Type: ADR233A (ADITYA V2 Series) (Preliminary) ASHIDA Numerical 3 Phase Tx. Differential Protection Relay
|
|
- Roland Kelly
- 5 years ago
- Views:
Transcription
1 Ashida Numerical 3 Directional Phase Tx. 3O/C Differential + 1E/F Protection PROTH. ERR FAULT 87 L5 L6 REF L7 BF TRIP ADR 233B_V2 233A_V2 Protection Features: 3Phase Tx. Differential Protection + REF Programmable (Non- Volatile) Setting By local keys as well as remote setting by communication port Latching of fault current value. Operation base on fundamental frequency value. Harmonics restrain for Tx charging and CT saturation condition. Breaker Failure detection. Cross harmonics restrain. Programmable starting current. Programmable Internal ICT( interposing CT) ratio to match different transformer having different vector groups Programmable dual bias setting Wide setting range 10-50% for bias in steps of 5% Programmable 2nd HRM restrain 10% - 80% Design Features: Large 20x4 LCD display for Parameter and setting display Disturbance Recorder. Up 1 sec of actual waveform of current along with logical and physical status, are captured & saved in the built-in memory with date time stamping, for analyzing fault condition & fault location. Fully communicable with IEC or IEC61850 protocol Very low burden on CT (less than 0.5VA) Continuous monitoring of module s internal hardware and alarm generation in case of failure of any critical components. Facility to synchronised time from SCADA 5 Digital Output contacts for local alarm as well as tele-signalling 5 Optically isolated digital status input for monitoring of status and avoid used of external relay logic Page 1 / 11
2 100 nos of event memory, event such CB close, Trip, digital status change, relay pkp etc. All events are with date and time stamped up to 1ms. 10 nos of Fault data stored with keypad interface and time stamping. Description: ADR233A is second generation Numerical Transformer differential. It consist all the necessary protection and monitoring functions required for transformer, it consist of 1. High Speed Digital DSP Controller 2. Analog Measuring Module 3. Power supply Module 4. Digital Input output module. The High speed Digital Signal Controller continuously monitors line HV and LV current + REF current. Along with different status input, through CTs, and optical isolated status connections. The high-speed micro-controller samples these current signals through a A/D converter. The Digital Signal performs powerful Numerical Algorithms to find out RMS of fundamental & harmonic contents of the current. All measurement is tuned to fundamental frequency i.e 50Hz, thus relay remain stable during distorted waveform generated electronics loco-motive. All these measure values are then used for different protection function.. These measured values are also displayed on large 20 x 4 LCD display for metering purpose. The DSC also monitor different digital input through optical isolator and control potential free contact for control CB and generate ALARM and Telesignalling. The power supply module is basically DC DC converted designed using modern PWM based Switching mode technique to convert 110Vdc station battery supply to the 12V and 24Vdc low voltage supply for relay electronics and control circuit. It also provides necessary isolation from station battery. There are two type of power supply modules are available 1) having range of 77Vdc 250Vdc. Covering requirement of 110Vdc and 220Vdc station battery system 2) having range of 18Vdc to 52Vdc covering 24Vdc, 30Vdc, 48Vdc station battery requirement. The relay is having total 8 nos of dual LED of high intensity for easy identification of type of fault for easy user interface. LEDs L5, L6 and L7 and R1 to R5, digital status input and controlled output are fully programmable via key pad interface. Main Functions The ADR233A are having following protection functions. 1. Transformer differential protection. 2. REF protection. 3. Breaker Failure Detection. 4. Monitoring Functions. Each of these functions are independently programmable and can be enable or disable by user depending upon requirement Page 2 / 11
3 Differential Protection (87): The ADR233A monitor HV and LV current of power transformer through respective CT. The sample current values are processed by power fully DSP controller. It convert the these current samples in to equivalent vectors and numbers of parameter such as RMS values of IHV and ILV and phases. IHV represent HV current and ILV represent LV current. Normally to match HV and LV CT ratio, phase shift between two winding due to transformer vector group, ICTs (interposing CTs) are needed. In ADR233A ICTs are software selectable. There are two separate ICT ratio and vector groups are provided, one for HV value and another for LV value. After applying this corrective factor, relay calculate operating and restring signal from IHx and ILx (IH1 and IL1 is HV and LV current after applying ICT correction factor. x denote phase, 1 for R, 2 for Y and 3 for B). Base on this and setting relay decide to operate or restrain. Operating Current Iox = IHx ILx Restraining Current Ibx = ( IHx + ILx ) / 2 operate when Io is greater than pick-up current setting and Iox > = S Ibx Where S = set bias. (Slope 1) The relay support dual bias characteristic. The bias (slop 1) is settable from 10% to 50% This is a normal bias characteristic. The relay follows this characteristic up to Ibx become equal to 2nd Bias I setting. During heavy through fault due to CT saturation large difference current might generate, which lead to mal operation of relay. To prevent mal operation during such heavy through fault relay is provided with dual bias characteristic. In which after 2nd Bias I setting the relay change it bias setting from set value to 80% SLOP 1 SLOP 2 automatically. The relay is provided with differential highest protection where IHx-ILx is greater than a preset value relay will provided high-set protection. High-set setting can be bypassed when it is not required. The relay detect transformer charging condition from 2nd harmonics contents. If 2nd harmonics are more than set limit then relay block tripping operation. Similarly relay detect over excitation condition from 5th and restrain it operation. Most of the relays are multifunction and having large numbers of setting. The ADR series relay Page 3 / 11
4 having big 4 line 20 character back lit LCD display and very strong user interface, this make very easy to manage the relay setting. All setting are arranged in menus for easy understanding of parameter Restricted Earth Fault: The relay is equipped special REF protection section for transformer winding. The setting for REF protection is 5% to 80% of rated. The relay give instant trip command as soon as it detected EF in restricted zone. Maximum settings in one display The relay shows all the parameters such current before ICT current after ICT, Primary current, Bias and difference current. Breaker Failure Detection:- Normally after tripping current should become Zero within ms time depend upon type of fault and breaker mechanism. After Fault ADR233A trigger internal timer (settable from 0.1s to 1.0s) If fault is not cleared during this time then relay declare as Breaker fail (LBB function) and change another contacts. This contact is marked as Breaker Fail can be used to trip back up breaker or can be used to generate ALARM signal. Programmable DI/DO and LED:- The ADR233A has got 5 digital outputs, 5 optoisolated input and 6 general purpose LEDs. These can be programmed by local key board. Any logical of physical status can be assigned to any relay contact The logic of digital status input as well as logical status can be formed and assigned to any of the relay output. The disturbance record can be trigger from external logical input. Monitoring Functions (Event, Disturbance Record):- Apart from basic protection functions. is continuously monitors all substations operation through status, it internal functions, internal hardware etc. if any changed is observed it Page 4 / 11
5 marked as event. Such type of events is stored in internal non-volatile memory along with time stamped. Following some of the events. PKP, Reset, CB Trip, CB close, Changed of any digital status input, setting changed etc. Up to 100 such event can be stored and can be download for detailed analysis. Apart from Event record also record actual waveform of current along with all digital and logical status during fault condition. Up to 10 such waveforms can be recorded, the duration of disturbance record is 1 sec. The disturbance record can be trigger from physical status input as well as from pick, trip operation of relay. This waveform can be downloaded through communication port for further analysis. By using this software data such as event log, disturbance records etc can be down loaded and can be further analysis. The disturbance record data can be saved in standard COMTRADE Format which is understandable by numbers of relay testing units for play back. Talk Software: The general communication software is provided to communicate with relay, known as Talk. Following as some of software clips All The data can view at time Page 5 / 11
6 Event list with real time The waveform and logical and physical status latched by relay can be view and analysed Data can be viewed as raw sine wave or RMS value Page 6 / 11
7 Page 7 / 11
8 While Ordering Specify the following Information for ADR233AA Definition of Model No of Aditya Series of s AM XXX XX X X XX X Reserved for Future Use PT Secondary 0 = NO PT 1 = 63.5 PT sec CT Secondary 1 = 1 Amp. 2 = 5 Amp. 3 = 1 Amp. / 5 Amp. Selectable Auxiliary Supply 01 = V dc 06 = 110 V dc 02 = V dc 07 = 220 V dc 03 = 24 V dc 04 = 30 V dc 05 = 48 V dc AM XXX XX X Over current Earth Fault For Adity-V2 series start from 201. For V1 series refer respective document with standard Back Connection with IEC Communication with standard Back Connection with IEC61850 Communication CSE H CSE H Ordering information: A D R A - A M - X X X - X X - X - X - X X - X Example ADR233A AM with standard setting IEC com St. Back terminal layout Cabinet Type: CSE -150 H Terminal Removable Auxiliary Supply: Vdc CT sec: 1 Amp. / 5 Amp selectable Page 8 / 11
9 Technical Specifications: General specifications Sr. No. Specification Particulars I. Current Input : Suitable for CT secondary 5 Amp. or 1 Amp site selectable II. Aux. Supply : VDC. Or 18V 52V to be specify III. VA burden on CT : Less than 0.2VA IV. VA burden on Aux. : Less than 10 Watts V. Operating Temp. range : -10 deg. To + 65 deg. VI. Continuous Current carrying capacity : 2 x of rated VII. Pick up : with in 1.1 times of set VIII. Reset Value : 95% to 90% of pick up. IX. Output Contact : 2 for Trip : 1 for REF Trip : 1 for BF : 1 for PROTH. : 1 for RL OK : 5 for General Programmable X. Contact Rating : Continuous: 5A : Make & carry for 0.5 sec : 30A : Make carry for 3 sec : 15A XI. Opto Isolated input general programmable : 2 + common Input : 5 -ve common XII. Operating Time : Diff < 40ms at 2 times :REF < 25ms at 5 times XIII. Thermal With stand for CT : 20 x of rated for 3.0 sec. Differential Protection (87) XIV. Vector group compensation for HV winding Vector group compensation for LV winding REF section (Ie) XV. Ie : 87 OFF/ON : Operating Current (Io) 10% - 100% insteps of 1% : Bias : 10-50%. In steps of 5% : 2 nd Harm. Restrain : 10% to 80 % settable : High Set setting : 100% to 2000% in steps of 100% : 2 nd Bias I 100% -400% insteps of 50% : VH:- Yy0,Yy2,Yy4,Yy6,Yy8,Yy10,Yd1,Yd3,Yd5, Yd7,Yd9,Yd11,Ydy0 and Ydy6 : VL:- Yy0,Yy2,Yy4,Yy6,Yy8,Yy10,Yd1,Yd3,Yd5, Yd7,Yd9,Yd11,Ydy0 and Ydy6 :Ie> : OFF / ON :Ie> 5% - 80% insteps of 5% Page 9 / 11
10 Breaker Fail (BF) XVI. :BF OFF/ON :BF delay : 0.1S 1.0s XVII. Operational Indicators (Flags) PROT.H /ERR : Green LED indicates OK (Protection Healthy) : In case of following condition led become Red 1. Problem in relay Hardware. FAULT - 87 : Red LED indicates FAULT Hand Reset (HR) Type. REF : Red LED indicate REF Fault XVIII. BF L5 / L6 / L7 TRIP Drawing References : Green LED indicate Breaker Fail (HR) Type : Spare LED Programmable : Green LED indicates Output trip relay contact closer (SR) Type : For Cabinet Type - MAC01302 : For Back Connections - ADV01301 : For Typical External connection - ADV01401 : For Draw-out Arrangement - MAC01303 Sr. No. Title Standard no. Electromagnetic Compatibility Type Test : I. High Frequency test : IEC , class III : Frequency : 1MHz Damped Oscillatory : Longitudinal :5 KV (peak) : Duration: sec duration 2 sec. : Between input current Terminal II. Electrostatic discharge Direct application : IEC Class III and IEC class III. : Contact discharge: 6kV, : Air discharge: 8KV : Polarity: both +ve and Ve polarities. III. Indirect application : IEC , Class-III IV. Fast transient disturbance V. Surge immunity test VI. VII. VIII. Power frequency immunity test Power frequency magnetic field test Radiated electromagnetic field disturbance : IEC and IEC , class A : 1.2KV; 5/50ns; 5KHz burst duration = 15ms. : Repetition rate 300ms; Both polarities; Ri = 50Ω; duration 1 min. : IEC / IEC class 4 : Differential Mode = 2kV : Common Mode = 4kV : 1.2/50uS, 5 surges of each polarity : IEC , Class-A : IEC , Class-V : IEC : EN : Frequency 80MHz 1GHz Page 10 / 11
11 IX. Conducted Disturbance induced by Radio Frequency field X. AC Ripple in DC supply Test XI. Radiated emission : IEC : IEC / IEC : : Freq. 150kHz 80MHz, Amplitude 10 V, Modulation 80% 1 KHz : IEC Insulation tests: XII. High Voltage Test : IEC class III : At 2.5kV 50Hz between all terminal connected together and earth for 1 minutes XIII. Impulse Voltage Test : IEC class III : Test voltage: 5KV (peak) 1.2 / 50us, : Energy :0.5 J, : Polarity : + ve and Ve : Nos. of impulses : 3 positive and 3 negative impulse : Duration between Impulses : 5 sec. Environmental tests: XIV. Cold test Storage test : IEC XV. Dry heat test : IEC XVI. Damp heat test, steady state : IEC XVII. Damp heat test, cyclic : IEC CE compliance XVIII. Immunity : IEC XIX. Emissive Test : IEC XX. Low voltage directive : EN Mechanical tests XXI. Vibration : IEC class 1 : Frequency Range = 10Hz 150Hz, acceleration. = 1g n (9.8 m/s 2 ) : Sweep rate 1 octave/min; 20 cycle in 3 orthogonal axis. XXII. Shock and bump : IEC XXIII. Seismic : IEC Revision Date Description Jan 2008 Original specs Page 11 / 11
12
13
14
15
ASHIDA Numerical 3OC + 1EF Protection Relay
PROTH. ERR L5 PKP FAULT DT REC LOCK BF L6 L7 CLOSE TRIP ADR 241B Protection Features : 4 Element (3 Phase + EF + Sensitive EF) Over current IDMT/DMT with instant trip. Programmable (Non- Volatile) Setting
More informationASHIDA Numerical Directional 3OC + 1EF Protection Relay
Ashida Numerical Directional 3O/C + 1E/F PROTH. PROTH. ERR L5 FAULT PKP PKP FAULT L6 PT DT REC LOCK BF L7 CLOSE TRIP TRIP CLOSE ADR 145B 245B Protection Features: 4 Element (3 Phase + EF +sensitive EF)
More informationASHIDA Numerical OC/EF Protection Relay
ASHIDA Numerical OC/EF Protection Relay Features: 4 Element (3 Phase + EF) over current IDMT with instant trip. Back - lit LCD display for settings. Display of fault current. / Load current. Selection
More informationOvercurrent Protection / 7SJ45
Overcurrent Protection / SJ SIPROTEC easy SJ numerical overcurrent protection relay powered by CTs Fig. / Description SIPROTEC easy SJ numerical overcurrent protection relay powered by current transformers
More informationHigh-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime
Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with
More informationNPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.
REGULATION AUTOMATIC SYNCHRONIZER for GENERATOR NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds
More informationNPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator
REGULATION Automatic Synchronizer for Generator NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds
More informationRelion 605 series Self-Powered Feeder Protection REJ603 Product Guide
Relion 605 series Relion 605 series Self-Powered Feeder Protection Product Guide Contents 1 Description...3 2 Protection functions...3 3 Application...4 4 Self-supervision...4 5 Inputs and outputs...4
More informationALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring
ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring The first Real-Time Protection and Automation platform that can be adapted to a wide variety of applications. While
More informationSIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay
Overcurrent Protection / 7SJ46 SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Function overview Fig. /11 Description The SIPROTEC easy 7SJ46 is a numerical overcurrent protection relay which
More informationSPECIFICATION FOR OVERCURRENT RELAYS
SPECIFICATION FOR OVERCURRENT RELAYS 1/9 1. Procedure A manufacturer willing to classify an overcurrent relay according to this specification should provide: A complete file providing a clear, unambiguous
More informationApplication Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters
Technical Data Sheet Alpha 20 Alpha 20 is a compact multifunction instrument which Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel
More informationwww. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay
Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:
More informationREK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual
REK 50 protection of a synchronous machine User s Manual REK 50 X 0 9 8 7 6 5 4 0 V 00 V 0 V 5 6 7 Ordering No: REK 50-AA Uau = 00/0 Vac Un = 48 V Serial No: fn = 50/60 Hz Uec = ma 600 Vdc MRS 75587-MUM
More informationRS Pro ENGLISH. Datasheet
Datasheet Article No: 136-5385 Digital AC Ammeter, 48x96, 1Phase, 1 or 5 Amps AC, Supply 40-300V ac/dc 136-5387 Digital AC Ammeter, 96x96, 1Phase, 1 or 5 Amps AC, Supply 40-300V ac/dc 136-5388 Digital
More informationJewell DPM EINE BEST IN CLASS
Application: Silent Features: The digital panel meter has been designed Fast & Easy installation on panel with the for industrial applications, which help of external swivel screws. frequently require
More informationALPHA 20 MULTIFUNCTION METER (ALPHA SERIES)
Alpha Series www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters Shunts ALPHA
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities
More informationStabilized Differential Relay SPAD 346. Product Guide
Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault
More informationProtection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique
Protection and control Sepam range Sepam 0 LA Self-powering protection Merlin Gerin Square D Telemecanique presentation contents page presentation protection functional and connection schemes other connection
More informationRS Pro ENGLISH. Datasheet
Datasheet ENGLISH Article No: 136-5390 Digital AC Ammeter, 48x96, 3Phase, 1 or 5 Amps AC, Supply 40-300V ac/dc 136-5391 Digital AC Ammeter, 96x96, 3Phase, 1 or 5 Amps AC, Supply 40-300V ac/dc 136-5393
More informationAMIK 200 / 201 Technical Data Sheet
AMIK 200 / 201 Technical Data Sheet AMIK Special Features MODBUS (RS-485) Communication available only on Amik 201 On site Programmable CT/PT Ratios User selectable CT Secondary 1A/5A User selectable PT
More informationpresentation contents application advantages
presentation contents page presentation protection functional and connection schemes other connection schemes connection characteristics 9 installation 0 commissioning ordering information Sepam 00 is
More informationSPECIFICATION. Online UPS 3000VA
Page 1 / 7 DESCRIPTION Pure sine-wave output UPS on-line double conversion type. INPUT AC Mains voltage 230V ac 1 phase Mains voltage range 184...264V ac Mains frequency range 47...63Hz Power factor at
More informationTransformer differential protection
Transformer differential protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970883) Features Three phase differential protection with two, three, five or
More informationAMIK Three Phase Digital Panel Meters
AMIK Three Phase Digital Panel Meters USA SICE 1936 ELIAILIT EOD MEASUE Special Features 3 Line 4 Digits ultra bright LED Display (up to 9999) On site Programmable CT/PT atios User selectable CT Secondary
More informationFault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice
Issued: April 1999 Status: Updated Version: B/08.11.200 Data subject to change without notice Features Versatile, multifunction line fault indicator for distribution networks Overcurrent, earth-fault and
More informationUtility Communications Teleprotection Equipment TPT-200
Utility Communications Teleprotection Equipment TPT-200 5C Communications Inc. All rights reserved Teleprotection is designed to transfer protection commands coming, in most cases, from distance protection
More informationSPAD 346 C Stabilized differential relay
SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault
More informationT/3000 T/3000. Substation Maintenance and Commissioning Test Equipment
T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY
More informationRISH Delta Energy / Demand (Multifunction instrument) Data Sheet
ISH Delta Energy / Demand (Multifunction instrument) Data Sheet www.rishabh.co.in Page 1 of 6 Version: D 14 / 03 / 2012 Application: ISH Delta Energy measures important electrical parameters in 3 phase
More informationTheta 20A / 20V. Technical Data Sheet. Special Features
Technical Data Sheet Theta 20A / 20V Theta 20A / 20V is used to measure and convert AC Voltage or Current input into a load independent DC current or voltage output signal. Special Features Available in
More informationPower Meter Series PM3200 Functions and characteristics
Functions and characteristics PB108433 This PowerLogic Power meter offers basic to advanced measurement capabilities. With compact size and DIN rail mounting, the PM3200 allows mains and feeders monitoring
More informationMHCO MHCO-RI. General Characteristics The transducer MHCO provide a measurement of current or voltage fully isolated and safe.
-TVI -RI -RV D.C. MEASURING CONVERTER Converter for D.C. Current and/or Voltage measurement. Direct connection to D.C. mains rating up to 4 kvcc. Fully isolated multi-voltage power suppy. Fiber optic connection
More informationContents. 1 Introduction. 2 System-Level Electrostatic Discharge (ESD) and Electrical Fast Transient. 3 Electromagnetic Interference
Issue 3, October 2002 Electromagnetic Compatibility and Electrical Safety Contents Telcordia GR-1089 - Documentation Information Generic Requirements Notice Of Disclaimer................. iii Contents.......................................
More informationTransformer protection IED RET 670
Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth
More informationDOBLE F6150e TECHNICAL SPECIFICATIONS
DOBLE F6150e TECHNICAL SPECIFICATIONS The F6150e line of System Simulators is designed for simulation tests on relay and protection schemes. There are four distinct models for your specific testing needs.
More informationIRIG-B Interface (De-modulated) External clock synchronization signal IRIG format B00X
P847B&C Technical Data Sheet INTERFACES IRIG-B (De-modulated) Use Standard Connector Cable type Isolation Input signal Input impedance at dc Accuracy IRIG-B Interface (De-modulated) External clock synchronization
More informationPM5000 Series. PowerLogic PM5100, PM5300 and PM5500 series
Functions and characteristics PowerLogic PM5100, PM5300 and PM5500 series PB111776 The PowerLogic applications. It provides the measurement capailities needed to allocate energy usage, perform tenant metering
More informationTime over/underfrequency relay with protection assemblies
Time over/underfrequency relay with protection assemblies RXFK 2H and RAFK 509 009-BEN Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970104) (SE970108) Features
More informationEASUN REYROLLE LIMITED
OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT
More informationTechnical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay
Technical Datasheet RELAY-1 RELAY-2 k V Hz RESET ABH TEST True RMS Measurement True RMS Digital Protection V/Hz is used to protect against Over Voltage, Under Voltage, Phase Unbalance, Phase Sequence detection,
More information)HDWXUHV Voltage restraint overcurrent stage with five different inverse or definite time characteristics
9ROWDJHUHVWUDLQWRYHUFXUUHQW UHOD\DQGSURWHFWLRQ DVVHPEOLHV 5;,6.+DQG 5$,6. 509 033-BEN Page 1 Issued: September 2001 Changed since: June 1999 Data subject to change without notice (SE970171) (SE970896)
More information02/11/2015
Modem communication plug and play solutions GSM Part number 88970119 For remote control of your application Automatic notification of alarms via SMS (GSM Modem) / email or on a PC with M3 ALARM software.
More informationApplication and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16
Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16 COMMISSIONING 17-22 WIRING DIAGRAM 23 1. INTRODUCTION
More informationTest Specification for Type Approval
A2 (1991) (Rev.1 1993) (Rev.2 1997) (Rev. 2.1 July 1999) (Rev.3 May 2001) (Corr.1 July 2003) (Rev.4 May 2004) (Rev.5 Dec 2006) (Rev.6 Oct 2014) Test Specification for Type Approval.1 General This Test
More information02/11/2015
Modem communication plug and play solutions GSM Part number 88970119 For remote control of your application Automatic notification of alarms via SMS (GSM Modem) / email or on a PC with M3 ALARM software.
More informationALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)
Alpha Series www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters Shunts ALPHA
More informationTechnical Datasheet. True RMS Digital Protection Relay. Voltage Protection Relay
Technical Datasheet RELAY-1 RISHABH k V RESET True RMS Digital Protection Relay RELAY-2 TEST True RMS Measurement RISH Relay V is used to protect against Over Voltage, Under Voltage, Phase Sequence detection,
More informationDOBLE F6150SV TECHNICAL SPECIFICATIONS
DOBLE F6150SV TECHNICAL SPECIFICATIONS The F6150sv line of System Simulators is designed for simulation tests on relay and protection schemes. There are four distinct models for your specific testing needs.
More informationHarmonic restraint earth fault or single-phase overcurrent protection
Harmonic restraint earth fault or single-phase overcurrent protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970885) Features Sensitive earth fault protection
More informationHI-Physix Laboratory, L-83, Sector-1, DSIDC Industrial Area, Bawana, Delhi. Discipline Electronics Testing Issue Date
Last Amended on - Page 1 of 14 I. AUDIO EQUIPMENT 1. Audio-Video and Similar Electronics Apparatus Safety Requirement Marking & Instructions Laser Radiation (Products Marked Class I only) Heating under
More informationRISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:
(With All Display Parameters) Application : RISH EM 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network
More informationRelay. Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay
Line Monitoring Technical Datasheet RISH RELAY-1 RELAY-2 RISHABH k V Hz True RMS Digital Protection RISH V/Hz is used to protect against Over Voltage, Under Voltage, Phase Unbalance, Phase Sequence detection,
More informationXDC 6000 Watt and Watt Series Digital Programmable DC Power Supply. Operating Manual
XDC 10-600 XDC 20-300 XDC 30-200 XDC 40-150 XDC 60-100 XDC 80-75 XDC 100-60 XDC 150-40 XDC 300-20 XDC 600-10 XDC 10-1200 XDC 20-600 XDC 30-400 XDC 40-300 XDC 60-200 XDC 80-150 XDC 100-120 XDC 150-80 XDC
More informationLaboratory Accreditation Programmes
Laboratory Address PO Box 68307, Newton, Auckland, 1145 47 Mackelvie Street, Grey Lynn, Auckland, 1021 Telephone 09 360-0862 Fax 09 360-0861 URL Authorised Representative Client No. 2218 Programme Accreditation
More informationTechnical Data Sheet. x1000. kwh R Y B
Technical Data Sheet x1000 Von kwh IRev 3600 imp /kwh R Y B is a compact multifunction instrument which is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy
More informationSPAE 010, 011 High Impedance Protection Relay
SPAE 010, 011 High Impedance Protection Relay User s manual and Technical description f n = 50/60 Hz U n = 50 / 100 / 200 V 2 5 U REF > SPAE 010 0.8 U aux 0.6 1.0 RESET OK x 80... 265 V ~ _ 0.4 U > U n
More informationData Sheet. RISH Master Record %THD
Data Sheet %THD Application : measures important electrical parameters & replaces the multiple analog panel meters. It measures electrical parameters like AC current, Voltage, frequency, active energy
More informationTransformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK
Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK (RXLK_2H.tif) RALK.psd Features Micro-processor based time-overexcitation relay with continuous settings for
More informationSPAD 346 C. Stabilized Differential Relay. User s manual and Technical description SPAD 346 C V ~ V. f n SPCD 3D53 SPCJ 4D28
SPAD 6 C Stabilized Differential Relay User s manual and Technical description f n = 50Hz 60Hz I n = A 5A ( I ) I n = A 5A ( I ) I n = A 5A ( I 0 ) I n = A 5A ( I 0 ) 5 I I d L L I L I > IRF I 0 > I 0
More informationModular multifunction generator protection
Modular multifunction generator Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970186) Features is a modular generator that enables selection of the desired in
More informationDSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.
15 Watts xxx Series Ultra Slim Design 15% Peak Load for 3 seconds Ambient Operation from -1 C to +7 C High Efficiency Selectable Overload Characteristic Selectable Remote Inhibit or Enable 3 Year Warranty
More informationTechnical Data Sheet AMIK 300 / 301
USA SINCE 1936 RELIABILITY BEYOND MEASURE Technical Data Sheet AMIK 300 / 301 LISTED File No. E471457 AMIK AMIK 300 is a compact multifunction instrument with touch screen LCD utility which measures important
More informationT 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers
Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator Test results and settings are saved into local memory
More informationCentrale de mesure Power Meter PM500 Merlin Gerin
Notice d'installation et d'utilisation Installation and user manual Centrale de mesure Power Meter PM500 Merlin Gerin 059473_D Introduction and description Package contents c one PM500 power meter with
More informationHV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point
2010 MAP Range HV / MV / LV electrical network quality analyzers Class A > Network quality Analyzers PRODUCT ADVANTAGES COMPLIANT with the EN 61000-4-30 standard, Class A DETECTION of the fault LOCATION
More informationDevice Under Test: ALTEA VS- 24-I VS-24-I. 0 24/09/12 First issue A. Peretto L. Peretto 1 24/06/16 All text review E. Scala L. Peretto J. L.
/9 TECHNICAL SPECIFICATIONS VOLTAGE LOW-POWER TRANSFORMER VS- Rev. Date Revision Description Prepared by Checked by Approved by 0 24/09/2 First issue A. Peretto L. Peretto 24/06/6 All text review E. Scala
More informationDigital Multifunction Instrument - Rish Master 3440
Application Rish Master 3440 measures important electrical parameters in 3 phase and single phase etwork & replaces the multiple analog panel meters. It measures electrical parameters like AC current,
More informationRISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:
Application : RISH Master 3490 SS is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy having auto-resetting 8 digit seven segment LED counter. The unit
More informationPLC-K506 Series FEATURES DESCRIPTION FEATURES
FEATURES Two High Speed Counters Two Pulse Train Outputs Two Pulse Width Modulation Outputs Inputs 10 Outputs 1 RS232 Port 2 RS485 Ports Supports Modbus RTU Protocol Communicate With Up to 32 Devices DESCRIPTION
More informationTD 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers
Secondary Injection Relay Test Set Designed for testing relays and transducers Two current outputs to test differential relays Convertible current and voltage generator With phase angle shifter Frequency
More informationTable of Contents. 1 Introduction. 2 System-Level Electrostatic Discharge (ESD) and Electrical Fast Transient (EFT) 3 Electromagnetic Interference
Electromagnetic Compatibility and Electrical Safety GR-1089-CORE Table of Contents Table of Contents 1 Introduction 1.1 Purpose and Scope.................................. 1 1 1.2 Items Not Covered in
More informationRISH Master Digital Multifunction Instrument with onsite pluggable output options. Application : Product Features:
Application : RISH Master 3430 measures important electrical parameters in 3 phase and single phase Network & replaces the multiple analog panel meters. It measures electrical parameters like AC current,
More informationProtective Relays Digitrip 3000
New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer
More informationsatech SynchroStar GPS 200 Series
satech SynchroStar GPS 200 Series KEY BENEFITS Designed with high quality oscillator OCXO the device is characterized by superior frequency stability and improved holdover performance that allows maintaining
More informationA Comparison Between MIL-STD and Commercial EMC Requirements Part 2. By Vincent W. Greb President, EMC Integrity, Inc.
A Comparison Between MIL-STD and Commercial EMC Requirements Part 2 By Vincent W. Greb President, EMC Integrity, Inc. OVERVIEW Compare and contrast military (i.e., MIL-STD) and commercial EMC immunity
More informationMulti-voltage Multi-function. Wiring diagram (without control signal)
80 Modular timers 16 A 80 Multi-function and mono-function timer range 80.01T - Multi-function & multi-voltage 80.11T - On-delay, multi-voltage Complies with EN 45545-2:2013 (protection against fire of
More informationPowerLogic power-monitoring units. PM700 series power meter. Technical data sheet
PowerLogic power-monitoring units PM700 series power meter Technical data sheet 2009 Functions and characteristics The PowerLogic PM700 series power meter offers all the measurement capabilities required
More information1 INTRODUCTION ORDER CODE / INFORMATION
INTRODUCTION ORDER CODE / INFORMATION 269/269Plus * * * * * * 269/269Plus SV D/O.4 ORDER CODE / INFORMATION Motor management relay Standard version Drawout version Phase CT Ground CT (required for D/O
More informationINTER PLANT STANDARD STEEL INDUSTRY VARIABLE VOLTAGE VARIABLE FREQUENCY SYSTEM (V.V.V.F.) V/F, VECTOR CONTROL / TORQUE CONTROL
INTER PLANT STANDARD STEEL INDUSTRY VARIABLE VOLTAGE VARIABLE FREQUENCY SYSTEM (V.V.V.F.) V/F, VECTOR CONTROL / TORQUE CONTROL IPSS: 1-10-035-06 IPSS Corresponding IS does not exist 0. FOREWORD 0.1 This
More informationwww. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay
Generator Differential Relay The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3G relay offers the following
More informationReyrolle Protection Devices. 7SG14 Duobias M Transformer Protection. Answers for energy
Reyrolle Protection Devices 7SG4 Duobias M Transformer Protection Answers for energy 7SG4 Duobias M Transformer Protection Description Optional Functionality High Impedance Restricted Earth Fault per winding
More information200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features
CT ratio Power Harmonics ac+dc 200ADM-P Current Injection System with Phase Shift Features 0-200A output current True RMS metering with 1 cycle capture Variable auxiliary AC voltage/current output with
More informationSIPROTEC 7SS60 Centralized Numerical Busbar Protection
SIPROTEC 7SS60 Centralized Numerical Busbar Protection Fig. /1 Description The SIPROTEC 7SS60 system is an inexpensive numerical differential current protection for busbars in a centralized configuration.
More informationn True RMS measurement n Fully onsite programmable input voltage range (for CIP-V)
Tranducers for alternating current/voltage n True RMS measurement n Fully onsite programmable input voltage range (for CIP-V) and input current range (for CIP-I) n Available in single or dual output type
More informationKNC-PLC-K506 Series FEATURES DESCRIPTION FEATURES
FEATURES Two High Speed Counters Two Pulse Train Outputs Two Pulse Width Modulation Outputs Inputs 10 Outputs 1 RS232 Port 2 RS485 Ports Supports Modbus RTU Protocol Communicate with up to 32 devices DESCRIPTION
More informationSirius 250/350 Watts, Single / Multi output AC-DC, modular power solution
Up to 350W Up to 6 outputs Voltages up to 28V, Current up to 50 mps Fast-on output connection Worldwide approvals 3 Year Warranty Sirius 250/350 Watts, Single / Multi output C-DC, modular power solution
More information2017 Advanced Energy Industries, Inc. HITEK POWER MV2000 SERIES MEDIUM-VOLTAGE HIGH-CURRENT POWER SUPPLIES
2017 Advanced Energy Industries, Inc. HITEK POWER MV2000 SERIES MEDIUM-VOLTAGE HIGH-CURRENT POWER SUPPLIES Medium-voltage rack-mount power supplies Page 2 The MV2000 series high-performance, medium output
More informationAdvanced, accurate and intelligent monitoring for your transformer
QUALITROL 505 ITM Intelligent transformer monitor Advanced, accurate and intelligent monitoring for your transformer The power to know your transformer health immediately with TransLife Advanced thermal
More informationModern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions
1 Transmission transformers are important links in the bulk power system. They allow transfer of power from generation centers, up to the high-voltage grid, and to bulk electric substations for distribution
More informationProtection and control VIP300. Technical manual
Protection and control VIP300 Technical manual contents 1. presentation of the VIP300...3 2. use and settings...4 3. choice of sensors and operating ranges...9 4. connection scheme...10 5. assembly...11
More informationManual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual.
Manual Title: 550A Getting Started Supplement Issue: Part Number: 415509 Issue Date: 9/18 Print Date: November 01 Page Count: 19 Revision/Date: This supplement contains information necessary to ensure
More informationDRTS 66 The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters
The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual
More informationDigital Motor Bus Transfer System M 4272
SYNCHRONIZING Digital Motor Bus Transfer System M 4272 Integrated Synchronizing System Provides Automatic and Manual transfers of motor bus systems in power plants and industrial processing plants to ensure
More informationWIRELESS INSULATOR POLLUTION MONITORING SYSTEM
SYSTEM OVERVIEW Pollution monitoring of high voltage insulators in electrical power transmission and distribution systems, switchyards and substations is essential in order to minimise the risk of power
More informationElectrical network management. Schneider Electric. PM3200 Technical Datasheet
Electrical network management Schneider Electric PM3200 Technical Datasheet Functions and characteristics PB108433 This PowerLogic Power meter offers basic to advanced measurement capabilities. With compact
More informationMedical Safety Approvals (-M versions) Industrial Heavy Duty Terminals. Output Power up to 1500 W. High Power Density - 18W/in 3
HPU1K5 Series Low Profile 1.7 (43.2 mm), Industrial Supply Medical Safety Approvals (-M versions) Industrial Heavy Duty Terminals Output Power up to 1500 W Load dependant variable speed fans for audible
More informationTB65 65W Single Output Test and Measurement/Industrial Series
Features 2.0 x 3.5 x 1.3 Package TB65 Up to 65W Convection Cooled Output Power Compliant to high levels of EMC per EN61000-4 15kV ESD (Air), 8kV (Contact) 4kV Surge Meets Class B Conducted EMI with 6db
More information