1 Short Circuit Current and Voltage Stability Analysis of a Realistic Generation System Using Fault Current Limiter and SVC 1 Ezz Badry, 1 Salah Kamel, 1 Loai S.Nasrat, 1,2 Ziad M. Ali 1 Department of Electrical Engineering, Faculty of Engineering, Aswan University, Aswan, Egypt 2 Electrical Engineering Department, Faculty of Engineering, Prince Sattam Bin Abdualziz University, 54 Wadi eldawaser11991, Kingdom of Saudi Arabia Ezzeldin.badry@khalda-eg.com, skamel@aswu.edu.eg, loaisaad@yahoo.com, dr.ziad.elhalwany@aswu.edu.eg Abstract_ Due to the frequently increasing in loads, the generated power must be upgraded to match this increasing, consequently a new short-circuit level will be developed based on the value of the generation system upgraded, this raising on short-circuit current level could be extremely harmful on the protective equipment. To overcome the problem of the new S.C. level a new approach can be achieved by using the fault current limiter (FCL) which consider the most economical and practical solution. This paper investigates a realistic power plant Khalda Petroleum Company (KPC), which located at Egypt western desert. The main target is to add a new 7 MW Generator to an existing 14 MW power plant drawn by three Generators therefor a short-circuit study will be calculated after and before adding the new Generator. An adequate FCL will be selected to maintain the short-circuit within the previous levels, on the other hand the S.V.C. will be used to maintain the voltage level likewise the existing by carrying out the Load Flow analysis after adding the FCL, all operations will be executed using ETAP 12.6 software. Keywords Fault current limiter, Short Circuit, Load Flow, SVC, ETAP I. INTRODUCTION Catastrophically damage for all components of the power system will be occurs due to frequently increasing of loads which demanding increasing in system generation in the power plant so an increasing in the short circuit level may exceed the equipment breaking capacity. By using larger stepper transformer, the level of the voltage will be increase and so adequate the S.C. level and this will grantee the safety conditions for the equipment of the system, or by readjusting the existing protection scope to be matches with the new S.C. level. Actually, both solutions will be expensive to carry out because of the high equipment fees, so an economical and a practical solution is needed to solve this problem without any change in the existing protection relay scope in the power system. This work illustrates in details a realistic example of power plant consists of three generators and needed to add a new generator as per loading increases therefor Fault Current Limiter are being uses to maintain short circuit level, SVC will also be used as the voltage drops on the 3.3 KV switchgear Bus Bar due to using of the FCL. II. Fault Current Limiter (FCL). FCL is a nonlinear devices works on decreasing the amount of the fault current cause it has a high impedance that can be added to the electric circuit when fault take place. Some of FLC has low impedance at the normal operation change to high impedance device extremely fast once the faults happened, and before a circuit breaker take action to trip a few milliseconds later. The common condition that for different current limiters is the operation should be at the distribution voltage level [1], and the FLC could be classified into two main types as following: A. Passive Limiters: It is permanently connected in series with the circuit of the power system so no need to turn on or using an external signal to control its operation, the series inductors and superconducting fault current limiters are considered passive devices[2-4], Reactors are counted as the most common passive limiter and flexible to be connected anywhere in the distribution circuit. They are a linear inductive reactance; arithmetically the impedance will be added to the system to reduce of the fault currents, a voltage regulation carried out to maintain the distribution system voltage within the limits, due to voltage drop, which exists due to the current flow through the reactors, are in the same quadrature with the load voltage. The case under study with this type of FCL will be investigated in this work. Reference Number: JO-P

2 B. Solid State Limiters(SSL) During the fault case and after a few milliseconds of its action the solid state devices inserted by electronic switches to increase the system impedance and to limit fault currents. [5]. SSL is categorized into two main types: The resonance based devices and the impedance switched bypass limiters. The operation of resonance-based devices is based on that during the fault the voltage sags will be happened and will have a direct effect on the fault current values [6, 7]. The impedance switched bypass limiters connected in series with the main distribution line, a pair of GTO are shunted with it to operate during the voltage alternate half cycles to create a new path of low impedance. The GTO switches are closed due to the fault and a large impedance will be appeared and so limiting the current, but there are some disadvantages due to switching power loss and its reliability cause the switching times effects are under search and study to enhance [8-9]. III. SHORT CIRCUIT STUDY. A short circuit study is modeled to get the values of the Max. and Min., a new generator or Fault Current limiter is added and so the study will be updated and repeat the adding process until optimize the best efficient limiter which will contribute on limiting the fault current to the same values before adding the new generator. All S.C. calculations were carried by using ETAP 12.6 based on IEC [10-13], the associated standards classify short circuit currents according to their magnitudes (maximum and minimum) and classify the fault distances from the generator (far and near). Maximum short circuit currents determine equipment ratings, while minimum currents dictate protective device settings. Near-to-generator and far-from-generator classifications determine which of the AC components decrease in the calculation. IV. STATIC VAR COMPENSATOR OPERATION To provide the fast acting reactive power the static VAR compensator (SVC) is installed on high voltage transmission networks [14-15], SVCs are parts of the Flexible AC transmission system [16-17] device family, regulating voltage, power factor, harmonics and stabilizing the system, and here in our case study the SVC has to be used after adding the adequate fault current limiter to regulate the far end bus voltage which influence in stabilizing the system. V. RESULT AND DISCUSSION The power plant single line diagram is shown in Fig.3 consists of three existing generator, two 2MVA power transformers 11 KV/.4KV, two 2.5MVA power transformer 11KV/3.3KV, 14 medium voltage CBs mounted with its related protective devices, 4 CBs represent as incoming feeders from the 4 generators to the two main bus bars feeding the 11 KV switchgear, when the coupler will maintain always closed the operation of adding new generator of 10 MW will be implemented as per the following steps: A- Calculate the short circuit values on the main four buses and at the far end, six buses are depicted in table (1), from the table (1). The Max. Values of S.C. are KA at BUS 1 & 2. these values should be adequate to the breaking capacity of the protective devices such as the CB, CT and PT. Bus No. Table (1) Short-Circuit Summary GROUND FAULT Voltage B- Calculate the short circuit values for the previous buses after adding the new 7 MW generator which will certainly as a result on increasing the Max. Fault current as shown in table (2). Table (2) Short-Circuit Summary GROUND FAULT Bus No. Voltage Reference Number: JO-P

3 C- Adding the fault current reactor in series with both Generators 3&4 as in Fig. 1 Then calculate the new short circuit values as shown in table (3). The results show that the sufficient values of the Max. Fault current which dropped from8.312 KA to 7.43 KA resulting on adding new fault current limiter reactors. Table (3) Short-Circuit Summary GROUND FAULT Bus No. Voltage D- Preform the load flow analysis to check the voltage stability for all the mentioned buses and found all buses listed on table (4) in under voltage case which resulting of inserting series reactor on the circuit, this problem had been overcome by using Static Var Compensator at the far end bus#48 As shown in Fig. (1) Fig. (2) Shows the amount of current change before and after adding the new generator and after adding the fault current limiter. Fig. (1) SLD after adding the FCL Table (4) LF Marginal Alerts results Bus No. Condition Rating % operating 37 Under voltage Under voltage Under voltage Under voltage Under voltage Under voltage Under voltage Under voltage Under voltage Under voltage Reference Number: JO-P

4 VI. CONCLUSION Fig. (2) Fault current values in the three cases Fig (3) Single line diagram Upgrading generation station is one of the most required operations now days, due to the rapidly increased in loads, some of this stations were not prepared for upgrading and leading to risky rises in the fault current level, all equipment, which are dealing directly with the system current, must withstand this rises in S.C. level. To overcome this problem there are two direction one of them is rise the voltage level of the system and the other is increase the impedance of the faulty circuit, in this paper after adding new 10 MW generator to an existing system of 15 MW we trying to maintain the new fault current level to the same as was before adding the new generator thus we don t have to replace any of the system equipment, this minimizing of the fault current had been achieved by adding Reference Number: JO-P

5 limitation, in Power Engineering Society Winter Meeting, vol. 4. two of passive FLC (reactors / Z= 4 ohm) in series with the IEEE Power Engineering Society, Jan. 2000, pp two Generator 3&4,results show that the adding of FLC is [8] R. K. S. et al., Solid state distribution current limiter and able to control the fault current by increasing the impedance circuit breaker: Application requirements and control strategies, IEEE Transactions on Power Delivery, vol. 8, no. 3, pp of the system without adding or interrupting the circuit. The 1164, July fault current limiter is proved to be and effective technique [9] P. K. C. Meyer and R. W. DeDoncker, Design of a novel low to limit the current in the faulty network without any loss fault current limiter for medium-voltage systems, in Applied physical change in the structure of the network. Power Electronics Conference and Exposition, vol. 3. IEEE APEC, 2004, pp VII. REFERENCES [1] P. G. S. et al., The utility requirements of a fault current limiter, IEEE Transactions on Power Delivery, vol. 7, no. 3, pp , Apr [2] J. F. Amon, P. C. Fernandez, E. H. Rose, A. D Ajuz and A. Castanheira, Brazilian Successful Experience in the Usage of Current Limiting Reactors for Short-Circuit Limitation, International Conference on Power Systems Transients (IPST 05), Montreal, June 2005, pp [3] W. Paul and M. Chen, Superconducting control for surge currents, IEEE Spectrum, pp , May [4] B. W. Lee, J. Sim, K. B. Park and I. S. Oh, Practical Application Issues of Superconducting Fault Current Limiters for Electric Power Systems, IEEE Transactions on Applied Superconductivity, Vol. 18, No. 2, 2008, pp [5] D. Fedasyuk, P. Serdyuk, Y. Semchyshyn and Lviv Polytechnic National University, Resistive Superconducting Fault Current Limiter Simulation and Design, 15th International Conference, Poznan, June 2008, pp [6] Principles of Fault Current Limitation by a Resonant LC Circuit, vol IEE, Jan [7] C. S. Chang and P. C. Loh, Designs synthesis of resonant fault current limiter for voltage sag mitigation and current [10] IEC Short-Circuit Currents in Three-phase a.c. systems - Part 0: Calculation of Currents (including 2002 corrigendum 1) for systems up to 500kV. [11] IEC Short-circuit currents in three-phase a.c. systems - Part 1: Factors for the calculation of short-circuit currents according to IEC [12] IEC Electrical equipment - Data for short-circuit current calculations in accordance with IEC 909 (1988) [13] IEC Short-circuit currents in three-phase a.c. systems Part 4: Examples for the calculation of short-circuit currents [14] De Kock, Jan; Strauss, Cobus (2004). Practical Power Distribution for Industry. Elsevier. pp ISBN [15] Deb, Anjan K. Power Line Ampacity System. CRC Press. pp ISBN [16] Song, Y.H., Johns, A.T. Flexible ac transmission systems. IEE. ISBN [17] Hingorani, N.G. & Gyugyi, L. Understanding FACTS - Concepts and Technology of Flexible AC Transmission Systems. IEEE. ISBN Reference Number: JO-P

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453 www.ijecs.in International Journal Of Engineering And Computer Science ISSN:2319-7242 Volume 3 Issue 6 June, 2014 Page No. 6453-6457 Role of Fault Current Limiter in Power System Network Poornima G P.1,

More information

Investigation of D-Statcom Operation in Electric Distribution System

Investigation of D-Statcom Operation in Electric Distribution System J. Basic. Appl. Sci. Res., (2)29-297, 2 2, TextRoad Publication ISSN 29-434 Journal of Basic and Applied Scientific Research www.textroad.com Investigation of D-Statcom Operation in Electric Distribution

More information

Power Quality enhancement of a distribution line with DSTATCOM

Power Quality enhancement of a distribution line with DSTATCOM ower Quality enhancement of a distribution line with DSTATCOM Divya arashar 1 Department of Electrical Engineering BSACET Mathura INDIA Aseem Chandel 2 SMIEEE,Deepak arashar 3 Department of Electrical

More information

Protection from Voltage Sags and Swells by Using FACTS Controller

Protection from Voltage Sags and Swells by Using FACTS Controller Protection from Voltage Sags and Swells by Using FACTS Controller M.R.Mohanraj 1, V.P.Suresh 2, G.Syed Zabiyullah 3 Assistant Professor, Department of Electrical and Electronics Engineering, Excel College

More information

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator Ishwar Lal Yadav Department of Electrical Engineering Rungta College of Engineering and Technology Bhilai, India

More information

FACTS devices in Distributed Generation

FACTS devices in Distributed Generation FACTS devices in Distributed Generation 1 K. B. MOHD. UMAR ANSARI, 2 SATYENDRA VISHWAKARMA, 3 GOLDY SHARMA 1, 2, 3 M.Tech (Electrical Power & Energy Systems), Department of Electrical & Electronics Engineering,

More information

Impact of Distributed Generation on Network Voltage Levels

Impact of Distributed Generation on Network Voltage Levels EEE8052 Distributed Generation Taster Material Impact of Distributed Generation on Network Voltage Levels Steady-state rise in network voltage levels Existing practice is to control distribution voltage

More information

Past CIGRE and Emerging IEEE Guide Documents on FCLs

Past CIGRE and Emerging IEEE Guide Documents on FCLs Past CIGRE and Emerging IEEE Guide Documents on FCLs Michael Mischa Steurer Leader Power Systems Research Group at FSU-CAPS Email: steurer@caps.fsu.edu, phone: 850-644-1629 Presented by W. Hassenzahl Advanced

More information

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems T. C. Dias, B. D. Bonatto, J. M. C. Filho Abstract-- Isolated industrial power systems or with high selfgeneration,

More information

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control Spring 2014 Instructor: Kai Sun 1 References Saadat s Chapters 12.6 ~12.7 Kundur s Sections

More information

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages Waruna Chandrasena, Bruno Bisewski, and Jeff Carrara Abstract-- This paper describes several system

More information

Performance Improvement of Power System Using Static Synchronous Compensator (STATCOM) Priya Naikwad, Mayuri Kalmegh, Poonam Bhonge

Performance Improvement of Power System Using Static Synchronous Compensator (STATCOM) Priya Naikwad, Mayuri Kalmegh, Poonam Bhonge 2017 IJSRST Volume 3 Issue 2 Print ISSN: 235-6011 Online ISSN: 235-602X National Conference on Advances in Engineering and Applied Science (NCAEAS) 16 th February 2017 In association with International

More information

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India Abstract: The objective of this research is to develop a novel voltage control scheme that

More information

I. INTRODUCTION IJSRST Volume 3 Issue 2 Print ISSN: Online ISSN: X

I. INTRODUCTION IJSRST Volume 3 Issue 2 Print ISSN: Online ISSN: X 2017 IJSRST Volume 3 Issue 2 Print ISSN: 2395-6011 Online ISSN: 2395-602X National Conference on Advances in Engineering and Applied Science (NCAEAS) 16 th February 2017 In association with International

More information

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults Enhancement of Power Quality in Distribution System Using D-Statcom for Different s Dr. B. Sure Kumar 1, B. Shravanya 2 1 Assistant Professor, CBIT, HYD 2 M.E (P.S & P.E), CBIT, HYD Abstract: The main

More information

Power Quality Improvement using Hysteresis Voltage Control of DVR

Power Quality Improvement using Hysteresis Voltage Control of DVR Power Quality Improvement using Hysteresis Voltage Control of DVR J Sivasankari 1, U.Shyamala 2, M.Vigneshwaran 3 P.G Scholar, Dept of EEE, M.Kumarasamy college of Engineering, Karur, Tamilnadu, India

More information

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India e t International Journal on Emerging Technologies 4(1): 10-16(2013) ISSN No. (Print) : 0975-8364 ISSN No. (Online) : 2249-3255 Control of Synchronous Generator Excitation and Rotor Angle Stability by

More information

ESB National Grid Transmission Planning Criteria

ESB National Grid Transmission Planning Criteria ESB National Grid Transmission Planning Criteria 1 General Principles 1.1 Objective The specific function of transmission planning is to ensure the co-ordinated development of a reliable, efficient, and

More information

Brief Study on TSCS, SSSC, SVC Facts Device

Brief Study on TSCS, SSSC, SVC Facts Device Brief Study on TSCS, SSSC, SVC Facts Device Ramesh Kumari, Parveen M.Tech. Student, Department of EEE, Mata Rajkaur Institute of Engineering & technology, Rewari, Haryana, India Asst. Professor, Department

More information

Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer

Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer Deepa Francis Dept. of Electrical and Electronics Engineering, St. Joseph s College of Engineering and Technology, Palai Kerala, India-686579

More information

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping P. Mestas, M. C. Tavares Abstract. The optimization of the grounding neutral reactor is a common practice

More information

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM N.Shakeela Begum M.Tech Student P.V.K.K Institute of Technology. Abstract This paper presents a modified instantaneous

More information

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1 Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load MADHYAMA V. WANKHEDE Department Of Electrical Engineering G. H. Raisoni College of

More information

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation Course ELEC0014 - Introduction to electric power and energy systems Additional exercises with answers December 2017 Exercise A1 Consider the system represented in the figure below. The four transmission

More information

Designing Of Distributed Power-Flow Controller

Designing Of Distributed Power-Flow Controller IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) ISSN: 2278-1676 Volume 2, Issue 5 (Sep-Oct. 2012), PP 01-09 Designing Of Distributed Power-Flow Controller 1 R. Lokeswar Reddy (M.Tech),

More information

PERFORMANCE ANALYSIS OF SURGE CURRENT PROTECTION USING SUPERCONDUCTORS

PERFORMANCE ANALYSIS OF SURGE CURRENT PROTECTION USING SUPERCONDUCTORS PERFORMANCE ANALYSIS OF SURGE CURRENT PROTECTION USING SUPERCONDUCTORS Engr. Makinde K Department Of Electrical Engineering Federal Polytechnic Bida, Niger State Dr. Enemuoh F. O Department Of Electrical

More information

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR) Mr. A. S. Patil Mr. S. K. Patil Department of Electrical Engg. Department of Electrical Engg. I. C. R. E. Gargoti I. C. R. E. Gargoti

More information

A NOVEL APPROACH ON INSTANTANEOUS POWER CONTROL OF D-STATCOM WITH CONSIDERATION OF POWER FACTOR CORRECTION

A NOVEL APPROACH ON INSTANTANEOUS POWER CONTROL OF D-STATCOM WITH CONSIDERATION OF POWER FACTOR CORRECTION IMPACT: International Journal of Research in Engineering & Technology (IMPACT: IJRET) ISSN(E): 2321-8843; ISSN(P): 2347-4599 Vol. 2, Issue 7, Jul 2014, 13-18 Impact Journals A NOVEL APPROACH ON INSTANTANEOUS

More information

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics EE589-Power System Quality & Harmonics Electrical Engineering Department School of Engineering University of Jordan 1 Control of Harmonics

More information

A Case Study of Resonance in 11kV Network in the Presence of Series Current Limiting Reactors, VSDs and Power Factor Improvement Capacitors

A Case Study of Resonance in 11kV Network in the Presence of Series Current Limiting Reactors, VSDs and Power Factor Improvement Capacitors International Journal of Electrical Energy, Vol. 2, No., December 201 A Case Study of Resonance in 11kV Network in the Presence of Series Limiting s, VSDs and Power Factor Improvement s Yadavalli Venkata

More information

FAULT CURRENT LIMITERS PRINCIPLES AND APPLICATION

FAULT CURRENT LIMITERS PRINCIPLES AND APPLICATION FAULT CURRENT LIMITERS PRINCIPLES AND APPLICATION Georgi GANEV 1, Krastjo HINOV 2, Nikolay KARADZHOV 3 1 TU Sofia, branch Plovdiv, e-mail: gganev@tu-plovdiv.bg 2 TU Sofia, e-mail: k_hinov@yahoo.co.uk 3

More information

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR) Research Journal of Engineering Sciences ISSN 2278 9472 Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR) Abstract Srishti Verma * and Anupama Huddar Electrical Engineering

More information

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM

EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM EARTH FAULT PROTECTION VIS-A-VIS GENERATOR GROUNDING SYSTEM BY MR. H. C. MEHTA AT 1 ST INDIA DOBLE PROTECTION AND AUTOMATION CONFERENCE, NOV 2008 POWER-LINKER Wisdom is not Virtue but Necessity hcmehta@powerlinker.org

More information

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss Siemens AG, EV NP3 P.O. Box 3220 91050 Erlangen, Germany e-mail: Michael.Weinhold@erls04.siemens.de

More information

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP Kiran V. Natkar 1, Naveen Kumar 2 1 Student, M.E., Electrical Power System, MSS CET/ Dr. B.A.M. University, (India) 2 Electrical Power System,

More information

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle Jules Esztergalyos, Senior Member, IEEE Abstract--The measuring technique described in this paper is based on Electro Magnetic

More information

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE Ms. K. Kamaladevi 1, N. Mohan Murali Krishna 2 1 Asst. Professor, Department of EEE, 2 PG Scholar, Department of

More information

ISSN Vol.07,Issue.21, December-2015, Pages:

ISSN Vol.07,Issue.21, December-2015, Pages: ISSN 2348 2370 Vol.07,Issue.21, December-2015, Pages:4128-4132 www.ijatir.org Mitigation of Multi Sag/Swell using DVR with Hysteresis Voltage Control DAKOJU H V V S S N MURTHY 1, V. KAMARAJU 2 1 PG Scholar,

More information

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme

Transient stability improvement by using shunt FACT device (STATCOM) with Reference Voltage Compensation (RVC) control scheme I J E E E C International Journal of Electrical, Electronics ISSN No. (Online) : 2277-2626 and Computer Engineering 2(1): 7-12(2013) Transient stability improvement by using shunt FACT device (STATCOM)

More information

SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER

SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER S. Tara Kalyani 1 and G. Tulasiram Das 1 1 Department of Electrical Engineering, Jawaharlal Nehru Technological University, Hyderabad,

More information

International Journal of Advance Engineering and Research Development. Short-circuit analysis of Industrial plant

International Journal of Advance Engineering and Research Development. Short-circuit analysis of Industrial plant Scientific Journal of Impact Factor (SJIF): 5.71 International Journal of Advance Engineering and Research Development Volume 5, Issue 03, March -2018 Short-circuit analysis of Industrial plant Ashokkumar

More information

Analysis of Transient Recovery Voltage in Transmission Lines Compsensated with Tpcs-tcsc Considering Accurate Model of Transformer & Generator

Analysis of Transient Recovery Voltage in Transmission Lines Compsensated with Tpcs-tcsc Considering Accurate Model of Transformer & Generator Australian Journal of Basic and Applied Sciences, 5(5): 816-824, 2011 ISSN 1991-8178 Analysis of Transient Recovery Voltage in Transmission Lines Compsensated with Tpcs-tcsc Considering Accurate Model

More information

In power system, transients have bad impact on its

In power system, transients have bad impact on its Analysis and Mitigation of Shunt Capacitor Bank Switching Transients on 132 kv Grid Station, Qasimabad Hyderabad SUNNY KATYARA*, ASHFAQUE AHMED HASHMANI**, AND BHAWANI SHANKAR CHOWDHRY*** RECEIVED ON 1811.2014

More information

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions Ferroresonance Conditions Associated With a Voltage Regulator During Back-feed Conditions D. Shoup, J. Paserba, A. Mannarino Abstract-- This paper describes ferroresonance conditions for a feeder circuit

More information

Power Quality and the Need for Compensation

Power Quality and the Need for Compensation Power Quality and the Need for Compensation Risha Dastagir 1, Prof. Manish Khemariya 2, Prof. Vivek Rai 3 1 Research Scholar, 2,3 Asst. Professor, Lakshmi Narain College of Technology Bhopal, India Abstract

More information

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India) ISSN: 2349-7637 (Online) RESEARCH HUB International Multidisciplinary Research Journal (RHIMRJ) Research Paper Available online at: www.rhimrj.com Modeling and Simulation of Distribution STATCOM Bhavin

More information

Wind Power Facility Technical Requirements CHANGE HISTORY

Wind Power Facility Technical Requirements CHANGE HISTORY CHANGE HISTORY DATE VERSION DETAIL CHANGED BY November 15, 2004 Page 2 of 24 TABLE OF CONTENTS LIST OF TABLES...5 LIST OF FIGURES...5 1.0 INTRODUCTION...6 1.1 Purpose of the Wind Power Facility Technical

More information

The Influence of Thyristor Controlled Phase Shifting Transformer on Balance Fault Analysis

The Influence of Thyristor Controlled Phase Shifting Transformer on Balance Fault Analysis Vol.2, Issue.4, July-Aug. 2012 pp-2472-2476 ISSN: 2249-6645 The Influence of Thyristor Controlled Phase Shifting Transformer on Balance Fault Analysis Pratik Biswas (Department of Electrical Engineering,

More information

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) VOL. 4, NO. 4, JUNE 9 ISSN 89-668 6-9 Asian Research Publishing Network (ARPN). All rights reserved. MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR) Rosli Omar and Nasrudin Abd Rahim

More information

Analysis of a 405 km transmission line with series compensation

Analysis of a 405 km transmission line with series compensation Analysis of a 405 km transmission line with series compensation by Dr. Rupert Gouws, North-West University This paper presents an investigative case study and energy efficiency analysis of the 405 km,

More information

Design and Control of Small Scale Laboratory Model of a Thyristor Controlled Series Capacitor (TCSC) to Improve System Stability

Design and Control of Small Scale Laboratory Model of a Thyristor Controlled Series Capacitor (TCSC) to Improve System Stability International Journal of Scientific & Engineering Research Volume 3, Issue 5, May-2012 1 Design and Control of Small Scale Laboratory Model of a Thyristor Controlled Series Capacitor (TCSC) to Improve

More information

Power Control Scheme of D-Statcom

Power Control Scheme of D-Statcom ISSN : 48-96, Vol. 4, Issue 6( Version 3), June 04, pp.37-4 RESEARCH ARTICLE OPEN ACCESS Power Control Scheme of D-Statcom A. Sai Krishna, Y. Suri Babu (M. Tech (PS)) Dept of EEE, R.V.R. & J.C. College

More information

Application of SVCs to Satisfy Reactive Power Needs of Power Systems

Application of SVCs to Satisfy Reactive Power Needs of Power Systems 1 Application of SVCs to Satisfy Reactive Power Needs of Power Systems H. K. Tyll, Senior Member, IEEE Abstract In the early days of power transmission problems like voltage deviation during load changes

More information

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY A PATH FOR HORIZING YOUR INNOVATIVE WORK SPECIAL ISSUE FOR NATIONAL LEVEL CONFERENCE "Technology Enabling Modernization

More information

An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays

An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third Zone of Distance Relays An Enhanced Adaptive Algorithm to Mitigate Mis-coordination Problem of the Third one of Distance Relays M. Azari, M. Ojaghi and K. Mazlumi* Electrical Engineering Department University of anjan anjan,

More information

Distribution System Development & Preliminary Studies

Distribution System Development & Preliminary Studies Distribution System Development & Preliminary Studies IEEE CED January 27, 2016 (second night) 2016 KBR, Inc. All Rights Reserved. Agenda Distribution System Development Modeling Data Studies Overview

More information

Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation

Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation RESEARCH ARTICLE OPEN ACCESS Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation * G.Ravinder Reddy Assistant Professor,**M.Thirupathaiah * Assistant Professor. (Deparment of Electrical

More information

Impact of Thyristor Controlled Series Capacitor on Voltage Profile of Transmission Lines using PSAT

Impact of Thyristor Controlled Series Capacitor on Voltage Profile of Transmission Lines using PSAT Impact of Thyristor Controlled Series Capacitor on Voltage Profile of Transmission Lines using PSAT Babar Noor 1, Muhammad Aamir Aman 1, Murad Ali 1, Sanaullah Ahmad 1, Fazal Wahab Karam. 2 Electrical

More information

Chapter # : 17 Symmetrical Fault Calculations

Chapter # : 17 Symmetrical Fault Calculations Chapter # : 17 Symmetrical Fault Calculations Introduction Most of the faults on the power system lead to a short-circuit condition. The short circuit current flows through the equipment, causing considerable

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

HARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus

HARMONIC distortion complicates the computation of. The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus 1592 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 20, NO. 2, APRIL 2005 The Optimal Passive Filters to Minimize Voltage Harmonic Distortion at a Load Bus Ahmed Faheem Zobaa, Senior Member, IEEE Abstract A

More information

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller Phanikumar.Ch, M.Tech Dept of Electrical and Electronics Engineering Bapatla Engineering College, Bapatla,

More information

EH2741 Communication and Control in Electric Power Systems Lecture 2

EH2741 Communication and Control in Electric Power Systems Lecture 2 KTH ROYAL INSTITUTE OF TECHNOLOGY EH2741 Communication and Control in Electric Power Systems Lecture 2 Lars Nordström larsno@kth.se Course map Outline Transmission Grids vs Distribution grids Primary Equipment

More information

Performance of DVR & Distribution STATCOM in Power Systems

Performance of DVR & Distribution STATCOM in Power Systems International Journal on Recent and Innovation Trends in Computing and Communication ISSN: 232-869 Volume: 3 Issue: 2 83 89 Performance of DVR & Distribution STATCOM in Power Systems Akil Ahemad Electrical

More information

Modelling of Four Switch Buck Boost Dynamic Capacitor

Modelling of Four Switch Buck Boost Dynamic Capacitor Modelling of Four Switch Buck Boost Dynamic Capacitor Mudit Gupta PG Scholar, Department of Electrical Engineering Scope College of Engineering Bhopal, India N. K Singh Head of Department ( Electrical

More information

ELEMENTS OF FACTS CONTROLLERS

ELEMENTS OF FACTS CONTROLLERS 1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are

More information

Performance Analysis of Various Types of Fault Current Limiters Using PSCAD

Performance Analysis of Various Types of Fault Current Limiters Using PSCAD Performance Analysis of Various Types of Fault Current Limiters Using PSCAD Anurag.G 1, Sudhagar.V 2 PG student,[pse] Dept. of EEE, Valliammai Engineering College, Chennai, Tamilnadu, India 1 Assistant

More information

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

thepower to protect  the power to protect i-gard LITERATURE Low and medium voltage thepower to protect i-gard LITERATURE Low and medium voltage distribution systems Arc Flash Hazards and High Resistance Grounding Grounding of Standby and Emergency Power Systems Neutral Grounding Resistors

More information

II. RESEARCH METHODOLOGY

II. RESEARCH METHODOLOGY Comparison of thyristor controlled series capacitor and discrete PWM generator six pulses in the reduction of voltage sag Manisha Chadar Electrical Engineering Department, Jabalpur Engineering College

More information

Optimal Allocation of TCSC Devices Using Genetic Algorithms

Optimal Allocation of TCSC Devices Using Genetic Algorithms Proceedings of the 14 th International Middle East Power Systems Conference (MEPCON 10), Cairo University, Egypt, December 19-21, 2010, Paper ID 195. Optimal Allocation of TCSC Devices Using Genetic Algorithms

More information

Address for Correspondence

Address for Correspondence Research Paper COMPENSATION BY TCSC IN OPEN LOOP CONTROL SYSTEM 1* Sunita Tiwari, S.P. Shukla Address for Correspondence 1* Sr. Lecturer, Polytechnic,Durg Professor, Bhilai Institute of Technology, Durg

More information

Modeling and Analysis of DPFC to Improve Power Quality

Modeling and Analysis of DPFC to Improve Power Quality Modeling and Analysis of DPFC to Improve Power Quality Ishwar K. Charawande 1, S.S. Dhamse 2 P.G. Student, Department of Electrical Engineering, Government College of Engineering, Aurangabad, Maharashtra,

More information

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: ; e-issn:

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER  CSEA2012 ISSN: ; e-issn: POWER FLOW CONTROL BY USING OPTIMAL LOCATION OF STATCOM S.B. ARUNA Assistant Professor, Dept. of EEE, Sree Vidyanikethan Engineering College, Tirupati aruna_ee@hotmail.com 305 ABSTRACT In present scenario,

More information

Chapter 10: Compensation of Power Transmission Systems

Chapter 10: Compensation of Power Transmission Systems Chapter 10: Compensation of Power Transmission Systems Introduction The two major problems that the modern power systems are facing are voltage and angle stabilities. There are various approaches to overcome

More information

FAULT CURRENT LIMITER IN SINGLE PHASE AND THREE PHASE LINES FOR COMPENSATING VOLTAGE SAG

FAULT CURRENT LIMITER IN SINGLE PHASE AND THREE PHASE LINES FOR COMPENSATING VOLTAGE SAG FAULT CURRENT LIMITER IN SINGLE PHASE AND THREE PHASE LINES FOR COMPENSATING VOLTAGE SAG B. Navya Sree 1, K.Sudha 2, U. Madhuri 3 1 Asst. Professor, Department of Electrical and Electronics Engineering,

More information

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 9, Issue 3 Ver. I (May Jun. 2014), PP 36-41 Analysis, Modeling and Simulation of Dynamic Voltage

More information

Power Quality Improvement in Distribution System Using D-STATCOM

Power Quality Improvement in Distribution System Using D-STATCOM Power Quality Improvement in Distribution System Using D-STATCOM 1 K.L.Sireesha, 2 K.Bhushana Kumar 1 K L University, AP, India 2 Sasi Institute of Technology, Tadepalligudem, AP, India Abstract This paper

More information

ISSN Vol.03,Issue.11, December-2015, Pages:

ISSN Vol.03,Issue.11, December-2015, Pages: WWW.IJITECH.ORG ISSN 2321-8665 Vol.03,Issue.11, December-2015, Pages:2020-2026 Power Quality Improvement using BESS Based Dynamic Voltage Restorer B. ABHINETHRI 1, K. SABITHA 2 1 PG Scholar, Dr. K.V. Subba

More information

Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis

Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis Thyristor Based Static Transfer Switch: Theory, Modeling and Analysis M. N. Moschakis* N. D. Hatziargyriou National Technical University of Athens Department of Electrical and Computer Engineering 9, Iroon

More information

Long lasting transients in power filter circuits

Long lasting transients in power filter circuits Computer Applications in Electrical Engineering Vol. 12 2014 Long lasting transients in power filter circuits Jurij Warecki, Michał Gajdzica AGH University of Science and Technology 30-059 Kraków, Al.

More information

Volume I Issue VI 2012 September-2012 ISSN

Volume I Issue VI 2012 September-2012 ISSN A 24-pulse STATCOM Simulation model to improve voltage sag due to starting of 1 HP Induction-Motor Mr. Ajay Kumar Bansal 1 Mr. Govind Lal Suthar 2 Mr. Rohan Sharma 3 1 Associate Professor, Department of

More information

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar Electrical Engineering department, Jabalpur Engineering College Jabalpur, India Abstract:

More information

FERRORESONANCE SIMULATION STUDIES USING EMTP

FERRORESONANCE SIMULATION STUDIES USING EMTP FERRORESONANCE SIMULATION STUDIES USING EMTP Jaya Bharati, R. S. Gorayan Department of Electrical Engineering Institute of Technology, BHU Varanasi, India jbharatiele@gmail.com, rsgorayan.eee@itbhu.ac.in

More information

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 84 CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS 4.1 INTRODUCTION Now a days, the growth of digital economy implies a widespread use of electronic equipment not only in the industrial

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

A Review on Mid-point Compensation of a Two-machine System Using STATCOM

A Review on Mid-point Compensation of a Two-machine System Using STATCOM Volume-4, Issue-2, April-2014, ISSN No.: 2250-0758 International Journal of Engineering and Management Research Available at: www.ijemr.net Page Number: 109-115 A Review on Mid-point Compensation of a

More information

MITIGATION OF VOLTAGE SAG AND SWELL FOR POWER QUALITY IMPROVEMENT USING DISTRIBUTED POWER FLOW CONTROLLER

MITIGATION OF VOLTAGE SAG AND SWELL FOR POWER QUALITY IMPROVEMENT USING DISTRIBUTED POWER FLOW CONTROLLER MITIGATION OF VOLTAGE SAG AND SWELL FOR POWER QUALITY IMPROVEMENT USING DISTRIBUTED POWER FLOW CONTROLLER Sai Lakshmi K Department of Electrical and Electronics engineering, G.Narayanamma Institute of

More information

AORC Technical meeting 2014

AORC Technical meeting 2014 http : //www.cigre.org B4-112 AORC Technical meeting 214 HVDC Circuit Breakers for HVDC Grid Applications K. Tahata, S. Ka, S. Tokoyoda, K. Kamei, K. Kikuchi, D. Yoshida, Y. Kono, R. Yamamoto, H. Ito Mitsubishi

More information

Improving the Power Factor Correction in the Presence of Harmonics by Reducing the Effect of Resonance and Harmonics

Improving the Power Factor Correction in the Presence of Harmonics by Reducing the Effect of Resonance and Harmonics Indonesian Journal of Electrical Engineering and Computer Science Vol. 3, No. 2, August 2016, pp. 282 ~ 295 DOI: 10.11591/ijeecs.v3.i2.pp282-295 282 Improving the Power Factor Correction in the Presence

More information

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8]

3. (a) List out the advantages and disadvantages of HRC fuse (b) Explain fuse Characteristics in detail. [8+8] Code No: RR320205 Set No. 1 1. (a) Explain about Bewley s Lattice diagrams and also mention the uses of these diagrams. [6+2] (b) A line of surge impedance of 400 ohms is charged from a battery of constant

More information

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads Ponananthi.V, Rajesh Kumar. B Final year PG student, Department of Power Systems Engineering, M.Kumarasamy College of

More information

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 86 CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS 5.1 POWER QUALITY IMPROVEMENT This chapter deals with the harmonic elimination in Power System by adopting various methods. Due to the

More information

Analysis of FACTS Devices in Transmission System

Analysis of FACTS Devices in Transmission System Volume 02 - Issue 02 February 2017 PP. 22-27 Analysis of FACTS Devices in Transmission System Anand K. Singh, Harshad M. Mummadwar PG Scholar-Electrical Engineering (IPS)-DMIETR-Wardha, PG Scholar-Electrical

More information

Harmonic Study in Low Voltage Distribution Network in a Real Time Foundry Industry

Harmonic Study in Low Voltage Distribution Network in a Real Time Foundry Industry I J C T A, 9(37) 2016, pp. 769-781 International Science Press Harmonic Study in Low Voltage Distribution Network in a Real Time Foundry Industry D. Ravichandran * and Er. R. Panneerselvam ** Abstract:

More information

Power Quality Basics. Presented by. Scott Peele PE

Power Quality Basics. Presented by. Scott Peele PE Power Quality Basics Presented by Scott Peele PE PQ Basics Terms and Definitions Surge, Sag, Swell, Momentary, etc. Measurements Causes of Events Possible Mitigation PQ Tool Questions Power Quality Measurement

More information

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 % BE Semester- V (Electrical Engineering) Question Bank (E 605 ELECTRCAL POWER SYSTEM - ) All questions carry equal marks (10 marks) Q.1 Explain per unit system in context with three-phase power system and

More information

Interline Power Flow Controller: Review Paper

Interline Power Flow Controller: Review Paper Vol. (0) No. 3, pp. 550-554 ISSN 078-365 Interline Power Flow Controller: Review Paper Akhilesh A. Nimje, Chinmoy Kumar Panigrahi, Ajaya Kumar Mohanty Abstract The Interline Power Flow Controller (IPFC)

More information

factors that can be affecting the performance of a electrical power transmission system. Main problems which cause instability to a power system is vo

factors that can be affecting the performance of a electrical power transmission system. Main problems which cause instability to a power system is vo 2011 International Conference on Signal, Image Processing and Applications With workshop of ICEEA 2011 IPCSIT vol.21 (2011) (2011) IACSIT Press, Singapore Location of FACTS devices for Real and Reactive

More information

Design and Simulation of Passive Filter

Design and Simulation of Passive Filter Chapter 3 Design and Simulation of Passive Filter 3.1 Introduction Passive LC filters are conventionally used to suppress the harmonic distortion in power system. In general they consist of various shunt

More information

Overview of Actuation Thrust

Overview of Actuation Thrust Overview of Actuation Thrust Fred Wang Thrust Leader, UTK Professor Prepared for CURENT Course September 4, 2013 Actuation in CURENT Wide Area Control of Power Power Grid Grid Measurement &Monitoring HVDC

More information