power Engineering 9 () 3-3 doi:.7/93-897/.3. D DAVID PUBLISHIG Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

More information

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N S C I E N C E P A S S I O N T E C H N O L O G Y HVDC Transmission Michael Muhr Graz University of Technology Austria www.tugraz.at 1 Definition HV High Voltage AC Voltage > 60kV 220kV DC Voltage > 60kV

More information

TECHNIQUES AND STANDARD

TECHNIQUES AND STANDARD TRANSFORMER TESTING TECHNIQUES AND STANDARD DEVELOPMENT BY DIEGO M. ROBALINO, PhD, PMP, MEGGER-AVO Training Institute Transformer manufacturers and field operators have always benefitted when new technologies

More information

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH

TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH TRANSFORMERS FAULT ANALYSIS - A MULTIDISCIPLINARY APPROACH Giuseppe Cappai, Bernhard Heinrich, Giuseppe Simioli, Leonardo Trevisan Weidmann Electrical Technology AG, Switzerland Abstract: A large solar

More information

GUJARAT TECHNOLOGICAL UNIVERSITY

GUJARAT TECHNOLOGICAL UNIVERSITY GUJARAT TECHNOLOGICAL UNIVERSITY POWER ELECTRONICS (24) HIGH VOLTAGE ENGINEERING SUBJECT CODE: 2162411 BE 6 th SEMESTER Type of Course: Engineering Science (Electrical) Prerequisite: NA Rationale: The

More information

Comparison of measurement methods for partial discharge measurement in power cables

Comparison of measurement methods for partial discharge measurement in power cables Comparison of measurement methods for partial discharge measurement in power cables L. W. van Veen Supervisor: Prof. dr. J. J. Smit Daily supervisor: Dr.ir. A. Rodrigo Mor April 2014 INTELLIGENT ELECTRICAL

More information

PD ANALYSIS OF GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR DURING FACTORY ASSEMBLY AND SITE COMMISSIONING

PD ANALYSIS OF GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR DURING FACTORY ASSEMBLY AND SITE COMMISSIONING PD ANALYSIS OF GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR DURING FACTORY ASSEMBLY AND SITE COMMISSIONING Andreas F.X. WELSCH*, Siegfried A. RUHLAND* *AREVA Sachsenwerk GmbH - Germany andreas.welsch@areva-td.com

More information

ELEC-E8409 High Voltage Engineering. Condition Monitoring of Power Cables

ELEC-E8409 High Voltage Engineering. Condition Monitoring of Power Cables ELEC-E8409 High Voltage Engineering Condition Monitoring of Power Cables ON-SITE DC MEASUREMENTS Measurements quick and simple, several kv voltage, does not require expensive equipment Insulation Resistance

More information

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS Shashi Kumar 1, Brajesh Kumar Prajapati 2, Vikramjeet Singh 3 1, 2 Students, Electrical Engineering Department Greater Noida

More information