Appendix C Construction Details

Size: px
Start display at page:

Download "Appendix C Construction Details"

Transcription

1 7172 Kennedy Road Warrenton, Virginia Appendix C Construction Details November 2017

2 TABLE OF CONTENTS THRUST BLOCKS Anchorage for 11 1/4 o, 22 1/2 o & 45 o Upper Vertical Bends... AV 01 Buttresses for 11 1/4 o Horizontal Bend... BB 01 Buttresses for 22 1/2 o Horizontal Bend... BB 02 Buttresses for 45 o Horizontal Bend... BB 03 Buttresses for 90 o Horizontal Bend... BB 04 Buttresses for Tees, Plugs and Caps... BT 01 Buttresses for 11 1/4 o, 22 1/2 o & 45 o Lower Vertical Bends... BV 01 GENERAL CONSTRUCTION Pipe Embedment and Backfill for Ductile Iron Pipe... G 01 Pipe Embedment and Backfill for Plastic Pipe... G 02 Typical Gate Valve and Valve Box... G 03 Standard Concrete Cradle and Encasement... G 04 Steel Casing Detail... G 05 Sanitary Sewer Design Calculation Sheet... G 06 SEWER CONSTRUCTION Combination Air/Vacuum Release Valve for Sewage Force Main... SC 01 Waterproof Manhole Insert... SC 02 External Manhole Chimney Seal... SC 03

3 Internal Manhole Chimney Seal... SC 04 Standard 4 ID Precast Concrete Manhole... SC 05 Typical 5 and 6 Diameter Pre Cast Concrete Manhole with 4 Stack... SC 06 Typical 4 Manhole with Outside Drop Connection... SC 07 Inside Drop Manhole... SC 07A Standard Sanitary Sewer Service Lateral Connection... SC 08 Sanitary Sewer Service Lateral Connection with Riser... SC 09 Sewage Force Main 2 Connection... SC 10 Small Diameter Sewage Force Main Service Connection to Gravity Sewer... SC 11 Termination for Dead End Runs of HDPE Force Main (2 and Smaller)... SC 12 Pressure Lateral Assembly... SC 13 UTILITY LOCATION & EASEMENT LAYOUT R 2 Conventional & Larger Lot Subdivisions... UL 01 R 3 & R 4 Conventional and R 2 Cluster Subdivisions... UL 02 R 3 & R 4 Cluster Subdivisions... UL 03 Townhouse Subdivisions on Public Roads... UL 04 WATER DISTRIBUTION SYSTEM Blow Off Detail... WD 01 Sampling Station... WD 02 Air Release Valve... WD 03 Typical Fire Hydrant... WD 04

4 WATER METERS Standard Water Meter Box & Fittings Up to 1... WM /2 and 2 Water Meter and Service Connection... WM 02 Combined Domestic & Fire Service Meter Vault Detail... WM 03 Standard Water Subtraction Meter... WM 04 Temporary Hydrant Meter Assembly... WM 05 Standard Water Service Connection for Water Meter Sizes Up to 1... WS 01

5 8'' min. Reinforcing Bars (typ.) Pipe Dia. (min.) Reinforcing Bar Notes: 1) Reinforcing Bars shall be hooked at each end and embedded minimum 8" into concrete. Exposed portion of all bars shall be painted with a minimum two coats of bituminous paint. 2) Where 3 bars are used, they shall be arranged as shown on the detail above. 3) Where 4 bars are used, 2 bars shall be located at each of end of the bend, symmetrically located on either side of the fitting. Concrete Notes: 1) Fc=3000 PSI AT 28 DAYS. 2) Carry all bearing surfaces to undisturbed earth or firm subgrade. 3) The anchorage dimensions shown are based on design water pressure of 150 psi. Where a higher pressure specification is required, the volume of the concrete (L x W x D) shall be adjusted proportionally according to the design pressure used. AV-01 Anchorage for 11-1/4, 22-1/2 & 45 Upper Vertical Bends Not to Scale Revised: 03/31/05

6 Carry concrete to undisturbed earth or firm subgrade. Concrete Block Dimensions At 150 PSI Pressure Amount to be added to dimension 'D' for each 50 psi (or portion thereof) design pressure above 150 psi (up to 300 psi). Adjustment to Concrete Area for Different Height, Hc. To Be Measured from Finished Grade to C of Pipe CS = 0 PSF Φ = 15 Loose Silty Sand CS = 1000 PSF Φ = 15 Soft Silty Clay & Better Notes: 1) Dimensions D & E shall be adjusted based on required area for value of Hc. 2) Dimensions F & G are constant for a given pipe size. 3) Dimension D shall be adjusted for required pressure in excess of 150 psi before making adjustment for Hc (above). Soil and Concrete Notes: 1) FC = 3000 psi at 28 days. 2) CS = Soil cohesion in psf 3) Φ = Angle of Internal Friction. 4) All bearing surfaces shall be carried to undisturbed earth or firm subgrade. Buttresses for 11-1/4 Horizontal Bend BB-01 Not to Scale Revised: 03/31/05

7 Carry concrete to undisturbed earth or firm subgrade. Concrete Block Dimensions At 150 PSI Pressure Amount to be added to dimension 'D' for each 50 psi (or portion thereof) design pressure above 150 psi (up to 300 psi). Adjustment to Concrete Area for Different Height, Hc. To Be Measured from Finished Grade to C of Pipe CS = 0 PSF Φ = 15 Loose Silty Sand CS = 1000 PSF Φ = 15 Soft Silty Clay & Better Notes: 1) Dimensions D & E shall be adjusted based on required area for value of Hc. 2) Dimensions F & G are constant for a given pipe size. 3) Dimension D shall be adjusted for required pressure in excess of 150 psi before making adjustment for Hc (above). Soil and Concrete Notes: 1) FC = 3000 psi at 28 days. 2) CS = Soil cohesion in psf 3) Φ = Angle of Internal Friction. 4) All bearing surfaces shall be carried to undisturbed earth or firm subgrade. Buttresses for 22-1/2 Horizontal Bend BB-02 Not to Scale Revised: 03/31/05

8 Carry concrete to undisturbed earth or firm subgrade. Concrete Block Dimensions At 150 PSI Pressure Amount to be added to dimension 'D' for each 50 psi (or portion thereof) design pressure above 150 psi (up to 300 psi). Adjustment to Concrete Area for Different Height, Hc. To Be Measured from Finished Grade to C of Pipe CS = 0 PSF Φ = 15 Loose Silty Sand CS = 1000 PSF Φ = 15 Soft Silty Clay & Better Notes: 1) Dimensions D & E shall be adjusted based on required area for value of Hc. 2) Dimensions F & G are constant for a given pipe size. 3) Dimension D shall be adjusted for required pressure in excess of 150 psi before making adjustment for Hc (above). Soil and Concrete Notes: 1) FC = 3000 psi at 28 days. 2) CS = Soil cohesion in psf 3) Φ = Angle of Internal Friction. 4) All bearing surfaces shall be carried to undisturbed earth or firm subgrade. Buttresses for 45 Horizontal Bend BB-03 Not to Scale Revised: 03/31/05

9 Extend concrete to undisturbed earth. Concrete Block Dimensions At 150 PSI Pressure Amount to be added to dimension 'D' for each 50 psi (or portion thereof) design pressure above 150 psi (up to 300 psi). Adjustment to Concrete Area for Different Height, Hc. To Be Measured from Finished Grade to C of Pipe Notes: 1) Dimensions D & E shall be adjusted based on required area for value of Hc. 2) Dimensions F & G are constant for a given pipe size. 3) Dimension D shall be adjusted for required pressure in excess of 150 psi before making adjustment for Hc (above). 4) Special design required for lines 24" in diameter or greater. Concrete Notes: 1) FC = 3000 psi at 28 days. 2) All bearing surfaces shall be carried to undisturbed earth or firm subgrade. Buttresses for 90 Horizontal Bend BB-04 Not to Scale Revised: 03/31/05

10 Notes: 1) FC = 3000 psi at 28 days. 2) Buttress block dimensions are appropriate for design water pressure less than or equal to 150 psi. 3) Where design water pressure exceeds 150 psi, block dimensions shall be proprtioned based on actual design pressure. 4) All bearing surfaces shall be extended to undisturbed earth or firm subgrade. 5) Tapping assemblies and sleeves shall be buttressed as comparably sized tees. Buttresses for Tees, Plugs and Caps BT-01 Not to Scale Revised: 03/31/05

11 Notes: 1) FC = 3000 psi at 28 days. 2) Buttress block dimensions are appropriate for design water pressure less than or equal to 150 psi. 3) Where design water pressure exceeds 150 psi, block dimensions shall be proprtioned based on actual design pressure. 4) Where soil bearing pressure is less than 2500 psi, dimension 'L' shall be muliplied by 2 and Dimension 'M' shall be multiplied by ) All bearing surfaces shall be extended to undisturbed earth or firm subgrade. BV-01 Buttresses for 11-1/4, 22-1/2 & 45 Lower Vertical Bends Not to Scale Revised: 03/31/05

12 G-01 Pipe Embedment and Backfill for Ductile Iron Pipe Not to Scale Revised: 03/31/05

13 G-02 Pipe Embedment and Backfill for Plastic Pipe Not to Scale Revised: 03/31/05

14 WATER G-03 Typical Gate Valve and Valve Box Not to Scale Revised: 11/28/17

15 Standard Concrete Cradle and Encasement G-04 Not to Scale Revised: 03/31/05

16 Steel Casing Detail G-05 Not to Scale Revised: 03/31/05

17 Sanitary Sewer Design Calculation Sheet G-06 Not to Scale Revised: 03/31/05

18 SC-01 Combination Air/Vacuum Release Valve for Sewage Force Main Not to Scale Revised: 11/28/17

19 SC-02 Waterproof Manhole Insert Not to Scale Revised: 03/31/05

20 SC-03 External Manhole Chimney Seal Not to Scale Revised: 03/31/05

21 SC-04 Internal Manhole Chimney Seal Not to Scale Revised: 03/31/05

22 SC-05 Standard 4' ID Precast Concrete Manhole Not to Scale Revised: 03/31/05

23 SC-06 Typical 5' and 6' Diameter Pre-Cast Concrete Manhole with 4' Stack Not to Scale Revised: 03/31/05

24 SC-07 Typical 4' Manhole with Outside Drop Connection Not to Scale Revised: 03/31/05

25 A A SC-07A Inside Drop Manhole Not to Scale Revised: 11/28/17

26 SC-08 Standard Sanitary Sewer Service Lateral Connection Not to Scale Revised: 03/31/05

27 SC-09 Sanitary Sewer Service Lateral Connection with Riser Not to Scale Revised: 03/31/05

28 SC-10 Sewage Force Main 2" Connection Not to Scale Revised: 03/31/05

29 SC-11 Small Diameter Sewage Force Main Service Connection to Gravity Sewer Not to Scale Revised: 11/28/17

30 SC-12 Termination for Dead-End Runs of HDPE Force Main (2" and Smaller) Not to Scale Adopted: 04/29/09

31 SC-13 Pressure Lateral Assembly Not to Scale Revised: 11/28/17

32 FCWSA Utility Location & Easement Layout Detail (UL-01) Showing Typical Water & Sewer Utility Locations and Minimum Easement Widths along Internal Subdivision Streets in R-2 Conventional Subdivisions & other Subdivisions with lots sized 20,000 SF or greater When routing sanitary sewer around curves in the road, the manholes and the center line of the pipe shall be placed no closer than 5.0' from the Easement and ROW lines. Utility Easement Line (Typ.) Sanitary Sewer Lateral (Typ.) Sanitary Sewer Line (Typ.) 15.00' (min.) ROW Line (Typ.) Sanitary Sewer CL Easement (Typ.) CL Road (Typ.) GRAPHIC SCALE ( IN FEET ) 1 inch = 50 ft. 5.00' (min.) 10.00' (min.) ROW Line (Typ.) Water Line (Typ.) Utility Easement Line (Typ.) Water Service (Typ.) 5' Sidewalk (Typ.) Curb & Gutter (Typ.) Property Line (Typ.) Min. Yard Line (Typ.) Notes: 1) All dimensions are minimums. 2) Typical sanitary sewer line location shall be 7.5' outside the ROW with a 15' utility easement. 3) Typical waterline location shall be 5' outside the ROW with a 10' utility easement. 4) Curve radii of less than 250' on water lines will necessitate the use of fittings. Where fittings are used, the waterline shall be routed so that the centerline of the pipe remains a minimum 3' from both ROW and easement lines. 5) Water valve boxes shall not be located in sidewalks, curb & gutter or pavement. 6) This detail is applicable only for internal subdivision streets. Easement widths for all other streets and roads shall be in accordance with the Authority's Utility Standards Manual (USM) Section ) All design and construction shall be in accordance with the Authority's USM. UL Utility Location & Easement Layout R-2 Conventional & Larger Lot Subdivisions Scale: 1" = 50' 03/05/07

33 FCWSA Utility Location & Easement Layout Detail (UL-02) Showing Typical Water & Sewer Utility Locations and Minimum Easement Widths along Internal Subdivision Streets in R-3 Conventional, R-4 Conventional and R-2 Cluster Subdivisions with Single Family Dwellings When routing sanitary sewer around curves in the road, the manholes and the center line of the pipe shall be placed no closer than 3.0' from the Easement and ROW lines. Sanitary Sewer Lateral (Typ.) Utility Easement Line (Typ.) Sanitary Sewer Line (Typ.) Sanitary Sewer CL Easement (Typ.) 12.00' (min.) ROW Line (Typ.) CL Road (Typ.) GRAPHIC SCALE ( IN FEET ) 1 inch = 50 ft ' (min.) 3.00' (min.) ROW Line (Typ.) Water Line (Typ.) Utility Easement Line (Typ.) Water Service (Typ.) 5' Sidewalk (Typ.) Curb & Gutter (Typ.) Property Line (Typ.) Min. Yard Line (Typ.) Notes: 1) All dimensions are minimums. 2) Typical sanitary sewer line location shall be 6.0' outside the ROW with a 12' utility easement. 3) Typical waterline location shall be 3' outside the ROW with an 8' utility easement. 4) Curve radii of less than 250' on water lines will necessitate the use of fittings. Where fittings are used, the waterline shall be routed so that the centerline of the pipe remains a minimum 3' from both ROW and easement lines. 5) Water valve boxes shall not be located in sidewalks, curb & gutter or pavement. 6) This detail is applicable only for internal subdivision streets. Easement widths for all other streets and roads shall be in accordance with the Authority's Utility Standards Manual (USM) Section ) All design and construction shall be in accordance with the Authority's USM. Utility Location & Easement Layout R-3 & R-4 Conventional and R-2 Cluster Subdivisions UL-02 Scale: 1" = 50' 03/05/07

34 FCWSA Utility Location & Easement Layout Detail (UL-03) Showing Typical Water & Sewer Utility Locations and Minimum Easement Widths along Internal Subdivision Streets in R-3 Cluster and R-4 Cluster Subdivisions with Single Family Dwellings When routing sanitary sewer around curves in the road, the manholes and the center line of the pipe shall be placed no closer than 2.5' from the Easement and ROW lines. Utility Easement Line (Typ.) Sanitary Sewer Line (Typ.) Sanitary Sewer CL Easement (Typ.) Sanitary Sewer Lateral (Typ.) 10.00' (min.) ROW Line (Typ.) CL Road (Typ.) 5.00' (min.) 2.00' (min.) ROW Line (Typ.) Water Line (Typ.) Water Service (Typ.) Utility Easement Line (Typ.) 5' Sidewalk (Typ.) Curb & Gutter (Typ.) Property Line (Typ.) Min. Yard Line (Typ.) Notes: 1) All dimensions are minimums. 2) Typical sanitary sewer line location shall be 5.0' outside the ROW with a 10' utility easement. 3) Typical waterline location shall be 2' outside the ROW with a 5' utility easement. 4) Curve radii of less than 250' on water lines will necessitate the use of fittings. Where fittings are used, the waterline shall be routed so that the centerline of the pipe remains a minimum 2' from both ROW and easement lines. 5) Water valve boxes shall not be located in sidewalks, curb & gutter or pavement. 6) This detail is applicable only for internal subdivision streets. Easement widths for all other streets and roads shall be in accordance with the Authority's Utility Standards Manual (USM) Section ) All design and construction shall be in accordance with the Authority's USM. GRAPHIC SCALE ( IN FEET ) 1 inch = 50 ft. 200 UL-03 Utility Location & Easement Layout R-3 & R-4 Cluster Subdivisions Scale: 1" = 50' 03/05/07

35 FCWSA Utility Location & Easement Layout Detail (UL-04) Showing Typical Water & Sewer Utility Locations and Minimum Easement Widths along Internal Streets in Townhouse Subdivisions with units fronting on Public Roads with parallel parking. When routing sanitary sewer around curves in the road, the manholes and the center line of the pipe shall be placed no closer than 2.5' from the Easement and ROW lines. ROW Line (Typ.) Utility Easement Line (Typ.) Sanitary Sewer CL Easement (Typ.) Sanitary Sewer Line (Typ.) 10.00' (min.) Typ. Parallel Parking CL Road (Typ.) 5.00' (min.) ROW Line (Typ.) Water Line (Typ.) Utility Easement Line (Typ.) Water Service (Typ.) 5' Sidewalk (Typ.) Curb & Gutter (Typ.) Property Line (Typ.) Min. Yard Line (Typ.) 2.00' (min.) GRAPHIC SCALE ( IN FEET ) 1 inch = 50 ft. 200 Notes: 1) All dimensions are minimums. 2) Typical sanitary sewer line location shall be 5.0' outside the ROW with a 10' utility easement. 3) Typical waterline location shall be 2' outside the ROW with a 5' utility easement. 4) Curve radii of less than 250' on water lines will necessitate the use of fittings. Where fittings are used, the waterline shall be routed so that the centerline of the pipe remains a minimum 2' from both ROW and easement lines. 5) Water valve boxes shall not be located in sidewalks, curb & gutter or pavement. 6) This detail is applicable only for internal subdivision streets. Easement widths for all other streets and roads shall be in accordance with the Authority's Utility Standards Manual (USM) Section ) All design and construction shall be in accordance with the Authority's USM. UL-04 Utility Location & Easement Layout Townhouse Subdivisions on Public Roads Scale: 1" = 50' 03/05/07

36 WATER WATER Not to Scale Water Distribution System Blow-Off Detail WD-01 Revised: 11/28/17

37 INSET Not to Scale Water Distribution System Sampling Station WD-02 Revised: 11/28/17

38 WD-03 Water Distribution System Air Release Valve Not to Scale Revised: 11/28/17

39 WD-04 Water Distribution System Typical Fire Hydrant Not to Scale Revised: 11/28/17

40 60 +/- WM-01 Standard Water Meter Box & Fittings Up to 1" Not to Scale Revised: 11/28/17

41 WM /2" and 2" Water Meter and Service Connection Not to Scale Revised: 11/28/17

42 12" MIN. WM-03 Combined Domestic & Fire Service Meter Vault Detail Not to Scale Revised: 11/28/17

43 NOTE: Irrigation service line shall be connected to the customer's service line on the customer's side of the main meter. Easement/R.O.W. Line Ex. Water Meter (Primary Service) Ex. Customer-owned Service Line To House Polyethylene Tubing Prop. Subtraction Meter 3' +/- 3' +/- To Irrigation System Typical Connection of Subtraction Meter Ford Type 'A32-T' or 'C32-T' Meter Box Cover. Top to be set between 1/2" and 2" above finished grade. Note: Meter box lid shall include a 1-3/4" hole for mounting a touch read pad. Note: Part Numbers shown on this Detail are from Ford Manufacturing Company products. Approved equals may be used. Finished Grade 18" x 30" Round Concrete or PVC Pit-Setter Angle Valve with Padlock Wings Angled Dual Check Valve (Cartridge Style) 18" Min. 24" Max. 14 Gauge Insulated Copper Tracer Wire Attached Here Fill Pit-Setter with Sand or Stone Dust Bedding up to the Bottom of the Meter Yoke. Meter Yoke Bar Connect To Customer Side of Water Service Line 6" Minimum "Pig-Tail" (for connection to Irrigation System) to terminate 2' from meter barrel Meter Box Detail for 5/8" x 3/4" Water Subtraction Meter Note: ALL compression fittings shall include grip joints. Ford HHCA94-323D-G Ford AV94-323W-G Drain on Meter Side of Check Valve. Ford YLN-23 (2) Ford Y502 Meter Yoke Stainless Steel Inserts to be Used Inside Plastic Tubing. WM-04 Meter Yoke Detail Standard Water Subtraction Meter Not to Scale Revised: 03/20/07

44 WM-05 Temporary Hydrant Meter Assembly Not to Scale Revised: 11/28/17

45 WS-01 Standard Water Service Connection For Water Meter Sizes Up to 1'' Not to Scale Revised: 11/28/17

Engineering and Construction Services Division Construction Drawings for Sewers and Watermains. T No. Revision T No. Revision Remarks All T drawings

Engineering and Construction Services Division Construction Drawings for Sewers and Watermains. T No. Revision T No. Revision Remarks All T drawings Engineering and Construction Services Division Construction Drawings for Sewers and Watermains Revision No. 8 April All T drawings New title block for each drawing is now standardized. Revision numbers

More information

SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS

SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS 9. STANDARD DETAILS SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS j:\clerical\royse city\1-4086 general services\168-tech const standards review\tcss manual\2018 tcss manual\sec-9a

More information

NEWTON COUNTY WATER AND SEWERAGE AUTHORITY RESIDENTIAL, COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL SUBDIVISIONS CONSTRUCTION PLANS CHECK LIST

NEWTON COUNTY WATER AND SEWERAGE AUTHORITY RESIDENTIAL, COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL SUBDIVISIONS CONSTRUCTION PLANS CHECK LIST NEWTON COUNTY WATER AND SEWERAGE AUTHORITY RESIDENTIAL, COMMERCIAL, INSTITUTIONAL AND INDUSTRIAL SUBDIVISIONS CONSTRUCTION PLANS CHECK LIST Project Name Checked By Date Designer Check List marks to be

More information

UPDATE LOG FOR STANDARD DRAWINGS Item(s) Changed 6/1/18 STANDARD DRAWINGS

UPDATE LOG FOR STANDARD DRAWINGS Item(s) Changed 6/1/18 STANDARD DRAWINGS Date 6/1/18 STANDARD DRAWINGS UPDATE LOG FOR STANDARD DRAWINGS Item(s) Changed WATER STANDARD DRAWINGS Title Drawing Number Current Date Fire Hydrant and Appurtenance Locations, Improved Streets with Curb

More information

DIVISION APPROVED MATERIAL LIST AND STANDARD DETAILS

DIVISION APPROVED MATERIAL LIST AND STANDARD DETAILS DIVISION 400 - APPROVED MATERIAL LIST AND STANDARD DETAILS Section 403 - STANDARD DETAILS TABLE OF CONTENTS DIVISION 400, Section 403 - STANDARD DETAILS SECTION DETAIL NOS. Application Table 403-1 I. Concrete

More information

CITY OF MUSKEGO DRAFTING STANDARDS

CITY OF MUSKEGO DRAFTING STANDARDS CITY OF MUSKEGO DRAFTING STANDARDS GENERAL - These standards apply to all plans. 1. Plans must be prepared on sheets measuring 36 inch across and 22 inch to 24 inch high unless otherwise specified under

More information

PART 4 STANDARD DRAWINGS FOR CONSTRUCTION

PART 4 STANDARD DRAWINGS FOR CONSTRUCTION 4.0. INTRODUCTION PART 4 STANDARD DRAWINGS FOR CONSTRUCTION In this document, Ivins City adopts the most recent edition (currently 2007), including all amendments, of the APWA Utah Chapter s Manual of

More information

MANHOLES PART I: GENERAL. A. Precast Concrete Manholes

MANHOLES PART I: GENERAL. A. Precast Concrete Manholes MANHOLES PART I: GENERAL A. Precast Concrete Manholes 1) Manholes shall be made of precast concrete sections of which the top section shall be eccentric or flat slab top. The bottom section shall be a

More information

ACSA PLAN REVIEW CHECKLIST (Guideline Only) (4) Standard water and sewer general plan notes (attached).

ACSA PLAN REVIEW CHECKLIST (Guideline Only) (4) Standard water and sewer general plan notes (attached). ACSA PLAN REVIEW CHECKLIST (Guideline Only) Revised: December 3, 2015 General (1) Proper Title (2) Vicinity map on first sheet. (3) Date and latest plan revision. (4) Standard water and sewer general plan

More information

UTILITY AND STREET CONSTRUCTION PLAN REQUIREMENTS SECTION 1

UTILITY AND STREET CONSTRUCTION PLAN REQUIREMENTS SECTION 1 UTILITY AND STREET CONSTRUCTION PLAN REQUIREMENTS SECTION 1 ENGINEERING STANDARDS FOR UTILITY AND STREET CONSTRUCTION PLANS MARCH 2014 CONSTRUCTION PLAN SHEET FORMAT REQUIREMENTS REPRODUCIBLE MYLAR 1.

More information

Existing and proposed contours at 1-foot intervals. The fill and/or excavation quantities in cubic yards.

Existing and proposed contours at 1-foot intervals. The fill and/or excavation quantities in cubic yards. PLAN REQUIREMENTS The plans for street design shall conform to the requirements of Sections 3 and 4. The following requirements shall also be shown on the plans where applicable. Road and Storm Plans:

More information

SECTION MANHOLES

SECTION MANHOLES SECTION 02601 MANHOLES PART 1 GENERAL 1.01 SCOPE OF WORK A. WORK required under this section consists of all materials, accessories, equipment, tools, and labor required to install precast concrete standard

More information

MSD STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY

MSD STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY MSD M etr o p olitan S e w e r Di s t r ict STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY 40203-1911 STANDARD DRAWINGS DIVISION

More information

SECTION 095 SPECIFICATIONS DETAIL DRAWINGS. Index of Detail Drawings

SECTION 095 SPECIFICATIONS DETAIL DRAWINGS. Index of Detail Drawings SECTION 095 SPECIFICATIONS DETAIL DRAWINGS Index of Detail Drawings Flat Top Manhole... 095-1 Splash Drop Manhole and Regular Drop Manhole... 095-2 Special Detail Splash Drop Manhole and Special Detail

More information

B.2 MAJOR SUBDIVISION PRELIMINARY PLAN CHECKLIST

B.2 MAJOR SUBDIVISION PRELIMINARY PLAN CHECKLIST B.2 MAJOR SUBDIVISION PRELIMINARY PLAN CHECKLIST YES* GENERAL SUBMISSION ITEMS Does the submission include: 1. Thirteen (13) copies of completed Application Form? 2. Thirteen (13) copies of the Preliminary

More information

ACWWA DRAWING SUBMITTAL INFORMATION - UTILITY DRAWING REQUIREMENTS

ACWWA DRAWING SUBMITTAL INFORMATION - UTILITY DRAWING REQUIREMENTS ACWWA DRAWING SUBMITTAL INFORMATION - UTILITY DRAWING REQUIREMENTS Detailed construction drawings for system extensions shall be prepared for approval with a submittal to the Authority. All construction

More information

September 21, Mannik Smith Group 1771 North Dixie Highway Monroe, Michigan RE: LA Fitness City File No.: CVLP

September 21, Mannik Smith Group 1771 North Dixie Highway Monroe, Michigan RE: LA Fitness City File No.: CVLP CITY OF ANN ARBOR, MICHIGAN Public Services Area / Engineering 301 E. Huron Street, P.O. Box 8647 Ann Arbor, Michigan 48107 Phone (734) 794-6410 Fax (734) 994-1744 Web: www.a2gov.org Printed on recycled

More information

BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006

BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006 Project Name: BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006 Phase: Unit: # Lots: Development Type (residential, commercial, industrial, etc.) Braselton Project No.

More information

SECTION III SUBMITTALS AND APPROVALS

SECTION III SUBMITTALS AND APPROVALS SECTION III SUBMITTALS AND APPROVALS In order to expedite the approval process of new water distribution system and sanitary sewer collection system extensions, the Hilton Head No. 1 Public Service District

More information

Authorized Agent: City of Manassas Check List Attached: Contact: Address: Phone Number: Fax Number: Developer s Name: Phone Number:

Authorized Agent: City of Manassas Check List Attached: Contact:   Address: Phone Number: Fax Number: Developer s Name: Phone Number: CITY OF MANASSAS DEPARTMENT OF COMMUNITY DEVELOPMENT DEVELOPMENT SERVICES DIVISION 9027 Center Street Room 201 Manassas, Virginia, 20110 Phone: 703-257-8278 Fax: 703-257-5831 Application Date: APPLICANT

More information

STANDARD BID ITEM NUMBERS

STANDARD BID ITEM NUMBERS 10701 TRAFFIC CONTROL LUMP SUM 10702 Traffic Control for Storm Sewer Installation LUMP SUM 10703 Traffic Control for Water Main Installation LUMP SUM 10704 Traffic Control for Sanitary Sewer Installation

More information

Manhole or Catch Basin Type A & B Cone Sections Precast - Design F Manhole or Catch Basin Cover (Reducer Cone Section Precast) Design D

Manhole or Catch Basin Type A & B Cone Sections Precast - Design F Manhole or Catch Basin Cover (Reducer Cone Section Precast) Design D MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Program Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (14-02) MANUAL: Standard

More information

CITY OF REEDLEY NEW DEVELOPMENT PLAN REVIEW CHECK LIST

CITY OF REEDLEY NEW DEVELOPMENT PLAN REVIEW CHECK LIST CITY OF REEDLEY NEW DEVELOPMENT PLAN REVIEW CHECK LIST Tract Number and Subdivision Name: Engineering Firm: Contact Person: Address: City: State: Zip: Phone No. Fax No. Assessor s Parcel Number(s) Tentative

More information

SECTION 39 - MANHOLES TABLE OF CONTENTS

SECTION 39 - MANHOLES TABLE OF CONTENTS SECTION 39 - MANHOLES TABLE OF CONTENTS Section Page 39-1 GENERAL... 39.1 39-2 PRECAST CONCRETE MANHOLES... 39.1 39-2.01 Precast Concrete Sewer Manholes... 39.1 39-2.02 Precast Concrete Storm Drain Manholes...

More information

Grease Interceptor Design Checklist

Grease Interceptor Design Checklist CHECKLIST C2 Revised 5/2/2016 Grease Interceptor Design Checklist Public Works DISCLAIMER - This checklist is provided to Consulting Engineers for the express purpose of assisting them in compiling private

More information

VILLAGE OF VILLA PARK CENTRAL BOULEVARD IMPROVEMENTS LOCATION MAP (NOT TO SCALE) CORTESI AVE. MYRTLE AVE. CENTRAL BLVD.

VILLAGE OF VILLA PARK CENTRAL BOULEVARD IMPROVEMENTS LOCATION MAP (NOT TO SCALE) CORTESI AVE. MYRTLE AVE. CENTRAL BLVD. Q:\VillaPark_IL\11283000 Astor-Myrtle Sewer Separation Preliminary Design\D.4 CAD\Sheets\North\1. Cover.dwg INDEX OF SHEETS 1 COVER 2 GENERAL NOTES 3 SUMMARY OF QUANTITIES 4 ALIGNMENT 5-9 DRAINAGE AND

More information

Pipe Product Catalog Table of Contents

Pipe Product Catalog Table of Contents Pipe Product Catalog Table of Contents Section A: Drawing #: Page Description A1 Reinforced Concrete Pipe A3 Storm Manhole Sizing Chart (48" - 96") A3.1 Storm Manhole Sizing Chart (108" - 144") A4 48"

More information

INSTRUCTIONS: 1. Record the transmittal letter number, date, and subject on the transmittal record sheet located in the front of the manual.

INSTRUCTIONS: 1. Record the transmittal letter number, date, and subject on the transmittal record sheet located in the front of the manual. MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Technical Support Design Services Section TRANSMITTAL LETTER NO. (0-03) MANUAL: Standard Plates DATED: September

More information

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 8

The Manitoba Water Services Board SECTION Standard Construction Specifications September 2013 Page 1 of 8 September 2013 Page 1 of 8 Part 1 General 1.1 DESCRIPTION OF WORK.1 The work described herein shall consist of the construction of air release chambers, flushout chambers, valve chambers, meter chambers

More information

APPENDIX 1: CONSTRUCTION PLAN CHECKLIST

APPENDIX 1: CONSTRUCTION PLAN CHECKLIST APPENDIX 1: CONSTRUCTION PLAN CHECKLIST October 2017 APPENDIX A APPENDIX 1: CONSTRUCTION PLAN CHECKLIST ALL PLANS Plans on 24-inch by 36-inch paper (Originals shall be transmitted on a CD as an electronic

More information

2. Remove from the Standard Plate manual: Standard Plate Index, Sheets 1-4 of 4, Numerical Index of Standard Plates (August 31, 2012)

2. Remove from the Standard Plate manual: Standard Plate Index, Sheets 1-4 of 4, Numerical Index of Standard Plates (August 31, 2012) MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Program Management & Technical Support, Design Support Section TRANSMITTAL LETTER NO. (12-04) MANUAL: Standard

More information

City of Vaughan Engineering Department DESIGN STANDARD DRAWINGS

City of Vaughan Engineering Department DESIGN STANDARD DRAWINGS City of Vaughan Engineering Department DESIGN STANDARD DRAWINGS March 2004 STANDARD DRAWINGS Partners With The Environment March 2004 FORWARD The March 2004 version of the City of Vaughan Design Standard

More information

Valley Road Main Replacement

Valley Road Main Replacement Bonding Provided Construction Co., Construction, Construction, 5% 5% 5% 5% 5% 5% 5% acknowledged 2 - Bidder Acknowledges Receipt of Addendums there was only 1 Affadivit of Preferential Bidders Status not

More information

Miscellaneous. Demolition

Miscellaneous. Demolition Public Improvements Miscellaneous 1 Mobilization L.S. ** 2 Clearing and Grubbing L.S. *** 3 Structural Concrete Incl. Reinforcing C.Y. $1,325.00 4 6" PVC Sleeves L.F. $26.00 Demolition 5 Remove Asphalt

More information

STRUCTURES FOR SANITARY AND STORM SEWERS

STRUCTURES FOR SANITARY AND STORM SEWERS SUDAS Standard Specifications Division 6 - Structures for Sanitary and Storm Sewers Section 600 - Structures for Sanitary and Storm Sewers STRUCTURES FOR SANITARY AND STORM SEWERS PART - GENERAL.0 SECTION

More information

STORM M ANHOLE FOR 42" PIPE AND SM ALLER JOB NO. SHEET NO. DATE MARCH 2015 OF MIN OF 3 CRSES MAX OF 5 CRSES 30"MAX 3 OR 3.5 PRECAST ECCENTIC CONC

STORM M ANHOLE FOR 42 PIPE AND SM ALLER JOB NO. SHEET NO. DATE MARCH 2015 OF MIN OF 3 CRSES MAX OF 5 CRSES 30MAX 3 OR 3.5 PRECAST ECCENTIC CONC 01-APR-2015 13:33 = I:\MSV8i\Plotting\piblack.ptb V:\201001\\C\8x11_Howell_Det\stm_det01_8x11_st01.dgn TIME = MIN 3 CRSES MAX 5 CRSES 3 OR 3.5 PRECAST ECCENTIC CONC ID PIPE GRADE A CONC FILL 4" 8" 2-0"SUMP

More information

SUBJECT: Standard Plates 4132, 4155, Drainage Structures and Castings Info

SUBJECT: Standard Plates 4132, 4155, Drainage Structures and Castings Info MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Project Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (18-01) MANUAL: Standard

More information

C. A. D. STANDARDS. Projection. NAD 1983 Rhode Island State Plane US Feet. Scale 1 = 100. Layers. Appendix H - 1

C. A. D. STANDARDS. Projection. NAD 1983 Rhode Island State Plane US Feet. Scale 1 = 100. Layers. Appendix H - 1 C. A. D. STANDARDS The Authority requires that all CAD drawings be submitted in accordance to the following standards. Using these standards will allow the Authority to efficiently import and attribute

More information

Sewer Line Extension Permit Design Checklist

Sewer Line Extension Permit Design Checklist CHECKLIST C1 Revised 4/7/2017 Sewer Line Extension Permit Design Checklist DISCLAIMER - This checklist is provided to Consulting Engineers for the express purpose of assisting them in compiling sewer line

More information

WATER & SEWER CONSTRUCTION SITE PLAN DESIGN SUMMARY COMMERCIAL & RESIDENTIAL

WATER & SEWER CONSTRUCTION SITE PLAN DESIGN SUMMARY COMMERCIAL & RESIDENTIAL WATER & SEWER CONSTRUCTION SITE PLAN DESIGN SUMMARY COMMERCIAL & RESIDENTIAL This summary is not all inclusive of the requirements set forth by the York County Planning & Development Services, York County

More information

1. TRACER WIRE. I. Application. Material Specification. Page 1 of 16

1. TRACER WIRE. I. Application. Material Specification. Page 1 of 16 Page 1 of 16 1. TRACER WIRE I. Application A Tracer Wire must be installed on all non-metallic watermains and sanitary force mains. The wire shall be installed in such a manner as to be able to properly

More information

SECTION 100 PRELIMINARY CONSIDERATIONS & INSTRUCTIONS

SECTION 100 PRELIMINARY CONSIDERATIONS & INSTRUCTIONS SECTION 100 PRELIMINARY CONSIDERATIONS & INSTRUCTIONS 101 General 102 Submittal Requirements A. Initial Submittal B. Second Submittal 103 Plan Requirements A. Subdivisions B. Site Plans 104 Approval of

More information

CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION

CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 407 NOVEMBER 2013 CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION TABLE OF CONTENTS 407.01

More information

SECTION MANHOLES

SECTION MANHOLES SECTION 33 05 13 MANHOLES PART 1 GENERAL 1.01 SECTION INCLUDES A. CONTRACTOR shall furnish and install precast concrete manhole base, sections, adjusting rings, steps, and manhole ring and cover, complete.

More information

Plan Submittal and Review Checklist

Plan Submittal and Review Checklist Improving quality of life today creating a better tomorrow Plan Submittal and Review Checklist Version 1.2 September 4, 2017 Contents Overview... 2 Plan Submittal Checklist... 2 Plan Review Checklist -

More information

Anne Arundel County Dept. of Inspections and Permits Water Sewer Plan Checklist

Anne Arundel County Dept. of Inspections and Permits Water Sewer Plan Checklist Project Name Project Number Engineer Plans are to be designed based on the standards set forth in the Anne Arundel County Design Manual Standards and Specifications, and all other manuals as stipulated

More information

SUBJECT: Standard Plate Turf Establishment Areas (at Pipe Culvert Ends)

SUBJECT: Standard Plate Turf Establishment Areas (at Pipe Culvert Ends) MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Program Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (14-01) MANUAL: Standard

More information

This addendum forms a part of the Contract Documents dated: August 10, 2012.

This addendum forms a part of the Contract Documents dated: August 10, 2012. Addendum # 1 Date Issued: August 28, 2012 Issued By: Project: Owner: Renker Eich Parks Architects 1609 Dr. Martin Luther King Street North St. Petersburg, Florida 33704 Ph# (727) 821-2986 Fax # (727) 896-4911

More information

Oil-Water Separator Design Checklist

Oil-Water Separator Design Checklist CHECKLIST C3 Revised 5/2/2016 Oil-Water Separator Design Checklist DISCLAIMER - This checklist is provided to Consulting Engineers for the express purpose of assisting them in compiling private oil-water

More information

Current Standard Plates including Transmittal Letters are available on the web at:

Current Standard Plates including Transmittal Letters are available on the web at: MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Project Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (17-04) MANUAL: Standard

More information

Standard Plate 7036 is discontinued. It is replaced by Standard Plan Pedestrian Curb Ramp Details.

Standard Plate 7036 is discontinued. It is replaced by Standard Plan Pedestrian Curb Ramp Details. DEVELOPED BY: Design Standards ISSUED BY: Office of Program Management & Technical Support, Design Support Section TRANSMITTAL LETTER NO. (12-02) MANUAL: Standard Plates DATED: May 11, 2012 SUBJECT: Standard

More information

STORM SEWER SCHEDULE STRUCTURES ALIGNMENT CODES: 'CW'= COMANCHE WAY PIPES BURNING WOOD, COMANCHE, 4TH SHEET NO. UTIL W RESURF ASSESSMENT DISTRICT-2015 U-3 PROJECT NO. 53W1930 COMANCHE WAY STORM SEWER SCHEDULE

More information

REPAIR CLAMP PARTS H fax: MULTIPLIER

REPAIR CLAMP PARTS H fax: MULTIPLIER REPAIR CLAMP PARTS Part Number Component Description Model Number Product Size List Price Unit V001 Neoprene Sheet Gasket AS All Sizes Square Inch V002 Waffle Pattern Gasket (NBR) AS All Sizes Square Inch

More information

SECTION PRECAST CONCRETE SECTIONAL MANHOLES

SECTION PRECAST CONCRETE SECTIONAL MANHOLES SECTION 02545 PRECAST CONCRETE SECTIONAL MANHOLES PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Precast reinforced concrete cylindrical sectional manholes, complete with openings, inserts, hardware,

More information

Charlotte County Utilities DESCRIPTION

Charlotte County Utilities DESCRIPTION As-built Drawings / Surveyor 1. Electronic copy of survey data in tabular form of the utility assets 2. A signed and sealed letter with the following statement: "I hereby certify that the as-built location

More information

ROUTES: 65 SECTIONS: miles in length. THE FOLLOWING ITEMS AND APPROXIMATE QUANTITIES ARE INVOLVED:

ROUTES: 65 SECTIONS: miles in length. THE FOLLOWING ITEMS AND APPROXIMATE QUANTITIES ARE INVOLVED: ARKANSAS DEPARTMENT OF TRANSPORTATION CA0801 HWY. 110 - CLINTON (WIDENING) (S) FEDERAL AID PROJECT ACNHPP-0071(31) THE PURPOSE OF THIS PROJECT IS TO WIDEN HIGHWAY 65 IN VAN BUREN COUNTY. THIS PROJECT CONSISTS

More information

Introduction. Classifications of piping: Industrial. Residential (i.e., plumbing) Carries liquids and gases used in the manufacture of products

Introduction. Classifications of piping: Industrial. Residential (i.e., plumbing) Carries liquids and gases used in the manufacture of products Plumbing Plans Introduction Classifications of piping: Industrial Carries liquids and gases used in the manufacture of products Residential (i.e., plumbing) Carries fresh water, gas, liquid, solid waste

More information

Town of Westlake Construction Plans Review Checklist

Town of Westlake Construction Plans Review Checklist CONSTRUCTION PLANS CONTENTS All Drawings 24 x 36 Cover Sheet Final Plat Site Plan Demolition Plan Utility Plan Drainage Area Map and Calculations Paving Plan & Profile Sheets Storm Drain Plan & Profile

More information

ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030 ADDENDUM NO. 3 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO. 2018-008-COM.00030 To: Prospective Bidders of Record Date: January 8, 2019 The following changes, additions, revisions, and/or deletions

More information

SUBJECT: Standard Plate 9102 Turf Establishment Areas At Pipe Culvert Ends

SUBJECT: Standard Plate 9102 Turf Establishment Areas At Pipe Culvert Ends MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Project Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (17-03) MANUAL: Standard

More information

KC Water Rules and Regulations For Water Main Extensions and Relocations

KC Water Rules and Regulations For Water Main Extensions and Relocations KC Water Rules and Regulations For Water Main Extensions and Relocations MAY 2017 NOTE: Changes from 2016 are highlighted in yellow and appear on Pages 5, 8, 10-11, 13, and 15. Additional changes made

More information

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections

SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS Section 1 Definitions 2 Scope of Work 3 Extent of Work 4 Inspection and Performance of Work 5 Trenching 6 Duct Installation

More information

Utility Structures. Utility vaults, trenches, transformer pads Electrical Pole Bases and switching cubicles

Utility Structures. Utility vaults, trenches, transformer pads Electrical Pole Bases and switching cubicles Utility Structures Utility vaults, trenches, transformer pads Electrical Pole Bases and switching cubicles PRODUCT GUIDE & TECHNICAL REFERENCE MANUAL Providing the right solutions. UTILITY STRUCTURES Perfect

More information

"A" "A" SECTION "A-A" X-SECTION VERTICAL CURB (TYPE B) Village STREET & PAVEMENT STR-05. Engineering Department

A A SECTION A-A X-SECTION VERTICAL CURB (TYPE B) Village STREET & PAVEMENT STR-05. Engineering Department 1" 1/2" PRE-MOLDED NON-EXTRUDING JOINT FILLLER AT EXPANSION JOINTS (MAXIMUM 50' SPACING) 2" R "A" SEE NOTE 3 0.5" 1/8" R (TYP) DEPRESSED 1.5" PAVEMENT THICKNESS 3.5" 5.0" "A" 2" MINIMUM STONE CUSHION GRADATION

More information

STANDARD CATCH BASIN GUTTER LINE CB INLET FRAME & GRATE, GROUTED TO GRADE RINGS AS REQ'D CONCRETE CURB FINISHED GRADE ASPHALT MAX 50 MIN

STANDARD CATCH BASIN GUTTER LINE CB INLET FRAME & GRATE, GROUTED TO GRADE RINGS AS REQ'D CONCRETE CURB FINISHED GRADE ASPHALT MAX 50 MIN CB INLET FRAME & GRATE, GROUTED TO GRADE RINGS AS REQ'D ASPHALT 20 GUTTER LINE CONCRETE CURB FINISHED GRADE PRECAST GRADE RINGS, 2 50 100 MAX PRECAST CB LID GROUT ALL AROUND CB LEAD, INSIDE & OUTSIDE OF

More information

CITY OF LA MARQUE CHAPTER GRAPHIC REQUIREMENTS CONSTRUCTION PLAN AND MISCELLANEOUS REQUIREMENTS

CITY OF LA MARQUE CHAPTER GRAPHIC REQUIREMENTS CONSTRUCTION PLAN AND MISCELLANEOUS REQUIREMENTS CITY OF LA MARQUE CHAPTER 2 -------------------------------------------- GRAPHIC REQUIREMENTS CONSTRUCTION PLAN AND MISCELLANEOUS REQUIREMENTS CHAPTER 2 ------------------------------------------------

More information

FOR SERVICE BOXES IN CONCRETE DRIVEWAYS, SEE NOTE Min. COVER UNDER DITCHES. 600 Min. COVER

FOR SERVICE BOXES IN CONCRETE DRIVEWAYS, SEE NOTE Min. COVER UNDER DITCHES. 600 Min. COVER WOOD SERVICE MARKER STAKE (50 x 00) PAINTED BLUE PL mm FROM PROPERTY LINE STANDARD CONCRETE SERVICE BOX WITH EXTENSION AS REQ'D 00 FINISHED GROUND/ROAD SURFACE FOR SERVICE BOXES IN CONCRETE DRIVEWAYS,

More information

Sewer/Water Utility - Trace Wire Specification

Sewer/Water Utility - Trace Wire Specification Sewer/Water Utility - Trace Wire Specification Materials General All trace wire and trace wire products shall be domestically manufactured in the U.S.A. All trace wire shall have HDPE insulation intended

More information

SECTION UNDERGROUND POWER DUCT AND SUB-STRUCTURES. A. Section : Trenching, Backfilling, and Compacting

SECTION UNDERGROUND POWER DUCT AND SUB-STRUCTURES. A. Section : Trenching, Backfilling, and Compacting SECTION 33 71 19 UNDERGROUND POWER DUCT AND SUB-STRUCTURES PART 1 GENERAL 1.1 RELATED WORK A. Section 31 23 33: Trenching, Backfilling, and Compacting B. Section 32 01 00: Site Restoration and Rehabilitation

More information

3. The PAC (Permit Application Center) will notify the design professional of plan review results.

3. The PAC (Permit Application Center) will notify the design professional of plan review results. Planning and Development Dept. Infrastructure Division P.O. Box 11706, or 155 Johnston Street Rock Hill, South Carolina 29731-1706 Phone: 803-329-5515 FAX: 803-329-7228 www.cityofrockhill.com AS-BUILT

More information

Clarifications in italics added July 2018

Clarifications in italics added July 2018 SECTION 10000 RECORD DRAWING CHECKLIST Clarifications in italics added July 2018 All entities who construct public infrastructure, private streets, private storm drain collection systems and travel lanes,

More information

CITY OF VISTA STANDARD DRAWINGS

CITY OF VISTA STANDARD DRAWINGS CITY OF VISTA STANDARD DRAWINGS May, 2015 THIS SHEET INTENTIONALLY LEFT BLANK TABLE OF CONTENTS MODIFICATIONS Modifications to San Diego Regional Standard Drawings DRAINAGE STRUCTURES DRN 01 Corrugated

More information

Foundation Specifications for 5.6-Meter Modular Earth Station Antennas

Foundation Specifications for 5.6-Meter Modular Earth Station Antennas Installation Instructions Bulletin 237029 Foundation Specifications for 5.6-Meter Modular Earth Station Antennas Revision A Introduction This document specifies typical foundation characteristics, designs,

More information

DESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA

DESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA DESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA 94544-1395 PUBLIC WORKS DESIGN GUIDELINES TABLE OF CONTENTS SD-100 SERIES SPECIAL DRAWINGS SD-100 8/1991 SILT

More information

Foundation Specifications for 7.6-Meter Modular Earth Station Antennas

Foundation Specifications for 7.6-Meter Modular Earth Station Antennas Installation Instructions Foundation Specifications for 7.6-Meter Modular Earth Station Antennas Bulletin 237186A Revision A Introduction This document specifies typical foundation characteristics, designs,

More information

SUPPLEMENTARY STANDARD DETAIL DRAWINGS

SUPPLEMENTARY STANDARD DETAIL DRAWINGS CITY OF MAPLE RIDGE DESIGN AND CONSTRUCTION DOCUMENTS Part 4 SUPPLEMENTARY STANDARD DETAIL DRAWINGS September 2015 Updated: October 2015 THIS PAGE INTENTIONALLY LEFT BLANK City of Maple Ridge Supplementary

More information

LOWNDES COUNTY ENGINEERING PLAN REVIEW CHECKLIST. Design Professional: Phone: Developer: Phone: 2 nd Submittal (No Fee)

LOWNDES COUNTY ENGINEERING PLAN REVIEW CHECKLIST. Design Professional: Phone: Developer: Phone: 2 nd Submittal (No Fee) MEMORANDUM MICHAEL B. FLETCHER, P.E. COUNTY ENGINEER 327 N. Ashley Street Valdosta, GA 31601 Telephone: (229) 671-2424 Fax: (229) 245-5299 mfletcher@lowndescounty.com LOWNDES COUNTY ENGINEERING PLAN REVIEW

More information

HUSSEY GAY BELL SAVANNAH, GEORGIA

HUSSEY GAY BELL SAVANNAH, GEORGIA HUSSEY GAY BELL SAVANNAH, GEORGIA ------------------------------------------------------------------------------------------------------------ ADDENDUM NO. 3 TO THE CONTRACT DOCUMENTS AND TECHNICAL SPECIFICATIONS

More information

CHECKLIST PRELIMINARY SUBDIVISION AND PRELIMINARY SITE PLAN

CHECKLIST PRELIMINARY SUBDIVISION AND PRELIMINARY SITE PLAN N/A Waiver (1) Four (4) copies of application form. (2) Fifteen (15) copies of plan (3) Subdivision/site plan application fee & professional review escrow deposit (4) Variance application fee & professional

More information

RECORD DRAWINGS REVISED TO CONFORM TO CONSTRUCTION RECORDS PROVIDED BY CONTRACTOR GMG BY DATE 11/13 CRS NO.

RECORD DRAWINGS REVISED TO CONFORM TO CONSTRUCTION RECORDS PROVIDED BY CONTRACTOR GMG BY DATE 11/13 CRS NO. CELL: (715) 803-8009 MABOSI@WISCONSINPUBLICSERVICE.COM CELL: (715) 573-7806 CHVIRCKS@WISCONSINPUBLICSERVICE.COM CALVIN.KLADE@FTR.COM DGAU@KRONENWETTER.COM SCOTT OLSEN (715) 302-1348 S REVISED TO CONFORM

More information

MAY J. Collins Engineering Associates, LLC San Jose Blvd. Jacksonville, Florida 32223

MAY J. Collins Engineering Associates, LLC San Jose Blvd. Jacksonville, Florida 32223 PROJECT LOCATION: 95 NOCATEE PARKWAY PONTE VEDRA, FL. 38 J. Collins Engineering Associates, LLC 56-3 San Jose Blvd. Jacksonville, Florida 32223 NOT TO SCALE 904-262-42 sm sm ON DRAWING WHERE SECTION OR

More information

CITY OF VISTA STANDARD DRAWINGS

CITY OF VISTA STANDARD DRAWINGS CITY OF VISTA STANDARD DRAWINGS May, 2015 THIS SHEET INTENTIONALLY LEFT BLANK TABLE OF CONTENTS MODIFICATIONS Modifications to San Diego Regional Standard Drawings DRAINAGE STRUCTURES DRN 01 Corrugated

More information

Section E NSPS MODEL STANDARDS FOR TOPOGRAPHIC SURVEYS Approved 3/12/02

Section E NSPS MODEL STANDARDS FOR TOPOGRAPHIC SURVEYS Approved 3/12/02 Section E NSPS MODEL STANDARDS FOR TOPOGRAPHIC SURVEYS Approved 3/12/02 1. INTRODUCTION This standard is written to provide the professional surveyor (Surveyor) and the client with a guideline for producing

More information

CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA (360)

CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA (360) CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA 98501 (360) 754-4180 Email: cdd@ci.tumwater.wa.us WATER-SEWER-STREET-STORM (IN CITY) Submittal Checklist TUM - RCVD BY DATE STAMP APPLICANT INFORMATION

More information

1.1 GENERAL RECORD DRAWING REQUIREMENTS

1.1 GENERAL RECORD DRAWING REQUIREMENTS Page 1 of 5 VILLAGE OF ROMEOVILLE RECORD DRAWINGS CHECKLIST PART I GENERAL Record drawings are required to provide a means of schematic verification that the intent of the approved engineering design has

More information

General Information...SA1-SA4

General Information...SA1-SA4 SECTION S INDEX Product Description Page Number General Information................................................................SA1-SA4 Type FSK Thruwall & Floor Seal For Conduit, Pipe or Tubing............................

More information

INSTALLATION INSTRUCTIONS. March 2016 FOR FURTHER QUESTIONS, PLEASE CALL

INSTALLATION INSTRUCTIONS. March 2016 FOR FURTHER QUESTIONS, PLEASE CALL March 2016 INSTALLATION INSTRUCTIONS FOR FURTHER QUESTIONS, PLEASE CALL 775 440 2025 JENSEN WATER RESOURCES 521 Dunn Circle, Sparks, NV 89431 JensenPumps.com Figure 1: This illustration shows a complete

More information

WATER STRUCTURE LEGAL & SURVEY TOPOGRAPHY/GRADING LANDSCAPE/VEGETATION

WATER STRUCTURE LEGAL & SURVEY TOPOGRAPHY/GRADING LANDSCAPE/VEGETATION REVISION IDENTIFIER DETAIL LABEL CALLOUT LABEL 1 SHEET ABANDONED ASBESTOS CEMENT BALK OF WALK BEGINNING OF CURVE BENCH MARK BUILDING CAPACITY CAST IRON CATCH BASIN CATCH BASIN MANHOLE CENTER LINE CERTIFICATE

More information

REQUEST FOR BIDS WELL #4 ABANDONMENT

REQUEST FOR BIDS WELL #4 ABANDONMENT REQUEST FOR BIDS WELL #4 ABANDONMENT Department of Public Services 1015 S Lincoln Avenue Three Rivers, MI 49093 (269) 273-1845 Table of Contents Well #4 Abandonment... 8 Performance Bids... 8 I. Instructions...

More information

10010 RECORD DRAWING INFORMATION

10010 RECORD DRAWING INFORMATION SECTION 10000 RECORD DRAWING CHECK LIST All entities who construct public infrastructure, private streets, private storm drain collection systems and travel lanes, shall submit to the Town of Cary Engineering

More information

Thru Wall Floor Seals For New Installation

Thru Wall Floor Seals For New Installation The O-Z/Gedney Thruwall and Floor Seals provide a positive means of sealing pipe, conduit or tube where they pass through a concrete foundation of a structure below grade or below ground water level or

More information

GENERAL ISOMETRIC LAYOUT

GENERAL ISOMETRIC LAYOUT EXISTING OR PROPOSED WIPER WALL SUPPORT STRUCTURE GATE LID CARBATHAN HG 0 WEB GRAY LOWER PAN GRATING ALUMINUM WIPER WALL CARBATHANE HG, 90 GRAY STRUCTURAL SPECIFICATIONS:. FLOODGATE MATERIAL TO BE ALUMINUM

More information

SYARIKAT BEKALAN AIR SELANGOR SDN BHD

SYARIKAT BEKALAN AIR SELANGOR SDN BHD NOTE : 1. FOR LEGEND, ABBREVIATION AND GENERAL NOTES SEE DRG. NO. SYA / STD / 001. 2. ALL DIMENSIONS ARE IN mm UNLESS OTHERWISE STATED. 3. ACTUAL LENGTH OF PE COMMUNICATION PIPES SHALL BE DETERMINED ON

More information

Standard Specifications

Standard Specifications Standard Specifications PART 1.00 GENERAL 1.01 DECRIPTION SECTION 02620 PRECAST REINFORCED CONCRETE SANITARY MANHOLES A. Work included: The Contractor shall furnish all labor, materials, equipment, and

More information

18" 1.5" 3"R 11.5" 10" 3-1/2" MINIMUM STONE CUSHION GRADATION CA-6

18 1.5 3R 11.5 10 3-1/2 MINIMUM STONE CUSHION GRADATION CA-6 18" 1.5" 3"R 1.5" 4"R 1" 11.5" 10" 13.5" 5" 3-1/2" MINIMUM STONE CUSHION GRADATION CA-6 NOTES: 1. REINFORCEMENT: PROVIDE TWO (2) #4 REINFORCING BARS CONTINUOUS BETWEEN EXPANSION JOINTS, WITH LOCATION SPACING

More information

Current Standard Plates including Transmittal Letters are available on the web at:

Current Standard Plates including Transmittal Letters are available on the web at: MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Project Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (15-03) MANUAL: Standard

More information

F-5-1a. Concrete Bollards (Detail 1 of 2) WEIGHT: 166kg. WEIGHT: 227kg. WEIGHT: 113kg. WEIGHT: 212kg

F-5-1a. Concrete Bollards (Detail 1 of 2) WEIGHT: 166kg. WEIGHT: 227kg. WEIGHT: 113kg. WEIGHT: 212kg Contents F-5-1a Concrete Bollards F-5-1b Concrete Bollards F-5-2 Concrete Bollards with City Logo F-5-3 Cast Iron Bollards F-5-4 Decorative Steel Bollard F-5-5 Swivel P Gate Steel Bollard F-5-6 Steel Bollard

More information

MH Table of Contents Standard Title/Scope Page Table of Contents SCE Public

MH Table of Contents Standard Title/Scope Page Table of Contents SCE Public MH Table of Contents Standard Title/Scope MH 300 MH 310 MH 318 MH 320 MH 325 MH 330 MH 335 MH 340 MH 350 Manholes Requirements MH 300.1 Manholes Requirements...........................................

More information

Meter Box Access Solutions

Meter Box Access Solutions Meter Box Access Solutions Table of Contents Meter Box Access Solutions Oval Meter Boxes Round Meter Boxes Rectangular Meter Boxes Meter Pits Adapter Rings Meter Lids Meter Covers, Plates and Lids Accessories

More information

SAUSALITO-MARIN CITY SANITARY DISTRICT MISCELLANEOUS UPGRADES PROJECT. Addendum No. 2

SAUSALITO-MARIN CITY SANITARY DISTRICT MISCELLANEOUS UPGRADES PROJECT. Addendum No. 2 SAUSALITO-MARIN CITY SANITARY DISTRICT MISCELLANEOUS UPGRADES PROJECT Addendum No. 2 The following shall modify the Contract Documents. The work shall be accomplished in accordance with such modifications.

More information