STANDARD BID ITEM NUMBERS
|
|
- Brice Wilson
- 6 years ago
- Views:
Transcription
1 10701 TRAFFIC CONTROL LUMP SUM Traffic Control for Storm Sewer Installation LUMP SUM Traffic Control for Water Main Installation LUMP SUM Traffic Control for Sanitary Sewer Installation LUMP SUM TYPE III BARRICADE EACH Field Office LUMP SUM MOBILIZATION LUMP SUM Mobilization for Storm Sewer Installation LUMP SUM Mobilization for Water Main Installation LUMP SUM Mobilization for Sanitary Sewer Installation LUMP SUM
2 20101 Excavation Cut C.Y Rock Excavation C.Y Ditching T.F Undercut C.Y Finish Grading LUMP SUM Fill TON Fill C.Y Select Fill Borrow TON Select Fill Borrow C.Y Select Fill Sand TON Select Fill Sand C.Y Select Fill Gravel TON Select Fill Gravel C.Y Select Fill Crusher Run Crushed Stone TON Select Fill Crushed Concrete TON Salvable Crushed Stone TON Crushed Stone Base Course TON Clear Stone TON Breaker Run TON Topsoil S.Y Heavy Riprap C.Y Heavy Riprap TON Heavy Riprap Filter Fabric S.Y Geotextile Fabric Type SAS Non Woven S.Y Underdrain L.F Sawcut Concrete Pavement L.F Sawcut Concrete Pavement Full Depth L.F Sawcut Bituminous Pavement L.F Remove Sewer Access Structure EACH Remove Catchbasin EACH Remove Inlet EACH Remove Pipe L.F Remove Concrete Pavement S.Y Remove Concrete Curb & Gutter L.F Remove Concrete Sidewalk & Drive S.F Remove Concrete Steps S.F Remove Guard Rail L.F Remove Fence L.F Abandon Sewer Access Structure EACH Abandon Catchbasin EACH
3 20333 Abandon Inlet EACH Abandon Sewer Pipe with Slurry C.Y Pipe Plug EACH Clearing I.D Clearing STA Grubbing I.D Grubbing STA Adjust Sewer Access Structure EACH Adjust Catchbasin EACH Adjust Inlet EACH Adjust Valve Casting EACH Adjust Monument EACH Obliterate Street STA Sun Terrace Seeding S.Y Shade Terrace Seeding S.Y Temporary Seeding S.Y Infiltration Seeding S.Y Detention Basin Seeding S.Y Tall Grass Prairie Seeding S.Y Sodding S.Y Silt Fence Complete L.F Erosion Matting, Class I, Type URBAN S.Y Erosion Matting, Class I, Type A S.Y Erosion Matting, Class I, Type B S.Y Erosion Matting, Class II, Type A S.Y Erosion Matting, Class II, Type B S.Y Erosion Matting, Class II, Type C S.Y Erosion Matting, Class III, Type A S.Y Erosion Matting, Class III, Type B S.Y Erosion Matting, Class III, Type C S.Y Erosion Matting, Class III, Type D S.Y Erosion Bales Complete EACH Clear Stone Berm for Erosion Control EACH Construction Entrance EACH Terrace Restoration T.F Terrace Restoration S.Y.
4 30101 #4 Epoxy Coated Pavement Tie EACH #5 Epoxy Coated Pavement Tie EACH #6 Epoxy Coated Pavement Tie EACH #7 Epoxy Coated Pavement Tie EACH #8 Epoxy Coated Pavement Tie EACH #9 Epoxy Coated Pavement Tie EACH #10 Epoxy Coated Pavement Tie EACH #11 Epoxy Coated Pavement Tie EACH #12 Epoxy Coated Pavement Tie EACH Inch Epoxy Coated Dowel Bar EACH /8 Inch Epoxy Coated Dowel Bar EACH /4 Inch Epoxy Coated Dowel Bar EACH /8 Inch Epoxy Coated Dowel Bar EACH /2 Inch Epoxy Coated Dowel Bar EACH Epoxy Coated Bar Steel Reinforcing LBS Epoxy Coated Bar Steel Reinforcing L.F COLD WEATHER PROTECTION OF CONCRETE SIDEWALK & DR L.F COLD WEATHER PROTECTION OF CONCRETE CURB & GUTTER L.F COLD WEATHER PROTECTION OF CONCRETE SIDEWALK & DR L.F COLD WEATHER PROTECTION OF CONCRETE CURB & GUTTER L.F Type A Slurry C.Y Type B Slurry C.Y Type "A" Concrete Curb & Gutter L.F Type "B" Concrete Curb & Gutter L.F Type "X" Concrete Curb & Gutter L.F Type "D" Concrete Curb & Gutter L.F Type "E" Concrete Curb & Gutter L.F Type "G" Concrete Curb & Gutter L.F Type "H" Concrete Curb & Gutter L.F Hand Formed Concrete Curb & Gutter (Tree Locations) L.F Inch Concrete Sidewalk S.F Inch Concrete Sidewalk & Drive S.F Commercial Drive Opening EACH Concrete Traffic Island S.F Concrete Mountable Median S.F Concrete Steps S.F Profile Sawcut L.F.
5 30401 Concrete Retaining Wall S.F Boulder Retaining Wall S.F Timber Retaining Wall S.F Split Block Retaining Wall S.F Lannon Stone Retaining Wall S.F RESET MONUMENT EACH
6 40201 HMA Pavement Type E-0.3 TON HMA Pavement Type E-1 TON HMA Pavement Type E-3 TON HMA Pavement Type E-10 TON HMA Pavement Type SMA TON Tack Coat GAL Seal Coat GAL Machine Laid Asphalt Curb L.F Asphalt Drive & Terrace S.Y Asphalt Drive & Terrace TON Asphalt Walk & Bikepath S.Y Asphalt Walk & Bikepath TON Asphalt Material For Curb Front Fill L.F Grinding S.Y Pavement Joint Grinding L.F Full Width Grinding for Patch S.Y Pulverize and Shape S.Y Undercut S.Y Base Patch Grinding, Method 1 S.Y Base Patch Grinding, Method 2 S.Y Base Patch Grinding, Method 3 S.Y Ramping SAS EACH Asphalt Base Patching, 5-8 Inch S.Y Asphalt Base Patching, 8-10 Inch S.Y Asphalt Base Patching, Over 10 inches S.Y SAS Adjusting Ring EACH Adjust Access Structure Casting - Resurfacing EACH Adjust Catchbasin Casting - Resurfacing EACH Adjust Inlet Casting, Type "H" - Resurfacing EACH Adjust Inlet Casting, "Tub" Type - Resurfacing EACH Rebuild Inlet - Resurfacing EACH Adjust Valve Casting, Method #1 - Resurfacing EACH Adjust Valve Casting, Method #2 - Resurfacing EACH Adjust Monument Casting - Resurfacing EACH Rebuild Access Structure Top - Resurfacing EACH Remove and Replace Concrete Curb & Gutter, Machine Placed - Res L.F Remove and Replace Concrete Curb & Gutter, Hand Placed - Resurfa L.F Remove and Replace 5" Thick Concrete Sidewalk - Resurfacing S.F Remove and Replace 7" Thick Concrete Sidewalk - Resurfacing S.F Crushed Stone Base Course - Resurfacing TON Remove Asphalt Surface - Resurfacing S.Y.
7 40392 Remove Concrete Utility Patch L.F Inch Concrete Pavement S.Y Inch Concrete Pavement S.Y Inch Concrete Pavement S.Y Inch Concrete Pavement S.Y Inch Concrete Pavement S.Y Concrete Pavement Reconstruction S.Y.
8 50101 RCBC Roof Repair, Type I EACH RCBC Roof Repair, Type II EACH Reconstruct Bench and Flowline(s) EACH ROCK EXCAVATION C.Y TYPE II DEWATERING LUMP SUM SELECT BACKFILL FOR STORM SEWER T.F SELECT BACKFILL FOR SANITARY SEWER T.F ADDITIONAL FILL C.Y Utility Trench Patch Type I T.F Utility Trench Patch Type I S.Y Utility Trench Patch Type II T.F Utility Trench Patch Type II S.Y Utility Trench Patch Type III T.F Utility Trench Patch Type III S.Y Utility Trench Patch Type IV T.F Utility Trench Patch Type IV S.Y Utility Trench Patch Temporary T.F Utility Trench Patch Temporary S.Y Inch PVC Sanitary Sewer Pipe L.F Inch PVC Sanitary Sewer Pipe L.F Inch PVC Sanitary Sewer Pipe L.F Inch PVC Sanitary Sewer Pipe L.F Inch PVC Sanitary Sewer Pipe L.F Inch PVC Sanitary Sewer Pipe L.F Inch PVC Sanitary Sewer Pipe L.F Inch CW PVC Sanitary Sewer Pipe L.F Inch CW PVC Sanitary Sewer Pipe L.F Inch CW PVC Sanitary Sewer Pipe L.F Inch CW PVC Sanitary Sewer Pipe L.F Inch CW PVC Sanitary Sewer Pipe L.F Inch CW PVC Sanitary Sewer Pipe L.F Inch CW PVC Sanitary Sewer Pipe L.F Inch PVC PRESSURE Sanitary Sewer Pipe L.F Inch PVC PRESSURE Sanitary Sewer Pipe L.F Inch PVC PRESSURE Sanitary Sewer Pipe L.F Inch PVC PRESSURE Sanitary Sewer Pipe L.F Inch PVC PRESSURE Sanitary Sewer Pipe L.F Inch PVC PRESSURE Sanitary Sewer Pipe L.F Inch PVC PRESSURE Sanitary Sewer Pipe L.F Inch RCP Sanitary Sewer Pipe L.F.
9 Inch RCP Sanitary Sewer Pipe L.F Inch RCP Sanitary Sewer Pipe L.F Inch RCP Sanitary Sewer Pipe L.F Inch RCP Sanitary Sewer Pipe L.F Inch RCP Sanitary Sewer Pipe L.F Inch RCP Sanitary Sewer Pipe L.F Inch Sanitary Sewer Lateral L.F Inch Sanitary Sewer Lateral L.F Sanitary Sewer Lateral L.F Reconnect EACH Sanitary Sewer Riser V.F Variable Sized Wyes EACH Compression Coupling EACH Wastewater Control LUMP SUM INCH STORM SEWER PIPE L.F INCH STORM SEWER PIPE L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch RCP Storm Sewer Pipe L.F Inch x 23 Inch HERCP Storm Sewer Pipe L.F Inch x 30 Inch HERCP Storm Sewer Pipe L.F Inch x 38 Inch HERCP Storm Sewer Pipe L.F Inch x 45 Inch HERCP Storm Sewer Pipe L.F Inch x 53 Inch HERCP Storm Sewer Pipe L.F Inch x 60 Inch HERCP Storm Sewer Pipe L.F Inch x 68 Inch HERCP Storm Sewer Pipe L.F Inch x 76 Inch HERCP Storm Sewer Pipe L.F Inch x 83 Inch HERCP Storm Sewer Pipe L.F.
10 Inch x 91 Inch HERCP Storm Sewer Pipe L.F Inch x 98 Inch HERCP Storm Sewer Pipe L.F Inch x 106 Inch HERCP Storm Sewer Pipe L.F Inch x 113 Inch HERCP Storm Sewer Pipe L.F Inch x 123 Inch HERCP Storm Sewer Pipe L.F. RESERVED for Storm Sewer Wyes, Tees, Angles, or Other Precast EACH Sections Inch RCP AE EACH Inch RCP AE EACH Inch RCP AE EACH Inch RCP AE EACH Inch RCP AE EACH Inch RCP AE EACH Inch RCP AE EACH Inch RCP AE EACH Inch RCP AE EACH Inch RCP AE EACH Inch RCP AE EACH Inch RCP AE EACH Inch RCP AE EACH Inch RCP AE EACH Inch RCP AE EACH Inch RCP AE EACH Inch x 23 Inch HERCP AE EACH Inch x 30 Inch HERCP AE EACH Inch x 38 Inch HERCP AE EACH Inch x 45 Inch HERCP AE EACH Inch x 53 Inch HERCP AE EACH Inch x 60 Inch HERCP AE EACH Inch x 68 Inch HERCP AE EACH Inch x 76 Inch HERCP AE EACH Inch x 83 Inch HERCP AE EACH Inch x 91 Inch HERCP AE EACH Inch x 98 Inch HERCP AE EACH Inch x 106 Inch HERCP AE EACH Inch x 113 Inch HERCP AE EACH Inch x 123 Inch HERCP AE EACH Joint Ties EACH Concrete Collar EACH RESERVED for Box Culverts L.F RESERVED for Box Culvert Wingwalls EACH
11 Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch RCP AE GATE EACH Inch x 23 Inch HERCP AE GATE EACH Inch x 30 Inch HERCP AE GATE EACH Inch x 38 Inch HERCP AE GATE EACH Inch x 45 Inch HERCP AE GATE EACH Inch x 53 Inch HERCP AE GATE EACH Inch x 60 Inch HERCP AE GATE EACH Inch x 68 Inch HERCP AE GATE EACH Inch x 76 Inch HERCP AE GATE EACH Inch x 83 Inch HERCP AE GATE EACH Inch x 91 Inch HERCP AE GATE EACH Inch x 98 Inch HERCP AE GATE EACH Inch x 106 Inch HERCP AE GATE EACH Inch x 113 Inch HERCP AE GATE EACH Inch x 123 Inch HERCP AE GATE EACH RESERVED for Box Culvert INLET GATES EACH RESERVED for Box Culvert OUTLET GATES EACH ' DIA. SANITARY SAS EACH ' DIA. SANITARY SAS EACH ' DIA. SANITARY SAS WITH SALVAGED CASTING EACH ' DIA. SANITARY SAS WITH SALVAGED CASTING EACH 'X3' CATCHBASIN EACH 'x6' CATCHBASIN EACH 'X3' STORM SAS EACH 'X4' STORM SAS EACH 'X5' STORM SAS EACH
12 'X6' STORM SAS EACH 'X3' CATCHBASIN WITH SALVAGED CASTING EACH 'x6' CATCHBASIN WITH SALVAGED CASTING EACH 'X3' STORM SAS WITH SALVAGED CASTING EACH 'X4' STORM SAS WITH SALVAGED CASTING EACH 'X5' STORM SAS WITH SALVAGED CASTING EACH 'X6' STORM SAS WITH SALVAGED CASTING EACH TYPE "H" INLET EACH TYPE "S" INLET EACH Type "H" Inlet with Salvaged Casting EACH TYPE "S" INLET WITH SALVAGED CASTING EACH SADDLED INLET TYPE I EACH SADDLED INLET TYPE II EACH TERRACE INLET EACH CURB OUTLET STRUCTURE EACH INTERNAL CHIMNEY SEAL EACH Inch Sanitary Sewer Outside Drop V.F Inch Sanitary Sewer Outside Drop V.F INSIDE DROP V.F SANITARY SEWER TAP EACH STORM SEWER TAP EACH Utility Line Opening EACH CONCRETE SUPPORTS EACH REINFORCED CONCRETE BEAM SUPPORT EACH
13 60201 Furnish & Install 1 Inch Cable-In-Duct by "Open Trench" Method L.F Install City-Furnished 1 Inch Cable-In-Duct by "Open Trench" Method L.F Furnish & Install 1 Inch Cable-In-Duct L.F Install City-Furnished 1 Inch Cable-In-Duct L.F Furnish & Install 1 1/4 Inch Cable-In-Duct by "Open Trench" Method L.F Install City-Furnished 1 1/4 Inch Cable-In-Duct by "Open Trench" Met L.F Furnish & Install 1 1/4 Inch Cable-In-Duct L.F Install City-Furnished 1 1/4 Inch Cable-In-Duct L.F Furnish & Install 3 Inch PVC (Schedule 80) Conduit by "Open Trench" L.F Furnish & Install 3 Inch PVC (Schedule 80) Conduit L.F Furnish & Install 3 Inch PVC (Schedule 40) Conduit by "Open Trench" L.F Furnish & Install 3 Inch PVC (Schedule 40) Conduit L.F Furnish & Install 2 1/2 Inch PVC (Schedule 80) Conduit by "Open Tre L.F Furnish & Install 2 1/2 Inch PVC (Schedule 80) Conduit L.F Furnish & Install 2 1/2 Inch PVC (Schedule 40) Conduit by "Open Tre L.F Furnish & Install 2 1/2 Inch PVC (Schedule 40) Conduit L.F Furnish & Install 2 Inch PVC (Schedule 80) Conduit by "Open Trench" L.F Furnish & Install 2 Inch PVC (Schedule 80) Conduit L.F Furnish & Install 2 Inch PVC (Schedule 40) Conduit by "Open Trench" L.F Furnish & Install 2 Inch PVC (Schedule 40) Conduit L.F Furnish & Install 1 1/4 Inch PVC (Schedule 40) Conduit by "Open Tre L.F Furnish & Install 1 1/4 Inch PVC (Schedule 40) Conduit L.F Furnish & Install 1 Inch PVC (Schedule 40) Conduit by "Open Trench" L.F Furnish & Install 1 Inch PVC (Schedule 40) Conduit L.F Gopher Raceway for Electrical Conduit or Cable-In-Duct L.F Furnish & Install 6 #4 Wires in Existing or Contractor-Installed Condui L.F Furnish & Install 5 #4 Wires in Existing or Contractor-Installed Condui L.F Furnish & Install 3 #4 Wires in Existing or Contractor-Installed Condui L.F Furnish & Install 2 #4 Wires in Existing or Contractor-Installed Condui L.F Remove Existing Aerial Distribution Wiring LUMP SUM Construct LB-2 Base EACH Construct LB-2 Base EACH Construct LB-3 Base EACH Construct LB-4 Base EACH Construct LB-7 Base EACH Construct LB-8 Base EACH Construct Type "G' Base EACH Construct Type "M' Base EACH Construct Type "P' Base EACH Remove Street Light Unit EACH Remove Street Light Base EACH Remove Street Light Pole EACH
14 60424 Remove Traffic Signal or Fire Alarm Base EACH Abandon Existing Handhole EACH Abandon Existing Manhole EACH Auger Street Light Base EACH Install City Furnished Street Light Unit EACH Install City-Furnished Street Light Unit, Twin Arms EACH Install City-Furnished Pedsetrian Street Light Unit EACH Electrical Trench L.F Electrical Trench Paved Roadway EACH Install City-Furnished Prewired Control Panel EACH Construct Electrical Manhole Type "I' EACH Construct Electrical Manhole Type "II' EACH Construct Electrical Handhole Type "I' EACH Construct Electrical Handhole Type "II' EACH Construct Electrical Box-Out EACH
15 70001 Furnish and Install 4 Inch Pipe & Fittings L.F Furnish and Install 6 Inch Pipe & Fittings L.F Furnish and Install 8 Inch Pipe & Fittings L.F Furnish and Install 10 Inch Pipe & Fittings L.F Furnish and Install 12 Inch Pipe & Fittings L.F Furnish and Install 16 Inch Pipe & Fittings L.F Furnish and Install 20 Inch Pipe & Fittings L.F Furnish and Install 24 Inch Pipe & Fittings L.F Furnish and Install 1 Inch Service Laterals L.F Furnish and Install 1 1/2 Inch Service Laterals L.F Furnish and Install 2 Inch Service Laterals L.F Furnish and Install 18 Inch Steel Casing L.F Furnish and Install 20 Inch Steel Casing L.F Furnish and Install 24 Inch Steel Casing L.F Furnish and Install 30 Inch Steel Casing L.F Rock Excavation C.Y Additional Excavation, Including Undercut C.Y Removal of Excess Amounts of Boulders C.Y Cut-In Connection Each Furnish and Install Hydrant Each Select Fill - Sand for Water L.F Lead Service Replacement L.F Extend and Reconnect Service Lateral L.F Reconnect or Disconnect Service Lateral Each Furnish and Install Styrofoam L.F Cut Off Existing Water Main Each Abandon Water Valve Box Each Abandon Hydrant Each Abandon Water Valve Access Structure Each Adjust Water Valve Box Each Relocate Hydrant Each Water Valve Access Structure Each Install Boltless Restrained Joint Pipe & Fittings Each Tunneling and Jacking Water Pipe L.F Trench Restoration for Water Main L.F Cut Out Existing Water Main Fitting Each Cut Out and Replace Existing Water Main Valve Each
Miscellaneous. Demolition
Public Improvements Miscellaneous 1 Mobilization L.S. ** 2 Clearing and Grubbing L.S. *** 3 Structural Concrete Incl. Reinforcing C.Y. $1,325.00 4 6" PVC Sleeves L.F. $26.00 Demolition 5 Remove Asphalt
More informationCITY OF DANA POINT DEVELOPMENT REVIEW
Section I EARTHWORK CITY OF DANA POINT DEVELOPMENT REVIEW COST ESTIMATE UNIT PRICE LIST May 2002 Page 1 of 12 Section I EARTHWORK TABLE OF CONTENTS SECTION AND TOPICS...PAGE INTRODUCTION... i I EARTHWORK...
More informationPART 4 STANDARD DRAWINGS FOR CONSTRUCTION
4.0. INTRODUCTION PART 4 STANDARD DRAWINGS FOR CONSTRUCTION In this document, Ivins City adopts the most recent edition (currently 2007), including all amendments, of the APWA Utah Chapter s Manual of
More informationStandard Plate 7036 is discontinued. It is replaced by Standard Plan Pedestrian Curb Ramp Details.
DEVELOPED BY: Design Standards ISSUED BY: Office of Program Management & Technical Support, Design Support Section TRANSMITTAL LETTER NO. (12-02) MANUAL: Standard Plates DATED: May 11, 2012 SUBJECT: Standard
More informationVILLAGE OF VILLA PARK CENTRAL BOULEVARD IMPROVEMENTS LOCATION MAP (NOT TO SCALE) CORTESI AVE. MYRTLE AVE. CENTRAL BLVD.
Q:\VillaPark_IL\11283000 Astor-Myrtle Sewer Separation Preliminary Design\D.4 CAD\Sheets\North\1. Cover.dwg INDEX OF SHEETS 1 COVER 2 GENERAL NOTES 3 SUMMARY OF QUANTITIES 4 ALIGNMENT 5-9 DRAINAGE AND
More informationMSD STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY
MSD M etr o p olitan S e w e r Di s t r ict STANDARD DRAWINGS LOUISVILLE AND JEFFERSON COUNTY METROPOLITAN SEWER DISTRICT 700 WEST LIBERTY STREET LOUISVILLE, KENTUCKY 40203-1911 STANDARD DRAWINGS DIVISION
More informationROUTES: 65 SECTIONS: miles in length. THE FOLLOWING ITEMS AND APPROXIMATE QUANTITIES ARE INVOLVED:
ARKANSAS DEPARTMENT OF TRANSPORTATION CA0801 HWY. 110 - CLINTON (WIDENING) (S) FEDERAL AID PROJECT ACNHPP-0071(31) THE PURPOSE OF THIS PROJECT IS TO WIDEN HIGHWAY 65 IN VAN BUREN COUNTY. THIS PROJECT CONSISTS
More informationSUBJECT: Standard Plate 9102 Turf Establishment Areas At Pipe Culvert Ends
MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Project Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (17-03) MANUAL: Standard
More information11/06/2014 Pay Items - 1
Pay Item Description Pay Unit 90701 Mobilization.... LS 91101 Excavation.... L.F. 91102 Excavation.... mi 91103 Excavation.... LS 91104 Borrow..... C.Y. 91105 Borrow..... LS 91106 Existing Trail Restoration...
More informationM I N N E S O T A D O T BID TABULATION SUMMARY JOB PAGE 1 ON 01/14/97 MINNESOTA PROJECT NO.S: DPI 015-8(021) DPI 015-8(022)
BID TABULATION SUMMARY JOB 970010 PAGE 1 STATE PROJECT NO. 27-618-70 BIDS RECEIVED UNTIL 2:00 P.M. ON 01/14/97 MINNESOTA PROJECT NO.S: DPI 015-8(021) DPI 015-8(022) AT THE JUNCTION OF AUTO CLUB ROAD AND
More informationSECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS
9. STANDARD DETAILS SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS j:\clerical\royse city\1-4086 general services\168-tech const standards review\tcss manual\2018 tcss manual\sec-9a
More information2. Remove from the Standard Plate manual: Standard Plate Index, Sheets 1-4 of 4, Numerical Index of Standard Plates (August 31, 2012)
MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Program Management & Technical Support, Design Support Section TRANSMITTAL LETTER NO. (12-04) MANUAL: Standard
More informationManhole or Catch Basin Type A & B Cone Sections Precast - Design F Manhole or Catch Basin Cover (Reducer Cone Section Precast) Design D
MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Program Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (14-02) MANUAL: Standard
More informationSUBJECT: Standard Plate Turf Establishment Areas (at Pipe Culvert Ends)
MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Program Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (14-01) MANUAL: Standard
More informationINSTRUCTIONS: 1. Record the transmittal letter number, date, and subject on the transmittal record sheet located in the front of the manual.
MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Technical Support Design Services Section TRANSMITTAL LETTER NO. (0-03) MANUAL: Standard Plates DATED: September
More informationImmediately following the Committee of the Whole meeting Mukwonago Municipal Building/Board Room, 440 River Crest Court
Dated 06-29-17 SPECIAL VILLAGE BOARD MEETING Notice of Meeting and Agenda Wednesday, July 5, 2017 Time: Place: Immediately following the Committee of the Whole meeting Mukwonago Municipal Building/Board
More informationCITY OF SAN MARCOS ENGINEERING DIVISION
AN APPLICANT S GUIDE TO PROCEDURES FOR: CITY OF SAN MARCOS ENGINEERING DIVISION ENGINEER S COST ESTIMATE USING UNIT PRICES FOR BOND PURPOSES-REVISED NOVEMBER 9, 2006 (Calculations are already set-up in
More informationGovernment Of Newfoundland & Labrador Municipal Water, Sewer And Roads Master Construction Specifications
PAGE NO. : 1 OF 4 Revision Date: July 2009 STANDARD DRAWINGS TABLE OF CONTENTS DRAWING # DESCRIPTION 0030............ Work Adjacent to Roadway 0040............ Work at the Edge of Roadway 0050............
More informationCurrent Standard Plates including Transmittal Letters are available on the web at:
MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Project Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (17-04) MANUAL: Standard
More informationSUBJECT: Standard Plates 4132, 4155, Drainage Structures and Castings Info
MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Project Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (18-01) MANUAL: Standard
More informationSTORM SEWER SCHEDULE STRUCTURES ALIGNMENT CODES: 'CW'= COMANCHE WAY PIPES BURNING WOOD, COMANCHE, 4TH SHEET NO. UTIL W RESURF ASSESSMENT DISTRICT-2015 U-3 PROJECT NO. 53W1930 COMANCHE WAY STORM SEWER SCHEDULE
More informationDESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA
DESIGN GUIDELINES (SD) COUNTY OF ALAMEDA PUBLIC WORKS AGENCY 399 ELMHURST STREET HAYWARD, CA 94544-1395 PUBLIC WORKS DESIGN GUIDELINES TABLE OF CONTENTS SD-100 SERIES SPECIAL DRAWINGS SD-100 8/1991 SILT
More informationValley Road Main Replacement
Bonding Provided Construction Co., Construction, Construction, 5% 5% 5% 5% 5% 5% 5% acknowledged 2 - Bidder Acknowledges Receipt of Addendums there was only 1 Affadivit of Preferential Bidders Status not
More informationCurrent Standard Plates including Transmittal Letters are available on the web at:
MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Project Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (15-03) MANUAL: Standard
More informationMunicipality of Anchorage Public Works Department Project Management and Engineering Division BID TABS
Municipality of Anchorage Public Works Department Project Management and Engineering Division BID TABS 2016 20.02 M 20.03 M 20.03 SP 20.04 M 20.04 M 20.04 M 20.06 M 20.06 M 20.07 M 20.07 M 20.08 M 20.08
More informationPlate 8132A - Preformed Rigid PVC Conduit Loop Detector, is a new plate requested by OTST.
DISTRIBUTION: 7 MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Design Services Section TRANSMITTAL LETTER NO. (0-0) MANUAL: Standard Plates DATED: January 9, 00 SUBJECT:
More informationRECORD DRAWINGS REVISED TO CONFORM TO CONSTRUCTION RECORDS PROVIDED BY CONTRACTOR GMG BY DATE 11/13 CRS NO.
CELL: (715) 803-8009 MABOSI@WISCONSINPUBLICSERVICE.COM CELL: (715) 573-7806 CHVIRCKS@WISCONSINPUBLICSERVICE.COM CALVIN.KLADE@FTR.COM DGAU@KRONENWETTER.COM SCOTT OLSEN (715) 302-1348 S REVISED TO CONFORM
More informationRiverside County Flood Control & Water Conservation District
10/11/2018 Page 1 of 10 ENGINEER'S ESTIMATE MAMCO, INC. dba ALABBASI G.J. GENTRY GENERAL ENGINEERING, INC. 1 MOBILIZATION L.S. 1 $100,000.00 $100,000.00 $48,000.00 $48,000.00 $88,580.77 $88,580.77 2 WATER
More informationCHAPTER 11. Plan Standards
CHAPTER 11 Plan Standards A. Introduction The city requires uniform public improvement plans for ease of record keeping and understanding. The following standards govern most plan submittals to the city.
More informationPipe Product Catalog Table of Contents
Pipe Product Catalog Table of Contents Section A: Drawing #: Page Description A1 Reinforced Concrete Pipe A3 Storm Manhole Sizing Chart (48" - 96") A3.1 Storm Manhole Sizing Chart (108" - 144") A4 48"
More informationCITY OF MUSKEGO DRAFTING STANDARDS
CITY OF MUSKEGO DRAFTING STANDARDS GENERAL - These standards apply to all plans. 1. Plans must be prepared on sheets measuring 36 inch across and 22 inch to 24 inch high unless otherwise specified under
More informationPORT OF ST. HELENS SCAPPOOSE INDUSTRIAL AIRPARK PARALLEL TAXIWAY B RELOCATON AIP PROJECT ADDENDUM NO. 1
PORT OF ST. HELENS SCAPPOOSE INDUSTRIAL AIRPARK PARALLEL TAXIWAY B RELOCATON AIP PROJECT 3-41-0056-024-2018 ADDENDUM NO. 1 Addendum No. 1 hereby amends the contract documents and drawings for the Scappoose
More informationSUPPLEMENTARY STANDARD DETAIL DRAWINGS
CITY OF MAPLE RIDGE DESIGN AND CONSTRUCTION DOCUMENTS Part 4 SUPPLEMENTARY STANDARD DETAIL DRAWINGS September 2015 Updated: October 2015 THIS PAGE INTENTIONALLY LEFT BLANK City of Maple Ridge Supplementary
More informationCITY OF VISTA STANDARD DRAWINGS
CITY OF VISTA STANDARD DRAWINGS May, 2015 THIS SHEET INTENTIONALLY LEFT BLANK TABLE OF CONTENTS MODIFICATIONS Modifications to San Diego Regional Standard Drawings DRAINAGE STRUCTURES DRN 01 Corrugated
More informationLETTING : CALL : 029 COUNTIES : GOODHUE
PAGE : -1 NUMBER OF DAYS: 80 BRIDGE COUNT : 2 CONTRACT DESCRIPTION : GRADING, SURFACING, LIGHTING AND BRIDGE NO. 25024. CONTRACT LOCATION: LOCATED ON T.H. 61 FROM 30' NORTH OF NORTH LAKESHORE DRIVE TO
More informationCITY OF VISTA STANDARD DRAWINGS
CITY OF VISTA STANDARD DRAWINGS May, 2015 THIS SHEET INTENTIONALLY LEFT BLANK TABLE OF CONTENTS MODIFICATIONS Modifications to San Diego Regional Standard Drawings DRAINAGE STRUCTURES DRN 01 Corrugated
More informationTAXIWAY B NORTH ROAD RUNWAY TAXIWAY C NORTH ROAD VICINITY MAP. Plans Prepared By:
CONSTRUCTION PLANS CITY OF NAPLES AUTHORITY (APF) NAPLES, COLLIER COUNTY, FLORIDA NAA BID NO. : TBD FAA AIP NO.: N/A FDOT FM NO.: N/A HANSON PROJ. NO. 15A0023 CITY OF NAPLES AUTHORITY BOARD OF COMMISSIONERS
More informationSTORM M ANHOLE FOR 42" PIPE AND SM ALLER JOB NO. SHEET NO. DATE MARCH 2015 OF MIN OF 3 CRSES MAX OF 5 CRSES 30"MAX 3 OR 3.5 PRECAST ECCENTIC CONC
01-APR-2015 13:33 = I:\MSV8i\Plotting\piblack.ptb V:\201001\\C\8x11_Howell_Det\stm_det01_8x11_st01.dgn TIME = MIN 3 CRSES MAX 5 CRSES 3 OR 3.5 PRECAST ECCENTIC CONC ID PIPE GRADE A CONC FILL 4" 8" 2-0"SUMP
More informationEngineering and Construction Services Division Construction Drawings for Sewers and Watermains. T No. Revision T No. Revision Remarks All T drawings
Engineering and Construction Services Division Construction Drawings for Sewers and Watermains Revision No. 8 April All T drawings New title block for each drawing is now standardized. Revision numbers
More informationSTANDARD CATCH BASIN GUTTER LINE CB INLET FRAME & GRATE, GROUTED TO GRADE RINGS AS REQ'D CONCRETE CURB FINISHED GRADE ASPHALT MAX 50 MIN
CB INLET FRAME & GRATE, GROUTED TO GRADE RINGS AS REQ'D ASPHALT 20 GUTTER LINE CONCRETE CURB FINISHED GRADE PRECAST GRADE RINGS, 2 50 100 MAX PRECAST CB LID GROUT ALL AROUND CB LEAD, INSIDE & OUTSIDE OF
More informationSECTION 39 - MANHOLES TABLE OF CONTENTS
SECTION 39 - MANHOLES TABLE OF CONTENTS Section Page 39-1 GENERAL... 39.1 39-2 PRECAST CONCRETE MANHOLES... 39.1 39-2.01 Precast Concrete Sewer Manholes... 39.1 39-2.02 Precast Concrete Storm Drain Manholes...
More informationAppendix C Construction Details
7172 Kennedy Road Warrenton, Virginia 20187 Appendix C Construction Details November 2017 TABLE OF CONTENTS THRUST BLOCKS Anchorage for 11 1/4 o, 22 1/2 o & 45 o Upper Vertical Bends... AV 01 Buttresses
More informationCity of Massillon Site Plan Checklist
City of Massillon Site Plan Checklist The following information MUST be included with all Site Plans submitted for review and processing in order to constitute a complete Site Plan Package. Incomplete
More informationStandard Plate Sheer Reinforcement for Precast Drainage Structures has been updated upon recommendation of the Bridge Office.
MINNESOTA DEPARTMENT OF TRANSPORTATION DEVELOPED BY: Design Standards ISSUED BY: Office of Program Management and Technical Support, Design Support Section TRANSMITTAL LETTER NO. (13-03) MANUAL: Standard
More informationUTILITY AND STREET CONSTRUCTION PLAN REQUIREMENTS SECTION 1
UTILITY AND STREET CONSTRUCTION PLAN REQUIREMENTS SECTION 1 ENGINEERING STANDARDS FOR UTILITY AND STREET CONSTRUCTION PLANS MARCH 2014 CONSTRUCTION PLAN SHEET FORMAT REQUIREMENTS REPRODUCIBLE MYLAR 1.
More informationMARQUETTE GREENWAY TRAIL
------ ------ TRAFFIC DATA A.A.D.T. (2010) A.A.D.T. (ED 2022) D.H.V. (2022) DIRECTIONAL DISTRIBUTION TRUCKS N/A N/A N/A N/A N/A DESIGN DATA DESIGN SPEED DESIGN CRITERIA FUNCTIONAL CLASSIFICATION RURAL/URBAN
More informationRiverside County Flood Control & Water Conservation District
9/28/2016 Page 1 of 10 ENGINEER'S ESTIMATE MAMCO, INC. dba ALABBASI H & H GENERAL CONTRACTORS, INC. 1 MOBILIZATION L.S. 1 $50,000.00 $50,000.00 $106,571.00 $106,571.00 $180,000.00 $180,000.00 2 WATER CONTROL
More informationExisting and proposed contours at 1-foot intervals. The fill and/or excavation quantities in cubic yards.
PLAN REQUIREMENTS The plans for street design shall conform to the requirements of Sections 3 and 4. The following requirements shall also be shown on the plans where applicable. Road and Storm Plans:
More informationDIVISION APPROVED MATERIAL LIST AND STANDARD DETAILS
DIVISION 400 - APPROVED MATERIAL LIST AND STANDARD DETAILS Section 403 - STANDARD DETAILS TABLE OF CONTENTS DIVISION 400, Section 403 - STANDARD DETAILS SECTION DETAIL NOS. Application Table 403-1 I. Concrete
More informationSECTION 095 SPECIFICATIONS DETAIL DRAWINGS. Index of Detail Drawings
SECTION 095 SPECIFICATIONS DETAIL DRAWINGS Index of Detail Drawings Flat Top Manhole... 095-1 Splash Drop Manhole and Regular Drop Manhole... 095-2 Special Detail Splash Drop Manhole and Special Detail
More informationUPDATE LOG FOR STANDARD DRAWINGS Item(s) Changed 6/1/18 STANDARD DRAWINGS
Date 6/1/18 STANDARD DRAWINGS UPDATE LOG FOR STANDARD DRAWINGS Item(s) Changed WATER STANDARD DRAWINGS Title Drawing Number Current Date Fire Hydrant and Appurtenance Locations, Improved Streets with Curb
More information"A" "A" SECTION "A-A" X-SECTION VERTICAL CURB (TYPE B) Village STREET & PAVEMENT STR-05. Engineering Department
1" 1/2" PRE-MOLDED NON-EXTRUDING JOINT FILLLER AT EXPANSION JOINTS (MAXIMUM 50' SPACING) 2" R "A" SEE NOTE 3 0.5" 1/8" R (TYP) DEPRESSED 1.5" PAVEMENT THICKNESS 3.5" 5.0" "A" 2" MINIMUM STONE CUSHION GRADATION
More informationMAINTENANCE HOLES, CATCH BASINS AND DITCH INLETS - MTC FORM 407 INDEX
407-1 - MAINTENANCE HOLES, CATCH BASINS AND DITCH INLETS - MTC FORM 407 INDEX 407-1.1 GENERAL Tender Items Specifications Standard Drawings 407-1.1.1 Frame and Grate Selection 407-1.1.2 Selection of Structure
More information3. DESIGN SPECIFICATIONS
Schedule H to Bylaw 7452, Subdivision Bylaw Page 10 3. DESIGN SPECIFICATIONS 3.1 General 3.1.1 The Design Specifications apply to the design of sanitary sewers, storm drains, waterworks, roadways, and
More informationCONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION
ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 407 NOVEMBER 2013 CONSTRUCTION SPECIFICATION FOR MAINTENANCE HOLE, CATCH BASIN, DITCH INLET, AND VALVE CHAMBER INSTALLATION TABLE OF CONTENTS 407.01
More informationCity of Regina Standard Construction Specification SECTION 2999 LISTING OF ROADWAY STANDARD DRAWINGS
City of Regina Standard Construction Specification SECTION 2999 LISTING OF ROADWAY STANDARD DRAWINGS R-1 Alternate Pavement Structures July/10 R-2 Typical Cross Sections for Asphaltic Concrete Pavements
More informationSECTION 58 PRECAST CONCRETE BOX CULVERT. This work consists of furnishing and installing Pre-cast Concrete Box Culverts.
SECTION 58 PRECAST CONCRETE BOX CULVERT 58.1 DESCRIPTION A. General This work consists of furnishing and installing Pre-cast Concrete Box Culverts. B. Related Work Section 51 Section 52 Section 53 Section
More informationCity of Vaughan Engineering Department DESIGN STANDARD DRAWINGS
City of Vaughan Engineering Department DESIGN STANDARD DRAWINGS March 2004 STANDARD DRAWINGS Partners With The Environment March 2004 FORWARD The March 2004 version of the City of Vaughan Design Standard
More informationSeptember 21, Mannik Smith Group 1771 North Dixie Highway Monroe, Michigan RE: LA Fitness City File No.: CVLP
CITY OF ANN ARBOR, MICHIGAN Public Services Area / Engineering 301 E. Huron Street, P.O. Box 8647 Ann Arbor, Michigan 48107 Phone (734) 794-6410 Fax (734) 994-1744 Web: www.a2gov.org Printed on recycled
More informationThis addendum forms a part of the Contract Documents dated: August 10, 2012.
Addendum # 1 Date Issued: August 28, 2012 Issued By: Project: Owner: Renker Eich Parks Architects 1609 Dr. Martin Luther King Street North St. Petersburg, Florida 33704 Ph# (727) 821-2986 Fax # (727) 896-4911
More informationSECTION MANHOLES
SECTION 33 05 13 MANHOLES PART 1 GENERAL 1.01 SECTION INCLUDES A. CONTRACTOR shall furnish and install precast concrete manhole base, sections, adjusting rings, steps, and manhole ring and cover, complete.
More informationSTANDARD DETAILS Crow Canyon Road San Ramon, CA Telephone: (925) Fax: (925)
STANDARD DETAILS 2401 Crow Canyon Road San Ramon, CA 94583 Telephone: (925) 973-2670 Fax: (925) 838-3937 CITY OF SAN RAMON STANDARD DETAILS INDEX CONCRETE WORK NAME DRAWING # Curb, Gutter & Sidewalk C-1
More informationPlan Submittal Checklist for Permit Projects Compliance Required Information. (Answer Yes or Not Applicable (NA)) Yes NA
Note: This Checklist has been created to assist in and maintain a uniform review of Construction Design Documents for projects done under permit with the County. This document has been created by the Permit
More information2. What are the estimated volumes for the Residuum Harvesting See response to Question 1
No. Question Answer 1. What are the approximate earthwork quantities for this job? FBP approximate quantities will be provided via amendment with or before the CADD files. Contractor is still responsible
More informationSOUTH CAROLINA DEPARTMENT OF TRANSPORTATION NOTICE TO CONTRACTORS FOR REGULAR HIGHWAY LETTING June 13, 2017
SOUTH CAROLINA DEPARTMENT OF TRANSPORTATION NOTICE TO CONTRACTORS FOR REGULAR HIGHWAY LETTING June 13, 2017 Letting Location: SCDOT Headquarters Building Conference Room 332 955 Park Street Columbia, SC
More informationManholes Table of Contents
Standard MH 300 Title Manholes Requirements MH 300.1 Manholes Requirements Manholes Table of Contents Underground Structures Standards MH 310 MH 318 MH 320 MH 325 MH 330 MH 335 MH 340 MH 350 Precast Tub-Type
More informationSECTION 3 IMPROVEMENT PLAN REQUIREMENTS
SECTION 3 IMPROVEMENT PLAN REQUIREMENTS CONTENTS Page 3-1 Digital Submittals 3-2 3-2 Paper Size and Scale 3-2 3-3 Drafting Standard 3-2 3-4 Title Sheet 3-2 3-5 Title Block 3-3 3-6 Drainage, Sewer, Water,
More informationINDEX OF SHEETS FLAMING GORGE RANGER DISTRICT OFFICE ADDITION REGION 4 INTERMOUNTAIN REGION ASHLEY NATIONAL FOREST DRAWING SHEET INDEX
INDEX OF SHEETS SHT. DWG. SHEET TITLE GENERAL 1 G1 COVER SHEET, VICINITY MAP, PROJECT DESCRIPTION 43 A402 INTERIOR ELEVATIONS WOMENS 44 A403 INTERIOR ELEVATIONS MENS 45 A404 INTERIOR ELEVATIONS BUILDING-PLUMBING
More informationEXTERIOR BUILDING, ROOFING, AND SITE IMPROVEMENTS
CONTRACT NUMBER: IFB-8-B006 ARCHITECT / ENGINEER : HURST-ROSCHE, INC. NO. LINOIS 62203 (68) 398-0890 -7 E. RANDLE ST./ N. FRITZ ST. 402 CHERRY ST., 404-406 ST. LOUIS ST. 502-506 DEE ST. 50-505 PLUM ST.
More informationMINIMUM C/L RADII OF CURVATURE OF LOCAL ROADS IN SUBDIVISIONS
75m 70m 65m 60m DEFLECTION ANGLE C/L RADII OF CURVATURE 55m 50m 45m 40m 35m 30m 25m 20m 15m 90 80 70 60 50 40 30 20 10 0 DEFLECTION ANGLE - MINIMUM C/L RADII OF CURVATURE OF LOCAL ROADS IN SUBDIVISIONS
More informationBID TABULATION SUMMARY Project: CONTRACT 3 SANITARY SEWER REPLACEMENTS Bid Date: Wednesday, January 10, :00 PM
PATTERSON AVENUE 101 Mobilization, Bonds, Insurance LS 1 $40,000.00 $40,000.00 $22,072.00 $22,072.00 102 18-Inch SDR-26 PVC Sanitary Sewer Line Installation LF 1048 $275.00 $288,200.00 $334.00 $350,032.00
More information18" 1.5" 3"R 11.5" 10" 3-1/2" MINIMUM STONE CUSHION GRADATION CA-6
18" 1.5" 3"R 1.5" 4"R 1" 11.5" 10" 13.5" 5" 3-1/2" MINIMUM STONE CUSHION GRADATION CA-6 NOTES: 1. REINFORCEMENT: PROVIDE TWO (2) #4 REINFORCING BARS CONTINUOUS BETWEEN EXPANSION JOINTS, WITH LOCATION SPACING
More informationB-PERMIT PLAN CHECK MANUAL
B-PERMIT PLAN CHECK MANUAL 5. SEWER PLANS Sewer Plans are usually submitted in conjunction with Street Plans to meet the requirements of conditions imposed on a Planning or Zoning action. In some cases
More information1. MATERIALS SHALL CONFORM TO THE FOLLOWING: a) STEEL REINFORCING - WIRE FABRIC (4x4) GALVANIZED - G G REINFORCING EARS TO BE EPOXY CO
1. MATERIALS SHALL CONFORM TO THE FOLLOWING: a) STEEL REINFORCING - WIRE FABRIC (4x4) GALVANIZED - G40.20-041G40.21-04 REINFORCING EARS TO BE EPOXY COATED - D3963/D3963M CEMENT - PORTLAND GU b) FINE AGGREGATE
More information8' PUE 8' PUE VARIABLE 5' STORM SEWER (SOUTH AND EAST) 1. UTILITIES SHALL BE LOCATED AS SHOWN UNLESS OTHERWISE APPROVED BY THE CITY ENGINEER.
R/W R/W 8' PUE 8' PUE VARIABLE VARIABLE C L 3.5' 2.5' MIN COVER 3' MIN COVER STANDARD CURB & GUTTER PWR, GAS, TEL, TV SEE NOTE 6 STORM SEWER (ALTERNATE LOCATION) SANITARY SEWER (NORTH AND WEST) 5' 5' STORM
More informationSTATE UNIVERSITY CONSTRUCTION FUND
DIRECTIVE 1C-12 Issue date: August 2012 1. General SURVEY, MAPPING AND UTILITY LOCATING This Directive has been developed as a general guide for the survey and mapping effort required for Fund projects.
More informationMH Table of Contents Standard Title/Scope Page Table of Contents SCE Public
MH Table of Contents Standard Title/Scope MH 300 MH 310 MH 318 MH 320 MH 325 MH 330 MH 335 MH 340 MH 350 Manholes Requirements MH 300.1 Manholes Requirements...........................................
More informationREQUIREMENTS. for ENGINEERING SERVICES PUBLIC CONSTRUCTION PROJECTS
REQUIREMENTS for ENGINEERING SERVICES on PUBLIC CONSTRUCTION PROJECTS April, 2007 David W. Johnson Senior Engineer Design & Construction Requirements for Engineering Services on Public Construction Projects
More informationSurvey Control Point Observations
Level Name SURVEY_CTRL SURVEY_CTRL_CHK_NODE SURVEY_CTRL_NODE SURVEY_CTRL_OBS SURVEY_CTRL_REF_SYM SURVEY_CTRL_SETUPS SURVEY_CTRL_SYM SURVEY_CTRL_TXT SURVEY_DTM_BREAKLINE SURVEY_DTM_BREAKLINE_NODE SURVEY_DTM_CHECK_NODE
More informationPlease remove and replace the entire Table of Contents, Section A to Section J and all Appendices.
Please remove and replace the entire Table of Contents, Section A to Section J and all Appendices. The following is a list of changes to the Design Criteria: 1. A2.01 General Note 4 Utility Coordination
More informationPUBLIC WORKS DEPARTMENT. File: E-2000 July 11, Town of Whitby Design Criteria and Engineering Standard Drawing Revisions
PUBLIC WORKS DEPARTMENT File: E-2000 July 11, 2011 To: All Manual Holders and Engineering Standard Drawing Revisions Please find attached a list of the revisions to the and the Engineering Standard Drawings.
More informationPORTLAND COMMUNITY COLLEGE ROCK CREEK CAMPUS ELECTRICAL POWER GENERATION FEASIBILITY STUDY APPENDIX A, DETAILED (CONCEPT LEVEL) PROBABLE COST ESTIMATE
PORTLAND COMMUNITY COLLEGE ROCK CREEK CAMPUS ELECTRICAL POWER GENERATION FEASIBILITY STUDY APPENDIX A, DETAILED (CONCEPT LEVEL) PROBABLE COST ESTIMATE September 14th, 2018 Prepared by: DAO Architecture
More informationCONSTRUCTION PLANS. for TOWN OF YORKVILLE 2017 PAVING & DRAINAGE PROGRAM BRAUN ROAD (57TH DRIVE TO WOODLAND TRAIL) 53RD DRIVE
LOG CT. TR. CONSTRUCTION PLANS for TOWN YORKVILLE INDEX Plan Sheet COVER TYPICAL SECTIONS & CONSTRUCTION DETAILS PLAN & PRILE Sheet No. 1 2 3-8 LEGEND Description EDGE WOODS DECIDUOUS TREE DECIDUOUS TREE
More informationSTANDARD DRAWINGS INDEX MODIFIED FOR CENTRAL REGION Revised August 6, 2018
SYMBOLS STANDARD DRAWINGS INDEX No Statewide Standard - Use Regional A3 Legend Detail Sheet BRIDGE AND STRUCTURES B-08.00 Bin Walls 1 CONSTRUCTION-BARRICADES AND SIGNING C-04.12 Location of Double Traffic
More informationSUBDIVISION APPLICATION FOR DRT SUBMITTAL PUBLIC WORKS DEPARTMENT
Case #: SUBDIVISION APPLICATION FOR DRT SUBMITTAL PUBLIC WORKS DEPARTMENT 171 North Ross Street, Suite 200 Auburn, AL 36830 (334) 501-3000 ~ Fax: (334) 501-7294 Applicant Name: Mailing Address: Email Address:
More informationCITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA (360)
CITY OF TUMWATER 555 ISRAEL RD. SW, TUMWATER, WA 98501 (360) 754-4180 Email: cdd@ci.tumwater.wa.us WATER-SEWER-STREET-STORM (IN CITY) Submittal Checklist TUM - RCVD BY DATE STAMP APPLICANT INFORMATION
More informationCITY OF CHELAN LIFT STATION IMPROVEMENTS CITY OFFICIALS. Mike Cooney Mayor. Kelly Allen Ray Dobbs Tim Hollingsworth. Ty Witt City Council
CHELAN COUNTY CITY OFFICIALS Mike Cooney Mayor Kelly Allen Ray Dobbs Tim Hollingsworth Wendy Isenhart Erin McCardle Servando Robledo Ty Witt City Council Jake Youngren Dwane Van Epps Mike Jackson City
More informationSTATE OF KANSAS DEPARTMENT OF TRANSPORTATION PLAN AND PROFILE OF PROPOSED STATE HIGHWAY FEDERAL AID PROJECT 1 PAWNEE COUNTY US-56
OF INDEX OF 1 7 FOUNDATION TREATMENT, COMPACTION & SUBGRADING DETAIL 8 SALVAGED TOPSOIL 15 SIDEROAD PLAN-PROFILE 16 RIGHT OF WAY MONUMENT INSTALLATION DETAIL SHEET -23 PAVING DETAILS 24-29 PAVEMENT DETAILS
More informationSPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS. Notification of Completed Conduit Sections
SPECIFICATIONS FOR THE INSTALLATION OF CONDUIT SYSTEMS IN RESIDENTIAL SUBDIVISIONS Section 1 Definitions 2 Scope of Work 3 Extent of Work 4 Inspection and Performance of Work 5 Trenching 6 Duct Installation
More informationCity of Regina Standard Construction Specifications SECTION LIST OF SEWER STANDARD DRAWINGS
City of Regina Standard Construction Specifications SECTION 14999 LIST OF SEWER STANDARD DRAWINGS S-1 No Drawing Feb/10 S-2 Precast Manhole 1050mm Dia. July/10 S-2B Precast Manhole 1200mm Dia. Jan/17 S-3
More informationSECTION 8: DRAINAGE, SEWER AND WATER SUPPLY NETWORKS
UDNP Standard Specifications SECTION 8: DRAINAGE, SEWER AND WATER SUPPLY NETWORKS 8.01 - Page i UDNP Standard Specifications SECTION 8: DRAINAGE, SEWER AND WATER SUPPLY NETWORKS Table of Contents SECTION
More informationCONSTRUCTION CERTIFICATION PACKAGE
Purpose: The intent of this Construction Certification Package is to ensure that acceptable documentation is maintained during the construction of stormwater management practices (SMPs). For general information
More information50.24 Type, Size and Location Plans for Culverts, Bridges and Culvert Bridges
50.24 Culverts, Bridges and Culvert Bridges Type, Size and Location (T, S & L) Plans shall be required for all Bridges, Culvert Bridges and Culverts of eight-foot (8') clear span or greater as follows:
More informationStandard Details Index NWTP Improvements and MF System Installation
Detail Standard Details Index NWTP Improvements and MF System Installation Marco Island, Florida Description 0315-001 PLASTIC WATERSTOP 0315-003 HYDROPHILIC/GROOVE WATERSTOP 0315-011 WATERSTOP JOINT 0315-154
More informationKC Water Rules and Regulations For Water Main Extensions and Relocations
KC Water Rules and Regulations For Water Main Extensions and Relocations MAY 2017 NOTE: Changes from 2016 are highlighted in yellow and appear on Pages 5, 8, 10-11, 13, and 15. Additional changes made
More informationW 869 SN 303 S. Paterson Street, Ste. 1 Madison, WI ph Structural Engineering: /Users/paulcuta/Desktop/1603 Finals/1603
869 86 863 W 869 SN 303 S. Paterson Street, Ste. 1 Madison, WI 53703 ph 608-709-1250 Structural Engineering: /Users/paulcuta/Desktop/1603 Finals/1603 Re Submit/15002_Titleblock.dwg 868 SN LEGEND W 867
More informationTYPE 4-C TYPE 6 TYPE 7 TYPE 8
````` Face of ase rad. 42 TYPE rad. " T T T 22.5 2'- unless otherwise shown on plans 5" 5" 5" Slope 2: TYPE 2 rad. Concrete TYPE 2-A rad. Wearing Course Concrete ase Course TYPE 2-0" rad. TYPE 3 As Shown
More informationMANHOLES PART I: GENERAL. A. Precast Concrete Manholes
MANHOLES PART I: GENERAL A. Precast Concrete Manholes 1) Manholes shall be made of precast concrete sections of which the top section shall be eccentric or flat slab top. The bottom section shall be a
More information.1 Applicability: These criteria shall be applied as follows:
DESIGN CRITERIA DIVISION 4800 STREET LIGHTING 4801 GENERAL: These criteria shall be adhered to for the design of all publiclyfinanced or privately-financed traffic signal systems to be installed in the
More informationSECTION MANHOLES
SECTION 02601 MANHOLES PART 1 GENERAL 1.01 SCOPE OF WORK A. WORK required under this section consists of all materials, accessories, equipment, tools, and labor required to install precast concrete standard
More information