Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16

Size: px
Start display at page:

Download "Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16"

Transcription

1

2 Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16 COMMISSIONING WIRING DIAGRAM 23

3 1. INTRODUCTION APPLICATION The type MVT181 numeric under voltage / over voltage relay combines the power and flexibility of microprocessor technology.two protection elements, multiple characteristics and TRUE RMS measurements are available. Moreover, supervisory components and self monitoring features give high confidence of serviceability. 2. APPLICATION MVT181 is a numerical TRUE RMS single pole over voltage and under voltage relay, which can be used to protect the power system during over voltage and under voltage conditions. Though the relay is generally applicable for any under and over voltage application, this relay is best suited for capacitor bank protection as this is having an in-built timer function. A time delay function is necessary in a capacitor bank protection to allow the capacitor bank to discharge to a safer level, before reconnecting the same to the system. Otherwise there will be a danger to the breaker and the capacitor bank, while the capacitor charged to a negative peak is connected to the system voltage when it is in positive peak. 3. DESCRIPTION 3.1. Two Elements MVT181 is a numerical TRUE RMS single pole relay consists of two elements. Each element can be selected for under voltage function or over voltage function or switched off. The characteristics setting, voltage setting and time multiplier setting are independently settable for each element and the voltage setting is in terms of voltage. Hence this relay can also be used as a two stage under voltage / two stage over voltage protection. One stage U/V & One stage O/V Multiple Characteristics Over voltage function is provided with four operating characteristics and under voltage function has two operating characteristics Over Voltage Characteristics a) Definite time lag b) Long time Inverse Characteristic t = 40 * T M [ (V/V ) - 1] S 2

4 c) Extremely Inverse 1 (EI 1) 5 * T M t = 2 2 [ (V/V S) - 1 ] d) Extremely inverse 2 (EI 2) This curve is based on ANSI / IEEE C37.99 and IEC The time delay for various multiples of over voltage is given below for TMS 1.0. Multiples of Setting Voltage Operating time (Sec) Where t = Operating Time in Secs V = Fault Voltage V s = Setting voltage T M = Time Multiplier Setting 3.4. Under Voltage Characteristics a) Definite Time Lag b) Extremely Inverse 1 (EI 1) 5 * T M t = 2 [1 (V/V ) ] 3.5. Timer S 2 The relay is provided with two status inputs, one of which is to be connected across the circuit breaker auxiliary contact 52a. From this the circuit breaker closed or opened condition is found out. This information is used to introduce a time delay between successive switching of the capacitor banks which allows the capacitor bank to discharge to a safer value after disconnected from a live network. This timer function is a settable one and its output (N/O) contact is used in the closing circuit of the circuit breaker. The completion of the time delay is also indicated by 'TIMER' LED in the front fascia. In addition the same status input can be used for trip circuit supervision also. During the under voltage and over voltage applications this timer function can be disabled or used as an independent timer function Trip Circuit Supervision Pre-closing and post closing supervision of the trip circuit and trip supply is possible with this relay. A low value of DC current is passed through the entire trip circuit to monitor the trip coil, its auxiliary 3

5 switch and the associated wiring. One of the status input is connected across the tripping contact and another status input is connected across the 52a contact (auxiliary contact of the circuit breaker) in series with the trip coil. During trip circuit fail condition the monitoring current flow ceases and the energized status input drops off and the relay gives a contact output to indicate this condition. In addition to this contact On LED is provided in the front fascia to indicate the 'T.C.FAIL'. A time delay of approximately 400 m.sec has been given to avoid false trip circuit fail indication at the time of normal tripping. Thus trip circuit supervision is the integral part of the relay. If this function is not required the same can be put off in the setting menu. 4. TECHNICAL INFORMATION 4.1. Rating upto 230 V AC (same terminals) Frequency 50 Hz Nominal 4.2. Auxiliary Supply Nominal Voltage Voltage Range 24 / 30 / 48 / 110V DC V DC 48/110/220 V DC or 110V AC V DC 4.3. DC Status Input Nominal Voltage Voltage Range 24 / 30 DC V DC * - For status input nominal voltage greater than 30V, external dropper resistors should be used Settings Element Setting Element 1: UV, OV or OFF Element 2 : UV, OV or OFF Voltage Setting 5V to 275V in steps of 1V Characteristic Setting When the element is set as Under Voltage a) Definite time lag (DTL) characteristics 0 to 200 sec in steps of 0.1 sec b) Extremely inverse 1 (EI 1) characteristics t = 5 * T M 2 2 [1 (V/V s) ] 4

6 When the element is set as Over Voltage a) Definite time lag characteristics 0 to 200 sec in steps of 0.1 sec b) Long Time Inverse characteristics t = 40 * T M [ (V/V ) - 1 ] s c) Extremely Inverse 1 (EI 1) characteristics 5 * T M t = [ (V/V ) 1 ] 2 2 s d) Extremely Inverse 2 (EI 1) characteristics This is based on ANSI / IEEE C37-99 and IEC The standard time delay for various multiples of over voltage is given as under for time multiplier setting of 1.0. Multiples of Setting Voltage Operating time (Secs) Where t V V T s M = Operating Time in Secs = Fault Voltage = Setting voltage = Time Multiplier Setting Time Multiplier Setting to 1.0 in steps of ( for all inverse characteristics) Time setting if DTL is selected 0 to 200 Secs in steps of 0.1 Sec Timer For CB Closing Interlock 0 to 600 secs in steps of 1 sec or OFF Trip Circuit Supervision On or OFF 5

7 4.5. Accuracy Starter pick-up (UV) 96% of V s +3% Starter drop-off (UV) <106% of V s Starter pickup (OV) 104% of V +3% ( except for EI 2) s Starter Pickup (OV) 108% of V s +3% (EI 2) Starter drop-off (OV) >94% of V s Inverse operating time +5% or 35 m.sec Voltage measurement +3% DTL operating time +1% or 35 m.sec 4.6. Output Contact Rating Carry continuously Make & Carry Break 5A AC rms or DC 20A AC or DC for 0.2 Sec 50W DC with a max. of 300V or 5A DC L/R <40mS 4.7. Indication Green LED Protection Healthy Yellow LED Starter Indication Red LED Trip Indication Red LED Trip circuit fail Red LED Completion of timer 7 segment Display Settings / Trip indication 4.8. Burden AC < 0.015VA at 63.5V < 0.035VA at 110V < 0.15VA at 230V DC (Quiescent) 5W 5. ENVIRONMENTAL 5.1. Temperature IEC /2 Operating Range -10 C to + 55 C Storage Range -25 C to + 70 C 5.2. Humidity IEC days at 40 C and 93% RH 6

8 5.3. Transient Over voltage IEC kV,1.2/50µS, 0.5j between all terminals and earth or between any two terminals without damage or flashover Insulation IEC kV rms for 1 min between all terminals and earth 2.0kV rms for 1 min between independent circuits 1.0kV rms for 1 min across normally open contacts 5.5. High Frequency Disturbance IEC , Class III Variation 2.5kV Common (Longitudinal) mode <3% 1.0kV series (Transverse) mode <3% 5.6. Electrostatic Discharge IEC , Class III Variation 6kV Contact Discharge <5% 8kV Air Discharge <5% 5.7. Radio Frequency Interference IEC , Class III Variation 20MHz to 1000 MHz, 10V/m <3% 5.8. Fast Transient IEC , Class IV Variation 4kV, 5/50 ns, 2.5kHz repetitive <5% 5.9. Vibration (Sinusoidal) IEC , Class Shock & Bump IEC , Class 1 6. CUTOUT DETAILS 151 x 151mm (2/3 Vedette draw out case) 7

9 1. UNPACKING INSTALLATION On receipt, remove the relay from the carton box in which it was received and inspect it for obvious damage. It is recommended that the relay is not removed from the relay case. To prevent the possible ingress of dirt, the sealed polythene bag should not be opened until the relay is to be used. If damage has been sustained, please inform Easun Reyrolle Ltd., for necessary action. 2. STORAGE When the relay is not required for immediate use, it should be returned to its original carton and stored in a clean dry place. 3. HANDLING The relay's electronic circuits are protected from damage by static discharge when the relay is housed in its case. When relay is withdrawn from the case, static handling procedures should be observed: Before removing the relay from its case the operator must first ensure that he is at the same potential as the relay, by touching the case. The relay must not be handled by any of the relay terminals at the rear of the chassis. Ensure that anyone else handling the relay is at the same potential. As there are no user serviceable parts and adjustable user settings inside the relay, there should be no requirement to remove any modules from the chassis. If any modules are removed or tampered with, then the guarantee will be invalidated. 4. MOUNTING Mount the relay using 2 nos. mounting straps and 1no earth strap. Ensure that an earth wire is connected to the earth strap from the earth terminal 23. Terminal 23 should be directly connected to the system ground. Only settings or trip details can be accessed via the pushbuttons when the cover is fitted. To change the settings the front cover has to be removed. Sealing arrangement is provided in one of the four knurling screws fitted on the cover. Sealing can be done using a sealing wire. Thus mechanical interlock is provided to avoid unauthorized setting change. 5. EQUIPMENT 5.1. Voltage Selection MVT 181 relay is suitable for up to 230V A.C. applications 8

10 5.2. Status Input Two status inputs ( 5& 6, 7 & 8) have to be wired for trip circuit fail application/ capacitor discharge timer interlock. One status input (7&8) can be used for only capacitor discharge timer interlock. The status input external resistors are connected as per the typical wiring diagram shown (Fig 4) and the resistors value is given in the following table. Nominal Voltage Operating Range R1,R2,R3 & R4 Relay terminal nos. 48V DC 1.36 to 60V DC 1.0K ohms/9w 110V DC 2.88 to 135V DC 3.9K ohms/9w 5 & 6, 7 & V DC to 280V DC 8.2K ohms/9w 5.3. Human Machine Interface (HMI) Table 1 shows input external resistors The user friendly HMI provided on the front panel has following features: 1. Six digit, 7 segment LED display (First two digits are Red colour and other four digits are Green colour). first two digits (Red) displays the main menu or type Element operated when selected for Setting mode or Trip indication respectively. Remaining four digits (Green) displays Sub menu or "Trip" indication respectively. 2. Green LED - Protection healthy indication 3. Yellow LED(STARTER) - Starter indication 4. Red LED (TRIP) - Trip indication 5. Red LED (in Key) - Sub Menu 6. Red LED (T.C.FAIL) - Trip circuit Fail indication 7. Red LED (TIMER) - Timer operated indication 8. Key - Up scrolling 9. Key - Down scrolling 10. Key - Sub menu 11. x Key - Enter / Reset / Cancel / To check Version 9

11 5.4. How to operate HMI Remove the front cover by unscrewing the four knurling screws. Apply DC supply. Terminals 22,24 and 23 are for positive, negative and earth respectively as per relay rating. When the relay powers up it takes few seconds to complete the self-test routing. Ensure Protection Healthy LED (Green) is ON and busy indication appears on the LED display unit. Wait until the busy indication goes off. Press or key nnut I8 is displayed nnut I8 Represents MVT 181 relay Press key repeatedly scrolls down the Factory setting Main menu in the following order on the display. El off - Element 1 is OFF ( El is Main menu and off is sub menu) E2 off - Element 2 is OFF td l0 - Timer setting is 10Secs tc off - Trip circuit supervision is OFF 6. SETTING INSTRUCTIONS 6.1. Voltage Function Selection ELEMENT 1 Pressing key repeatedly to get El off Main menu, press Submenu Key, LED in the Key Lit to indicate that the Sub menu is activated off - voltage function is OFF undr - Under voltage ** ouer - Over voltage By pressing or key choose the desired voltage function(under voltage or Over voltage or OFF) for Element 1 and press key. Now the Submenu LED goes OFF and the Main menu appears on the LED display ELEMENT 2 Pressing key repeatedly to get E2 off Main menu, press Submenu Key, LED in the Key Lit to indicate that the Sub menu is activated. 10

12 off - voltage function is OFF undr - Under voltage ** ouer - Over voltage By pressing or key choose the desired voltage function((under voltage or Over voltage or OFF) for Element 2 and press key. Now the Submenu LED goes OFF and the Main menu appears on the LED display ** Ensure AC voltage input more than the setting is given to the relay terminal number 11 &12 before selecting Under voltage function to avoid unnecessary tripping Voltage Settings Setting Range : 5V to 275V in steps of 1V ( For Element 1 - over voltage /under voltage and Element 2 - over voltage /under voltage) Pressing key Ul l00 (represents voltage for Element 1 is 100V) display will appear if Element 1 voltage function is chosen Pressing key U2 l00 (represents voltage for Element 2 is 100V) display will appear if Element 2 voltage function is chosen The voltage function can be select to OFF. If any voltage function is chosen to off that particular voltage main menu will not appear in display ELEMENT 1 Pressing key repeatedly and Ul l00 Main menu (represents voltage for Element 1 has been set to 100V), press key (Submenu LED On) to get the Sub menu. Pressing the or key, changes the voltage setting in 1V increment or decrement. Upon selecting the desired setting, once again press the key (Sub menu LED goes OFF) to return to the main menu ELEMENT 2 Pressing key repeatedly and U2 l00 Main menu (represents voltage for Element 1 has been set to 100V), press key (Submenu LED On) to get the Sub menu. Pressing the or key, changes the voltage setting in 1V increment or decrement. Upon selecting the desired setting, once again press the key (Sub menu LED goes OFF) to return to the main menu Select Characteristics ELEMENT 1 a) For Under Voltage 11

13 From Cl Ell Main menu, press Submenu Key, LED in the Key Lit to indicate that the Sub menu is activated. Pressing key repeatedly the Sub menu will scroll down in the following order on the display Ell - Extremely Inverse 1(EI1) d tl - Definite Time Lag (DTL) By pressing or key choose the desired characteristic and press Key. Now the Submenu LED goes OFF and the Main menu appears on the LED display. b) For Over Voltage From C2 Ell Main menu, press Submenu Key, LED in the Key Lit to indicate that the Sub menu is activated. Pressing key repeatedly the Sub menu will scroll down in the following order on the display Ell - Extremely Inverse 1(EI1) El2 - Extremely Inverse 2(EI2) Ltl - Long Time Inverse (LTI) dtl - Definite Time Lag (DTL) ELEMENT 2 a) For Under Voltage From CI Ell Main menu, press Submenu Key, LED in the Key Lit to indicate that the Sub menu is activated. Pressing key repeatedly the Sub menu will scroll down in the following order on the display Ell - Extremely Inverse 1(EI1) dtl - Definite Time Lag (DTL) By pressing or key choose the desired characteristic and press Key. Now the Submenu LED goes OFF and the Main menu appears on the LED display. b) For Over Voltage From C2 Ell Main menu, press Submenu Key, LED in the Key Lit to indicate that the Sub menu is activated. 12

14 Pressing key repeatedly the Sub menu will scroll down in the following order on the display Ell - Extremely Inverse 1(EI1) El2 - Extremely Inverse 2(EI2) Ltl - Long Time Inverse (LTI) dtl - Definite Time Lag (DTL) By pressing or key choose the desired characteristic and press key. Now the Submenu LED goes OFF and the Main menu appears on the LED display Time Setting If characteristic is selected as Definite Time Lag, the Time setting range is, 0.0 Sec to Sec in steps of 0.1Sec. If characteristic is selected as Inverse curve, the Time Multiplier setting range is to in steps of ELEMENT 1 a) For Inverse Characteristics Pressing key repeatedly and get ti I.000 Main menu(represents time multiplier for Element 1 has been set to 1.000), press key (Submenu LED On) to get the Sub menu. Pressing the or key, changes the time setting by increment or decrement. Upon selecting the desired setting, once again press the key (Sub menu LED goes OFF) to return to the main menu. b) For Definite Time Lag Pressing key repeatedly and get ti 3.0 Main menu (represents time setting for Element 1 has been set to 3.0sec), press key (Submenu LED On) to get the Sub menu. Pressing the or key, changes the time setting by 0.1sec increment or decrement. Upon selecting the desired setting, once again press the key (Sub menu LED goes OFF) to return to the main menu ELEMENT 2 a) Inverse Characteristics Pressing key repeatedly and get t2 I.000 Main menu(represents time multiplier for Element 2 has been set to 1.000), press key (Submenu LED On) to get the Sub menu. Pressing the or key, changes the time setting by increment or decrement. Upon selecting the desired setting, once again press the key (Sub menu LED goes OFF) to return to the main menu. 13

15 b) Definite Time Lag Pressing key repeatedly and get t2 3.0 Main menu(represents time setting for Element 2 has been set to 3.0sec), press key (Submenu LED On) to get the Sub menu. Pressing the or key, changes the time setting by 0.1sec increment or decrement. Upon selecting the desired setting, once again press the key (Sub menu LED goes OFF) to return to the main menu Time selection for TIMER (Circuit Breaker close prevention for capacitor) Setting range: 0 to 600 Secs in steps of 1Sec or OFF Pressing key repeatedly and get td I0 Main menu(represents time delay for TIMER has been chosen to 10Sec), press key (Submenu LED On) to get the Sub menu. Pressing the or key, changes the Timer setting in 1Sec increment or decrement. Upon selecting the desired setting, once again press the key (Sub menu LED goes OFF) to return to the main menu Trip circuit Supervision Pressing key repeatedly and get tc off Main menu ( represents Trip Circuit Supervision function is OFF), press key (Submenu LED On) to get the Sub menu. Press key on - Represents trip circuit supervision is ON select either Trip circuit is ON or OFF, once again press the key (Sub menu LED goes OFF) to return to the main menu Acceptance of Settings (ENTER) For the relay to accept the above setting changes press X key once, now the display goes off and the settings are updated. By pressing any key again nnut I8 Indication will appear Ensure all the chosen settings. In case of any changes required use Sub menu key and then do the changes and finally press enter X key once. 7. TO CHECK THE RELAY VERSION Press X key four times, example of relay version display is as follows : I8I. 001 Represent M V T 181 relay version 1 To get back the main menu, press or key. ENSURE TO PRESS X TO ACCEPT THE CHANGES 8. TO CANCEL SETTING WHILE CHANGING (CANCEL) While the particular setting is being changed (using or key) with Submenu LED ON, pressing X key, the original setting is restored 14

16 9. TRIP INDICATION AND RESETTING OF TRIP INDICATION (RESET) When the relay operates, "TRIP" LED indicates tripping. To find which element operated press or key. There is possibility for the following display after the trip, EI utrp E2 utrp EI otrp E2 otrp Indicates Element 1 is operated due to under voltage Indicates Element 2 is operated due to under voltage Indicates Element 1 is operated due to over voltage Indicates Element 2 is operated due to over voltage Suppose Element 1 has started but not initiated trip, but Element 2 is tripped then pressing any arrow key EI.o.5tr (Indicates Element 1 is started due to Over voltage) E2.o.trp (Indicates Element 2 is tripped due to Over voltage) will appear alternatively for each pressing of the key. Once the fault is cleared, press X key twice to reset the trip indication. The trip indication will be retained in Non - volatile memory during auxiliary DC power supply failure. 10. TRIP CIRCUIT SUPERVISION INDICATION When the Status inputs are used for Trip Circuit Supervision and when the Trip Circuit Supervision function is made to "ON", upon failure of Trip Circuit, the "T.C.FAIL" LED will appear. On restoration of the Trip Circuit back to healthy condition, this LED will disappear automatically. 11. TIMER INDICATION The TIMER function is dependent on the Status input, if time delay is selected in the TIMER function and after completion of time delay "TIMER" LED will appear in the relay. This is self-reset in nature and goes off if the Status input is off. 12. SPECIAL INSTRUCTION In case of accidental setting of under voltage without giving AC input voltage (terminal 11 &12) and X key is pressed, the relay will trip an account of no voltage present. The display EI utrp (for Element 1) or E2utrp (for Element 2) will appear and "STARTER", "TRIP" LED's will glow. To restore back under this condition follow the special resetting procedures mentioned below, Press arrow key for about 30 to 50 seconds continuously. nnut I8 Display will appear. 15

17 Press key you will see the following settings EI off - Element 1 is OFF E2 off - Element 2 is OFF td off - Timer setting is OFF tc off - Trip circuit supervision is OFF Press the X key once, "STARTER" LED will disappear Now use the normal technique of going to Submenu and changing the required setting. Ensure you correctly set the relay Press X key once and put off the auxiliary voltage supply to the relay Apply A.C input voltage to terminal 11 & 12 if required (if you have selected under voltage) then on the auxiliary voltage supply, now "TRIP" LED will disappear. In case of accidental setting of over voltage less than or equal to under voltage setting also special resetting technique of the above to be used. 16

18 COMMISSIONING 1. REQUIRED TEST EQUIPMENTS 500V insulation test sets. Variable secondary injection voltage source rated 230V a.c. or greater. Time interval meter Primary injection equipment A DC supply with a nominal voltage within the working range of the relays DC auxiliary supply ratings 2. INSPECTION Ensure that all connections are tight and in accordance with the relay wiring diagram and the scheme diagram. Check if the relay is correctly programmed and the relay is fully inserted into the case. 3. APPLYING SETTINGS The relay settings for the particular application should be applied before any secondary testing is started. 4. PRECAUTIONS Before testing commences, the equipment should be isolated from the voltage transformers. The tripping and alarm circuits should also be isolated, where practical. Also, ensure that trip links are removed. Ensure that correct DC auxiliary voltage and polarity is applied. See the relevant scheme diagrams for the relay connections. 5. TESTS 5.1. Insulation Connect together all relay PT terminals and measure the insulation resistance between these terminals and all the other relay terminals connected together to earth. Connect together the terminals of the DC auxiliary supply (only +ve and -ve) and measure the insulation resistance between these terminals and all other terminals connected together to earth. Connect together all the output relay terminals and measure the insulation resistance between these terminals and all other terminals connected together to earth. A minimum value of 2. 5 to 3 meg ohms can be considered as satisfactory value Secondary Injection Select the relay configuration and settings for the application. 17

19 PICK UP AND RESET a) Over Voltage Characteristic The test checks accuracy of the voltage settings for the relay over voltage and under voltage characteristics. Apply single-phase voltage into the voltage inputs. Slowly increase the voltage until the starter LED (yellow) operates and record the pick up voltage in Table 2. Reduce the voltage until the LED goes off and record this as the reset level. Check that the pick up voltage level are measured within 104% + 3% (except EI 2 characteristic) of the applied setting. Check that the reset levels are > 94% of the setting. CHARAC- TERISTIC PICK-UP SETTING MEASURED PICK-UP PICK-UP ERROR MEASURED RESET RESET ERROR Over voltage TABLE 2 b) Under Voltage Characteristic Apply single phase voltage, higher than the setting level into the voltage inputs. Slowly reduce the voltage until the starter LED ( yellow) operates and record the pick up voltage in Table 3. Increase the voltage until the LED goes off and record this as the reset level. Check the pick up voltage level are measured with in 96% ± 3% of applied voltage setting and check the reset level 106% of voltage setting. CHARAC- TERISTIC PICK-UP SETTING MEASURED PICK-UP PICK-UP ERROR MEASURED RESET RESET ERROR under voltage TABLE DTL/IDMTL CHARACTERISTICS This test checks the accuracy of the main time delay characteristics ( DTL/IDMTL ). Select the relay voltage setting characteristics and time multiplier settings as required and then inject a level of voltage which is a multiple of the relay setting. A time interval meter should be connected to the correct output contact terminals. The timer should be started by the source "ON" switch for O/V and OFF switch for U/V and stopped by the relay trip contacts. A secondary injection timing test circuit is illustrated in Fig. 1. The secondary injection test equipment should be made 'OFF', once the relay contact is closed Table 4 & 6 shows theoretical value of each characteristic with time multiplier set to Record the actual results in Table 5 & 7 for both over voltage and under voltage characteristic and check that the measured times are within + 5% or + 35 m. sec of theoretical value. 18

20 a) Over voltage CURVE 1.2 xvs 1.7 xvs 2.2 xvs DTL * * * LTI EI EI TABLE 4 * USER SETTING Characteristic Curve 1.2 x Vs 1.7 x Vs 2.2 x Vs Over voltage DTL,LTI,EI 1 & EI 2 Delay Error (±5%) Delay Error (±5%) Delay Error (±5%) TABLE 5 b) Under voltage CURVE 0.05 xvs 0.5 xvs 0.95 xvs DTL * * * EI TABLE 6 * USER SETTING Characteristic Curve Under voltage DTL & EI xVs 0.5xVs 0.95xVs Delay Error (±5%) Delay Error (±5%) Delay Error (±5%) TABLE 7 19

21 TIMER FOR CLOSE PREVENTION When enabled test the timer as shown in Fig TRIP CIRCUIT FAIL When enabled test the trip circuit fail both in breaker ON & OFF condition by Removing the trip circuit wiring OUTPUT CONTACTS COMBINATION a) Starter 1 N/O This contact to be used while testing the pick up and reset value of the relay. b) Common trip & alarm for U/V AND O/V 2 N/O contacts These contacts to be used while testing the under voltage and over voltage characteristics. c) U/V or O/V Element 1 operated 1 N/O contact This contact to be used while testing the U/V or O/V characteristic of element 1. d) U/V or O/V Element 2 operated 1 N/O contact This contact to be used while testing the U/V or O/V characteristic of element 2. e) Protection Healthy - 1 N/C contact This contact indicates the relay healthiness. f) Trip circuit fail 1 N/O contact. This contact will indicate the trip circuit failure condition. g) Timer output - 1 N/O contact. This contact to be used for time delay functions Primary Injection Primary injection tests are essential to check the ratio and polarity of the transformers as well as the secondary wiring. Ensure the instrument transformer is potential free and isolated from the primary system. Using the circuit shown in Fig.2, check the voltage transformer ratio and VT phase to earth connection. Inject a voltage of sufficient magnitude.the secondary voltage is 20

22 Vs = Primary voltage / VT ratio 5.4. Putting Into Service After completing all tests satisfactorily, the relay should be put into service as follows: 1. Make a final check of the secondary wiring and tightness of all terminal connections. 2. Insert the DC supply fuse. 3. Check the relay healthy indication/display. 4. Replace the relay cover. 5. Insert the trip links. 6. Perform trip test by secondary injection. 7. Remove all test connections Variable single Phase AC supply Double Pole Switch* V O/V START TIME INTERVAL METER 23 + ve D.C SUPPLY - ve STOP 3 4 * Use Good Quality Switch Fig.1 Secondary Injection Timing Test 21

23 MVT 181 U/V or O/V V D.C SUPPLY + ve - ve PRIMARY INJECTION TEST SOURCE Fig.2 Primary Injection Test Circuit Double Pole Switch* DC POWER SUPPLY SOURCE +ve -ve STATUS ** INPUT START TIME INTERVAL METER 23 D.C SUPPLY STOP 3 4 * Use Good Quality Switch ** Nominal Voltage for Status Input is 24/30V DC. For higher voltage use external dropper resister as detailed in the MVT181-Wiring Diagram. TIMER OUTPUT Fig.3 Close prevention Timing Test 22

24 T R I P S U P P L Y + VE TRIP CO NTACT 52 a TRIP COIL - VE 52 b VOLTAG E INPUT R1 STATUS R2 INPUT 1 R3 STATUS R4 INPUT 2 See Note 1 AUXILIARY + VE SUPPLY - VE EARTH MVT ALARM 2 3 TRIP 4 13 CO MMON 14 ELEMENT 1 O PERATED 15 ELEMENT 2 OPERATED 18 PROTECTION UNHEALTHY 21 TRIP CIRCUIT FAIL 16 TIMER 17 O UTPUT 19 STARTER 20 Fig.4 MVT WIRING DIAGRAM (-)Ve (+) Ve Earth CASE TERMINALS VIEWED FROM REAR Note : 1. Status input is rated for 24 / 30 V DC nominal voltage input (18 to 36V operating range) without any external resistors. For higher DC nominal voltage input, use external dropper resistors (R1, R2, R3 & R4) as follows. Nominal Voltage 48V DC 110V DC 220V DC Status Input External Resistances R1, R2, R3 & R4 Operating range 36 to 60V 88 to 135 V 176 to 280 V 1.0 kw ± 5% ; 9 W 3.9 kw ± 5% ; 9 W 8.2 kw ± 5% ; 9 W 2. Terminal No.23 (Earth) is to be connected directly to Earth bar. 23

25 NOTES 24

26

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11

Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11 Application and Commissioning Manual for Numerical Over Current Protection Relays Type MIT 121/131 CONTENTS PAGE APPLICATION 2-4 INSTALLATION 5-11 COMMISSIONING 12-16 DRAWINGS 17-18 1 1. INTRODUCTION APPLICATION

More information

EASUN REYROLLE LIMITED

EASUN REYROLLE LIMITED OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT

More information

ASHIDA Numerical OC/EF Protection Relay

ASHIDA Numerical OC/EF Protection Relay ASHIDA Numerical OC/EF Protection Relay Features: 4 Element (3 Phase + EF) over current IDMT with instant trip. Back - lit LCD display for settings. Display of fault current. / Load current. Selection

More information

ASHIDA Numerical 3OC + 1EF Protection Relay

ASHIDA Numerical 3OC + 1EF Protection Relay PROTH. ERR L5 PKP FAULT DT REC LOCK BF L6 L7 CLOSE TRIP ADR 241B Protection Features : 4 Element (3 Phase + EF + Sensitive EF) Over current IDMT/DMT with instant trip. Programmable (Non- Volatile) Setting

More information

PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY

PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY Sheet 1 of 15 TEST DATE: CUSTOMER: SERIAL NO: OLTC ACKNOWLEDGE SETUP AUTOMATIC or FEEDBACK CONTROL PRODUCT/TEST MANUAL 2V162K12 VOLTAGE REGULATOR RELAY Issue Date Level A 06/01/1997 Initial issue. Summary

More information

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide Relion 605 series Relion 605 series Self-Powered Feeder Protection Product Guide Contents 1 Description...3 2 Protection functions...3 3 Application...4 4 Self-supervision...4 5 Inputs and outputs...4

More information

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay

7SR21 Non-Directional 7SR22 Directional Overcurrent Relay 7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Function diagrams amended,

More information

Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay

Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay Technical Datasheet RELAY-1 RELAY-2 k V Hz RESET ABH TEST True RMS Measurement True RMS Digital Protection V/Hz is used to protect against Over Voltage, Under Voltage, Phase Unbalance, Phase Sequence detection,

More information

Relay. Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay

Relay. Technical Datasheet. True RMS Digital Protection Relay. Line Monitoring Relay Line Monitoring Technical Datasheet RISH RELAY-1 RELAY-2 RISHABH k V Hz True RMS Digital Protection RISH V/Hz is used to protect against Over Voltage, Under Voltage, Phase Unbalance, Phase Sequence detection,

More information

Technical Datasheet. True RMS Digital Protection Relay. Voltage Protection Relay

Technical Datasheet. True RMS Digital Protection Relay. Voltage Protection Relay Technical Datasheet RELAY-1 RISHABH k V RESET True RMS Digital Protection Relay RELAY-2 TEST True RMS Measurement RISH Relay V is used to protect against Over Voltage, Under Voltage, Phase Sequence detection,

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

GE Power Management. Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C

GE Power Management. Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C GE Power Management Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C 7$%/(2)&217(176 1. DESCRIPTION...2 2. APPLICATION...6 3. CHARACTERISTICS...7

More information

PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY

PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY Sheet 1 of 12 TEST DATE CUSTOMER SERIAL No OLTC ACKNOWLEDGE SETUP AUTOMATIC or FEEDBACK CONTROL PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY Issue Date Level I 21/05/1998 Initial issue. Summary

More information

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Additional Options 15kV Isolation

More information

3 Pole high impedance differential relay 7VH83

3 Pole high impedance differential relay 7VH83 Fig 1. High impedance differential protection relay 7VH83 Features l Integral CT shorting relay. l Robust solid state design. l Inrush stabilisation through filtering. l Fast operating time. l LED indicator.

More information

6RZ. > <8ms and <30ms performance versions > Single and dual element versions > Draw out case > Flush panel or rack mount > Made in Australia

6RZ. > <8ms and <30ms performance versions > Single and dual element versions > Draw out case > Flush panel or rack mount > Made in Australia High Speed Interposing Relay The Series comprises a range of compact low burden interposing relays for power utility protection and control applications. >

More information

1 INTRODUCTION ORDER CODE / INFORMATION

1 INTRODUCTION ORDER CODE / INFORMATION INTRODUCTION ORDER CODE / INFORMATION 269/269Plus * * * * * * 269/269Plus SV D/O.4 ORDER CODE / INFORMATION Motor management relay Standard version Drawout version Phase CT Ground CT (required for D/O

More information

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Additional Options Solkor

More information

ASHIDA Numerical Directional 3OC + 1EF Protection Relay

ASHIDA Numerical Directional 3OC + 1EF Protection Relay Ashida Numerical Directional 3O/C + 1E/F PROTH. PROTH. ERR L5 FAULT PKP PKP FAULT L6 PT DT REC LOCK BF L7 CLOSE TRIP TRIP CLOSE ADR 145B 245B Protection Features: 4 Element (3 Phase + EF +sensitive EF)

More information

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters Technical Data Sheet Alpha 20 Alpha 20 is a compact multifunction instrument which Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel

More information

Instantaneous Overcurrent Relay

Instantaneous Overcurrent Relay Midos Type MCRI Instantaneous Overcurrent Relay Features High speed operation Not slowed by dc transients Settings readily adjustable on relay front plate Two phase and earth fault relay Figure 1: Type

More information

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays

Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General

More information

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES)

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES) Alpha Series www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters Shunts ALPHA

More information

Type: ADR233A (ADITYA V2 Series) (Preliminary) ASHIDA Numerical 3 Phase Tx. Differential Protection Relay

Type: ADR233A (ADITYA V2 Series) (Preliminary) ASHIDA Numerical 3 Phase Tx. Differential Protection Relay Ashida Numerical 3 Directional Phase Tx. 3O/C Differential + 1E/F Protection PROTH. ERR FAULT 87 L5 L6 REF L7 BF TRIP ADR 233B_V2 233A_V2 Protection Features: 3Phase Tx. Differential Protection + REF Programmable

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

Overcurrent Protection / 7SJ45

Overcurrent Protection / 7SJ45 Overcurrent Protection / SJ SIPROTEC easy SJ numerical overcurrent protection relay powered by CTs Fig. / Description SIPROTEC easy SJ numerical overcurrent protection relay powered by current transformers

More information

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION GEK-00682D INTRODUCTION INTRODUCTION. PRODUCT DESCRIPTION The MDP Digital Time Overcurrent Relay is a digital, microprocessor based, nondirectional overcurrent relay that protects against phase-to-phase

More information

Protection and control VIP300. Technical manual

Protection and control VIP300. Technical manual Protection and control VIP300 Technical manual contents 1. presentation of the VIP300...3 2. use and settings...4 3. choice of sensors and operating ranges...9 4. connection scheme...10 5. assembly...11

More information

Technical Data Sheet. x1000. kwh R Y B

Technical Data Sheet. x1000. kwh R Y B Technical Data Sheet x1000 Von kwh IRev 3600 imp /kwh R Y B is a compact multifunction instrument which is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy

More information

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay Relay withdrawn from case Application The type CDG 11 relay

More information

AMIK 200 / 201 Technical Data Sheet

AMIK 200 / 201 Technical Data Sheet AMIK 200 / 201 Technical Data Sheet AMIK Special Features MODBUS (RS-485) Communication available only on Amik 201 On site Programmable CT/PT Ratios User selectable CT Secondary 1A/5A User selectable PT

More information

Testing Potential Transformers

Testing Potential Transformers Testing Potential Transformers By Les Warner (PCA Valence) and Chris Werstiuk ( LLC) Potential transformers (PTs) are necessary to a power system for metering and protective relaying to convert higher

More information

Protection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique

Protection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique Protection and control Sepam range Sepam 0 LA Self-powering protection Merlin Gerin Square D Telemecanique presentation contents page presentation protection functional and connection schemes other connection

More information

DIAC Type 66K. DIGITAL OVERCURRENT RELAY Instruction Manual. GE Power Management

DIAC Type 66K. DIGITAL OVERCURRENT RELAY Instruction Manual. GE Power Management g GE Power Management DIAC Type K DIGITAL OVERCURRENT RELAY Instruction Manual DIAC K Revision: SPDV0.A0 Manual P/N: GEK-0C Copyright 000 GE Power Management GE Power Management Anderson Avenue, Markham,

More information

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication: Application : RISH Master 3490 SS is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy having auto-resetting 8 digit seven segment LED counter. The unit

More information

XI1-I Time overcurrent relay. (Januar 2007) Manual XI1-I (Revision New)

XI1-I Time overcurrent relay. (Januar 2007) Manual XI1-I (Revision New) XI1-I Time overcurrent relay (Januar 2007) Manual XI1-I (Revision New) Woodward Manual XI1-I GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009

Catalog 200 Contactors up to 115 A Motor Starters up to 55 kw 03/2009 Catalog 00 Contactors up to 5 A Motor Starters up to 55 kw 03/009 Kraus & Naimer The development of the Blue Line rotary switch, contactor and motor starter product ranges is based on more than hundred

More information

XF2 Frequency Relay. Manual XF2 (Revision A)

XF2 Frequency Relay. Manual XF2 (Revision A) XF2 Frequency Relay Manual XF2 (Revision A) Woodward Manual XF2 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by Woodward Governor

More information

Back to the Basics Current Transformer (CT) Testing

Back to the Basics Current Transformer (CT) Testing Back to the Basics Current Transformer (CT) Testing As test equipment becomes more sophisticated with better features and accuracy, we risk turning our field personnel into test set operators instead of

More information

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New) XUA1 AC Voltage and phase balance relay (August 1996) Manual XUA1 (Revision New) Woodward Manual XUA1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

RS Pro ENGLISH. Datasheet

RS Pro ENGLISH. Datasheet Datasheet Article No: 136-5385 Digital AC Ammeter, 48x96, 1Phase, 1 or 5 Amps AC, Supply 40-300V ac/dc 136-5387 Digital AC Ammeter, 96x96, 1Phase, 1 or 5 Amps AC, Supply 40-300V ac/dc 136-5388 Digital

More information

XP2-R Power and Reverse Power Relay

XP2-R Power and Reverse Power Relay XP2-R Power and Reverse Power Relay Manual XP2-R (Revision C) Woodward Manual XP2-RE Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward

More information

RS Pro ENGLISH. Datasheet

RS Pro ENGLISH. Datasheet Datasheet ENGLISH Article No: 136-5390 Digital AC Ammeter, 48x96, 3Phase, 1 or 5 Amps AC, Supply 40-300V ac/dc 136-5391 Digital AC Ammeter, 96x96, 3Phase, 1 or 5 Amps AC, Supply 40-300V ac/dc 136-5393

More information

MBCI (Translay S) Technical Manual. Differential Feeder and Transformer Feeder Protection. Publication Reference: GRID

MBCI (Translay S) Technical Manual. Differential Feeder and Transformer Feeder Protection. Publication Reference: GRID MBCI (Translay S) Technical Manual Differential Feeder and Transformer Feeder Protection Publication Reference: R8011G R8011G 2011. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks

More information

DEIF A/S. Insulation monitor. Type SIM-Q

DEIF A/S. Insulation monitor. Type SIM-Q Insulation monitor 4921232C Monitoring of insulation resistance on ungrounded AC networks (IT network) Working voltage up to 69V AC, withstands up to V DC Measuring range 1...Mohm or 1...Mohm Alarm on

More information

Reyrolle Protection Devices. 7SG14 Duobias M Transformer Protection. Answers for energy

Reyrolle Protection Devices. 7SG14 Duobias M Transformer Protection. Answers for energy Reyrolle Protection Devices 7SG4 Duobias M Transformer Protection Answers for energy 7SG4 Duobias M Transformer Protection Description Optional Functionality High Impedance Restricted Earth Fault per winding

More information

presentation contents application advantages

presentation contents application advantages presentation contents page presentation protection functional and connection schemes other connection schemes connection characteristics 9 installation 0 commissioning ordering information Sepam 00 is

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Solkor R & Solkor Rf

More information

Relion 605 series. Self-Powered Feeder Protection REJ603 Application manual

Relion 605 series. Self-Powered Feeder Protection REJ603 Application manual Relion 605 series Relion 605 series Relion 605 series Self-Powered Feeder Protection REJ603 Application manual Document ID: 1MDU07206-YN 6 2 4 This document and parts thereof must not be reproduced or

More information

XU2-AC AC voltage relay. (Februar 1997) Manual XU2-AC (Revision New)

XU2-AC AC voltage relay. (Februar 1997) Manual XU2-AC (Revision New) XU2-AC AC voltage relay (Februar 1997) Manual XU2-AC (Revision New) Woodward Manual XU2-AC GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information

More information

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER

AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER AC/DC Current Probe GCP-100 QUICK START GUIDE ISO-9001 CERTIFIED MANUFACTURER This manual contains proprietary information, which is protected by copyright. All rights are reserved. No part of this manual

More information

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual

REK 510 Current injection device for earth-fault protection of a synchronous machine rotor. User s Manual REK 50 protection of a synchronous machine User s Manual REK 50 X 0 9 8 7 6 5 4 0 V 00 V 0 V 5 6 7 Ordering No: REK 50-AA Uau = 00/0 Vac Un = 48 V Serial No: fn = 50/60 Hz Uec = ma 600 Vdc MRS 75587-MUM

More information

DEIF A/S. Insulation monitor. Type SIM-Q/SIM-Q LF

DEIF A/S. Insulation monitor. Type SIM-Q/SIM-Q LF / LF Insulation monitor Monitoring of insulation resistance on ungrounded AC networks (IT network) Working voltage up to 69V AC, withstands up to V DC Measuring range...kω or 1...MΩ Working frequency down

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

Type VAEM 22 Negative Potential Biasing Relay

Type VAEM 22 Negative Potential Biasing Relay Type VAEM 22 Negative Potential Biasing Relay Type VAEM 22 Negative Potential Biasing Relay VAEM 22 Relay withdrawn from case Features l Simple and robust construction l High sensitivity Application The

More information

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New)

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New) XP2-R Power and reverse power relay (January 2006) Manual XP2-R (Revision New) Woodward Manual XP2-R GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

Computer-14d - xx - 144a

Computer-14d - xx - 144a POWER FACTOR REGULATOR Computer-14d - xx - 144a INSTRUCTION MANUAL ( M 981 602 / 98B ) (c) CIRCUTOR S.A. -------- POWER FACTOR REGULATOR COMPUTER- 14d --------- Page 2 1.- POWER FACTOR REGULATORS COMPUTER-14d-144a

More information

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300 Monitoring Technique VARIMETER IMD Insulation monitor RN 5897/300 0274214 Your Advantages For mobile generator sets according to DIN VDE 0100-551 Preventive fire and system protection Detection of symmetric

More information

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49 TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument True RMS measurement User-friendly programing Four different types for optimal specification RS485 interface For 3- or 4-wire connection Compact

More information

Phase and neutral overcurrent protection

Phase and neutral overcurrent protection Phase and neutral overcurrent protection Page 1 ssued June 1999 Changed since July 1998 Data subject to change without notice (SE970165) Features Two-phase or three-phase time-overcurrent and earth fault

More information

Instructions for D64RPB30 Series C1 Ground Fault Relay

Instructions for D64RPB30 Series C1 Ground Fault Relay Instructions for D64RPB30 Series C1 Ground Fault Relay Cat. No. D64RPB30 CT 24-240V AC / DC N.C. N.O. 1 2 3 4 5 6 7 8 ON F2024-01-01 FLASHES: 1 = E/F 2 = S/C 3 = BACKUP 4 = CT 5 = F/S CV LOSS CONT = TRIP

More information

User s manual and Technical description. Self-Powered Feeder Protection REJ603

User s manual and Technical description. Self-Powered Feeder Protection REJ603 and Technical description Self-Powered Feeder Protection 2 Document ID: Issued: 18.02.2008 Revision: A Product version:1.0 Copyright 2008 ABB. All rights reserved 3 Copyright This document and parts thereof

More information

www. ElectricalPartManuals. com Basler Electric P. 0. BOX 269 HIGHLAND, ILLINOIS 62249, U.S.A. PHONE FAX

www. ElectricalPartManuals. com Basler Electric P. 0. BOX 269 HIGHLAND, ILLINOIS 62249, U.S.A. PHONE FAX The BE1-47N Voltage Phase Sequence Relay provides protection for rotating equipment from the damaging effects of excessive negative sequence voltage resulting from phase failure, phase unbalance and reversed

More information

VOLTAGE REGULATOR R 449. Installation and maintenance. This manual must be sent to the end user R 449 X2 Z1 X1 Z2 E+ E- (12V - 10A)

VOLTAGE REGULATOR R 449. Installation and maintenance. This manual must be sent to the end user R 449 X2 Z1 X1 Z2 E+ E- (12V - 10A) This manual must be sent to the end user X2 Z1 X1 Z2 E+ E- J1 t (12V - 10A) ~ 10 ohms Exciter field + - Isolated DC power supply Installation and maintenance WARNING TO AVOID HARM EITHER TO PEOPLE OR TO

More information

IRI1-ER - Stabilized Earth Fault Current Relay. Manual IRI1-ER (Revision A)

IRI1-ER - Stabilized Earth Fault Current Relay. Manual IRI1-ER (Revision A) IRI1-ER - Stabilized Earth Fault Current Relay Manual IRI1-ER (Revision A) Woodward Manual IRI-ER GB Woodward Governor Company reserves the right to update any portion of this publication at any time.

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

GPM. Field and Stator Ground Fault Protection Modules. Instruction Manual AF1. GE Grid Solutions

GPM. Field and Stator Ground Fault Protection Modules. Instruction Manual AF1. GE Grid Solutions GE Grid Solutions GPM Field and Stator Ground Fault Protection Modules Instruction Manual Product version: 2.0x GE publication code: 1601-0256-AF1 (GEK-113231D) 1601-0256-AF1 Copyright 2017 GE Multilin

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Numerical Multi-Function Motor Protection Relay RHO 3. Operation & Maintenance Instruction Manual

Numerical Multi-Function Motor Protection Relay RHO 3. Operation & Maintenance Instruction Manual Numerical Multi-Function Motor Protection Relay RHO 3 Operation & Maintenance Instruction Manual RHO MANUAL Contents Section Page Description of operation 4 2 Performance specification 20 3 Relay settings

More information

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C) XR1 Rotor Earth Fault Relay Manual XR1 (Revision C) Woodward Manual XR1 (EN) Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided by

More information

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Overcurrent Protection / 7SJ46 SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Function overview Fig. /11 Description The SIPROTEC easy 7SJ46 is a numerical overcurrent protection relay which

More information

Earth Fault Relay EFSPL-1A/5A

Earth Fault Relay EFSPL-1A/5A Earth Fault Relay EFSPL-1A/5A IEEE DEVICES CODE-50N Features Static Device Compact, Reliable with Aesthetic Value Rugged, Robust and Tropicalised design Consistent repeat accuracy Wide Current Operating

More information

ZHUHAI PILOT TECHNOLOGY CO., LTD.

ZHUHAI PILOT TECHNOLOGY CO., LTD. SPM32 Multifunctional Power Meter SPM32 Multifunction Power Meter Installation & Operation Manual V1.0 ZHUHAI PILOT TECHNOLOGY CO., LTD. Danger and warning! This device can be installed only by professionals.

More information

7PG23 5B3 Restricted Earth Fault Answers for energy

7PG23 5B3 Restricted Earth Fault Answers for energy Reyrolle Protection Devices 7PG23 5B3 Restricted Earth Fault Answers for energy 7PG23 5B3 Contents Contents Technical Manual Chapters 1. Description of Operation 2. Performance Specification 3. Applications

More information

SPECIFICATION FOR OVERCURRENT RELAYS

SPECIFICATION FOR OVERCURRENT RELAYS SPECIFICATION FOR OVERCURRENT RELAYS 1/9 1. Procedure A manufacturer willing to classify an overcurrent relay according to this specification should provide: A complete file providing a clear, unambiguous

More information

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters RI-F200 Series Single and Three Phase Multifunction Energy Meter DIN 96 panel mounted -/1A or -/5A current transformer input Single phase or three phase network compatible Programmable voltage and current

More information

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features: (With All Display Parameters) Application : RISH EM 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network

More information

Instruction Manual for Digital Grounding Resistance Meter

Instruction Manual for Digital Grounding Resistance Meter Instruction Manual for Digital Grounding Resistance Meter Instruction Manual for Digital Grounding Resistance Meter Table of Contents I. Overview...2 II. Open-case Inspection...3 III. Safety Precautions...4

More information

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2 BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY The BE1-67N Ground Directional Overcurrent Relay provides ground fault protection for transmission and distribution lines by sensing the direction and magnitude

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) The toolbox for substation 3-phase testing Three currents and four voltages Stand-alone functionality Rugged and reliable

More information

XUA1 - AC Voltage and phase balance relay

XUA1 - AC Voltage and phase balance relay XUA1 - AC Voltage and phase balance relay Contents 1. Applications and features 2. Design 3. Function 3.1 Voltage supervision 3.2 Unbalanced voltage supervision 4. Operation and settings 4.1 Setting of

More information

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:

More information

Transformer differential protection

Transformer differential protection Transformer differential protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970883) Features Three phase differential protection with two, three, five or

More information

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual.

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual. Manual Title: 5502E Getting Started Supplement Issue: 3 Part Number: 4155211 Issue Date: 9/18 Print Date: November 2012 Page Count: 12 Revision/Date: This supplement contains information necessary to ensure

More information

Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK

Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK Transformer and generator time-overexcitation relay and protection assemblies RXLK 2H and RALK (RXLK_2H.tif) RALK.psd Features Micro-processor based time-overexcitation relay with continuous settings for

More information

CBCT TM CIRCUIT BREAKER COIL TESTER

CBCT TM CIRCUIT BREAKER COIL TESTER CBCT TM CIRCUIT BREAKER COIL TESTER USER S MANUAL Vanguard Instruments Company, Inc. 1520 S. Hellman Ave. Ontario, California 91761, USA TEL: (909) 923-9390 FAX: (909) 923-9391 August 2010 Revision 1 SAFETY

More information

IRI1-ER - Stabilized Earth Fault Current Relay

IRI1-ER - Stabilized Earth Fault Current Relay IRI1-ER - Stabilized Earth Fault Current Relay TB IRI1-ER 02.97 E 1 Contents 1. Summary 2. Applications 3. Characteristics and features 4. Design 4.1 Connections 4.1.1 Analog inputs 4.1.2 Output relays

More information

RISH Delta Energy / Demand (Multifunction instrument) Data Sheet

RISH Delta Energy / Demand (Multifunction instrument) Data Sheet ISH Delta Energy / Demand (Multifunction instrument) Data Sheet www.rishabh.co.in Page 1 of 6 Version: D 14 / 03 / 2012 Application: ISH Delta Energy measures important electrical parameters in 3 phase

More information

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000

More information

Data Sheet. RISH Master Record %THD

Data Sheet. RISH Master Record %THD Data Sheet %THD Application : measures important electrical parameters & replaces the multiple analog panel meters. It measures electrical parameters like AC current, Voltage, frequency, active energy

More information

Type CVX and CVX-1 Synchro-Verifier Relays

Type CVX and CVX-1 Synchro-Verifier Relays I.L. 41-682.11 Type CVX and CVX-1 Synchro-Verifier Relays TIME DIAL POTENTIOMETER (R3) CIRCLE ADJUST RESTRAINT ELECTROMAGNET Figure 1. CVX-1 Relay Front View, Out of Case OPERATING ELECTROMAGNET TELEPHONE

More information

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New) XR1 Rotor Earth Fault Relay (May 2007) Manual XR1 (Revision New) Woodward Manual XR1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information provided

More information

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER OPERATOR S MANUAL DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER Masibus Automation & Instrumentation Pvt. Ltd. B/30, GIDC Electronics Estate, Sector-25, Gandhinagar-382044, Gujarat, India Web Site: www..com

More information

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID RI-D140 Three Phase Multifunction DIN Rail Energy Meter (MID Certified) Four module DIN rail mounted Energy pulse LED True RMS measurement Cost effective and accurate Modbus communication -/1A or -/5A

More information

Generator Protection M 3420

Generator Protection M 3420 PROTECTION Generator Protection M 3420 Integrated Protection System for Generators of All Sizes Unit shown with optional M 3920 Target Module and M 3931 HMI (Human-Machine Interface) Module Microprocessor-based

More information

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection DATASHEET - ETR4-70-A Delivery program Timing relay, 2W, 0.05s-100h, multi-function, 24-240VAC/DC, potentiometer connection Part no. ETR4-70-A Catalog No. 031888 Eaton Catalog No. XTTR6A100H70B EL-Nummer

More information

Digital Motor Bus Transfer System M 4272

Digital Motor Bus Transfer System M 4272 SYNCHRONIZING Digital Motor Bus Transfer System M 4272 Integrated Synchronizing System Provides Automatic and Manual transfers of motor bus systems in power plants and industrial processing plants to ensure

More information