Protection and control. Sepam range Sepam 2000 Testing
|
|
- Dayna Pierce
- 5 years ago
- Views:
Transcription
1 Protection and control Sepam range Sepam Testing
2 Contents chapter/page Sepam tests protection function tests / to /5 testing equipment, test wiring diagram / to /8 commissioning tests /9 test and setting record sheets / to /4 Sepam - Testing
3 Sepam tests When commissioning Sepam, it is not necessary to test the metering and protection functions individually. Sepam has been designed and developed to provide the following functions: c protection, c metering, c program logic. Each of the functions has been fully tested. In addition, Sepam has a highly efficient self-testing system which continuously checks function integrity (e.g. no settings outside the tolerance range, etc.). The product is ready to use, which simplifies commissioning. By simply testing a function, the user is assured of overall device operation, provided the device has been correctly installed. It is therefore sufficient to check that Sepam has been installed properly. The following are checked: c parameter setting, c current and voltage sensor connections, c switchgear control and annunciation connections. The chapter entitled commissioning tests describes the simple, exhaustive method that is applied for checking. Individual testing of each protection and control function is no longer essential. However, should the testing of a function prove to be necessary, please refer to the section entitled function tests. Sepam - Testing
4 Protection function tests Content NSI code chapter/page protection function tests / introduction / measurement and testing method / 5-5 phase overcurrent protection /4 5V-5V voltage restrained overcurrent protection /7 5N-5N earth fault protection /9 5-5 percentage-based single-phase overcurrent / 67 directional overcurrent protection / 67N directional earth fault protection /4 67NC directional earth fault protection for compensated /6 networks 49 thermal overload protection /8 5G-5G sensitive earth fault protection /5 46 negative sequence / unbalance /6 66 starts per hour /8 5LR excessive starting time and locked rotor protection / 7 phase undercurrent protection / 7 phase-to-phase undervoltage protection / 7R remanent undervoltage protection / 7D - 47 positive sequence undervoltage and phase /4 rotation direction check protection 59 phase-to-phase overvoltage protection /5 59N neutral voltage displacement protection /6 8L underfrequency protection /8 8H overfrequency protection /9 8R rate of change of frequency protection /4 7P under power protection /4 P real overpower protection /4 Q reactive overpower protection /45 49T - 8 temperature monitoring by PT RTD /47 87M-87G motor/generator differential protection /49 47 negative sequence overvoltage /5 64REF restricted earth fault protection /5 5 synchronism check /5 5BF-6 protection against circuit breaker faults /54 Sepam - Testing /
5 Introduction This chapter describes the procedures used to test the protection functions that are available in the Sepam range. The tests call for: c knowledge of how to use Sepam c a set of testing equipment c a TSM pocket terminal or a PC microcomputer which includes the SFT 8 PC software package c documentation The tests that are described relate to the method referred to as the "current and voltage sensor secondary injection" method. In the rest of the document, "pocket terminal" refers to: c the TSM pocket terminal, c a computer which includes the SFT 8 PC software package. / Sepam - Testing
6 Measurement and testing method General information Each protection function may be activated individually by disabling the set points of the other functions. ctivating and de-activating functions does not disturb function operation in any way. Most of the tests may be performed using a Single-Phase injection unit, with the exception of phase rotation checking. Three-phase injection is recommended for checking certain functions, in particular: c earth fault current measured by the sum of the CTs, c neutral voltage displacement measured by the sum of the VTs, c positive sequence undervoltage and phase rotation, c directional overcurrent. Terminal boxes (type "Entrelec", "Secura", etc ) are generally used for testing in LV cubicles, which means that it is not necessary to disconnect any existing wiring connections. Checks c prior to energizing Check: v auxiliary voltages of Sepam and ESB, ESTOR modules, v coherency between the cartridge and Sepam labels (model, type), v module insertion and presence of DPC straps, v setting of microswitches on the ECM, U/Vo and EC modules, v connection of the core balance CT (P-P and S-S directions), v wiring of currents and voltages (rotation and matching), v wiring and polarization of the required inputs and ouputs. c after energizing v set the parameters under the status heading, v set () the time delays required by the automation systems (T, T etc ), the parameters values (KPxx), v in the case of customized program logic: check that the protection contacts (FXXX/X) to be tested, as well as the output relays associated with the protections, are being used. c prior to injection v set the values of the protections to be tested, v disable the set points of other protections that are liable to interfere with testing. Please note: Remember to re-activate the protections at the end of testing (protections are generally disabled by setting to 999, k, kv, etc ). c tolerance ranges and injection limits v current: - minimum.5% of CT In (5 m or 75 m) (), - maximum times steady state In ( or 5 ) (), 4 times In for s (4 or ) (), - 5 Hz (±%); v voltage: - minimum.5% of Un (.86% of Vn) i.e..5 V for V (), - maximum 5% of Un, - 5 Hz (±%). Remarks: In order to simplify the presentation of examples, injection current values are given in primary amperes (like Sepam measurements). When the current injection unit is equipped with electronic ON/OFF controls, check that current is zero in the automatic OFF position (since the static contactor may allow more than 5% of the current to flow through, depending on the position of the cursor). When the starts per hour protection is being tested, in particular, the current broken should be less than 5% of Ib. () in the case of standard logic, refer to the control and monitoring function manuals () to the position corresponding to or 5 according to the microswitch setting () according to SM pocket terminal setting of the value (Uns) of the VT secondary circuit Un : phase-to-phase voltage Vn : phase voltage In : rated current on CT primary Ib : exact load current (manufacturer data) Sepam - Testing /
7 Phase overcurrent protection NSI Code 5-5 function n FX for phase I overcurrent protection X 6 FY for phase I' overcurrent protection Y Equipment c single-phase or three-phase current generator c ammeters c adapter for EC module c chronometer c documentation Injection unit wiring c diagram B or B or B8 c protection relays: F/, F/ F/, F/ F/, F/ F/, F/ F/, F/ F4/, F4/ F5/, F5/ F6/, F6/ Procedure c protection parameter setting: O/C X or frame leak v select the curve v set Is to the desired value v set T to the desired value v disable the following protections () : unbalance; the other O/C protections, E/F (if CT sum is used) Checking of definite time Is set point t T Test Is I c read the section entitled measurement and testing method This protection is three-phase and may be tested on each phase individually with single-phase current. c status parameter setting v select the value of the CT primary circuits v check the microswitches ( or 5) which correspond to the CT secondary circuits v or check and set the microswitches on the EC module. c protection parameter setting v select the definite curve v set T to.5 s (for immediate pick-up of the output relay) c test v gradually inject the current or currents until the output relay linked to the protection in program logic picks up v read the Is current value on the ammeter v check the meter and the I TRIP () values on the display unit or pocket terminal v stop the injection v press reset () on the Sepam to erase the messages and reset the output relay Checking of the definite time set point and time delay c protection parameter setting: O/C X v set T to the desired value v prepare the injection with twice the value of Is v set the chronometer to zero c test v start up injection and the chronometer at the same time v Sepam's output relay stops the chronometer v read the value T measured by the chronometer () this function may only be activated if your program logic has been customized. () remember to reactivate the protections at the end of testing. X = number of the protective relay. /4 Sepam - Testing
8 Checking of IDMT set point and time delay The set point and time delay are interrelated. They correspond to curve coordinates (see appendices). t t T,Is i Is a time t corresponds to an injected value i. I/Is c protection parameter setting: O/C X v select the standard inverse (SIT), very inverse (VIT), extremely inverse (EIT) or ultra inverse (UIT) curve v set Is (asymptote: for an injection i = Is, so t = infinity) v set T (corresponding to Is: for an injection i = Is, so t = T) v identify on the curve the different coordinates of the points that you will be testing (i and t) c test the different points on the curve v preset the injection i (to a value >. Is) and make a note of the value v stop the injection and reset the chronometer to zero v press reset if required () v start up injection and the chronometer at the same time v check the injection value on the ammeter (stability) v Sepam's output relay stops the chronometer v read the t value measured by the chronometer v compare with the value given in the curve v check the meter and the I TRIP () values on the display unit or pocket terminal v stop the injection v press reset () on Sepam to erase the messages and reset the output relay Example Status In = 4 settings very inverse curve Is = T =.5 s injection i = (.75 or.75 ) In the very inverse column of the chart which gives K for I/Is, read the value K = 8 which corresponds to I/Is =.5 (= /) for an injection i =, the relay will pick up after a time period t = 8 x.5 s = 9 s (t = K x T) (Ib is not used in the O/C protections) () this function may only be activated if your program logic has been customized. X = number of the protective relay. Sepam - Testing /5
9 Phase overcurrent protection (cont'd) K factor chart I/Is inverse (SIT) very inv. (VIT) ext. inv. (EIT) ultra inv. (UIT) I/Is inverse (SIT) very inv. (VIT) ext. inv. (EIT) ultra inv. (UIT) /6 Sepam - Testing
10 Voltage restrained overcurrent protection NSI code 5V-5V function n F9X for voltage-restrained overcurrent protection X FY for voltage-restrained overcurrent protection Y Equipment c single-phase and three-phase current and voltage generators c phase shifter with angle indicator c ammeters c voltmeter c chronometer c calculator c adapter for EC module c documentation Procedure c protection parameter setting: V Rest O/C (refer to the section entitled phase overcurrent) v select the curve (definite or IDMT) v set Is to the desired value v set T to the desired value (Is IDMT) v disable the unbalance protections; O/C X; U U/V X; U U/V; U/C; E/F X (when the sum of CTs is used) t Wiring c B5 or B6 diagram c protective relay: F9/, F9/ F/, F/ Test T,Is I* zone dependent on "u" Is Testing of definite time set points I c read the section entitled measurement and testing method This protection is three-phase and may be tested on each phase individually with single-phase. The set point is adjusted in accordance with the lowest phase-to-phase voltage measured. c checking of the set points for this protection, at rated voltage Uns, is the same as for the phase overcurrent protection test c for voltage lower than Uns, an adjustment factor is used which, when multiplied by the Is set point, gives the new protection activation set point I*. Set point to be tested I* = K.Is or with K = / x (4u / Uns -.) c status parameter setting: enter all data items v Fn network frequency v Unp network phase-to-phase voltage v Uns phase-to-phase voltage of the VT secondary circuits v number of VTs connected ( VT for single-phase testing) v select In the CT primary value v check and set the microswitches on the U/Vo, ECM and EC modules () remember to reactivate the protections at the end of testing. X = number of the protective relay. c parameter setting v set Is to the desired value v set T to.5 s c test v inject "u" = Uns (into U for single-phase injection) v lower one of the voltages and calculate the ratio u/uns v gradually increase the current or currents until the protective relay picks up v read the value I* on the ammeter Testing of definite time delay c parameter setting v inject "u" = Uns (into U for single-phase injection) v set i higher than Is v set T to the desired value c test v set the chronometer to zero v start up the chronometer and injection at the same time v the Sepam relay stops the chronometer v read the value T measured by the chronometer Chart giving the Is set point adjustment factor as a function of the change of voltage. u/uns K u/uns K u/uns K u/uns K < > Sepam - Testing /7
11 Voltage restrained overcurrent protection (cont'd) Testing of IDMT set points For injection voltage u = Uns, testing of the O/C V REST protection is the same as IDMT phase overcurrent testing. t T,Is Is I* Is I c protection parameter setting: V Rest O/C v select the standard inverse, very inverse, extremely inverse or ultra inverse curve v set Is (asymptote: for an injection i = Is, so t = infinity) v set T (corresponding to Is: for an injection i = Is, so t = T) v identify on the curve the different coordinates of the points that you will be testing (i and t) c test the different points on the curve v set and inject voltage u and calculate u/uns v preset the injection i = I* = Is.u/Uns v stop the injection and reset the chronometer to zero v press reset if required () v start up injection and the chronometer at the same time v check the injection value on the ammeter (stability) v Sepam's output relay stops the chronometer v read the value t measured by the chronometer v compare with the value given in the curve and the chart corresponding to I* v check the meter and the I TRIP value on the display unit or pocket terminal () v stop the injection v press reset () on Sepam to erase the messages and reset the output relay Example Status In = Uns = V settings very inverse curve Is = T =.5 s for u = 44 V U Uns = 44 =,44 : k =,5 the new value of I* will therefore be x.5 = 4 Injection i = In the very inverse column of the chart which gives K for i/i*, read the value K = which corresponds to i/i* =.9 (= / (.u/uns)). for an injection i = the relay will pick up after a period of time t = x.5 s = 5 s (t = K x T) () this function may only be activated if your program logic has been customized. /8 Sepam - Testing
12 Earth fault protection NSI code 5N-5N or 5G-5G function n F6X, F8X for earth fault protection Io X 4 F7Y, F9Y for additional earth fault protection Io' Y Equipment c single-phase or three-phase current generator c ammeters c CT c adapter for EC module c chronometer c documentation Wiring c diagram B, B7 or B8 c protective relays: F6/, F6/, F7/, F7/ F6/, F6/, F7/, F7/ F6/, F6/, F64/, F64/, F8/, F8/, F9/, F9/ F8/, F8/, F9/, F9/ F8/, F8/, F84/, F84/. Test c read the section entitled measurement and testing method c status parameter setting: v select the Io measurement method: interposing ring CT, core balance CT or sum of CTs v check the microswitches on the ECM and EC modules v check the connection of the interposing ring CT to the connector. Procedure c protection parameter setting: E/F X v select the definite curve v set Iso to the desired value v set T to the desired value v disable the Unbalance protections () ; O/C X, (for sum of CTs); the other earth fault set points Io Checking of definite time Iso set point t T Is Io The direction of current injection is irrelevant for this protection. c parameter setting v set T to.5 s c test v gradually inject the real current until the output relay linked with the protection in program logic picks up v read the Iso current value on the ammeter v check the meter and I TRIP () values on the display unit or pocket terminal v stop the injection v press reset () on the Sepam to erase the messages and reset the output relay Checking of harmonic restraint () c parameter setting v set H Rest = yes c testing v inject a real current I until the output relay linked to the protection in the program logic picks up v inject a harmonic current (frequency Hz or Hz according to the network frequency) with a value greater than. I into another phase v the output relay should drop out v stop the injection v preset reset () on Sepam to erase the messages () this function may only be activated if your program logic has been customized. () remember to reactivate the protections at the end of testing. () for F8X and F9Y protections only. Restaint available as of version 994 SFT 8. X = number of the protective relay. Checking of the definite time delay T c protection parameter setting: E/F X v set T to the desired value v prepare the injection with twice the value of Iso v set the chronometer to zero c test v start up injection and the chronometer at the same time v Sepam's output relay stops the chronometer v read the T value measured by the chronometer. Sepam - Testing /9
13 Earth fault protection (cont'd) Checking of IDMT set points and time delay The set point and time delay are IDMT and correspond to the curve and chart coordinates (see protection function sheets in appendix). The protection testing is the same as the IDMT phase overcurrent test. t to T,Iso io Iso a time to corresponds to an injected value io. I/Iso c protection parameter setting: E/F X v select the standard inverse, very inverse or extremely inverse or ultra inverse curve v set Iso (asymptote: for an injection io = Is, to = infinity) v set T (corresponding to Iso: for an injection io = Iso, to = T) v identify on the curve the different coordinates of the points that you will be testing (io and to) c test the different points on the curve v preset the injection i and make a note of the value v stop the injection and reset the chronometer to zero v press reset if required () v start up injection and the chronometer at the same time v check the injection value on the ammeter (stability) v Sepam's output relay stops the chronometer v read the t value measured by the chronometer v compare with the value given in the curve and calculate using the charts v check the meter and I TRIP () values on the pocket terminal v stop the injection v press reset () on Sepam to erase the messages and reset the output relay. Example In = 4 Status measurement by CT (connection of 4 and ) Settings definite Iso = T =.5 s Injection i = For an injection io =, the output relay picks up after time t =.5 s. Sepam measures Io = and I TRIP = Example In = 4 Status measurement by CT (connection of 4 and ) The CT test is the equivalent of the CT test; measurement range is different. Settings standard inverse curve Iso = T =.5 s Injection i = In the standard inverse column of the chart which gives K for I/Is, read the value K = that corresponds to I/Is = = (/) For an injection io =, the output relay picks up after time t = x.5 s =.5 s (t=k x T). Sepam measures Io = and ITRIP =. Example In = 4 Status measurement by core balance CT (connection of 4 and ) c select for the Io sensor the value of the CT primary circuit. In the example: In = 4 c check that number of times the wire enters the CHS interposing ring CT is in accordance with the value of the CT secondary circuit (5 times for or once for 5 ) Settings extremely inverse curve Iso = (minimum = 5% x 4 ) T =. s Injection io = In the extremement inverse column of the chart which gives K for I/Is, read the value K = 4.5 that corresponds to I/Is = 5 = (/) For an injection io =, the output relay picks up after time t = 4. x..4 s (t = K x T). Sepam measures Io = and ITRIP =. Example 4 In = /5 Status measurement by sum of CTs Settings standard inverse curve Iso = T = 4 s Injection io = 4 ( secondary) In the standard inverse column of the chart that gives K for I/Is, read the value K =.76 that corresponds to I/Is = = (4/) For an injection io = 4, the output relay picks up after time t =.76 x 4.4 s (t=k x T). Sepam measures Io = 4 and ITRIP = 4. Please note: In order to reduce the injection unit current Ii, it is possible insert the wire through the CT several times. The Sepam measurement will be equal to: Ii multiply by the number of turns in CT. () this function may only be activated if your program logic has been customized. X = number of the protective relay. / Sepam - Testing
14 Percentage-based single-phase overcurrent protection NSI code 5-5 function n FX for the phase overcurrent I protection X F4X for the phase overcurrent I protection F5X for the phase overcurrent I protection FY for the phase overcurrent I' protection Y FY for the phase overcurrent I' protection FY for the phase overcurrent I' protection Equipment c single-phase current generator c ammeters c chronometer c documentation Wiring c B diagram c protective relays: F/, F/, F4/, F4/, F5/, F5/, F/, F/, F/, F/, F/, F/. Test c read the section entitled measurement and testing method c status parameter setting v check the microswitches ( or 5 ) that correspond to the CT secondary circuits. Please note: the choice of the CT primary value has no effect. Procedure c protection parameter setting: Iph O/C X with ph =. or v set Is to the desired value v set T to the desired value v disable the set points of the following protections () : - unbalance, O/C, E/F (if CT sum is used) - the other Iph O/C protections Checking of the set point c parameter setting v set T to.5 s c test v gradually inject a current until the output relay linked to to the protection in the program logic picks up v read the Is value of the current on the ammeter v stop the injection v press reset () on Sepam to erase the messages and de-activate the outputs. Checking of the time delay c parameter setting v set T to the desired value v preset the injection to twice the value of Is v set the chronometer to zero c test v start up the chronometer and the injection at the same time v the Sepam output relay stops the chronometer v read the value t measured by the chronometer. () this function may only be activated if your program logic has been customized. () remember to reactivate the protections at the end of testing. X = number of the protective relay. Sepam - Testing /
15 Directional overcurrent protection NSI code 67 function n F5X for -phase directional overcurrent (I, I) X F5X for -phase directional overcurrent (I, I, I) In order to use this function, it is necessary to be familiar with the overcurrent and overvoltage protection function procedures and settings (refer to appropriate sections). Equipment c single-phase and three-phase current and voltage generators c phase shifter with angle indicator c ammeters c voltmeter c chronometer c calculator c adaptater for EC module c documentation Wiring c diagrams B5 or B6 c protective relays: F5/, F5/ for normal zone of set point F5/, F5/4 for inverse zone of set point F5/, F5/ for normal zone of set point () F5/, F5/4 for inverse zone of set point () F5/, F5/ for normal zone of set point F5/, F5/4 for inverse zone of set point F5/, F5/ for normal zone of set point () F5/, F5/4 for inverse zone of set point () Test c read the section entitled measurement and testing method c status parameter setting v select Fn network frequency v set Unp the VT secondary circuit phase-to-phase voltage v set Uns, the VT secondary phase-to-phase voltage v set the number of wired VTs to U v select the value of the CT primary circuits v check the microswitches on the U/Vo, ECM or EC modules. () this function may only be activated if your program logic has been customized. () only one relay is used in standard applications. () remember to reactivate the protections at the end of testing. (4) input value not taken into account by the F5X function X = number of the protective relay. Procedure This protection checks the direction of currents I, I (4) and I in comparison with voltages U, U (4) and U respectively, so that testing can be carried out using single-phase current and voltage, changing only one current and the shift with respect to its voltage each time. I ϕ= α θ c protection parameter setting: Dir O/C X v select the curve v set Is to the desired value v set T to the desired value (see curves in appendix) v select angle θ (characteristic angle) v disable the following protections () O/C X; Under/C X; U/V X ; Unbalance; E/F (for sum of CTs) ; N Vol Disp (for sum of VTs) v inject the voltage or voltages and the current or currents in accordance with diagram B5 or B6 v select the appropriate phase shift in accordance with the protection activation zone, given: ϕ = α or ϕ = α or ϕ = α (single phase) ϕ = α + 9 or ϕ = α + 9 or ϕ = α + 9 (three phase) or ϕ, ϕ and ϕ being the angles read on the pocket terminal (±) α, α et α being the phase shift angles of the injection unit. Example of test on U and I using single-phase current and voltage (see diagram B5) I Is inverse zone θ inverse zone V ϕ α θ Is ϕ=9 +(α) Characteristic line U normal zone Characteristic line U normal zone v connect voltage U: to input U (terminal ) and V to input U (terminal 4) v connect current I: to input N (terminal B) and I to input I (terminal B4) c testing of Is set point for θ = and definite time v inject phase-to-phase voltage Uns v set T to.5 s v inject current so that the phase shift angle ϕ can be set to and v check ϕ on the pocket terminal v stop current injection and reset Sepam to zero () v gradually increase the current until the protection output relay picks up: F5/ or F5/ for ϕ = F5/ or F5/4 for ϕ = v read Is on the ammeter. / Sepam - Testing
16 c testing of T Once the protection activation zone has been determined, the T tests are the same as the definite time and IDMT curve phase overcurrent protection tests (see section on phase overcurrent). c testing of protective relay normal and inverse zones The zone limits are: ϕ = 9 + θ to ϕ = 7 + θ v inject phase-to-phase voltage Uns v set T to.5 s v select θ according to the different examples given below v preset the current to twice Is and the phase shift according to the chart v stop current injection and reset Sepam () v inject the current with a phase shift that is outside the zone concerned by the protective relay to be tested v vary the phase shift angle a of the injection unit so as to determine the angle limits of the activation zone v reset to zero when leaving the zone each time the output relay () is activated. c three-phase testing These tests are performed using the same procedures as those described previously. v connect the voltages (N, V, V, V) and currents according to diagram B6 v inject the voltages and currents v the change in the injection box phase difference angle is determined by the protection activation zone (see chart). characteristic normal zone inverse zone angle F5X/ and F5X/ F5X/ and F5X/4 F5X/ and F5X/ F5X/ and F5X/4 ϕ or ϕ or ϕ ϕ or ϕ or ϕ θ = ( ) to (8 ) to θ = 45 5 ( ) to 5 5 (8 ) to 5 θ = 6 ( ) to 5 5 (8 ) to Remark s a rule, the angle indicated by the injection unit is the phase shift between phase voltage and current. Example injection unit pocket terminal α ϕ ou The voltage is created electronically and is shifted with respect to the current that serves as the reference for phase shift measurement. () this function may only be activated if your program logic has been customized. X = number of the protective relay. Sepam - Testing /
17 Directional earth fault protection NSI code 67N function n F5X X In order to use this function, it is necessary to be familiar with the overcurrent and residual voltage protection function procedures and settings (refer to appropriate sections). Equipment c single-phase current and voltage generators c phase shifter with angle indicator c ammeters c voltmeter c chronometer c calculator c adapter for EC module c documentation Wiring c B5 or B6 or B7 diagram c protective relays: F5/, F5/ for normal zone of set point F5/, F5/4 for inverse zone of set point F5/, F5/ for normal zone of set point () F5/, F5/4 for inverse zone of set point () Test c read the section entitled measurement and testing method c status parameter setting v select Fn network frequency v set Unp phase-to-phase voltage v set Uns VT secondary circuit phase-to-phase voltage v select Vo measurement method v select CT primary value v select Io measurement method v check microswitches on the U/Vo, ECM or EC modules. Procedure c protection parameter setting: Dir. E/F v set Iso to the desired value v set T to the desired value v select angle θo (characteristic angle) v disable the following protections () : - related to Vo if measurement is by the sum of the VTs: U O/V; U O/V X; U U/V; U U/V X - related to Io if measurement is by the sum of the CTs: all O/C, E/F and Unbalance set points v inject voltage which corresponds to Vo >.6 % of Unp Checking of set point with θo = c parameter setting v set T to.5 s v select θo = c test (see figure ) v gradually inject current i with a phase shift of 8 with respect to Vo until the output relay linked with the normal protection zone in program logic picks up v read the current value on the ammeter v stop current injection v press reset () on Sepam to erase the messages and reset the output relay. Checking of time delay T c parameter setting v set T to the desired value c test (see figure ) v preset the current injection to. times the Iso value and the 8 phase shift with respect to Vo v set the chronometer to zero v start up injection and the chronometer at the same time v Sepam's output relay stops the chronometer v read the value measured by the chronometer Checking of the protection range using a phase shifter c parameter setting v set T to the minimum (.5 s) v set Iso c test (see figures, and 4) v set the injection current i to a value that is clearly greater than Iso so that its projection Ipo will be greater than Iso v the angle limits of the normal and inverse ranges will be: - normal zone [ϕo] = 8 + θo ±ω - inverse zone [ϕo] = 6 + θo ±ω with cosω = Iso/i θo = angle of the line formed by the projection of i with respect to Vo (set via the pocket terminal). () this function may only be activated if your program logic has been customized () only one relay is used in standard applications () remember to reactivate the protections at the end of the test. X = number of the protective relay. /4 Sepam - Testing
18 example c angle θo = (see figure graph) settings Iso = T =.5 s for injection i = 5, the protection is activated: cosω = /5 =.4 hence ω = 66.4 v in normal zone 8 + ±ω i.e. [ϕo] equal to.6 to v in inverse zone 6 + ±66.4 i.e. [ϕo] equal to 9.6 to 66.4 (46.4). c angle θo = (see figure graph) with strong current (limit of 4 ranges) settings Iso = T =.5 s for injection i =, the protection is activated: cosω = / =. hence ω = 84. v in normal zone 8 + ±84. i.e. [ϕo] equal to 4 to 56, no processing outside this range. v in inverse zone 6 + ±84. i.e. [ϕo] equal to 84 to 76 (46 ), no porcessing outside this range. c angle θo = (see figures and 4 graphs) settings Iso = T =.5 s for injection i = 5, the protection is activated: cosω = /5 =.4 hence ω = 66.4 v in normal zone 8 + ±ω i.e. [ϕo] equal to 4.6 to v in inverse zone 6 + ±66.4 i.e. [ϕo] equal to.6 to 96.4 (456.4 ). c angle θo = -45 (see figures and 4 graphs) setttings Iso = T =.5 s for injection i =, the protection is activated: cosω = / =. hence ω = 78.4 v in normal zone 8 +(-45 ±ω) i.e. [ϕo] equal to 56.6 to.4. v in inverse zone 6 +(-45 ±66.4 ) i.e. [ϕo] equal to 48.6 to.4 (8.4 ). Fig normal zone F5/ F5/ F5/ F5/ Fig normal zone F5/ F5/ F5/ F5/ Ipo resistive "i" projected fault Ipo "i" "i" 4 -Iso 4 Fig Fig 4 Ipo normal zone ω "i" Iso ϕo (parameter) α (injection) θo (protection) Vo Iso Iso Ipo normal zone "i" plan where Ipo > Iso angles : θo protection = ϕo parameter = 8 α injection = 8 Vo Vo inverse zone F5/ F5/4 F5/ F5/4 angles : θo protection = ϕo parameter = 4 à 56 α injection = 4 à 56 ω ω "i" Iso ϕo (parameter) α (injection) projection line θo (protection) Vo Variation in "i" around Vo normal zone inverse zone F5/ Special cases c the injection unit performs a special phase shift and angle measurement, which makes it necessary to make an angle correspondence chart. Example Injection according to wiring diagram B7 (i is 8 from Vo). F8/ Iso Vo θo = o F5/ 5%Ino Corresponding program logic diagram: F5/ Kxx F8/ injection unit a pocket terminal ϕo or The voltage is created electronically and has a phase shift with respect to the current that serves as the reference for phase shift measurement. c when combined with an earth fault protection set point, the directional protection can use the inverse time time delay. The combination is made via customized program logic. Sepam - Testing /5
19 Directional earth fault protection for compensated networks NSI code 67NC function n F48X X In order to use this function, it is necessary to be familiar with the overcurrent and residual voltage protection function procedures and settings (refer to appropriate sections). Equipment c single-phase current and voltage generators c phase shifter with angle indicator c ammeters c voltmeter c chronometer 66 c calculator c adapter for EC module c documentation Wiring c diagram B5 or B6 or B7 c protective relays: F48/, F48/ for normal zone set point F48/, F48/4 for inverse zone set point F48/5 for Vo > Vso. F48/, F48/ for normal zone set point F48/, F48/4 for inverse zone set point F48/5 for Vo > Vso. Test c read the section entitled measurement and testing method c status parameter setting v select Fn network frequency v set Unp to the phase-to-phase voltage value v select Uns the VT secondary circuit phase-to-phase voltage v select the Vo measurement method v select the value of the CT primary circuit v select the Io measurement method v check the microswitches on the U/Vo, ECM or EC modules. Procedure c protection parameter setting: CNSdir, E/F v set Iso to the desired value v select sector angle 8 or 86 v set T the protection time delay v set Vso v set Tmem disengaging time v disable the following protections: - related to Vo if measurement is by the sum of the VTs: U U/V; U U/V X; U O/V; U O/V X, N Vol Disp (if included) - related to Io if measurement is by the sum of the CTs: O/C X, E/F X and unbalance. Checking of Iso set point c parameter setting v set Iso to the desired value v set T to.5 s c test v inject voltage which corresponds to Vo > Vso (see chapter on N Vol Disp) v once the activation zone has been determined (normal or inverse), phase shift between i and u of for inverse zone and of 8 for normal zone v inject current i, gradually increasing it until the relay linked to the protection picks up v read the Iso value on the ammeter. v stop the current injection v press reset () on Sepam to erase the messages and deactivate the output. Checking of T c parameter setting v set T to the desired value c test v present current i to twice Iso and the injection unit angle in accordance with the zone concerned v reset Sepam and the chronometer v start up injection and the chronometer at the same time v the output relay stops the chronometer v read T on the chronometer normal zone inverse zone Ipo Io sector Iso Vo () this function may only be activated if your program logic has been customized. () remember to reactivate these protections if need be at the end of testing. X = number of the protective relay. /6 Sepam - Testing
20 Checking of protection disengaging time This time delay is activated on the falling edge of each fault signal. It processes very brief transient faults which, when repetitive, allow T to be reached. The relay linked with the protection must not be a latching relay in order for this check to be performed. c parameter setting v set Tdis to the desired value c test v set up the chronometer wiring so that it will start up when injection stops and the dropping out of the protective relay will stop the counting operation v create a fault by injecting current and voltage v reset the chronometer to zero v stop current or voltage injection and start up the chronometer v when the Sepam relay drops out, read the Tdis value on the chronometer Checking of the protection activation zone (sector) c parameter setting v set T to.5 s v select the sector c test v inject voltage which corresponds to Vo > Vso (see section on N Vol Disp) v preset current Io to twice Iso, with a phase shift of 9 and then 7 with respect to Vo v vary the phase shift angle a of the injection unit so as to determine the angle limits of the activation zone sector normal zone inverse zone v reset to zero when leaving the zone each time the output relay is activated. Sepam - Testing /7
21 Thermal overload protection NSI code 49 function n F4 Equipment c single-phase current generator c ammeters c chronometer c CSP adapter c calculator c documentation Wiring c diagram B or B or B8 or B9 or B c protective relays: F4/ corresponding to OL F4/ corresponding to OL Test c read the section entitled measurement and testing method c status parameter setting v select the value of the CT primary circuit v set the value of Ib (rated current given by the manufacturer on the manufacturer plate of the motor or transformer) v check the microswitches ( or 5 ) which correspond to the CT secondary circuits v or check and set the microswitches on the EC module Procedure c set protection parameters: thermal v set OL, OL (% heat rise set points) v set djust (none, low, average or high) v set T (heating time constant) v set T (cooling time constant) v disable: O/C X, Unbalance, E/F X if sum of CTs is used Checking of heat rise time c parameter setting v preset i to the desired value (X times Ib) c test v stop injection v set the chronometer to zero Cold curve v reset Heating to zero on the pocket terminal (password + clear) v start up injection and the chronometer at the same time v monitor the injection value on the ammeter (stability) v use the pocket terminal to monitor heat rise Heating When OL is reached: v the Sepam output relay stops the chronometer v read the t value measured by the chronometer v stop the injection v press reset () on Sepam to erase the messages and reset the relay (if Heating < OL) c example: heat rise Case of a transformer (T = T, djust = None) In = 4 Ib = 8 v set OL = 95% v set OL = 5% v set T = 5 mn v set T = 5 mn v set djust = None See the chart which gives t/t for f(ol, I/Ib). In the example, i =. Ib For an injection i = Ib + % =. x 8 = 64 the protection trips OL in a time period of t =.858 x 5 x 6 = 47.7 s (4 mn 8 s) and OL in a time period of t =.49 x 5 x 6 = 4. s (5 mn 4 s) Monitor Heating the variation in heat rise on the pocket terminal. () this function may only be activated if your program logic has been customized. () remember to reactivate the protections at the end of testing if required. X = number of the protective relay. /8 Sepam - Testing
22 Setting djust = None does not take into account the unbalance value and does not allow single-phase injection to be used. c example: heat rise Case of an unbalanced motor. Use of diagram B9. In = 4 Ib = 8 I, I, I v set OL = 95% v set OL = 5% v set T = 5 mn v set T = mn v set djust = High (= 9) v Heating = % The equivalent current value should be calculated so as to enable the user to select the right I/Ib ratio in the chart that gives t/t for f(ol, I/Ib). In the example i =. Ib ieq = (Ib+%Ib) + 9([Ib+%Ib] /.7) i.e. ieq = () fi ieq = 78 hence I/Ib = 78 /8 =.6 For an injection i = 64, in accordance with diagram B9 or B, the protection will trip OL in a time period of t =.54 x 5 x 6 = 45 s and OL in a time period of t =.865 x 5 x 6 = 55.9 s Monitor Heating the variation in heat rise Heating on the pocket terminal. Hot curve v reach Heating = % v start up injection and the chronometer at the same time v monitor the injection value on the ammeter (stability) v use the pocket termial to monitor the variation in heat rise Heating When OL is reached v the Sepam output relay stops the chronometer v read the t value measured by the chronometer v stop the injection v press reset () on Sepam to erase the messages and reset the relay (if Heating > OL). Practical method of protection time measurement and testing using initial heat rise v set OL to the initial heat rise value Ei v reset heat rise to zero using the pocket terminal (password + clear) v start up injection and the chronometer When OL = Ei is reached v the chronmeter indicates the time ti v set OL to the desired value v reset heat rise Heating to zero using the pocket terminal (access code + clear) v start up injection and the chronometer. When OL is reached v the chronmeter indicates the time tf. v the protection operating time starting from initial heat rise Ei is t = tf - ti. Sepam - Testing /9
23 Thermal overload protection (cont'd) Cold curves: t/t = f(ol, I/Ib) The following charts give the numerical values of the cold curves. Example of chart use For an operation set point OL of 5% with a time constant T of 5 mn, what is the operation time when cold at.6 Ib? Using the cold curve chart: c read the value of t/t =.865 at the intersection of row OL = 5 and column I/Ib =.6 c calculate the operation time t =.865 x T i.e. t =.865 x 5 x 6 = 67.8 s I/Ib OL (%) / Sepam - Testing
24 Cold curves I/Ib OL (%) Sepam - Testing /
25 Thermal overload protection (cont'd) Cold curves I/Ib OL (%) / Sepam - Testing
26 Hot curves: t/t = f(ol, I/Ib) The following charts give the numerical values of the hot curves. Example of chart use For an operation set point OL of 5% with a time constant T of 5 mn, what is the operation time when hot at.6 Ib? Using the hot curve chart: c read the value t/t =. 64 at the intersection of row OL = 5 and column I/Ib =.6 c calculate the operation time t =.64 x T i.e. t =.64 x 5 x 6 =.7 s I/Ib OL (%) Sepam - Testing /
27 Thermal overload protection (cont'd) Hot curves I/Ib OL (%) I/Ib OL (%) /4 Sepam - Testing
Protection and control. Sepam range Sepam 2000 Metering and protection functions
Protection and control Sepam range Sepam 2 Metering and protection functions Contents chapter / page metering functions 1/1 protection functions 2/1 appendix 3/1 Notation c Sepam 2 may include several
More informationProtection and control. Sepam range Sepam 1000 Substations Busbars Transformers Motors
Protection and control Sepam range Substations Busbars Transformers Motors Presentation Contents page presentation selection table 4 metering 5 protection 6 control and monitoring 9 functional and connection
More informationProtection and control. Sepam range Sepam 2000 Generator
Protection and control Sepam range Sepam 000 Presentation Contents page presentation selection table metering protection control and monitoring functional and connection schemes other connection schemes
More informationSubstation applications
Substation applications To make it easy to choose the right for a protection application, the most typical applications are presented with the type of for them. Each sample application is presented by:
More informationProtection and control. Sepam range Sepam 2000 SX
Protection and control Sepam range Sepam 000 SX Presentation Contents page presentation selection table metering protection control and monitoring functional and connection schemes 9 other connection schemes
More informationModular range of digital protection relays
S e p a m s e r i e s 2 0, 4 0, 8 0 Modular range of digital protection relays Fast Dependable Simple Fast response Maximum dependability Your electrical equipment is under control. With Sepam protection
More informationProtection and control. Sepam range Sepam 2000 Metering and control
Protection and control Sepam range Sepam 000 Metering and control Presentation Contents page presentation selection table metering customized control logic standard control and monitoring functional and
More informationGenerator Protection GENERATOR CONTROL AND PROTECTION
Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault
More informationPD300. Transformer, generator and motor protection Data sheet
PD300 Transformer, generator and motor protection Data sheet DSE_PD300_eng_AO No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam T&D. One of
More informationProtection and control VIP300. Technical manual
Protection and control VIP300 Technical manual contents 1. presentation of the VIP300...3 2. use and settings...4 3. choice of sensors and operating ranges...9 4. connection scheme...10 5. assembly...11
More informationProtection of Electrical Networks. Christophe Prévé
Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé
More informationNTG MULTIFUNCTON GENERATOR PROTECTION RELAY. NTG-Slide
NTG MULTIFUNCTON GENERATOR PROTECTION RELAY 1 NTG Digital protection relay that integrates a number of functions required r for the protection of generators. It is used in power stations from gas, steam,
More informationOvercurrent and Overload Protection of AC Machines and Power Transformers
Exercise 2 Overcurrent and Overload Protection of AC Machines and Power Transformers EXERCISE OBJECTIVE When you have completed this exercise, you will understand the relationship between the power rating
More informationProtection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique
Protection and control Sepam range Sepam 0 LA Self-powering protection Merlin Gerin Square D Telemecanique presentation contents page presentation protection functional and connection schemes other connection
More informationStabilized Differential Relay SPAD 346. Product Guide
Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault
More informationRETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).
RETROFITTING Motor Protection Relay NPM800R (R2 case) and NPM800RE (R3 case) are dedicated to the refurbishment of 7000 series (R2 and R3 cases) of CEE relays providing the protection of medium voltage
More informationTransformer protection IED RET 670
Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth
More informationNumbering System for Protective Devices, Control and Indication Devices for Power Systems
Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements
More informationpresentation contents application advantages
presentation contents page presentation protection functional and connection schemes other connection schemes connection characteristics 9 installation 0 commissioning ordering information Sepam 00 is
More informationTechnical catalogue. Emax Low voltage air circuit-breakers. Hotline:
Technical catalogue Emax Low voltage air circuit-breakers www.alobitanbd.com Hotline: 01711548558 PAGE : 02 The new Emax have received innumerable international certifications and approval by the major
More informationINSTRUCTION MANUAL. AQ F3x0 Feeder protection IED
INSTRUCTION MANUAL AQ F3x0 Feeder protection IED Instruction manual AQ F3x0 Feeder protection IED 2 (173) Revision 1.00 Date November 2010 Changes - The first revision. Revision 1.01 Date January 2011
More informationSPAD 346 C Stabilized differential relay
SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault
More informationVOLTAGE REGULATOR R 449. Installation and maintenance. This manual must be sent to the end user R 449 X2 Z1 X1 Z2 E+ E- (12V - 10A)
This manual must be sent to the end user X2 Z1 X1 Z2 E+ E- J1 t (12V - 10A) ~ 10 ohms Exciter field + - Isolated DC power supply Installation and maintenance WARNING TO AVOID HARM EITHER TO PEOPLE OR TO
More information7SR21 Non-Directional 7SR22 Directional Overcurrent Relay
7SR21 Non-Directional 7SR22 Directional Overcurrent Relay Document Release History This document is issue 2010/05. The list of revisions up to and including this issue is: 2010/05 Function diagrams amended,
More informationPower System Protection Manual
Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,
More informationOVERCURRENT PROTECTION RELAY GRD110
INSTRUCTION MANUAL OVERCURRENT PROTECTION RELAY GRD110 TOSHIBA Corporation 2002 All Rights Reserved. ( Ver. 3.1) Safety Precautions Before using this product, please read this chapter carefully. 1 This
More informationPower Plant and Transmission System Protection Coordination
Technical Reference Document Power Plant and Transmission System Protection Coordination NERC System Protection and Control Subcommittee Revision 1 July 2010 Table of Contents 1. Introduction... 1 1.1.
More informationPOWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS
POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS Juan Manuel Gers, PhD Protection coordination principles Relay coordination is the process of selecting settings that will assure that the relays
More informationVoltage Relays. Ensuring Reliable Protection for Electrical Systems against Voltage Faults. ISO 9001:2008 Certified.
Ensuring Reliable Protection for Electrical Systems against Voltage Faults Voltage Relays Inside the Catalogue Range Model Selection Specifications Technical Terms & Data ISO 9001:2008 Certified Delivering
More informationModern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions
1 Transmission transformers are important links in the bulk power system. They allow transfer of power from generation centers, up to the high-voltage grid, and to bulk electric substations for distribution
More informationPARAMETER LIST PARAMETER LIST
PRMETER LIST PRMETER LIST dvanced Genset Controller, GC 200 larm list Parameter list Document no.: 489340605L SW version 4.2.x or later GC 200 parameter list 489340605 UK Contents: General information...
More informationCOPYRIGHTED MATERIAL. Index
Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,
More informationBurdens & Current Transformer Requirements of MiCOM Relays. Application Notes B&CT/EN AP/B11. www. ElectricalPartManuals. com
Burdens & Current Transformer Requirements of MiCOM Relays Application Notes B&CT/EN AP/B11 Application Notes B&CT/EN AP/B11 Burdens & CT Req. of MiCOM Relays Page 1/46 CONTENTS 1. ABBREVIATIONS & SYMBOLS
More informationSystem Protection and Control Subcommittee
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationBase unit Connection
Connection. 2 8 fixing points for 4 spring clips. 3 Red LED: Sepam unavailable. 4 Green LED: Sepam on. 5 Gasket. A B B2 20-pin connector for: b 24 V DC to 250 V DC auxiliary supply b 5 relay outputs. Connector
More informationNO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.
MODBUS/BECO2200-M3425A Communication Data Base for M-3425A Integrated Protection System Device I.D. = 150 Specifications presented herein are thought to be accurate at the time of publication but are subject
More informationDetecting and Managing Geomagnetically Induced Currents With Relays
Detecting and Managing Geomagnetically Induced Currents With Relays Copyright SEL 2013 Transformer Relay Connections Voltage Current Control RTDs Transformer Protective Relay Measures differential current
More informationBUS2000 Busbar Differential Protection System
BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection 1 Typical Busbar Arrangements Single Busbar Double Busbar with Coupler Breaker and a Half
More informationTransformer Fault Categories
Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)
More informationEEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER
EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER Objective To analyse the differential protection scheme as applied to a three-phase power transformer
More informationPower systems Protection course
Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and
More informationCompany Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D
Document type Page Verksamhetsstyrande 1 (11) Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D17-0008990 1.0 Organisation Valid from Valid until Regionnätsaffärer
More informationg GE POWER MANAGEMENT
745 FREQUENTLY ASKED QUESTIONS 1 I get a communication error with the relay when I try to store a setpoint. This error can occur for several different reasons. First of all, verify that the address is
More informationT1000 USER S MANUAL DATE: 02/02/2006 DOC.MIE10093 REV. 7
Istrumentazioni Sistemi Automatici S.r.l. VIA BERGAMO 41-21020 TAINO (VA) - ITALY OFFICES TEL. +39.0331.956081 - FAX +39.0331.957091 LAB: TEL. +39.0331.956483 - E-MAIL isa@isatest.com WEB www.isatest.com
More informationPower Plant and Transmission System Protection Coordination
Agenda Item 5.h Attachment 1 A Technical Reference Document Power Plant and Transmission System Protection Coordination Draft 6.9 November 19, 2009 NERC System Protection and Control Subcommittee November
More informationImpact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis
1 Impact of transient saturation of Current Transformer during cyclic operations Analysis and Diagnosis BK Pandey, DGM(OS-Elect) Venkateswara Rao Bitra, Manager (EMD Simhadri) 1.0 Introduction: Current
More informationTransformer Protection
Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing
More informationEarth Fault Protection
Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774
More informationwww. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay
Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:
More informationHands On Relay School Open Lecture Transformer Differential Protection Scott Cooper
Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost
More informationNEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :
NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata - 700 032, Tel : 033 2477 3126; Fax : 033 2477 2403 www.ntplindia.com SPECIFICATION NTPL MAKE MICRO-CONTROLLER BASED AUTOMATIC 50KV/10A AC HIGH VOLTAGE
More informationEASUN REYROLLE LIMITED
OCTOBER 2003 APPLICATION AND COMMISSIONING MANUAL FOR NUMERICAL BIASED DIFFERENTIAL PROTECTION RELAY TYPE - MIB202 EASUN REYROLLE LIMITED 1 ISSUE NO : 1 st Issue DATE OF ISSUE : 01-10 - 2003 DEPARTMENT
More informationSVERKER 750/780 Relay Test Sets
/780 The engineer s toolbox for all single phase relay testing Stand-alone functionality Rugged and reliable for field use DESCRIPTION The /780 Relay Test Set is the engineer's toolbox. The control panel
More informationPSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)
1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1
More informationPROTECTION of electricity distribution networks
PROTECTION of electricity distribution networks Juan M. Gers and Edward J. Holmes The Institution of Electrical Engineers Contents Preface and acknowledgments x 1 Introduction 1 1.1 Basic principles of
More information27/04/2015
Modular Carril DIN 35 mm HIL Part number 84871120 Control of AC and DC currents Automatic recognition of AC/DC Measurement ranges from 2 ma to 10 A Choice between over and undercurrent True RMS measurement
More informationNERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination Phase Distance (21) and Voltage-Controlled or Voltage-Restrained Overcurrent Protection (51V) NERC Protection Coordination Webinar Series June
More informationTransformer Protection
Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary
More informationImproving Transformer Protection
Omaha, NB October 12, 2017 Improving Transformer Protection Wayne Hartmann VP, Customer Excellence Senior Member, IEEE Wayne Hartmann Senior VP, Customer Excellence Speaker Bio whartmann@beckwithelectric.com
More informationInstallation and Operating Instructions. Power IT Power Factor Controller RVC
Installation and Operating Instructions Power IT Power Factor Controller RVC Table of contents Page 1. Read this first... 3 About this Instruction Manual... 3 Safety... 3 Electromagnetic compatibility...
More informationNumerical Multi-Function Motor Protection Relay RHO 3. Operation & Maintenance Instruction Manual
Numerical Multi-Function Motor Protection Relay RHO 3 Operation & Maintenance Instruction Manual RHO MANUAL Contents Section Page Description of operation 4 2 Performance specification 20 3 Relay settings
More informationNERC Protection Coordination Webinar Series July 15, Jon Gardell
Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),
More informationPIPSPC. Prepared by Eng: Ahmed Safie Eldin. And. Introduction. Protection Control. Practical. System. Power
PIPSPC Practical Introduction Power System Protection Control Practical Introduction To Power System Protection And Control Prepared by Eng: Ahmed Safie Eldin 2005 Contents POWER SYSTEMS PRINCIPALS. 1
More informationDifferential Protection with REF 542plus Feeder Terminal
Differential Protection with REF 542plus Application and Setting Guide kansikuva_bw 1MRS 756281 Issued: 09.01.2007 Version: A Differential Protection with REF 542plus Application and Setting Guide Contents:
More informationPBM. Motor management system USER S MANUAL. EN_PBM_User-Manual_R011.Docx
PBM Motor management system USER S MANUAL EN_PBM_User-Manual_R011.Docx 1. RECEPTION, HANDLING, INSTALLATION... 6 1.1. Unpacking... 6 1.2. Reception of relays... 6 1.3. Handling electronic equipment...
More informationINSTRUCTION MANUAL TRANSFORMER PROTECTION RELAY GRT100 - B
INSTRUCTION MANUAL TRANSFORMER PROTECTION RELAY GRT00 - B Toshiba Energy Systems & Solutions Corporation 207 All Rights Reserved. ( Ver. 3.) Safety Precautions Before using this product, be sure to read
More informationGE Power Management. Microprocessor Based Generator Protection Relay MGC series Instructions GEK B
GE Power Management Microprocessor Based Generator Protection Relay MGC series 1000 Instructions GEK 105191B *(Ã3RZHUÃ0DQDJHPHQW $Q\WKLQJ\RXFDQ WILQG" $Q\WKLQJQRWFOHDUHQRXJK",)Ã
More informationSequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network
Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria
More informationTransmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection
Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed
More informationDP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation
DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Technical Requirements for Interconnection and Parallel Operation of Distributed Generation Single Phase
More informationPower factor correction and harmonic filtering. Automatic power factor regulators R.1
Power factor correction and harmonic filtering Automatic power factor regulators R.1 R.1 Automatic power factor regulators R.1 - Automatic power factor regulators Selection table R1-4 computer Plus-T Intelligent
More information1960 Research Drive, Suite 100, Troy, Michigan with. REVISION: December 10, 2007 (Supersedes previous versions) Prepared by:
ENGINEERING SERVICES 1960 Research Drive, Suite 100, Troy, Michigan 48083 ARC FLASH REDUCTION with SEPAM RELAY ZONE SELECTIVE INTERLOCKING REVISION: December 10, 2007 (Supersedes previous versions) Prepared
More informationHands On Relay School Open Lecture Transformer Differential Protection Scott Cooper
Hands On Relay School Open Lecture Transformer Differential Protection Scott Cooper Transformer Differential Protection ntroduction: Transformer differential protection schemes are ubiquitous to almost
More informationASHIDA Numerical OC/EF Protection Relay
ASHIDA Numerical OC/EF Protection Relay Features: 4 Element (3 Phase + EF) over current IDMT with instant trip. Back - lit LCD display for settings. Display of fault current. / Load current. Selection
More informationEarth Fault Relay EFSPL-1A/5A
Earth Fault Relay EFSPL-1A/5A IEEE DEVICES CODE-50N Features Static Device Compact, Reliable with Aesthetic Value Rugged, Robust and Tropicalised design Consistent repeat accuracy Wide Current Operating
More informationApplication and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16
Application and Commissioning Manual for Numerical Over & Under Voltage Protection Relays Type MVT181 CONTENTS PAGE APPLICATION 2-7 INSTALLATION 8-16 COMMISSIONING 17-22 WIRING DIAGRAM 23 1. INTRODUCTION
More informationINSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12
INSTRUCTION MANUAL Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS Power Factor Controller A12 1. CONTENTS 1. CONTENTS 1 2. FEATURES 2 3. INSTALLATION, CONNECTION AND APPLYING POWER 2 4.
More informationR448 & R448 V50 A.V.R. Installation and maintenance R 448 ST5 ST3 ST10. Armature + 6- Field X2 Z1 X1 Z2 E+ E- 0V Slow fuse 250V 10 A
Armature + 6- Field Thismanualistobegivento theenduser F1 ST5 Slow fuse 250V 10 A with LAM without LAM 10 Yellow 11 Red 12 Black 9 Green X2 Z1 X1 Z2 E+ E- 0V 110 22 ST3 requency 50Hz 60Hz ST10 R 448 This
More informationN. TEST TEST DESCRIPTION
Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities
More informationNERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell
Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series
More informationT/3000 T/3000. Substation Maintenance and Commissioning Test Equipment
T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY
More informationMV protection relay. Installation assistance guide. Sepam ranges
MV protection relay Installation assistance guide Sepam ranges Series 20 Series 40 Series 80 Sepam 2000 51312779F0 A2 1/60 Contents Aims of the guide... 3 Reference documents... 3 Part I: Generic installation
More informationProtective Relaying for DER
Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed
More informationFuseless Capacitor Bank Protection
Fuseless Bank Protection Minnesota Power Systems Conference St. Paul, MN. November 2, 1999 by: Tom Ernst, Minnesota Power Other Papers of Interest Presented at Western Protective Relay Conference, Oct.
More informationFMR. Ultra Line FEEDER MANAGER RELAY
Ultra Line FEEDER MANAGER RELAY Protective Functions F49 : One Thermal Image element F50/51/67 : Three levels for phase overcurrent independentely programmable as directional or non directional F50N/51N/67N
More informationR438 A.V.R. Installation and maintenance. This manual is to be given to. the end user CALL US TODAY POWER-58. SHOP ONLINE
T1 T7 T2 T8 This manual is to be given to the end user T4 T10 140 mm T5 T11 X2 Z1X1 Z2 E+ E- 0V 110 220 380 200 mm z P1 ST9 AREP PMG This manual concerns the alternator which you have just purchased. We
More informationXD1-T Transformer differential protection relay. Manual XD1-T (Revision A)
XD1-T Transformer differential protection relay Manual XD1-T (Revision A) Woodward Manual XD1-T GB Woodward Governor Company reserves the right to update any portion of this publication at any time. Information
More informationTransformer Protection Principles
Transformer Protection Principles 1. Introduction Transformers are a critical and expensive component of the power system. Due to the long lead time for repair of and replacement of transformers, a major
More informationTesting Numerical Transformer Differential Relays
Feature Testing Numerical Transformer Differential Relays Steve Turner Beckwith Electric Co., nc. ntroduction Numerical transformer differential relays require careful consideration as to how to test properly.
More informationAdvanced Test Equipment Rentals ATEC (2832)
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) The toolbox for substation 3-phase testing Three currents and four voltages Stand-alone functionality Rugged and reliable
More informationAddendum Operation Manual IM30-DREK MICROPROCESSOR OVERCURRENT AND DIRECTIONAL EARTH FAULT PROTECTION RELAY + AUTORECLOSE TYPE IM30-DREK ADDENDUM
K Pag. 1 of 6 MICROPROCESSOR OVERCURRENT AND DIRECTIONAL EARTH FAULT PROTECTION RELAY + AUTORECLOSE TYPE K ADDENDUM OPERATION MANUAL I> I>> O> O>> MICROELETTRICA MILANO SCIENTIFICA ITALY PROG/ I.R.F. I2>
More informationDIGITAL EARTH FAULT RELAY
DIGITAL IDMT / DEFINITE TIME / INSTANTANEOUS Features ŸCompact ŸIDMT (4 IEC curves), Definite Time & Instantaneous ŸWide setting ranges ŸFully digital acquisition & processing of data ŸWide operating voltages
More informationElectrical Protection System Design and Operation
ELEC9713 Industrial and Commercial Power Systems Electrical Protection System Design and Operation 1. Function of Electrical Protection Systems The three primary aims of overcurrent electrical protection
More informationWD series DIN Rail or Screw Mounted Protective Relays
WD series DIN Rail or Screw Mounted Protective Relays WD25 Paralleling (Synch Check) Relays WD2759 Over/undervoltage Relays WD32 Reverse Power Relays WD47 Phase Sequence Relays WD5051 Single- or Three-Phase
More information200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features
CT ratio Power Harmonics ac+dc 200ADM-P Current Injection System with Phase Shift Features 0-200A output current True RMS metering with 1 cycle capture Variable auxiliary AC voltage/current output with
More informationUnit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21
Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...4 Negative Atomic Charge...4 Positive
More informationAPPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges.
APPLICATION: Basler Electric offers a New Line of digitally controlled brush (static) or brushless excitation systems designed for use with existing Hydro, Gas as well as Diesel driven generators requiring
More informationPreface...x Chapter 1 Electrical Fundamentals
Preface...x Chapter 1 Electrical Fundamentals Unit 1 Matter...3 Introduction...3 1.1 Matter...3 1.2 Atomic Theory...3 1.3 Law of Electrical Charges...4 1.4 Law of Atomic Charges...5 Negative Atomic Charge...5
More informationXUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)
XUA1 AC Voltage and phase balance relay (August 1996) Manual XUA1 (Revision New) Woodward Manual XUA1 GB Woodward Governor Company reserves the right to update any portion of this publication at any time.
More informationSPAE 010, 011 High Impedance Protection Relay
SPAE 010, 011 High Impedance Protection Relay User s manual and Technical description f n = 50/60 Hz U n = 50 / 100 / 200 V 2 5 U REF > SPAE 010 0.8 U aux 0.6 1.0 RESET OK x 80... 265 V ~ _ 0.4 U > U n
More information