Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines

Size: px
Start display at page:

Download "Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines"

Transcription

1 Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines David K Olson Paul Nyombi Xcel Energy Pratap G Mysore Pratap Consulting Services Minnesota Power Systems Conference St. Paul, MN November 7-9, 2017

2 Acknowledgement American Transmission Company (ATC) study group for bringing up DCZ issues during the line design studies on one of the CAPX lines. This prompted three utilities associated with CAPX to determine the impact of shunt reactors on their lines and to determine mitigation methods. 2

3 Transmission Line Representation Long Transmission lines can be represented as several series connected modules made up of series resistance, Series Inductance and Shunt capacitance. Lines are also represented with Lumped parameters where the line capacitances are split between two ends. 3

4 Line Parameters Typical 345 KV System Line Resistance: Ω/Mile Line Reactance: Ω/Mile Line Inductance: mh/mile Line Charging MVAR: MVAR/Mile Line Capacitance: µf/mile Resistance can be ignored for our discussions. 4

5 Transmission Line Behavior During Light load or no load conditions, Transmission line has the same effect as capacitance connected to the system. System voltage increases with the connection of open ended transmission Lines. Capacitance of the line is distributed over the entire length. Remote end voltage increases with increase in length Also Known as Ferranti Effect 5

6 Shunt Reactor Application To Keep System Voltage below allowable maximum value System voltage needs to be within the allowable range to prevent connected Equipment failures. - IEEE (R2004) IEEE Standard Preferred Voltage Ratings for Alternating-Current Electrical Systems and Equipment Operating at Voltages Above 230 kv Nominal Installed on Tertiaries of transmission Transformers On Transmission Lines Either at both Ends or at only one end. Middle of the line 6

7 Shunt Compensated Lines Transmission Lines with shunt reactors connected. Total shunt reactor MVAR_R = Sum of all shunt reactors connected on the line. Degree of Compensation, M = Where, MVAR_C is the Line Charging MVAR Degree of Compensation is determined by planning studies- Can exceed 100% 7

8 Effect of Shunt Reactors Decreases the voltage by compensating for the capacitive charging currents. Reactor current, I L lags voltage by 90 0 Capacitor (line charging) current, I C leads voltage by 90 0 Decreases the current through the breaker current ( I C - I L ) * (f ile Paper1.pl4; x-v ar t) v :I_L1 c:i_c2 - c:i_l1 -I_L2 c:xx0002-i_l1 factors: E offsets: Steady State current and Voltage phase relationship

9 Line Currents During Energization Voltage waveform: V Sin (ωt +φ) where φ is the delay angle of switching on the voltage waveform from voltage zero. 300 * (f ile Paper1.pl4; x-v ar t) v :XX0006 Charging (Capacitive) Current: I Sin(ωt+φ+90) Reactor Current: MI [Sin (ωt+φ-90)+ Cosφ e -t/τ ] 9

10 Line Breaker Current I C = I Cos(ωt+φ) I L = MI[-Cos(ωt+φ)+ Cosφ e -t/τ ] Breaker Current, I BRφ = I L +I C I BRφ = I L +I C =(1-M)I Cos(ωt+φ) + MI Cosφ e -t/τ Maximum DC offset is seen when the line with reactor is switched at Voltage zero Crossing. I BR0 = (1-M)I Cos(ωt) + MI e -t/τ 10

11 Line Breaker Current Components AC sinusoidal wave has a peak value of (1-M)I DC component is exponentially decaying with time constant of τ sec. X/R of oil filled reactors are in the range of ; τ can be as high as 2 seconds (~=750/377). DC component will decay to less than 2% of the initial value after 4τ time. 11

12 Line Breaker Delayed Current Zero If AC component Peak (1-M)I is greater than DC component MI, AC waveform will always cross current zero axis or else, Current zero occurs after a delay Delayed Current Zero (DCZ) DC Component 2 Breaker Current Delayed Current Zero

13 Criterion to Prevent DCZ during Normal Switching Boundary Condition: (1-M)I = MI; M = 0.5; Under normal switching, the degree of compensation, M cannot exceed 50% to prevent Delayed Current Zero on Breaker Current. 13

14 Time to first Current Zero If the Degree of compensation is greater than 50%, the AC waveform will cross current zero line when the peak equals or exceeds the decayed DC component (1-M) = M * e -t/τ Solving for t, t Seconds τln Degree of Compensation VS Time to first Current Zero (τ =2 sec) 1.2 ; Degree of Compensation Time for first current zero

15 Effect of Source Impedance The time constant of DC Component is the overall time constant of the system: (X total /R Total) ) If the source is another transmission line behind the line, X/R is typically around 17. Overall X/R reduces. DC component decays faster. Z Source = j47.5 Ohms for 2500 MVA, 345 kv source (X/R=17) Z Reactor = j (X/R =750) Z total = j2428 (X/R=428.6) 15

16 Energizing Faulted Line Fault Location: at the shunt Reactor Voltage Shift on un-faulted phase is the maximum at the fault location and is maximum for double line to Ground Fault Voltage of B-Phase (PU) for A-G fault V B = e -j240 - ; K= 16 B-C-G fault, V A (PU) = For K=2.8, A-Phase voltage increases to PU for B-C-G fault B-phase voltage increases to 1.23

17 M Limit - Effect on DCZ due to Faults Voltage rise on un-faulted phase of the shunt reactor results in higher DC component due to Voltage zero switching and also due to voltage rise. Capacitive current doesn t increase in the same proportion due to distributed Capacitance of the line. Is affected by inter-phase capacitance Transient studies are needed to determine the reduction in M from 50% to prevent DCZ 17

18 18 System Simulation

19 Energization of Shunt Compensated Line Simulated case 1a: Radial line energization from South with A- and B- phases poles closing at voltage zero a. With both shunt reactors connected (approx. 86% compensation) b. With both shunt reactors connected and utilization of 425ohm pre-insertion resistors inserted for 13ms (f ile North_South_345kV.pl4; x-v ar t) c:sth_ba-sth_la c:sth_bb-sth_lb c:sth_bc-sth_lc (f ile North_South_345kV.pl4; x-v ar t) c:sth_ba-sth_la c:sth_bb-sth_lb c:sth_bc-sth_lc

20 Energization of Shunt Compensated Line Simulated case 1b: Radial line energization from South with A- and B- poles closing at voltage zero a. With only North line-end shunt reactor connected (approx. 43% compensation) b. Energizing the transmission line into a close-in BC-Ground fault with only one reactor connected. A-Phase current is shown below (f ile North_South_345kV.pl4; x-v ar t) c:sth_ba-sth_la c:sth_bb-sth_lb c:sth_bc-sth_lc (f ile North_South_345kV.pl4; x-v ar t) c:sth_ba-sth_la

21 Energization of Shunt Compensated Line Observations: Energization of the line with only one reactor connected eliminates DCZ 43% shunt compensation DCZ may also be minimized by using pre-insertion resistors and/or increasing pre-insertion time Several faults may need to be studied as their impact on DCZ depends on other factors like system parameters and line configuration. 43% compensation was found to be adequate in this case for minimizing DCZ for all switching scenarios. 21

22 Switching of Shunt Reactor on an energized line a. Switching South line-end shunt reactor during limited/no loading on the line. South line end breaker currents are shown below: b. Switching of the shunt reactor with at least 46MW flowing from South to North substation. DCZ on South line-end currents is eliminated (f ile North_South_345kV.pl4; x-v ar t) c:sth_ba-sth_la c:sth_bb-sth_lb c:sth_bc-sth_lc (f ile North_South_345kV.pl4; x-v ar t) c:sth_ba-sth_la c:sth_bb-sth_lb c:sth_bc-sth_lc 22

23 Switching of Shunt Reactor on an energized line Observations: Switching of shunt reactor at voltage zero crossings creates DC offsets at line-end breakers, with the strongest source experiencing the greatest offset. Line breakers experience DCZ if the offset is greater than the capacitance from the reactor up to the breaker location. A minimum of 46MW, power flow from South to North, is found to be adequate in mitigating the delayed current zeros when energizing the second shunt reactor 23

24 Switching of line/shunt reactor for transmission line fault events Simulated case 3a: South line-end A-Phase reactor current following a close-in A-G fault on transmission line Under this study: A-Phase to ground fault is considered to occur at A-Phase voltage zero crossing Both reactors are connected with the line closed through Shunt reactor current takes several cycles to decay to zero; X/R ~ 1.68s (f ile North_South_345kV.pl4; x-v ar t) c:sth_la-sth_ra 24

25 Transmission line de-energization under no fault conditions Simulated case 3b: South line-end B-Phase line voltage following line de-energization with both reactors connected Trapped energy in the shunt capacitance and shunt reactors creates high frequency transients that may take several seconds to decay A- and C- Phases also do experience voltage transients. Only B-Phase is shown for clarity. 400 * (f ile North_South_345kV.pl4; x-v ar t) v :STH_LB 25

26 Switching of line/shunt reactor for transmission line fault events Observations: Shunt reactors should not be tripped for faults on transmission line. Disabling high-speed reclosing is recommended especially for lines that have more than 50% compensation. Adequate time may be required before safely reducing the shunt compensation for re-energization. 26

27 Delayed Current Zero Mitigation Methods 1. Use of pre-insertion resistors on line breakers Limitations: Breaker manufacturers do typically guarantee only 8-12ms of pre-insertion time. Pre-insertion time of at least 13ms was required in our case study during normal energization. The time duration was not enough to eliminate DCZ during faulted line energization. Depending on the breaker closing mechanism, increasing pre-insertion resistor size created new transients when the main contact by-passes the pre-insertion resistor 27

28 Delayed Current Zero Mitigation Methods 2. Limit degree of line compensation during line energization Limitations: Reduced line compensation increases remote end line voltages. Remote end line connected equipment must be rated adequately Surge Arrestors, CCVTs, etc 28

29 Delayed Current Zero Mitigation Methods 3. Utilization of controlled closing on shunt reactor breakers Limitations: Implementation of this may be challenging on existing shunt reactor breakers as this may require breaker upgrade 29

30 Delayed Current Zero Mitigation Methods 4. Consider moving reactors (or some of them) from transmission line to substation buses Limitations: Implementation of this may be challenging for existing substations 30

31 Tripping and reclosing considerations for shunt compensated lines Radial energization of a transmission line with less 50% shunt compensation is recommended. Disabling high-speed reclosing is recommended on lines with more than 50% shunt compensation. 31

32 Tripping and reclosing considerations for shunt compensated lines Delaying line breaker tripping for transmission line faults is suggested allows for appearance of current zero crossing for faults (during light load periods) on lines with more than 50% compensation. South line-end currents are shown below for close-in A-G fault (f ile North_South_345kV.pl4; x-v ar t) c:sth_bb-sth_lb c:sth_bc-sth_lc 32

33 Conclusions a. On line energization to prevent DCZ: If shunt reactor(s) on the line is not required to limit open end voltage to acceptable level, energize the line without shunt Reactors. Keep Shunt Compensation below 50% during line energization. Energize the line through breakers equipped with preinsertion resistors that provide enough damping to produce current zeros within breaker interrupting time. This is dependent on the resistor value and duration of insertion. It may not work under all the cases if the degree of compensation is close to 100%. 33

34 Conclusions b. On Shunt reactor energization onto energized lines, to prevent DCZ: Switch shunt reactors less than 50% of the total charging current. Switch shunt reactor at voltage maximum point on the wave. Switch shunt reactors if their inductive MVAR is not greater than the minimum load on the line, in MW. 34

35 Conclusions c. Tripping for line faults: Trip only the line breakers and not shunt reactors. Shunt reactors need to be tripped only after several seconds delay to allow full decay of reactor current on the faulted phase. Total interrupting time of faults on lines with shunt compensation greater than 50% may need to be at least few cycles to allow presence of current zeros on healthy phase(s) during faults. This is dependent on the zero sequence currents flowing on the healthy phases or the minimum load on the healthy phases. 35

36 Conclusions d. Tripping for shunt reactor faults: Trip the shunt reactors only if they are equipped with breakers. 36

37 Conclusions e. Reclosing on Lines: Instantaneous reclose is disabled on lines where shunt reactor switching is required to reduce the degree of compensation. Time delay reclose is enabled after the reactor is switched out. Synch-check reclosing at the other end after energizing the line may generate offsets on the currents. DC offset is dependent on the load picked up after restoration. 37

38 38 Questions

39

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines David K Olson Xcel Energy Minneapolis, MN Paul Nyombi Xcel Energy Minneapolis, MN Pratap G Mysore Pratap Consulting Services,

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN Effectiveness of Surge Capacitors on Transformer Tertiary connected shunt reactors in preventing failures- Field measurements and comparison with Transient study results Pratap G. Mysore, P.E Pratap Consulting

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

In power system, transients have bad impact on its

In power system, transients have bad impact on its Analysis and Mitigation of Shunt Capacitor Bank Switching Transients on 132 kv Grid Station, Qasimabad Hyderabad SUNNY KATYARA*, ASHFAQUE AHMED HASHMANI**, AND BHAWANI SHANKAR CHOWDHRY*** RECEIVED ON 1811.2014

More information

OCCURRENCE OF DELAYED CURRENT ZERO CROSSING DUE TO LINE REACTIVE OVERCOMPENSATION LT CAMPINAS FERNAO DIAS 500 kv.

OCCURRENCE OF DELAYED CURRENT ZERO CROSSING DUE TO LINE REACTIVE OVERCOMPENSATION LT CAMPINAS FERNAO DIAS 500 kv. OCCURRENCE OF DELAYED CURRENT ZERO CROSSING DUE TO LINE REACTIVE OVERCOMPENSATION LT CAMPINAS FERNAO DIAS 500 kv. Ricardo André Gonçalves 1 / 17 1 - INTRODUCRION Studies conducted on several 500 kv compensated

More information

Switching and Fault Transient Analysis of 765 kv Transmission Systems

Switching and Fault Transient Analysis of 765 kv Transmission Systems Third International Conference on Power Systems, Kharagpur, INDIA December >Paper #< Switching and Transient Analysis of 6 kv Transmission Systems D Thukaram, SM IEEE, K Ravishankar, Rajendra Kumar A Department

More information

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice

More information

Solving Customer Power Quality Problems Due to Voltage Magnification

Solving Customer Power Quality Problems Due to Voltage Magnification PE-384-PWRD-0-11-1997 Solving Customer Power Quality Problems Due to Voltage Magnification R. A. Adams, Senior Member S. W. Middlekauff, Member Duke Power Company Charlotte, NC 28201 USA E. H. Camm, Member

More information

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Level 6 Graduate Diploma in Engineering Electrical Energy Systems 9210-114 Level 6 Graduate Diploma in Engineering Electrical Energy Systems Sample Paper You should have the following for this examination one answer book non-programmable calculator pen, pencil, ruler,

More information

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014 BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014 Expiry Year: 2018 APPROVED BY: Original signed by: Paul

More information

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL Basically the HVDC transmission consists in the basic case of two convertor stations which are connected to each other by a transmission link consisting of an overhead

More information

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Code No: R3 R1 Set No: 1 III B.Tech. II Semester Supplementary Examinations, January -14 POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours Max Marks: 75 Answer any FIVE Questions

More information

Conventional Paper-II-2011 Part-1A

Conventional Paper-II-2011 Part-1A Conventional Paper-II-2011 Part-1A 1(a) (b) (c) (d) (e) (f) (g) (h) The purpose of providing dummy coils in the armature of a DC machine is to: (A) Increase voltage induced (B) Decrease the armature resistance

More information

2. Current interruption transients

2. Current interruption transients 1 2. Current interruption transients For circuit breakers or other switching facilities, transient voltages just after the current interruptions are of great concern with successful current breakings,

More information

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Detecting and Managing Geomagnetically Induced Currents With Relays

Detecting and Managing Geomagnetically Induced Currents With Relays Detecting and Managing Geomagnetically Induced Currents With Relays Copyright SEL 2013 Transformer Relay Connections Voltage Current Control RTDs Transformer Protective Relay Measures differential current

More information

Southern Company Interconnection Requirements for Inverter-Based Generation

Southern Company Interconnection Requirements for Inverter-Based Generation Southern Company Interconnection Requirements for Inverter-Based Generation September 19, 2016 Page 1 of 16 All inverter-based generation connected to Southern Companies transmission system (Point of Interconnection

More information

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström EH27401 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsn@ics.kth.se 1 Course map 2 Outline 1. Power System Topologies Transmission Grids vs Distribution grids Radial grids

More information

Chapter 31 Alternating Current

Chapter 31 Alternating Current Chapter 31 Alternating Current In this chapter we will learn how resistors, inductors, and capacitors behave in circuits with sinusoidally vary voltages and currents. We will define the relationship between

More information

Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits

Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits 1 Considerations for the Application of Thyristor Controlled Series Capacitors to Radial Power Distribution Circuits M. N. Moschakis, E. A. Leonidaki, Student Member, IEEE, N. D. Hatziargyriou, Senior

More information

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: IDAHO POWER COMPANY Designated Contact Person: Jeremiah Creason Address: 1221 W. Idaho Street, Boise ID 83702 Telephone

More information

Power Quality Basics. Presented by. Scott Peele PE

Power Quality Basics. Presented by. Scott Peele PE Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement

More information

Power Systems Modelling and Fault Analysis

Power Systems Modelling and Fault Analysis Power Systems Modelling and Fault Analysis Theory and Practice Nasser D. Tleis BSc, MSc, PhD, CEng, FIEE AMSTERDAM BOSTON HEIDELBERG LONDON NEW YORK OXFORD PARIS SAN DIEGO SAN FRANCISCO SINGAPORE SYDNEY

More information

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Waruna Chandrasena, Bruno Bisewski, and Jeff Carrara Abstract-- This paper describes several system

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

Harmonic control devices

Harmonic control devices ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 24 1 Today Harmonic control devices In-line reactors (chokes)

More information

Power Quality enhancement of a distribution line with DSTATCOM

Power Quality enhancement of a distribution line with DSTATCOM ower Quality enhancement of a distribution line with DSTATCOM Divya arashar 1 Department of Electrical Engineering BSACET Mathura INDIA Aseem Chandel 2 SMIEEE,Deepak arashar 3 Department of Electrical

More information

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:

More information

PAPER-II (Subjective)

PAPER-II (Subjective) PAPER-II (Subjective) 1.(A) Choose and write the correct answer from among the four options given in each case for (a) to (j) below: (a) Improved commutation in d.c machines cannot be achieved by (i) Use

More information

A Guide to the DC Decay of Fault Current and X/R Ratios

A Guide to the DC Decay of Fault Current and X/R Ratios A Guide to the DC Decay of Fault Current and X/R Ratios Introduction This guide presents a guide to the theory of DC decay of fault currents and X/R ratios and the calculation of these values in Ipsa.

More information

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION R.Rahnavard 1, 2 M.Valizadeh 1 A.A.B.Sharifian 2 S.H.Hosseini 1 rerahnavard@gmail.com mj_valizad@yahoo.com hosseini@tabrizu.ac.ir

More information

Although shunt capacitors

Although shunt capacitors INSIDE PQ The Trouble With Capacitors Part 1 Switching capacitors seems like a simple proposition, but it can lead to some very interesting problems By R. Fehr, P.E., Engineering Consultant Although shunt

More information

Great Northern Transmission Line: Behind the (Electrical) Design

Great Northern Transmission Line: Behind the (Electrical) Design Great Northern Transmission Line: Behind the (Electrical) Design November 8, 2017 Christian Winter, P.E. Minnesota Power Sivasis Panigrahi, P.E. POWER Engineers, Inc. What is the Great Northern Transmission

More information

Do Capacitor Switching Transients Still Cause Problems?

Do Capacitor Switching Transients Still Cause Problems? Do Capacitor Switching Transients Still Cause Problems? Mark McGranaghan We have been evaluating problems related to capacitor switching transients for many years. Capacitor banks have been used on distribution

More information

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Ishwar Lal Yadav Department of Electrical Engineering Rungta College of Engineering and Technology Bhilai, India

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed

More information

Analysis of a 405 km transmission line with series compensation

Analysis of a 405 km transmission line with series compensation Analysis of a 405 km transmission line with series compensation by Dr. Rupert Gouws, North-West University This paper presents an investigative case study and energy efficiency analysis of the 405 km,

More information

Lecture Outline Chapter 24. Physics, 4 th Edition James S. Walker. Copyright 2010 Pearson Education, Inc.

Lecture Outline Chapter 24. Physics, 4 th Edition James S. Walker. Copyright 2010 Pearson Education, Inc. Lecture Outline Chapter 24 Physics, 4 th Edition James S. Walker Chapter 24 Alternating-Current Circuits Units of Chapter 24 Alternating Voltages and Currents Capacitors in AC Circuits RC Circuits Inductors

More information

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System

Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System Analyzing the Impact of Shunt Reactor Switching Operations Based on DFR Monitoring System Lalit Ghatpande, SynchroGrid, College Station, Texas, 77840 Naveen Ganta, SynchroGrid, College Station, Texas,

More information

How OSHA s New Transient Overvoltage Requirements Affect Work Practices. B.A. YEUNG, H. BRANCO Leidos Engineering, LLC USA

How OSHA s New Transient Overvoltage Requirements Affect Work Practices. B.A. YEUNG, H. BRANCO Leidos Engineering, LLC USA 21, rue d Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2016 Grid of the Future Symposium How OSHA s New Transient Overvoltage Requirements Affect Work Practices B.A. YEUNG,

More information

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents Page: 1 Electrical Transient Analyzer Program Short Circuit Analysis ANSI Standard 3-Phase Fault Currents Number of Buses: Swing Generator Load Total 1 0 4 5 Number of Branches: XFMR2 XFMR3 Reactor Line/Cable

More information

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D Electricity Ten Year Statement November 2017 01 Electricity Ten Year Statement November 2017 001 Appendix D 1 Short-circuit currents 02 2 Short-circuit current terminology 04 3 Data requirements 07 4 Fault

More information

Protecting Feeders With Distributed Resource Scott Elling HDR Inc HDR, all rights reserved.

Protecting Feeders With Distributed Resource Scott Elling HDR Inc HDR, all rights reserved. Protecting Feeders With Distributed Resource Scott Elling HDR Inc. 2015 HDR, all rights reserved. Background Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

More information

Appendix D Fault Levels

Appendix D Fault Levels Appendix D Fault Levels Page 1 Electricity Ten Year Statement November 2013 D.1 Short Circuit Currents Short Circuit Currents Three phase to earth and single phase to earth short circuit current analyses

More information

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) 7 February 2018 RM Zavadil COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR) Brief Overview of Sub-Synchronous Resonance Series

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

Transient Analysis and Mitigation of Capacitor Bank Switching on a Standalone Wind Farm

Transient Analysis and Mitigation of Capacitor Bank Switching on a Standalone Wind Farm ol:1, No:4, 216 Transient Analysis and Mitigation of Capacitor Bank Switching on a Standalone Wind Farm Ajibola O. Akinrinde, Andrew Swanson, Remy Tiako Digital Open Science Index, Electrical and Computer

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi

More information

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Company Directive STANDARD TECHNIQUE: SD7F/2 Determination of Short Circuit Duty for Switchgear on the WPD Distribution System Policy Summary This document provides guidance on calculation of fault levels

More information

Autotransformer Inadvertent Energization Through Circuit Breakers Gradient Capacitors

Autotransformer Inadvertent Energization Through Circuit Breakers Gradient Capacitors Autotransformer Inadvertent Through Circuit Breakers Gradient Capacitors E. Martínez M., E. Godoy A., R. Ruelas T. Abstract- This paper discusses the commissioning experience with a 4/23/34.5 kv (primary/secondary/tertiary)

More information

System grounding of wind farm medium voltage cable grids

System grounding of wind farm medium voltage cable grids Downloaded from orbit.dtu.dk on: Apr 23, 2018 System grounding of wind farm medium voltage cable grids Hansen, Peter; Østergaard, Jacob; Christiansen, Jan S. Published in: NWPC 2007 Publication date: 2007

More information

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Alexander Apostolov AREVA T&D Automation I. INTRODUCTION The electric utilities industry is going through significant

More information

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit

More information

In Class Examples (ICE)

In Class Examples (ICE) In Class Examples (ICE) 1 1. A 3φ 765kV, 60Hz, 300km, completely transposed line has the following positive-sequence impedance and admittance: z = 0.0165 + j0.3306 = 0.3310 87.14 o Ω/km y = j4.67 410-6

More information

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity Event Analysis Event: May 8, 2011 Loss of Multiple Elements Category 1a Event Texas Reliability Entity July 2011 Page 1 of 10 Table of Contents Executive Summary... 3 I. Event

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

Effects of Transient Recovery Voltages on Circuit Breaker Ratings

Effects of Transient Recovery Voltages on Circuit Breaker Ratings Effects of Transient Recovery Voltages on Circuit Breaker Ratings Term Project: - EE22 - Power System Transients. Spring 28 Instructor: - Dr. Bruce Mork Team: - Himanshu Bahirat Muhammad Ali Praveen KK

More information

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM 3.1 INTRODUCTION Static synchronous compensator is a shunt connected reactive power compensation device that is capable of generating or

More information

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum International Journal of Scientific & Engineering Research, Volume 7, Issue 4, April-216 628 REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD Abhilash.G.R Smitha K.S Vocational Teacher

More information

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS Introduction Where fuses are unsuitable or inadequate, protective relays and circuit breakers are used in combination to detect and isolate faults. Circuit breakers

More information

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78) Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,

More information

Distance Relay Response to Transformer Energization: Problems and Solutions

Distance Relay Response to Transformer Energization: Problems and Solutions 1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

Electricity & Optics

Electricity & Optics Physics 24100 Electricity & Optics Lecture 19 Chapter 29 sec. 1,2,5 Fall 2017 Semester Professor Koltick Series and Parallel R and L Resistors and inductors in series: R series = R 1 + R 2 L series = L

More information

Relevant Factors to a Statistical Analysis of Overvoltages - Application to Three-Phase Reclosing of Compensated Transmission Lines

Relevant Factors to a Statistical Analysis of Overvoltages - Application to Three-Phase Reclosing of Compensated Transmission Lines Energy and Power Engineering, 2013, 5, 1165-1171 doi:10.4236/epe.2013.54b221 Published Online July 2013 (http://www.scirp.org/journal/epe) Relevant Factors to a Statistical Analysis of Overvoltages - Application

More information

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1 Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load MADHYAMA V. WANKHEDE Department Of Electrical Engineering G. H. Raisoni College of

More information

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM Dolly Chouhan 1, Kasongo Hyacinthe Kapumpa 2, Ajay Chouhan 3 1 M. Tech. Scholar, 2

More information

Harmonic filter design for electrified railways

Harmonic filter design for electrified railways filter design for electrified railways DIgSILENT USER GROUP Sydney 5 September 2013 M Jansen, S Hagaman, T George Railway electrification project Adds significant unbalanced non-linear load to the grid

More information

High voltage engineering

High voltage engineering High voltage engineering Overvoltages power frequency switching surges lightning surges Overvoltage protection earth wires spark gaps surge arresters Insulation coordination Overvoltages power frequency

More information

Transient Performance for a Series- Compensation in a High Voltage Transmission System

Transient Performance for a Series- Compensation in a High Voltage Transmission System 1 Transient Performance for a Series- Compensation in a High Voltage Transmission System Alfredo A. Cuello-Reyna, Daniel A. Rodríguez-Delgado, Student Member, IEEE, and Lionel Orama- Exclusa, Member, IEEE

More information

Lab 1. Objectives. Single Line Diagram. Methodology. Observations. Jon Jawnsy Yu 26 October 2009

Lab 1. Objectives. Single Line Diagram. Methodology. Observations. Jon Jawnsy Yu 26 October 2009 Lab 1 Objectives In this lab, our objective is to simulate a simple single machine infinite bus configuration using the PowerWorld Simulator software. We design a local generator system (a synchronous

More information

Comparison of recloser and breaker standards

Comparison of recloser and breaker standards s Technical Data TD280024EN Supersedes February 1994 (R280-90-5) COOPER POWER SERIES Comparison of recloser and breaker standards Technical Data TD280024EN Comparison of recloser and breaker standards

More information

A Study on Ferroresonance Mitigation Techniques for Power Transformer

A Study on Ferroresonance Mitigation Techniques for Power Transformer A Study on Ferroresonance Mitigation Techniques for Power Transformer S. I. Kim, B. C. Sung, S. N. Kim, Y. C. Choi, H. J. Kim Abstract--This paper presents a comprehensive study on the ferroresonance mitigation

More information

Inrush current and Total Harmonic Distortion Transient of Power Transformer with Switching Capacitor Bank

Inrush current and Total Harmonic Distortion Transient of Power Transformer with Switching Capacitor Bank IRACST Engineering Science and Technology: An International Journal (ESTIJ), ISSN: -9, Vol., No., June and Total Harmonic Distortion Transient of Power Transformer with Switching Capacitor Bank ABDELSALAM.

More information

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006 October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date

More information

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM) ABHIYANTRIKI Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM) An International Journal of Engineering & Technology (A Peer Reviewed & Indexed Journal) Vol.

More information

Relaying 101. by: Tom Ernst GE Grid Solutions

Relaying 101. by: Tom Ernst GE Grid Solutions Relaying 101 by: Tom Ernst GE Grid Solutions Thomas.ernst@ge.com Relaying 101 The abridged edition Too Much to Cover Power system theory review Phasor domain representation of sinusoidal waveforms 1-phase

More information

Electric Power Quality: Voltage Sags Momentary Interruptions

Electric Power Quality: Voltage Sags Momentary Interruptions Slide 1 Electric Power Quality: Voltage Sags Momentary Interruptions Ward Jewell Wichita State University ward.jewell@wichita.edu Slide 2 Power Quality Events Voltage sags Outages/interruptions Voltage

More information

ESB National Grid Transmission Planning Criteria

ESB National Grid Transmission Planning Criteria ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and

More information

Shunt Reactor Switching

Shunt Reactor Switching Shunt Reactor Switching Dielectric stresses produced by circuit-breakers to shunt reactors. Presentation made during the IEEE Transformers Committee meeting, Amsterdam, Netherlands, April 2001 Presented

More information

ACS 1000 Transformer Failure Investigation. Nathan Schachter, Peng

ACS 1000 Transformer Failure Investigation. Nathan Schachter, Peng Investigation Nathan Schachter, Peng Objectives Learn what happened Explain why it happened Discuss solutions Suggest remedies so it does not happen again Prevention is the key to success 2 ACS 1000 VFD

More information

Progress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010

Progress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010 The Team: Jim McBride: IEEE Member Larry Coffeen: IEEE Senior Member President, JMX Services, Inc. Senior Research Engineer, NEETRAC BS EE Georgia Tech BS EE Georgia Tech Testing, DAQ, and Measurement

More information

COPYRIGHTED MATERIAL. Index

COPYRIGHTED MATERIAL. Index Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,

More information

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria

More information

Resonances in Collection Grids of Offshore Wind Farms

Resonances in Collection Grids of Offshore Wind Farms Downloaded from orbit.dtu.dk on: Dec 20, 2017 Resonances in Collection Grids of Offshore Wind Farms Holdyk, Andrzej Publication date: 2013 Link back to DTU Orbit Citation (APA): Holdyk, A. (2013). Resonances

More information

Parameter Study of Ferro-Resonance with Harmonic Balance Method

Parameter Study of Ferro-Resonance with Harmonic Balance Method Parameter Study of Ferro-Resonance with Harmonic Balance Method ALI ERBAY Degree project in Electric Power Systems Second Level, Stockholm, Sweden 2012 XR-EE-ES 2012:010 PARAMETER STUDY OF FERRO RESONANCE

More information

Transmission Interconnection Requirements for Inverter-Based Generation

Transmission Interconnection Requirements for Inverter-Based Generation Transmission Requirements for Inverter-Based Generation June 25, 2018 Page 1 Overview: Every generator interconnecting to the transmission system must adhere to all applicable Federal and State jurisdictional

More information

Electromagnetic Oscillations and Currents. March 23, 2014 Chapter 30 1

Electromagnetic Oscillations and Currents. March 23, 2014 Chapter 30 1 Electromagnetic Oscillations and Currents March 23, 2014 Chapter 30 1 Driven LC Circuit! The voltage V can be thought of as the projection of the vertical axis of the phasor V m representing the time-varying

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS

HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS HYBRID STATCOM SOLUTIONS IN RENEWABLE SYSTEMS Enrique PÉREZ Santiago REMENTERIA Aitor LAKA Arteche Spain Arteche Spain Ingeteam Power Technology-Spain ep@arteche.es sr@arteche.es Aitor.Laka@ingeteam.com

More information

Harmonic filter design for IEC compliance

Harmonic filter design for IEC compliance Harmonic filter design for IEC 61000 compliance Marius Jansen ALSTOM Grid Power System Compensation Brisbane, Australia marius.jansen@alstom.com Abstract The paper 1 provides a guideline for the selection

More information

PWM DRIVE OVERVOLTAGE TRIPS IN ELECTROCHEMICAL PLANTS

PWM DRIVE OVERVOLTAGE TRIPS IN ELECTROCHEMICAL PLANTS PWM DRIVE OVERVOLTAGE TRIPS IN ELECTROCHEMICAL PLANTS Copyright Material IEEE Paper No. PCIC Paul Buddingh, P.Eng. MEMBER, IEEE ANDRITZ AUTOMATION Ltd. 13700 International Place, Suite 100 Richmond, BC

More information

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines Presenter Mark McVey C4/B5.41 INTERNATIONAL COUNCIL ON LARGE

More information

Relay Coordination in the Protection of Radially- Connected Power System Network

Relay Coordination in the Protection of Radially- Connected Power System Network Relay Coordination in the Protection of Radially- Connected Power System Network Zankhana Shah Electrical Department, Kalol institute of research centre, Ahemedabad-Mehshana Highway, kalol, India 1 zankhu.shah@gmail.com

More information