Real Time Monitoring of SF6 Gas Pressure for Optimization Point on Wave Switching of SF6 Circuit Breaker

Size: px
Start display at page:

Download "Real Time Monitoring of SF6 Gas Pressure for Optimization Point on Wave Switching of SF6 Circuit Breaker"

Transcription

1 Real Time Monitoring of SF6 Gas Pressure for Optimization Point on Wave Switching of SF6 Circuit Breaker Ashish Maheshwari 1, Sunil Kumar Singla 2 1 PG Scholar, EIE Department, Thapar University Patiala, India 2 Assistant Professor, EIE Department, Thapar University Patiala, India Abstract This paper introduce the real time analysis of sf6 gas pressure for optimizing point on wave switching of sf6 circuit breaker. Circuit Breaker plays an important role in today s growing Indian economy in power systems. It provides protection to transmission equipment incorporated in transmission networks. SF6 Circuit Breaker is very important equipment in Power Systems which is used for up to 1200 kv because of its excellent performance. SF6 Gas plays a vital role to operate the Breaker. Also with the help of SF6 gas contact life of circuit breaker is increased. This paper describes the Operation of SF6 Circuit Breaker in real time due to variation in SF6 gas pressure as SF6 gas is used for arc quenching in the Circuit Breaker to obtain the Point on wave Switching and stress free operation. The paper also describes the Compensation of SF6 Gas Pressure on Point on wave switching method used for Controlled operation of Circuit Breaker. Keywords Circuit Breaker, Sf6 gas, Controlled Switching, Compensation I. INTRODUCTION SF6 has been used as arc quenching and insulating medium for high voltage switchgear systems. The favourable electro technical, chemical and physical characteristics of the gas have considerably influenced the development of the switchgear technology. SF6 is an alternative to other conventional insulating and quenching media such as e.g. oil, and air. The use of SF6 gas considerably increases, in some applications, the efficient utilization of resources in energy transmission and distribution with respect to technology, finances and personnel. At the same time SF6 in comparison to oil reduces the risk of hazard (e.g. Fire, explosion) to personnel and the environment. An overall evaluation considering all ecological, economic, safety and technological aspects has proven that SF6 is still an excellent choice as insulating medium. The existing SF6 technology in the field of energy transmission and distribution is the result of decades of optimization and contributes essentially to the further development of the economically efficient power distribution [1]. The point on wave switching for circuit breakers is installed with an electronic device that monitors the health of the circuit breaker and takes in the command from the user in order to CLOSE or OPEN the breaker on the point of wave of a reference voltage or current. The point on wave is also called as synchronous switching or controlled switching [1] [2]. II. SF6 CIRCUIT BREAKER SF6 circuit breaker is getting a major position in the field of circuit breakers because of its excellent performance. Some of the outstanding properties of SF6 making it desirable to use in power applications such as high dielectric strength, unique arc-quenching ability, excellent thermal stability and good thermal conductivity. The SF6 CB is also dependent on the pressure of two gases Air and SF6. Based on the pressure its mechanism requires certain amount time for actuation. Furthermore the switching phenomenon is largely based on the angles at which the phases are CLOSE or OPEN. By this we mean that sequence and angles of switching of phases for a specific load is important. In this for capacitive load close switching is done on the voltage peak when the current is zero per phase. New applications are being researched that adapts to different angles dynamically based on the load type. Thus the overall circuit breaker for point on wave switching is largely dependent on parameters such as DC voltage to coil, SF6 pressure, Air Pressure, load type, frequency of the reference phase, in this we take R-Phase as a reference [4]. III. CONTROLLED SWITCHING Controlled switching is used for elimination of harmful electrical transients upon planned switching of mainly capacitor banks, shunt reactors and power transformers. The method is also gaining acceptance for re-energizing of EHV transmission lines, and replacing traditional pre-insertion resistors. A key aspect of all controlled switching applications is the precision achieved during making and breaking. Optimization of the switching instant minimizes number of re-ignitions and the corresponding over voltages. Uncontrolled making or breaking can lead to increased stress on the equipment; closing resistors and reactors that were previously used to reduce these stresses may no longer be required. Controlled switching offers an economical alternative. By taking current values into consideration, the control unit optimizes the switching operations of the circuit breaker with reference to current or voltage phase [5]. ISSN: Page 2909

2 IV. POINT ON WAVE SWITCHING (POWS) Point on wave switching (POWS) is a method to eliminate harmful transients with time controlled switching operations. Closing or Opening commands to circuit breaker are delayed in such a way that the closing or the Opening of contact will occur at optimum time related to phase angle. With the help of POWS we can increase the performance and life of the circuit breaker. The following (Figure 1) example illustrates the general operating principle of a system, for energizing of a capacitor bank. In order to avoid switching transients, the making instant in this case shall be at voltage zero. For simplicity, only a single phase is considered [4]. A. Closing Time Figure. 1 Point on Wave Switching Block Diagram [4] V. PARAMETERS IN POWS [4] Time from energizing the closing coil until contact touches the circuit breaker. B. Opening Time Time from energizing the opening coil until contact separation occurs. C. Make/Break Time Time for energizing the closing coil until current starts flowing in the main circuit; Adaptation control adjusts the making instant. D. Pre-arcing Time Time from start of current flow in the main circuit until contact touch. Pre-arcing time = Closing time - Make time E. Arcing Time Time from contact separation until contact separation occurs. F. RDDS The rate of decrease of dielectric strength, circuit breaker characteristics that describe the rate of fall of the voltage withstand at closing of a circuit breaker. G. RRDS Rate of rise of dielectric strength, Circuit breaker characteristic that describes the rate of rise of the voltage withstand at the opening of a circuit breaker. The value of the RRDS defines the minimum arcing time needed for re-ignition free interruption of inductive loads [6]. VI. BENEFITS OF POWS The major benefit of point on wave switching is the reduction of switching transients, with an associated reduction of stresses in the system and its components. Decreased transient stresses, e.g. on a power transformer, will have a positive impact on the ageing of the equipment. Therefore controlled switching may be considered a valuable tool contributing to maximize the useful service life of expensive equipment [7]. In addition, the controlled circuit breaker itself will experience reduced energization currents, which will result in reduced interrupter wear. Optimizing the instant of contact parting also means that life-limiting restrike or Regnition phenomena are avoided or reduced in severity. For capacitor bank, filter bank and shunt reactor applications, the number of load switching operations can therefore typically be doubled before a scheduled overhaul is required, compared to uncontrolled operation [7]. VII. CONTROL SYSTEM The purpose of the Control system is to provide controlled (synchronous) switching commands to the OPEN and CLOSE coils of the circuit breaker. Successful controlled switching reduces the mechanical and electromagnetic stresses endured during normal switching operations by reducing the inrush currents upon closing and re-ignition currents during the opening. A further benefit is that the insertion resistors, as commonly found in air-blast breakers, can be done away with as well as their costly recurring maintenance requirements. Given the well documented effect of fluctuations in operating variables (temperature, pressure, auxiliary voltage, etc.) on the operating time of the breaker, compensation is built into the calculation algorithm, ensuring optimum performance over a wide range. Due to differences in operating times between phases, the system is designed to compute and send phase segregated switching commands to the breaker. Monitoring of inrush and re-ignition currents confirms successful synchronous switching of the breaker. The operating principles use the zero-crossings of a sinusoidal signal; a voltage signal will be used as a reference prior to closing and a current or voltage signal can be used prior to opening. When the breaker characteristics are identical for each phase, then a constant time delay (T/6) exists between synchronous commands in each phase, for example in the R, Y, B sequence (1/3 of a cycle overall). For ungrounded capacitor bank switching, simultaneous switching of the two leading phases is followed by a quarter cycle delay in the switching of the third phase. As soon as a CLOSE command is received, it is blocked and a time delay is initiated, awaiting the first zero-crossing of ISSN: Page 2910

3 the voltage. Should no zero-crossing be detected within the preset time delay, synchronous switching is aborted and a 3- phase random CLOSE is executed. Should a zero-crossing occur within the preset delay and no further failures are detected, synchronous CLOSE commands to each phase are issued after the computed time delays. The computed time delays are measured from the reference zero-crossing and compensated for variable effects and variations in the breaker characteristics of each phase. Sequencing of individual phase is monitored to insure proper sequencing at the breaker coils. Sequencing of individual phase commands is monitored. Output control circuits are monitored for timing analysis, if a sequence error is detected, synchronous control is aborted and a 3-phase random control switching is executed. Following Figures 2 and 3 shows the opening operation and closing operation with a control system respectively. The functional design of the OPEN operation is the same as that for CLOSE with the variation that a current or a voltage zero-crossing can be used as the reference signal and that reignited currents are monitored [6] [8]. Figure.2 Opening operation of circuit breaker with a control system [6] 1 - Current zero crossing 2 - Phase R current 3 - Open command input 4 - Open output (power output to open CB coil) 5 - Breaker Contacts Ty - Delay to achieve breaker synchronization (calculated) Topen - Mechanical breaker opening time (predicted) Tarc - Arcing delay (planned and Para metered) Figure.3 Closing operation of circuit breaker with a control system [6] 1 - Voltage zero crossing 2 - Phase Neutral Voltage 3 - Close command input 4 - Close output (power output to close CB coil) 5 - Breaker Contacts Tx - Delay to achieve breaker synchronization (calculated) Tferm - Mechanical breaker closing time (predicted) Tdel - Pre-arcing delay (planned and Para metered) VIII. COMPENSATION IN CONTROL SYSTEM When the circuit breaker has a well-known variation in its behaviour, with variations in external conditions, corrections for these can be made. Verification of systematic mechanical variations depending upon varying ambient conditions like influence of idle time, change of temperature, change of coil voltage, change of air pressure and change of SF6 gas pressure. Variations upon an ambient parameter variation can be compensated for by suitable transducers. The need for compensation will depend on the degree of variation and the actual operating conditions. For frequent operation adaptation control may be good enough to gradually take small variations into account. The system can compensate the circuit breaker s expected operating time for variations in temperature, pressures, SF6 gas pressure and auxiliary voltage supply. In this paper we only discuss SF6 gas pressure compensation for real time monitoring of sf6 gas pressure for optimization point on wave switching of sf6 circuit breaker [2]. IX. SF6 GAS COMPENSATION SF6 gas is the ideal media for the arc interruption and dielectric strength. This compensation comes into action during the closing operation; at close time SF6 gas rated pressure is 7 Kg/cm² at C temperature. Real time monitoring of SF6 gas pressure is very important for the compensation provided in the system. In table I we provide the sf6 gas compensation with the help of windows based software in this we set breaker close time of 80 msec for each phase (R, Y, B) and sf6 gas pressure is varied. In this the ideal operation is performed when sf6 gas pressure in 7 kg/cm² at C temperature As the temperature increases the sf6 gas pressure should be decreased [9]. TABLE I SF6 GAS PRESSURE COMPENSATION FOR BREAKER CLOSE TIME sf6 (kg/cm²) Breaker CLOSE time R (msec) Y (msec) B (msec) X. RESULTS OF SF6 GAS COMPENSATION ISSN: Page 2911

4 SF6 circuit breaker gives the best results during closing and opening that s why they are widely used in the power system The best about this circuit breaker is SF6 gas which quenches the arc in very less time among all other circuit breaker. Table II describes the final results we obtained when we set the coil voltage at 110 Volts and we varied the close angle i e and and as shown in Figure and 3, the error is very less i e when our closing angle is breaker closing pulse is at voltage peak and when our angle is breaker closing pulse is at voltage zero. In this we take R- Phase for reference. DC1 Voltage TABLE III SF6 GAS PRESSURE COMPENSATION SF6 Pressure R (kg/cm²) R Y B Expected Time (msec) Observed Time (msec) Error Figure. 5 R-Phase wave form when closing angle is 0 As seen from the Figure 4, when we set the closing angle at 90 degrees we get close command at the voltage peak which shows its 90 degrees. Same case in Figure 5 angle is changed from 90 degree to 0 degree and we get close command exact at 0 degrees. This shows Sf6 gas pressure compensation comes into action when we perform closing operation and gives accurate results even when we have less pressure In Figure 6, it can be seen that the expected time and observed time are very close to each other so the error is reduced to a minimum. Thus, after giving the close command to the circuit breaker so it will be closed at the expected time. Figure 4 and 5 gives the resulted wave form of the Sf6 gas pressure compensation. Fig. 6 R-Phase Close Time Characteristics with SF6 gas compensation Figure. 4 R- Phase waveform when closing angle is 90 XI. CONCLUSIONS This paper presents a method for setting the close and open targets in a controlled switching system based on sf6 gas pressure compensation which is provided with the help of windows based configuration software. The paper also highlights the importance of the sf6 gas pressure compensation as sf6 gas pressure is not in a healthy state, we cannot achieve point on wave switching. To achieve the point on wave switching in circuit breakers there are various types of compensations like idle time compensation, coil voltage compensation, temperature compensation etc. which are not described in this paper. This paper is only meant for the sf6 gas pressure compensation. Furthermore, it was confirmed, in connection with the variations in closing or opening time in response to the operating conditions, that the operating characteristics could be stably compensated over a long period by using the characteristics obtained from the factory test. ISSN: Page 2912

5 ACKNOWLEDGMENT This work is supported by the CG Global R&D Centre Crompton Greaves Ltd. The grateful acknowledgement is made to the contributions of Upendra Kambli, Neelabh Trivedi, Mayank Shukla, Rohit Jain, Rohit Arora and Roshan Joseph for giving their support in the development and testing of the work described in this paper. REFERENCES [1] F Jun Liu; Huang, G.M.; Zhiying Ma; Geng, Yingsan, "A Novel Smart High-Voltage Circuit Breaker for Smart Grid Applications," Smart Grid, IEEE Transactions on, vol.2, no.2, pp.254,264, June 2011 [2] Namjoshi Y, Auto-Calibration of a Sf6 Circuit Breaker for Point-onwave Switching an Application of Signal processing to Switchgear, International Conference on Electrical and Electronics Engineering, Goa, pp , 2013 [3] Sharma S ; Bhardwaj H, How to maintain sf6 circuit breaker, International Journal of Scientific Research Engineering &Technology, vol. 1, pp March 2012 [4] Condition monitoring of SF6 circuit breakers. by U. Akesson etal., CIGRE 1992 Session, Paper , 8 pages [5] Tsudata, H Controlled Switching System for Capacitor Bank and Transformer Switching In Electrical Engineering [6] ABB, Controlled Switching with Switchsync, Presentation manual Edition [7] H Ito Controlled Switching Technologies, State-of-the-Art, Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES, Pages , Vol. 2, 2002 [8] Controlled switching technologies, state-of-the-art, Ito, H.; Transmission and Distribution Conference and Exhibition 2002: Asia Pacific. IEEE/PES, Volume: 2, Publication Year: 2002, Page(s): vol.2 [9] Catalogue publication 1HSM en Controlled Switching, Buyer s Guide, Application Guide Edition , ISSN: Page 2913

FACTORY AND FIELD VERIFICATION TESTS OF CONTROLLED SWITCHING SYSTEM

FACTORY AND FIELD VERIFICATION TESTS OF CONTROLLED SWITCHING SYSTEM FACTORY AND FIELD VERIFICATION TESTS OF CONTROLLED SWITCHING SYSTEM by H. Ito, H. Tsutada, H. Kohyama, H. Yamamoto Mitsubishi Electric Corp. H. Wilson, S. Billings Mitsubishi Electric Power Products, Inc.

More information

Abstract. 1 Introduction

Abstract. 1 Introduction Energy Production and Management in the 21st Century, Vol. 1 345 Investigation of the electrical strength of a contact gap of the high voltage live tank circuit breaker 126 kv class using an intelligent

More information

CIRCUIT BREAKERS TRANSIENT REDUCTION BY USING A DEDICATED CONTROLLED SWITCHING SYSTEM

CIRCUIT BREAKERS TRANSIENT REDUCTION BY USING A DEDICATED CONTROLLED SWITCHING SYSTEM CIRCUIT BREAKERS TRANSIENT REDUCTION BY USING A DEDICATED CONTROLLED SWITCHING SYSTEM Virginia Ivanov Maria Brojboiu Sergiu Ivanov University of Craiova Faculty of Electrical Engineering Faculty of Electrical

More information

Although shunt capacitors

Although shunt capacitors INSIDE PQ The Trouble With Capacitors Part 1 Switching capacitors seems like a simple proposition, but it can lead to some very interesting problems By R. Fehr, P.E., Engineering Consultant Although shunt

More information

Shunt Reactor Switching

Shunt Reactor Switching Shunt Reactor Switching Dielectric stresses produced by circuit-breakers to shunt reactors. Presentation made during the IEEE Transformers Committee meeting, Amsterdam, Netherlands, April 2001 Presented

More information

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS Shashi Kumar 1, Brajesh Kumar Prajapati 2, Vikramjeet Singh 3 1, 2 Students, Electrical Engineering Department Greater Noida

More information

DC current interruption tests with HV mechanical DC circuit breaker

DC current interruption tests with HV mechanical DC circuit breaker http: //www.cigre.org CIGRÉ A3/B4-124 CIGRÉ Winnipeg 2017 Colloquium Study Committees A3, B4 & D1 Winnipeg, Canada September 30 October 6, 2017 DC current interruption tests with HV mechanical DC circuit

More information

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice

More information

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Title MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING Training Duration 5 days Training Date MV, HV and EHV Switchgear Testing & Commissioning 5 21 25 Sep $3,750 Dubai, UAE In any of the 5 star

More information

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad Day 2 - Session IV-A High Voltage 163 Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad B. Kondala Rao, Gopal Gajjar ABB Ltd., Maneja, Vadodara, India Introduction Circuit breakers play

More information

CONTENTS. 1. Introduction Generating Stations 9 40

CONTENTS. 1. Introduction Generating Stations 9 40 CONTENTS 1. Introduction 1 8 Importance of Electrical Energy Generation of Electrical Energy Sources of Energy Comparison of Energy Sources Units of Energy Relationship among Energy Units Efficiency Calorific

More information

A Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks

A Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks A Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks C. D. TSIREKIS Hellenic Transmission System Operator Kastoros 72, Piraeus GREECE

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi

More information

HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS

HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS Enrique PÉREZ Santiago REMENTERIA Aitor LAKA Arteche Spain Arteche Spain Ingeteam Power Technology-Spain ep@arteche.es sr@arteche.es Aitor.Laka@ingeteam.com

More information

A SEMINAR REPORT PRESENT ON AIR BLAST CIRCUIT BREAKER

A SEMINAR REPORT PRESENT ON AIR BLAST CIRCUIT BREAKER A SEMINAR REPORT PRESENT ON AIR BLAST CIRCUIT BREAKER Submitted by :- submitted to:- Tazinder singh E.E. 3 rd year (BBDNIIT) 1 Acknowledgement 2 content Topic Page no. Air blast circuit breaker 04 Principle

More information

Grounding System Theory and Practice

Grounding System Theory and Practice Grounding System Theory and Practice Course No. E-3046 Credit: 3 PDH Grounding System Theory and Practice Velimir Lackovic, Electrical Engineer System grounding has been used since electrical power systems

More information

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY Dr. Karthik Reddy VENNA Hong URBANEK Nils ANGER Siemens AG Germany Siemens AG Germany Siemens AG Germany karthikreddy.venna@siemens.com

More information

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR CIRCUIT BREAKER SF 6 ING. VÁCLAV JEŽEK PROF. ING. ZDENĚK VOSTRACKÝ, DRSC., DR.H.C. Abstract: This article describes the analysis of faults interrupted by generator

More information

Electrical Engineering. Power Systems. Comprehensive Theory with Solved Examples and Practice Questions. Publications

Electrical Engineering. Power Systems. Comprehensive Theory with Solved Examples and Practice Questions. Publications Electrical Engineering Power Systems Comprehensive Theory with Solved Examples and Practice Questions Publications Publications MADE EASY Publications Corporate Office: 44-A/4, Kalu Sarai (Near Hauz Khas

More information

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453 www.ijecs.in International Journal Of Engineering And Computer Science ISSN:2319-7242 Volume 3 Issue 6 June, 2014 Page No. 6453-6457 Role of Fault Current Limiter in Power System Network Poornima G P.1,

More information

2. Current interruption transients

2. Current interruption transients 1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,

More information

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES

A3-308 HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES 21, rue d'artois, F-75008 Paris http://www.cigre.org A3-308 Session 2004 CIGRÉ HIGH SPEED GROUNDING SWITCH FOR EXTRA-HIGH VOLTAGE LINES G.E. Agafonov, I.V. Babkin, B.E. Berlin Y. F. Kaminsky, S. V. Tretiakov,

More information

FUNCTIONS OF CIRCUIT BREAKERS

FUNCTIONS OF CIRCUIT BREAKERS FUNCTIONS OF CIRCUIT BREAKERS Circuit breakers are designed to carry out the following functions: 1. They must be capable of closing on and carrying full-load currents at rated power factors continuously.

More information

Switching and Fault Transient Analysis of 765 kv Transmission Systems

Switching and Fault Transient Analysis of 765 kv Transmission Systems Third International Conference on Power Systems, Kharagpur, INDIA December >Paper #< Switching and Transient Analysis of 6 kv Transmission Systems D Thukaram, SM IEEE, K Ravishankar, Rajendra Kumar A Department

More information

LV/MV/HV CIRCUIT BREAKERS (SWITCH GEAR) DESIGN, INSPECTION, MAINTENANCE, REPAIR & TROUBLESHOOTING

LV/MV/HV CIRCUIT BREAKERS (SWITCH GEAR) DESIGN, INSPECTION, MAINTENANCE, REPAIR & TROUBLESHOOTING Training Title LV/MV/HV CIRCUIT BREAKERS (SWITCH GEAR) DESIGN, INSPECTION, MAINTENANCE, REPAIR & TROUBLESHOOTING Training Duration 5 days Training Venue and Dates LV/MV/HV Circuit Breakers (Switchgear):

More information

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY 9. INTRODUCTION Control Cabling The protection and control equipment in power plants and substations is influenced by various of environmental conditions. One of the most significant environmental factor

More information

SIMPLE SOLUTIONS FOR IMPROVING LIFE OF BREAKERS USED IN TRANSMISSION AND DISTRIBUTION SYSTEMS

SIMPLE SOLUTIONS FOR IMPROVING LIFE OF BREAKERS USED IN TRANSMISSION AND DISTRIBUTION SYSTEMS SIMPLE SOLUTIONS FOR IMPROVING LIFE OF BREAKERS USED IN TRANSMISSION AND DISTRIBUTION SYSTEMS Dr. V. R. Kanetkar and Mr. K. E. Shinde Shreem Electric Limited, Jaysingpur Dist. Kolhapur, Maharashtra State

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

HIGH VOLTAGE CIRCUIT BREAKERS

HIGH VOLTAGE CIRCUIT BREAKERS HIGH VOLTAGE CIRCUIT BREAKERS Design and Applications Second Edition, Revised and Expanded RUBEN D. GARZON Square D Co. Smyrna, Tennessee MARCEL Ш D E К К E R MARCEL DEKKER, INC. NEW YORK BASEL CONTENTS

More information

Revision of TRV Requirements for the Application of Generator Circuit-Breakers

Revision of TRV Requirements for the Application of Generator Circuit-Breakers Revision of TRV Requirements for the Application of Generator Circuit-Breakers M. Palazzo, M. Popov, A. Marmolejo and M. Delfanti Abstract-- The requirements imposed on generator circuitbreakers greatly

More information

Copyright 2008 IEEE.

Copyright 2008 IEEE. Copyright 2008 IEEE. Paper presented at IEEE PES 2008 T&D Chicago meeting, Apr. 21 24, 2008 This material is posted here with permission of the IEEE. Such permission of the IEEE does not in any way imply

More information

Transformers TRANS FORM ERS

Transformers TRANS FORM ERS Transformers TRANS FORM ERS Meiden Transformers are standard design, standard quality. Our Factories on world-wide supply chain Since its founding in 1897 Meidensha Corporation has not only built up a

More information

Preface...x Chapter 1 Electrical Fundamentals

Preface...x Chapter 1 Electrical Fundamentals Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5

More information

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21 Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive

More information

5. Black box arc modelling

5. Black box arc modelling 1 5. Black box arc modelling Circuit-breaker s performance in power system is analysed by representing the circuit-breaker characteristics by a function of electrical parameters such as current/voltage,

More information

Transformer energisation after network blackout

Transformer energisation after network blackout Transformer energisation after network blackout Impact on network restoration and improvement of its process ABSTRACT According to ENTSO-E Network policy 5, responsibility for system restoration after

More information

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION R.Rahnavard 1, 2 M.Valizadeh 1 A.A.B.Sharifian 2 S.H.Hosseini 1 rerahnavard@gmail.com mj_valizad@yahoo.com hosseini@tabrizu.ac.ir

More information

Do Capacitor Switching Transients Still Cause Problems?

Do Capacitor Switching Transients Still Cause Problems? Do Capacitor Switching Transients Still Cause Problems? Mark McGranaghan We have been evaluating problems related to capacitor switching transients for many years. Capacitor banks have been used on distribution

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

In power system, transients have bad impact on its

In power system, transients have bad impact on its Analysis and Mitigation of Shunt Capacitor Bank Switching Transients on 132 kv Grid Station, Qasimabad Hyderabad SUNNY KATYARA*, ASHFAQUE AHMED HASHMANI**, AND BHAWANI SHANKAR CHOWDHRY*** RECEIVED ON 1811.2014

More information

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER Rajesh Kr. Ahuja 1, Aasha Chauhan 2, Sachin Sharma 3 Rajesh Kr. Ahuja Faculty, Electrical & Electronics Engineering Dept.

More information

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP IJSTE - International Journal of Science Technology & Engineering Volume 3 Issue 2 August 216 ISSN (online): 2349-784X Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

More information

Medium voltage products. Field Application Support Analysis and calculations in Medium-Voltage electrical networks

Medium voltage products. Field Application Support Analysis and calculations in Medium-Voltage electrical networks Medium voltage products Field Application Support Analysis and calculations in Medium-Voltage electrical networks Concept The electrical installation of an industrial site is a complex structure. Analyzing

More information

DEPARTMENT OF EEE QUESTION BANK

DEPARTMENT OF EEE QUESTION BANK DEPARTMENT OF EEE QUESTION BANK (As Per AUT 2008 REGULATION) SUB CODE: EE1004 SUB NAME: POWER SYSTEM TRANSIENTS YEAR : IV SEM : VIII PREPARED BY J.S. MEGAVATHI AP/EEE UNIT-I SWITCHING TRANSIENTS 1.What

More information

Electrical Equipment Condition Assessment

Electrical Equipment Condition Assessment Feature Electrical Equipment Condition Assessment Using On-Line Solid Insulation Sampling Importance of Electrical Insulation Electrical insulation plays a vital role in the design and operation of all

More information

FERRORESONANCE SIMULATION STUDIES USING EMTP

FERRORESONANCE SIMULATION STUDIES USING EMTP FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in

More information

High-Voltage Test Techniques

High-Voltage Test Techniques High-Voltage Test Techniques Dieter Kind Kurt Feser 2nd Revised and Enlarged Edition With 211 Figures and 12 Laboratory Experiments Translated from the German by Y. Narayana Rao Professor of Electrical

More information

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider

Shunt Reactors. Global Top Energy, Machinery & Plant Solution Provider Shunt Reactors Global Top Energy, Machinery & Plant Solution Provider Our Business Brief introduction of Hyosung Power & Industrial Systems PG While Hyosung is an established name for world-class electrical

More information

HV AC TESTING OF SUPER-LONG CABLES

HV AC TESTING OF SUPER-LONG CABLES HV AC TESTING OF SUPER-LONG CABLES Stefan SCHIERIG, (Germany), schierig@highvolt.de Peter COORS, (Germany), coors@highvolt.de Wolfgang HAUSCHILD, IEC, CIGRE, (Germany), hauschild@highvolt.de ABSTRACT The

More information

EE030: Circuit Breaker & Switchgears Inspection, Maintenance, Design, Repair & Troubleshooting

EE030: Circuit Breaker & Switchgears Inspection, Maintenance, Design, Repair & Troubleshooting EE030: Circuit Breaker & Switchgears Inspection, Maintenance, Design, Repair & Troubleshooting EE030 Rev.001 CMCT COURSE OUTLINE Page 1 of 6 Training Description: This course is designed to update participants

More information

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers International Conference on Power System Transients IPST 23 in New Orleans, USA Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

More information

VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK

VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK VALIDATION THROUGH REAL TIME SIMULATION OF A CONTROL AND PROTECTION SYSTEM APPLIED TO A RESONANT EARTHED NEUTRAL NETWORK Eduardo MARTÍNEZ eduardo_martinez@fcirce.es Samuel BORROY sborroy@fcirce.es Laura

More information

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum International Journal of Scientific & Engineering Research, Volume 7, Issue 4, April-216 628 REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD Abhilash.G.R Smitha K.S Vocational Teacher

More information

Upgrading Your Electrical Distribution System To Resistance Grounding

Upgrading Your Electrical Distribution System To Resistance Grounding Upgrading Your Electrical Distribution System To Resistance Grounding The term grounding is commonly used in the electrical industry to mean both equipment grounding and system grounding. Equipment grounding

More information

Volume I Issue VI 2012 September-2012 ISSN

Volume I Issue VI 2012 September-2012 ISSN A 24-pulse STATCOM Simulation model to improve voltage sag due to starting of 1 HP Induction-Motor Mr. Ajay Kumar Bansal 1 Mr. Govind Lal Suthar 2 Mr. Rohan Sharma 3 1 Associate Professor, Department of

More information

STATCOM WITH POD CONTROLLER FOR REACTIVE POWER COMPENSATION Vijai Jairaj 1, Vishnu.J 2 and Sreenath.N.R 3

STATCOM WITH POD CONTROLLER FOR REACTIVE POWER COMPENSATION Vijai Jairaj 1, Vishnu.J 2 and Sreenath.N.R 3 STATCOM WITH POD CONTROLLER FOR REACTIVE POWER COMPENSATION Vijai Jairaj 1, Vishnu.J 2 and Sreenath.N.R 3 1 PG Student [Electrical Machines], Department of EEE, Sree Buddha College of Engineering Pattoor,

More information

I. INTRODUCTION IJSRST Volume 3 Issue 2 Print ISSN: Online ISSN: X

I. INTRODUCTION IJSRST Volume 3 Issue 2 Print ISSN: Online ISSN: X 2017 IJSRST Volume 3 Issue 2 Print ISSN: 2395-6011 Online ISSN: 2395-602X National Conference on Advances in Engineering and Applied Science (NCAEAS) 16 th February 2017 In association with International

More information

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN Effectiveness of Surge Capacitors on Transformer Tertiary connected shunt reactors in preventing failures- Field measurements and comparison with Transient study results Pratap G. Mysore, P.E Pratap Consulting

More information

DEVELOPMENTS IN EHV/UHV CIRCUIT BREAKER TESTING

DEVELOPMENTS IN EHV/UHV CIRCUIT BREAKER TESTING DEVELOPMENTS IN EHV/HV CIRCIT BREAKER TESTING ABSTRACT R.P.P. Smeets, A.B. Hofstee, M. Dekker DNV GL, KEMA Laboratories trechtseweg 310, 6812 AR Arnhem, the Netherlands rene.smeets@dnvgl.com Nowadays,

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads Ponananthi.V, Rajesh Kumar. B Final year PG student, Department of Power Systems Engineering, M.Kumarasamy College of

More information

Weidong Zhang, May.9, 2016 Development of Pre-Insertion Resistor for an 800kV GIS Circuit Breaker. ABB Group May 11, 2016 Slide 1

Weidong Zhang, May.9, 2016 Development of Pre-Insertion Resistor for an 800kV GIS Circuit Breaker. ABB Group May 11, 2016 Slide 1 Weidong Zhang, May.9, 2016 Development of Pre-Insertion Resistor for an 800kV GIS Circuit Breaker Group Slide 1 Background & Objects EHV/UHV system: Widely application for long distance transmission from

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

POWER SYSTEM TRANSIENTS - Switching Overvoltages in Power Systems - Juan A. Martinez-Velasco, Jacinto Martin-Arnedo

POWER SYSTEM TRANSIENTS - Switching Overvoltages in Power Systems - Juan A. Martinez-Velasco, Jacinto Martin-Arnedo SWITCHING OVERVOLTAGES IN POWER SYSTEMS Juan A. Martinez-Velasco Universitat Politècnica de Catalunya, Barcelona, Spain Jacinto Martin-Arnedo Estabanell Energía, Granollers, Spain Keywords: Switching overvoltages,

More information

GIS Disconnector Switching Operation VFTO Study

GIS Disconnector Switching Operation VFTO Study GIS Disconnector Switching Operation VFTO Study Mariusz Stosur, Marcin Szewczyk, Wojciech Piasecki, Marek Florkowski, Marek Fulczyk ABB Corporate Research Center in Krakow Starowislna 13A, 31-038 Krakow,

More information

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology Condition Assessment of High Voltage Insulation in Power System Equipment R.E. James and Q. Su The Institution of Engineering and Technology Contents Preface xi 1 Introduction 1 1.1 Interconnection of

More information

Universal Protection System for Ac Industrial Motors

Universal Protection System for Ac Industrial Motors Universal Protection System for Ac Industrial Motors Mr. Ibrahim Rawat 1, Mr. Saurabh Patel 2, Mr. Akshil Chauhan 3, Mr. Nisargkumar Parmar 4, Mr. Sunil Malival 5 1234 B.E Students, ITM Universe, Vadodara

More information

Circuit Breaker. By Shashidhar kasthala Assistant Professor Indian Naval Academy

Circuit Breaker. By Shashidhar kasthala Assistant Professor Indian Naval Academy Circuit Breaker By Shashidhar kasthala Assistant Professor Indian Naval Academy In power system, various circuits (e.g., transmission lines, distributors, generating plants etc.) will be switch on-off

More information

DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK

DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK 1 Hitesh Kumar Yadav, 2 Mr.S.M.Deshmukh 1 M.Tech Research Scholar, EEE Department, DIMAT Raipur (Chhattisgarh), India 2 Asst. Professor, EEE Department,

More information

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP Kiran V. Natkar 1, Naveen Kumar 2 1 Student, M.E., Electrical Power System, MSS CET/ Dr. B.A.M. University, (India) 2 Electrical Power System,

More information

Design and Implementation of Economical Power Factor Transducer

Design and Implementation of Economical Power Factor Transducer Design and Implementation of Economical Power Factor Transducer Prof. P. D. Debre Akhilesh Menghare Swapnil Bhongade Snehalata Thote Sujata Barde HOD (Dept. of EE), RGCER, Nagpur RGCER, Nagpur RGCER, Nagpur

More information

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS Introduction Where fuses are unsuitable or inadequate, protective relays and circuit breakers are used in combination to detect and isolate faults. Circuit breakers

More information

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding

More information

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax : NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE

More information

Electrical Power Systems

Electrical Power Systems Electrical Power Systems CONCEPT, THEORY AND PRACTICE SECOND EDITION SUBIR RAY Professor MVJ College of Engineering Bangalore PHI Learning Pfcte tofm Delhi-110092 2014 Preface xv Preface to the First Edition

More information

ON-LINE PARTIAL DISCHARGE MEASUREMENT AND CONTROL

ON-LINE PARTIAL DISCHARGE MEASUREMENT AND CONTROL REPRINT 19TH INTERNATIONAL CONFERENCE AND EXHIBITION ON ELECTRICITY DISTRIBUTION REED MESSE WIEN CONGRESS CENTER, VIENNA MAY 21-24, 2007 ON-LINE PARTIAL DISCHARGE MEASUREMENT AND CONTROL Kristian Winter,

More information

Webinar: An Effective Arc Flash Safety Program

Webinar: An Effective Arc Flash Safety Program Webinar: An Effective Arc Flash Safety Program Daleep Mohla September 10 th, 2015: 2pm ET Agenda Arc Flash Defined and Quantified NFPA 70E / CSA Z 462 - Recent Updates What is the ANSI Z10 Hierarchy of

More information

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

FGJTCFWPKPUVKVWVGQHVGEJPQNQI[ FGRCTVOGPVQHGNGEVTKECNGPIKPGGTKPI VGG246JKIJXQNVCIGGPIKPGGTKPI FGJTFWP"KPUKWG"QH"GEJPQNQI[" FGRTOGP"QH"GNGETKEN"GPIKPGGTKPI" GG"46"JKIJ"XQNIG"GPIKPGGTKPI Resonant Transformers: The fig. (b) shows the equivalent circuit of a high voltage testing transformer (shown

More information

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY A PATH FOR HORIZING YOUR INNOVATIVE WORK SPECIAL ISSUE FOR NATIONAL LEVEL CONFERENCE "Technology Enabling Modernization

More information

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation

Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation Impact of Harmonic Resonance and V-THD in Sohar Industrial Port C Substation R. S. Al Abri, M. H. Albadi, M. H. Al Abri, U. K. Al Rasbi, M. H. Al Hasni, S. M. Al Shidi Abstract This paper presents an analysis

More information

Accurate Current Measurement Transducer for Relaying Purpose

Accurate Current Measurement Transducer for Relaying Purpose Accurate Current Measurement Transducer for Relaying Purpose Ashish S. Paramane 1, Dr.P.K.Katti 2 Department of Electrical Engineering Dr. Babasaheb Ambedkar Technological University, Lonere, Maharashtra

More information

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS M. Kondalu, Dr. P.S. Subramanyam Electrical & Electronics Engineering, JNT University. Hyderabad. Joginpally B.R. Engineering

More information

Circuit Breaker Based Feeder Pillar

Circuit Breaker Based Feeder Pillar IJIRST International Journal for Innovative Research in Science & Technology Volume Issue 09 February 06 ISSN (online): 349-600 Circuit Breaker Based Feeder Pillar Neha A. Ninave Nikita M. Nimbulkar Minal

More information

GUIDE FOR APPLICATION OF IEC AND IEC

GUIDE FOR APPLICATION OF IEC AND IEC 305 GUIDE FOR APPLICATION OF IEC 67-00 AND IEC 67- PART MAKING AND BREAKING TESTS Working Group A3. October 006 GUIDE FOR APPLICATION OF IEC 67-00 AND IEC 67- PART MAKING AND BREAKING TESTS Working Group

More information

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation M. Kondalu1, Dr. P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. 1 Kondalu_m@yahoo.com

More information

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation M. Kondalu1, P.S. Subramanyam2 Electrical & Electronics Engineering, JNT University. Hyderabad. 1 Kondalu_m@yahoo.com

More information

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION David TOPOLANEK Petr TOMAN Michal PTACEK Jaromir DVORAK Brno University of Technology - Czech

More information

PRACTICAL CONSIDERATIONS FOR CONTROLLED SWITCHING OF POWER TRANSFORMERS

PRACTICAL CONSIDERATIONS FOR CONTROLLED SWITCHING OF POWER TRANSFORMERS Seminar / Workshop on Controlled Switching Possible Benefits for Transformers Applications PRACTICAL CONSIDERATIONS FOR CONTROLLED SWITCHING OF POWER TRANSFORMERS Esteban Portales Yvon Filion André Mercier

More information

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection SolidGround TM GIC grid stability and harmonics mitigation

More information

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit Validation of a Power Transformer Model for Ferroresonance with System Tests on a 4 kv Circuit Charalambos Charalambous 1, Z.D. Wang 1, Jie Li 1, Mark Osborne 2 and Paul Jarman 2 Abstract-- National Grid

More information

A3-00. SPECIAL REPORT FOR SC A3 (High Voltage Equipment) the Netherlands. Special Reporters

A3-00. SPECIAL REPORT FOR SC A3 (High Voltage Equipment) the Netherlands. Special Reporters CIGRE 2018 A3-00 SPECIAL REPORT FOR SC A3 (High Voltage Equipment) Anton Janssen the Netherlands Tadao Minagawa Japan Special Reporters For the SC A3 Session 2018, three Preferential Subjects have been

More information

Power Systems Modelling and Fault Analysis

Power Systems Modelling and Fault Analysis Power Systems Modelling and Fault Analysis Theory and Practice Nasser D. Tleis BSc, MSc, PhD, CEng, FIEE AMSTERDAM BOSTON HEIDELBERG LONDON NEW YORK OXFORD PARIS SAN DIEGO SAN FRANCISCO SINGAPORE SYDNEY

More information

Medium voltage circuit breaker technical guide

Medium voltage circuit breaker technical guide IEC 56-1987 - ANSI C37-06 1987 COMPARISON CONTENTS page 1 - Rated voltage 3 2 - Rated isolating level 3 3 - Rated voltage during normal running 4 4 - Allowable short time current 4 5 - Allowable current

More information

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company

P2 Power Solutions Pvt. Ltd. P2 Power Magnetics. Quality Power within your Reach. An ISO 9001:2008 Company P2 Power Solutions Pvt. Ltd. An ISO 9001:2008 Company Quality Power within your Reach P2 Power Magnetics P2 Power Solutions Pvt. Ltd. P2 Power Solutions Pvt. Ltd. provides EMC and power quality solutions,

More information

This is a preview - click here to buy the full publication

This is a preview - click here to buy the full publication CONSOLIDATED VERSION IEC TR 62271-306 Edition 1.1 2018-08 colour inside High-voltage switchgear and controlgear Part 306: Guide to IEC 62271-100, IEC 62271-1 and other IEC standards related to alternating

More information

Primary Test Manager (PTM) Testing and management software for primary assets

Primary Test Manager (PTM) Testing and management software for primary assets Primary Test Manager (PTM) Testing and management software for primary assets Asset diagnostics now easier than ever How well do you know your assets? High-voltage assets are subjected to aging and wear

More information

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Ishwar Lal Yadav Department of Electrical Engineering Rungta College of Engineering and Technology Bhilai, India

More information

Diagnostic testing of cast resin transformers

Diagnostic testing of cast resin transformers Paper of the Month Diagnostic testing of cast resin transformers Author Michael Krüger, OMICRON, Austria michael.krueger@omiconenergy.com Christoph Engelen, OMICRON, Austria christoph.engelen@omicronenergy.com

More information

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol A New Approach for Transformer Bushing Monitoring Emilio Morales Technical Application Specialist Qualitrol Abstract Transformer bushings are one of the most critical components of a transformer. Up to

More information

OCCURRENCE OF DELAYED CURRENT ZERO CROSSING DUE TO LINE REACTIVE OVERCOMPENSATION LT CAMPINAS FERNAO DIAS 500 kv.

OCCURRENCE OF DELAYED CURRENT ZERO CROSSING DUE TO LINE REACTIVE OVERCOMPENSATION LT CAMPINAS FERNAO DIAS 500 kv. OCCURRENCE OF DELAYED CURRENT ZERO CROSSING DUE TO LINE REACTIVE OVERCOMPENSATION LT CAMPINAS FERNAO DIAS 500 kv. Ricardo André Gonçalves 1 / 17 1 - INTRODUCRION Studies conducted on several 500 kv compensated

More information