Generator Protection M 3420
|
|
- Jack Morris
- 5 years ago
- Views:
Transcription
1 PROTECTION Generator Protection M 3420 Integrated Protection System for Generators of All Sizes Unit shown with optional M 3920 Target Module and M 3931 HMI (Human-Machine Interface) Module Microprocessor-based Generator Protection system provides 17 protective relay functions Individually programmable input contacts can be programmed to activate any one of eight output contacts Local and remote communications capability for both monitoring and control functions Industry Leader Since 1969 Made in the USA
2 Protective Functions Overexcitation (V/Hz) protection (24) Phase Undervoltage protection (27) Sensitive dual-setpoint, reverse power detection suitable for sequential tripping (32) Dual-zone, offset-mho loss-of-field protection (40) Sensitive negative-sequence overcurrent protection and alarming (46) Instantaneous overcurrent () protection Inadvertent generator energizing protection (/27) Generator breaker failure protection (BF) Neutral inverse time overcurrent (51N) Instantaneous overcurrent (N) protection Three-phase inverse time overcurrent (51V) Phase overvoltage (59) Generator ground fault protection (59N) VT fuse-loss detection and blocking (60FL) Four-step over/underfrequency protection (81) Generator phase differential (87) Ground differential (87GD) protection Standard Features Eight programmable outputs and six programmable inputs Oscillography recording 32-target storage Metering of all measured parameters Two RS-232 and one RS-485 communications ports Standard 19" rack-mount design Removable printed circuit board and power supply Both and 60 Hz models available Both 1 and 5 A rated CT inputs available Additional trip inputs for externally connected devices M 3800A IPScom Communications Software S-3400 IPScom Communications Software for Windows 7 or later IRIG-B time synchronization Includes Modbus and BECO 2200 protocols Optional Features Redundant power supply M 3920 Target Module M 3931 HMI Module M 3801A IPSplot Oscillograph Analysis Software 4-Wire RS-485 Connection 2
3 PROTECTIVE FUNCTIONS M 3420 Generator Protection Relay Device Setpoint Number Function Ranges Increment Accuracy 24 Volts/Hz Definite Time Pickup #1, #2 100 to 200% 1% 1% Time Delay #1, #2 30 to 8160 Cycles 1 Cycle +25 Cycles Inverse Time Characteristic Curves Inverse Time #1 #4 Pickup 100 to 200% 1% 1% Time Dial: Curve #1 1 to Time Dial: Curves #2 #4 0 to Reset Rate 1 to 999 Sec. 1 Sec. 3 Cycles or 1% (from threshold of trip) The percent pickup is based on nominal VT secondary voltage and nominal system frequency settings. The pickup accuracy stated is only applicable from 10 to 80 Hz, 0 to 180 V, and 100 to 1% V/Hz. 27 RMS Undervoltage Pickup #1, #2 5 to 200 V 1 V 0.5 V or 0.5% 0.8 V or 0.75%* Time Delay #1, #2 1 to 8160 Cycles 1 Cycle +20 Cycles or 1%** * When both RMS and line ground to line line is selected. **When RMS (total waveform) is selected, timing accuracy is +20 cycles or 1%; when DFT (fundamental RMS) is selected, accuracy is 1 to +3 cycles or 1%. 32 Directional Power Pickup #1, # to PU PU PU or 2% Time Delay #1, #2 1 to 8160 Cycles 1 Cycle +16 Cycles or 1% The per-unit pickup is based on nominal VT secondary voltage and nominal CT secondary current settings. 40 Loss of Field (dual-zone offset-mho characteristic) Circle Diameter #1, #2 0.1 to Ω 0.1 Ω 0.1 Ω or 5% (0.5 to 0.0 Ω) ( 0.5 Ω or 5%) Offset #1, #2.0 to.0 Ω 0.1 Ω 0.1 Ω or 5% ( 2.0 to 2.0 Ω) ( 0.5 Ω or 5%) Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 to +3 Cycles or 1% Voltage Control 5 to 200 V 1 V 0.5 V or 0.5% (positive sequence) Directional Element Fixed at 13 Voltage control for each zone can be individually enabled. Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating. 3
4 PROTECTIVE FUNCTIONS (cont.) Device Setpoint Number Function Ranges Increment Accuracy 46 Negative Sequence Overcurrent Definite Time Pickup 3 to 100% 1% 0.5% at 5 A ( 0.5% at 1 A) Time Delay 1 to 8160 Cycles 1 Cycle 1 to +3 Cycles Inverse Time Pickup 3 to 100% 1% 0.5% at 5 A ( 0.5% at 1 A) Time Dial Setting (K= I 22 t) 1 to % Definite Maximum Time to Trip 600 to 65,0 Cycles 1 Cycle 1 to +3 Cycles or 1% Reset Time (Linear) Pickup is based on the nominal CT secondary current. Instantaneous Overcurrent 4 minutes (from threshold of trip) Pickup 1.0 to A 0.1 A 0.1 A or 3% (0.2 to 48.0 A) ( 0.02 A or 3%) Trip Time Response 2 Cycles 2 Cycles Instantaneous Overcurrent, Neutral N Pickup 1.0 to A 0.1 A ±0.1 A or ±3% (0.2 to 48.0 A) (±0.02 A or ±3%) Trip Time Response 2 Cycles ±2 Cycles Inadvertent Energizing / Overcurrent Pickup 0. to A 0.01 A ±0.1 A or ±2% (0.10 to 3.00 A) (±0.02 A or ±2%) Undervoltage Pickup 40 to 130 V 1 V ±0.5 V Pick-up Time Delay 1 to 8160 Cycles 1 Cycle 1 to +3 Cycles or ±1% Drop-out Time Delay 1 to 8160 Cycles 1 Cycle 1 to +3 Cycles or ±1% BF BF-Ph BF-N Breaker Failure Pickup Phase Current 0.10 to A 0.01 A ±0.1 A or ±2% (0.02 to 2.00 A) (±0.02 A or ±2%) Neutral Current 0.10 to A 0.01 A ±0.1 A or ±2% (0.02 to 2.00 A) (±0.02 A or ±2%) Time Delay 1 to 8160 Cycles 1 Cycle 1 to +3 Cycles or ±1% BF can be initiated from designated output contacts or status inputs. Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating. 4
5 PROTECTIVE FUNCTIONS (cont.) Device Setpoint Number Function Ranges Increment Accuracy Inverse Time Overcurrent, Neutral 51N Characteristic Curve Definite Time/Inverse/Very Inverse/Extremely Inverse Tap Setting 0.5 to A 0.01 A (0.10 to 2.40 A) Time Dial Setting 0.5 to ±3 Cycles or ±3% Inverse Time Overcurrent, with Voltage Control or Voltage Restraint 51V Characteristic Curve Definite Time/Inverse/Very Inverse/Extremely Inverse Tap Setting 0.5 to A 0.01 A (0.10 to 2.40 A) Time Dial Setting 0.5 to ±3 Cycles or ±3% Voltage Control (VC) 5 to 200 V 1 V ±0.5 V or ±0.5% or Voltage Restraint (VR) Linear Restraint 59 RMS Overvoltage Pickup #1, #2 5 to 200 V 1 V 0.5 V or 0.5% 0.8 V or 0.75%* Time Delay #1, #2 1 to 8160 Cycles 1 Cycle +20 Cycles or 1%** Accuracy applies to values below 180 V pickup. * When both RMS and line ground to line line is selected. **When RMS (total waveform) is selected, timing accuracy is +20 cycles or 1%; when DFT (fundamental RMS) is selected, accuracy is 1 to +3 cycles or 1%. RMS Overvoltage, Neutral 59N Pickup #1, #2 5.0 to V 0.1 V ±0.5 V or ±0.5% Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 to +3 Cycles or ±1% VT Fuse-Loss Detection 60 FL A VT fuse-loss condition is detected by using the positive and negative sequence components of the voltages and currents. VT fuse-loss output can be initiated from internally generated logic or from input contacts. 81 Time Delay 1 to 8160 Cycles 1 Cycle 1 to +3 Cycles or 1% Frequency Pickup #1,#2,#3,#4.00 to Hz 0.01 Hz 0.02 Hz to Hz* Time Delay #1,#2,#3,#4 2 to 65,0 Cycles 1 Cycle 2 to +3 Cycles or 1% The pickup accuracy applies to 60 Hz models at a range of 57 to 63 Hz, and to Hz models at a range of 47 to 53 Hz. Beyond these ranges, the accuracy is 0.1 Hz. Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating. 5
6 * This range applies to Hz nominal frequency models. PROTECTIVE FUNCTIONS (cont.) Device Setpoint Number Function Ranges Increment Accuracy 87 Phase Differential Current Minimum Pickup 0.20 A to 3.00 A 0.01 A 0.10 A or 5% (0.04 to 0.60 A) ( 0.02 A or 5%) Percent Slope 1 to 100% 1% 2% Time Delay 1 to 8160 Cycles 1 Cycle 1 to +3 Cycles or 1% When a time delay of 1 cycle is selected, the response time is less than 1 1 / 2 cycles. 87 GD Ground (zero sequence) Differential Pickup 0.2 to 10 A 0.01 ±0.1 or ±5% (0.04 to 2.00 A) Time Delay 1 to 8160 Cycles 1 Cycle 1 to +3 Cycles or ±1% CT Ratio Correction (R C ) 0.10 to The 87GD function is provided primarily for low-impedance grounded generator applications. This function operates as a directional differential. If 3I 0 or I n is extremely small, the directional element is disabled. External Functions EXT Two functions are provided for externally connected devices to trip through the M 3420 to provide additional logic and target information. Any one or more of the input contacts (INPUT1 through INPUT6) can be programmed to activate designated output contacts after a selected time delay. Time Delay #1, #2 1 to 8160 Cycles 1 Cycle 1 to +3 Cycles or 1% Nominal Settings Nominal Voltage 60 to 140 V 1 V Nominal Current 0. to 6.00 A 0.01 A VT Configuration Line-Line / Line-Ground/Line-Ground to Line-Line* Seal-In Delay 2 to 8160 Cycles 1 cycle 1 to +3 Cycles or ±1% * When Line-Ground to Line-Line is selected, the relay internally calculates the line-line voltage from the lineground voltages for all voltage-sensitive functions. This Line-Ground to Line-Line selection should only be used for a VT nominal secondary voltage of 69 V (not 120 V). Select the greater of these accuracy values. Values in parentheses apply to 1 A CT secondary rating. 6
7 Metering The M 3420 provides metering of voltages (phase, neutral and sequence quantities), currents (phase, neutral and sequence quantities), real power, reactive power, power factor and impedance measurements. Metering accuracies are: Voltage: Current: Power : Frequency: 0.5 V or 0.5%, whichever is greater 0.8 V or 0.75%, whichever is greater (when both RMS and line ground to line line are selected) 5 A rating, 0.1 A or 3%, whichever is greater 1 A rating, 0.02 A or 3%, whichever is greater 0.01 PU or ±2%, whichever is greater (real and reactive) 0.02 Hz (from 57 to 63 Hz for 60 Hz models; from 47 to 53 Hz for Hz models) Oscillograph Recorder The oscillograph recorder provides comprehensive data recording of all monitored waveforms, storing up to 170 cycles of data. The total record length may be configured by the user for 1, 2, 3 or 4 partitions. The sampling rate is 16 times the power system nominal frequency ( or 60 Hz). When armed, the recorder is triggered either via the designated status inputs, trip outputs, or via serial communications. When armed yet untriggered, the recorder continuously stores waveform data, keeping the most recent data in memory. When triggered, the recorder continues to store data in memory for a user-defined, post-trigger delay period. Target Storage A total of 32 targets can be stored. The information will include the function(s) operated, the functions picked up, input/output contact status, timer status, time stamp, and phase and neutral currents at the time of trip. Calculations Current and Voltage RMS Values: Uses discrete Fourier transform (DFT) algorithm on sampled (16 times per cycle) voltage and current signals to extract fundamental frequency phasors for M 3420 calculations. RMS phase voltages for the 59 and 27 functions (when total RMS is selected), and the 24 function are obtained using the time domain approach to obtain accuracy over a wide frequency band. When the RMS option is selected, the magnitude calculation is accurate over a wide frequency range (10 to 80 Hz). When the DFT option is selected, the magnitude calculation is accurate near nominal frequency ( or 60 Hz). Power Input Options Nominal 110/120/230/240 V ac, /60 Hz, or nominal 110/125/220/2 V dc. UL/CSA rating 85 V ac to 265 V ac and from 80 V dc to 288 V dc. Burden 20 VA at 120 V ac/125 V dc. Withstands 300 V ac or 300 V dc for 1 second. Nominal 24/48 V dc, operating range from 18 V dc to 56 V dc. Burden 20 VA at 24 V dc and 20 VA at 48 V dc. Withstands 65 V dc for 1 second. An optional redundant power supply is available. Sensing Inputs Four Voltage Inputs: Rated nominal voltage of 60 V ac to 140 V ac, 60 Hz/( Hz optional). Will withstand 240 V continuous voltage and 360 V for 10 seconds. Source voltages may be line-to-ground or line-to-line connected. Phase sequence ABC/ACB is selectable. Voltage transformer burden less than 0.2 VA at 120 V. Seven Current Inputs: Rated nominal current (I R ) of 5.0 A or 1.0 A (optional), 60 Hz/( Hz optional). Will withstand 2I R continuous current and 100I R for 1 second. Current transformer burden is less than 0.5 VA at 5 A (5 A option), or 0.3 VA at 1 A (1 A option). 7
8 Status Input Contacts The status inputs, INPUT1 through INPUT6, can be programmed to block any of the M 3420 functions, to trigger the oscillograph recorder, or to operate one or more outputs. The status inputs should be dry contacts and are internally connected (wetted) to a 24 V dc power supply. To provide breaker status LED indication on the front panel, the INPUT1 status input contact must be connected to the 52b breaker status contact. The minimum current value to initiate/pickup an Input is >25 ma. Output Contacts The eight programmable output contacts (six form a and two form c ), the power supply alarm output contact (form b ), and the self-test alarm output contact (form c ) are all rated as per IEEE C37.90 (See Tests and Standards section for details). Any of the M 3420 functions can be individually programmed to activate any one or more of the eight programmable output contacts. Target/Status Indicators and Controls The RELAY OK LED reveals proper cycling of the microcomputer. The BRKR CLOSED LED will turn on when the breaker is closed (when the 52b contact input is open). The OSC TRIG LED indicates that oscillographic data has been recorded in the unit's memory. The TARGET LED will turn on when any of the relay functions operate. Pressing and releasing the TARGET RESET button resets the target LED if the conditions causing the operation have been removed. Pressing and holding the TARGET RESET button displays the present pickup status of the M 3420 functions. The PS1 and PS2 LEDs will remain on as long as power is applied to the unit and the power supply is operating properly. Communication Communications ports include rear panel RS 232 and RS-485 ports, a front panel RS-232 port, and an IRIG B port. The communications protocol implements serial, byte-oriented, asynchronous communication, providing the following functions when used with the Microsoft Windows-compatible M 3800A or S-3400 (Windows 7 or later) IPScom Communications Software package. MODBUS and BECO 2200 protocols are supported, providing: Interrogation and modification of setpoints Time-stamped trip target information for the 32 most recent events Real-time metering of all quantities measured. Downloading of recorded oscillographic data (Not available with MODBUS) IRIG-B The M 3420 can accept a modulated IRIG B time clock synchronization signal through a BNC connector provided at the rear of the unit. The IRIG B time synchronization information is used to correct the hour, minute, seconds and milliseconds information. HMI Module (optional) Local access to the is provided through an optional M-3931 HMI (Human-Machine Interface) Module, allowing for easy-to-use, menu-driven access to all functions via six buttons and a 2-line by 24 character alphanumeric LCD. Features of the HMI Module include the following: User-definable access codes allow three levels of security Interrogation and modification of setpoints Time-stamped trip target information for the 32 most recent events Real-time metering of all quantities measured 8
9 Target Module (optional) An optional M-3920 Target Module provides 24 target and 8 output LEDs. Appropriate target LEDs will light when the corresponding M 3420 function operates. The targets can be reset with the TARGET RESET button. The OUTPUT LEDs indicate the status of the programmable output contacts. Type Tests and Standards The M 3420 Generator Protection relay complies with the following type tests and standards: Voltage Withstand Dielectric Withstand IEC ,0 V dc for 1 minute applied to each independent circuit to earth 3,0 V dc for 1 minute applied between each independent circuit 1,0 V dc for 1 minute applied to IRIG-B circuit to earth 1,0 V dc for 1 minute applied between IRIG-B to each independent circuit Impulse Voltage IEC ,000 V pk, +/- polarity applied to each independent circuit to earth 5,000 V pk, +/- polarity applied between each independent circuit 1.2 by µs, 0 ohms impedance, three surges at 5 second intervals Insulation Resistance IEC > 40 Megaohms Electrical Environment Electrostatic Discharge Test IEC Class 4 (8 kv) point contact discharge Fast Transient Disturbance Test IEC Class 4 (4 kv, 2.5 khz) Surge Withstand Capability ANSI/IEEE C Radiated Susceptibility ANSI/IEEE C ,0 V pk-pk oscillatory applied to each independent circuit to earth 2,0 V pk-pk applied between each independent circuit 5,000 V pk Fast Transient applied to each independent circuit to earth 5,000 V pk Fast Transient applied between each independent circuit V/m Output Contacts Ratings IEEE C37.90 UL 8 CSA C22.2 No A make for 0.2 seconds at 2 Vdc resistive 8 A carry at 120 Vac, /60 Hz 6 A break at 120 Vac, /60 Hz 0.1 A break at 125 Vdc 0.1 A break at 120 Vac 9
10 Atmospheric Environment Temperature IEC IEC IEC Cold, 20 C for 96 hours Dry Heat, +70 C for 96 hours Damp Heat, % RH, for 96 hours Mechanical Environment Vibration IEC Vibration response Class 1, 0.5 g Vibration endurance Class 1, 1.0 g Compliance UL-Listed per 8 Industrial Control Equipment CSA-Certified per C22.2 No Industrial Control Equipment External Connections M 3420 Generator Protection Relay External Connections are illustrated in Figures 1, 2, and 3 on the following pages. Physical Size: 19.00" wide x 5.21" high x 10.00" deep (48.3 cm x 13.2 cm x 25.4 cm) Mounting: The unit is a standard 19", semiflush, three-unit high, rack-mount panel design, conforming to ANSI/EIA RS-310C and DIN Part 5 specifications. Vertical or horizontal panel-mount options are available. Contact Beckwith Electric for optional GE L 2/Westinghouse FT 41 retrofit panel vertical mounting details. Environmental: For flat surface mounting on a Type 1 enclosure, rated to 70 C surrounding air ambient. Approximate Weight: 13 lbs (7.7 kg) Approximate Shipping Weight: 15 lbs (11.3 kg) Recommended Storage Parameters Temperature: 5 C to 40 C Humidity: Maximum relative humidity 80% for temperatures up to 31 C, decreasing to 31 C linearly to % relative humidity at 40 C. Environment: Storage area to be free of dust, corrosive gases, flammable materials, dew, percolating water, rain and solar radiation. See Instruction Book, Appendix E, Layup and Storage for additional information. Patent & Warranty The M 3420 Generator Protection Relay is covered by U.S. Patents 5,592,393 and 5,224,011. The M 3420 Generator Protection Relay is covered by a five year warranty from date of shipment. Specification subject to change without notice. 10
11 U C L US LISTED IND.CONT.EQ. 83F4 R NRTL /C LR B E C K W IT H E L E C T R I C C O. I N C t h AV E NO. L A RG O, FL WA RNING! CONTA CT W ITH T ERMINALS MAY CA USE ELECT RIC SHOCK Danger! Contact avec les terminaux peut causer un choc electrique FO R CO NT ACT RAT INGS SEE INSTRUCT ION MANUAL MODEL: FIRMWARE: Hz 60 Hz SERIAL NO IRIG- B COM 2 RS RX TX RS48 5 COM 3 I N I N I N I N I N I N P U T S I N ( 5 2 b ) I N R T N P / S S E L F - T E S T A L A R M S O U T P U T S V V A B V A B V B C V V C V C A N I I I A B C I N I a I b I c P S 2 P S F 1 P S 2 P S 1 F RAT ED VO LT AGE RATED CURRENT 1A,NOM 5 A,NOM , / 6 0Hz AMP,25 0V (3 AB) U.S. PATENT 5,592,393, 5,224,011 F 3 F 4 Figure 1 External Connections NOTES: 1. Output contacts #1 through #4 are high speed operation contacts. 2. To comply with UL and CSA listing requirements, terminal block connections must be made with #22 12 AWG solid or stranded copper wire inserted in an AMP # (or equivalent) connector. Wire insulation must be rated at 75 C minimum. Terminal block connections 1 through 34 must be tightened to 12 in lbs torque. Terminal block connections 35 through 63 must be tightened to 8.0 in lbs, minimum, 9.0 in-lbs, maximum torque. Over torquing may result in terminal damage. 3. ONLY dry contacts must be connected to inputs (terminals 5 through 10 with 11 common) because these contact inputs are internally wetted. Application of external voltage on these inputs may result in damage to the units. 4. All relays are shown in the de-energized state. 5. The power supply relay (P/S) is energized when the power supply is functioning properly. 6. The self-test relay is energized when the relay has performed all self-tests successfully. 7. FIELD GND connection is intended for future use.!! 11
12 Utility System Typical Connection Diagram This function provides control for the function to which it points. NOTE: Some functions are mutually exclusive; see Instruction Book for details. 52 Unit BFPh CT Gen VT FL 32 51V CT 87 GD BFN N 51N CT R Low Impedance Grounding with Overcurrent Stator Ground Fault Protection VT 59N R High Impedance Grounding Figure 2 One-Line Connection Diagram 12
13 UTILITY SYSTEM A B C Other Relays a b c Other Relays ALTERNATE CONNECTIONS a b c Other Relays I C I B I A Gen A B C 52b Three VT Wye-Wye Connection 1 1 Two VT Open-Delta Connection Generator Other Relays A B C Low Impedance Grounding ➁ ➂ ➃ ➄ ➅ Alternate VT connections Required generator breaker status input (52b). Contact is closed when generator breaker is open. Use unit breaker contact if no generator breaker present. Output contact pairs designated by user. Alarm output can be grouped to a single alarm at discretion of user. Available control output to supervise other relays for VT Fuse Loss can be designated. Input contact number is designated by user. 8 WARNING: ONLY dry contacts must be connected because these contact inputs are internally wetted. Application of external voltage on these inputs may result in damage to the units. High Impedance Grounding nnote: current terminal polarity marks ( ) indicate "entering" current direction when primary current is "from" the generator. If CT connections differ from those shown, adjust input terminals. Example of Control / Output Connections + DC: 24 V 48 V OR DC: 110 V 125 V 220 V 2 V AC: 110 V 120 V 230 V 240 V + POWER SUPPLY b BREAKER FAILURE INITIATE 6 60FL OSCILLOGRAPH RECORDER INITIATE TRIP ALARM SELF-TEST FAILURE ALARM POWER OK STATUS ALARM 5 VT FUSE LOSS TRIP 3 52G 52Ga - 4 EXTERNAL INPUTS ALARM OUTPUTS CONTROL OUTPUTS TRIP OUTPUT Figure 3 Three-Line Connection Diagram 13
14 17.68 [44.91] 17. [44.45] ACTUAL 5.21 [13.23] ACTUAL 5.28 [13.41] RECOMMENDED CUTOUT WHEN RELAY IS NOT USED AS STANDARD RACK MOUNT 17. [44.45] [25.91] [48.26] [46.51] 0.35 [0.89] 0.40 [1.02] X 0.27 [0.68] Slot (4X) 2.25 [5.72] 1.48 [3.76] Standard 19" Horizontal Mount Chassis NOTE: Dimensions in brackets are in centimeters. Figure 4 Mounting Dimensions 14
15 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT 6 OUT 7 OUT 8 M 3420 Generator Protection Relay 5.65 [14.40] 0.35 [0.89] 6.19 [15.7] 2.25 [5.72] 1.97 [5.0] 0.28 [0.71] Dia. (4X) 5.59 [14.20] Actual 2.25 [5.72] 1.67 [4.24] 0.03 [0.076] TARGETS [48.26] OUTPUTS [46.51] 17.5 [44.45] ACTUAL [44.91] EXIT ENTER TARGET RESET PS 2 PS 1 TARGET DIAG BRKR CLOSED OSC. TRIG RELAY OK TIME SYNC COM [44.45] Recommended cutout when relay is not used as standard rack mount and is panel cut out mounted [25.91] [48.26] NOTE: Dimensions in brackets are in centimeters. Figure 5 Vertical Mounting Dimensions NOTE: Panels for vertical mounting are available. When mounted vertically, the target module will be located at the top and all front-panel text will be horizontally aligned. Consult Beckwith Electric Co. for details. 15
16 BECKWITH ELECTRIC CO., INC th Avenue North Largo, Florida U.S.A. PHONE (727) FAX (727) ISO 9001: Beckwith Electric Co. Printed in U.S.A. ( ) SP-16MC
Generator Protection M 3425
PROTECTION Generator Protection M 3425 Integrated Protection System for Generators of All Sizes Unit shown with optional M 3925 Target Module and M 3931 HMI (Human Machine Interface) Module Provides all
More informationInstruction Book. M-3425A Generator Protection
Instruction Book M-3425A Generator Protection PROTECTION Generator Protection M 3425A Integrated Protection System for Generators of All Sizes Unit shown with optional M 3925A Target Module and M 3931
More informationInstruction Book. M 3425A Generator Protection
Instruction Book M 3425A Generator Protection TRADEMARKS All brand or product names referenced in this document may be trademarks or registered trademarks of their respective holders. The content of this
More informationGenerator Protection M 3425A
PROTECTION Generator Protection M 3425A Integrated Protection System for Generators of All Sizes Unit shown with optional M 3925A Target Module and M 3931 HMI (Human Machine Interface) Module Exceeds IEEE
More informationTransformer Protection M 3310
PROTETION Transformer Protection M 3310 Integrated Protection System for Transformers of ll Sizes Unit shown with optional M 3931 HMI Module and M 3910 Target Module Fully Digital Multifunction Relay with
More informationDigital Motor Bus Transfer System M 4272
SYNCHRONIZING Digital Motor Bus Transfer System M 4272 Integrated Synchronizing System Provides Automatic and Manual transfers of motor bus systems in power plants and industrial processing plants to ensure
More informationTransformer Protection M-3311A
PROTECTON Transformer Protection ntegrated Protection System Unit shown with optional M-3931 HM Module and M-3911 Target Module For Transformers of All Sizes: 2, 3 or 4 winding Transformers for Transmission
More informationNO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.
MODBUS/BECO2200-M3425A Communication Data Base for M-3425A Integrated Protection System Device I.D. = 150 Specifications presented herein are thought to be accurate at the time of publication but are subject
More informationBE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2
BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY The BE1-67N Ground Directional Overcurrent Relay provides ground fault protection for transmission and distribution lines by sensing the direction and magnitude
More informationNPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function.
REGULATION AUTOMATIC SYNCHRONIZER for GENERATOR NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds
More information1 INTRODUCTION ORDER CODE / INFORMATION
INTRODUCTION ORDER CODE / INFORMATION 269/269Plus * * * * * * 269/269Plus SV D/O.4 ORDER CODE / INFORMATION Motor management relay Standard version Drawout version Phase CT Ground CT (required for D/O
More informationNPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator
REGULATION Automatic Synchronizer for Generator NPRG860 & NPRG870 perform synchronization and paralleling of generators with electrical network. NPRG860 features a speed adjustment function. NPRG870 adds
More informationGenerator Protection GENERATOR CONTROL AND PROTECTION
Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault
More informationwww. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay
Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:
More informationProtection components
Multifunction protection relays LT-P Environment Conforming to standards IEC 947-4-1, IEC 34-11, IEC 755, VDE 010, VDE 00. &Ãmarking Meets the essential requirements of the Low Voltage equipment (LV) &
More informationALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring
ALP-UDR Universal Detection Relay user-defined protection, automation, and monitoring The first Real-Time Protection and Automation platform that can be adapted to a wide variety of applications. While
More informationCurrent Loop Interface Module M 2025D
CONTROLS Current Loop Interface Module M 2025D Current-to-Voltage Analog Converter used with the M 2001 Series Digital Tapchanger Control and M-2948 Tap Position Sensors to provide positive tap position
More informationThese drawings and single line diagrams provide an outlook of Basler Electric solutions for Excitation System installations and retrofit
BSLER ELECTRIC DECS EXCITTION SYSTEMS For Retrofitting solutions and New installations These drawings and single line diagrams provide an outlook of Basler Electric solutions for Excitation System installations
More informationAddendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays
Dual-Source Power Supply Addendum to I.B. 17555 Addendum to Instructions for Installation, Operation and Maintenance of Digitrip 3000 Protective Relays Table of Contents Page 1.0 Introduction...1 2.0 General
More informationPD300. Transformer, generator and motor protection Data sheet
PD300 Transformer, generator and motor protection Data sheet DSE_PD300_eng_AO No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam T&D. One of
More informationsatech SynchroStar GPS 200 Series
satech SynchroStar GPS 200 Series KEY BENEFITS Designed with high quality oscillator OCXO the device is characterized by superior frequency stability and improved holdover performance that allows maintaining
More informationwww. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay
Generator Differential Relay The MD3G Rotating Machine Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3G relay offers the following
More informationAPPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges.
APPLICATION: Basler Electric offers a New Line of digitally controlled brush (static) or brushless excitation systems designed for use with existing Hydro, Gas as well as Diesel driven generators requiring
More informationOvercurrent Protection / 7SJ45
Overcurrent Protection / SJ SIPROTEC easy SJ numerical overcurrent protection relay powered by CTs Fig. / Description SIPROTEC easy SJ numerical overcurrent protection relay powered by current transformers
More informationInstantaneous Overcurrent Relay
Midos Type MCRI Instantaneous Overcurrent Relay Features High speed operation Not slowed by dc transients Settings readily adjustable on relay front plate Two phase and earth fault relay Figure 1: Type
More informationT/3000 T/3000. Substation Maintenance and Commissioning Test Equipment
T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY
More informationCurrent Loop Interface Module M-2025C
CONTROLS Interface Module M-2025C Current-to-Voltage Analog Converter used with the M-2001 Series Digital Tapchanger Control and M-2948/M-2949 Tap Position Sensors to provide positive tap position knowledge
More informationDECS-200N-C1 Negative Forcing Digital Excitation Control System
DECS-200N-C1 Negative Forcing Digital Excitation Control System The DECS-200N is a very compact Negative Forcing Digital Excitation Control System. This compact design accommodates 63 Vdc and 125 Vdc applications
More informationNTG MULTIFUNCTON GENERATOR PROTECTION RELAY. NTG-Slide
NTG MULTIFUNCTON GENERATOR PROTECTION RELAY 1 NTG Digital protection relay that integrates a number of functions required r for the protection of generators. It is used in power stations from gas, steam,
More informationSPECIFICATION FOR OVERCURRENT RELAYS
SPECIFICATION FOR OVERCURRENT RELAYS 1/9 1. Procedure A manufacturer willing to classify an overcurrent relay according to this specification should provide: A complete file providing a clear, unambiguous
More informationProtective Relays Digitrip 3000
New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer
More information1 INTRODUCTION 1.1 PRODUCT DESCRIPTION
GEK-00682D INTRODUCTION INTRODUCTION. PRODUCT DESCRIPTION The MDP Digital Time Overcurrent Relay is a digital, microprocessor based, nondirectional overcurrent relay that protects against phase-to-phase
More informationPQube 3 Specifications
PQube 3 Specifications Reference conditions for factory tests: 19~25 C, 10%~70% RH MAINS VOLTAGE MEASURING CHANNELS Measurement Channels Power Configuration/ Range of Nominal Input Voltage 3 Line to Neutral,
More informationPower Meter Series PM3200 Functions and characteristics
Functions and characteristics PB108433 This PowerLogic Power meter offers basic to advanced measurement capabilities. With compact size and DIN rail mounting, the PM3200 allows mains and feeders monitoring
More informationHigh-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime
Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with
More informationBE1-81O/U DIGITAL FREQUENCY RELAY FEATURES
BE1-81O/U DIGITAL FREQUENCY RELAY The BE1-81O/U Digital Frequency Relay senses an ac voltage from a power system or generator to provide protection in the event that the frequency exceeds predetermined
More informationASHIDA Numerical OC/EF Protection Relay
ASHIDA Numerical OC/EF Protection Relay Features: 4 Element (3 Phase + EF) over current IDMT with instant trip. Back - lit LCD display for settings. Display of fault current. / Load current. Selection
More informationD I G I T A L V O L T A G E R E G U L A T O R
The Cat Digital Voltage Regulator is a microprocessor based control designed to provide precise voltage control, robust transient response, and generator protection with industry leading features and versatility.
More informationBE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY
BE1-87G VARIABLE PERCENTAGE DIFFERENTIAL RELAY The BE1-87G is a single or three-phase solid-state variable percentage differential relay designed to provide selective, high-speed, differential protection
More informationMultimeter 500CVD21 RTU500 series
Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase
More informationDIFFERENTIAL CURRENT GENERATOR «POCDIF» (AC/DC - 32A - 50V - 12 ranges)
PERFORMANCES 12 ranges of AC current from 16 ma to 128 A peak AC permanent current up to 26 ARMS Nine ranges of DC permanent current from 16 ma to 12 A DC current ± 6mA or ± 10 ma stackable to AC current
More informationSEL-2664 Field Ground Module Data Sheet
SEL-2664 Field Ground Module Protect Against Major Damage by Adding Field Ground Protection to the SEL-300G, SEL-700G, and SEL-2664S Relays With the SEL-2664 High Reliability, Low Price Ten-Year, Worldwide
More informationRelion 605 series Self-Powered Feeder Protection REJ603 Product Guide
Relion 605 series Relion 605 series Self-Powered Feeder Protection Product Guide Contents 1 Description...3 2 Protection functions...3 3 Application...4 4 Self-supervision...4 5 Inputs and outputs...4
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities
More informationReplacement solution
Replacement solution for the ABB DPU2000R protection and control relay Specification File, Revision, Date (Pages) Replacement Relay Specification_ABB DPU2000R_0.doc, Revision 0, August 2, 2013 (37) Table
More informationWaterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology
Waterpower '97 August 5 8, 1997 Atlanta, GA Upgrading Hydroelectric Generator Protection Using Digital Technology Charles J. Beckwith Electric Company 6190-118th Avenue North Largo, FL 33773-3724 U.S.A.
More informationUtility Communications Teleprotection Equipment TPT-200
Utility Communications Teleprotection Equipment TPT-200 5C Communications Inc. All rights reserved Teleprotection is designed to transfer protection commands coming, in most cases, from distance protection
More informationTransformer differential protection
Transformer differential protection Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice (SE970883) Features Three phase differential protection with two, three, five or
More informationEnergy Management Three-phase energy meter with output modules Type EM4-DIN
Energy Management Three-phase energy meter with output modules Type EM4-DIN Class 1 (active energy) Class 2 (reactive energy) Three-phase multi-function energy meter Back-lighted LCD display 3 1 / 2 DGT
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities
More informationATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink
Characteristics variable speed drive ATV12-4kW - 5hp - 200..240V - 3ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly
More informationFuzzy Temperature Controllers E5AF
Fuzzy Temperature Controllers 1/4 DIN Controller Combines Fuzzy and PID Control For Fast Response to Process Disturbances Advanced PID control provides optimal response during start-up and steadystate
More informationUniversal Protective Relay Test Set
AVO INTERNATIONAL BRINGING RELIABILITY TO AMPS VOLTS OHMS MULTI-AMP Model SR-98 Digital Signal Processor Based technology High Current/High Power output New CA mode captures high speed trip on MCCB 0 to
More informationwww. ElectricalPartManuals. com Basler Electric P. 0. BOX 269 HIGHLAND, ILLINOIS 62249, U.S.A. PHONE FAX
The BE1-47N Voltage Phase Sequence Relay provides protection for rotating equipment from the damaging effects of excessive negative sequence voltage resulting from phase failure, phase unbalance and reversed
More information489 Generator Management Relay Instruction Manual
Digital Energy Multilin Firmware Revision: 4.0X Manual Part Number: 1601-0150-AF Manual Order Code: GEK-106494P Copyright 2011 GE Multilin 489 Generator Management Relay Instruction Manual GE Multilin
More informationMICROPROCESSOR-BASED METERING EQUIPMENT SECTION 16901C PART 2
PART 1 PART 2 PRODUCTS 2.01 MANUFACTURERS A. Eaton products B.. C.. The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features
More informationATV12H018F1 variable speed drive ATV kW hp V - 1ph
Characteristics variable speed drive ATV12-0.18kW - 0.25hp - 100..120V - 1ph Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component
More informationATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink
Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Main Range of product Altivar 12 Product or component type Product destination Product specific application
More information02/11/2015
Modem communication plug and play solutions GSM Part number 88970119 For remote control of your application Automatic notification of alarms via SMS (GSM Modem) / email or on a PC with M3 ALARM software.
More informationDigital Line Protection System
Digital Line Protection System! Microprocessor Based Protection, Control and Monitoring System! Waveform Sampling! Proven Protection! Economical! Ease of Retrofit 1 DLP-D D Enhancements ASCII SUBSET Three
More informationEnergy Management Energy Meter with plug-in Output Modules Type EM4-DIN
Energy Management Energy Meter with plug-in Output Modules Type EM4-DIN Degree of protection (front): IP 40 Front dimensions: 9 DIN modules RS 422/485 Serial port by means of optional module Dual pulse
More informationPowerLogic power-monitoring units. PM700 series power meter. Technical data sheet
PowerLogic power-monitoring units PM700 series power meter Technical data sheet 2009 Functions and characteristics The PowerLogic PM700 series power meter offers all the measurement capabilities required
More informationIRIG-B Interface (De-modulated) External clock synchronization signal IRIG format B00X
P847B&C Technical Data Sheet INTERFACES IRIG-B (De-modulated) Use Standard Connector Cable type Isolation Input signal Input impedance at dc Accuracy IRIG-B Interface (De-modulated) External clock synchronization
More informationSIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay
Overcurrent Protection / 7SJ46 SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay Function overview Fig. /11 Description The SIPROTEC easy 7SJ46 is a numerical overcurrent protection relay which
More informationWIRELESS INSULATOR POLLUTION MONITORING SYSTEM
SYSTEM OVERVIEW Pollution monitoring of high voltage insulators in electrical power transmission and distribution systems, switchyards and substations is essential in order to minimise the risk of power
More informationRI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters
RI-D440 Three Phase easywire Multifunction DIN Rail Energy Meter Four module DIN rail mounted Energy pulse LED 330mV Input from easywire CTs (or -/1A and -/5A current transformer input with TAS-SCTEWA
More informationPROTECTION OF TRANSFORMERS M-3311A TEST PLAN
PROTECTION OF TRANSFORMERS M-3311A TEST PLAN Chuck Mozina -- is a Consultant, Protection and Protection Systems for Beckwith Electric and resides in Palm Harbor (near Tampa), Florida.. He is a Life Fellow
More informationGPM. Field and Stator Ground Fault Protection Modules. Instruction Manual AF1. GE Grid Solutions
GE Grid Solutions GPM Field and Stator Ground Fault Protection Modules Instruction Manual Product version: 2.0x GE publication code: 1601-0256-AF1 (GEK-113231D) 1601-0256-AF1 Copyright 2017 GE Multilin
More informationADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W
ADC5000 SERIES AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications 60W, 125W and 250 W Input voltage 230/115 VAC voltages 12, 24, 36 or 48 VDC Statistical MTBF >3 000
More informationATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol
Product datasheet Characteristics ATV12HU22M2 Complementary Main Range of product Altivar 12 Product or component type Product destination Product specific application Assembly style Component name Variable
More informationLZS-A500-3 POWER SUPPLY Installation, Operation, and Maintenance Manual. IM-LZSA500-3 January 2008 Revision H
LZS-A500-3 POWER SUPPLY Installation, Operation, and Maintenance Manual IM-LZSA500-3 January 2008 Revision H Table of Contents LZS-A500-3 Power Supply 1) Safety and Recommended Practices 2 1.1 General
More informationMeasuring Transducer MT4xx series Programmable AC Current Transducer MT418
Measuring Transducer MT4xx series Programmable AC Current Transducer MT418 o RMS AC current or frequency measurements o Current auto range measurements up to 12 A o Frequency measurement range 16 400 Hz
More informationGE Power Management. Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C
GE Power Management Digital Microprocessor-based Non-directional Overcurrent Relays MIC series 1000 Instructions GEK 98840C 7$%/(2)&217(176 1. DESCRIPTION...2 2. APPLICATION...6 3. CHARACTERISTICS...7
More informationApplication and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16
Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16 COMMISSIONING 17-22 WIRING DIAGRAM 23 1. INTRODUCTION
More informationSOLUTIONS FOR AN EVOLVING WORLD RFL Programmable FSK Powerline carrier system
SOLUTIONS FOR AN EVOLVING WORLD RFL 9780 Programmable FSK Powerline carrier system Your world is changing and so are we. At RFL, we know your needs change much faster than your infrastructure. Our comprehensive
More informationRISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:
Application : RISH Master 3490 SS is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy having auto-resetting 8 digit seven segment LED counter. The unit
More information02/11/2015
Modem communication plug and play solutions GSM Part number 88970119 For remote control of your application Automatic notification of alarms via SMS (GSM Modem) / email or on a PC with M3 ALARM software.
More informationINTELLIMETER REGISTER
INTELLIMETER REGISTER MODEL RG2 INSTALLATION AND CONNECTIONS INSTALLATION MANUAL WARNING: Any work on or near energized metering equipment can present a danger of electrical shock. All work on these products
More informationType CP-S, CP-C & CP-A Switch mode
Switch mode power CP-S, CP-C & CP-A Switch mode Characteristics CP-S and CP-C range Output current 5 A, 10 A and 20 A Integrated power reserve of up to 50 % 5 A and 10 A devices with pluggable connecting
More informationPRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID
RI-D140 Three Phase Multifunction DIN Rail Energy Meter (MID Certified) Four module DIN rail mounted Energy pulse LED True RMS measurement Cost effective and accurate Modbus communication -/1A or -/5A
More informationES-777-MV-P2_A1 03/01/10
ENGINEERING SPECIFICATION SYMCOM MODEL 777-MV-P2 Electronic Overload Relay PART 1 GENERAL 1.1 REFERENCES A. UL 508 Industrial Control Equipment Underwriters Laboratories B. IEC 60947 Low Voltage Switchgear
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationProtection and control VIP300. Technical manual
Protection and control VIP300 Technical manual contents 1. presentation of the VIP300...3 2. use and settings...4 3. choice of sensors and operating ranges...9 4. connection scheme...10 5. assembly...11
More informationSULTANATE OF OMAN METERING AND DATA EXCHANGE CODE
1.0 GENERAL SULTANATE OF OMAN METERING AND DATA EXCHANGE CODE STANDARD: OES-22F THREE PHASE KILOWATT-HOUR DIGITAL METERS, CURRENT TRANSFORMER OPERATED, CONNECTED FOR SERVICE CONNECTIONS Electronic three
More informationBE1-32R, BE1-32 O/U DIRECTIONAL POWER RELAY
BE1-32R, BE1-32 O/U DIRECTIONAL POWER RELAY The BE1-32R Directional Overpower Relay and the BE1-32 O/U Directional Over/Underpower Relay are solid-state devices which provide versatility and control in
More informationStabilized Differential Relay SPAD 346. Product Guide
Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault
More informationATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink
Characteristics variable speed drive ATV12-0.37kW - 0.55hp - 100..120V - 1ph - with heat sink Product availability : Stock - Normally stocked in distribution facility Price* : 191.76 USD Main Range of
More informationLCL Series. SIngle Output Industrial Supplies. High Efficiency. Low Cost. 150 W Convection Cooled. 300 W & 500 W with Internal Fans
LCL Series SIngle Output Industrial Supplies High Efficiency Low Cost 150 W Convection Cooled 300 W & 500 W with Internal Fans Outputs form 12 V to 48 V 3 Year Warranty The LCL series is a low cost chassis
More informationT 1000 PLUS Secondary Injection Relay Test Set
Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator Test results and settings are saved into local memory
More informationT 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers
Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator High power outputs Large graphical display Compact
More information489 Generator Management Relay
GE Grid Solutions 489 Generator Management Relay Instruction Manual Product version: 4.0x GE publication code: 1601-0150-AM (GEK-106494W) 1601-0150-AM Copyright 2016 GE Multilin Inc. All rights reserved.
More informationMultimeter 560CVD11 Data sheet
RTU500 series Multimeter 560CVD11 Data sheet The fault current is measured up to 20 times nominal current. The current inputs withstand 50 times nominal current for 1 s. The Multimeter is equipped with
More informationULTRA RAPID POWER QUALITY ANALYZER
ULTRA RAPID POWER QUALITY ANALYZER Ultra rapid (cycle by cycle) advanced electrical network analysis Complete network harmonics analysis, up to 63 rd harmonic High visibility, 5 graphic LCD screen with
More informationSPAD 346 C Stabilized differential relay
SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault
More informationCentrale de mesure Power Meter PM500 Merlin Gerin
Notice d'installation et d'utilisation Installation and user manual Centrale de mesure Power Meter PM500 Merlin Gerin 059473_D Introduction and description Package contents c one PM500 power meter with
More informationRI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters
RI-F200 Series Single and Three Phase Multifunction Energy Meter DIN 96 panel mounted -/1A or -/5A current transformer input Single phase or three phase network compatible Programmable voltage and current
More informationTechnical Data Sheet. x1000. kwh R Y B
Technical Data Sheet x1000 Von kwh IRev 3600 imp /kwh R Y B is a compact multifunction instrument which is a 96mm x 96mm panel mounted kilowatt hour meter it measures active energy with class 1.0 accuracy
More informationASHIDA Numerical 3OC + 1EF Protection Relay
PROTH. ERR L5 PKP FAULT DT REC LOCK BF L6 L7 CLOSE TRIP ADR 241B Protection Features : 4 Element (3 Phase + EF + Sensitive EF) Over current IDMT/DMT with instant trip. Programmable (Non- Volatile) Setting
More informationLXM32CD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V kw
Product data sheet Characteristics LXM32CD18N4 motion servo drive - Lexium 32 - three-phase supply voltage 208/480V - 1.8 kw Main Range of product Lexium 32 Product or component type Device short name
More informationModel Number Structure. Ordering Information. Solid-state Power OFF-delay Timer H3DE-H. Model Number Legend. List of Models
Solid-state Power OFF-delay Timer H3DE-H Timers Two delay-time models available. 0.1 to 12 seconds (S Series) 1 to 120 seconds (L Series) Covers wide range of supply voltage. Model Number Structure Model
More information