Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications

Size: px
Start display at page:

Download "Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications"

Transcription

1 Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications Technical Report to the Line Protection Subcommittee of the PES, Power Systems Relaying Committee Presented by Working Group D-3 Line Protection Subcommittee

2 Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications Working Group D-3 Members: John Appleyard, Jeffrey Barsch, Gabriel Benmouyal, Art Buanno, Randy Crellin, Randy Cunico, Normann Fischer, Michael Fleck, Robert Frye, Charles Henville, Meyer Kao (Chair), Shoukat Khan, Gary Kobet, Alex Lee, Don Lukach, Walter McCannon, Joe Mooney, Jim O brien, Cristian Paduraru, Suhag Patel, Russell Patterson, Frank Plumptre, Elmo Price (Vice-chair), Ryland Revelle, Sinan Saygin, Mark Schroeder, Steve Turner

3 What is Polarization The process of comparing a reference phasor, voltage or current, to line current phasor to determine the direction to a fault The reference phasor is generally referred to as the polarizing quantity Basis for design of directional elements

4 Why Use It for Ground Overcurrent Application In a network transmission system, ground overcurrent elements can be very difficult to coordinate Ground directional elements are used to supervise ground overcurrent elements so that they only operate for faults in a desired direction

5 Sequence Network for Ground Faults

6 Sequence Network for Ground Faults, Cont. G * LINE H I 1, I 2, I 0 X A-G *Tertiary not loaded I P RELAY V 2, V 0 Z G0 Z TM0 Z TH0 Z L0 Z H0 I 0 I P Z TL0 V 0 Zero

7 Polarizing Methods for Ground Directional Elements Zero sequence voltage Negative sequence voltage Zero sequence current Dual Polarizing, combination of zero sequence voltage and zero sequence current Negative sequence and zero sequence impedance Virtual polarizing Voltage compensation

8 System Vectors, Balanced and During a Single Line to Ground (SLG) Fault

9 Zero and Negative Sequence Voltage Polarizing Source Sequence voltages are obtained from the three phase to neutral voltages, or -3V0 obtained from broken delta connection

10 Zero and Negative Sequence Voltage Directional Operating Characteristics

11 Zero Sequence Current (Current Polarizing) Polarizing Source + P R H + P R M (a) Υ (b) Υ Υ R M Virtually always OK + P + P (c) Zig-zag OK at times R N + P (d) Auto with tertiary

12 Zero Sequence Current (Current Polarizing) Directional Operating Characteristics Operating Sensitivity Minimum Levels Non-operating Region Reverse Operating Regio n Forwa rd Operating Regio n I pol (Polarizing) 3I 0 (Operating) Transformer Zero Sequence Current Polarized Directional Ground Fault Function

13 Dual Polarizing, Combination of Zero Seq. Voltage and Zero Seq. Current

14 Dual Polarizing, Multiple Directional Element Designs Electromechanical Designs Separate voltage polarized and current polarized units with their forward (closing torque) operating contacts arranged in parallel so that either unit may indicate forward ground fault direction A single directional unit that has both polarizing elements acting simultaneously on the same unit, so that a single contact that operates on the sum of the torque is developed by the two methods

15 Dual Polarizing, Multiple Directional Element Designs, Cont. Numerical Relay Designs Paralleling (OR gate) of the appropriate outputs of the two methods, however, the voltage polarizing unit is blocked if polarizing current is available. The voltage unit will only operate if polarizing current is not available.

16 Dual Polarizing, Multiple Directional Element Designs, Cont. Numerical Relay Designs, Cont. Dual polarization by summing the polarizing voltage phasor, 3V0, and the polarizing current phasor rotated by the angle α, the arg(v0/i0) for a strong forward fault.

17 Other Methods Negative and zero sequence impedance Negative sequence Impedance: ZZ 2 = RRRR VV 2 θθ 2 II 2 II 2 2 Zero sequence Impedance: ZZ 0 = RRRR VV 0 θθ 0 II 0 II 0 2

18 Other Methods, Cont. Virtual polarization Based on phase selector has identified the faulted phase Phase Selector Pickup A Phase Fault B Phase Fault C Phase Fault No selection Virtual Residual, VN polarizing V B + V C V A + V C V A + V B V A + V B + V C

19 Other Methods, Cont. Voltage Compensation Either negative or zero sequence voltage compensation Long line and resistive fault applications; low operating current and strong source with low source impedance Vpol = -V 0A + I 0R * K*e jrca ; care when choosing K so that the direction is not forward for a reverse fault Z 0A I 0R = I 0A Z 0L I 0B Z 0B I 0A REL A V 0A = - I 0A Z 0A K V 0K = - I 0A(Z 0A+K) REL B

20 Application Consideration of Different Methods Zero sequence mutually coupled lines Line and source impedance consideration Mismatch of polarization methods on line terminals in communication assisted trip scheme Other considerations

21 Zero Sequence Mutually Coupled Lines: Application Example (Zero Seq. Voltage and Zero Seq. Current Polarized) Station 1 Station 2 500kV 57mi Z 0 =0.044pu 40% Other lines Z 0M =0.04pu 85% Other lines Station 3 161kV 27mi Z 0 =0.25pu R R

22 Fault on 500kV Bus at Station 1 (Neglect Mutual Coupling) Station 1 X 3I 0 =2510A Other lines 500kV 57mi 3I 0 =480A Z 0 =0.044pu Other lines Station 2 Station 3 161kV 27mi Z 0 =0.25pu R Without mutual coupling R 100A 3Io -3Vo Reverse fault -3Vo Forward fault 3Io

23 Fault on 500kV Bus at Station 1, Partial Zero Seq. Network (Neglect Mutual Coupling) Station 1 500kV 2510A Station 2 R X 480A Z 0L Station 3 To negative sequence network MidPt R 69kV MidPt 100A V 0 To positive sequence network

24 Fault on 500kV Bus at Station 1 (With Mutual Coupling) At Station 3, forward direction asserted for both zero sequence voltage and current polarizing elements Station 1 X 3I 0 =2740A 40% Other lines 500kV 57mi Z 0M =0.04pu 85% 3I 0 =470A Z 0 =0.044pu Other lines Station 2 Station 3 161kV 27mi Z 0 =0.25pu With mutual coupling 3Io -3Vo Forward fault Forward fault -3Vo R 3Io R 70A

25 Fault on 500kV Bus at Station 1, Partial Zero Seq. Network (With Mutual Coupling) Station 1 500kV X 2740A 1:1 Station 2 Z 0L 470A R Station 3 To negative sequence network MidPt R Z 0M 69kV MidPt 70A V 0 To positive sequence network

26 Evaluation of Polarizing Method Considering Line and Source Impedance, Z0 and Z2

27 Simplified Sequence Network at the Fault Location Z1S Z1L Z1 = Z1S+Z1L Phase-to-ground V A1 V A1 Phase-to-phaseto-ground Z2S Z2L Z2 = Z2S+Z2L Z1 V A2 V A2 Z0S Z0L Z0 = Z0S+Z0L V A0 V A0

28 Magnitude of Sequence Voltages Vary with Fault Type and the Z0/Z1 Ratio, As Viewed from the Fault Point Single Line-to-Ground (SLG) VV AAA = VV AAA = ZZ 0 ZZ 1 ZZ 0 ZZ ZZ 0 ZZ Line-to-Line-to-Ground (LLG) VV AAA = VV AAA = ZZ 0 ZZ 1 2ZZ 0 ZZ 1 + 1

29 Evaluation of Polarizing Method Considering Line and Source Impedance, Z0 and Z2 Observations: If the system is homogeneous, that is if the ratios of source to line impedances are similar in the zero and negative sequence networks then the ratios of voltages at the relay will be the same as at the fault. Because line zero sequence impedance is roughly three times that of positive/negative sequence impedance, zero sequence voltage polarizing is superior.

30 Evaluation of Polarizing Method Considering Line and Source Impedance, Z0 and Z2 Observations (Cont.): Where the system is not homogeneous, the relative zero and negative sequence voltages at the relay can be easily estimated for ground fault at any point on the line VV AA0RR VV AAAAA = ZZ 0 ZZ 2 1+ nn ZZ 1LL ZZ 1SS 1+ nn ZZ 0LL ZZ 0SS VV AAAAA = 1+ nn ZZ 1LL ZZ 1SS VV AAAAA 1+ nn ZZ 0LL ZZ 0SS SLG LLG

31 Evaluation of Polarizing Method Considering Line and Source Impedance, Z0 and Z2 Observations (Cont.): The magnitude of the negative- or zerosequence voltages are directly proportional to the current and the source impedance behind the relay location. Therefore, it can be seen that given a long line with a strong source behind the relay (Z2L >> Z2S or Z0L >> Z0S) the negative or zero-sequence voltage at the relay location can be relatively small.

32 Evaluation of Polarizing Method Considering Line and Source Impedance, Z0 and Z2 Observations (Cont.): To evaluate the choice of the sequence voltages at the relay, the magnitude of zero and negative sequence voltages at the relay can be estimated for ground fault at end of the line VV AAAAA = VV AAAAA = 1 1 ZZ 0 ZZ 1 +2 ZZ 2LL ZZ 2SS +1 ZZ 0 ZZ 1 1 ZZ 0 ZZ 1 +2 ZZ 0LL ZZ 0SS +1 per unit per unit

33 Inadequate Negative Sequence Voltage Example Z S+ =0.01pu Z S0 =0.02pu Phase-to-ground line- Station 1 3I 0 =760A end fault Station 2 240/1 161kV 96mi Z + =0.3pu Z 0 =0.74pu X 1400/1 V 2 =590V I 2 =250A R NOTE: All quantities at Station 1 are after the breaker at Station 2 has tripped Breaker trips by ground instantaneous

34 Sources of Error in calculating V2 and V0 Untransposed Lines V A V A V A V B av C 3V 0 3V 2 V C a 2 V b V C V B Compute 3V 0 Compute 3V 2 Normally Expected Phase and Sequence Fault Voltages, A Phase SLG

35 Sources of Error in calculating V2 and V0 Untransposed Lines, Cont. V A V A V A V B av C 3V 0 V C V C V B 3V 2 a 2 V b Compute 3V 0 Compute 3V 2 Phase and Sequence Fault Voltages Showing Reversal of 3V 0, A Phase SLG

36 Sources of Error in calculating V2 and V0 Untransposed Lines, Cont. V A V A V A av C V B 3V 0 3V 2 a 2 V b V C V B V C Compute 3V 0 Compute 3V 2 Phase and Sequence Fault Voltages Showing Reversal of 3V 2, A Phase SLG

37 Mismatch of polarization methods on line terminals in communication assisted trip scheme Bus F, relay system K: Zero sequence voltage and current polarized Bus H, relay system M: Negative sequence voltage polarized

38 Mismatch of polarization methods on line terminals in communication assisted trip scheme, Cont.

39 Mismatch of polarization methods on line terminals in communication assisted trip scheme, Cont. Sequence Currents (IFH2 and IFH0) in Per Unit of If on Line FH for Different Fault Locations on Line FG m Distance from Bus F

40 Mismatch of polarization methods on line terminals in communication assisted trip scheme, Cont. The negative and zero sequence currents will flow in opposite directions on line FH for faults between 0.45 and p.u. of line FG length as measured from Bus F m IFH IFH

41 Other Considerations Single pole open affecting an adjacent line Series compensated lines or lines near series compensated lines and static var compensator Inherently directional; strong source impedance behind and weak forward source impedance Current polarizing at stations with more than one transformer and split low-sides Modeling of ground directional element in software

42 Recommendation on Choosing Appropriate Method Configuration: Short and medium length lines (SIR > 0.5) Long lines** (SIR 0.5) DCB or POTT Relay at the remote terminal with zero sequence polarizing Significant Zero Sequence Mutual Coupling Negative Sequence Voltage Zero Sequence (Voltage, Current, or Dual) No OK* OK* Yes OK* NR No SR OK* Yes SR NR No NR OK* Yes NR SR * - OK, but study recommended NR - Not recommended SR - Study required ** - special compensation may be required or inherent directionality may make directional control unnecessary

43 Summary: Choice of polarizing method for directional ground elements is an important decision that should not be overlooked or reduced to a cookie-cutter approach. Each application should be carefully evaluated for adequacy. Manufacturer recommendations and/or traditional utility practices should never be used in lieu of thorough study of the particular relay in question on the protected line.

Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications

Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications Working Group D-3, Line Protection Subcommittee IEEE PES Power System Relaying Committee Considerations in Choosing Directional Polarizing Methods for Ground Overcurrent Elements in Line Protection Applications

More information

What s New in C IEEE Guide for Protective Relay Applications to Transmission Lines Western Protective Relay Conference

What s New in C IEEE Guide for Protective Relay Applications to Transmission Lines Western Protective Relay Conference What s New in C37.113-2015 IEEE Guide for Protective Relay Applications to Transmission Lines 2017 Western Protective Relay Conference History Revision of C37.113-1999 Application of relays and protection

More information

Transmission Line Applications of Directional Ground Overcurrent Relays. Working Group D24 Report to the Line Protection Subcommittee January 2014

Transmission Line Applications of Directional Ground Overcurrent Relays. Working Group D24 Report to the Line Protection Subcommittee January 2014 Transmission Line Applications of Directional Ground Overcurrent Relays Working Group D24 Report to the Line Protection Subcommittee January 2014 Working Group Members: Don Lukach (Chairman), Rick Taylor

More information

What s New in C TM -2015, IEEE Guide for Protective Relay Applications to Transmission Lines

What s New in C TM -2015, IEEE Guide for Protective Relay Applications to Transmission Lines What s New in C37.113 TM -2015, IEEE Guide for Protective Relay Applications to Transmission Lines This paper is a product of the IEEE PSRC D36 Working Group. The working group consisted of the following

More information

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME

AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME AUTOMATIC CALCULATION OF RELAY SETTINGS FOR A BLOCKING PILOT SCHEME Donald M. MACGREGOR Electrocon Int l, Inc. USA eii@electrocon.com Venkat TIRUPATI Electrocon Int l, Inc. USA eii@electrocon.com Russell

More information

Relaying 101. by: Tom Ernst GE Grid Solutions

Relaying 101. by: Tom Ernst GE Grid Solutions Relaying 101 by: Tom Ernst GE Grid Solutions Thomas.ernst@ge.com Relaying 101 The abridged edition Too Much to Cover Power system theory review Phasor domain representation of sinusoidal waveforms 1-phase

More information

Using a Multiple Analog Input Distance Relay as a DFR

Using a Multiple Analog Input Distance Relay as a DFR Using a Multiple Analog Input Distance Relay as a DFR Dennis Denison Senior Transmission Specialist Entergy Rich Hunt, M.S., P.E. Senior Field Application Engineer NxtPhase T&D Corporation Presented at

More information

NEW DESIGN OF GROUND FAULT PROTECTION

NEW DESIGN OF GROUND FAULT PROTECTION NEW DESIGN OF GROUND FAULT PROTECTION J. Blumschein*, Y. Yelgin* *SIEMENS AG, Germany, email: joerg.blumschein@siemens.com Keywords: Ground fault protection, directional element, faulted phase selection

More information

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB

This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB This webinar brought to you by the Relion product family Advanced protection and control IEDs from ABB Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter,

More information

Defining and Measuring the Performance of Line Protective Relays

Defining and Measuring the Performance of Line Protective Relays Defining and Measuring the Performance of Line Protective Relays Edmund O. Schweitzer, III, Bogdan Kasztenny, Mangapathirao V. Mynam, Armando Guzmán, Normann Fischer, and Veselin Skendzic Schweitzer Engineering

More information

DOUBLE-ENDED FAULT LOCATORS

DOUBLE-ENDED FAULT LOCATORS The InterNational Electrical Testing Association Journal FEATURE END-TO-END TESTING OF DOUBLE-ENDED FAULT LOCATORS BY STEVE TURNER, Beckwith Electric Company, Inc.. www.netaworld.org FOR HIGH VOLTAGE,

More information

Generator Protection GENERATOR CONTROL AND PROTECTION

Generator Protection GENERATOR CONTROL AND PROTECTION Generator Protection Generator Protection Introduction Device Numbers Symmetrical Components Fault Current Behavior Generator Grounding Stator Phase Fault (87G) Field Ground Fault (64F) Stator Ground Fault

More information

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes Transmission Line Protection Objective General knowledge and familiarity with transmission protection schemes Transmission Line Protection Topics Primary/backup protection Coordination Communication-based

More information

Directional Elements in L-PRO 4000

Directional Elements in L-PRO 4000 Directional Elements in L-PRO 4000 ERLPhase Power Technologies Ltd. All Rights Reserved. 1 Objectives This Technical Note clarifies: 1. Directional Elements used in L-PRO 4000: A. Default Directional Element

More information

Protecting Large Machines for Arcing Faults

Protecting Large Machines for Arcing Faults Protecting Large Machines for Arcing Faults March 2, 2010 INTRODUCTION Arcing faults occur due to dirty insulators or broken strands in the stator windings. Such faults if undetected can lead to overheating

More information

Transmission Protection Overview

Transmission Protection Overview Transmission Protection Overview 2017 Hands-On Relay School Daniel Henriod Schweitzer Engineering Laboratories Pullman, WA Transmission Line Protection Objective General knowledge and familiarity with

More information

Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There? What Is a Distance Protection Element?

Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There? What Is a Distance Protection Element? Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There? Edmund O. Schweitzer, III and Bogdan Kasztenny Schweitzer Engineering Laboratories Copyright SEL 2017

More information

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection

Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection Transmission Lines and Feeders Protection Pilot wire differential relays (Device 87L) Distance protection 133 1. Pilot wire differential relays (Device 87L) The pilot wire differential relay is a high-speed

More information

COPYRIGHTED MATERIAL. Index

COPYRIGHTED MATERIAL. Index Index Note: Bold italic type refers to entries in the Table of Contents, refers to a Standard Title and Reference number and # refers to a specific standard within the buff book 91, 40, 48* 100, 8, 22*,

More information

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525.

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525. Time Overcurrent Relays More or less approximates thermal fuse» Allow coordination with fuses Direction of Current nduced Torque Restraining Spring Reset Position Time Dial Setting Disk Basic equation

More information

Tutorial on Symmetrical Components

Tutorial on Symmetrical Components Tutorial on Symmetrical Components Part : Examples Ariana Amberg and Alex Rangel, Schweitzer Engineering Laboratories, nc. Abstract Symmetrical components and the per-unit system are two of the most fundamental

More information

DIRECTIONAL PROTECTION

DIRECTIONAL PROTECTION UNIVERSITY OF LJUBLJANA FACULTY OF ELECTRICAL ENGINEERING DIRECTIONAL PROTECTION Seminar work in the course Distribution and industrial networks Mentor: Prof. Grega Bizjak Author: Amar Zejnilović Ljubljana,

More information

Pinhook 500kV Transformer Neutral CT Saturation

Pinhook 500kV Transformer Neutral CT Saturation Russell W. Patterson Tennessee Valley Authority Presented to the 9th Annual Fault and Disturbance Analysis Conference May 1-2, 26 Abstract This paper discusses the saturation of a 5kV neutral CT upon energization

More information

Distance Element Performance Under Conditions of CT Saturation

Distance Element Performance Under Conditions of CT Saturation Distance Element Performance Under Conditions of CT Saturation Joe Mooney Schweitzer Engineering Laboratories, Inc. Published in the proceedings of the th Annual Georgia Tech Fault and Disturbance Analysis

More information

Directional STANDARDS: Overcurrent Relaying

Directional STANDARDS: Overcurrent Relaying A CABLE Technicians TESTING Approach to Directional STANDARDS: Overcurrent Relaying Understanding O V E R V I E W and O F Testing T H E Directional Relays 1 Moderator n Ron Spataro AVO Training Institute

More information

Protection Introduction

Protection Introduction 1.0 Introduction Protection 2 There are five basic classes of protective relays: Magnitude relays Directional relays Ratio (impedance) relays Differential relays Pilot relays We will study each of these.

More information

Ground Fault Protection of Pilot Schemes: Basics and Applications

Ground Fault Protection of Pilot Schemes: Basics and Applications Ground Fault Protection of Pilot Schemes: Basics and Applications Yiyan Xue, Jay Zeek, Manish Thakhar, Bill Zhang, Weidong Zhang American Electric Power Company Abstract- The detection of ground fault

More information

Summary Paper for C IEEE Guide for Application of Digital Line Current Differential Relays Using Digital Communication

Summary Paper for C IEEE Guide for Application of Digital Line Current Differential Relays Using Digital Communication Summary Paper for C37.243 IEEE Guide for Application of Digital Line Current Differential Relays Using Digital Communication by: Neftaly Torres, P.E. 70 th Annual Conference for Protective Relay Engineers,

More information

Distance Protection in Distribution Systems: How It Assists With Integrating Distributed Resources

Distance Protection in Distribution Systems: How It Assists With Integrating Distributed Resources 1 Distance Protection in Distribution Systems: How It Assists With Integrating Distributed Resources David Martin and Pankaj Sharma, Hydro One Networks Inc. Amy Sinclair and Dale Finney, Schweitzer Engineering

More information

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network Preface p. iii Introduction and General Philosophies p. 1 Introduction p. 1 Classification of Relays p. 1 Analog/Digital/Numerical p. 2 Protective Relaying Systems and Their Design p. 2 Design Criteria

More information

Disturbance Analysis Enhances the Art and Science of Protective Relaying

Disturbance Analysis Enhances the Art and Science of Protective Relaying Disturbance Analysis Enhances the Art and Science of Protective Relaying Presented to Western Protective Relay Conference 2011 Spokane, Washington, USA Authored by Mukesh Nagpal, Ralph Barone, Xing Chen,

More information

Utility Interconnection and System Protection

Utility Interconnection and System Protection Utility Interconnection and System Protection Alex Steselboim President, Advanced Power Technologies, Inc. Utility paralleling vs. isolated operation. Isochronous kw load sharing Reactive power (VAR) sharing

More information

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006

MODEL POWER SYSTEM TESTING GUIDE October 25, 2006 October 25, 2006 Document name Category MODEL POWER SYSTEM TESTING GUIDE ( ) Regional Reliability Standard ( ) Regional Criteria ( ) Policy ( ) Guideline ( x ) Report or other ( ) Charter Document date

More information

Protective Relaying for DER

Protective Relaying for DER Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed

More information

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG

A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG A NEW DIRECTIONAL OVER CURRENT RELAYING SCHEME FOR DISTRIBUTION FEEDERS IN THE PRESENCE OF DG CHAPTER 3 3.1 INTRODUCTION In plain radial feeders, the non-directional relays are used as they operate when

More information

System Protection and Control Subcommittee

System Protection and Control Subcommittee Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller

Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer. Anura Perera, Paul Keller Shortcomings of the Low impedance Restricted Earth Fault function as applied to an Auto Transformer Anura Perera, Paul Keller System Operator - Eskom Transmission Introduction During the design phase of

More information

Communication Aided Tripping. Common Methods, Schemes and Considerations

Communication Aided Tripping. Common Methods, Schemes and Considerations Communication Aided Tripping Common Methods, Schemes and Considerations Presented by: Matt Horvath, P.E. March 13, 2017 Content Summary Background Purpose Methods and Mediums Schemes Considerations Application:

More information

PROTECTION SIGNALLING

PROTECTION SIGNALLING PROTECTION SIGNALLING 1 Directional Comparison Distance Protection Schemes The importance of transmission system integrity necessitates high-speed fault clearing times and highspeed auto reclosing to avoid

More information

Obtaining a Reliable Polarizing Source for Ground Directional Elements in Multisource, Isolated-Neutral Distribution Systems

Obtaining a Reliable Polarizing Source for Ground Directional Elements in Multisource, Isolated-Neutral Distribution Systems Obtaining a Reliable Polarizing Source for Ground Directional Elements in Multisource, Isolated-Neutral Distribution Systems Jeff Roberts, Normann Fischer, Bill Fleming, and Robin Jenkins Schweitzer Engineering

More information

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS 1 STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS Z. GAJIĆ S. HOLST D. BONMANN D. BAARS ABB AB, SA Products ABB AB, SA Products ABB AG, Transformers ELEQ bv Sweden Sweden Germany Netherlands zoran.gajic@se.abb.com

More information

This document covers common questions concerning the design of an effectively grounded system.

This document covers common questions concerning the design of an effectively grounded system. This document covers common questions concerning the design of an effectively grounded system. To prevent against temporary overvoltage conditions when a line-to-ground fault occurs on the power grid.

More information

Transformer Protection

Transformer Protection Transformer Protection Transformer Protection Outline Fuses Protection Example Overcurrent Protection Differential Relaying Current Matching Phase Shift Compensation Tap Changing Under Load Magnetizing

More information

Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There?

Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There? Distance Protection: Why Have We Started With a Circle, Does It Matter, and What Else Is Out There? Edmund O. Schweitzer, III and Bogdan Kasztenny Schweitzer Engineering Laboratories, Inc. 2018 IEEE. Personal

More information

Relay-assisted commissioning

Relay-assisted commissioning Relay-assisted commissioning by Casper Labuschagne and Normann Fischer, Schweitzer Engineering Laboratories (SEL) Power transformer differential relays were among the first protection relays to use digital

More information

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2 BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY The BE1-67N Ground Directional Overcurrent Relay provides ground fault protection for transmission and distribution lines by sensing the direction and magnitude

More information

g GE POWER MANAGEMENT

g GE POWER MANAGEMENT 745 FREQUENTLY ASKED QUESTIONS 1 I get a communication error with the relay when I try to store a setpoint. This error can occur for several different reasons. First of all, verify that the address is

More information

Protection Challenges for Transmission Lines with Long Taps

Protection Challenges for Transmission Lines with Long Taps Protection Challenges for Transmission Lines with Long Taps Jenny Patten, Majida Malki, Quanta Technology, Matt Jones, American Transmission Co. Abstract Tapped transmission lines are quite common as they

More information

An Alternative Method for Obtaining the Optimal. Directional Characteristic Angle of Directional. Overcurrent Relays in Transmission Networks

An Alternative Method for Obtaining the Optimal. Directional Characteristic Angle of Directional. Overcurrent Relays in Transmission Networks Contemporary Engineering Sciences, Vol. 11, 2018, no. 4, 149-164 HIKARI Ltd, www.m-hikari.com https://doi.org/10.12988/ces.2018.8111 An Alternative Method for Obtaining the Optimal Directional Characteristic

More information

Distance Relay Response to Transformer Energization: Problems and Solutions

Distance Relay Response to Transformer Energization: Problems and Solutions 1 Distance Relay Response to Transformer Energization: Problems and Solutions Joe Mooney, P.E. and Satish Samineni, Schweitzer Engineering Laboratories Abstract Modern distance relays use various filtering

More information

Practical Setting Considerations for Protective Relays That Use Incremental Quantities and Traveling Waves

Practical Setting Considerations for Protective Relays That Use Incremental Quantities and Traveling Waves Practical Setting Considerations for Protective Relays That Use Incremental Quantities and Traveling Waves Bogdan Kasztenny, rmando Guzmán, Normann Fischer, Mangapathirao V. Mynam, and Douglas Taylor Schweitzer

More information

USING SUPERIMPOSED PRINCIPLES (DELTA) IN PROTECTION TECHNIQUES IN AN INCREASINGLY CHALLENGING POWER NETWORK

USING SUPERIMPOSED PRINCIPLES (DELTA) IN PROTECTION TECHNIQUES IN AN INCREASINGLY CHALLENGING POWER NETWORK USING SUPERIMPOSED PRINCIPLES (DELTA) IN PROTECTION TECHNIQUES IN AN INCREASINGLY CHALLENGING POWER NETWORK P Horton, S Swain patricia.horton@ge.com, simon.swain@ge.com UK INTRODUCTION Superimposed techniques

More information

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc. 770 565-1556 John@L-3.com 1 Protection Fundamentals By John Levine 2 Introductions Tools Outline Enervista Launchpad

More information

10/15/ /16/ :00 pm - 7:00 pm Registration - Red Lion Hotel at the Park Convention Office

10/15/ /16/ :00 pm - 7:00 pm Registration - Red Lion Hotel at the Park Convention Office 10/15/2012 5:00 pm - 7:00 pm Registration - Red Lion Hotel at the Park Convention Office 5:00 pm - 9:00 pm Visit Vendor Suites - Red Lion Hotel at the Park 10/16/2012 7:45 am - 8:00 am Welcome by Dr. Anjan

More information

Considerations and Experiences in Implementing Ground Differential Protection for Transformer Protection at TVA

Considerations and Experiences in Implementing Ground Differential Protection for Transformer Protection at TVA Considerations and Experiences in Implementing Ground Differential Protection for Transformer Protection at TVA Meyer Kao - Consultant, Gary Kobet - Tennessee Valley Authority George Pitts -Tennessee Valley

More information

ELECTRICAL POWER TRANSMISSION TRAINER

ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER ELECTRICAL POWER TRANSMISSION TRAINER This training system has been designed to provide the students with a fully comprehensive knowledge in Electrical Power Engineering

More information

Performance of Time-Domain Line Protection Elements on Real-World Faults

Performance of Time-Domain Line Protection Elements on Real-World Faults Performance of Time-Domain Line Protection Elements on Real-World Faults Edmund O. Schweitzer, III, Bogdan Kasztenny, and Mangapathirao V. Mynam Schweitzer Engineering Laboratories, Inc. Presented at the

More information

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering Expo - Nov. 3, 2014 Index Normal Distribution System

More information

Modeling and Performance Analysis of Mho-Relay in Matlab

Modeling and Performance Analysis of Mho-Relay in Matlab Modeling and Performance Analysis of Mho-Relay in Matlab Purra Sai Kiran M.Tech Student, Padmasri Dr. B V Raju Institute of Technology, Narsapur, Medak, Telangana. ABSTRACT: This paper describes the opportunity

More information

Power systems Protection course

Power systems Protection course Al-Balqa Applied University Power systems Protection course Department of Electrical Energy Engineering 1 Part 5 Relays 2 3 Relay Is a device which receive a signal from the power system thought CT and

More information

70 TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS TEXAS A&M UNIVERSITY COLLEGE STATION, TEXAS APRIL 3 APRIL 6, 2017

70 TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS TEXAS A&M UNIVERSITY COLLEGE STATION, TEXAS APRIL 3 APRIL 6, 2017 70 TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS TEXAS A&M UNIVERSITY COLLEGE STATION, TEXAS APRIL 3 APRIL 6, 2017 MICROPROCESSOR RELAY DIRECTIONAL CHANGE DURING CURRENT REVERSAL MICHEAL DAVIS, JR,

More information

Distance Protection. Course No: E Credit: 4 PDH. Velimir Lackovic, Char. Eng.

Distance Protection. Course No: E Credit: 4 PDH. Velimir Lackovic, Char. Eng. Distance Protection Course No: E04-034 Credit: 4 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay

www. ElectricalPartManuals. com Transformer Differential Relay MD32T Transformer Differential Relay Transformer Differential Relay The MD3T Transformer Differential Relay is a member of Cooper Power Systems Edison line of microprocessor based protective relays. The MD3T relay offers the following functions:

More information

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants

A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants A Tutorial on the Application and Setting of Collector Feeder Overcurrent Relays at Wind Electric Plants Martin Best and Stephanie Mercer, UC Synergetic, LLC Abstract Wind generating plants employ several

More information

Performance of Relaying During Wide-area Stressed Conditions

Performance of Relaying During Wide-area Stressed Conditions Performance of Relaying During Wide-area Stressed Conditions IEEE Power Systems Relaying Committee C12 Working Group Report Presented by Pratap Mysore HDR Engineering Inc. July 25, 2012, San Diego, CA

More information

Earth Fault Protection

Earth Fault Protection Earth Fault Protection Course No: E03-038 Credit: 3 PDH Velimir Lackovic, Char. Eng. Continuing Education and Development, Inc. 9 Greyridge Farm Court Stony Point, NY 10980 P: (877) 322-5800 F: (877) 322-4774

More information

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions ENOSERV 2014 Relay & Protection Training Conference Course Descriptions Day 1 Generation Protection/Motor Bus Transfer Generator Protection: 4 hours This session highlights MV generator protection and

More information

Overcurrent Elements

Overcurrent Elements Exercise Objectives Hands-On Relay Testing Session Overcurrent Elements After completing this exercise, you should be able to do the following: Identify overcurrent element settings. Determine effective

More information

Transformer protection IED RET 670

Transformer protection IED RET 670 Gunnar Stranne Transformer protection IED RET 670 Santiago Septiembre 5, 2006 1 Transformer protection IED RET670 2 Introduction features and applications Differential protection functions Restricted Earth

More information

Waterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology

Waterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology Waterpower '97 August 5 8, 1997 Atlanta, GA Upgrading Hydroelectric Generator Protection Using Digital Technology Charles J. Beckwith Electric Company 6190-118th Avenue North Largo, FL 33773-3724 U.S.A.

More information

Forward to the Basics: Selected Topics in Distribution Protection

Forward to the Basics: Selected Topics in Distribution Protection Forward to the Basics: Selected Topics in Distribution Protection Lee Underwood and David Costello Schweitzer Engineering Laboratories, Inc. Presented at the IEEE Rural Electric Power Conference Orlando,

More information

Catastrophic Relay Misoperations and Successful Relay Operation

Catastrophic Relay Misoperations and Successful Relay Operation Catastrophic Relay Misoperations and Successful Relay Operation Steve Turner (Beckwith Electric Co., Inc.) Introduction This paper provides detailed technical analysis of several catastrophic relay misoperations

More information

Hands-On-Relay School 2015 Distribution Event Analysis. Randy Spacek Protection Engineer Manager

Hands-On-Relay School 2015 Distribution Event Analysis. Randy Spacek Protection Engineer Manager Hands-On-Relay School 2015 Distribution Event Analysis Randy Spacek Protection Engineer Manager OVERVIEW Available Tools Fault Type Identification: line and transformer Relay Event Record: Oscillography

More information

Time-current Coordination

Time-current Coordination 269 5.2.3.1 Time-current Coordination Time that is controlled by current magnitude permits discriminating faults at one location from another. There are three variables available to discriminate faults,

More information

Phase Comparison Relaying

Phase Comparison Relaying MULTILIN GER-2681B GE Power Management Phase Comparison Relaying PHASE COMPARISON RELAYING INTRODUCTION Phase comparison relaying is a kind of differential relaying that compares the phase angles of the

More information

Microgrid Protection

Microgrid Protection Panel: Microgrid Research and Field Testing IEEE PES General Meeting, 4-8 June 7, Tampa, FL Microgrid Protection H. Nikkhajoei, Member, IEEE, R. H. Lasseter, Fellow, Abstract In general, a microgrid can

More information

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web: Phone: (818) 734-5300 Fax: (818) 734-5320 Web: www.capstoneturbine.com Technical Reference Capstone MicroTurbine Electrical Installation 410009 Rev F (October 2013) Page 1 of 31 Capstone Turbine Corporation

More information

889 Advanced Generator Protection Technical Note

889 Advanced Generator Protection Technical Note GE Grid Solutions 8 Series 889 Advanced Generator Protection Technical Note GE Publication Number: GET-20056 Copyright 2017 GE Multilin Inc. Overview The Multilin 889 is part of the 8 Series platform that

More information

DISTRIBUTION DEVICE COORDINATION

DISTRIBUTION DEVICE COORDINATION DISTRIBUTION DEVICE COORDINATION Kevin Damron & Calvin Howard Avista Utilities Presented March th, 08 At the 5 th Annual Hands-On Relay School Washington State University Pullman, Washington TABLE OF CONTENTS

More information

SPAD 346 C Stabilized differential relay

SPAD 346 C Stabilized differential relay SPAD 346 C Stabilized differential relay Stabilized Differential Relay Type SPAD 346 C Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Unit Protection Differential Relays

Unit Protection Differential Relays Unit Protection PROF. SHAHRAM MONTASER KOUHSARI Current, pu Current, pu Protection Relays - BASICS Note on CT polarity dots Through-current: must not operate Internal fault: must operate The CT currents

More information

Ultra-High-Speed Relaying for Transmission Lines

Ultra-High-Speed Relaying for Transmission Lines Ultra-High-Speed Relaying for Transmission Lines Copyright SEL 2015 Focus for Today Benefits of faster line protection Limitations of present-day phasor-based protection Principles of time-domain protection

More information

, ,54 A

, ,54 A AEB5EN2 Ground fault Example Power line 22 kv has the partial capacity to the ground 4,3.0 F/km. Decide whether ground fault currents compensation is required if the line length is 30 km. We calculate

More information

Real and Reactive Power Control by using 48-pulse Series Connected Three-level NPC Converter for UPFC

Real and Reactive Power Control by using 48-pulse Series Connected Three-level NPC Converter for UPFC Real and Reactive Power Control by using 48-pulse Series Connected Three-level NPC Converter for UPFC A.Naveena, M.Venkateswara Rao 2 Department of EEE, GMRIT, Rajam Email id: allumalla.naveena@ gmail.com,

More information

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell Power Plant and Transmission System Protection Coordination GSU Phase Overcurrent (51T), GSU Ground Overcurrent (51TG), and Breaker Failure (50BF) Protection NERC Protection Coordination Webinar Series

More information

Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK

Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK Implementation and Evaluation a SIMULINK Model of a Distance Relay in MATLAB/SIMULINK Omar G. Mrehel Hassan B. Elfetori AbdAllah O. Hawal Electrical and Electronic Dept. Operation Department Electrical

More information

International Journal for Research in Applied Science & Engineering Technology (IJRASET) Distance Protection Scheme for Transmission Lines

International Journal for Research in Applied Science & Engineering Technology (IJRASET) Distance Protection Scheme for Transmission Lines Technology (IJRSET Distance Protection Scheme for Transmission Lines S.Tharun Kumar 1, M.Karthikeyan 2, M.nand 3, S.K.Surya 4 1,3,4 Department of EEE, 2 ssistant Professor, Department of EEE Velammal Engineering

More information

Analog Simulator Tests Qualify Distance Relay Designs to Today s Stringent Protection Requirements

Analog Simulator Tests Qualify Distance Relay Designs to Today s Stringent Protection Requirements Analog Simulator Tests Qualify Distance Relay Designs to Today s Stringent Protection Requirements Zexin Zhou and Xiaofan Shen EPRI China Daqing Hou and Shaojun Chen Schweitzer Engineering Laboratories,

More information

Stabilized Differential Relay SPAD 346. Product Guide

Stabilized Differential Relay SPAD 346. Product Guide Issued: July 1998 Status: Updated Version: D/21.03.2006 Data subject to change without notice Features Integrated three-phase differential relay, three-phase overcurrent relay and multiconfigurable earth-fault

More information

Babak Enayati National Grid Thursday, April 17

Babak Enayati National Grid Thursday, April 17 2014 IEEE PES Transmission & Distribution Conference & Exposition Impacts of the Distribution System Renewable Energy Resources on the Power System Protection Babak Enayati National Grid Thursday, April

More information

Protection of Extra High Voltage Transmission Line Using Distance Protection

Protection of Extra High Voltage Transmission Line Using Distance Protection Protection of Extra High Voltage Transmission Line Using Distance Protection Ko Ko Aung 1, Soe Soe Ei Aung 2 Department of Electrical Power Engineering Yangon Technological University, Insein Township

More information

Synchronism Check Equipment

Synchronism Check Equipment MULTILIN GER-2622A GE Power Management Synchronism Check Equipment SYNCHRONISM CHECK EQUIPMENT K. Winick INTRODUCTION Synchronism check equipment is that kind of equipment that is used to check whether

More information

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner

Data. Dr Murari Mohan Saha ABB AB. KTH/EH2740 Lecture 3. Data Acquisition Block. Logic. Measurement. S/H and A/D Converter. signal conditioner Digital Protective Relay Dr Murari Mohan Saha ABB AB KTH/EH2740 Lecture 3 Introduction to Modern Power System Protection A digital protective relay is an industrial microprocessor system operating in real

More information

NERC Protection Coordination Webinar Series July 15, Jon Gardell

NERC Protection Coordination Webinar Series July 15, Jon Gardell Power Plant and Transmission System Protection Coordination Reverse Power (32), Negative Sequence Current (46), Inadvertent Energizing (50/27), Stator Ground Fault (59GN/27TH), Generator Differential (87G),

More information

System Protection and Control Seminar

System Protection and Control Seminar System Protection and Control Seminar Desirable Protection We want to detect a fault within 100% of the zone of protection. We want to avoid interrupting non-faulted zones of protection. We want to clear

More information

Busbars and lines are important elements

Busbars and lines are important elements CHAPTER CHAPTER 23 Protection of Busbars and Lines 23.1 Busbar Protection 23.2 Protection of Lines 23.3 Time-Graded Overcurrent Protection 23.4 Differential Pilot-Wire Protection 23.5 Distance Protection

More information

Testing Numerical Transformer Differential Relays

Testing Numerical Transformer Differential Relays Feature Testing Numerical Transformer Differential Relays Steve Turner Beckwith Electric Co., nc. ntroduction Numerical transformer differential relays require careful consideration as to how to test properly.

More information

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78)

Power Plant and Transmission System Protection Coordination of-field (40) and Out-of. of-step Protection (78) Power Plant and Transmission System Protection Coordination Loss-of of-field (40) and Out-of of-step Protection (78) System Protection and Control Subcommittee Protection Coordination Workshop Phoenix,

More information

Protecting Feeders With Distributed Resource Scott Elling HDR Inc HDR, all rights reserved.

Protecting Feeders With Distributed Resource Scott Elling HDR Inc HDR, all rights reserved. Protecting Feeders With Distributed Resource Scott Elling HDR Inc. 2015 HDR, all rights reserved. Background Several Hundred Mega Watts of distributed PV Distribution Grid is no longer radial Protection

More information

ELEMENTS OF FACTS CONTROLLERS

ELEMENTS OF FACTS CONTROLLERS 1 ELEMENTS OF FACTS CONTROLLERS Rajiv K. Varma Associate Professor Hydro One Chair in Power Systems Engineering University of Western Ontario London, ON, CANADA rkvarma@uwo.ca POWER SYSTEMS - Where are

More information