1 Application Installation requirements for commercial services from Tacoma Power overhead or underground facilities. It applies to new construction or upgrades of older services. Electrical service may be provided in the following three methods: In This Standard I. Overhead Service II. Underground Service from Padmount Transformer III. Underground Service from Polemount Transformer (UGP) Topic See Page Terms 1 Responsibilities & Inspections 2 I Overhead Service 3 II Underground Service from Padmount Transformer 3 III Underground Service from Polemount Transformer (UGP) 3-11 Limitations 3 Selection of Conduit from Pole to SSB 4 Selection of SSB 5 SSB (Bottomless Plastic Enclosure) 6-7 SSB (Precast Concrete Vault) 8-11 Conduit Entry 11 Terms Term Construction Inspector Electrical Inspector Electrical Secondary Electrical Service New Services Engineer Secondary Service Box (SSB) Definition Representative from Tacoma Power T&D Construction Staff. A preconstruction meeting with the Construction Inspector must happen prior to any construction. Call Tacoma Power electrical inspection staff that inspect for compliance to the Tacoma Power standards, Tacoma Electrical Code, NEC, WAC and Electric Service Handbook requirements. Conduit and cables (less than 600 volts) that connect from the transformer to the SSB. Utility owned. Conduit and cables from the transformer to the service entrance or from the SSB to the service entrance. Customer owned. Tacoma Power engineering staff that provide design, cost estimates, and coordination of the commercial secondary service project. A plastic or concrete vault designed to contain the point of connection for the electrical service which connects the electrical secondary cables to the electrical service cables. Transmission & Distribution Standards Page 1 of 11

2 Responsibilities and Inspections Construction Area Location of SSB SSB Work in Road Right-of-Way Electrical Secondary Conduit and Pole Conduit Riser Completion of the Pole Conduit Riser Electrical Secondary Cables & Connections Electrical Service Responsibility The New Services Engineer will work with the customer s electrical contractor to determine the location of the SSB on the customer s property. The customer s electrical contractor will install the SSB per this standard under the direction of the New Services Engineer. The customer s electrical contractor will be responsible for installing conduit in the road right-ofway per the requirements of the permitting agency. Permits to cut and restore the road and any other work in the road right-of-way must be obtained before work in the right-of-way can begin. A copy of the approved permit must be on site while the road work is being done. The customer s electrical contractor will install conduit from the SSB to the pole and a portion of the conduit riser on the pole according to Customer Requirements Standard C-UG-1200, Pole Conduit Riser. Tacoma Power T&D Construction Staff Tacoma Power T&D Construction Staff will: install the electrical secondary cables from the pole to the SSB or from the padmount transformer to the SSB, and make all connections at the SSB, at the pole and/or at the padmount transformer. The customer s electrical contractor will install the electrical service. Inspection by Construction Inspector Construction Inspector Construction Inspector Construction Inspector Not needed Not needed Electrical Inspector Transmission & Distribution Standards Page 2 of 11

3 I Overhead Service An overhead service drop may be provided for services of up to 400A (the New Services Engineer will determine if a 600A service can be furnished) provided that it meets all criteria of the overhead service drop. Contact New Services Engineer for information. II Underground Service from Padmount Transformer Underground service from a padmount transformer requires the installation of a primary underground system. Contact New Services Engineer. Pre-construction meeting with the Construction Inspector must happen prior to any construction. If the New Services Engineer determines an SSB is to be installed, see section Selection of SSB with Table 1 and Table 2 to help determine the size of SSB necessary per the size of electrical service. III Underground Service from Polemount Transformer (UGP) In areas with an existing overhead electrical system, an underground service from a polemount transformer (UGP) may be provided for services in accordance with the limitations in the table below. Contact New Services Engineer Pre-construction meeting with the Construction Inspector must happen prior to any construction. Limitations UGP s have the following limitations: Issue Maximum Service Panel Size Maximum Cable Size Minimum Wire Size Maximum Distance from Pole to SSB Maximum Number of Conduit Bends from Pole to SSB Single Phase: 400A Requirements Three Phase: Contact New Services Engineer See section Selection of SSB with Table 1 and Table 2, unless approved by New Services Engineer #10 AWG 200 feet 270 o (degrees) of bends / elbows, including the 90 o pole conduit riser elbow on the pole and the 90 o conduit elbow into a bottomless plastic SSB (if applicable) Transmission & Distribution Standards Page 3 of 11

4 Figure 1 Typical UGP SSB 10' max. 8' min. Pole Quadrants 2 & 3 are reserved for utility equipment. Quadrants 1 & 4 are reserved for climbing by utility personnel. In any case, pole quadrant to be used will be determined by the Construction Inspector at the pre-construction meeting. 4" min. To customer service entrance Pole Conduit Riser per C-UG " Electrical Service Roadway Electrical Secondary Selection of Conduit From Pole to SSB The size and number of conduits required for the electrical secondary are listed below: Size of Service Panel Single Phase Service Conduit (Quantity and Size) up to 200A A to 400A Three Phase Service Contact New Services Engineer Transmission & Distribution Standards Page 4 of 11

5 Selection of SSB The following tables will provide guidelines on how to select the type and size of SSB. In any case the customer s electrical contractor shall coordinate with the New Services Engineer on the type and size of the SSB to be used on the project. Bottomless plastic enclosure SSBs shall not be located in driveways, areas subject to vehicular loading, or in the public right-of-way. All precast concrete SSBs can be located in areas not subject to any vehicular loading, off-street or incidental traffic areas, or in the public rightof-way. All precast concrete SSBs shall have a non-skid type cover (see standard C-UG-2000 Customer Requirements, Precast Concrete Vaults Approved Vendors. All conduit quantities in Tables 1 and 2 are the sum total of electrical service and electrical secondary cables from customer and Tacoma Power respectively. Table 1 SSB Selection for Bottomless Plastic Enclosures (No Vehicular Loading) Tacoma Power Description Total Conduit (Quantity and Size) Cables (Max. Size) SSB (Small) only 250 kcmil SSB (Large) max or 4 4 max 350 kcmil Manufacturer and Model # PenCell #PE-20GS-2X PenCell #PE-20PL-2X-TAC PenCell #PE-30GS PenCell #PE-30PLX-TAC Tacoma Power MID # Base #19118 Cover #19437 Base #37920 Cover #37921 Table 2 SSB Selection for Precast Concrete Vaults (Off-Street, Incidental Traffic) Tacoma Power Description 233 Vault Total Conduit (Quantity and Size) max or 4 4 max Cables (Maximum Size) 350 kcmil Manufacturer and Model # Tacoma Power MID # 554 Vault 8 4 max 500 kcmil 774 Vault 8 conduit max 750 kcmil If electrical service size exceeds 8 runs of 750 kcmil, New Services Engineer will determine quantity and size of SSBs or the use of a secondary service cabinet (see standard A-UG-1600 Secondary Service Cabinet ) See C-UG-2000 Customer Requirements, Precast Concrete Vaults Approved Vendors Transmission & Distribution Standards Page 5 of 11

6 SSB (Bottomless Plastic Enclosure) Step Procedure Call Construction Inspector for pre-construction meeting prior to any construction. Establish location and final grade for the SSB and install SSB. Select size of SSB per Table 1. o SSB covers shall have Tacoma Power embossed on them for identification purposes. Bottomless SSBs shall not be located in driveways, areas subject to vehicular loading, or in the public right-of-way. SSBs shall not be placed in a depression or in low areas that would tend to fill with water or silt. Ensure there are no rocks between SSB base and cover to avoid damage to the cover. The top of the SSB cover shall be: o 2 inches above final grade in landscaped areas. o flush with final grade in paved areas. Establish location of and install pole conduit riser per standard C-UG Customer Requirements, Pole Conduit Riser. Dig trench from the SSB to the service entrance and to the pole. Dig service and secondary trenches to the same side of the SSB, property side of SSB preferred. On private property, the trench shall be deep enough to maintain a minimum of 24 inches of cover over the conduit. In road right-of-way, the trench shall be deep enough to maintain a minimum of 36 inches of cover over the conduit. Permits from local governmental agency must be obtained before any work in the road right-of-way can begin and a copy of the approved permit on site while the road work is being done. The trench must be deep enough at the SSB so the conduit elbow(s) can be terminated vertically within the SSB. The trench should be dug as straight as possible and the trench bed leveled and free of rocks larger than 2 inches diameter. Install conduit from SSB to the service entrance and to the pole. From pole to SSB, conduit shall be 2.5 or 4 Sch. 40 gray PVC. Excavate beneath the SSB and insert the 90 conduit elbows. All conduit must be at the same end of the SSB and grouped closely together (property side of the SSB preferred). Conduit ends shall extend vertically 2 inches above the bottom of the SSB. Identify conduit ends with customer building address. Install bell ends on the conduit ends. Do not glue bell ends inside SSB. Transmission & Distribution Standards Page 6 of 11

7 SSB (Bottomless Plastic Enclosure) (continued) Inspections for conduit (BEFORE Backfill) are as follows: From the service entrance to the SSB inspection and approval by the Electrical Inspector. From the pole to the SSB, including the SSB inspection and approval by the Construction Inspector. Backfill the trench. Per the requirements of any permits and site requirements of Tacoma Power and others. Use available clean material. Pieces of scrap cable and other construction items must not be buried in the trench. Large rocks must be removed and if native soil is rock, sand bedding may be required. Tamp the soil, leaving a slight mound to allow for settling. Pull in electrical service cables from the service entrance to the SSB. Leave 4 feet minimum of cable, measured from the top of the SSB, inside the SSB. Ensure any parallel cables have matching phase tapes. Identify cables with customer building address. Ensure the following has been done: All applicable fees are paid. All right-of-way and easement issues are resolved (if any). All inspections have been passed. Tacoma Power T&D Construction Staff will: complete the pole conduit riser. pull in electrical secondary cables from the pole to the SSB. energize the service. Transmission & Distribution Standards Page 7 of 11

8 Figure 2 Typical SSB (Bottomless Plastic Enclosure) SSB (Precast Concrete Vault) Step 1 2 Procedure Call Construction Inspector for pre-construction meeting prior to any construction. Establish location and final grade for the SSB and install the SSB. Select size of SSB per Table 2. o SSB covers shall have Tacoma Power embossed on them for identification purposes. Concrete SSBs can be located in areas not subject to any vehicular loading, off-street or incidental traffic areas, or in the public right-of-way. SSBs shall not be placed in a depression or in low areas that would tend to fill with water or silt. The top of the SSB cover shall be: o 6 inches above final grade in landscaped areas. o flush with final grade in paved areas. Transmission & Distribution Standards Page 8 of 11

9 SSB (Precast Concrete Vault) (continued) Establish location of and install pole conduit riser per standard C-UG-1200 Customer Requirements, Pole Conduit Riser. Dig trench from the SSB to the service entrance and to the pole. On private property, the trench shall be deep enough to maintain a minimum of 24 inches of cover over the conduit. In road right-of-way, the trench shall be deep enough to maintain a minimum of 36 inches of cover over the conduit. Permits from local governmental agency must be obtained before any work in the road right-of-way can begin and a copy of the approved permit on site while the road work is being done. The trench should be dug as straight as possible and the trench bed leveled and free of rocks larger than 2 inches diameter. Install conduit from SSB to the service entrance and to the pole (see Figure 3). From pole to SSB, conduit shall be 2.5 or 4 Sch. 40 gray PVC. Install conduit 4 inches minimum into the SSB perpendicular to the vault wall. Identify conduit ends with customer building address. Install bell ends on the conduit ends. Do not glue bell ends inside SSB. Grout around knockouts. Inspections for conduit (BEFORE Backfill) are as follows: From the service entrance to the SSB inspection and approval by the Electrical Inspector. From the pole to the SSB, including the SSB inspection and approval by the Construction Inspector. Transmission & Distribution Standards Page 9 of 11

10 SSB (Precast Concrete Vault) (continued) Backfill the SSB excavation as shown below: 7 Clean fill as directed by the Construction Inspector Vault base 9 min. of 5/8 minus crushed rock well compacted and extending 12 min. beyond the edge of the vault in all directions Backfill the trench. Per the requirements of any permits and site requirements of Tacoma Power and others. Use available clean material. Pieces of scrap cable and other construction items must not be buried in the trench. Large rocks must be removed and if native soil is rock, sand bedding may be required. Tamp the soil, leaving a slight mound to allow for settling. Pull in electrical service cables from the SSB to the service entrance. Leave the following minimum length of each service cable, measured from the top of the SSB, inside the SSB: o 233 or 554 vault 10 feet of cable o 774 vault 15 feet of cable Ensure any parallel cables have matching phase tapes. Identify cables with customer building address. Ensure the following has been done: All applicable fees are paid. All right-of-way and easement issues are resolved (if any). All inspections have been passed. Tacoma Power T&D Construction Staff will: complete the pole conduit riser. pull in electrical secondary cables from the pole to the vault. energize the service. Transmission & Distribution Standards Page 10 of 11

11 Figure 3 Typical SSB (Precast Concrete Vault) Conduit Entry Conduit entering the vault shall consistently enter the left side knockouts on all sides. This is for the training of cable in the vault in the same direction. The Construction Inspector may approve exceptions on a site-by-site basis only. In any case, the service conduit entry and the secondary conduit entry shall allow all cables to be trained in the same clockwise or counter-clockwise direction (See Figure 3). Transmission & Distribution Standards Page 11 of 11

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS Section 1 Definitions 2 Scope of Work 3 Extent of Work 4 Inspection and Performance of Work 5 Trenching 6 Duct Installation

More information

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEM(S) FOR STREETLIGHTS. 1 Definitions. 2 Scope of Work. 3 Extent of Work

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEM(S) FOR STREETLIGHTS. 1 Definitions. 2 Scope of Work. 3 Extent of Work SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEM(S) FOR STREETLIGHTS Section 1 Definitions 2 Scope of Work 3 Extent of Work 4 Inspection and Performance of Work 5 Trenching 6 Duct Installation 7 Backfilling

More information

Page Electric Utility Service Specifications

Page Electric Utility Service Specifications T Y P I C A L U N D E R G R O U N D S E R V I C E R E Q U I R E M E N T S 200 Amps Maximum - UG-1 Sheet 1 of 3 87 T Y P I C A L U N D E R G R O U N D S E R V I C E R E Q U I R E M E N T S 200 Amps Maximum

More information

Section. DEVELOPMENT STANDARDS City of Ellensburg ILLUMINATION STANDARDS

Section. DEVELOPMENT STANDARDS City of Ellensburg ILLUMINATION STANDARDS Section 8 City of Ellensburg ILLUMINATION STANDARDS Table of Contents STREET ILLUMINATION...3-5 GENERAL NOTES...3 INSTALLATION AND CONNECTIONS...3 MARKING...3 STAKING...3-4 TRENCH REQUIREMENTS...4 ILLUMINATION

More information

SECTION 5 TRANSFORMERS

SECTION 5 TRANSFORMERS SECTION 5 TRANSFORMERS Necessary transformers will be installed and maintained by The City of Aspen. The City of Aspen will not furnish transformers unless they are of standard size and voltage as established

More information

Customer Connection Guide Updates Effective May 2017

Customer Connection Guide Updates Effective May 2017 This document provides a list of the updates to the EPCOR Distribution and Transmission Inc. (EDTI) Customer Connection Guide. If you have any questions, please contact EDTI Customer Engineering Services

More information

Customer Requirements RF Antenna Installations

Customer Requirements RF Antenna Installations Application Terms Attachment requirements and clearances on the Pole for Radio Frequency (RF) antenna equipment installations. This standard is intended to allow electrical workers to perform their normal

More information

2' x 3' Polymer Pull Box Cover 4'-0" 7'-0" 24" x 76" Access Opening 3'-6"

2' x 3' Polymer Pull Box Cover 4'-0 7'-0 24 x 76 Access Opening 3'-6 Scope.1 Precast Concrete Equipment Slab Box 8' x 10' x Pad with 4' x 7' x 3'- Box for 5-Way RAM Gas Switch, 2-Way, 3-Way, and 4-Way Pad-Mounted RAG Gas Switches, VFI 9, VFI 12, Bypass Switch, and 33 kv

More information

SECTION UNDERGROUND POWER DUCT AND SUB-STRUCTURES. A. Section : Trenching, Backfilling, and Compacting

SECTION UNDERGROUND POWER DUCT AND SUB-STRUCTURES. A. Section : Trenching, Backfilling, and Compacting SECTION 33 71 19 UNDERGROUND POWER DUCT AND SUB-STRUCTURES PART 1 GENERAL 1.1 RELATED WORK A. Section 31 23 33: Trenching, Backfilling, and Compacting B. Section 32 01 00: Site Restoration and Rehabilitation

More information

Electric Service Guide. Residential Subdivision

Electric Service Guide. Residential Subdivision Electric Service Guide Residential Subdivision January 1, 2017 Contact MID s Electric Engineering Department (electric.standards@mid.org) with any questions about this Service Guide. Check MID s website

More information

Utility Structures. Utility vaults, trenches, transformer pads Electrical Pole Bases and switching cubicles

Utility Structures. Utility vaults, trenches, transformer pads Electrical Pole Bases and switching cubicles Utility Structures Utility vaults, trenches, transformer pads Electrical Pole Bases and switching cubicles PRODUCT GUIDE & TECHNICAL REFERENCE MANUAL Providing the right solutions. UTILITY STRUCTURES Perfect

More information

SAUSALITO-MARIN CITY SANITARY DISTRICT MISCELLANEOUS UPGRADES PROJECT. Addendum No. 2

SAUSALITO-MARIN CITY SANITARY DISTRICT MISCELLANEOUS UPGRADES PROJECT. Addendum No. 2 SAUSALITO-MARIN CITY SANITARY DISTRICT MISCELLANEOUS UPGRADES PROJECT Addendum No. 2 The following shall modify the Contract Documents. The work shall be accomplished in accordance with such modifications.

More information

MH Table of Contents Standard Title/Scope Page Table of Contents SCE Public

MH Table of Contents Standard Title/Scope Page Table of Contents SCE Public MH Table of Contents Standard Title/Scope MH 300 MH 310 MH 318 MH 320 MH 325 MH 330 MH 335 MH 340 MH 350 Manholes Requirements MH 300.1 Manholes Requirements...........................................

More information

EXCAVATION AND BACKFILL

EXCAVATION AND BACKFILL Standard Specification 2565.3, 2451, and 1805 A basic understanding of specifications is needed to properly replace the disturbed soil and restore the condition of the excavated area. The size of the disturbed

More information

SECTION 58 PRECAST CONCRETE BOX CULVERT. This work consists of furnishing and installing Pre-cast Concrete Box Culverts.

SECTION 58 PRECAST CONCRETE BOX CULVERT. This work consists of furnishing and installing Pre-cast Concrete Box Culverts. SECTION 58 PRECAST CONCRETE BOX CULVERT 58.1 DESCRIPTION A. General This work consists of furnishing and installing Pre-cast Concrete Box Culverts. B. Related Work Section 51 Section 52 Section 53 Section

More information

Manholes Table of Contents

Manholes Table of Contents Standard MH 300 Title Manholes Requirements MH 300.1 Manholes Requirements Manholes Table of Contents Underground Structures Standards MH 310 MH 318 MH 320 MH 325 MH 330 MH 335 MH 340 MH 350 Precast Tub-Type

More information

Work Type Definition and Submittal Requirements Work Type: Subsurface Utility Engineering (SUE)

Work Type Definition and Submittal Requirements Work Type: Subsurface Utility Engineering (SUE) MUST be qualified under Minnesota Department of Transportation Prequalification Program - Work Type 15.1 Subsurface Utility Engineering The first section, Work Type Definition, provides a detailed explanation

More information

CITY OF LA MARQUE CHAPTER GRAPHIC REQUIREMENTS CONSTRUCTION PLAN AND MISCELLANEOUS REQUIREMENTS

CITY OF LA MARQUE CHAPTER GRAPHIC REQUIREMENTS CONSTRUCTION PLAN AND MISCELLANEOUS REQUIREMENTS CITY OF LA MARQUE CHAPTER 2 -------------------------------------------- GRAPHIC REQUIREMENTS CONSTRUCTION PLAN AND MISCELLANEOUS REQUIREMENTS CHAPTER 2 ------------------------------------------------

More information

A. Deviation from this standard must be approved by the Project Architect.

A. Deviation from this standard must be approved by the Project Architect. September 2012, rev. 00 26 5600 Exterior Lighting PART 1. GENERAL 1.01 Related Documents A. Deviation from this standard must be approved by the Project Architect. B. Drawings and general provisions of

More information

NEW OR UPGRADED ELECTRICAL SERVICE

NEW OR UPGRADED ELECTRICAL SERVICE NEW OR UPGRADED ELECTRICAL SERVICE The following steps summarize the general process and procedures necessary for CVEA to complete construction of a new or upgraded service. Variances may be necessary

More information

SECTION 39 - MANHOLES TABLE OF CONTENTS

SECTION 39 - MANHOLES TABLE OF CONTENTS SECTION 39 - MANHOLES TABLE OF CONTENTS Section Page 39-1 GENERAL... 39.1 39-2 PRECAST CONCRETE MANHOLES... 39.1 39-2.01 Precast Concrete Sewer Manholes... 39.1 39-2.02 Precast Concrete Storm Drain Manholes...

More information

.1 Applicability: These criteria shall be applied as follows:

.1 Applicability: These criteria shall be applied as follows: DESIGN CRITERIA DIVISION 4800 STREET LIGHTING 4801 GENERAL: These criteria shall be adhered to for the design of all publiclyfinanced or privately-financed traffic signal systems to be installed in the

More information

Delivering Reliability. Services. Strength You Can Count On. oldcastleprecast.com/services

Delivering Reliability. Services. Strength You Can Count On. oldcastleprecast.com/services Delivering Reliability A Strength You Can Count On SERVICES TENANT IMPROVEMENTS Above And Below Ground Solutions Strength You Can Count On Oldcastle Precast is well trained and knowledgeable in all aspects

More information

CONTINUING EDUC ATION

CONTINUING EDUC ATION 3 CONTINUING EDUC ATION FOR WISCONSIN ELECTRICIANS 2017 NEC Article 250 2 Hours WISCONSIN CONTRACTORS INSTITUTE N16 W23217 Stone Ridge Drive Suite 290 Waukesha, WI 53188 262-409-4282 www.wcitraining.com

More information

Existing and proposed contours at 1-foot intervals. The fill and/or excavation quantities in cubic yards.

Existing and proposed contours at 1-foot intervals. The fill and/or excavation quantities in cubic yards. PLAN REQUIREMENTS The plans for street design shall conform to the requirements of Sections 3 and 4. The following requirements shall also be shown on the plans where applicable. Road and Storm Plans:

More information

Precast Concrete. Installation Guide V GR-WI-599. Page 1

Precast Concrete. Installation Guide V GR-WI-599. Page 1 Precast Concrete Installation Guide V.1 2019 GR-WI-599 Page 1 Introduction Cubis Systems designs, manufactures and distributes a wide range of precast concrete cable pits and access covers for all major

More information

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 422 MAY 1993 CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS 422.01 SCOPE 422.02 REFERENCES 422.03 DEFINITIONS

More information

Plastibeton Trench System. Installation Packet

Plastibeton Trench System. Installation Packet Plastibeton Trench System Installation Packet Plastibeton Installation Guide This Installation Guide is intended to assist in the preparation and installation of Plastibeton products manufactured by Oldcastle

More information

SECTION MANHOLES

SECTION MANHOLES SECTION 33 05 13 MANHOLES PART 1 GENERAL 1.01 SECTION INCLUDES A. CONTRACTOR shall furnish and install precast concrete manhole base, sections, adjusting rings, steps, and manhole ring and cover, complete.

More information

3.1 Overview of ATCO Electric s URD System Design

3.1 Overview of ATCO Electric s URD System Design Page: 3-1 3.0 URD DESIGN GUIDELINES 3.1 Overview of ATCO Electric s URD System Design ATCO Electric s design for distribution power supply to URD areas is a primary looped supply system. This is generically

More information

TECHNICAL SPECIAL PROVISIONS

TECHNICAL SPECIAL PROVISIONS TECHNICAL SPECIAL PROVISIONS FOR CITY OF TALLAHASSEE ADVANCED TRANSPORTATION MANAGEMENT SYSTEM OCTOBER 2004 TECHNICAL SPECIAL PROVISIONS FOR CITY OF TALLAHASSEE ADVANCED TRANSPORTATION MANAGEMENT SYSTEM

More information

PROPOSED FIBER OPTIC CONDUIT INSTALLATION E. 50TH ST. AND S. COTTAGE GROVE AV. CHICAGO, ILLINOIS

PROPOSED FIBER OPTIC CONDUIT INSTALLATION E. 50TH ST. AND S. COTTAGE GROVE AV. CHICAGO, ILLINOIS EVANS DREXEL DREXEL ELLIS ELLIS PROPOSED FIBER OPTIC CONDUIT INSTALLATION E. 50TH ST. AND S. COTTAGE GROVE AV. CHICAGO, ILLINOIS SHEETS INDEX TO SHEETS DESCRIPTION 90 294 94 LANGLEY EVANS 48TH COTTAGE

More information

PART 4 STANDARD DRAWINGS FOR CONSTRUCTION

PART 4 STANDARD DRAWINGS FOR CONSTRUCTION 4.0. INTRODUCTION PART 4 STANDARD DRAWINGS FOR CONSTRUCTION In this document, Ivins City adopts the most recent edition (currently 2007), including all amendments, of the APWA Utah Chapter s Manual of

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION PART 1 GENERAL 1.01 SUMMARY Section 16195 A. This Section includes electrical identification for the following: 1. Nameplates and labels 2. Wire and cable markers 3. Conduit markers 4. Cable tray markers

More information

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions

MECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING. Code Consistency Questions MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement 2/9/11 ELECTRICAL CONSISTENCY MEETING Code Consistency Questions 1. I have a 500 KVA generator, with no overcurrent protection

More information

HDD Training. HDD Construction Process. Mark Miller, PE Jon Robison, PE

HDD Training. HDD Construction Process. Mark Miller, PE Jon Robison, PE HDD Training HDD Construction Process Mark Miller, PE Jon Robison, PE What is HDD Horizontal Directional Drilling (HDD) is meant to be a convenient method of installing utilities beneath sensitive areas

More information

CITY OF LOMPOC DEVELOPMENT ASSISTANCE BROCHURE ENCROACHMENT PERMITS AND PUBLIC IMPROVEMENT PLANS

CITY OF LOMPOC DEVELOPMENT ASSISTANCE BROCHURE ENCROACHMENT PERMITS AND PUBLIC IMPROVEMENT PLANS CITY OF LOMPOC DEVELOPMENT ASSISTANCE BROCHURE E-10 ENCROACHMENT PERMITS AND PUBLIC IMPROVEMENT PLANS The City of Lompoc has determined that the Engineering Division should administer and issue Encroachment

More information

Guidelines for the Preparation of Traffic Signal & Intelligent Transportation System Plans on Design-Build Projects August 2007

Guidelines for the Preparation of Traffic Signal & Intelligent Transportation System Plans on Design-Build Projects August 2007 Guidelines for the Preparation of Traffic Signal & Intelligent Transportation System Plans on Design-Build Projects August 2007 INTRODUCTION Use the following Guidelines in conjunction with the Traffic

More information

TAXIWAY B NORTH ROAD RUNWAY TAXIWAY C NORTH ROAD VICINITY MAP. Plans Prepared By:

TAXIWAY B NORTH ROAD RUNWAY TAXIWAY C NORTH ROAD VICINITY MAP. Plans Prepared By: CONSTRUCTION PLANS CITY OF NAPLES AUTHORITY (APF) NAPLES, COLLIER COUNTY, FLORIDA NAA BID NO. : TBD FAA AIP NO.: N/A FDOT FM NO.: N/A HANSON PROJ. NO. 15A0023 CITY OF NAPLES AUTHORITY BOARD OF COMMISSIONERS

More information

LA DOTD s Nighttime Standards for Construction Operations. Presented by: Tom Ervin Traffic Solutions, Inc.

LA DOTD s Nighttime Standards for Construction Operations. Presented by: Tom Ervin Traffic Solutions, Inc. LA DOTD s Nighttime Standards for Construction Operations Presented by: Tom Ervin Traffic Solutions, Inc. NIGHTTIME CONSTRUCTION OPERATIONS (02/06) NIGHTTIME CONSTRUCTION OPERATIONS (02/06): Section 105,

More information

SECTION PRECAST CONCRETE SECTIONAL MANHOLES

SECTION PRECAST CONCRETE SECTIONAL MANHOLES SECTION 02545 PRECAST CONCRETE SECTIONAL MANHOLES PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Precast reinforced concrete cylindrical sectional manholes, complete with openings, inserts, hardware,

More information

STATE UNIVERSITY CONSTRUCTION FUND

STATE UNIVERSITY CONSTRUCTION FUND DIRECTIVE 1C-12 Issue date: August 2012 1. General SURVEY, MAPPING AND UTILITY LOCATING This Directive has been developed as a general guide for the survey and mapping effort required for Fund projects.

More information

CHAPTER 29 PROJECT COMPLETION DOCUMENTS

CHAPTER 29 PROJECT COMPLETION DOCUMENTS CHAPTER 29 PROJECT COMPLETION DOCUMENTS PROJECT COMPLETION Upon completion of traffic control signal system and lighting projects, there are forms and checklists to ensure that the project is closed out

More information

CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil Engineering Division STREET/ALLEY IMPROVEMENT PLAN REVIEW CHECKLIST

CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil Engineering Division STREET/ALLEY IMPROVEMENT PLAN REVIEW CHECKLIST CITY OF BEVERLY HILLS Department of Public Works and Transportation Civil ing Division STREET/ALLEY IMPROVEMENT PLAN REVIEW CHECKLIST The following checklist consists of the minimum requirements for preparation

More information

SECTION ELECTRICAL IDENTIFICATION

SECTION ELECTRICAL IDENTIFICATION SECTION 16075 ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

Plastibeton Trench System. Installation Packet

Plastibeton Trench System. Installation Packet Plastibeton Trench System Installation Packet Plastibeton Installation Guide This Installation Guide is intended to assist in the preparation and installation of Plastibeton products manufactured by Oldcastle

More information

MANHOLES PART I: GENERAL. A. Precast Concrete Manholes

MANHOLES PART I: GENERAL. A. Precast Concrete Manholes MANHOLES PART I: GENERAL A. Precast Concrete Manholes 1) Manholes shall be made of precast concrete sections of which the top section shall be eccentric or flat slab top. The bottom section shall be a

More information

STANDARD BID ITEM NUMBERS

STANDARD BID ITEM NUMBERS 10701 TRAFFIC CONTROL LUMP SUM 10702 Traffic Control for Storm Sewer Installation LUMP SUM 10703 Traffic Control for Water Main Installation LUMP SUM 10704 Traffic Control for Sanitary Sewer Installation

More information

VILLAGE OF VILLA PARK CENTRAL BOULEVARD IMPROVEMENTS LOCATION MAP (NOT TO SCALE) CORTESI AVE. MYRTLE AVE. CENTRAL BLVD.

VILLAGE OF VILLA PARK CENTRAL BOULEVARD IMPROVEMENTS LOCATION MAP (NOT TO SCALE) CORTESI AVE. MYRTLE AVE. CENTRAL BLVD. Q:\VillaPark_IL\11283000 Astor-Myrtle Sewer Separation Preliminary Design\D.4 CAD\Sheets\North\1. Cover.dwg INDEX OF SHEETS 1 COVER 2 GENERAL NOTES 3 SUMMARY OF QUANTITIES 4 ALIGNMENT 5-9 DRAINAGE AND

More information

SECTION III SUBMITTALS AND APPROVALS

SECTION III SUBMITTALS AND APPROVALS SECTION III SUBMITTALS AND APPROVALS In order to expedite the approval process of new water distribution system and sanitary sewer collection system extensions, the Hilton Head No. 1 Public Service District

More information

DIVISION APPROVED MATERIAL LIST AND STANDARD DETAILS

DIVISION APPROVED MATERIAL LIST AND STANDARD DETAILS DIVISION 400 - APPROVED MATERIAL LIST AND STANDARD DETAILS Section 403 - STANDARD DETAILS TABLE OF CONTENTS DIVISION 400, Section 403 - STANDARD DETAILS SECTION DETAIL NOS. Application Table 403-1 I. Concrete

More information

City/County Design Guidelines for Wireless Communication Facility in the Right of Way. Acquire Agreement with City of Knoxville/Knox County

City/County Design Guidelines for Wireless Communication Facility in the Right of Way. Acquire Agreement with City of Knoxville/Knox County City/County Design Guidelines for Wireless Communication Facility in the Right of Way Part 1. Application Process Flow Chart Acquire Agreement with City of Knoxville/Knox County Establish Infrastructure

More information

SECTION CABLE TRAYS

SECTION CABLE TRAYS SECTION 16139 CABLE TRAYS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections,

More information

For crossing under a railroad, contact the specific railroad company's engineering department.

For crossing under a railroad, contact the specific railroad company's engineering department. PAGE 330524-1 SECTION 330524 SPECIFIER: This section is for the underground installation of piping by directional drilling. When specifying this method of piping installation, care must be taken to ensure

More information

UNDERGROUND UTILITY VAULTS

UNDERGROUND UTILITY VAULTS LEED Reference Guide For Precast Concrete Products Perfect for communications, electrical, gas or steam systems, precast concrete utility structures protect the vital connections and controls for utility

More information

Journeyman's Practice Exam

Journeyman's Practice Exam Journeyman's Practice Exam [Time limit 4.0 hrs.] (The test is open book. I've started at the front of the Code Book and worked toward the back for instructional purposes. The real test will not be in order

More information

Product Dimensions (Width x Length x Height) (inches)

Product Dimensions (Width x Length x Height) (inches) Mr. Dennis Hallahan, P.E. Infiltrator Water Technologies 4 Business Park Road P.O. Box 768 Old Saybrook, CT 06475 RE: Product Registration Renewal #2 Notice of Proprietary Distribution Product Listing

More information

POWER SERVICE DETAILS

POWER SERVICE DETAILS POWER SOURCE # POLE MOUNTED SERVICE TRANSFORMER BY POWER HANDHOLE 0/0V, -PHASE, SERVICE CONDUCTORS; -# AWG SERVICE CONDUCTOR AND -# AWG GROUNDED SERVICE CONDUCTOR (NEUTRAL) SERVICE XFMR SECONDARY. A 0V

More information

CITY OF PINE CITY SMALL WIRELESS FACILITY DESIGN GUIDELINES

CITY OF PINE CITY SMALL WIRELESS FACILITY DESIGN GUIDELINES CITY OF PINE CITY SMALL WIRELESS FACILITY DESIGN GUIDELINES I. PURPOSE AND COMPLIANCE In implementing City Code, Chapter 8, Section 815, the City Council of the City of Pine City (the City ) finds that

More information

TABLE OF CONTENTS 7.0 CABLE INSTALLATION IN UNDERGROUND STRUCTURES

TABLE OF CONTENTS 7.0 CABLE INSTALLATION IN UNDERGROUND STRUCTURES TABLE OF CONTENTS 1.0 SCOPE 2.0 BURIAL DEPTH 3.0 MINIMUM BENDING RADIUS FOR POWER CABLES 4.0 PULLING TENSIONS AND SIDEWALL PRESSURES 5.0 PARAMETERS OF CABLE PULLING 6.0 DIRECT BURIED CABLE INSTALLATION

More information

SPECIAL SPECIFICATION LIGHTNING PROTECTION SYSTEM

SPECIAL SPECIFICATION LIGHTNING PROTECTION SYSTEM 2004 Specifications CSJ 3622-01-001, ETC. SPECIAL SPECIFICATION 8398 LIGHTNING PROTECTION SYSTEM 1. Description. This Special Specification governs the design and installation of Lightning Protection System

More information

Minor Site Plan Application and Checklist Land Disturbing Activities

Minor Site Plan Application and Checklist Land Disturbing Activities Minor Site Plan Application and Checklist Land Disturbing Activities INSTRUCTIONS: Please provide the requested information below. The Development Services Department reviews each site plan submittal based

More information

Guidelines for the Preparation of ITS & Signal Plans by Private Engineering Firms

Guidelines for the Preparation of ITS & Signal Plans by Private Engineering Firms Guidelines for the Preparation of ITS & Signal Plans by Private Engineering Firms INTRODUCTION Use the following Guidelines in conjunction with the ITS & Signals Scope of work provided in the Project Scoping

More information

BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006

BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006 Project Name: BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006 Phase: Unit: # Lots: Development Type (residential, commercial, industrial, etc.) Braselton Project No.

More information

SURVEYING THE UNDERGROUND

SURVEYING THE UNDERGROUND SURVEYING THE UNDERGROUND An Introduction to ASCE 38-02 and the Practice of Subsurface Utility Engineering ACECMD March 28, 2018 Presented by: Art Worthman A. Morton Thomas & Associates, Inc. John Berrettini

More information

AWOS A Site Preparation Manual

AWOS A Site Preparation Manual Automated Weather Observing System AWOS A Site Preparation Manual 3000-A-025 Rev. B FAA APPROVED ECP233 2017 Aug 25 NOT FAA APPROVED All Weather Inc. 1165 National Drive Sacramento, CA 95834 USA 800.824.5873

More information

PRO-RIB FENCE PANELS INSTALLATION GUIDELINES. Virtually Maintenance Free Available in 24 Colors Custom Heights Available by the Inch

PRO-RIB FENCE PANELS INSTALLATION GUIDELINES. Virtually Maintenance Free Available in 24 Colors Custom Heights Available by the Inch PRO-RIB FENCE PANELS INSTALLATION GUIDELINES Virtually Maintenance Free Available in 24 Colors Custom Heights Available by the Inch www.midwestmanufacturing.com Page 2 TOOLS NEEDED Measuring Tape Drill

More information

Building a Hoop Barn: Setting posts and constructing knee wall

Building a Hoop Barn: Setting posts and constructing knee wall Building a Hoop Barn: Setting posts and constructing knee wall In the previous article, I discussed planning and preparation for two new hoop barns to be used for hay storage. In this article, we will

More information

MERALCO Standards: Electrical Design. Engr. Eduard Mercado Electrical Design Team

MERALCO Standards: Electrical Design. Engr. Eduard Mercado Electrical Design Team MERALCO Standards: Electrical Design Engr. Eduard Mercado Electrical Design Team Electrical Design Standards SERVICE VOLTAGES SECONDARY METERED - 240 V, 400 V, 460 V PRIMARY METERING -34.5 kv, 13.8 kv

More information

SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS

SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS 9. STANDARD DETAILS SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS j:\clerical\royse city\1-4086 general services\168-tech const standards review\tcss manual\2018 tcss manual\sec-9a

More information

SELF-ALIGNING PLASTIC INCLINOMETER CASING IN BOREHOLES. Model GEO-LOK. Roctest Limited, All rights reserved.

SELF-ALIGNING PLASTIC INCLINOMETER CASING IN BOREHOLES. Model GEO-LOK. Roctest Limited, All rights reserved. INSTRUCTION MANUAL SELF-ALIGNING PLASTIC INCLINOMETER CASING IN BOREHOLES Model Roctest Limited, 2013. All rights reserved. This product should be installed and operated only by qualified personnel. Its

More information

ACSA PLAN REVIEW CHECKLIST (Guideline Only) (4) Standard water and sewer general plan notes (attached).

ACSA PLAN REVIEW CHECKLIST (Guideline Only) (4) Standard water and sewer general plan notes (attached). ACSA PLAN REVIEW CHECKLIST (Guideline Only) Revised: December 3, 2015 General (1) Proper Title (2) Vicinity map on first sheet. (3) Date and latest plan revision. (4) Standard water and sewer general plan

More information

EPG. by Chris C. Kleronomos

EPG. by Chris C. Kleronomos April 1994 EFFECTIVE EQUIPMENT GROUNDING ECOS Electronics Corporation by Chris C. Kleronomos The quality of the electrical wiring and grounding in a facility containing sensitive electronic equipment is

More information

Grease Interceptor Design Checklist

Grease Interceptor Design Checklist CHECKLIST C2 Revised 5/2/2016 Grease Interceptor Design Checklist Public Works DISCLAIMER - This checklist is provided to Consulting Engineers for the express purpose of assisting them in compiling private

More information

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT

SECTION WIREWAYS FOR RADIOLOGY EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION SECTION 26 05 36 WIREWAYS FOR RADIOLOGY EQUIPMENT SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also, delete any other item or paragraph not applicable

More information

SECTION 3 IMPROVEMENT PLAN REQUIREMENTS

SECTION 3 IMPROVEMENT PLAN REQUIREMENTS SECTION 3 IMPROVEMENT PLAN REQUIREMENTS CONTENTS Page 3-1 Digital Submittals 3-2 3-2 Paper Size and Scale 3-2 3-3 Drafting Standard 3-2 3-4 Title Sheet 3-2 3-5 Title Block 3-3 3-6 Drainage, Sewer, Water,

More information

INSTRUCTIONS: 1. Record the transmittal letter number, date, and subject on the transmittal record sheet located in the front of the manual.

INSTRUCTIONS: 1. Record the transmittal letter number, date, and subject on the transmittal record sheet located in the front of the manual. MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Technical Support Design Services Section TRANSMITTAL LETTER NO. (0-03) MANUAL: Standard Plates DATED: September

More information

HP 2 SERIES Integral Driver - Solid State LED

HP 2 SERIES Integral Driver - Solid State LED HP 2 SERIES Installation Instructions Warning High Voltage Hot Surface NEEDED FOR INSTALLATION: By Others 1/8 & 5/32 Allen Wrench Waterproof Wire Connectors Level Phillips Screwdriver IMPORTANT - WEAR

More information

SUBSTATION SECURITY WALL INSTALLATION MANUAL

SUBSTATION SECURITY WALL INSTALLATION MANUAL SUBSTATION SECURITY WALL INSTALLATION MANUAL JULY 26, 2016 OLDCASTLE PRECAST, INC. 3000 New McEver Rd, Acworth, Ga 30101 Substation Security Wall Installation Manual This Installation Manual is intended

More information

High-Tensile Coated Wire Fence Installation Guide

High-Tensile Coated Wire Fence Installation Guide High-Tensile Coated Wire Fence Installation Guide Please follow directions for a long lasting installation that will not sag after tension is applied to the rails. Proper bracing of corner and end posts

More information

MSD STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY

MSD STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY MSD M etr o p olitan S e w e r Di s t r ict STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY 40203-1911 STANDARD DRAWINGS DIVISION

More information

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section

SECTION STEEL LIGHTING STANDARDS. 1. Electrical conduit and fittings; Section 02760-1 of 5 SECTION 02760 STEEL LIGHTING STANDARDS 02760.01 GENERAL A. Description Steel lighting standards shall include, but not necessarily be limited to, furnishing and installing steel lighting poles,

More information

City of Massillon Site Plan Checklist

City of Massillon Site Plan Checklist City of Massillon Site Plan Checklist The following information MUST be included with all Site Plans submitted for review and processing in order to constitute a complete Site Plan Package. Incomplete

More information

ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030 ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO. 2018-008-COM.00030 To: Prospective Bidders of Record Date: January 8, 2019 The following changes, additions, revisions, and/or deletions

More information

FieldSmart Fiber Scalability Center (FSC) Installation Manual

FieldSmart Fiber Scalability Center (FSC) Installation Manual FieldSmart Fiber Scalability Center (FSC) Installation Manual 288/432/576/1152 PON Cabinets 432/864 Cross-Connect Cabinets Hub Collapse Cabinets (HCC) Vaults PenCell and Channell 288/432 Pole Mount and

More information

Appendix C Construction Details

Appendix C Construction Details 7172 Kennedy Road Warrenton, Virginia 20187 Appendix C Construction Details November 2017 TABLE OF CONTENTS THRUST BLOCKS Anchorage for 11 1/4 o, 22 1/2 o & 45 o Upper Vertical Bends... AV 01 Buttresses

More information

CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA (360)

CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA (360) CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA 98501 (360) 754-4180 Email: cdd@ci.tumwater.wa.us WATER-SEWER-STREET-STORM (IN CITY) Submittal Checklist TUM - RCVD BY DATE STAMP APPLICANT INFORMATION

More information

SURVEYING THE UNDERGROUND

SURVEYING THE UNDERGROUND SURVEYING THE UNDERGROUND An Introduction to the Practice of Subsurface Utility Engineering Maryland Society of Surveyors Maryland Society of Professional Engineers Joint Conference October 8, 2015 Michael

More information

Diamond Knowledge Base. Inductive Loop Guide. Introduction

Diamond Knowledge Base. Inductive Loop Guide. Introduction Diamond Knowledge Base Inductive Loop Guide Introduction An inductive loop is basically a metal detector installed in the surface of the roadway. It consists of electrical wire embedded in the roadway,

More information

Standard Specifications

Standard Specifications Standard Specifications PART 1.00 GENERAL 1.01 DECRIPTION SECTION 02620 PRECAST REINFORCED CONCRETE SANITARY MANHOLES A. Work included: The Contractor shall furnish all labor, materials, equipment, and

More information

Driveway Alarm INSTALLATION MANUAL

Driveway Alarm INSTALLATION MANUAL WIRELESS ACCESS CONTROLS Driveway Alarm INSTALLATION MANUAL Mounting post Transmitter Receiver Transformer Sensor Kit Includes: Transmitter Module Sensor Receiver Transformer Mounting post (3 pieces) Installation

More information

PORT OF ST. HELENS SCAPPOOSE INDUSTRIAL AIRPARK PARALLEL TAXIWAY B RELOCATON AIP PROJECT ADDENDUM NO. 1

PORT OF ST. HELENS SCAPPOOSE INDUSTRIAL AIRPARK PARALLEL TAXIWAY B RELOCATON AIP PROJECT ADDENDUM NO. 1 PORT OF ST. HELENS SCAPPOOSE INDUSTRIAL AIRPARK PARALLEL TAXIWAY B RELOCATON AIP PROJECT 3-41-0056-024-2018 ADDENDUM NO. 1 Addendum No. 1 hereby amends the contract documents and drawings for the Scappoose

More information

SOUTH DUBLIN COUNTY COUNCIL Traffic Management Centre Roads (Traffic and Transportation) Department

SOUTH DUBLIN COUNTY COUNCIL Traffic Management Centre Roads (Traffic and Transportation) Department SOUTH DUBLIN COUNTY COUNCIL Roads (Traffic and Transportation) Department TECHNICAL SPECIFICATION 2 SDCC-TS-02 INDUCTIVE LOOPS & ABOVE GROUND DETECTION REQUIREMENTS FOR THE DESIGN AND INSTALLATION OF TRAFFIC

More information

Application for Site Plan Review

Application for Site Plan Review Application for Site Plan Review 3275 Central Blvd., Hudsonville, Michigan 49426-1450, 616.669.0200 fax 616.669.2330 It is STRONGLY recommended that any application that must go before the Planning Commission

More information

MULTIPLE-FAMILY DESIGN REVIEW SUBMITTAL CHECKLIST

MULTIPLE-FAMILY DESIGN REVIEW SUBMITTAL CHECKLIST MULTIPLE-FAMILY DESIGN REVIEW SUBMITTAL CHECKLIST This application lists the content and format of the submittal requirements to initiate the Design Review process. An incomplete application will not be

More information

CITY OF MUSKEGO DRAFTING STANDARDS

CITY OF MUSKEGO DRAFTING STANDARDS CITY OF MUSKEGO DRAFTING STANDARDS GENERAL - These standards apply to all plans. 1. Plans must be prepared on sheets measuring 36 inch across and 22 inch to 24 inch high unless otherwise specified under

More information

RESIDENTIAL DEMOLITION PERMIT APPLICANT CHECKLIST

RESIDENTIAL DEMOLITION PERMIT APPLICANT CHECKLIST RESIDENTIAL DEMOLITION PERMIT APPLICANT CHECKLIST The purpose of this form is to inform applicants of: 1) the requirements for building permits and stormwater permits for residential demolition projects;

More information

CONTINUOUS COUNTERPOISE ON POLES

CONTINUOUS COUNTERPOISE ON POLES Project Procedure CONTINUOUS COUNTERPOISE ON POLES 07/25/2011 PAGE 1 OF 5 1.0 PURPOSE The purpose of this procedure is to provide guidance and direction for the installation of continuous counterpoise

More information

GCG ASSOCIATES, INC. February 8, Mr. Nathaniel Strosberg, Town Planner 101 Main Street Town of Ashland Ashland, MA 01721

GCG ASSOCIATES, INC. February 8, Mr. Nathaniel Strosberg, Town Planner 101 Main Street Town of Ashland Ashland, MA 01721 GCG ASSOCIATES, INC. CIVIL ENGINEERING AND LAND SURVEYING 84 Main Street Wilmington, Massachusetts 01887 Phone: (978) 657-9714 Fax: (978) 657-7915 February 8, 2016 Mr. Nathaniel Strosberg, Town Planner

More information

MILL HILL ARTS VILLAGE

MILL HILL ARTS VILLAGE OWNER CIVIL ENGINEER MACON-BIBB URBAN DEVELOPMENT AUTHORITY ALEX MORRISON, EXECUTIVE DIRECTOR 200 CHERRY STREET, SUITE 300 MACON, GA 31201 OFFICE PHONE : (478) 803-2402 TRIPLE POINT ENGINEERING DAN WALLACE,

More information