Protection and control. Sepam range Sepam 2000 Generator

Size: px
Start display at page:

Download "Protection and control. Sepam range Sepam 2000 Generator"

Transcription

1 Protection and control Sepam range Sepam 000

2 Presentation Contents page presentation selection table metering protection control and monitoring functional and connection schemes other connection schemes examples of connections communication characteristics installation ordering information protection and control consists of performing the metering, protection, control and monitoring functions required for operation. Sepam 000 provides all these functions globally. All the equipment and mechanisms that are generally found in a MV cubicle control cabinet are replaced by a single device which performs: c protection, c metering, c control and monitoring using protection functions and logic inputs to activate the trip outputs, closing outputs, etc. and annunciation. Sepam 000 compact S. Sepam 000 standard S. Advantages c Indication of phase and earth fault current values at the time of breaking provides the operator with useful assistance in determining the causes and seriousness of the fault, c The high level of electromagnetic compatibility (EMC) makes it possible to use advanced digital technology functions in electrical substations, without the need for any particular precautions, c Sepam 000's continuous self-testing sets the device in a predetermined fail-safe position whenever a failure occurs, thereby preventing random operation, c Terminals that are individually disconnectable while energized allow easy maintenance, c The optional communication functions can be used for remote setting, remote metering, remote annunciation and remote control via a two-wire link with a supervisor for centralized management. c Setting and testing are extremely simple: v the settings may be made on the front panel (serial link): - one by one, using the TSM00 pocket terminal, or the SFT0 PC software program, - all at once using the SFT PC software program (downloading), v a direct readout is given for primary current and voltage and for the metering function, simple testing by injection guarantees the coherency of all settings. c Each Sepam 000 is design to meet all the application needs and includes all the necessary functions ready for use (protection functions, metering, control logic and communication). This control logic may be adapted to most usuals schemes by a simple parametring. This allows a better safety and optimization of wiring. Installation in the switchboard is simplified: c just one device to install, the Sepam 000. It comes in two models with different widths: v S (standard), v S (compact for certain types), c cabling is limited to: v standard A or A current transformers, v voltage transformers, v temperature sensors v control and annunciation units (start/stop pushbutton, device position, etc), v actuators (trip and closing coils). Customization () Standard control and monitoring carried out in Sepam 000's internal PLC can be customized. The number of inputs and outputs can be increased by adding extension boards (please contact us for further information). () Please refer to document Sepam 000 customized application.

3 Selection table Sepam 000 generators functions ANSI Sepam types () () generatorcode transfomer unit G0 G0 G0 G0 G0 G0 G0 G0 G G G00 G G G G protections phase overcurrent 0/ /* /* thermal overload voltage restrained overcurrent 0V/V negative sequence/ unbalance earth fault 0N/N (G) neutral 0G/G undervoltage () *** *** *** *** overvoltage () neutral voltage displacement () N/ directional overcurrent directional earth fault N reverse real power P field loss (reverse reactive power) Q/0 underfrequency () L overfrequency () H temperature set points (RTDs /) /T / / restricted earth fault REF biased differential G synchronism check metering phase currents (I, I, I) c c c c c c c c c/c* c/c* c c/c* c/c* peak demands phase currents (I, I, I) c c c c c c c c c c c c c voltages (U, U, U, V, V, V) c c c/c** c/c** c c c c c c c c c real / reactive power (P,Q) c c c c c c c c c c c c c peak demand real/ reactive power c c c c c c c c c c c c c power factor c c c c c c c c c c c c c frequency c c c c c c c c c c c c c thermal capacity used c c c c c c c c c c c c accumulated real/ reactive energy (±Wh, ±VArh) c c c c c c c c c c c c c tripping currents (I, I, I, Io) c c c c c c c c c c c c c true rms current c c c c c c c c c c c c c temperature c c c c c c disturbance recording c c c c c c c c c c c c c residual current c c c c c c c c c c c c/c* c/c* residual voltage c c c c c c c c c c c c c cumulative breaking current and number of breaks c c c c c c c c c c c c differential and through currents c c control and monitoring open/ close c c c c c c c c c c c c lockout relay c c c c c c c c c c c c c inhibit closing c c c c c c c c c c c c annunciation 0 c c c c c c c c c c c c c logic discrimination c c c c c c c c c c c c c trip circuit supervision c c c c c c c c c c c c Buchholz, thermal, DGPT, PTC c c c generator shutdown logic c c c c c c c c c c c c de-energizing logic c c c c c c c c c c c c detection of plugged connectors () c c c c c c c c c c c c c operation counter c c c c c c c c c c c c running hours counter c c c c c c c c c c c c phase fault trip counter c c c c c c c c c c c c disturbance recording triggering c c c c c c c c c c c c c VT monitoring c c Sepam models standard S XR SR/ TR TS XR SR/ XR SR LR LS LR LS SS SS compact S LT LT number of standard ESTOR boards The figures in the columns represent the number of similar protection devices. For example, for phase overcurrent protection, "" means separate overcurrent protection devices. () these functions can be performed by Sepam B0 type. () for differential protection use Sepam 00 LD. () the generator protection can t be connected to CSP sensors. (*) function available with sets of sensors. (**) phase-to-neutral voltage measurement available with second set of sensors only with a single T. (***) U and U only.

4 Metering Sepam 000 is an accurate metering device. It gives a direct readout of values, together with the related units, A, V, W... All the values needed for operation and used for commissioning are available locally and in the control room. Measurements needed for operation Currents Measurement of the current for each of the phases of the circuit. Peak demand currents Measurement of the greatest average current value on the phases. The average current measurement is computed periodically (adjustable period:, 0,, 0 or 0 minutes). The clear button is pressed for zero reset. Voltages Measurement of the circuit phase-to-phase and phase-to-neutral voltages. Real / reactive power Measurement of the real and reactive power, with the sign, in balanced and unbalanced -phase networks. Peak demand real / reactive power Measurement of the greatest average real power (and reactive power) value, used to find the power absorbed during peak load periods. The average value is computed periodically (adjustable period:, 0,, 0 or 0 minutes). The clear button is pressed for zero reset. Measurements accessed on the front panel of Sepam 000 (serial link and/or display) and via the communication system. Power factor (p.f.) Measurement of the power factor, with the sign and type (capacitive or inductive), of the power absorbed. Frequency Measurement of frequency (based on positive sequence voltage or the U voltage input). Thermal capacity used Measurement of the relative thermal capacity used (with respect to the nominal thermal capacity) on account of the load. Accumulated real / reactive energy The alphanumerical display unit shows the accumulated real / reactive energy values: c real energy consumed, c reverse real energy, c reactive energy consumed, c reverse reactive energy. These values are saved in the event of a power failure. Tripping currents Measurements of the phase currents and the residual current that were stored at the time that Sepam 000 gave the tripping order. Used to find the fault current (fault analysis) and assess the level of wear of the breaker (maintenance assistance). The "clear" button is pressed for zero reset. True rms current Measurement of the rms value of phase current up to In, taking into account: c fundamental, c harmonics up to rank. Temperature Temperature measurement in C for each RTD. Disturbance recording Recording of electrical signals and logical information before and after a fault recorder triggering order is given.

5 Measurements used for commissioning and maintenance Residual current / residual voltage Used to check the current and voltage sensor connections by giving the measurement of: c the residual current used for the earth fault protection function, c the residual voltage used for the directional earth fault protection function. Cumulative breaking current and number of breaks Used for breaking device maintenance. Characteristics functions ranges accuracy () ammeter () 0 to In ±0.% peak demand current () 0 to In ±0.% voltmeter () 0 to. Un ±0.% wattmeter () 0 to MW ±% varmeter () 0 to MVAr ±% peak demand real power () 0 to MW ±% peak demand reactive power () 0 to MVAr ±% power factor () () - to frequency meter () to Hz ±0.0 Hz accumulated real energy () 0 to 0.0 MWh ±% accumulated reactive energy () 0 to 0.0 MVArh ±% tripping currents () phase: 0 to In ±% earth: 0 to 0 Ino ±% true rms current () 0 to In ±% up to rank disturbance recording () record periods samples duration per period time before to periods triggering event thermal capacity used () 0 to % ±% temperature () -0 to 0 C ± C residual current () 0 to 0 Ino ±% residual voltage () 0 to. Un ±% cumulative breaking current () 0 to (ka) +0% number of breaks () 0 to () measurement accessed on the front panel of Sepam 000 (display and serial link) and via the communication system. () measurement accessed on the front panel of Sepam 000 (serial link). () capacitive or inductive () typical accuracy with nominal values according to IEC 0-. () transfer of records to the front panel of Sepam 000 using the SFT0 software program and via Jbus/Modbus communication. () measurement accessed on front panel of Sepam 000 (serial link) and via the communication system. Reminder: Rated current In, basis current Ib, rated voltage Un and current Ino are general parameters that are set at the time of Sepam 000 commissioning. In is the current sensor rated current (CT rating). Ib is the current which corresponds to the motor power rating, adjustable from 0. to. In. Ino is the core balance CT current rating. Un is the phase-to-phase voltage of the voltage sensor primary windings. Example of the processing of a disturbance recording record using the SFT PC software program.

6 Protection Phase overcurrent (ANSI 0/) F0 to F0* Three-phase equipment protection against phase-tophase (short-circuit) faults. The following types of time delay settings are available definite, standard inverse, very inverse, extremely inverse or ultra inverse. Thermal overload (ANSI ) F* Protection of generator against thermal damage caused by overloads. Thermal overload is calculated according to a mathematical model, with time constants (T and T), taking into account harmonics up to rank st and the effect of negative sequence current by means of an adjustable weighting coefficient. The function comprises: c an adjustable alarm setting, c an adjustable trip setting. Voltage restrained overcurrent (ANSI 0V/V) F* Three-phase protection against alternator phase faults. Its characteristics are suitable for the weak current supplied by the alternator when a short-circuit occurs. Negative sequence / unbalance (ANSI ) F* Protection of equipment against overheating caused by an unbalanced power supply, phase inversion or phase break, and against low levels of overcurrent between phases. Recommendation: c use IDMT curves. Earth fault (neutral) (ANSI N or G) F0 to F0, F0, F0, F0, F0* The following types of time delay settings are available: definite, standard inverse, very inverse, extremely inverse or ultra inverse. Residual current detection can be provided by: c the three phase current transformers, in which case a harmonic restraint is used to do away with transformer closing related tripping. c a current transformer (or A), combined with a CSH0 interposing ring CT, c a CSH0 or CSH00 core balance CT, according to the required diameter, this method being the most accurate one. The two ratings available ( and 0A), provide a very wide setting range. c a different core balance CT, associated with the ACE 0 interface. Undervoltage (ANSI ) F, F, F, F, F, F* Protection used either for automated functions (changeover, load shedding) or for the protection of several motors against undervoltage. This function checks for undervoltage in each of the system voltages measured. Overvoltage (ANSI ) F0, F0* Protection against abnormally high voltage and checking that there is sufficient voltage for power supply changeover. This protection monitors system voltage U Neutral voltage displacement (ANSI N/) F* Detection of insulation faults in ungrounded systems by measurement of neutral voltage displacement. Directional overcurrent (ANSI ) F* Incomer protection, which provides quick, selective protection against upstream faults when there are several parallel power supply sources in the network. Directional earth fault (ANSI N) F0* This protection provides quick, selective detection of earth faults at the generator end when there are several incomers in parallel, each of which has an earthing system. Reverse real power (ANSI P) F* Protection against the transferring of power between sources, e.g. to prevent an autonomous means of energy generation from ouputting into the normal energy distributor power supply source.it is based on the "real overpower" F* function. Field loss (reverse reactive power) (ANSI Q/0) F* Protection of a synchronous machine against de-energizing which causes excessive consumption of reactive power. Underfrequency(ANSI L) F* Detection of variances with respect to the rated frequency, in order to maintain high quality power supply. This protection can be used for overall tripping or for load shedding. Overfrequency (ANSI H) F* Protection against abnormally high frequency. Temperature monitoring (RTDs) (ANSI /T) F... F, F... F* Protection which detects abnormal overheating of generators (bearings and/or windings) equiped with Pt 00 type platinum resistive temperature devices: c alarm setting, c trip setting. The RTD cabling is continuously monitored. Restricted earth fault (ANSI REF) F* Protection against phase-to-earth faults in three-phase windings with earthed neutral. Biased differential (ANSI G) F* Fast, sensitive motor protection against internal faults due to damaged insulation. The protection is based on the principle of percentage differentials. It includes starting current restraint to sustain stability in spite of its high level of sensibility. Synchro-check (ANSI ) F* Authorizes the closing of the breaking device, only if the two circuits have voltage, frequency and phase gaps within the planned limits. The choice of an operating mode with voltage absent allows the generator to be coupled with a de-energized installation. *Fxxx function identification used for protection setting using the TSM 00 pocket terminal. Current sensor sizing The current sensors used should be such that they will not be saturated by the current values which they are required to measure, with accuracy (at least In): c for definite time functions (DT):. times the setting current, c for IDMT functions (SIT, VIT, EIT and UIT):. times the greatest working value in the curve. Practical solution when setting information is lacking secondary CT power and resistance resistance current In accuracy class () CT secondary R CT wiring R W A. VA P 0 < Ω 0.0 Ω A. VA P 0 < 0. Ω 0.0 Ω () determination in accordance with class X allows the sensor current to be optimized with R CT secondary winding resistance, R W wiring resistance. c For restricted earth protection: The current transformers must be of the P0 type. The power rating must be chosen so that the wiring resistance (R w ) is less than the rated load of the current transformer (VA CT ), i.e.: VA CT > R w.in.

7 Setting ranges functions Fxxx () setting time delays phase overcurrent F0-F0-F0-F0 definite time DT 0. to In t: 0.0 to s IDMT () 0. to. In t: 0. to. s at 0 Is thermal overload F negative sequence/unbalance coefficient: 0;.;.; time constants: heating T: to 0 mn cooling T: to 00 mn warm state: 0% to 00% of nominal thermal capacity used tripping: 0% to 00% of nominal thermal capacity used voltage restrained overcurrent F definite time DT 0. to In t: 0.0 to s IDMT () 0. to. In t: 0. to. s at 0 Is negative sequence / unbalance F definite time 0. to Ib t: 0. to s IDMT 0. to 0. Ib t: 0. to s at Ib earth fault F0-F0-F0-F0 type of sensor F0-F0-F0-F0 definite time DT 0.0 to 0 In sum of phase currents t : 0,0 to s 0. to 0 A CSH core bal. CT, A. to 00 A CSH core bal. CT, 0 A 0.0 to 0 Ino A or A CT () 0.0 to 0 Ino core balance CT () IDMT () 0.0 to In sum of phase currents t: 0. to. s at 0 Iso 0. to A CSH core bal. CT, A. to 0 A CSH core bal. CT, 0 A 0.0 to Ino A or A CT () 0.0 to Ino core balance CT () harmonic restraint taken yes into account no undervoltage F-F-F-F-F-F % to 00% of Un t: 0.0 to s overvoltage F0-F0 0% to 0% of Un t: 0.0 to s neutral voltage displacement F % to 0% of Un if VT: Un/ /00/ t: 0.0 to s % to 0% of Un if VT: Un/ /00/ underfrequency F Hz to 0 Hz ( to 0 Hz) t: 0. to s overfrequency F 0Hz to Hz (0 to Hz) t: 0. to s directional earth fault F characteristic angle 0,, 0 definite time DT 0. to In t: 0.0 to s IDMT () 0. to. In t: 0. to. s at 0 Is directional earth fault F0 characteristic angle 0,, 0,, 0, 0 et - definite time DT 0.0 to 0 In sum of phase currents t: 0.0 to s 0. to 0 A CSH core bal. CT, A. to 00 A CSH core bal. CT, 0 A 0.0 to 0 Ino A or A CT () 0.0 to 0 Ino core balance CT () () function identification for protection setting. () IDMT curves: - inverse: SIT, - very inverse: VIT, - extremely inverse: EIT, - ultra inverse: UIT, - long time inverse: LTI. () with CSH 0 interposing ring CT. () core balance CT with ratio /n (0 i n i 00) with ACE 0 interface.

8 Protection (cont d) Setting ranges (cont d) functions Fxxx () setting time delays reverse real power F % to 0% of Sn (Sn = Un x In) t: 0. to s reactive reverse power F % to 0% of Sn (Sn = Un x In) t: 0. to s temperature monitoring (RTDs) F to F, F to F 0 C to 0 C restricted earth fault F-F 0.0 to 0. In if In u 0 A 0. to 0. In if In < 0 A biased differential F to 0 % with min. A synchro-check F voltage gap to 0% Un frequency gap 0.00 to 0. Hz phase gap to 0 degrees voltage present 0. to. Un voltage absent 0. to 0. Un Usync absent, Usync present mode Usync absent, Usync present mode (Usync absent, Usync present) mode or (Usync absent, Usync present) (Usync absent, Usync present) mode or (Usync absent, Usync present) or (Usync and Usync absent) anticipation ta: 0 to 0. s Reminder: rated current In, basis current Ib, rated voltage Un and current Ino are general parameters that are set at the time of Sepam 000 commissioning. In is the current sensor rated current (CT rating). Ib is the current which corresponds to the rated power of the generator. Un is the phase-to-phase voltage of the voltage sensor primary windings. Ino is the core balance CT current rating. Rated thermal a capacity use : corresponds to a steady current egal to Ib. () function identification for protection setting.

9 Control and monitoring Open / close control Used to control breaking devices equiped with different types of opening and closing coils: c circuit breaker with shunt-trip or undervoltage release coil, c latching contactor with shunt-trip coil, c contactor with impulse control. Parameter setting via the TSM 00 pocket terminal, or PC softwares (SFT 0 or SFT ), allows the logic to be adapted to suit the equipment being used (by default, the logic is adapted for control of a circuit breaker with a shunt-trip coil). The opening order (via input I) differs according to the programmed type of control: c normally open contact for shunt trip coil (circuit breaker or contactor with latched order control), c normally closed contact for undervoltage release coil (circuit breaker and contactor with impulse control). Lockout relay (ANSI ) Stores tripping orders (lockout) and requires user action to be put back into operation (reset). Inhibit closing (ANSI ) Inhibits the closing of the circuit breaker or the contactor according to operating conditions. Annunciation (ANSI 0) Keeps the user informed by the display of messages. Thermostat, Buchholz, DGPT, sondes PTC Traitement des défauts détectés avec les dispositifs intégrés dans l équipement : alarme, déclenchement et signalisation (utilisation avec les groupes-blocs). Logic discrimination (ANSI ) Enables quick, selective tripping of the phase overcurrent and earth fault protection relays, whether definite time (DT) or IDMT (standard inverse SIT, very inverse VIT, extremely inverse EIT or ultra inverse UIT). The function triggers the transmission of a "blocking input" signal whenever one of the protection settings is exceeded. Blocking input signal transmission can be used by the Sepam 000 Logic discrimination function for substation, generator, transformer and busbar connection applications. Trip circuit supervision and discrepancy (ANSI ) Detects tripping (by shunt-trip coil) circuit faults. Can be used when the Sepam 000 and the tripping auxiliary power sources have the same voltage rating. If the equipment contains an undervoltage release coil only, the tripping circuit is not supervised since it is fail-safe. This function can also detect position information discrepancies (neither open nor closed or simultaneously open and closed) in the different control schemes. The connection of inputs I, I and trip output O on the ESB board must be done according to other connection schemes. Group stop Orders the shutdown of the drive when internal faults occur. De-excitation Orders the de-excitation and stopping of the group. The stopping is initiated by internal fault or external trip order. De-excitation is initiated by internal fault detection, external de-excitation order. Detection of plugged connectors (ANSI ) Indication on the display unit that one or more connectors are not plugged in (the terminals must be connected: see connection schemes). Operation counter () Counts the number of closing operations made by the breaking device, thereby facilitating equipment maintenance. Running hours counter () Determines the time during which the breaking device (contactor or circuit breaker) is in the in service-closed position, i.e. the number of hours of operation (0 to hours). Phase fault trip counter () Counts the number of operations for which breaking performances were required, thereby facilitating equipment maintenance. Disturbance recording triggering Triggers recording of electrical signals and logical states by: c voluntary local or remote action, c instantaneous overcurrent, earth fault and directional protections, c protection tripping order. VT monitoring Indicates the absence of the voltage needed for synchro-check following the opening of the LV circuit breaker or the melting of striker fuses or the disconnection of the VTs. () counters reading is via serial link on the front panel of Sepam 000, and via Jbus/Modbus communication. Load shedding request Allows the closing of an output contact following the detection of undervoltage or underfrequency caused by a generator overload. This data may be used by the Sepam motor load shedding function.

10 Control and monitoring (cont d) Operation of all Sepam 000 types (except for G00) functions commands outputs annunciation trip inhibit lock alarm fault device messages () closing out trip fault O O O O O O O O O phase overcurrent c c c c () c () c OVERCURRENT thermal c c c c THERMAL overload (trip) thermal overload c THERMAL (alarm) voltage restrained c c c c () c () c O/C V REST overcurrent negative sequence/ c c c c UNBALANCE unbalance neutral c c c c () c () c EARTH FAULT earth fault c c c c () c () c E/F directional overcurrent c c c c () c () c DIR. O/C directional earth fault c c c c () c () c DIR. E/F restricted earth fault c c c c c c REF biased differential c c c c c c GENE DIFF undervoltage () c () () c () () c () () c () c () () UNDERVOLT. X overvoltage () c () c () c () c () c c () OVERVOLT. X neutral voltage c () c () c () c c () c () N VOLT DISP displacement underfrequency () c () () c () () c () c ) () UNDERFREQ. overfrequency c () () c () () c () c () () OVERFREQ. reverse real power c () c () c () c () c () REVERSE P field loss c () c () c () c () c () FIELD LOSS (reverse reactive power) temperature alarm c c RTD x (RTD) temperature c c c c RTD x tripping (RTD) RTD fault c RTD FAULT transformer alarm c c c TRANSFO transformer tripping c c c c TRANSFO PTC sensor aux. voltage c PTC FAULT external protection c c c c EXT. TRIP trip group stop c c c c c EXT. STOP de-excitation c c c c DE-EXCIT. pole pressure c c c PRESSURE synchro-check () c ()() ANGLE GAP () FREQ. GAP () VOLTAGE GAP () STOP SYNC. () VT monitoring () c c U. SYNC FAIL U. SYNC FAIL trip circuit c c c? CONTROL? supervision detection of plugged connectors () () on Sepam 000 display unit (according to language version). () depending on set up. () if breaker open. () if breaker closed. () for types of Sepam equiped with these functions. () appear after a synchronized closing request that has failed. () only to deactivate, according to set-up, reverse real and reactive power protection in medium-size generator-transformer unit applications. xx number of the RTD (from to according to the type of Sepam). CONNECTOR 0

11 Set up of all Sepam 000 types (except for G00) functions parameters open / close control KP KP circuit breaker with shunt-trip coil 0 0 circuit breaker with undervoltage release coil 0 latching contactor with tripping by shunt-trip coil 0 contactor with impulse control external protection input logic "external protection trip" (I) by NO contact KP = 0 by NC contact KP = counters reset to zero of operation counter KP = reset to zero of phase fault trip counter KP0 = reset to zero of running hours counter KP = other tripping by undervoltage threshold KP = by undervoltage threshold KP = by overvoltage threshold KP = by overvoltage threshold KP = by neutral voltage displacement KP = by underfrequency KP0 = by overfrequency KP = latching undervoltage threshold KP = undervoltage threshold KP = overvoltage threshold KP = overvoltage threshold KP = field loss by overvoltage threshold KP = by overvoltage threshold KP = group stop by reverse real power KP = display of set up control scheme KP = BI (Blocking Input) pilot wire test KP = remote setting remote setting enable KP = 0 disable KP = disturbance recording inhibition KP0 = automatic triggering KP = manual triggering KP = synchro-check (Sepam 000 G0 and G0 types) synchro-check with KP = 0 without KP = operating mode with voltage acknowledgment KP = no acknowledgment KP = 0 transformeur monitoring (Sepam 000 G and G types) transformers sensors by NO contact KP = 0 by NC contact KP = use of Sepam 000 G0, G0 and G types with G00 (generators-transformer units) desactivation of reverse real and reactive power KP =

12 Control and monitoring (cont d) Operation of Sepam 000 type G00 functions commands outputs lock out transmit messages () BI O O O O O O O O 0 0 phase overcurrent c c OVER CURRENT directional overcurrent c c c DIR. O/C neutral c c EARTH FAULT directional earth fault c c c DIR E/F restricted earth fault c c REF undervoltage c () c UNDERVOLT.x overvoltage c () c c () c () OVERVOLT.x underfrequency c () c () c () UNDERFREQ. overfrequency c c OVERFREQ. neutral voltage displacement c c N VOLT DISP reverse real power c c REVERSE P. field loss c c FIELD LOSS (reverse reactive power) Buchholz alarm c c () BUCHHOLZ Buchholz tripping c c () BUCHHOLZ thermostat alarm c c () TR. TEMP PTC alarm thermostat tripping c c () TR. TEMP PTC tripping gas detector c c () TR. GAS alarm (KP = ) gas detector c c () TR. GAS trippingt (KP = 0) pressure detector c c () TRPRESSURE PTC sensor auxiliary c () RTD FAULT voltage detection of pluged CONNECTOR connectors () () according to set-up (protection latching). () according to set-up (assignment of outputs: according to G00-A or new assignment).

13 Set up of Sepam 000 type G00 functions Buchholz / thermostat / DGPT logic inputs paramètres transformer sensors by NO contact KP = 0 by NC contact KP = input I, detection of gas or drop in level tripping KP = 0 latching alarm KP = underfrequency KP0 = undervoltage, setting KP = undervoltage, setting KP = overvoltage, setting KP = overvoltage, setting KP = assignment of inputs / outputs outputs 0 to 0 without transformer failures O undervoltage KP = 0 O overfrequency O underfrequency O overvoltage outputs 0 to 0 with transformer failures O undervoltage OR underfrequency KP = O overvoltage OR overfrequency O Buchholz / thermostat / DGPT with alarm O Buchholz / thermostat / DGPT with tripping input I : remote control enable enable if I = KP = (acknowledgment, remote setting) enable regardless of position of I KP = 0 remote setting remote setting enable KP = 0 remote setting desable KP = disturbance recording inhibition KP0 = automatic triggering KP = manual triggering KP = The parameters are set using the TSM 00 pocket terminal or the SFT 0 or SFT PC software program. The KP0 to KP parameters are of the impulse type.

14 Functional and connection schemes G0, G0 and G types L L L () A A U/Vo N 0V V P Q 0 CE0 B A A () G Pt00 n n n n n n 0 0 A SONDE T G0 G ESB CDG O O l l A 0 0 ().A.A terminal number for compact (S) Sepam 000 terminal number for standard (S) Sepam 000 * B A ECM 0 A A 0 0G G () A ESTOR A ESTOR A () A CSH * This scheme does not allow CSP sensors to be used. A SONDE T G N.B. Refer to the "other connection schemes" section regarding other arrangements. : detection of plugged connectors. CDG: watchdog c Correspondence between primary and secondary connection (i.e.: P, S). Standard SXR or compact SLT (G0) or SSR (G0) or SSS (G) Sepam 000.

15 Functional and connection schemes (cont d) G0 and G0 types L L L Usync A U/Vo CE0 B A ESB A 0 G Usync A U/Vo N P Q 0 CDG O O l l 0 * B ECM 0V 0 V 0G G ESTOR A * This scheme does not allow CSP sensors to be used. N.B. Refer to the "other connection schemes" section regarding other arrangements. : detection of plugged connectors. CDG: watchdog. () the busbar VT (U.SYNC) and the generator VT (U.SYNC) are connected to the same phase. CSH A 0 A A A SONDE T G0 ESTOR A c Correspondence between primary and secondary connection (e.g.: P, S). Standard STR (G0) or S TS(G0) Sepam 000.

16 Functional and connection schemes (cont d) G0, G0, G0, G0 and G types L L L A U/Vo N H L 0V V P Q 0 N G0 G0 CE0 B A ESB A 0 G * Pt00 n 0 B A A ECM 0 A A SONDE 0 0G G REF T G0 G CDG O O l l 0 n ESTOR A n 0 n n * This scheme does not allow CSP sensors to be used. n ESTOR A N.B. Refer to the "other connection schemes" section regarding other arrangements. : detection of plugged connectors. CDG: watchdog. CSH A SONDE T G c Correspondence between primary and secondary connection (i.e.: P, S). Standard SXR (G0) or SSR (G0) or SSS (G) Sepam 000.

17 G and G types L L L * A U/Vo N H L 0V V P Q 0 CE0 B A G * B A B ECM 0 A A ECM 0G G 0 G ESB CDG O O l l A 0 0 A Pt00 n 0 A SONDE T G ESTOR A n CSH n 0 * This scheme does not allow CSP sensors to be used. N.B. Refer to the "other connection schemes" section regarding other arrangements. : detection of plugged connectors. CDG: watchdog. () the busbar VT (U.SYNC) and the generator VT (U.SYNC) are connected to the same phase. n n n ESTOR A c Correspondence between primary and secondary connection (i.e.: P, S). Standard SLR (G) or SLS (G) Sepam 000.

18 Functional and connection schemes (cont d) G and G types Protection of small generator-transformer units L L L * B ECM 0 0N N CE0 B A A G * A B U/Vo ECM N H L 0 0G G 0V V P Q 0 ESB CDG O O l l A 0 0 A 0 A A ESTOR A Pt00 n 0 A SONDE T G * This scheme does not allow CSP sensors to be used. N.B. Refer to the "other connection schemes" section regarding other arrangements. : detection of plugged connectors. CDG: watchdog. () the busbar VT (U.SYNC) and the generator VT (U.SYNC) are connected to the same phase. c Correspondence between primary and secondary connection (i.e.: P, S). CSH n n n n 0 ESTOR A n Standard SLR (G) or SLS (G) Sepam 000.

19 G00 type To be combined with G0, G0 or G types to protect medium-size generator-transformer units. L L L A U/Vo N H L N P Q 0 CE0 B A B A ECM 0 A A 0 0G G REF ESB CDG O O l l A 0 0 ESTOR A G ESTOR A N.B. Refer to the "other connection schemes" section regarding other arrangements. : detection of plugged connectors. CDG: watchdog. c Correspondence between primary and secondary connection (i.e.: P, S). Compact SLT Sepam 000.

20 Functional and connection schemes (cont d) Sepam 000 combination of G00 and G0 types or G0 or G type L L L Protection of medium generator-transformer units A U/Vo N H L N P Q 0 G00 * B ECM 0 0G G REF A 0 A A ().A.A terminal number for compact (S) Sepam 000 terminal number for standard (S) Sepam 000 G () A A U/Vo N P** Q** V G0 G0 G * This scheme does not allow CSP sensors to be used. ** protections inhibited by set-up N.B. Refer to the "other connection schemes" section regarding other arrangements. : detection of plugged connectors. CDG: watchdog. c Correspondence between primary and secondary connection (i.e.: P, S). * B A ECM 0 A A 0 0G G CSH CE0, ESB and ESTOR boards not shown. 0

21 Other connection schemes Phase voltage L L L L L L A U/Vo A U/Vo Connection of a voltage transformer (does not allow implementation of the neutral voltage displacement and directional earth fault protection functions and residual voltage measurement). V-connection of voltage transformers (does not allow implementation of the neutral voltage displacement and directional earth fault protection functions and residual voltage measurement). Phase and residual voltage L L L A U/Vo Broken delta connection of voltage transformers for residual voltage measurement. c Correspondence between primary and secondary connection (i.e.: P, S).

22 Other connection schemes (cont d) Residual current with CT A or A L L L CSH0 B A ECM 0 A A CT + CSH 0 CSH0 P S P S turns For connection of A transformers make turns at the CSH 0 primary A ECM 0 A A CT + CSH0 with sensors other than CSH 0 or CSH 00 L L L /n 0 n 00 * ACE 0 * A ECM (*) The core balance CT-ACE 0 and ACE 0-Sepam 000 connections depend on the transformer ratio of the core balance CT and the current to be measured. Phase current L L L CCA 0 cable L L L L L L ECA A Connection of special-purpose CSP sensors according to type of Sepam 000. c Correspondence between primary and secondary connection (i.e.: P, S).

23 Examples of connections Logic input and output boards for all types (except for G00) ESB board ESB CDG O O l l A 0 0 open closing coil tripping coil ESB A 0 CDG O 0 O l l open closing coil tripping coil ESB CDG O O l l A 0 0 open contactor coil Circuit breaker or latching contactor tripping by a shunt-trip coil. Circuit breaker tripping by an undervoltage release coil. Tripping by undervoltage release coil of a contactor with impulse control. G00 type ESB board ESB A CDG O O l l 0 0 terminals data connected to ESB board watchdog O directional earth fault OR neutral 0 OR restricted earth fault O directional overcurrent OR phase overcurrent l not used l not used N.B. The inputs are potential-free and require an external power supply source.

24 Examples of connections (cont d) Logic input and output boards for G0, G0 and G types ESTOR board terminals data connected to ESTOR board ESTOR A 0 I remote control enable: enables closing and acknowledgment control via the serial link: contact closed for "enable" l l l l l l O or or () () I "drawn out" position: contact closed for "drawn out" I pole pressure: contact closed for "breaking pole fault" I external protection tripping: normally closed or normally open contact according to set up I close: NO contact I open: NO contact for shunt trip coil NC contact for undervoltage release coil () common O O O l l 0 O de-excitation 0 O device fault (pressure fault or control fault) O fault tripping O alarm: thermal overload, PTC sensor I receive "blocking input" (BI) I earthing switch: contact open for earthing switch open ESTOR board terminals data connected to ESTOR board I not used ESTOR l l l l l l O O O O A 0 0 I not used I not used I external control de-energizing N/O contact I coupling enabled (contact closed for enable) () I external control generator shutdown common O group stop 0 O not used O not used O not used I emergency stop (contact closed in normal operation) l l I reserved for external communication synchro. () If control by input I is not used: - for a shunt trip coil, I = 0 permanently, - for an undervoltage release coil, I = permanently. () parameterizable. N.B. The inputs are potential-free and require an external power supply source.

25 Logic input and output boards for G0 to G0, G, G, G, G and G types ESTOR board terminals data connected to ESTOR board ESTOR A 0 I remote control enable: enables closing and acknowledgment control via the serial link: contact closed for "enable" l l l l l l O or or () () I "drawn out" position: contact closed for "drawn out" I pole pressure: contact closed for "breaking pole fault" I external protection tripping: normally closed or normally open contact according to set up I close: NO contact I open: NO contact for shunt trip coil NC contact for undervoltage release coil () common O O O l l 0 O de-excitation 0 O device fault (pressure fault or control fault) O fault tripping O alarm: thermal overload, PTC sensor I receive "blocking input" (BI) I earthing switch: contact open for earthing switch open ESTOR board terminals data connected to ESTOR board ESTOR l l l l l l O O O O l l A 0 0 () I checking of PTC sensor box auxiliary voltage () I VT circuit closed (contact closed) () transformer sensors: tripping () I Busbar VT circuit closed (contact closed) () transformer sensors : alarm () I external control de-energizing N/O contact I coupling enabled (contact closed for enable) I external control generator shutdown common O group stop 0 O neutral voltage displacement O overvoltage, overfrequency O undervoltage, underfrequency I primary stop (contact closed in normal operation) I reserved for external communication synchro () G and G types only (NO or NC contact according to set-up). () G0 and G0 types only. N.B. The inputs are potential-free and require an external power supply source.

26 Examples of connections (cont d) Logic input and output boards for Sepam 000 G00 type ESTOR board ESTOR l l l l l l O O O O l l A 0 0 terminals data connected to ESTOR board I remote control enable I not used I not used I not used I not used I not used common O receive "blocking input" (BI) 0 O neutral voltage displacement O field loss (reverse reactive power) O real reverse power I receive BI (blocking input) I not used ESTOR board ESTOR l l l l l l O O O O l l A 0 0 terminals data connected to ESTOR board I Buchholz tripping I Buchholz alarm I thermostat tripping I thermostat alarm I DGP, pressure I DGP : gas, level common O () overvoltage (settings and ) OR Buchholz / thermostat / DGPT tripping 0 O () underfrequency OR Buchholz / thermostat / DGPT alarm O () overfrequency OR overfrequency OR overvoltage (settings and ) O () undervoltage (settings and ) OR underfrequency OU undervoltage (settings and ) I PTC sensors (auxiliary voltage) I reserved for external communication synchro () according to KP set-up. N.B. The inputs are potential-free and require an external power supply source.

27 MERLIN GERIN Communication Introduction The communication option can be used to connect Sepam 000 to a remote monitoring and control system equipped with a master communication channel. Sepam can be equiped with different communication options: c Jbus/Modbus, master-slave protocol with RS type -wire physical link (00 to 00 baud rate). c FIPIO, FIP ISIS (please consult us). Sepam 000 / remote monitoring and control system communication. Communication table G0, G0 and G types remote indications logic input status logic output status operation counter phase fault trip counter running hours counter control fault: tripping or matching remote control open/close fault position/remote control discrepancy external protection tripping Sepam not reset (after fault) device closed device drawn out breaking pole fault earthing switch closed remote control enable phase overcurrent thermal overload voltage restrained overcurrent negative sequence/unbalance neutral neutral voltage displacement reverse real power () field loss (reverse reactive power) () temperature alarm temperature trip RTD fault inhibited disturbance recording remote setting disable remote readout-remote setting protection function curves, set points, time delays, angles... program logic time delays address C C C KTS KTS KTS KTS KTS KTS0 KTS KTS KTS KTS KTS KTS KTS KTS KTS KTS KTS KTS KTS KTS0 KTS KTS0 KTS () except when used with G00 (generator-transformer unit). () remote control order set to and to 0 by communication not available with FIP option. remote measurements phase current max. demand phase currents phase-to-phase and phase-to-neutral voltage frequency real power reactive power peak demand real power peak demand reactive power power factor (p.f.) inductive or capactive network temperature (RTDs) real energy reactive energy tripping currents thermal capacity used residual current residual voltage cumulative breaking current number of trips remote control orders address priority «stop» (latched) () KTC group stop (latched) () «opening» «closing» fault acknowledgment (reset) max. demand phase current zero reset (clear) peak demand W and VAr zero reset (clear) tripping current zero reset (clear) inhibition disturbance recording automatic disturbance recording triggering manual disturbance recording triggering priority stop (latching) priority stop (unlatching) KTC KTC KTC KTC KTC KTC KTC KTC0 KTC KTC KTC KTC The data above is available via the optional communication link. The measurements available depend on the type of Sepam 000.

28 Communication (cont d) Communication table G0 and G0 types remote indications logic input status logic output status operation counter phase fault trip counter running hours counter control fault: tripping or matching remote control open/close fault position/remote control discrepancy external protection tripping Sepam not reset (after fault) device closed device drawn out breaking pole fault earthing switch closed remote control enable phase overcurrent thermal overload voltage restrained overcurrent negative sequence/unbalance neutral undervoltage, setting undervoltage, setting overvoltage, setting overvoltage, setting neutral voltage displacement underfrequency overfrequency reverse real power field loss (reverse reactive power) temperature alarm temperature trip RTD fault inhibited disturbance recording remote setting disable synchro-check active synchronism use of voltage absent mode angle gap frequency gap voltage gap stop synchronization remote readout-remote setting protection function curves, set points, time delays, angles... program logic time delays address C C C KTS KTS KTS KTS KTS KTS0 KTS KTS KTS KTS KTS KTS KTS KTS KTS KTS0 KTS KTS KTS KTS KTS KTS KTS KTS KTS KTS0 KTS KTS0 KTS KTS KTS KTS KTS KTS KTS KTS remote measurements phase current max. demand phase currents phase-to-phase and phase-to-neutral voltage frequency real power reactive power peak demand real power peak demand reactive power power factor (p.f.) inductive or capactive network temperature (RTDs) real energy reactive energy tripping currents thermal capacity used residual current residual voltage cumulative breaking current number of trips remote control orders address priority stop (latched) () KTC group stop (latched) () opening closing fault acknowledgment (reset) max. demand phase current zero reset (clear) peak demand W and VAr zero reset (clear) tripping current zero reset (clear) inhibition disturbance recording automatic disturbance recording triggering manual disturbance recording triggering priority stop (latching) priority stop (unlatching) use with voltage absent mode use without voltage absent mode closing enabled without use of synchro-check monitoring of closing with synchro-check KTC KTC KTC KTC KTC KTC KTC KTC0 KTC KTC KTC KTC KTC KTC KTC KTC The data above is available via the optional communication link. The measurements available depend on the type of Sepam 000. () remote control order set to and to 0 by communication not available with FIP option.

29 Communication table G0, G0, G0, G0 and G types remote indications address logic input status logic output status operation counter C phase fault trip counter C running hours counter C control fault: KTS tripping or matching remote control open/close fault KTS position/remote control KTS discrepancy external protection tripping KTS Sepam not reset (after fault) KTS device closed KTS0 device drawn out KTS breaking pole fault KTS earthing switch closed KTS remote control enable KTS phase overcurrent KTS thermal overload KTS voltage restrained overcurrent KTS negative sequence/unbalance KTS neutral KTS undervoltage, setting KTS0 undervoltage, setting KTS overvoltage, setting KTS overvoltage, setting KTS neutral voltage displacement KTS underfrequency KTS overfrequency KTS reverse real power KTS field loss KTS (reverse reactive power) temperature alarm KTS temperature trip KTS0 RTD fault KTS directional overcurrent KTS () directional earth fault KTS () machine differential KTS () restricted earth fault KTS inhibition disturbance recording KTS0 remote setting disable KTS remote readout-remote setting protection function curves, set points, time delays, angles... program logic time delays remote measurements phase current max. demand phase currents phase-to-phase and phase-to-neutral voltage frequency real power reactive power peak demand real power peak demand reactive power power factor (p.f.) inductive or capactive network temperature (RTDs) real energy reactive energy tripping currents thermal capacity used residual current residual voltage cumulative breaking current number of trips remote control orders address priority stop (latched) () KTC group stop (latched) () opening closing fault acknowledgment (reset) max. demand phase current zero reset (clear) peak demand W and VAr zero reset (clear) tripping current zero reset (clear) inhibition disturbance recording automatic disturbance recording triggering manual disturbance recording triggering priority stop (latching) priority stop (unlatching) KTC KTC KTC KTC KTC KTC KTC KTC0 KTC KTC KTC KTC The data above is available via the optional communication link. The measurements available depend on the type of Sepam 000. () remote control order set to and to 0 by communication not available with FIP option. () only for types which include this protection function.

30 Communication (cont d) Communication table G, G, G and G types remote indications logic input status logic output status operation counter phase fault trip counter running hours counter control fault: tripping or matching remote control open/close fault position/remote control discrepancy external protection tripping Sepam not reset (after fault) device closed device drawn out breaking pole fault earthing switch closed remote control enable phase overcurrent thermal overload voltage restrained overcurrent negative sequence/unbalance neutral undervoltage, setting undervoltage, setting overvoltage, setting overvoltage, setting neutral voltage displacement underfrequency overfrequency reverse real power field loss (reverse reactive power) temperature alarm temperature trip temperature sensor fault + PTC auxiliary voltage transformer sensors alarm transformer sensors tripping additional overcurrent protection biased differential earth fault inhibition disturbance recording remote setting disable address C C C KTS KTS KTS KTS KTS KTS0 KTS KTS KTS KTS KTS KTS KTS KTS KTS KTS0 KTS KTS KTS KTS KTS KTS KTS KTS KTS KTS0 KTS KTS KTS KTS KTS KTS0 KTS0 KTS remote readout-remote setting protection function curves, set points, time delays, angles... program logic time delays remote measurements phase current max. demand phase currents phase-to-phase and phase-to-neutral voltage frequency real power reactive power peak demand real power peak demand reactive power power factor (p.f.) inductive or capactive network temperature (RTDs) real energy reactive energy tripping currents thermal capacity used residual current residual voltage cumulative breaking current number of trips remote control orders address priority stop (latched) () KTC group stop (latched) () opening closing fault acknowledgment (reset) max. demand phase current zero reset (clear) peak demand W and VAr zero reset (clear) tripping current zero reset (clear) inhibition disturbance recording automatic disturbance recording triggering manual disturbance recording triggering priority stop (latching) priority stop (unlatching) KTC KTC KTC KTC KTC KTC KTC KTC0 KTC KTC KTC KTC The data above is available via the optional communication link. The measurements available depend on the type of Sepam 000. () remote control order set to and to 0 by communication not available with FIP option. 0

31 Communication table G00 type remote indications logic input status logic output status Sepam not reset (after fault) remote control enable phase overcurrent neutral undervoltage, setting undervoltage, setting overvoltage, setting overvoltage, setting neutral voltage displacement underfrequency overfrequency reverse real power field loss (reverse reactive power) directional overcurrent directional earth fault send blocking input temperature alarm (DGPT, PTC) alarms (gas, Buchholz, PTC O/V) tripping (pressure, Buchholz) temperature tripping (DGPT, PTC) restricted earth fault inhibition disturbance recording remote setting disable remote readout-remote setting protection function curves, set points, time delays, angles... program logic time delays address KTS KTS KTS KTS KTS0 KTS KTS KTS KTS KTS KTS KTS KTS KTS KTS0 KTS KTS KTS KTS KTS KTS KTS0 KTS remote measurements phase current max. demand phase currents phase-to-phase and phase-to-neutral voltage frequency real power reactive power peak demand real power peak demand reactive power power factor (p.f.) inductive or capactive network real energy reactive energy tripping currents residual current residual voltage remote control orders address fault acknowledgment (reset) KTC max. demand phase current KTC zero reset (clear) peak demand W and VAr KTC zero reset (clear) tripping current KTC zero reset (clear) inhibition disturbance recording KTC0 automatic disturbance recording KTC triggering manual disturbance recording KTC triggering The data above is available via the optional communication link. The measurements available depend on the type of Sepam 000. () remote control order set to and to 0 by communication not available with FIP option.

Protection and control. Sepam range Sepam 2000 SX

Protection and control. Sepam range Sepam 2000 SX Protection and control Sepam range Sepam 000 SX Presentation Contents page presentation selection table metering protection control and monitoring functional and connection schemes 9 other connection schemes

More information

Protection and control. Sepam range Sepam 2000 Metering and control

Protection and control. Sepam range Sepam 2000 Metering and control Protection and control Sepam range Sepam 000 Metering and control Presentation Contents page presentation selection table metering customized control logic standard control and monitoring functional and

More information

Protection and control. Sepam range Sepam 2000 Metering and protection functions

Protection and control. Sepam range Sepam 2000 Metering and protection functions Protection and control Sepam range Sepam 2 Metering and protection functions Contents chapter / page metering functions 1/1 protection functions 2/1 appendix 3/1 Notation c Sepam 2 may include several

More information

Protection and control. Sepam range Sepam 2000 Testing

Protection and control. Sepam range Sepam 2000 Testing Protection and control Sepam range Sepam Testing Contents chapter/page Sepam tests protection function tests / to /5 testing equipment, test wiring diagram / to /8 commissioning tests /9 test and setting

More information

Protection and control. Sepam range Sepam 1000 Substations Busbars Transformers Motors

Protection and control. Sepam range Sepam 1000 Substations Busbars Transformers Motors Protection and control Sepam range Substations Busbars Transformers Motors Presentation Contents page presentation selection table 4 metering 5 protection 6 control and monitoring 9 functional and connection

More information

Substation applications

Substation applications Substation applications To make it easy to choose the right for a protection application, the most typical applications are presented with the type of for them. Each sample application is presented by:

More information

presentation contents application advantages

presentation contents application advantages presentation contents page presentation protection functional and connection schemes other connection schemes connection characteristics 9 installation 0 commissioning ordering information Sepam 00 is

More information

Protection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique

Protection and control. Sepam range Sepam 100 LA Self-powering protection. Merlin Gerin Square D Telemecanique Protection and control Sepam range Sepam 0 LA Self-powering protection Merlin Gerin Square D Telemecanique presentation contents page presentation protection functional and connection schemes other connection

More information

Modular range of digital protection relays

Modular range of digital protection relays S e p a m s e r i e s 2 0, 4 0, 8 0 Modular range of digital protection relays Fast Dependable Simple Fast response Maximum dependability Your electrical equipment is under control. With Sepam protection

More information

NTG MULTIFUNCTON GENERATOR PROTECTION RELAY. NTG-Slide

NTG MULTIFUNCTON GENERATOR PROTECTION RELAY. NTG-Slide NTG MULTIFUNCTON GENERATOR PROTECTION RELAY 1 NTG Digital protection relay that integrates a number of functions required r for the protection of generators. It is used in power stations from gas, steam,

More information

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR). RETROFITTING Motor Protection Relay NPM800R (R2 case) and NPM800RE (R3 case) are dedicated to the refurbishment of 7000 series (R2 and R3 cases) of CEE relays providing the protection of medium voltage

More information

Centrale de mesure Power Meter PM500 Merlin Gerin

Centrale de mesure Power Meter PM500 Merlin Gerin Notice d'installation et d'utilisation Installation and user manual Centrale de mesure Power Meter PM500 Merlin Gerin 059473_D Introduction and description Package contents c one PM500 power meter with

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Protection of Electrical Networks. Christophe Prévé

Protection of Electrical Networks. Christophe Prévé Protection of Electrical Networks Christophe Prévé This Page Intentionally Left Blank Protection of Electrical Networks This Page Intentionally Left Blank Protection of Electrical Networks Christophe Prévé

More information

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment

T/3000 T/3000. Substation Maintenance and Commissioning Test Equipment T/3000 Substation Maintenance and Commissioning Test Equipment MULTI FUNCTION SYSTEM FOR TESTING SUBSTATION EQUIPMENT SUCH AS: CURRENT, VOLTAGE AND POWER TRANSFORMERS, ALL TYPE OF PROTECTION RELAYS, ENERGY

More information

PD300. Transformer, generator and motor protection Data sheet

PD300. Transformer, generator and motor protection Data sheet PD300 Transformer, generator and motor protection Data sheet DSE_PD300_eng_AO No part of this publication may be reproduced by whatever means without the prior written permission of Ingeteam T&D. One of

More information

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems Appendix C Numbering System for Protective Devices, Control and Indication Devices for Power Systems C.1 APPLICATION OF PROTECTIVE RELAYS, CONTROL AND ALARM DEVICES FOR POWER SYSTEM CIRCUITS The requirements

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and

More information

Contents. Introduction and description Package contents Device identification PM Options... 80

Contents. Introduction and description Package contents Device identification PM Options... 80 Contents 1 Introduction and description Package contents... 77 Device identification... 77 2 Characteristics PM500... 78 Options... 80 3 Installation Front-panel cut-out... 82 Mounting... 82 4 Connections

More information

Micrologic control units 2.0 E X Y Z. Overview of functions. Functions and characteristics

Micrologic control units 2.0 E X Y Z. Overview of functions. Functions and characteristics Overview of functions All Masterpact circuit breakers are equipped with a Micrologic control unit that can be changed on site. Control units are designed to protect Power circuits and loads. Alarms may

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, all type of protection relays, energy meters and transducers Primary injection testing capabilities

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features

200ADM-P. Current Injection System with Phase Shift A 3.000s 2.000A 50.00Hz 0.0. Features CT ratio Power Harmonics ac+dc 200ADM-P Current Injection System with Phase Shift Features 0-200A output current True RMS metering with 1 cycle capture Variable auxiliary AC voltage/current output with

More information

Technical catalogue. Emax Low voltage air circuit-breakers. Hotline:

Technical catalogue. Emax Low voltage air circuit-breakers.   Hotline: Technical catalogue Emax Low voltage air circuit-breakers www.alobitanbd.com Hotline: 01711548558 PAGE : 02 The new Emax have received innumerable international certifications and approval by the major

More information

APPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges.

APPLICATION: The heart of the system is a DSR 100 Digital Static Regulator used in conjunction with standard SCR based rectifier bridges. APPLICATION: Basler Electric offers a New Line of digitally controlled brush (static) or brushless excitation systems designed for use with existing Hydro, Gas as well as Diesel driven generators requiring

More information

SPAD 346 C Stabilized differential relay

SPAD 346 C Stabilized differential relay SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria

More information

N. TEST TEST DESCRIPTION

N. TEST TEST DESCRIPTION Multi function system for testing substation equipment such as: current, voltage and power transformers, over-current protection relays, energy meters and transducers Primary injection testing capabilities

More information

Generator Protection GENERATOR CONTROL AND PROTECTION

Generator Protection GENERATOR CONTROL AND PROTECTION Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault

More information

COPYRIGHTED MATERIAL. Index

COPYRIGHTED MATERIAL. Index Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,

More information

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS) AC CURRENT GENERATOR PERFORMANCES Wide range of current 50 db dynamic range Signal-to-noise ratio: 80 db open loop protection Stability < 0,1% Very low THD distortion < 0,3% External synchronization Build-up

More information

Transformer Fault Categories

Transformer Fault Categories Transformer Fault Categories 1. Winding and terminal faults 2. Sustained or uncleared external faults 3. Abnormal operating conditions such as overload, overvoltage and overfluxing 4. Core faults 1 (1)

More information

BUS2000 Busbar Differential Protection System

BUS2000 Busbar Differential Protection System BUS2000 Busbar Differential Protection System Differential overcurrent system with percentage restraint protection 1 Typical Busbar Arrangements Single Busbar Double Busbar with Coupler Breaker and a Half

More information

Data Sheet. RISH Master Record %THD

Data Sheet. RISH Master Record %THD Data Sheet %THD Application : measures important electrical parameters & replaces the multiple analog panel meters. It measures electrical parameters like AC current, Voltage, frequency, active energy

More information

REF 610 Feeder Protection Relay. Technical Reference Manual

REF 610 Feeder Protection Relay. Technical Reference Manual REF 610 1MRS 755310 Issued: 05.10.2004 Version: A/05.10.2004 REF 610 Contents 1. Introduction...6 1.1. About this manual...6 1.2. The use of the relay...6 1.3. Features...6 1.4. Guarantee...8 2. Safety

More information

PROTECTION of electricity distribution networks

PROTECTION of electricity distribution networks PROTECTION of electricity distribution networks Juan M. Gers and Edward J. Holmes The Institution of Electrical Engineers Contents Preface and acknowledgments x 1 Introduction 1 1.1 Basic principles of

More information

Power System Protection Manual

Power System Protection Manual Power System Protection Manual Note: This manual is in the formative stage. Not all the experiments have been covered here though they are operational in the laboratory. When the full manual is ready,

More information

PARAMETER LIST PARAMETER LIST

PARAMETER LIST PARAMETER LIST PRMETER LIST PRMETER LIST dvanced Genset Controller, GC 200 larm list Parameter list Document no.: 489340605L SW version 4.2.x or later GC 200 parameter list 489340605 UK Contents: General information...

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

TD 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

TD 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers Secondary Injection Relay Test Set Designed for testing relays and transducers Two current outputs to test differential relays Convertible current and voltage generator With phase angle shifter Frequency

More information

Replacement solution

Replacement solution Replacement solution for the ABB DPU2000R protection and control relay Specification File, Revision, Date (Pages) Replacement Relay Specification_ABB DPU2000R_0.doc, Revision 0, August 2, 2013 (37) Table

More information

Protective Relays Digitrip 3000

Protective Relays Digitrip 3000 New Information Technical Data Effective: May 1999 Page 1 Applications Provides reliable 3-phase and ground overcurrent protection for all voltage levels. Primary feeder circuit protection Primary transformer

More information

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT. MODBUS/BECO2200-M3425A Communication Data Base for M-3425A Integrated Protection System Device I.D. = 150 Specifications presented herein are thought to be accurate at the time of publication but are subject

More information

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator Test results and settings are saved into local memory

More information

Numerical Multi-Function Motor Protection Relay RHO 3. Operation & Maintenance Instruction Manual

Numerical Multi-Function Motor Protection Relay RHO 3. Operation & Maintenance Instruction Manual Numerical Multi-Function Motor Protection Relay RHO 3 Operation & Maintenance Instruction Manual RHO MANUAL Contents Section Page Description of operation 4 2 Performance specification 20 3 Relay settings

More information

Energy Management. Type WM14 DIN Advanced version. Product Description 3-phase advanced power analyzer with integrated programming

Energy Management. Type WM14 DIN Advanced version. Product Description 3-phase advanced power analyzer with integrated programming Energy Management Type WM14 DI version Protection degree (front): IP40 2 digital outputs 16 freely configurable alarms with OR/AD logic linkable with up to 2 digital outputs RS422/485 serial output (MODBUS-RTU),

More information

ASHIDA Numerical 3OC + 1EF Protection Relay

ASHIDA Numerical 3OC + 1EF Protection Relay PROTH. ERR L5 PKP FAULT DT REC LOCK BF L6 L7 CLOSE TRIP ADR 241B Protection Features : 4 Element (3 Phase + EF + Sensitive EF) Over current IDMT/DMT with instant trip. Programmable (Non- Volatile) Setting

More information

489 Generator Management Relay Instruction Manual

489 Generator Management Relay Instruction Manual Digital Energy Multilin Firmware Revision: 4.0X Manual Part Number: 1601-0150-AF Manual Order Code: GEK-106494P Copyright 2011 GE Multilin 489 Generator Management Relay Instruction Manual GE Multilin

More information

Transformer Protection

Transformer Protection Transformer Protection Nature of transformer faults TXs, being static, totally enclosed and oil immersed develop faults only rarely but consequences large. Three main classes of faults. 1) Faults in Auxiliary

More information

Overcurrent and Overload Protection of AC Machines and Power Transformers

Overcurrent and Overload Protection of AC Machines and Power Transformers Exercise 2 Overcurrent and Overload Protection of AC Machines and Power Transformers EXERCISE OBJECTIVE When you have completed this exercise, you will understand the relationship between the power rating

More information

Digital Multifunction Instrument - Rish Master 3440

Digital Multifunction Instrument - Rish Master 3440 Application Rish Master 3440 measures important electrical parameters in 3 phase and single phase etwork & replaces the multiple analog panel meters. It measures electrical parameters like AC current,

More information

MV network design & devices selection EXERCISE BOOK

MV network design & devices selection EXERCISE BOOK MV network design & devices selection EXERCISE BOOK EXERCISES 01 - MV substation architectures 02 - MV substation architectures 03 - Industrial C13-200 MV substation 04 - Max. distance between surge arrester

More information

Power factor correction and harmonic filtering. Automatic power factor regulators

Power factor correction and harmonic filtering. Automatic power factor regulators Power factor correction and harmonic filtering Automatic power factor regulators Automatic power factor reguladors R.1 - Automatic power factor regulators Selection table R1-4 computer Plus-T Intelligent

More information

INSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12

INSTRUCTION MANUAL. Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS. Power Factor Controller A12 INSTRUCTION MANUAL Power Factor Controller - 12 steps Model A12 NOKIAN CAPACITORS Power Factor Controller A12 1. CONTENTS 1. CONTENTS 1 2. FEATURES 2 3. INSTALLATION, CONNECTION AND APPLYING POWER 2 4.

More information

T 1000 PLUS Secondary Injection Relay Test Set

T 1000 PLUS Secondary Injection Relay Test Set Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator Test results and settings are saved into local memory

More information

4Q POWER AMPLIFIERS AC AND DC 3000VA 3x3000VA

4Q POWER AMPLIFIERS AC AND DC 3000VA 3x3000VA PERFORMANCES High accuracy High stability Fast transients High inrush current facilities Wide bandwidth 25 khz at -3dB Internal waveform DC and up to 10 khz Very low distortion Quadrant change without

More information

Power factor correction and harmonic filtering. Automatic power factor regulators R.1

Power factor correction and harmonic filtering. Automatic power factor regulators R.1 Power factor correction and harmonic filtering Automatic power factor regulators R.1 R.1 Automatic power factor regulators R.1 - Automatic power factor regulators Selection table R1-4 computer Plus-T Intelligent

More information

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES)

ALPHA 50 MULTIFUNCTION METER (ALPHA SERIES) Alpha Series www.sifamtinsley.co.uk Multifunction Meters Transducers & Isolators Temperature Controllers Converters & Recorders Digital Panel Meters Current Transformers Analogue Panel Meters Shunts ALPHA

More information

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers

T 1000 PLUS. Secondary Injection Relay Test Set. Designed for testing relays and transducers Secondary Injection Relay Test Set Designed for testing relays and transducers Microprocessor controlled With phase angle shifter Frequency generator High power outputs Large graphical display Compact

More information

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime Issued: 5.06.999 Status: 5.06.999 Version: B/09..00 Data subject to change without notice Features Overvoltage and undervoltage protection Single- or three-phase operation High-set overvoltage stage with

More information

Integration between the MV protection and control unit REF542 and the LV protection trip unit PR123: selectivity and earth fault 1SDC007402G0201

Integration between the MV protection and control unit REF542 and the LV protection trip unit PR123: selectivity and earth fault 1SDC007402G0201 1SDC007402G0201 Index 1. Introduction... 2 2. Theoretical outline 2.1 Restricted earth fault... 3 2.2 Selectivity between medium and low voltage... 4 3. Application examples and wiring logic 3.1 Restricted

More information

DIRIS A40 DIRIS A41. Functions. Conformity to standards. Applications. Energy management DIRIS A40. Network analysis

DIRIS A40 DIRIS A41. Functions. Conformity to standards. Applications. Energy management DIRIS A40. Network analysis diris_561_b_3_x_cat 1 1. Backlit LCD display. 2. Direct access key for currents and setup wiring correction. 3. Direct access key for voltages and frequency. 4. Direct access key for active, reactive,

More information

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:

More information

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Additional Options 15kV Isolation

More information

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation

Excitation Systems THYRIPART. Compound-Excitation System for Synchronous Generators. Power Generation Excitation Systems Compound-Excitation System for Synchronous Generators Power Generation Operating Characteristics Load dependent Short circuit supporting Low voltage gradient dv/dt Black start capability

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements Applicability 1(1) Section 502.1 applies to the ISO, and subject to the provisions of subsections 1(2), (3) and (4) to any: (a) a new wind aggregated generating facility to be connected to the transmission

More information

VI 3 - i TABLE OF CONTENTS

VI 3 - i TABLE OF CONTENTS VI 3 - i TABLE OF CONTENTS 3 PROJECT SPECIFIC DATA... 1 3.1 DEFINITIONS... 1 3.1.1 Design Data, High and Medium Voltage... 1 3.1.2 Design Data, Low Voltage Equipment... 2 3.1.3 Phase Relationship... 3

More information

Advanced Test Equipment Rentals ATEC (2832)

Advanced Test Equipment Rentals ATEC (2832) Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) The toolbox for substation 3-phase testing Three currents and four voltages Stand-alone functionality Rugged and reliable

More information

CROSS Chassis from 160 A to 450 A

CROSS Chassis from 160 A to 450 A CROSS Chassis from 160 A to 450 A STS CATALOGUE Important note! The technical data enclosed is for general information. Please note that the operating instructions and references indicated on the products

More information

DM-III Multitest & DM-III Multitest F Power Quality Recorders

DM-III Multitest & DM-III Multitest F Power Quality Recorders DM-III Multitest & DM-III Multitest F Power Quality Recorders CAT 600V TRUE RMSz Amprobe s full-featured Three-Phase Power Quality Recorders provide the essential functions and capabilities required to

More information

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49

UNIVERSAL MEASURING INSTRUMENTS. TNM 34xx. TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument 1/49 TNM 3410 / 3420 / 3430 / 3440 Universal measuring instrument True RMS measurement User-friendly programing Four different types for optimal specification RS485 interface For 3- or 4-wire connection Compact

More information

ASHIDA Numerical Directional 3OC + 1EF Protection Relay

ASHIDA Numerical Directional 3OC + 1EF Protection Relay Ashida Numerical Directional 3O/C + 1E/F PROTH. PROTH. ERR L5 FAULT PKP PKP FAULT L6 PT DT REC LOCK BF L7 CLOSE TRIP TRIP CLOSE ADR 145B 245B Protection Features: 4 Element (3 Phase + EF +sensitive EF)

More information

Meters. Ampere Meter. Volt Meter. Watt Meter. Var. Meter. Power Factor Meter. Frequency Meter. Demand Meter. Meter Relay.

Meters. Ampere Meter. Volt Meter. Watt Meter. Var. Meter. Power Factor Meter. Frequency Meter. Demand Meter. Meter Relay. Meters Ampere Meter Volt Meter Watt Meter Var. Meter Power Factor Meter Frequency Meter Outside Connection (Watt, PF, Var) 3 2 7 Receive Indicator Meter Demand Meter Meter Relay Meter Dimensions Meter

More information

Motor Protection. May 31, Tom Ernst GE Grid Solutions

Motor Protection. May 31, Tom Ernst GE Grid Solutions Motor Protection May 31, 2017 Tom Ernst GE Grid Solutions Motor Relay Zone of Protection -Electrical Faults -Abnormal Conditions -Thermal Overloads -Mechanical Failure 2 Setting of the motor protection

More information

Multimeter 500CVD21 RTU500 series

Multimeter 500CVD21 RTU500 series Remote Terminal Units - Data sheet Multimeter 500CVD21 RTU500 series CT/VT interface with 4 voltage and 24 current inputs for direct monitoring of 3/4 wire 0 300 V AC (line to earth), 0...500 V AC (phase

More information

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D Document type Page Verksamhetsstyrande 1 (11) Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D17-0008990 1.0 Organisation Valid from Valid until Regionnätsaffärer

More information

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX SSE-N NEGATIVE FIELD FORCING SHUNT STATIC EXCITER/REGULATOR SYSTEM Control Chassis 6 SCR Power Chassis APPLICATION The SSE-N Negative Field Forcing Exciter/Regulator is used for both new and old installations

More information

DIFFERENTIAL CURRENT GENERATOR «POCDIF» (AC/DC - 32A - 50V - 12 ranges)

DIFFERENTIAL CURRENT GENERATOR «POCDIF» (AC/DC - 32A - 50V - 12 ranges) PERFORMANCES 12 ranges of AC current from 16 ma to 128 A peak AC permanent current up to 26 ARMS Nine ranges of DC permanent current from 16 ma to 12 A DC current ± 6mA or ± 10 ma stackable to AC current

More information

NX Series Inverters. HVAC Pocket Programming Guide

NX Series Inverters. HVAC Pocket Programming Guide NX Series Inverters HVAC Pocket Programming Guide HVAC Pocket Programming Guide HVAC Pocket Programming Guide / Contents This guide provides a single reference document for the user of NXL HVAC (product

More information

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide Relion 605 series Relion 605 series Self-Powered Feeder Protection Product Guide Contents 1 Description...3 2 Protection functions...3 3 Application...4 4 Self-supervision...4 5 Inputs and outputs...4

More information

1 INTRODUCTION ORDER CODE / INFORMATION

1 INTRODUCTION ORDER CODE / INFORMATION INTRODUCTION ORDER CODE / INFORMATION 269/269Plus * * * * * * 269/269Plus SV D/O.4 ORDER CODE / INFORMATION Motor management relay Standard version Drawout version Phase CT Ground CT (required for D/O

More information

Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613

Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613 Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613 Data Bulletin 0613IB1201 06/2012 Retain for future use. 0613IB1201 Modbus Communications System for Micrologic A, P, and H

More information

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) 1MRS752324-MUM Issued: 3/2000 Version: D/23.06.2005 Data subject to change without notice PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2) Contents 1. Introduction... 2 1.1

More information

DEIF A/S. Description of options. Option H1 Serial communication CAN open. Description of options. Functional description. Tables.

DEIF A/S. Description of options. Option H1 Serial communication CAN open. Description of options. Functional description. Tables. Description of options Option H1 Serial communication CAN open 4189340277G SW version 2.42.X Description of options Functional description DEIF A/S Tables Parameter list Object dictionary DEIF A/S, Frisenborgvej

More information

Transformer Protection Principles

Transformer Protection Principles Transformer Protection Principles 1. Introduction Transformers are a critical and expensive component of the power system. Due to the long lead time for repair of and replacement of transformers, a major

More information

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy Reyrolle Protection Devices 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Description Additional Options Solkor

More information

SVERKER 900 Relay and Substation Test System

SVERKER 900 Relay and Substation Test System SVERKER 900 The toolbox for substation 3-phase testing Three currents and four voltages Stand-alone functionality Rugged and reliable for field use Generation of 900 V and 105 A in single phase mode Secondary

More information

DRTS 66 The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters

DRTS 66 The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters The new generation of advanced test equipments for Relays, Energy meters, Transducers and Power quality meters Testing all relay technologies: electromechanical, solid state, numerical and IEC61850 Manual

More information

Fixed Series Compensation

Fixed Series Compensation Fixed Series Compensation High-reliable turnkey services for fixed series compensation NR Electric Corporation The Fixed Series Compensation (FSC) solution is composed of NR's PCS-9570 FSC control and

More information

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC

Catalogue 1SFC en, Edition 3 November 2003 Supersedes Catalogue 1SFC en, Edition 2 November Arc Guard System TVOC Catalogue 1SFC 266006-en, Edition 3 November 2003 Supersedes Catalogue 1SFC 266006-en, Edition 2 November 2000 Arc Guard System TVOC System units The two units of the are used as below: Approvals 1. with

More information

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELECTRICAL ENGINEERING DIVISION Distribution Network Department SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS ELA T150.2 en SRA 2250/6 Resistor specification The SRA 2250/6 Resistor is intended to increase

More information

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements Division 502 Technical Applicability 1(1) Section 502.1 applies to: Expedited Filing Draft August 22, 2017 the legal owner of an aggregated generating facility directly connected to the transmission system

More information

Burdens & Current Transformer Requirements of MiCOM Relays. Application Notes B&CT/EN AP/B11. www. ElectricalPartManuals. com

Burdens & Current Transformer Requirements of MiCOM Relays. Application Notes B&CT/EN AP/B11. www. ElectricalPartManuals. com Burdens & Current Transformer Requirements of MiCOM Relays Application Notes B&CT/EN AP/B11 Application Notes B&CT/EN AP/B11 Burdens & CT Req. of MiCOM Relays Page 1/46 CONTENTS 1. ABBREVIATIONS & SYMBOLS

More information

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions 1 Transmission transformers are important links in the bulk power system. They allow transfer of power from generation centers, up to the high-voltage grid, and to bulk electric substations for distribution

More information

ZHUHAI PILOT TECHNOLOGY CO., LTD.

ZHUHAI PILOT TECHNOLOGY CO., LTD. SPM32 Multifunctional Power Meter SPM32 Multifunction Power Meter Installation & Operation Manual V1.0 ZHUHAI PILOT TECHNOLOGY CO., LTD. Danger and warning! This device can be installed only by professionals.

More information

Power Plant and Transmission System Protection Coordination Fundamentals

Power Plant and Transmission System Protection Coordination Fundamentals Power Plant and Transmission System Protection Coordination Fundamentals NERC Protection Coordination Webinar Series June 2, 2010 Jon Gardell Agenda 2 Objective Introduction to Protection Generator and

More information

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice Issued: April 1999 Status: Updated Version: B/08.11.200 Data subject to change without notice Features Versatile, multifunction line fault indicator for distribution networks Overcurrent, earth-fault and

More information

CROMPTON INSTRUMENTS INTEGRA 1222 DIGITAL METERING SYSTEM

CROMPTON INSTRUMENTS INTEGRA 1222 DIGITAL METERING SYSTEM CROMPTON INSTRUMENTS INTEGRA 1222 DIGITAL METERING SYSTEM The Crompton Instruments INTEGRA 1222 digital metering system (dms) from TE Connectivity enables cost effective solution for the measurement and

More information

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS INSTRUCTION MANUAL BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS 1/23 More information than that reported

More information

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W Page 2 / 16 INDEX: GENERAL TYPES ACESSORIES AND OPTIONS INSTALLATION WIRING DIAGRAMS CONNECTING TERMINALS DIAGRAMS WIRING DIAGRAM DESCRIPTION WORKING DESCRIPTION AND KEYBOARD WORKING DESCRIPTION AND PROGRAMMING

More information