Type VAEM 22 Negative Potential Biasing Relay

Size: px
Start display at page:

Download "Type VAEM 22 Negative Potential Biasing Relay"

Transcription

1 Type VAEM 22 Negative Potential Biasing Relay

2 Type VAEM 22 Negative Potential Biasing Relay VAEM 22 Relay withdrawn from case Features l Simple and robust construction l High sensitivity Application The negative potential biasing relay type VAEM 22 is designed to prevent the failure of the fine wire coils of protective relays which can arise from electrolytic corrosion. In addition to preventing corrosion, the relay initiates an alarm, if an earthfault occurs on the dc system and also detects any deterioration of the insulation resistance of the dc system. On insulated battery systems, if the coil of a protective relay is at a positive potential with respect to earth, it is anodic to leakage currents and thus results in electrolytic corrosion. If moisture is also present any fine wire coil may be corroded until open circuit occurs. Hence batteries are sometimes earthed in order to prevent electrolytic corrosion. The negative pole cannot be earthed because of the corrosion risk, but solid earthing of positive pole could result in heavy current for a low resistance earthfault on the negative pole. Also, the positive pole cannot be monitored for earthfaults. Resistance earthing of the mid point of the battery enables both positive and negative bus wires to be monitored and the earthfault is limited, however, only part of the circuit is protected against corrosion. The only method of earthing of the battery which provides complete protection from corrosion, enables both bus wires to be monitored, and limits the earthfault current, is the use of a negative potential biasing relay. General description The connection and circuit diagram is shown in Figures 1 and 2. This is suitable for battery voltages upto 250 volts. Figures 1 and 2 show the method of detection using the principle of negative potential biasing, whereby an earthfault anywhere in the field circuit can be detected. The d.c. injection supply establishes a small bias on the alternator field circuit so that all points are negative with respect to earth. The auxiliary transformer used in the biasing circuit is rated at 240 volts ac 50 c/s supply. For systems upto 125 the secondary output is rectified to give a bias voltage of on open circuit. For a 250 system, the bias voltage is

3 The rectified output of a transformer fed from the system L.V. supply provides a biasing potential, which is connected with positive terminal to earth. The negative terminal is connected through a long core unit C to the positive pole of the field circuit. When a fault occurs, current flows in the long core unit, which in turn makes the relay A to operate to give a trip. The scheme will operate only if ac supply is available. If ac supply fails, relay B drop off and initiates an alarm. Operation The scheme will operate only if ac supply is available. If ac supply fails, relay B drops off and initiates an alarm. Technical data Supply rating a) Bias circuit volts 50 c/s. b) Battery voltage - 30 volts to 250 Bias voltage 32.5 ± 7.5% volts for 30 to ± 7.5% volts for 125 to 250 Figure 1: Schematic of negative potential biasing relay type VAEM 22 Earth leakage Setting: 2.25 ± 10%m. amp. dc Burden Less than 6VA at 240V ac Contacts 2 N/O self reset 1 N/C self reset for ac failure alarm. Figure 2: Earth fault detection using negative potential biasing principle in dc system

4 Contact ratings Make and carry Make and carry Break continuously for 3 seconds AC 1250 VA with 7500 VA with 1250 VA with maxima of 5 A maxima of 30 A maxima of 5 A and 660 V and 660 V and 660 V DC 1250 W with 7500 W with 100 W (resistive) maxima of 5 A maxima of 30 A 50 W (inductive) and 660 V and 660 V with maxima of 5 A and 660 V Critical insulation resistance Battery Insulation resistance in K.ohms voltage for fault on negative bus Insulation The relay meets the requirements of IS 3231:1965/IEC Series C-2 KV for 1 minute. Case 1 D drawout case suitable for flush or projection mounting. Information required with order 1. Battery voltage 2. Auxiliary ac voltage 3. Case mounting, flush or projection Note : For fault on positive bus the critical resistance for the operation of the relay is 6 k. ohm.

5 ALSTOM Limited Pallavaram Works: 19/1, GST Road, Pallavaram, Chennai India. Tel: Fax: ALSTOM Limited Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it. ALSTOM Limited cannot be held responsible for any reliance on any decision taken on its contents without specific advice. PR:065:0799:A Printed in India.

Type CAEM 21 Battery Earth Fault Relay

Type CAEM 21 Battery Earth Fault Relay Type CAEM 21 Battery Earth Fault Relay Type CAEM 21 Battery Earth Fault Relay CAEM 21 relay withdrawn from case Features l High sensitivity. l Variable setting range. l Fast operation. l High drop-off/pick-up

More information

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Relay withdrawn from case Application The type CDG 11 relay

More information

Type VDG 13 Undervoltage Relay

Type VDG 13 Undervoltage Relay Type VDG 13 Undervoltage Relay Type VDG 13 Undervoltage Relay VDG 13 relay withdrawn from case Features l Identical time/voltage characteristics on all taps. l Frequency compensated. l Simple construction,

More information

CDV 22, 62. Voltage Controlled Overcurrent Relay GRID PROTECTION

CDV 22, 62. Voltage Controlled Overcurrent Relay GRID PROTECTION PROTECTION CDV 22, 62 Voltage Controlled Overcurrent Relay CDV22 relay is used for overload and fault protection for ac generators when the sustained short circuit current is less than the full load current.

More information

Type MCAG 14, 34 T&D. High Stability Circulating Current Relay

Type MCAG 14, 34 T&D. High Stability Circulating Current Relay PROTETION Type MAG, 3 High Stability irculating urrent Relay The MAG relay, used with a stabilising resistor, is designed for applications where sensitive settings with stability on heavy through faults

More information

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Additional Options Solkor

More information

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Additional Options 15kV Isolation

More information

CIRCUITS THAT ARE AVAILABLE ON LODAR RECEIVERS Features listed below are available on 92 Series and 93 Series

CIRCUITS THAT ARE AVAILABLE ON LODAR RECEIVERS Features listed below are available on 92 Series and 93 Series CIRCUITS THAT ARE AVAILABLE ON LODAR RECEIVERS Features listed below are available on 9 Series and 9 Series STOP CIRCUIT uses are: - OVER TEMPERATURE and OVER PRESSURE, etc. ALLOWS AN EXTERNAL SENSOR TO

More information

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA Instruction Leaflet 41-348.1H Effective: November 1997 Supersedes I.L. I.L. 41-348.1G, Dated January 1985

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Reyrolle Protection Devices. 7PG18 - TR-A High speed tripping Relay. Energy Management.

Reyrolle Protection Devices. 7PG18 - TR-A High speed tripping Relay. Energy Management. Reyrolle Protection Devices 7PG18 - A High speed tripping Relay Energy Management. 7PG18 A High speed tripping relay Features High speed, positive action Can be supplied in modular and drawout type case

More information

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2 BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY The BE1-67N Ground Directional Overcurrent Relay provides ground fault protection for transmission and distribution lines by sensing the direction and magnitude

More information

Earth fault protection for isolated neutral systems with frequency converters

Earth fault protection for isolated neutral systems with frequency converters Earth fault protection for isolated neutral systems with frequency converters Page Issued June 999 Changed since July 998 Data subject to change without notice (SE97089) Features Earth fault and flash-over

More information

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Solkor R & Solkor Rf

More information

Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16

Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16 Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16 COMMISSIONING 17-22 WIRING DIAGRAM 23 1. INTRODUCTION

More information

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY

BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY The BE1-87G is a single or three-phase solid-state variable percentage differential relay designed to provide selective, high-speed, differential protection

More information

3 Pole high impedance differential relay 7VH83

3 Pole high impedance differential relay 7VH83 Fig 1. High impedance differential protection relay 7VH83 Features l Integral CT shorting relay. l Robust solid state design. l Inrush stabilisation through filtering. l Fast operating time. l LED indicator.

More information

Transformer Protection

Transformer Protection Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

7PG21 Solkor Rf Feeder Protection Energy Management

7PG21 Solkor Rf Feeder Protection Energy Management Reyrolle Protection Devices 7PG21 Solkor Rf Feeder Protection Energy Management 7PG21 Solkor Rf Contents Contents Technical Manual Chapters 1. Description of Operation 2. Performance Specification 3.

More information

Earth Fault Relay EFSPL-1A/5A

Earth Fault Relay EFSPL-1A/5A Earth Fault Relay EFSPL-1A/5A IEEE DEVICES CODE-50N Features Static Device Compact, Reliable with Aesthetic Value Rugged, Robust and Tropicalised design Consistent repeat accuracy Wide Current Operating

More information

Instantaneous Overcurrent Relay

Instantaneous Overcurrent Relay Midos Type MCRI Instantaneous Overcurrent Relay Features High speed operation Not slowed by dc transients Settings readily adjustable on relay front plate Two phase and earth fault relay Figure 1: Type

More information

Transformer Fault Categories

Transformer Fault Categories Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)

More information

STATIC EARTH FAULT RELAY

STATIC EARTH FAULT RELAY EARTH FAULT (EFR) EFSPL SERIES IEEE DEVICES CODE-50N Features ŸStatic Device ŸCompact, Reliable with Aesthetic Value ŸRugged, Robust and Tropicalised design ŸConsistent repeat accuracy ŸWide Current Operating

More information

PRODUCT TEST MANUAL 2SY110K28 SYNCHRONISM CHECK RELAY

PRODUCT TEST MANUAL 2SY110K28 SYNCHRONISM CHECK RELAY Sheet 1 of 7 Order Number Serial Number PRODUCT TEST MANUAL 2SY110K28 SYNCHRONISM CHECK RELAY Issue Date Level D 12/12/1996 Initial issue. Summary of changes Due to RMS continuous product improvement policy

More information

Current and voltage measuring relays RXIK 1, RXEEB 1 and RXIB 24

Current and voltage measuring relays RXIK 1, RXEEB 1 and RXIB 24 Current and voltage measuring relays RXIK 1, RXEEB 1 and RXIB 24 RXIK 1 (RXIK_1.tif) RXEEB 1 (RXEEB_1.tif) RXIB 24 (RXIB_24.tif) Features RXIK low current relay, 50-60 Hz and dc High sensitivity 0,5-2

More information

Circuit Breakers. Excerpt from Master Catalogue. Circuit Breakers. Specifically For You

Circuit Breakers. Excerpt from Master Catalogue. Circuit Breakers. Specifically For You Circuit Breakers Excerpt from Master Catalogue Circuit Breakers Specifically For You Hydraulic-magnetic technology ensures reduced nuisance tripping with temperature variance Always holds 00% rated current

More information

EASUN REYROLLE LIMITED

EASUN REYROLLE LIMITED OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W Page 2 / 16 INDEX: GENERAL TYPES ACESSORIES AND OPTIONS INSTALLATION WIRING DIAGRAMS CONNECTING TERMINALS DIAGRAMS WIRING DIAGRAM DESCRIPTION WORKING DESCRIPTION AND KEYBOARD WORKING DESCRIPTION AND PROGRAMMING

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd. Functional Range - Earth Fault Relay C&S Protection & Control Ltd. 2 Contents Page No. 1. Application 2. Operating Principle. Current Transformer Connections 5. Connections, Contact Arrangement and Setting

More information

PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY

PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY Sheet 1 of 12 TEST DATE CUSTOMER SERIAL No OLTC ACKNOWLEDGE SETUP AUTOMATIC or FEEDBACK CONTROL PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY Issue Date Level I 21/05/1998 Initial issue. Summary

More information

DEIF A/S. Insulation monitor. Type SIM-Q

DEIF A/S. Insulation monitor. Type SIM-Q Insulation monitor 4921232C Monitoring of insulation resistance on ungrounded AC networks (IT network) Working voltage up to 69V AC, withstands up to V DC Measuring range 1...Mohm or 1...Mohm Alarm on

More information

Substation Preventive Maintenance

Substation Preventive Maintenance Substation Preventive Maintenance PROVINCIAL ELECTRICITY AUTHORITY 1 Presentation Contents 1) A kind of substation 2) Electrical equipment details of AIS substation 3) Electrical equipment details of GIS

More information

SPAE 010, 011 High Impedance Protection Relay

SPAE 010, 011 High Impedance Protection Relay SPAE 010, 011 High Impedance Protection Relay User s manual and Technical description f n = 50/60 Hz U n = 50 / 100 / 200 V 2 5 U REF > SPAE 010 0.8 U aux 0.6 1.0 RESET OK x 80... 265 V ~ _ 0.4 U > U n

More information

DIGITAL EARTH FAULT RELAY

DIGITAL EARTH FAULT RELAY DIGITAL IDMT / DEFINITE TIME / INSTANTANEOUS Features ŸCompact ŸIDMT (4 IEC curves), Definite Time & Instantaneous ŸWide setting ranges ŸFully digital acquisition & processing of data ŸWide operating voltages

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INSTRUCTIONS MANUAL IM831-U v0.92 HRI-R40W sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS INDEX: GENERAL TYPES ACESSORIES AND OPTIONS

More information

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS. IR Values are to be read on the megger by meggering the Power transformer PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS TESTS ON TRANSFORMERS 1. IR Values This is measured to measure the Insulation Resistance of the whole transformer. a) For 33/11 KV Power Transformer

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY

PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY Sheet 1 of 15 TEST DATE: CUSTOMER: SERIAL NO: OLTC ACKNOWLEDGE SETUP AUTOMATIC or FEEDBACK CONTROL PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY Issue Date Level A 06/01/1997 Initial issue. Summary

More information

1 INTRODUCTION ORDER CODE / INFORMATION

1 INTRODUCTION ORDER CODE / INFORMATION INTRODUCTION ORDER CODE / INFORMATION 269/269Plus * * * * * * 269/269Plus SV D/O.4 ORDER CODE / INFORMATION Motor management relay Standard version Drawout version Phase CT Ground CT (required for D/O

More information

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM BY MR. H. C. MEHTA AT 1 ST INDIA DOBLE PROTECTION AND AUTOMATION CONFERENCE, NOV 2008 POWER-LINKER Wisdom is not Virtue but Necessity hcmehta@powerlinker.org

More information

POWER SYSTEM II LAB MANUAL

POWER SYSTEM II LAB MANUAL POWER SYSTEM II LAB MANUAL (CODE : EE 692) JIS COLLEGE OF ENGINEERING (An Autonomous Institution) Electrical Engineering Department Kalyani, Nadia POWER SYSTEM II CODE : EE 692 Contacts :3P Credits : 2

More information

MOTOR PROTECTION RELAY

MOTOR PROTECTION RELAY MOTOR Introduction Prok dv s make uses the state-ofthe-art Microcontroller based measurement techniques for providing protection for Motors up-to 75HP. The comprehensive protection features of the relay

More information

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300 Monitoring Technique VARIMETER IMD Insulation monitor RN 5897/300 0274214 Your Advantages For mobile generator sets according to DIN VDE 0100-551 Preventive fire and system protection Detection of symmetric

More information

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers

save energy, it is precious SYNERGY transformers Mfg. of all types of Distribution / Power & Furnace Transformers save energy, it is precious Mfg. of all types of Distribution / Power & Furnace Transformers SYNERGY transformers SAFETY AND EFFICIENCY, COMBINED WITH LONG-TERM RELIABILITY, ARE THE HALLMARKS OF WORLD-RENOWNED

More information

SYNCHRONISING AND VOLTAGE SELECTION

SYNCHRONISING AND VOLTAGE SELECTION SYNCHRONISING AND VOLTAGE SELECTION This document is for Relevant Electrical Standards document only. Disclaimer NGG and NGET or their agents, servants or contractors do not accept any liability for any

More information

DEIF A/S. Insulation monitor. Type SIM-Q/SIM-Q LF

DEIF A/S. Insulation monitor. Type SIM-Q/SIM-Q LF / LF Insulation monitor Monitoring of insulation resistance on ungrounded AC networks (IT network) Working voltage up to 69V AC, withstands up to V DC Measuring range...kω or 1...MΩ Working frequency down

More information

SPAD 346 C. Stabilized Differential Relay. User s manual and Technical description SPAD 346 C V ~ V. f n SPCD 3D53 SPCJ 4D28

SPAD 346 C. Stabilized Differential Relay. User s manual and Technical description SPAD 346 C V ~ V. f n SPCD 3D53 SPCJ 4D28 SPAD 6 C Stabilized Differential Relay User s manual and Technical description f n = 50Hz 60Hz I n = A 5A ( I ) I n = A 5A ( I ) I n = A 5A ( I 0 ) I n = A 5A ( I 0 ) 5 I I d L L I L I > IRF I 0 > I 0

More information

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed

More information

DIAC Type 66K. DIGITAL OVERCURRENT RELAY Instruction Manual. GE Power Management

DIAC Type 66K. DIGITAL OVERCURRENT RELAY Instruction Manual. GE Power Management g GE Power Management DIAC Type K DIGITAL OVERCURRENT RELAY Instruction Manual DIAC K Revision: SPDV0.A0 Manual P/N: GEK-0C Copyright 000 GE Power Management GE Power Management Anderson Avenue, Markham,

More information

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide Relion 605 series Relion 605 series Self-Powered Feeder Protection Product Guide Contents 1 Description...3 2 Protection functions...3 3 Application...4 4 Self-supervision...4 5 Inputs and outputs...4

More information

Differential Protection with REF 542plus Feeder Terminal

Differential Protection with REF 542plus Feeder Terminal Differential Protection with REF 542plus Application and Setting Guide kansikuva_bw 1MRS 756281 Issued: 09.01.2007 Version: A Differential Protection with REF 542plus Application and Setting Guide Contents:

More information

MBCI (Translay S) Technical Manual. Differential Feeder and Transformer Feeder Protection. Publication Reference: GRID

MBCI (Translay S) Technical Manual. Differential Feeder and Transformer Feeder Protection. Publication Reference: GRID MBCI (Translay S) Technical Manual Differential Feeder and Transformer Feeder Protection Publication Reference: R8011G R8011G 2011. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks

More information

Design a Power System Simulator Model and Implement the Generator and Motor Controlling

Design a Power System Simulator Model and Implement the Generator and Motor Controlling Design a Power System Simulator Model and Implement the Generator and Motor Controlling G.U De Silva, G.B Alahendra, A.C.P Aluthgama, P.G.L Arachchi Supervised by: Prof. J Rohan Lucas, Eng. J. Karunanayake

More information

High-Speed DC Circuit-Breaker for Fixed Installation Type UR26, UR36 & UR40

High-Speed DC Circuit-Breaker for Fixed Installation Type UR26, UR36 & UR40 High-Speed DC Circuit-Breaker for Fixed Installation Type UR26, UR36 & UR40 C O M P O N E N T S The UR26, UR36 & UR40 are DC high-speed current limiting air Circuit-Breakers, trip free, single pole, bi-directional,

More information

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers KNOW MORE ABOUT THE TRANSFORMERS Glossary Transformers Ambient temperature The existing temperature of the atmosphere surrounding a transformer installation. Ampere The practical unit of electric current.

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

Installation/operation instructions. Insulation monitor type SIM-Q/SIM-Q LF D (UK) Measuring range 1...0Mohm or 10...

Installation/operation instructions. Insulation monitor type SIM-Q/SIM-Q LF D (UK) Measuring range 1...0Mohm or 10... Installation/operation instructions Insulation monitor type SIM-Q/SIM-Q LF Monitoring of insulation resistance on an AC network Working voltage up to 690V AC, withstands up to 1000V DC Measuring range

More information

SPAA 341 C. Feeder Protection Relay. User s manual and Technical description SPAA 341 C. U aux V ~ V. f n. t 2 > [ s ] 0 I 0 >> Trip

SPAA 341 C. Feeder Protection Relay. User s manual and Technical description SPAA 341 C. U aux V ~ V. f n. t 2 > [ s ] 0 I 0 >> Trip SPAA C Feeder Protection Relay User s manual and Technical description f n = 0Hz 0Hz I n = A A ( I ) I n = A A ( I 0B ) I n = 0,A A ( I 0 ) U n = 00V 0V 0V ( ) U 0 I > I I L I L I L I o IRF Uo I o ϕ U

More information

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero Consider a bus and its associated circuits consisting of lines or transformers. The algebraic

More information

XD1-T - Transformer differential protection relay

XD1-T - Transformer differential protection relay XD1-T - Transformer differential protection relay Contents 1. Application and features 2. Design 3. Characteristics 3.1 Operating principle of the differential protection 3.2 Balancing of phases and current

More information

DIGITAL EARTH FAULT RELAY

DIGITAL EARTH FAULT RELAY DIGITAL IDMT / DEFINITE TIME / INSTANTANEOUS Features Compact IDMT (4 IEC curves), Definite Time & Instantaneous Wide setting ranges Fully digital acquisition & processing of data Wide operating voltages

More information

Apprentice Electrical Technician Test (ETT) Preparation Guide

Apprentice Electrical Technician Test (ETT) Preparation Guide Apprentice Electrical Technician Test (ETT) Preparation Guide APPRENTICE ELECTRICAL TECHNICIAN TEST (ETT) About the Test There are 40 questions with a maximum time limit of three hours. This is a closed

More information

Relion 605 series. Self-Powered Feeder Protection REJ603 Application manual

Relion 605 series. Self-Powered Feeder Protection REJ603 Application manual Relion 605 series Relion 605 series Relion 605 series Self-Powered Feeder Protection REJ603 Application manual Document ID: 1MDU07206-YN 6 2 4 This document and parts thereof must not be reproduced or

More information

RUDOLF Digital power analyzer. Advanced Version

RUDOLF Digital power analyzer. Advanced Version RUDOLF Digital power analyzer Advanced Version Digital power analyzer Advanced Version Company Introduction Bridex Singapore Pte Ltd is founded in 1978 as a manufacturer of instruments transformer for

More information

INTER PLANT STANDARD STEEL INDUSTRY

INTER PLANT STANDARD STEEL INDUSTRY INTER PLANT STANDARD STEEL INDUSTRY IPSS SPECIFICATION FOR VIBRATION MEASURING SYSTEM FOR LOW SPEED MACHINES (Second Revision) Corresponding IS does not exist IPSS:2-07-027-11 Formerly: IPSS:2-07-027-97

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

XD1-T Transformer differential protection relay. Manual XD1-T (Revision A)

XD1-T Transformer differential protection relay. Manual XD1-T (Revision A) XD1-T Transformer differential protection relay Manual XD1-T (Revision A) Woodward Manual XD1-T GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49 TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument True RMS measurement User-friendly programing Four different types for optimal specification RS485 interface For 3- or 4-wire connection Compact

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection) Differential Protection (Unit protection) Differential Protection Differential protection is the best technique in protection. In this type of protection the electrical quantities entering and leaving

More information

Earth Fault Indicator EFI-BLZ-50 User Manual

Earth Fault Indicator EFI-BLZ-50 User Manual Earth Fault Indicator EFI-BLZ-50 User Manual CONTENTS SAFETY NOTICE.................................................................................... 3 1 OVERVIEW......................................................................................

More information

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson...

Current Transformer Requirements for VA TECH Reyrolle ACP Relays. PREPARED BY:- A Allen... APPROVED :- B Watson... TECHNICAL REPORT APPLICATION GUIDE TITLE: Current Transformer Requirements for VA TECH Reyrolle ACP Relays PREPARED BY:- A Allen... APPROVED :- B Watson... REPORT NO:- 990/TIR/005/02 DATE :- 24 Jan 2000

More information

High-Tech Range. IRI1-ER- Stablized Earth Fault Current Relay. C&S Protection & Control Ltd.

High-Tech Range. IRI1-ER- Stablized Earth Fault Current Relay. C&S Protection & Control Ltd. High-Tech Range IRI1-ER- Stablized Earth Fault Current Relay C&S Protection & Control Ltd. Contents 1. Summary 7. Housing 2. Applications 3. Characteristics and features 4. Design 7.1 Individual housing

More information

YL SERIES RELAY LATCH DC COIL 4PDT, LOW LEVEL TO 5 AMP

YL SERIES RELAY LATCH DC COIL 4PDT, LOW LEVEL TO 5 AMP Magnetic latch operation All weld construction Contact arrangement 4 PDT Qualified to MIL-PRF-6106 PRINCIPLE TECHNICAL CHARACTERISTICS Applicable sockets: SO-1066-001 SM-1002-003 Contacts rated at Low

More information

KENYA ELECTRICITY GENERATING COMPANY LTD

KENYA ELECTRICITY GENERATING COMPANY LTD KENYA ELECTRICITY GENERATING COMPANY LTD TENDER No. KGN-HYD-014-2016 TENDER FOR REHABILITATION OF PROTECTION EQUIPMENT FOR MASINGA HYDRO POWER STATION 20/06/2016 ADDENDUM NO. 1 In accordance with the tender

More information

Trade of Electrician. The Transformer

Trade of Electrician. The Transformer Trade of Electrician Standards Based Apprenticeship The Transformer Phase 2 Module No. 2.1 Unit No. 2.1.10 COURSE NOTES Created by Gerry Ryan - Galway TC Revision 1 April 2000 by Gerry Ryan - Galway TC

More information

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24

HIGH VOLTAGE ENGINEERING(FEEE6402) LECTURER-24 LECTURER-24 GENERATION OF HIGH ALTERNATING VOLTAGES When test voltage requirements are less than about 300kV, a single transformer can be used for test purposes. The impedance of the transformer should

More information

Reyrolle Protection Devices. 7PG11-18 Alpha Electromechanical Relays. Siemens. Answers for energy.

Reyrolle Protection Devices. 7PG11-18 Alpha Electromechanical Relays. Siemens. Answers for energy. Reyrolle Protection Devices 7PG11-18 Alpha Electromechanical Relays Answers for energy. Siemens Alpha Technical Manual Contents Contents Technical Manual Chapters 1. Introduction to Electromechanical

More information

SPAD 346 C Stabilized differential relay

SPAD 346 C Stabilized differential relay SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

MFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work

MFAC. Grid Solutions. High Impedance Differential Relay. MFAC Types. Key Benefits. Application. Description. Imagination at work GE Grid Solutions MFAC High Impedance Differential Relay MFAC relays provide high speed differential protection for various types of power systems plants including generators, reactors, busbars, motors

More information

3 Circuit Theory. 3.2 Balanced Gain Stage (BGS) Input to the amplifier is balanced. The shield is isolated

3 Circuit Theory. 3.2 Balanced Gain Stage (BGS) Input to the amplifier is balanced. The shield is isolated Rev. D CE Series Power Amplifier Service Manual 3 Circuit Theory 3.0 Overview This section of the manual explains the general operation of the CE power amplifier. Topics covered include Front End Operation,

More information

Type: ADR233A (ADITYA V2 Series) (Preliminary) ASHIDA Numerical 3 Phase Tx. Differential Protection Relay

Type: ADR233A (ADITYA V2 Series) (Preliminary) ASHIDA Numerical 3 Phase Tx. Differential Protection Relay Ashida Numerical 3 Directional Phase Tx. 3O/C Differential + 1E/F Protection PROTH. ERR FAULT 87 L5 L6 REF L7 BF TRIP ADR 233B_V2 233A_V2 Protection Features: 3Phase Tx. Differential Protection + REF Programmable

More information

RESTRICTED EARTH FAULT RELAY

RESTRICTED EARTH FAULT RELAY RESTRICTED EARTH FAULT RELAY (REFR) IEEE Device Code: 87N Features ŸMicroprocessor Based Design ŸWide Setting Ranges ŸUniversal Auxiliary supply 85-275V AC/DC ŸRugged and Compact Design Ÿ8 Character Back-lit

More information

Testing Potential Transformers

Testing Potential Transformers Testing Potential Transformers By Les Warner (PCA Valence) and Chris Werstiuk ( LLC) Potential transformers (PTs) are necessary to a power system for metering and protective relaying to convert higher

More information

MONITORING OF DISTRIBUTION TRANSFORMER PARAMETERS USING PLC

MONITORING OF DISTRIBUTION TRANSFORMER PARAMETERS USING PLC MONITORING OF DISTRIBUTION TRANSFORMER PARAMETERS USING PLC Shubhangi Landge¹, Snehal Waydande², Sanjay Sangale³, Somesh Gaikwad⁴ ¹Assistant Professor, Dept. Of Electrical Engineering, AISSMS IOIT College,

More information

INSTRUCTION MANUAL FOR DIODE FAULT DETECTOR

INSTRUCTION MANUAL FOR DIODE FAULT DETECTOR Publication Number: 351-02014-00 Publication Date: September 1990 Revised: March 1998 INSTRUCTION MANUAL FOR DIODE FAULT DETECTOR Part Number: 508-00118-40 508-00118-41 508-00118-42 508-00118-44 508-00118-45

More information

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY

CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY CHIEF ENGINEER REG III/2 MARINE ELECTROTECHNOLOGY LIST OF TOPICS 1 Electric Circuit Principles 2 Electronic Circuit Principles 3 Generation 4 Distribution 5 Utilisation The expected learning outcome is

More information

www. ElectricalPartManuals. com Westinghouse HRU Instantaneous Overcurrent Relay with Harmonic Restraint Descriptive Bulletin Page 1

www. ElectricalPartManuals. com Westinghouse HRU Instantaneous Overcurrent Relay with Harmonic Restraint Descriptive Bulletin Page 1 Westinghouse Appl ication The H R U harmonic restraint relay is a high speed relay used for the supervision of differential, overcurrent. or pilot relays. It is applied in various transformer protection

More information

Electronic Circuit Breaker ESS1 for System SVS1

Electronic Circuit Breaker ESS1 for System SVS1 Electronic Circuit Breaker for System SVS Description The electronic circuit breaker is designed to ensure selective disconnection of individual s in industrial systems which are powered by a DC 24 V switch

More information

presentation contents application advantages

presentation contents application advantages presentation contents page presentation protection functional and connection schemes other connection schemes connection characteristics 9 installation 0 commissioning ordering information Sepam 00 is

More information

TRANSFORMER OPERATION

TRANSFORMER OPERATION Chapter 3 TRANSFORMER OPERATION 1 A transformer is a static device (no moving parts) used to transfer energy from one AC circuit to another. This transfer of energy may involve an increase or decrease

More information

M79 EARTH FAULT RELAY

M79 EARTH FAULT RELAY M79 EARTH FAULT RELAY 1 of 6 GENERAL INFORMATION The M79 static relay is used in DC distribution systems discharged to ground, to monitor, detect, and indicate any current leakage in the earth system.

More information

GE Power Management. Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C

GE Power Management. Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C GE Power Management Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C 7$%/(2)&217(176 1. DESCRIPTION...2 2. APPLICATION...6 3. CHARACTERISTICS...7

More information

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability

More information

Protection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique

Protection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique Protection and control Sepam range Sepam 0 LA Self-powering protection Merlin Gerin Square D Telemecanique presentation contents page presentation protection functional and connection schemes other connection

More information

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012

SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM. Unit Objectives. Unit Objectives 2/29/2012 SECTION 3 BASIC AUTOMATIC CONTROLS UNIT 12 BASIC ELECTRICITY AND MAGNETISM Unit Objectives Describe the structure of an atom. Identify atoms with a positive charge and atoms with a negative charge. Explain

More information