Coordination of protective relays in MV transformer stations using EasyPower Protector software

Size: px
Start display at page:

Download "Coordination of protective relays in MV transformer stations using EasyPower Protector software"

Transcription

1 Coordination of protective relays in MV transformer stations using EasyPower Protector software S. Nikolovski, Member, IEEE, I. Provci and D. Sljivac In this paper, the analysis of digital protection relays setting in a MV transformer station grounded via a low-ohmic resistor is presented. Theoretical background on low-ohmic resistor grounding in a transformer station is provided. EasyPower PowerProtector software is used for simulation and relay settings. Protective relay coordination after the simulation of a 3- phase fault and a line-to-ground fault on different selected buses in transformer station 35/10 kv is performed. Digital ABB relays series REF 541 were used for low-ohmic resistor thermal, shortcircuit and overcurrent protection and overload protection of the low voltage transformer side. The results of analysis indicate correct selectivity of overcurrent protection devices in all cases. Index Terms -- digital relay, fault, low-ohmic resistor, protection, transformer station T I. INTRODUCTION HE purpose of the power system neutral grounding is to limit the fault current, as well as to limit the values of overvoltages induced by line-to-ground faults. In the middle voltage (10 kv, 20 kv and 35 kv) networks neutral grounding is performed by voltaic connection between the energy transformers secondary wyes winding neutral and the ground. In the case when transformers connection type is not the same or transformers do not have the neutral point (delta winding), it is necessary to perform the artificial wye neutral grounding of the secondary winding. Artificial neutral is achieved by earthing the transformer with specific technical characteristics. There are basically two different types of grounding: direct and indirect. Indirect grounding can be performed using resistance or reactance. To the present, low-ohmic resistor grounding is the only grounding type used in the middle voltage power system of the Croatian National Grid. If the secondary winding neutral of all transformers in a transformer station is accessible, two grounding schemes or approaches are possible: 1. one low-ohmic resistor in station 2. one low-ohmic resistor at transformer The usual grounding scheme in the distribution area "Elektroistra" Pula is the one only one low-ohmic resistor in both 110/35 kv and 35/10(20) kv transformer stations. Current magnitudes and transient duration of power transformers switching into parallel operation, as well as the single-line-to-ground (SLG) fault resistance value are the important parameters which condition the correct operation of resistor relay protection. Inconsistent use of a typical solution for resistor protection settings or of back up lines protection can result in the false response of relay protection. False protection response indicates a different cause of failure, which makes the establishment of normal system operation more difficult. In order to avoid false protection response, current magnitude and response time are increased intuitively using engineering experience. However, care must be taken since an increased tap setting, may decrease the sensitivity during SLG faults and lead to resistor overheating and possible damage. Increase of the response time due to resistor bridging can result in high induced touch and step voltage voltages in a transformer station, as well as in damaging the grounding system, especially in the case of currents exceeding several ka. Information on resistor characteristics, network SLG conditions, and energy transformers operational transients leads to a different approach to selection of resistor protection in order to decrease consumer supply interruptions. II. MATHEMATICAL BACKGROUND A. Technical Characteristics of Low Ohmic Resistor Middle voltage resistor grounding characteristics are chosen for short overloads. The resistor is defined by these values: 1. nominal current with 5 seconds permitted duration 2. permanent permitted current minutes permitted current These are the parameters, which determine the choice and the protection settings of a resistor. Knowing the material of the resistive element, together with the nominal current with 5 seconds permitted duration, it is possible to calculate the maximum time of permitted overload for various current values above the nominal. SLG fault current in 35 kv network is typically limited to a nominal current of 300 A. SLG fault current in a 10 (20) kv network is limited to 150 A current in meshed or 300 A in a cable network. Calculation of the permitted overload duration will be conducted for those nominal resistor currents

2 according to the following expression: I a ln I n 2 I a 1 I n 2 t = T B max ϑ (1) where: T ϑ is the resistive element heating time constant; I a is the resistor current; I n is the nominal current of the resistive element and t B max is the maximum overloading duration. For the 300 A current, the resistive element is made with the permitted permanent current equal to or higher than 65 A, while for the 150 A current with permitted permanent current is equal to or higher than 32 A. Calculated current values are obtained according to manufacturer's characteristics, but in reality they are higher than those declared by manufacturers. The diagram in figure 1 presents calculated results. TABLE I TIME-CURRENT CHARACTERSITICS: α AND β CONSTANTS Time-current characteristic α β Normal inverse Very inverse Extremely inverse Long-time inverse Fig. 1. Calculated values of resistor currents There are four international standard time-current characteristics. Time and current ratio is defined according to the BS 142 and IEC standards as: t( s) k β = α I I > 1 where: t is the response time; k is the time multiplier; I is the fault current and I> is the overcurrent setting. α and β constants are dependent on the type of the characteristics according to table I. Fig. 2 (using table I) represents an example of choosing the time-current characteristics for 300 A nominal current low-ohmic resistor protection. (2) Fig. 2. Time-current characteristics for low-ohmic resistor For example, low-ohmic resistor protection in a 300 A current area, i.e. resistor thermal protection area, is performed using the long-time inverse characteristic defined by parameters k=1 and I=15 A. Low-ohmic resistor protection in a 150 A current area, i.e. resistor bridging protection area, is performed using extremely inverse characteristic defined by parameters k=0.05 and I=200 A. III. DIGITAL RELAYS SIMULATION IN EASYPOWER PROTECTOR SOFTWARE For the simulating the protection relays and proper coordination the EasyPower PowerProtector software module was used. It has the short circuit (SC) and the Time Current Curves (TCC) programs completely integrated with the one-

3 line diagram. The user does not have to create separate onelines for the TCC plots. Also all SC currents are automatically placed on the one-line diagram of the TCC Plots, and the TCC plot itself so there is a huge time savings in the analysis. EasyPower PowerProtector can model all the different types of Multi-Function relays on the one-line as a single relay, so the user actually sees the real protective system. The MF relays can perform many functions (plotted on the TCC) like a real unit. EasyPower Protector has the graphics capabilities to model all the different protective device relays, CT's, etc. so the real protection system is modeled. The problems associated with transformers working in parallel operation, and transients in the case of SLG faults, as well as SLG high-ohm faults, could be solved using several electromechanical or static relays with various current characteristics and various time-current settings. However, this kind of solution is very expensive. By using digital multifunctional relays which can perform several functions in a single device, it is possible to simplify the solution of these multiple problems and therefore to make the solution less expensive, together with decreasing the number of false protection operations. It is possible to configure the digital relays to simultaneously use the inverse time-current characteristics and definite time-currents characteristics together with supervision of the switching state of power station components important for operational logic of relay protection. A. Sample case: Transformer station 35/10 kv Pula Zapad The sample case of using the digital relays installed in a low voltage side of power transformer field terminals in a 35/10 kv transformer station Pula Zapad is described further in a text. The analysis of the real transformer station in cases of 3- phase and single line-to-ground faults was performed. Fig. 3. presents the protection scheme of TS 35/10 kv Pula Zapad. Using protection blocks in digital relays the following protections are achieved: 1. High-ohmic fault protection using definite time-current characteristic with settings: I=5 A and t=5 min (300 s) - used for switching off power transformers. 2. Thermal protection of low-ohmic resistor using long time inverse characteristic with settings: k=1, I=15 A (fig. 2.). 3. Low-ohmic resistor bridging using extremely inverse characteristic with settings: k=0.05, I=200 A (fig 2.). 4. SLG fault protection of the lines using definite time characteristic with settings: I=100 A and t=5 s (20) kv bus fault protection using definite time characteristic with settings: I=900 A and t=0.2 s. 6. Overload protection of LV side of power transformers using definite time characteristic with settings: I=492 A and t=1.8 s. According to the data from [6] the topology of the distribution network and the transformer station 35/10 kv Pula Zapad were simulated in the Protector module of EasyPower software. The REF 541 digital relay from ABB was used for lowohmic resistor thermal protection, short-circuit and overcurrent protection and overload protection of the low voltage transformer side. Due to the situation in TS Pula Zapad, it was neccessary to obtain the multi-function combination of 51DT/50, 51DT/50, 51/50N protection functions. Therefore, the tap time, time dial time, the instantaneous pickup time and the instantaneous delay time needed to be adjusted according to the calculated data from Dispatching Center of the Croatian Grid Company. The field terminal of REF 541 has: three protection blocks of 3-phase non-directional overcurrent protection (NOC3), three protection blocks of non-directional earth fault protection (NEF1) and three protection blocks of directional earth fault protection (DEF2). All relays setting are present in Fig. 4. Fig. 3. Protection scheme of TS 35/10 kv Pula Zapad Fig. 4. Database of ABB REF 541 digital relay settings

4 Since this relay is in the multi-function connection, these settings needed to be performed for 51/50N, as well as for 51DT/50N function. Protective settings of 10 kv feeders and transformers were adjusted and the 10/0.4 kv transformer was also introduced in the analysis in order to obtain the information on protective response in TS 35/10 kv Pula in cases of faults in low voltage networks. Low-resistor impedance on 10 kv side of transformers in TS Pula Zapad was 20 Ω. B. The results of the analysis The six sample cases were studied and assessment of timecurrent relays setting was performed: 1. 3-phase fault on 10 kv bus of TS Pula Zapad 2. 3-phase fault in 0.4 kv network 3. 3-phase fault in 10kV network with fault impedance10 Ω 4. Single line-to-ground fault on 10 kv bus of TS Pula Zapad 5. Single line-to-ground fault on 10 kv bus of TS Pula Zapad with zero low-resistor impedance 6. Single line-to-ground fault on 10 kv bus of TS Pula Zapad with variable fault impedance of: 20 Ω, 50 Ω, 100 Ω, 200 Ω, 500 Ω, 1000 Ω and 1200 Ω Fig. 6. Time-current curve for 3-phase fault on 10 kv bus of TS Pula Zapad Time-current curves indicate the response of the protective scheme in each case. Fig. 7. Relay s tripping and setting in case of a 3-phase fault on 10 kv bus Fig. 5. Single-line diagram for 3-phase fault on 10 kv bus of TS Pula Zapad For example, Figures 6 and 9 present time-current curves for 3-phase and a single line-to-ground fault on 10 kv bus of TS Pula Zapad respectively, with zero low-resistor impedance. The most important results of the analysis are described further in a text. Tables II, III and IV represents the simulated protection operation results in case of a 3-phase fault on 10 kv bus of TS Pula Zapad, a 3-phase fault in 0.4 kv network and a single line-to-ground fault on 10 kv bus of TS Pula Zapad, respectively.

5 Relay TABLE II 3-PHASE FAULT ON 10 KV BUS OF TS PULA ZAPAD Voltage level ( kv ) Device Function Fault Current I> ( A ) Responce Time t ( s ) Fault on low voltage on 0.4 kv bus of TS Pula Zapad was performed to point out the need to increase the response time of relay R-5 so that a high voltage fuse in transformer branch TX-3 has time to burn out and therefore to switch off the power transformer, but not the rest of the network. R DT/ R DT/ R DT/ From Table II. it can be seen that coordination of protective relays is done well, since the selectivity for a 3-phase fault is achieved. First, the relay in cable terminal R-5-1 will trip with an instantaneous delay of t=51ms, after that relay R-3-1 on the secondary side of the transformer station with an instantaneous delay of t=206 ms, and the last relay will be the relay on the primary side of the transformer station R-1, with definite time delay t=2.012 sec. From Fig. 5 it can be noticed that fault currents that flow from the supply network to 10 kv bus of TS where the fault is simulated crosses time-current characteristics of relays and those values are presented in Table II Fig. 9. Time-current curve for 3-phase fault on 0.4 kv bus of TS Pula Zapad It should be mentioned that in a sample network there is no HV fuse of 10/0.4 kv transformer when simulating the 0.4 kv fault, but in reality selectivity of 10 kv lines fault protection operation to operation of HV fuse of 10/0.4 kv transformers in case of close faults in 0.4 kv network is desirable. TABLE IV SINGLE LINE-TO-GROUND FAULT ON 10 KV BUS OF TS PULA ZAPAD Relay Device Function Fault Current I 0 > ( A ) Response Time t ( s ) Fig. 8. Single-line diagram for SLGfault on 10 kv bus of TS Pula Zapad Relay Voltage level ( kv ) TABLE III 3-PHASE FAULT IN 0.4 KV NETWORK Device Function Fault Current I> ( A ) Response Time t ( s ) R DT/ R DT/ R /50N R DT/50N R DT/ R DT/50N The analysis of relay protection coordination in case of the SLG fault at 10 kv bus in TS Pula Zapad indicates that the selectivity of the relays is also satisfactory. Relay R-5-1 is also presented in Fig. 6. although it is used for 2 or 3-phase faults. The reason is that overcurrent protection functions always "see" SLG faults due to their 3-phase performance, so there is a real possibility that a 10 kv feeder overcurrent element will be excited in the fault affected phase.

6 1, R-3-2, R-3-3 and R-3-4 will react on the same current value of ka, but the faster response has relay R-3-2 operating first which is set according to the very-inverse characteristic, resulting in a very good protection of the low-ohmic resistor, meaning that the response time of relay R-3-2 in case of resistor bridging is only s. IV. CONCLUSIONS Fig. 10. Time current curve for single line-to-ground fault on 10 kv bus of TS Pula Zapad Furthermore, the simulation of relay protection response on various fault impedances in the case of SLG fault on 10 kv bus of TS Pula Zapad is simulated. Fault resistance is changed from 20 ohm to 1000 ohm, for high-ohmic SLG faults. The results are presented in table V. It can be noticed that by increasing the fault impedance (i.e. decreasing the fault currents) the response current is decreases, while the response time is increases according to the TCC curves. TABLE V SINGLE LINE-TO-GROUND FAULT ON 10 KV BUS OF TS PULA ZAPAD Feeder field Transformer field Z (Ω) R-5-1 R-5-2 R-3-3 R (293A; 0.9s) (293A; 0.5s) (118A; 0.5s) (58.8A; 0.6s) (29.3A; 0.5s) (11.8A; 176.7s) (5.89A; 174.1s) (151; 13.9s) (59.6A; 42.1s) (30.2A; 14.9s) - - (150.1; 5.1s) (59.6A; 126.3s) (31.2A; 298.7s) (15A; 329.5s) (6A; 312.5s) - - Additionally, simulation of the grounding resistor which is short circuited is performed. Results indicate that relays R-3- The analysis of the digital protection relays setting in MV a transformer station grounded via low-ohmic resistor is presented in this paper. EasyPower PowerProtector software is used for simulation and coordination of the relay protection in MV TS 35/10 kv. Several functions of digital relays are simulated: High-ohmic fault protection using definite timecurrent characteristic. Thermal protection of low-ohmic resistor using long time inverse characteristic Low-ohmic resistor bridging using extremely inverse characteristic. SLG fault protection of the lines using definite time characteristic The 10(20) kv bus fault protection using definite time characteristic. Overload protection of LV side of power transformers using definite time characteristic. The analysis of relay protection co-ordination in case of the three-phase fault and SLG fault at 10 kv bus in TS Pula Zapad indicates that relay selectivity is satisfactory. V. ACKNOWLEDGMENT The authors gratefully acknowledge the contributions of Igor Vickovic, BSc from HEP - Croatian National Grid Company for his help and also to the Electrical System Analysis Inc. for their financial support to this project. VI. REFERENCES [1] S. H. Horowitz, Power System Relaying, 2nd ed, Research Studies Press LTD. Somerset, England, [2] A. T. Johns and S. K. Salman, Digital Protection for Power Systems IEEE Power Series 15, London, [3] S.Nikolovski, Basis of Relay Protection in Power System, Osijek, [4] ABB: Protective Relaying Theory and Aplication, [5] ABB: User s Manual and Tehnical Description REF 54_1999. [6] S. Drandić and N. Rudan, "Choice and setting of relay protection of lowohmic grounding resistor in MV electrical networks using digital relays," in Proc CIGRE Croatian Comitee Conference, November 4-8, Cavtat, Croatia VII. BIOGRAPHIES Srete Nikolovski was born in Belgrade on 01. October, He obtained his BSc degree in 1978 and Master of Science degree (MSc) in 1989, both in the field of Electrical Engineering, from the Faculty of Electrical Engineering, University of Belgrade. He received his PhD degree from the Faculty of Electrical Engineering and Computing, University of Zagreb, Croatia in Currently he is Associate Professor with the Power System Engineering Department at the Faculty of Electrical Engineering, Osijek, Croatia. His main interest is in power system modeling, simulation and analysis, especially in reliability assessment of power system and power system protection.

7 Igor Provci was born in Travnik, Bosnia and Hercegovina, on October 19, He graduated from the Faculty of Electrical Engineering in Osijek in In He received a scholar ship from HEP - Croatian National Grid Company, Direction section - Opatija. He was an active member of IAESTE (The International Association for the Exchange of Students for Technical Experience) during his unergraduate studies and carried out two practical trainings, one in Tunisia and the other one in Ireland. Damir Sljivac was born in Osijek, Croatia on February 4, He obtained his BSc degree in Electrical Engineering in 1997, from the Faculty of Electrical Engineering, University of Osijek, Croatia and his MSc degree in 2000, from the Faculty of Electrical Engineering and Computing, University of Zagreb, Croatia. At present he is a research assistant with Power System Department at the Faculty of Electrical Engineering, University of Osijek and a PhD student at Faculty of Electrical Engineering and Computing, University of Zagreb. In 2002, he was an academic visitor at a University of Manchester, Institute for Science and Technology (UMIST), UK. His main field of interest is in power system analysis, particularly power system reliability in deregulated electricity markets.

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS Juan Manuel Gers, PhD Protection coordination principles Relay coordination is the process of selecting settings that will assure that the relays

More information

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS Juan Manuel Gers, PhD Example - Single Line Example 1 - Data Calculate the following: 1. The three phase short circuit levels on busbars

More information

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems Alexander Apostolov AREVA T&D Automation I. INTRODUCTION The electric utilities industry is going through significant

More information

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements

RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements RAIDK, RAIDG, RAPDK and RACIK Phase overcurrent and earth-fault protection assemblies based on single phase measuring elements User s Guide General Most faults in power systems can be detected by applying

More information

Electrical Protection System Design and Operation

Electrical Protection System Design and Operation ELEC9713 Industrial and Commercial Power Systems Electrical Protection System Design and Operation 1. Function of Electrical Protection Systems The three primary aims of overcurrent electrical protection

More information

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network Copyright 2017 ABB. All rights reserved. 1. Introduction Many distribution networks around the world have limited earth-fault current by a resistor located in the LV winding neutral point of for example

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority

Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority Voltage Sag Mitigation by Neutral Grounding Resistance Application in Distribution System of Provincial Electricity Authority S. Songsiri * and S. Sirisumrannukul Abstract This paper presents an application

More information

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

S&C Vista Underground Distribution Switchgear Outdoor Distribution

S&C Vista Underground Distribution Switchgear Outdoor Distribution The offers superior overcurrent coordination. Among the features that provide excellent overcurrent coordination are unique coordinating speed tap and main time-current characteristic curves, which provide

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602

Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602 Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602 1 / 12 1 INTRODUCTION This document provides guidelines for the performance calculations required for high impedance differential

More information

PROTECTION of electricity distribution networks

PROTECTION of electricity distribution networks PROTECTION of electricity distribution networks Juan M. Gers and Edward J. Holmes The Institution of Electrical Engineers Contents Preface and acknowledgments x 1 Introduction 1 1.1 Basic principles of

More information

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson... TECHNICAL REPORT APPLICATION GUIDE TITLE: Current Transformer Requirements for VA TECH Reyrolle ACP Relays PREPARED BY:- A Allen... APPROVED :- B Watson... REPORT NO:- 990/TIR/005/02 DATE :- 24 Jan 2000

More information

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide Relion 605 series Relion 605 series Self-Powered Feeder Protection Product Guide Contents 1 Description...3 2 Protection functions...3 3 Application...4 4 Self-supervision...4 5 Inputs and outputs...4

More information

OVERCURRENT PROTECTION RELAY GRD110

OVERCURRENT PROTECTION RELAY GRD110 INSTRUCTION MANUAL OVERCURRENT PROTECTION RELAY GRD110 TOSHIBA Corporation 2002 All Rights Reserved. ( Ver. 3.1) Safety Precautions Before using this product, please read this chapter carefully. 1 This

More information

Transformer Fault Categories

Transformer Fault Categories Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)

More information

Power Flow Redistribution in Croatian Power System Network using Phase- Shifting Transformer

Power Flow Redistribution in Croatian Power System Network using Phase- Shifting Transformer Power Flow Redistribution in Croatian Power System Network using Phase- Shifting Transformer Ivica Pavić Faculty of Electrical Engineering and Computing Zagreb, CROATIA Sejid Tešnjak Faculty of Electrical

More information

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device ABB AG - EPDS The worldʼs fastest limiting and switching device Agenda The world s fastest limiting and switching device Customers Function: Insert-holder with insert Comparison: I S -limiter Circuit-breaker

More information

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University

POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE. Professor Akhtar Kalam Victoria University POWER SYSTEM PRINCIPLES APPLIED IN PROTECTION PRACTICE Professor Akhtar Kalam Victoria University The Problem Calculate & sketch the ZPS, NPS & PPS impedance networks. Calculate feeder faults. Calculate

More information

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525.

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525. Time Overcurrent Relays More or less approximates thermal fuse» Allow coordination with fuses Direction of Current nduced Torque Restraining Spring Reset Position Time Dial Setting Disk Basic equation

More information

Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content

Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION. Course Content Course No: 1 13 (3 Days) FAULT CURRENT CALCULATION & RELAY SETTING & RELAY CO-ORDINATION Sr. No. Course Content 1.0 Fault Current Calculations 1.1 Introduction to per unit and percentage impedance 1.2

More information

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS 1 B. RAMESH, 2 K. P. VITTAL Student Member, IEEE, EEE Department, National Institute of Technology Karnataka,

More information

Protection of a 138/34.5 kv transformer using SEL relay

Protection of a 138/34.5 kv transformer using SEL relay Scholars' Mine Masters Theses Student Theses and Dissertations Fall 2016 Protection of a 138/34.5 kv transformer using SEL 387-6 relay Aamani Lakkaraju Follow this and additional works at: http://scholarsmine.mst.edu/masters_theses

More information

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION A DUMMIES GUIDE TO GROUND FAULT PROTECTION What is Grounding? The term grounding is commonly used in the electrical industry to mean both equipment grounding

More information

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com ARC FLASH PPE GUIDELINES FOR

More information

Time-current Coordination

Time-current Coordination 269 5.2.3.1 Time-current Coordination Time that is controlled by current magnitude permits discriminating faults at one location from another. There are three variables available to discriminate faults,

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

TABLE OF CONTENT

TABLE OF CONTENT Page : 1 of 34 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia TABLE OF CONTENT SCOPE 3 REFERENCES

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

9 Overcurrent Protection for Phase and Earth Faults

9 Overcurrent Protection for Phase and Earth Faults Overcurrent Protection for Phase and Earth Faults Introduction 9. Co-ordination procedure 9.2 Principles of time/current grading 9.3 Standard I.D.M.T. overcurrent relays 9.4 Combined I.D.M.T. and high

More information

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017 NAME: LOCATION: 1. The primitive self-inductance per foot of length

More information

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants Martin Best and Stephanie Mercer, UC Synergetic, LLC Abstract Wind generating plants employ several

More information

Impact Assessment Generator Form

Impact Assessment Generator Form Impact Assessment Generator Form This connection impact assessment form provides information for the Connection Assessment and Connection Cost Estimate. Date: (dd/mm/yyyy) Consultant/Developer Name: Project

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

Optimizing HV Capacitor-Bank Design Protection & Testing

Optimizing HV Capacitor-Bank Design Protection & Testing Optimizing HV Capacitor-Bank Design Protection & Testing Benton Vandiver III ABB Inc. 71st Annual Conference for Protective Relay Engineers Texas A&M University Introduction Shunt Capacitor Bank Considerations

More information

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when

More information

Protection Introduction

Protection Introduction 1.0 Introduction Protection 2 There are five basic classes of protective relays: Magnitude relays Directional relays Ratio (impedance) relays Differential relays Pilot relays We will study each of these.

More information

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering) R10 Set No. 1 Code No: R41023 1. a) Explain how arc is initiated and sustained in a circuit breaker when the CB controls separates. b) The following data refers to a 3-phase, 50 Hz generator: emf between

More information

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21 Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive

More information

Preface...x Chapter 1 Electrical Fundamentals

Preface...x Chapter 1 Electrical Fundamentals Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5

More information

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME Donald M. MACGREGOR Electrocon Int l, Inc. USA eii@electrocon.com Venkat TIRUPATI Electrocon Int l, Inc. USA eii@electrocon.com Russell

More information

Overcurrent and Overload Protection of AC Machines and Power Transformers

Overcurrent and Overload Protection of AC Machines and Power Transformers Exercise 2 Overcurrent and Overload Protection of AC Machines and Power Transformers EXERCISE OBJECTIVE When you have completed this exercise, you will understand the relationship between the power rating

More information

PROTECTIVE DEVICES CO-ORDINATTION TOOLBOX ENHANCED BY AN EMBEDDED EXPERT SYSTEM - MEDIUM AND LOW VOLTAGE LEVELS

PROTECTIVE DEVICES CO-ORDINATTION TOOLBOX ENHANCED BY AN EMBEDDED EXPERT SYSTEM - MEDIUM AND LOW VOLTAGE LEVELS PROTECTIVE DEVICES CO-ORDINATTION TOOLBOX ENHANCED BY AN EMBEDDED EXPERT SYSTEM - MEDIUM AND LOW VOLTAGE LEVELS Attia El-Fergany Zagazig University - Egypt el_fergany@hotmail.com SUMMARY Industrial utilities

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D Document type Page Verksamhetsstyrande 1 (11) Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D17-0008990 1.0 Organisation Valid from Valid until Regionnätsaffärer

More information

Adaptive Relaying of Radial Distribution system with Distributed Generation

Adaptive Relaying of Radial Distribution system with Distributed Generation Adaptive Relaying of Radial Distribution system with Distributed Generation K.Vijetha M,Tech (Power Systems Engineering) National Institute of Technology-Warangal Warangal, INDIA. Email: vijetha258@gmail.com

More information

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit

Validation of a Power Transformer Model for Ferroresonance with System Tests on a 400 kv Circuit Validation of a Power Transformer Model for Ferroresonance with System Tests on a 4 kv Circuit Charalambos Charalambous 1, Z.D. Wang 1, Jie Li 1, Mark Osborne 2 and Paul Jarman 2 Abstract-- National Grid

More information

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents Page: 1 Electrical Transient Analyzer Program Short Circuit Analysis ANSI Standard 3-Phase Fault Currents Number of Buses: Swing Generator Load Total 1 0 4 5 Number of Branches: XFMR2 XFMR3 Reactor Line/Cable

More information

Transformer Protection Principles

Transformer Protection Principles Transformer Protection Principles 1. Introduction Transformers are a critical and expensive component of the power system. Due to the long lead time for repair of and replacement of transformers, a major

More information

REF 610 Feeder Protection Relay. Technical Reference Manual

REF 610 Feeder Protection Relay. Technical Reference Manual REF 610 1MRS 755310 Issued: 05.10.2004 Version: A/05.10.2004 REF 610 Contents 1. Introduction...6 1.1. About this manual...6 1.2. The use of the relay...6 1.3. Features...6 1.4. Guarantee...8 2. Safety

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Short-Circuit Analysis IEC Standard 1996-2009 Operation Technology, Inc. Workshop Notes: Short-Circuit IEC Purpose of Short-Circuit Studies A Short-Circuit Study can be used to determine any or all of

More information

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP Kiran V. Natkar 1, Naveen Kumar 2 1 Student, M.E., Electrical Power System, MSS CET/ Dr. B.A.M. University, (India) 2 Electrical Power System,

More information

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Relay withdrawn from case Application The type CDG 11 relay

More information

Power System Protection Where Are We Today?

Power System Protection Where Are We Today? 1 Power System Protection Where Are We Today? Meliha B. Selak Power System Protection & Control IEEE PES Distinguished Lecturer Program Preceding IEEE PES Vice President for Chapters melihas@ieee.org PES

More information

APPENDIX A MATLAB CODE FOR CALCULATION OF MOTOR TORQUE

APPENDIX A MATLAB CODE FOR CALCULATION OF MOTOR TORQUE APPENDIX A MATLAB CODE FOR CALCULATION OF MOTOR TORQUE Table 1 MATLAB code for calculating motor torque[1] %Definition of Motor Parameters V=4000/sqrt(3); %Phase voltage NoPh=3; %Number of Phase NoPo=2

More information

Generator Protection GENERATOR CONTROL AND PROTECTION

Generator Protection GENERATOR CONTROL AND PROTECTION Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault

More information

THE INFLUENCE OF GROUNDING TRANSFORMER ON GROUND FAULT CURRENT IN MV NETWORKS

THE INFLUENCE OF GROUNDING TRANSFORMER ON GROUND FAULT CURRENT IN MV NETWORKS THE INFUENCE OF GROUNDING TRANSFORMER ON GROUND FAUT CURRENT IN MV NETWORKS Hrvoje OPAČAK Tihomir ČAIĆ Siniša JERGOVIĆ HEP Elektroistra - Croatia HEP Elektroistra - Croatia HEP Elektroistra - Croatia hrvoje.opacak@hep.hr

More information

ISSN: Page 298

ISSN: Page 298 Sizing Current Transformers Rating To Enhance Digital Relay Operations Using Advanced Saturation Voltage Model *J.O. Aibangbee 1 and S.O. Onohaebi 2 *Department of Electrical &Computer Engineering, Bells

More information

Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP

Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP Simulation of Short Circuit and Lightning Transients on 110 kv Overhead and Cable Transmission Lines Using ATP-EMTP Predrag Maric 1, Srete Nikolovski 1, Laszlo Prikler 2 Kneza Trpimira 2B 1 Faculty of

More information

Impedance protection on power transformer.

Impedance protection on power transformer. Impedance protection on power transformer www.siemens.com/siprotec5 SIPROTEC 5 Application Impedance Protection on Power Transformer APN-045, Edition 1 Content 1...3 1.1 Introduction...3 1.2 Application

More information

Protecting Large Machines for Arcing Faults

Protecting Large Machines for Arcing Faults Protecting Large Machines for Arcing Faults March 2, 2010 INTRODUCTION Arcing faults occur due to dirty insulators or broken strands in the stator windings. Such faults if undetected can lead to overheating

More information

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11 Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11 COMMISSIONING 12-16 DRAWINGS 17-18 1 1. INTRODUCTION APPLICATION

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

Embedded Generation Connection Application Form

Embedded Generation Connection Application Form Embedded Generation Connection Application Form This Application Form provides information required for an initial assessment of the Embedded Generation project. All applicable sections must be completed

More information

Motor Protection. May 31, Tom Ernst GE Grid Solutions

Motor Protection. May 31, Tom Ernst GE Grid Solutions Motor Protection May 31, 2017 Tom Ernst GE Grid Solutions Motor Relay Zone of Protection -Electrical Faults -Abnormal Conditions -Thermal Overloads -Mechanical Failure 2 Setting of the motor protection

More information

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Cork Institute of Technology Bachelor of Science (Honours) in Electrical Power Systems - Award Instructions Answer FIVE questions. (EELPS_8_Y4) Autumn 2008 Electrical Energy Systems (Time: 3 Hours) Examiners:

More information

Overcurrent relays coordination using MATLAB model

Overcurrent relays coordination using MATLAB model JEMT 6 (2018) 8-15 ISSN 2053-3535 Overcurrent relays coordination using MATLAB model A. Akhikpemelo 1 *, M. J. E. Evbogbai 2 and M. S. Okundamiya 3 1 Department of Electrical and Electronic Engineering,

More information

SPAD 346 C Stabilized differential relay

SPAD 346 C Stabilized differential relay SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP

Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP Simulation of Lightning Transients on 110 kv overhead-cable transmission line using ATP-EMTP Kresimir Fekete 1, Srete Nikolovski 2, Goran Knezević 3, Marinko Stojkov 4, Zoran Kovač 5 # Power System Department,

More information

Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis

Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis M. N. Moschakis* N. D. Hatziargyriou National Technical University of Athens Department of Electrical and Computer Engineering 9, Iroon

More information

ARC FLASH HAZARD ANALYSIS AND MITIGATION

ARC FLASH HAZARD ANALYSIS AND MITIGATION ARC FLASH HAZARD ANALYSIS AND MITIGATION J.C. Das IEEE PRESS SERIES 0N POWER ENGINEERING Mohamed E. El-Hawary, Series Editor IEEE IEEE PRESS WILEY A JOHN WILEY & SONS, INC., PUBLICATION CONTENTS Foreword

More information

Lightning test in lab. Symmetrical fault and protection. Olof Samuelsson

Lightning test in lab. Symmetrical fault and protection. Olof Samuelsson Lightning test in lab Symmetrical fault and protection Olof Samuelsson Outline Three-phase short-circuit fault current Network representation Circuit breakers and disconnectors Measurement transformers

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities

More information

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

thepower to protect  the power to protect i-gard LITERATURE Low and medium voltage thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors

More information

Distance Protection for Distribution Feeders. Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng.

Distance Protection for Distribution Feeders. Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng. Distance Protection for Distribution Feeders Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng. Why use distance protection for distribution feeders? Distance protection is mainly used for protecting

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Tab 2 Voltage Stresses Switching Transients

Tab 2 Voltage Stresses Switching Transients Tab 2 Voltage Stresses Switching Transients Distribution System Engineering Course Unit 10 2017 Industry, Inc. All rights reserved. Transient Overvoltages Decay with time, usually within one or two cycles

More information

A Study on Ferroresonance Mitigation Techniques for Power Transformer

A Study on Ferroresonance Mitigation Techniques for Power Transformer A Study on Ferroresonance Mitigation Techniques for Power Transformer S. I. Kim, B. C. Sung, S. N. Kim, Y. C. Choi, H. J. Kim Abstract--This paper presents a comprehensive study on the ferroresonance mitigation

More information

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. The Importance of the Neutral-Grounding Resistor Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T. Presentation Preview What is high-resistance grounding (HRG)? What is the purpose of HRG? Why

More information

Overcurrent Protective Relays

Overcurrent Protective Relays Power System Protection Overcurrent Protective Relays Dr.Professor Mohammed Tawfeeq Lazim Alzuhairi 99 Power system protection Dr.Mohammed Tawfeeq Overcurrent Protective Relays Overcurrent relays Overcurrent

More information

Transformer Protection

Transformer Protection Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary

More information

DISTRIBUTION DEVICE COORDINATION

DISTRIBUTION DEVICE COORDINATION DISTRIBUTION DEVICE COORDINATION Kevin Damron & Calvin Howard Avista Utilities Presented March th, 08 At the 5 th Annual Hands-On Relay School Washington State University Pullman, Washington TABLE OF CONTENTS

More information

Integration between the MV protection and control unit REF542 and the LV protection trip unit PR123: selectivity and earth fault 1SDC007402G0201

Integration between the MV protection and control unit REF542 and the LV protection trip unit PR123: selectivity and earth fault 1SDC007402G0201 1SDC007402G0201 Index 1. Introduction... 2 2. Theoretical outline 2.1 Restricted earth fault... 3 2.2 Selectivity between medium and low voltage... 4 3. Application examples and wiring logic 3.1 Restricted

More information

How to maximize reliability using an alternative distribution system for critical loads

How to maximize reliability using an alternative distribution system for critical loads White Paper WP024001EN How to maximize reliability using an alternative distribution system for critical loads Executive summary The electric power industry has several different distribution topologies

More information

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM BY MR. H. C. MEHTA AT 1 ST INDIA DOBLE PROTECTION AND AUTOMATION CONFERENCE, NOV 2008 POWER-LINKER Wisdom is not Virtue but Necessity hcmehta@powerlinker.org

More information

This document covers common questions concerning the design of an effectively grounded system.

This document covers common questions concerning the design of an effectively grounded system. This document covers common questions concerning the design of an effectively grounded system. To prevent against temporary overvoltage conditions when a line-to-ground fault occurs on the power grid.

More information

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc. The InterNational Electrical Testing Association Journal FEATURE PROTECTION GUIDE 64S Theory, Application, and Commissioning of Generator 100 Percent Stator Ground Fault Protection Using Low Frequency

More information

Application of SVCs to Satisfy Reactive Power Needs of Power Systems

Application of SVCs to Satisfy Reactive Power Needs of Power Systems 1 Application of SVCs to Satisfy Reactive Power Needs of Power Systems H. K. Tyll, Senior Member, IEEE Abstract In the early days of power transmission problems like voltage deviation during load changes

More information

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY SECTION 16075 - SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Provide a short-circuit, component protection, flash

More information

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION David TOPOLANEK Petr TOMAN Michal PTACEK Jaromir DVORAK Brno University of Technology - Czech

More information

Summary of the Impacts of Grounding on System Protection

Summary of the Impacts of Grounding on System Protection Summary of the Impacts of Grounding on System Protection Grounding System grounding big impact on ability to detect ground faults Common ground options:» Isolated ground (ungrounded)» High impedance ground»

More information

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2 BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY The BE1-67N Ground Directional Overcurrent Relay provides ground fault protection for transmission and distribution lines by sensing the direction and magnitude

More information

TECHNICAL BULLETIN 004a Ferroresonance

TECHNICAL BULLETIN 004a Ferroresonance May 29, 2002 TECHNICAL BULLETIN 004a Ferroresonance Abstract - This paper describes the phenomenon of ferroresonance, the conditions under which it may appear in electric power systems, and some techniques

More information

NERC Protection Coordination Webinar Series July 15, Jon Gardell

NERC Protection Coordination Webinar Series July 15, Jon Gardell Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

7SG14 Duobias-M Transformer Protection

7SG14 Duobias-M Transformer Protection 7SG14 Duobias-M Transformer Protection Document Release History This document is issue 2010/02. The list of revisions up to and including this issue is: Pre release Revision Date Change 2010/02 Document

More information

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS 1 STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS Z. GAJIĆ S. HOLST D. BONMANN D. BAARS ABB AB, SA Products ABB AB, SA Products ABB AG, Transformers ELEQ bv Sweden Sweden Germany Netherlands zoran.gajic@se.abb.com

More information