Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines
|
|
- Mark Cobb
- 6 years ago
- Views:
Transcription
1 Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines David K Olson Paul Nyombi Xcel Energy Pratap G Mysore Pratap Consulting Services Minnesota Power Systems Conference St. Paul, MN November 7-9, 2017
2 Acknowledgement American Transmission Company (ATC) study group for bringing up DCZ issues during the line design studies on one of the CAPX lines. This prompted three utilities associated with CAPX to determine the impact of shunt reactors on their lines and to determine mitigation methods. 2
3 Transmission Line Representation Long Transmission lines can be represented as several series connected modules made up of series resistance, Series Inductance and Shunt capacitance. Lines are also represented with Lumped parameters where the line capacitances are split between two ends. 3
4 Line Parameters Typical 345 KV System Line Resistance: Ω/Mile Line Reactance: Ω/Mile Line Inductance: mh/mile Line Charging MVAR: MVAR/Mile Line Capacitance: µf/mile Resistance can be ignored for our discussions. 4
5 Transmission Line Behavior During Light load or no load conditions, Transmission line has the same effect as capacitance connected to the system. System voltage increases with the connection of open ended transmission Lines. Capacitance of the line is distributed over the entire length. Remote end voltage increases with increase in length Also Known as Ferranti Effect 5
6 Shunt Reactor Application To Keep System Voltage below allowable maximum value System voltage needs to be within the allowable range to prevent connected Equipment failures. - IEEE (R2004) IEEE Standard Preferred Voltage Ratings for Alternating-Current Electrical Systems and Equipment Operating at Voltages Above 230 kv Nominal Installed on Tertiaries of transmission Transformers On Transmission Lines Either at both Ends or at only one end. Middle of the line 6
7 Shunt Compensated Lines Transmission Lines with shunt reactors connected. Total shunt reactor MVAR_R = Sum of all shunt reactors connected on the line. Degree of Compensation, M = Where, MVAR_C is the Line Charging MVAR Degree of Compensation is determined by planning studies- Can exceed 100% 7
8 Effect of Shunt Reactors Decreases the voltage by compensating for the capacitive charging currents. Reactor current, I L lags voltage by 90 0 Capacitor (line charging) current, I C leads voltage by 90 0 Decreases the current through the breaker current ( I C - I L ) * (f ile Paper1.pl4; x-v ar t) v :I_L1 c:i_c2 - c:i_l1 -I_L2 c:xx0002-i_l1 factors: E offsets: Steady State current and Voltage phase relationship
9 Line Currents During Energization Voltage waveform: V Sin (ωt +φ) where φ is the delay angle of switching on the voltage waveform from voltage zero. 300 * (f ile Paper1.pl4; x-v ar t) v :XX0006 Charging (Capacitive) Current: I Sin(ωt+φ+90) Reactor Current: MI [Sin (ωt+φ-90)+ Cosφ e -t/τ ] 9
10 Line Breaker Current I C = I Cos(ωt+φ) I L = MI[-Cos(ωt+φ)+ Cosφ e -t/τ ] Breaker Current, I BRφ = I L +I C I BRφ = I L +I C =(1-M)I Cos(ωt+φ) + MI Cosφ e -t/τ Maximum DC offset is seen when the line with reactor is switched at Voltage zero Crossing. I BR0 = (1-M)I Cos(ωt) + MI e -t/τ 10
11 Line Breaker Current Components AC sinusoidal wave has a peak value of (1-M)I DC component is exponentially decaying with time constant of τ sec. X/R of oil filled reactors are in the range of ; τ can be as high as 2 seconds (~=750/377). DC component will decay to less than 2% of the initial value after 4τ time. 11
12 Line Breaker Delayed Current Zero If AC component Peak (1-M)I is greater than DC component MI, AC waveform will always cross current zero axis or else, Current zero occurs after a delay Delayed Current Zero (DCZ) DC Component 2 Breaker Current Delayed Current Zero
13 Criterion to Prevent DCZ during Normal Switching Boundary Condition: (1-M)I = MI; M = 0.5; Under normal switching, the degree of compensation, M cannot exceed 50% to prevent Delayed Current Zero on Breaker Current. 13
14 Time to first Current Zero If the Degree of compensation is greater than 50%, the AC waveform will cross current zero line when the peak equals or exceeds the decayed DC component (1-M) = M * e -t/τ Solving for t, t Seconds τln Degree of Compensation VS Time to first Current Zero (τ =2 sec) 1.2 ; Degree of Compensation Time for first current zero
15 Effect of Source Impedance The time constant of DC Component is the overall time constant of the system: (X total /R Total) ) If the source is another transmission line behind the line, X/R is typically around 17. Overall X/R reduces. DC component decays faster. Z Source = j47.5 Ohms for 2500 MVA, 345 kv source (X/R=17) Z Reactor = j (X/R =750) Z total = j2428 (X/R=428.6) 15
16 Energizing Faulted Line Fault Location: at the shunt Reactor Voltage Shift on un-faulted phase is the maximum at the fault location and is maximum for double line to Ground Fault Voltage of B-Phase (PU) for A-G fault V B = e -j240 - ; K= 16 B-C-G fault, V A (PU) = For K=2.8, A-Phase voltage increases to PU for B-C-G fault B-phase voltage increases to 1.23
17 M Limit - Effect on DCZ due to Faults Voltage rise on un-faulted phase of the shunt reactor results in higher DC component due to Voltage zero switching and also due to voltage rise. Capacitive current doesn t increase in the same proportion due to distributed Capacitance of the line. Is affected by inter-phase capacitance Transient studies are needed to determine the reduction in M from 50% to prevent DCZ 17
18 18 System Simulation
19 Energization of Shunt Compensated Line Simulated case 1a: Radial line energization from South with A- and B- phases poles closing at voltage zero a. With both shunt reactors connected (approx. 86% compensation) b. With both shunt reactors connected and utilization of 425ohm pre-insertion resistors inserted for 13ms (f ile North_South_345kV.pl4; x-v ar t) c:sth_ba-sth_la c:sth_bb-sth_lb c:sth_bc-sth_lc (f ile North_South_345kV.pl4; x-v ar t) c:sth_ba-sth_la c:sth_bb-sth_lb c:sth_bc-sth_lc
20 Energization of Shunt Compensated Line Simulated case 1b: Radial line energization from South with A- and B- poles closing at voltage zero a. With only North line-end shunt reactor connected (approx. 43% compensation) b. Energizing the transmission line into a close-in BC-Ground fault with only one reactor connected. A-Phase current is shown below (f ile North_South_345kV.pl4; x-v ar t) c:sth_ba-sth_la c:sth_bb-sth_lb c:sth_bc-sth_lc (f ile North_South_345kV.pl4; x-v ar t) c:sth_ba-sth_la
21 Energization of Shunt Compensated Line Observations: Energization of the line with only one reactor connected eliminates DCZ 43% shunt compensation DCZ may also be minimized by using pre-insertion resistors and/or increasing pre-insertion time Several faults may need to be studied as their impact on DCZ depends on other factors like system parameters and line configuration. 43% compensation was found to be adequate in this case for minimizing DCZ for all switching scenarios. 21
22 Switching of Shunt Reactor on an energized line a. Switching South line-end shunt reactor during limited/no loading on the line. South line end breaker currents are shown below: b. Switching of the shunt reactor with at least 46MW flowing from South to North substation. DCZ on South line-end currents is eliminated (f ile North_South_345kV.pl4; x-v ar t) c:sth_ba-sth_la c:sth_bb-sth_lb c:sth_bc-sth_lc (f ile North_South_345kV.pl4; x-v ar t) c:sth_ba-sth_la c:sth_bb-sth_lb c:sth_bc-sth_lc 22
23 Switching of Shunt Reactor on an energized line Observations: Switching of shunt reactor at voltage zero crossings creates DC offsets at line-end breakers, with the strongest source experiencing the greatest offset. Line breakers experience DCZ if the offset is greater than the capacitance from the reactor up to the breaker location. A minimum of 46MW, power flow from South to North, is found to be adequate in mitigating the delayed current zeros when energizing the second shunt reactor 23
24 Switching of line/shunt reactor for transmission line fault events Simulated case 3a: South line-end A-Phase reactor current following a close-in A-G fault on transmission line Under this study: A-Phase to ground fault is considered to occur at A-Phase voltage zero crossing Both reactors are connected with the line closed through Shunt reactor current takes several cycles to decay to zero; X/R ~ 1.68s (f ile North_South_345kV.pl4; x-v ar t) c:sth_la-sth_ra 24
25 Transmission line de-energization under no fault conditions Simulated case 3b: South line-end B-Phase line voltage following line de-energization with both reactors connected Trapped energy in the shunt capacitance and shunt reactors creates high frequency transients that may take several seconds to decay A- and C- Phases also do experience voltage transients. Only B-Phase is shown for clarity. 400 * (f ile North_South_345kV.pl4; x-v ar t) v :STH_LB 25
26 Switching of line/shunt reactor for transmission line fault events Observations: Shunt reactors should not be tripped for faults on transmission line. Disabling high-speed reclosing is recommended especially for lines that have more than 50% compensation. Adequate time may be required before safely reducing the shunt compensation for re-energization. 26
27 Delayed Current Zero Mitigation Methods 1. Use of pre-insertion resistors on line breakers Limitations: Breaker manufacturers do typically guarantee only 8-12ms of pre-insertion time. Pre-insertion time of at least 13ms was required in our case study during normal energization. The time duration was not enough to eliminate DCZ during faulted line energization. Depending on the breaker closing mechanism, increasing pre-insertion resistor size created new transients when the main contact by-passes the pre-insertion resistor 27
28 Delayed Current Zero Mitigation Methods 2. Limit degree of line compensation during line energization Limitations: Reduced line compensation increases remote end line voltages. Remote end line connected equipment must be rated adequately Surge Arrestors, CCVTs, etc 28
29 Delayed Current Zero Mitigation Methods 3. Utilization of controlled closing on shunt reactor breakers Limitations: Implementation of this may be challenging on existing shunt reactor breakers as this may require breaker upgrade 29
30 Delayed Current Zero Mitigation Methods 4. Consider moving reactors (or some of them) from transmission line to substation buses Limitations: Implementation of this may be challenging for existing substations 30
31 Tripping and reclosing considerations for shunt compensated lines Radial energization of a transmission line with less 50% shunt compensation is recommended. Disabling high-speed reclosing is recommended on lines with more than 50% shunt compensation. 31
32 Tripping and reclosing considerations for shunt compensated lines Delaying line breaker tripping for transmission line faults is suggested allows for appearance of current zero crossing for faults (during light load periods) on lines with more than 50% compensation. South line-end currents are shown below for close-in A-G fault (f ile North_South_345kV.pl4; x-v ar t) c:sth_bb-sth_lb c:sth_bc-sth_lc 32
33 Conclusions a. On line energization to prevent DCZ: If shunt reactor(s) on the line is not required to limit open end voltage to acceptable level, energize the line without shunt Reactors. Keep Shunt Compensation below 50% during line energization. Energize the line through breakers equipped with preinsertion resistors that provide enough damping to produce current zeros within breaker interrupting time. This is dependent on the resistor value and duration of insertion. It may not work under all the cases if the degree of compensation is close to 100%. 33
34 Conclusions b. On Shunt reactor energization onto energized lines, to prevent DCZ: Switch shunt reactors less than 50% of the total charging current. Switch shunt reactor at voltage maximum point on the wave. Switch shunt reactors if their inductive MVAR is not greater than the minimum load on the line, in MW. 34
35 Conclusions c. Tripping for line faults: Trip only the line breakers and not shunt reactors. Shunt reactors need to be tripped only after several seconds delay to allow full decay of reactor current on the faulted phase. Total interrupting time of faults on lines with shunt compensation greater than 50% may need to be at least few cycles to allow presence of current zeros on healthy phase(s) during faults. This is dependent on the zero sequence currents flowing on the healthy phases or the minimum load on the healthy phases. 35
36 Conclusions d. Tripping for shunt reactor faults: Trip the shunt reactors only if they are equipped with breakers. 36
37 Conclusions e. Reclosing on Lines: Instantaneous reclose is disabled on lines where shunt reactor switching is required to reduce the degree of compensation. Time delay reclose is enabled after the reactor is switched out. Synch-check reclosing at the other end after energizing the line may generate offsets on the currents. DC offset is dependent on the load picked up after restoration. 37
38 38 Questions
39
Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines
Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,
More informationTopic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017
Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length
More informationAdi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN
Effectiveness of Surge Capacitors on Transformer Tertiary connected shunt reactors in preventing failures- Field measurements and comparison with Transient study results Pratap G. Mysore, P.E Pratap Consulting
More informationTab 2 Voltage Stresses Switching Transients
Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles
More informationIn power system, transients have bad impact on its
Analysis and Mitigation of Shunt Capacitor Bank Switching Transients on 132 kv Grid Station, Qasimabad Hyderabad SUNNY KATYARA*, ASHFAQUE AHMED HASHMANI**, AND BHAWANI SHANKAR CHOWDHRY*** RECEIVED ON 1811.2014
More informationOCCURRENCE OF DELAYED CURRENT ZERO CROSSING DUE TO LINE REACTIVE OVERCOMPENSATION LT CAMPINAS FERNAO DIAS 500 kv.
OCCURRENCE OF DELAYED CURRENT ZERO CROSSING DUE TO LINE REACTIVE OVERCOMPENSATION LT CAMPINAS FERNAO DIAS 500 kv. Ricardo André Gonçalves 1 / 17 1 - INTRODUCRION Studies conducted on several 500 kv compensated
More informationSwitching and Fault Transient Analysis of 765 kv Transmission Systems
Third International Conference on Power Systems, Kharagpur, INDIA December >Paper #< Switching and Transient Analysis of 6 kv Transmission Systems D Thukaram, SM IEEE, K Ravishankar, Rajendra Kumar A Department
More informationNeutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping
Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice
More informationSolving Customer Power Quality Problems Due to Voltage Magnification
PE-384-PWRD-0-11-1997 Solving Customer Power Quality Problems Due to Voltage Magnification R. A. Adams, Senior Member S. W. Middlekauff, Member Duke Power Company Charlotte, NC 28201 USA E. H. Camm, Member
More informationLevel 6 Graduate Diploma in Engineering Electrical Energy Systems
9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,
More informationBC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014
BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014 Expiry Year: 2018 APPROVED BY: Original signed by: Paul
More informationChapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two
Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead
More informationR10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours
Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions
More informationConventional Paper-II-2011 Part-1A
Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance
More information2. Current interruption transients
1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,
More informationECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control
ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections
More informationTECHNICAL BULLETIN 004a Ferroresonance
May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques
More informationBE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %
BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements
Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system
More informationDetecting and Managing Geomagnetically Induced Currents With Relays
Detecting and Managing Geomagnetically Induced Currents With Relays Copyright SEL 2013 Transformer Relay Connections Voltage Current Control RTDs Transformer Protective Relay Measures differential current
More informationSouthern Company Interconnection Requirements for Inverter-Based Generation
Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection
More informationEH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström
EH27401 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsn@ics.kth.se 1 Course map 2 Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids
More informationChapter 31 Alternating Current
Chapter 31 Alternating Current In this chapter we will learn how resistors, inductors, and capacitors behave in circuits with sinusoidally vary voltages and currents. We will define the relationship between
More informationConsiderations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits
1 Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits M. N. Moschakis, E. A. Leonidaki, Student Member, IEEE, N. D. Hatziargyriou, Senior
More informationIDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)
IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone
More informationPower Quality Basics. Presented by. Scott Peele PE
Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement
More informationPower Systems Modelling and Fault Analysis
Power Systems Modelling and Fault Analysis Theory and Practice Nasser D. Tleis BSc, MSc, PhD, CEng, FIEE AMSTERDAM BOSTON HEIDELBERG LONDON NEW YORK OXFORD PARIS SAN DIEGO SAN FRANCISCO SINGAPORE SYDNEY
More informationEffects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages
Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Waruna Chandrasena, Bruno Bisewski, and Jeff Carrara Abstract-- This paper describes several system
More informationCHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS
84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial
More informationHarmonic control devices
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 24 1 Today Harmonic control devices In-line reactors (chokes)
More informationPower Quality enhancement of a distribution line with DSTATCOM
ower Quality enhancement of a distribution line with DSTATCOM Divya arashar 1 Department of Electrical Engineering BSACET Mathura INDIA Aseem Chandel 2 SMIEEE,Deepak arashar 3 Department of Electrical
More informationAnalysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar
Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:
More informationPAPER-II (Subjective)
PAPER-II (Subjective) 1.(A) Choose and write the correct answer from among the four options given in each case for (a) to (j) below: (a) Improved commutation in d.c machines cannot be achieved by (i) Use
More informationA Guide to the DC Decay of Fault Current and X/R Ratios
A Guide to the DC Decay of Fault Current and X/R Ratios Introduction This guide presents a guide to the theory of DC decay of fault currents and X/R ratios and the calculation of these values in Ipsa.
More informationANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION
ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION R.Rahnavard 1, 2 M.Valizadeh 1 A.A.B.Sharifian 2 S.H.Hosseini 1 rerahnavard@gmail.com mj_valizad@yahoo.com hosseini@tabrizu.ac.ir
More informationAlthough shunt capacitors
INSIDE PQ The Trouble With Capacitors Part 1 Switching capacitors seems like a simple proposition, but it can lead to some very interesting problems By R. Fehr, P.E., Engineering Consultant Although shunt
More informationGreat Northern Transmission Line: Behind the (Electrical) Design
Great Northern Transmission Line: Behind the (Electrical) Design November 8, 2017 Christian Winter, P.E. Minnesota Power Sivasis Panigrahi, P.E. POWER Engineers, Inc. What is the Great Northern Transmission
More informationDo Capacitor Switching Transients Still Cause Problems?
Do Capacitor Switching Transients Still Cause Problems? Mark McGranaghan We have been evaluating problems related to capacitor switching transients for many years. Capacitor banks have been used on distribution
More informationStability Enhancement for Transmission Lines using Static Synchronous Series Compensator
Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Ishwar Lal Yadav Department of Electrical Engineering Rungta College of Engineering and Technology Bhilai, India
More informationProtection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin
Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad
More informationTransmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection
Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed
More informationAnalysis of a 405 km transmission line with series compensation
Analysis of a 405 km transmission line with series compensation by Dr. Rupert Gouws, North-West University This paper presents an investigative case study and energy efficiency analysis of the 405 km,
More informationLecture Outline Chapter 24. Physics, 4 th Edition James S. Walker. Copyright 2010 Pearson Education, Inc.
Lecture Outline Chapter 24 Physics, 4 th Edition James S. Walker Chapter 24 Alternating-Current Circuits Units of Chapter 24 Alternating Voltages and Currents Capacitors in AC Circuits RC Circuits Inductors
More informationAnalyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System
Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System Lalit Ghatpande, SynchroGrid, College Station, Texas, 77840 Naveen Ganta, SynchroGrid, College Station, Texas,
More informationHow OSHA s New Transient Overvoltage Requirements Affect Work Practices. B.A. YEUNG, H. BRANCO Leidos Engineering, LLC USA
21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium How OSHA s New Transient Overvoltage Requirements Affect Work Practices B.A. YEUNG,
More informationETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents
Page: 1 Electrical Transient Analyzer Program Short Circuit Analysis ANSI Standard 3-Phase Fault Currents Number of Buses: Swing Generator Load Total 1 0 4 5 Number of Branches: XFMR2 XFMR3 Reactor Line/Cable
More informationElectricity Ten Year Statement November Electricity Ten Year Statement November Appendix D
Electricity Ten Year Statement November 2017 01 Electricity Ten Year Statement November 2017 001 Appendix D 1 Short-circuit currents 02 2 Short-circuit current terminology 04 3 Data requirements 07 4 Fault
More informationProtecting Feeders With Distributed Resource Scott Elling HDR Inc HDR, all rights reserved.
Protecting Feeders With Distributed Resource Scott Elling HDR Inc. 2015 HDR, all rights reserved. Background Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection
More informationAppendix D Fault Levels
Appendix D Fault Levels Page 1 Electricity Ten Year Statement November 2013 D.1 Short Circuit Currents Short Circuit Currents Three phase to earth and single phase to earth short circuit current analyses
More informationCOMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)
7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series
More informationCourse ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation
Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission
More informationTransient Analysis and Mitigation of Capacitor Bank Switching on a Standalone Wind Farm
ol:1, No:4, 216 Transient Analysis and Mitigation of Capacitor Bank Switching on a Standalone Wind Farm Ajibola O. Akinrinde, Andrew Swanson, Remy Tiako Digital Open Science Index, Electrical and Computer
More informationAORC Technical meeting 2014
http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi
More informationCompany Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System
Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels
More informationAutotransformer Inadvertent Energization Through Circuit Breakers Gradient Capacitors
Autotransformer Inadvertent Through Circuit Breakers Gradient Capacitors E. Martínez M., E. Godoy A., R. Ruelas T. Abstract- This paper discusses the commissioning experience with a 4/23/34.5 kv (primary/secondary/tertiary)
More informationSystem grounding of wind farm medium voltage cable grids
Downloaded from orbit.dtu.dk on: Apr 23, 2018 System grounding of wind farm medium voltage cable grids Hansen, Peter; Østergaard, Jacob; Christiansen, Jan S. Published in: NWPC 2007 Publication date: 2007
More informationReducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems
Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Alexander Apostolov AREVA T&D Automation I. INTRODUCTION The electric utilities industry is going through significant
More informationFerroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions
Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit
More informationIn Class Examples (ICE)
In Class Examples (ICE) 1 1. A 3φ 765kV, 60Hz, 300km, completely transposed line has the following positive-sequence impedance and admittance: z = 0.0165 + j0.3306 = 0.3310 87.14 o Ω/km y = j4.67 410-6
More informationTexas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event
Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event
More informationWind Power Facility Technical Requirements CHANGE HISTORY
CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical
More informationEffects of Transient Recovery Voltages on Circuit Breaker Ratings
Effects of Transient Recovery Voltages on Circuit Breaker Ratings Term Project: - EE22 - Power System Transients. Spring 28 Instructor: - Dr. Bruce Mork Team: - Himanshu Bahirat Muhammad Ali Praveen KK
More informationCHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM
CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM 3.1 INTRODUCTION Static synchronous compensator is a shunt connected reactive power compensation device that is capable of generating or
More informationREDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum
International Journal of Scientific & Engineering Research, Volume 7, Issue 4, April-216 628 REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD Abhilash.G.R Smitha K.S Vocational Teacher
More informationUNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET
UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS Introduction Where fuses are unsuitable or inadequate, protective relays and circuit breakers are used in combination to detect and isolate faults. Circuit breakers
More informationPower Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)
Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,
More informationDistance Relay Response to Transformer Energization: Problems and Solutions
1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering
More informationISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements
Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission
More informationFixed Series Compensation
Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and
More informationElectricity & Optics
Physics 24100 Electricity & Optics Lecture 19 Chapter 29 sec. 1,2,5 Fall 2017 Semester Professor Koltick Series and Parallel R and L Resistors and inductors in series: R series = R 1 + R 2 L series = L
More informationRelevant Factors to a Statistical Analysis of Overvoltages - Application to Three-Phase Reclosing of Compensated Transmission Lines
Energy and Power Engineering, 2013, 5, 1165-1171 doi:10.4236/epe.2013.54b221 Published Online July 2013 (http://www.scirp.org/journal/epe) Relevant Factors to a Statistical Analysis of Overvoltages - Application
More informationStatic Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1
Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load MADHYAMA V. WANKHEDE Department Of Electrical Engineering G. H. Raisoni College of
More informationVOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM
VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM Dolly Chouhan 1, Kasongo Hyacinthe Kapumpa 2, Ajay Chouhan 3 1 M. Tech. Scholar, 2
More informationHarmonic filter design for electrified railways
filter design for electrified railways DIgSILENT USER GROUP Sydney 5 September 2013 M Jansen, S Hagaman, T George Railway electrification project Adds significant unbalanced non-linear load to the grid
More informationHigh voltage engineering
High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency
More informationTransient Performance for a Series- Compensation in a High Voltage Transmission System
1 Transient Performance for a Series- Compensation in a High Voltage Transmission System Alfredo A. Cuello-Reyna, Daniel A. Rodríguez-Delgado, Student Member, IEEE, and Lionel Orama- Exclusa, Member, IEEE
More informationLab 1. Objectives. Single Line Diagram. Methodology. Observations. Jon Jawnsy Yu 26 October 2009
Lab 1 Objectives In this lab, our objective is to simulate a simple single machine infinite bus configuration using the PowerWorld Simulator software. We design a local generator system (a synchronous
More informationComparison of recloser and breaker standards
s Technical Data TD280024EN Supersedes February 1994 (R280-90-5) COOPER POWER SERIES Comparison of recloser and breaker standards Technical Data TD280024EN Comparison of recloser and breaker standards
More informationA Study on Ferroresonance Mitigation Techniques for Power Transformer
A Study on Ferroresonance Mitigation Techniques for Power Transformer S. I. Kim, B. C. Sung, S. N. Kim, Y. C. Choi, H. J. Kim Abstract--This paper presents a comprehensive study on the ferroresonance mitigation
More informationInrush current and Total Harmonic Distortion Transient of Power Transformer with Switching Capacitor Bank
IRACST Engineering Science and Technology: An International Journal (ESTIJ), ISSN: -9, Vol., No., June and Total Harmonic Distortion Transient of Power Transformer with Switching Capacitor Bank ABDELSALAM.
More informationMODEL POWER SYSTEM TESTING GUIDE October 25, 2006
October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date
More informationMitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)
ABHIYANTRIKI Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM) An International Journal of Engineering & Technology (A Peer Reviewed & Indexed Journal) Vol.
More informationRelaying 101. by: Tom Ernst GE Grid Solutions
Relaying 101 by: Tom Ernst GE Grid Solutions Thomas.ernst@ge.com Relaying 101 The abridged edition Too Much to Cover Power system theory review Phasor domain representation of sinusoidal waveforms 1-phase
More informationElectric Power Quality: Voltage Sags Momentary Interruptions
Slide 1 Electric Power Quality: Voltage Sags Momentary Interruptions Ward Jewell Wichita State University ward.jewell@wichita.edu Slide 2 Power Quality Events Voltage sags Outages/interruptions Voltage
More informationESB National Grid Transmission Planning Criteria
ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and
More informationShunt Reactor Switching
Shunt Reactor Switching Dielectric stresses produced by circuit-breakers to shunt reactors. Presentation made during the IEEE Transformers Committee meeting, Amsterdam, Netherlands, April 2001 Presented
More informationACS 1000 Transformer Failure Investigation. Nathan Schachter, Peng
Investigation Nathan Schachter, Peng Objectives Learn what happened Explain why it happened Discuss solutions Suggest remedies so it does not happen again Prevention is the key to success 2 ACS 1000 VFD
More informationProgress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010
The Team: Jim McBride: IEEE Member Larry Coffeen: IEEE Senior Member President, JMX Services, Inc. Senior Research Engineer, NEETRAC BS EE Georgia Tech BS EE Georgia Tech Testing, DAQ, and Measurement
More informationCOPYRIGHTED MATERIAL. Index
Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,
More informationSequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network
Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria
More informationResonances in Collection Grids of Offshore Wind Farms
Downloaded from orbit.dtu.dk on: Dec 20, 2017 Resonances in Collection Grids of Offshore Wind Farms Holdyk, Andrzej Publication date: 2013 Link back to DTU Orbit Citation (APA): Holdyk, A. (2013). Resonances
More informationParameter Study of Ferro-Resonance with Harmonic Balance Method
Parameter Study of Ferro-Resonance with Harmonic Balance Method ALI ERBAY Degree project in Electric Power Systems Second Level, Stockholm, Sweden 2012 XR-EE-ES 2012:010 PARAMETER STUDY OF FERRO RESONANCE
More informationTransmission Interconnection Requirements for Inverter-Based Generation
Transmission Requirements for Inverter-Based Generation June 25, 2018 Page 1 Overview: Every generator interconnecting to the transmission system must adhere to all applicable Federal and State jurisdictional
More informationElectromagnetic Oscillations and Currents. March 23, 2014 Chapter 30 1
Electromagnetic Oscillations and Currents March 23, 2014 Chapter 30 1 Driven LC Circuit! The voltage V can be thought of as the projection of the vertical axis of the phasor V m representing the time-varying
More informationEmbedded Generation Connection Application Form
Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed
More informationHYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS
HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS Enrique PÉREZ Santiago REMENTERIA Aitor LAKA Arteche Spain Arteche Spain Ingeteam Power Technology-Spain ep@arteche.es sr@arteche.es Aitor.Laka@ingeteam.com
More informationHarmonic filter design for IEC compliance
Harmonic filter design for IEC 61000 compliance Marius Jansen ALSTOM Grid Power System Compensation Brisbane, Australia marius.jansen@alstom.com Abstract The paper 1 provides a guideline for the selection
More informationPWM DRIVE OVERVOLTAGE TRIPS IN ELECTROCHEMICAL PLANTS
PWM DRIVE OVERVOLTAGE TRIPS IN ELECTROCHEMICAL PLANTS Copyright Material IEEE Paper No. PCIC Paul Buddingh, P.Eng. MEMBER, IEEE ANDRITZ AUTOMATION Ltd. 13700 International Place, Suite 100 Richmond, BC
More informationTransient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines
Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines Presenter Mark McVey C4/B5.41 INTERNATIONAL COUNCIL ON LARGE
More informationRelay Coordination in the Protection of Radially- Connected Power System Network
Relay Coordination in the Protection of Radially- Connected Power System Network Zankhana Shah Electrical Department, Kalol institute of research centre, Ahemedabad-Mehshana Highway, kalol, India 1 zankhu.shah@gmail.com
More information