1 Contents Reignition and Restrikes By :- Himanshu Bahirat EE5 : Power System Transients Date:- February, Normal and Abnormal Transients Reignition Reactor Switching Restrike Capacitor switching Three phase capacitor switching Grounded vs. Ungrounded banks Normal and Abnormal Transients Normal Transients Transients during energization Up to p.u. voltages No trapped charges assumed Capacitor Energization inrush currents and voltages Abnormal Transients During denergization Trapped charges Very high voltages and currents Current Chopping Interruption of currents Restrikes and Reignitions Reactor Switching Trapped Energy High Frequency oscillations of reactor voltage Dielectric Breakdown Rs Ls CB Vs SC Reactor
2 Circuit Breaker Current : Reignition Reactor Voltage :Reignition Interruption of circuit current with reignition 9 After Reignition [p.u] 7 5 Reignition : Current Reactor Side recovery Voltage : High frequency [ms] 5 (f ile Reactor_Switching_reignitions_P56.pl; x-v ar t) c:src -REACT [ms] 9. (file Reactor_Switching_reignitions_P56.pl; x-var t) v:react 8.88E [ms] 8.6 (f ile Reactor_Switching_reignitions_P56.pl; x-v ar t) c:src -REACT Reignition : Definition A reignition occurs when a current is interrupted at current zero and then re-establishes itself within one-eight of a power frequency cycle []. 9 Capacitor Switching Switching of normal load current Deenergization at system peak voltage Trapped charge on the capacitor Reignition region 8 6 V Ls CB V - Vs Cap Bank [ms] 5 (file Reactor_Switching_reignitions_P56.pl; x-var t) v:src c:xx-react
3 Capacitor Bank Trapped Voltage and TRV Restrikes and Voltage Escalation 8 6 [ka] 6 Trapped Voltage on Capacitor Bank after deenergization Circuit Breaker TRV [ms] 5 (f ile Restrike_Basics.pl; x-v ar t) v:capb v:capc - [ms] 5 (f ile Restrike_Basics.pl; x-v ar t) v :BUSB -CLRB v :BUSC -CLRC -6 6 [ms] 5 (file Restrike_Basics.pl; x-var t) v:capa c:busa -CLRA Voltage escalation with multiple restrikes Stored Voltage on Capacitor Bank increase with each restrike. ( st.p.u. nd 5 p.u Very high transient current spikes Restrikes : TRV Restrikes :Bus Voltage [ms] 5 (file Restrike_Basics.pl; x-var t) v:busa -CLRA 7.6E-6-7 [ms] 5 (f ile Restrike_Basics.pl; x-v ar t) v :BUSA
4 Restrikes :Ungrounded banks Capacitor Bank Voltage Restrikes :Ungrounded banks Circuit Breaker TRV [ms] 5 (file Restrike_Basics.pl; x-var t) v:capc v:capa 7.6E-6 7.6E-6 Higher trapped voltages than the case of grounded banks. Restrike on phase A results in escalation on phase c. First restrike trapped voltage increases to about.5 p.u - -5 [ms] 5 (file Restrike_Basics.pl; x-var t) v:busa -CLRA v:busc -CLRC 7.6E-6 7.6E-6 Restrike : Definition Restrike and Reignition: Comparison The term restrike is defined as a re-establishment of the current, one-quarter cycle or longer, following interruption of a capacitive current at a normal current zero []. 9 8 Reignition region Restrike region Restrike region [ms] 5 (file Reactor_Switching_reignitions_P56.pl; x-var t) v:src c:xx-react -9 [ms] 5 (file Reactor_Switching_reignitions_P56.pl; x-var t) v:src c:xx-react
5 Conclusions Abnormal transients are a result of trapped charges and energy. Reignitions and restrikes can lead to very magnitude transients. Multiple restrikes can damage circuit breakers and other equipments. Ungrounded Banks result in higher magnitude of transients than grounded banks. Can controlled with use of surge arresters. References. N. E. Dillow, I. B. Johnson, N. R. Schultz, and A. E. Were, "Switching Capacitive Kilovolt-Amperes with Power Circuit Breakers," AIEE Transactions, pp. 88--, 95.. R. D. Garzon, High Voltage Circuit Breakers:Design and Applications: Marcel Dekker, Inc.,996.. Shui-cheong Kam Modelling of Restriking and Reignition Phenomena in Threephase Capacitor and Shunt Reactor Switching. Allan Greenwood. Electrical Transients in Power Systems. Wiley, New York, NY.
Modelling of Restriking and Reignition Phenomena in Three-phase Capacitor and Shunt Reactor Switching
Modelling of Restriking and Reignition Phenomena in Three-phase Capacitor and Shunt Reactor Switching Shui-cheong Kam School of Engineering Systems Queensland University of Technology Brisbane, Australia
More informationTab 2 Voltage Stresses Switching Transients
Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles
More informationEffects of Transient Recovery Voltages on Circuit Breaker Ratings
Effects of Transient Recovery Voltages on Circuit Breaker Ratings Term Project: - EE22 - Power System Transients. Spring 28 Instructor: - Dr. Bruce Mork Team: - Himanshu Bahirat Muhammad Ali Praveen KK
More informationPOWER SYSTEM TRANSIENTS - Switching Overvoltages in Power Systems - Juan A. Martinez-Velasco, Jacinto Martin-Arnedo
SWITCHING OVERVOLTAGES IN POWER SYSTEMS Juan A. Martinez-Velasco Universitat Politècnica de Catalunya, Barcelona, Spain Jacinto Martin-Arnedo Estabanell Energía, Granollers, Spain Keywords: Switching overvoltages,
More informationAlthough shunt capacitors
INSIDE PQ The Trouble With Capacitors Part 1 Switching capacitors seems like a simple proposition, but it can lead to some very interesting problems By R. Fehr, P.E., Engineering Consultant Although shunt
More informationAdi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN
Effectiveness of Surge Capacitors on Transformer Tertiary connected shunt reactors in preventing failures- Field measurements and comparison with Transient study results Pratap G. Mysore, P.E Pratap Consulting
More informationSurge Protection for Ladle Melt Furnaces
Surge Protection for Ladle Melt Furnaces T.J. Dionise 1, S.A. Johnston 2 1 Eaton Electrical Group 130 Commonwealth Drive, Warrendale, PA, USA 15086 Phone: (724) 779-5864 Email: thomasjdionise@eaton.com
More informationEffects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages
Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Waruna Chandrasena, Bruno Bisewski, and Jeff Carrara Abstract-- This paper describes several system
More informationIn power system, transients have bad impact on its
Analysis and Mitigation of Shunt Capacitor Bank Switching Transients on 132 kv Grid Station, Qasimabad Hyderabad SUNNY KATYARA*, ASHFAQUE AHMED HASHMANI**, AND BHAWANI SHANKAR CHOWDHRY*** RECEIVED ON 1811.2014
More informationHIGH VOLTAGE CIRCUIT BREAKERS
HIGH VOLTAGE CIRCUIT BREAKERS Design and Applications Second Edition, Revised and Expanded RUBEN D. GARZON Square D Co. Smyrna, Tennessee MARCEL Ш D E К К E R MARCEL DEKKER, INC. NEW YORK BASEL CONTENTS
More informationTRV OVERVIEW FOR REACTANCE LIMITED FAULTS
The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com TRV OVERVIEW FOR REACTANCE
More informationSwitching Induced Transients:
Switching Induced Transients: Transformer switching is the most commonly performed operation in any power delivery system and most of the times this operation can be performed without any undesirable consequences.
More informationDIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY
DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY Dr. Karthik Reddy VENNA Hong URBANEK Nils ANGER Siemens AG Germany Siemens AG Germany Siemens AG Germany karthikreddy.venna@siemens.com
More informationShunt Reactor Switching
Shunt Reactor Switching Dielectric stresses produced by circuit-breakers to shunt reactors. Presentation made during the IEEE Transformers Committee meeting, Amsterdam, Netherlands, April 2001 Presented
More informationUNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET
UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS Introduction Where fuses are unsuitable or inadequate, protective relays and circuit breakers are used in combination to detect and isolate faults. Circuit breakers
More informationTransient Analysis and Mitigation of Capacitor Bank Switching on a Standalone Wind Farm
ol:1, No:4, 216 Transient Analysis and Mitigation of Capacitor Bank Switching on a Standalone Wind Farm Ajibola O. Akinrinde, Andrew Swanson, Remy Tiako Digital Open Science Index, Electrical and Computer
More informationDelayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines
Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,
More informationFACTORY AND FIELD VERIFICATION TESTS OF CONTROLLED SWITCHING SYSTEM
FACTORY AND FIELD VERIFICATION TESTS OF CONTROLLED SWITCHING SYSTEM by H. Ito, H. Tsutada, H. Kohyama, H. Yamamoto Mitsubishi Electric Corp. H. Wilson, S. Billings Mitsubishi Electric Power Products, Inc.
More information2. Current interruption transients
1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,
More informationA Review Study on Capacitor Switching Transients of HV Transmission Line With VCB
A Review Study on Capacitor Switching Transients of HV Transmission Line With VCB Ashwini S. Dharmadhikari 1 P.G. Student, Department of Electrical Engineering, Government Engineering College, Aurangabad,
More informationDo Capacitor Switching Transients Still Cause Problems?
Do Capacitor Switching Transients Still Cause Problems? Mark McGranaghan We have been evaluating problems related to capacitor switching transients for many years. Capacitor banks have been used on distribution
More informationDEPARTMENT OF EEE QUESTION BANK
DEPARTMENT OF EEE QUESTION BANK (As Per AUT 2008 REGULATION) SUB CODE: EE1004 SUB NAME: POWER SYSTEM TRANSIENTS YEAR : IV SEM : VIII PREPARED BY J.S. MEGAVATHI AP/EEE UNIT-I SWITCHING TRANSIENTS 1.What
More informationA Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks
A Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks C. D. TSIREKIS Hellenic Transmission System Operator Kastoros 72, Piraeus GREECE
More informationModelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad
Day 2 - Session IV-A High Voltage 163 Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad B. Kondala Rao, Gopal Gajjar ABB Ltd., Maneja, Vadodara, India Introduction Circuit breakers play
More informationComparison of switching surges and basic lightning impulse surges at transformer in MV cable grids
Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids Tarik Abdulahović #, Torbjörn Thiringer # # Division of Electric Power Engineering, Department of Energy
More informationSwitching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines
Switching Restrikes in HVAC Cable Lines and Hybrid HVAC Cable/OHL Lines F. Faria da Silva, Claus L. Bak, Per B. Holst Abstract--The disconnection of HV underground cables may, if unsuccessful, originate
More informationHigh voltage engineering
High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency
More informationPower and Instrument Transformer Failures Root Causes and Modern Methods Used to Mitigate Risk. IEEE-NCS,IAS/PES (March 2017)
Power and Instrument Transformer Failures Root Causes and Modern Methods Used to Mitigate Risk Tamer Abdelazim, PhD, PEng Senior Member, IEEE Eaton Corporation 2611 Hopewell Pl NE Calgary, AB T1Y 3Z8 Scott
More informationA TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS
A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS Shashi Kumar 1, Brajesh Kumar Prajapati 2, Vikramjeet Singh 3 1, 2 Students, Electrical Engineering Department Greater Noida
More information5. Black box arc modelling
1 5. Black box arc modelling Circuit-breaker s performance in power system is analysed by representing the circuit-breaker characteristics by a function of electrical parameters such as current/voltage,
More informationTransient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines
Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines Presenter Mark McVey C4/B5.41 INTERNATIONAL COUNCIL ON LARGE
More informationRelay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle
Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Jules Esztergalyos, Senior Member, IEEE Abstract--The measuring technique described in this paper is based on Electro Magnetic
More informationR10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)
R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between
More informationTransient recovery voltage analysis for various current breaking mathematical models: shunt reactor and capacitor bank de-energization study
ARCHIVES OF ELECTRICAL ENGINEERING VOL. 64(3), pp. 441-458 (2015) DOI 10.2478/aee-2015-0034 Transient recovery voltage analysis for various current breaking mathematical models: shunt reactor and capacitor
More informationDelayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines
Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines David K Olson Paul Nyombi Xcel Energy Pratap G Mysore Pratap Consulting Services Minnesota Power Systems Conference St.
More informationHigh-Power Testing of Circuit Breakers
High-Power Testing of Circuit Breakers Prof. Dr. Rene Smeets KEMA T&D Testing The Netherlands rene.smeets@kema.com IEEE Tutorial on Design and Application of High-Voltage Circuit Breakers July 2008 1 categories
More informationGUIDE FOR APPLICATION OF IEC AND IEC
305 GUIDE FOR APPLICATION OF IEC 67-00 AND IEC 67- PART MAKING AND BREAKING TESTS Working Group A3. October 006 GUIDE FOR APPLICATION OF IEC 67-00 AND IEC 67- PART MAKING AND BREAKING TESTS Working Group
More informationSimulation of switching overvoltages of 400 kv shunt reactor. Shunt reactor grounded through a neutral reactor in 400/132 kv highvoltage
TRENDS SIMULATIONS ABSTRACT Bam 400/132 kv substation in Kerman region, Iran, has a 50 MVAR shunt reactor on 400 kv busbar which is grounded through a 128 kvar neutral reactor. The neutral earthing reactor
More informationTHREE-PHASE SHORT-CIRCUIT TESTING OF HIGH-VOLTAGE CIRCUIT-BREAKERS USING SYNTHETIC CIRCUITS
Denis DUFOURNET Head of CERDA High Power and High Voltage Laboratories in Villeurbanne, France. Georges MONTILLET Dead Tank Circuit Breakers Product Manager Development, Charleroi, PA USA. Charleston,
More informationTopics in JNTU Syllabus Modules and Sub Modules Lecture. Basic characteristics L21 T1-Ch4, T2-Ch14 Characteristics. Modification of the control
SESSION PLAN Sl. Topics in JNTU Syllabus Modules and Sub Modules UNIT-III 9 Principal of DC link control Introduction Steady state equivalent circuit of a 2 terminal DC link Lecture L20 Suggested Books
More informationAC High-Voltage Circuit Breakers
AC High-Voltage Circuit Breakers Everything you wanted to know about ac highvoltage circuit breakers but were afraid to ask IEEE Switchgear Committee Portland (Maine, USA), October 2017 Denis Dufournet
More informationAnalysis of a 405 km transmission line with series compensation
Analysis of a 405 km transmission line with series compensation by Dr. Rupert Gouws, North-West University This paper presents an investigative case study and energy efficiency analysis of the 405 km,
More informationPower Quality and Reliablity Centre
Technical Note No. 8 April 2005 Power Quality and Reliablity Centre TRANSIENT OVERVOLTAGES ON THE ELECTRICITY SUPPLY NETWORK CLASSIFICATION, CAUSES AND PROPAGATION This Technical Note presents an overview
More informationVoltage Stability with Mechanically Switched Capacitors using Vacuum Circuit Breakers in the High-Voltage Grid
Voltage Stability with Mechanically Switched Capacitors using Vacuum Circuit Breakers in the High-Voltage Grid Timo Wenzel and Thomas Leibfried nstitute of Electric Energy Systems and High-Voltage Technology
More informationReal Time Monitoring of SF6 Gas Pressure for Optimization Point on Wave Switching of SF6 Circuit Breaker
Real Time Monitoring of SF6 Gas Pressure for Optimization Point on Wave Switching of SF6 Circuit Breaker Ashish Maheshwari 1, Sunil Kumar Singla 2 1 PG Scholar, EIE Department, Thapar University Patiala,
More informationAutotransformer Inadvertent Energization Through Circuit Breakers Gradient Capacitors
Autotransformer Inadvertent Through Circuit Breakers Gradient Capacitors E. Martínez M., E. Godoy A., R. Ruelas T. Abstract- This paper discusses the commissioning experience with a 4/23/34.5 kv (primary/secondary/tertiary)
More informationInternational Journal of Engineering Technology and Scientific Innovation
EFFECT OF BRAKING RESISTOR AND FAULT CURRENT LIMITER ON CIRCUIT BREAKER OPERATION Amir Ghorbani and Allahverdi Azadru Department of Electrical Engineering, Salmas Branch, Islamic Azad University, Salmas,
More informationRelevant Factors to a Statistical Analysis of Overvoltages - Application to Three-Phase Reclosing of Compensated Transmission Lines
Energy and Power Engineering, 2013, 5, 1165-1171 doi:10.4236/epe.2013.54b221 Published Online July 2013 (http://www.scirp.org/journal/epe) Relevant Factors to a Statistical Analysis of Overvoltages - Application
More informationCalculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS
Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering
More informationRevision of TRV Requirements for the Application of Generator Circuit-Breakers
Revision of TRV Requirements for the Application of Generator Circuit-Breakers M. Palazzo, M. Popov, A. Marmolejo and M. Delfanti Abstract-- The requirements imposed on generator circuitbreakers greatly
More informationCahier technique no. 101
Collection Technique... Cahier technique no. 101 The behaviour of SF 6 puffer circuit-breakers under exceptionally severe conditions J.C. Henry G. Perrissin C. Rollier "Cahiers Techniques" is a collection
More informationANALYSIS OF FAULTS INTERRUPTED BY GENERATOR
ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR CIRCUIT BREAKER SF 6 ING. VÁCLAV JEŽEK PROF. ING. ZDENĚK VOSTRACKÝ, DRSC., DR.H.C. Abstract: This article describes the analysis of faults interrupted by generator
More informationCOPYRIGHTED MATERIAL. Index
Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,
More informationA Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage
A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of Hz zero sequence continuous voltage S. Nishiwaki, T. Nakamura, Y.Miyazaki Abstract When an one line grounding fault in a transmission
More informationEstimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation
Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation M. Kondalu1, P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. 1 Kondalu_m@yahoo.com
More informationEstimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation
Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation M. Kondalu1, Dr. P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. 1 Kondalu_m@yahoo.com
More informationPWM DRIVE OVERVOLTAGE TRIPS IN ELECTROCHEMICAL PLANTS
PWM DRIVE OVERVOLTAGE TRIPS IN ELECTROCHEMICAL PLANTS Copyright Material IEEE Paper No. PCIC Paul Buddingh, P.Eng. MEMBER, IEEE ANDRITZ AUTOMATION Ltd. 13700 International Place, Suite 100 Richmond, BC
More informationFERRORESONANCE SIMULATION STUDIES USING EMTP
FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in
More informationSwitching and Fault Transient Analysis of 765 kv Transmission Systems
Third International Conference on Power Systems, Kharagpur, INDIA December >Paper #< Switching and Transient Analysis of 6 kv Transmission Systems D Thukaram, SM IEEE, K Ravishankar, Rajendra Kumar A Department
More informationA3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES
21, rue d'artois, F-75008 Paris http://www.cigre.org A3-308 Session 2004 CIGRÉ HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES G.E. Agafonov, I.V. Babkin, B.E. Berlin Y. F. Kaminsky, S. V. Tretiakov,
More informationANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM
ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM Anna Tjäder Chalmers University of Technology anna.tjader@chalmers.se Math Bollen Luleå University of Technology math.bollen@stri.se ABSTRACT Power
More informationNeutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping
Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice
More informationTopic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017
Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length
More informationGrounding System Theory and Practice
Grounding System Theory and Practice Course No. E-3046 Credit: 3 PDH Grounding System Theory and Practice Velimir Lackovic, Electrical Engineer System grounding has been used since electrical power systems
More informationEffects of Braking Resistor on Circuit Breaker Operations
Effects of Braking Resistor on Circuit Breaker Operations Allahverdi Azadrou Department of Electrical Engineering, Salmas Branch, Islamic Azad University, Salmas, Iran Azadrou.elec@gmail.com Abstract This
More informationA3-00. SPECIAL REPORT FOR SC A3 (High Voltage Equipment) the Netherlands. Special Reporters
CIGRE 2018 A3-00 SPECIAL REPORT FOR SC A3 (High Voltage Equipment) Anton Janssen the Netherlands Tadao Minagawa Japan Special Reporters For the SC A3 Session 2018, three Preferential Subjects have been
More informationANALYSIS, SIMULATION AND TESTING OF TRANSFORMER INSULATION FAILURES RELATED TO SWITCHING TRANSIENTS OVERVOLTAGES.
1, rue d'artois, F-75008 Paris http://www.cigre.org 1-116 Session 00 CIGRÉ ANALYSIS, SIMULATION AND TESTING OF TRANSFORMER INSULATION FAILURES RELATED TO SWITCHING TRANSIENTS OVERVOLTAGES. J.LOPEZ-ROLDAN,
More informationAORC Technical meeting 2014
http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi
More informationDEVELOPMENTS IN EHV/UHV CIRCUIT BREAKER TESTING
DEVELOPMENTS IN EHV/HV CIRCIT BREAKER TESTING ABSTRACT R.P.P. Smeets, A.B. Hofstee, M. Dekker DNV GL, KEMA Laboratories trechtseweg 310, 6812 AR Arnhem, the Netherlands rene.smeets@dnvgl.com Nowadays,
More informationThis is a preview - click here to buy the full publication
CONSOLIDATED VERSION IEC TR 62271-306 Edition 1.1 2018-08 colour inside High-voltage switchgear and controlgear Part 306: Guide to IEC 62271-100, IEC 62271-1 and other IEC standards related to alternating
More informationPotential Risk of Failures in Switching EHV Shunt Reactors in Some One-and-a-half Breaker Scheme Substations
b b International Conference on Power Systems Transients IPST in New Orleans, USA Potential Risk of Failures in Switching EHV Shunt Reactors in Some One-and-a-half Breaker Scheme Substations B. Khodabakhchian,
More informationVOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM
VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM Dolly Chouhan 1, Kasongo Hyacinthe Kapumpa 2, Ajay Chouhan 3 1 M. Tech. Scholar, 2
More informationSolving Customer Power Quality Problems Due to Voltage Magnification
PE-384-PWRD-0-11-1997 Solving Customer Power Quality Problems Due to Voltage Magnification R. A. Adams, Senior Member S. W. Middlekauff, Member Duke Power Company Charlotte, NC 28201 USA E. H. Camm, Member
More informationProtection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin
Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad
More informationFrequency Domain Analysis of Capacitor Transient Overvoltages
Frequency Domain Analysis of Capacitor Transient Overvoltages PATRICIA ROMEIRO DA SILVA JOTA Electrical Engineering Department CEFET-MG Av. Amazonas 7675, 30510-000 Belo Horizonte, Minas Gerais BRAZIL
More informationAbstract. 1 Introduction
Energy Production and Management in the 21st Century, Vol. 1 345 Investigation of the electrical strength of a contact gap of the high voltage live tank circuit breaker 126 kv class using an intelligent
More informationMedium voltage circuit breaker technical guide
IEC 56-1987 - ANSI C37-06 1987 COMPARISON CONTENTS page 1 - Rated voltage 3 2 - Rated isolating level 3 3 - Rated voltage during normal running 4 4 - Allowable short time current 4 5 - Allowable current
More informationInsulation Co-ordination For HVDC Station
Insulation Co-ordination For HVDC Station Insulation Co-ordination Definitions As per IEC 60071 Insulation Coordination is defined as selection of dielectric strength of equipment in relation to the operating
More informationFGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI
FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown
More informationDC Chopper Based Test Circuit for High Voltage DC Circuit Breakers
DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers D. Jovcic*, M.H. Hedayati *University of Aberdeen,UK, d.jovcic@abdn.ac.uk University of Aberdeen,UK, mhh@abdn.ac.uk Keywords: High Voltage
More informationTransients impact on power filter circuit sizing
Computer Applications in Electrical Engineering Vol. 13 2015 s impact on power filter circuit sizing Jurij Warecki, Michał Gajdzica AGH University of Science and Technology 30-059 Kraków, Al. Mickiewicza
More informationPOWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.
POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS. This document may be subject to changes. Contact ARTECHE to confirm the characteristics and availability of the products
More informationVFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES
VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES Shohreh Monshizadeh Islamic Azad University South Tehran Branch (IAU), Tehran,
More informationCAPACITORS are commonly found in distribution
1 Mitigation of Back-to-Back Capacitor Switching Transients on Distribution Circuits M.F. Iizarry-Silvestrini, PREPA T. E. Vélez-Sepúlveda, PREPA Abstract-- In this paper we evaluate three technologies
More informationEE 1402 HIGH VOLTAGE ENGINEERING
EE 1402 HIGH VOLTAGE ENGINEERING Unit 5 TESTS OF INSULATORS Type Test To Check The Design Features Routine Test To Check The Quality Of The Individual Test Piece. High Voltage Tests Include (i) Power frequency
More information10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY
9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor
More informationFUNCTIONS OF CIRCUIT BREAKERS
FUNCTIONS OF CIRCUIT BREAKERS Circuit breakers are designed to carry out the following functions: 1. They must be capable of closing on and carrying full-load currents at rated power factors continuously.
More informationACS 1000 Transformer Failure Investigation. Nathan Schachter, Peng
Investigation Nathan Schachter, Peng Objectives Learn what happened Explain why it happened Discuss solutions Suggest remedies so it does not happen again Prevention is the key to success 2 ACS 1000 VFD
More informationInrush current and Total Harmonic Distortion Transient of Power Transformer with Switching Capacitor Bank
IRACST Engineering Science and Technology: An International Journal (ESTIJ), ISSN: -9, Vol., No., June and Total Harmonic Distortion Transient of Power Transformer with Switching Capacitor Bank ABDELSALAM.
More informationCahier technique no. 193
Collection Technique... Cahier technique no. 193 MV breaking techniques S. Théoleyre "Cahiers Techniques" is a collection of documents intended for engineers and technicians, people in the industry who
More informationTab 8 Surge Arresters
s en em Tab 8 Surge Arresters Si Distribution System Engineering Course Unit 10 2017 Industry Inc., All Rights Reserved Surge Arresters The main protective devices against system transient overvoltages.
More information(2) New Standard IEEE P (3) Core : (4) Windings :
(d) Electrical characteristics (such as short-circuit withstand, commutating reactance, more number of windings, etc); (e) Longer life expectancy; (f) Energy efficiency; (g) more demanding environment.
More informationTransient Recovery Voltage Analysis on a Series Power Flow Control Device
Transient Recovery Voltage Analysis on a Series Power Flow Control Device L. V. Trevisan, G. Cappai, G. Álvarez Cordero Abstract-- In the frame of the Seventh Framework Program, TWENTIES project [1], it
More informationSubstation Insulation Coordination Study
[Type the document title] Substation nsulation Coordination Study MEG Energy Christina Lake Regional Project nsulation Coordination Schematic X0057 15km Lines TWR3 TWR2 TWR1 Afrm1 16 230k Source CCT 100
More informationCURRENT interrupting tests constitute an important part. Medium Voltage Laboratory for Load Break Switch Development. Erik Jonsson and Magne Runde
1 Medium Laboratory for Load Break Switch Development Erik Jonsson and Magne Runde Abstract A new, directly powered laboratory for studying current interruption in medium voltage load break switches has
More informationGreat Northern Transmission Line: Behind the (Electrical) Design
Great Northern Transmission Line: Behind the (Electrical) Design November 8, 2017 Christian Winter, P.E. Minnesota Power Sivasis Panigrahi, P.E. POWER Engineers, Inc. What is the Great Northern Transmission
More informationGIS Disconnector Switching Operation VFTO Study
GIS Disconnector Switching Operation VFTO Study Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki, Marek Florkowski, Marek Fulczyk ABB Corporate Research Center in Krakow Starowislna 13A, 31-038 Krakow,
More informationSection 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services
Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services Introduction The term power quality may take on any one of several definitions. The strict definition of power quality
More informationStudy of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T.
Aalborg Universitet Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T. Published in: Proceedings of the Danish PhD Seminar on Detailed
More informationLong lasting transients in power filter circuits
Computer Applications in Electrical Engineering Vol. 12 2014 Long lasting transients in power filter circuits Jurij Warecki, Michał Gajdzica AGH University of Science and Technology 30-059 Kraków, Al.
More information