SUPPLY & INSTALLATION OF SMART METERS (SINGLE PHASE, THREE PHASE WC, LT-CT, HT, AND DT) IN BYPL, NEW DELHI, INDIA (CMC/BY/18-19/RB/VKS/021)
|
|
- Christal O’Neal’
- 5 years ago
- Views:
Transcription
1 SUPPLY & INSTALLATION OF SMART METERS (SINGLE PHASE, THREE PHASE WC, LT-CT, HT, AND DT) IN BYPL, NEW DELHI, INDIA (CMC/BY/18-19/RB/VKS/021) SN Reference No. RFP Sentence/Clause Suggestion for Amendment/ Query BYPL Response f f. Baffle wall shall be provided above the cable entry base wall so Clarity required. Deleted that access to the terminals is not possible (even with thin metallic wire) without breaking the seal Guarantee: a. 7.5 years from the date of dispatch or 7 year from date of commissioning, whichever is earlier b. Manufacturer shall undertake a guarantee to replace meter up to a period of 7 Year from the date of supply. The meters which are found defective/inoperative within the guarantee period shall be replaced as per meter service level agreement Only 5 yrs from commissioning or 5.5 years from the date of delivery, whichever is earlier. Guarantee: a. 5.5 years from the date of dispatch or 5 year from date of commissioning, whichever is earlier b. Manufacturer shall undertake a guarantee to replace meter up to a period of 5 Year from the date of supply. The meters which are found defective/inoperative within the guarantee period shall be replaced as per meter service level agreement All the parameters mentioned in table A1 of IS (Part 2) along with following additional parameters shall be supported by meter: a. RF/ GSM signal Strength in milli db. b. Displacement PF. c. GPS coordinates. d. Temperature in Deg C. Cannot be provided from meters. All the parameters mentioned in table A1 of IS (Part 2) along with following additional parameters shall be supported by meter: a. Temperature in Deg C b. kvarh c. kvah c c. If clearance not gains, the meter locks out communication for 1 minute. The meter maintain counter for monitoring of unsuccessful attempts of performing meter operations and alerts to HES. If clearance is not got, the meter will not be able to communicate. How will the same be given to HES? If clearance not gains, the meter locks out local communication port for 1 minute. The meter maintain counter for monitoring of unsuccessful attempts of performing meter operations and alerts to HES d d. Up to 3 no s successful attempts are allowed, after which the Should be "unsuccessful attempts" port is locked out until authenticated from system administrator. Up to 3 no s of unsuccessful attempts are allowed, after which the port is locked out until authenticated from system administrator.
2 6 Annexure - C, c c. Bidder(s) must share the meter configuration source code to the BYPL/ communication provider of BYPL. Source code will not be provided. The protocol of meter configuration can be shared. Bidder(s) must share the meter configuration protocol to the BYPL/ communication provider of BYPL g. Remote command shall have priority over local In contravention to point 7.15.e above Local command shall have priority over remote Meter shall have following digital and analog inputs and outputs: 1. 4 no s Digital Inputs 2. 4 no s Digital outputs 3. 2 no s analog inputs. Input/outputs not available. Meter shall have following digital inputs and outputs (minimum): 1. 2 no s Digital Inputs suitable to read potential free contacts. 2.2 no's Digital Outputs (Potential Free Contacts) 9 Information to bidder (ITB)/2. Qualifying criteria/note Any bidder in India or abroad not fulfilling the PQR condition For trial order is there any need to submit tender for Financial turnover( Sr. No. 1&2 ) &past supply experience ( application fee and EMD or exempted. Please clarify. Sr. Nos. 7&8 ) may apply under this tender for the purpose of trial order as per BYPL Policy for Trial Order subject to meeting all technical specification and requirements. Any such bid submitted shall be considered for trial order strictly as per the BYPL procurement policy / DERC guidelines and shall not entitle bidder to qualify/claim for order of tender quantity Trial order will be considered for maximum 10% of total tender quantity. Bidder need to submit tender application fee along with bid. However, EMD to be submitted shall be 1% of estimated trial quantity value i.e. EMD is Rs Lacs Lithium ion battery with guaranteed shelf life of 10 years and capacity life of 15 years. Lithium thioyl Chloride battery will be preferred. In case battery removal or total discharge same should not affect the working & memory of the meter even in case of single wire power condition. Meters are designed for a life of maximum 10 years with a replacement guarantee of 5.5 years. Hence request to please align the battery life requirements accordingly. Further, in case of removal of battery or total discharge: a. It would not impact the energy recording during mains availability. b. But in case of single wire tamper and energy recording will not happen. Please clarify the use case perceived in this condition for meter. Also Single wire is not applicable in three phase meter. Lithium ion battery with guaranteed shelf life of 3 years and capacity life of 10 years. Lithium thioyl Chloride battery will be preferred. In case battery removal or total discharge same should not affect the working & memory of the meter even in case of single wire power condition.
3 Nameplate details a. Month of manufacturing. month of manufacturing will be provided on nameplate in line with IS Request you to delete the same. Shall be inline with standards Delete: a. Month of manufacturing These parameters can be programmed remotely by HES and locally by CMRI via proper access writes. Any programming from local port is not recommended because of security concerns. In AMI scenario all meters will be connected to network and programming can be done through HES/MDM, use case of programming through local port is not foreseen (a) These parameters can be programmed remotely by HES via proper access rights. Vendor to confirm for local configurations in case of remote failure c. For the purpose of sending the Last Gasp, meter shall have proper power backup (like a super capacitor). shall be inline with other variants i.e. "For the purpose of sending the Last Gasp, End Point shall have proper power backup (like a super capacitor)." 7.18 (c) Bidder to ensure sending of Last Gasp message Signal Strength (RF/GSM) In line with line item no. 8. Request you to delete the same Packing: a. Each meter must be packed, together with its terminal cover, in a separate environmental friendly cardboard box, which can be opened and re-closed without needing adhesives. b. Up to 10 single-phase meters in case of meter type 1 and 5 no s meters with enclosure in case of meter type 2 must be packed together with their terminal covers in a group cardboard box, which can be opened and reclosed without needing adhesives. g. Each pallet should contain between 70 and 300 meters. The actual number of meters on each pallet will be agreed with the BYPL in the event of order. h. An impact detector ("Shock-Watch") label shall be attached to the cardboard hood of several pallets in each container/ transport truck, to warn of possible rough handling during shipment, transport and storage. The meters will be transported in land so such comprehensive and costly packing with pallet is not required. The bidder anyways guarantees the proper packing and foolproof delivery of product. Packing: a. Each meter must be packed, together with its terminal cover, in a separate environmental friendly cardboard box, which can be opened and re-closed without needing adhesives. b. Up to 10 single-phase meters in case of meter type 1 and 5 no s meters with enclosure in case of meter type 2 must be packed together with their terminal covers in a group cardboard box, which can be opened and reclosed without needing adhesives. g. Each pallet should contain between 40 and 120 meters. The actual number of meters on each pallet will be agreed with the BYPL in the event of order. h. Visual indications (stickers) shall be attached to the cardboard hood of several pallets in each container/ transport truck, to warn of possible rough handling during shipment, transport and storage.
4 c. Load Switches shall be provided for all phases and neutral Neutral is not a measuring element so same requirement shall be deleted. No change Bidder may raise deviation with justification in detail with technical constraint Consumer display unit(optional): Provision of consumer interface unit (CIU) to access meter from consumer premises. Wireless IHD powered by battery Please clarify following:- 1) requirements of technology for CIU. 2) It will increase the cost of meter as 2 comms module will be required. However consumer portal/mobile apps etc.can be used for necessary information/interaction by the consumer Clause shall be deleted. shall be deleted 18 Tamper logic Distorted PF Time Based Event Stamp Please clarify requirement and use case of mentioned tamper logging Distorted PF and Time Based Event Stamp shall be deleted IS (Part 2) IS (Part 3) shall be applicable Shall be inline with standards IS (part 2) shall be read as IS (part 3) Consumer display unit(optional): Provision of consumer interface unit (CIU) to access meter from consumer premises. Wireless IHD powered by battery. Please clarify following:- 1) requirements of technology required for CIU. 2) It will increase the cost of meter as 2 comms module will be required. However consumer portal and SMS can be used for necessary information/interaction by the consumer shall be deleted 21 1 Accuracy class 0.5s/ 0.2s Please clarify accuracy class applicable for this tender Plz refer revised Price Schedule. clarification required vii. Displacement PF we request you to delete the same. Clause shall be deleted c. All the parameters mentioned in table 13 of IS (Part 3) shall be supported by meters with following additional parameters: i. GPS coordinates. parameters shall be deleted Programming for GPS coordinates shall be deleted parameters shall be deleted i. GPS coordinates - Deleted
5 Meter shall have self diagnostic for the following a. Date and RTC. b. Battery. c. Non volatile memory. d. Display communication card status not mentioned as requiremement in DT. Please align the same with other variants. Amendment required Amended clause as under- Meter shall have self diagnostic for the followinga. Date and RTC. b. Battery. c. Non volatile memory. d. Display e. Communication Card Status 25 Cl 7.15 g. Remote command shall have priority over local 26 Cl 7.20 Provision of consumer interface unit (CIU) to access meter from consumer premises. Wireless IHD powered by battery. Local comm should be on highest priority due to field conditions. CIU should be optional or Wired CIU should be preferred Local command shall have priority over remote 27 Clause 2.4, Page 5/200 IS (Part 1); AC Static Transformer Operated Watt-hour Smart Meters, Class 1.0 and 2.0 Part 1 Specification IS (Part 1) AC Static Direct Connected Watt-hour Smart Meters, Class 1.0 and 2.0 Part 1 Specification IS (Part 1) AC Static Direct Connected Watthour Smart Meters, Class 1.0 and 2.0 Part 1 Specification 28 Clause 6.5, f Page 10/200 Baffle wall shall be provided above the cable entry base wall so that access to the terminals is not possible (even with thin metallic wire) without breaking the seal Baffle wall should be deleted. As the meters are mounted in the box and terminal holes & cable entry holes are eccentric. Deleted. 29 Clause 6.6, Page 10/200 a. Terminals shall be suitable upto 25 Sqmm aluminium stranded cable. b. Two no s flat head screws and washers per terminal shall be provided c. Material of terminals, screws and washers should be brass or tinned copper. Terminals shall be tested for continuous current of 150 % Imax. a. Size shall be defined b. Washer req?? c. continuous current of 120 % Imax as per relevant IS Amended clause is as undera. Terminals shall be suitable upto 25 Sqmm aluminium stranded cable. b. Washer deleted. C. Continuous current as per IS requirement. 30 Cl 6.5 d. The terminal cover shall be extended type with baffle wall above the cable entry base wall so that access to the terminals is not possible (even with thin metallic wire) without breaking the seal. Terminal cover should have provision for cable entry from bottom. Baffle wall should be deleted. As the meters are mounted in the box and terminal holes & cable entry holes are eccentric. Deleted.
6 31 Cl 7.7 All the parameters mentioned in table A1 of IS along with following additional parameters shall be supported by meter. a. RF/ GSM signal Strength in milli db. b. % TDH in R phase Voltage c. % THD in Y Phase Voltage d. % THD in B Phase Voltage e. % THD in R phase Current f. % THD in Y Phase Current g. % THD in B Phase Current h. Displacement PF i. GPS Coordinates j. Temperature Method of Harmonic Measurement shall confirm to the IEEE Cl 6.4 d. The terminal cover shall be extended type with baffle wall above the cable entry base wall so that access to the terminals is not possible (even with thin metallic wire) without breaking the seal. Terminal cover should have provision for cable entry from bottom. Instant parameter profile should be as per IS These additional parameters not applicable as per IS Baffle wall should be deleted. As the meters are mounted in the box and terminal holes & cable entry holes are eccentric. All the parameters mentioned in table A1 of IS along with following additional parameters shall be supported by meter. a. % THD in R phase Voltage b. % THD in Y Phase Voltage c. % THD in B Phase Voltage d. % THD in R phase Current e. % THD in Y Phase Current f. % THD in B Phase Current g. GPS Coordinates h. Temperature Method of Harmonic Measurement shall confirm to the IEEE Deleted. 33 Annexure E 3.1 Material : Polycarbonate This should be SMC if CT's are mounted inside the Box 3.1 Material : SMC 34 Information to Bidder (ITB)/25 Completion Period: Bidder shall ensure completion of work within 24 months of the award of the contract/loi. Delivery of meters shall commence within 3 months from date of award of contract / LOI. Initially approx 35,000 smart meters shall be procured for deployment It will be mutually agreed between BSES and Genus at the time of signing of PO Completion Period: Bidder shall ensure completion of work within 36 months of the award of the contract/loi. Delivery of meters shall commence within 3 months from date of award of contract / LOI. Initially approx 35,000 smart meters shall be procured for deployment 35 Volume II/ commercial/section-i/21 Terms of Payment and Billing-----MS-3 ( 10% Retention Amount): 10% Retention for Part-A shall be released after 1 year of successful post Installation and integration of Smart meters with communication canopy ( Minimum 50,000 points ) Minimum 50,000 qty should be deleted. As installation of meter is a running progress. So payment should be on prorata basis. MS-3 ( 10% Retention Amount) 10% Retention for Part-A shall be released after 1 year of successful post Installation and integration of Smart meters with communication canopy.
7 36 Volume II/ commercial/section- I/38.2 Performance Guarantee: Within 15 days of the receipt of Notification of Award/ Letter of Intent/PO from the Purchaser, the successful Bidder shall furnish the Performance Bank Guarantee for an amount of 5% (Five percent) of the Contract Price in accordance with the format provided. The Performance Bond shall be valid for a period of Eighty Four months (84) from the date of the commissioning or Ninety months (90) from the last date of receipt of material (last consignment) at site/stores whichever is earlier plus 3 months towards claim period. Performance Bank Guarantee for an amount of 5% (Five Amended clause is as underpercent) of the Contract EX-WORKS (Basic) Price in accordance with the format provided. The Performance Bond shall be Performance Guarantee: Within 15 days of the receipt valid for a period of Sixty months (60) from the date of the of Notification of Award/ Letter of Intent/PO from the commissioning or Sixty six months (66) Purchaser, the successful Bidder shall furnish the Performance Bank Guarantee for an amount of 5% (Five percent) of the Contract Price in accordance with the format provided. The Performance Bond shall be valid for a period of Sixty months (60) from the date of the commissioning or Sixty Six months (66) from the last date of receipt of material (last consignment) at site/stores whichever is earlier plus 3 months towards claim period Evaluation Criteria/cl.7 Bidder has to mandatorily quote against each item of Bill of quantity and failing to do so BYPL may reject the bids Bidders allow to quote for partial BOQ Note: Any bidder in India or abroad not fulfilling the PQR condition for Financial turnover( Sr. No. 1&2 ) &past supply experience ( Sr. Nos. 7&8 ) may apply under this tender for the 1. Please confirm the qty of trial order given to bidder. 2. Please also confirm the amount of EMD given in this case. purpose of trial order as per BYPL Policy for Trial Order subject We should suggest then EMD value should to meeting all technical specification and requirements. Any such be proportionate value of the trial order bid submitted shall be considered for trial order strictly as per qty. the BYPL procurement policy / DERC guidelines and shall not entitle bidder to qualify/claim for order of tender quantity. Amend the clause is as under- Evaluation Criteria/cl.7 Bidder may quote against all items or partially in the Part-A of Price Format. Bidder shall also quote for corresponding items under Part-B and Part-C mandatorily. Trial order will be considered for maximum 10% of total tender quantity. Bidder need to submit tender application fee along with bid. However, EMD to be submitted shall be 1% of estimated trial quantity value i.e. EMD is Rs Lacs. 39 Scope of Supply...plug in communication modules (RF mesh only and RF + Cellular technology) 40 Communication modules (NIC). Communication Module/ NIC Type 2: RF and cellular communication module (LTE 4G with 3G and 2G fall back as per Indian Telecom Standards). The clause is amended as -...plug in communication modules (RF mesh only and Cellular technology only) Amended clause is as under. Communication Module/ NIC Type 2: Cellular communication module (LTE 4G with 3G and 2G fall back as per Indian Telecom Standards).
Corrigenum SUPPLY & INSTALLATION OF SMART METERS (SINGLE PHASE, THREE PHASE WC, LT CT, HT, AND DT) IN BRPL, NEW DELHI, INDIA (CMC/BR/18 19/FK/PG/674)
Corrigenum SUPPLY & INSTALLATION OF SMART METERS (SINGLE PHASE, THREE PHASE WC, LT CT, HT, AND DT) IN BRPL, NEW DELHI, INDIA (CMC/BR/18 19/FK/PG/674) SN Reference No. Meter RFP Sentence/Clause No. BRPL
More informationAnnexure - 1. Technical Specification for Smart Meters
Annexure - 1 Technical Specification for Smart Meters Doc No. - BR/18-19/SM/1PH/01 Index Record of Revision... 3 1. Scope of Supply... 4 2. Codes and Standards... 4 3. Service Conditions... 6 4. Distribution
More information1 of 12 Amendment to HTTV Meter Spec Category-A,B & C
CENTRAL ELECTRICITY SUPPLY UTILITY OF ORISSA Head. Office : IDCO TOWER, 2 nd Floor, Janpath, Bhubaneswar - 751022 Tel : 0674-2545681, 2542895 Fax : 0674-2543125 Website : www.cescoorissa.com No. CESU Hqrs/P&S/
More informationFabrication and Supply of Cable Tray. CTI Agartala, Aligarh, Gorakhpur, Muzaffarpur, Patna
Fabrication and Supply of Cable Tray at CTI Agartala, Aligarh, Gorakhpur, Muzaffarpur, Patna BROADCAST ENGINEERING CONSULTANTS INDIALIMITED 14-B, I. P. Estate, Ring Road, New Delhi CONTENTS Sr. No Title
More informationNATIONAL POWER TRAINING INSTITUTE (WR) (Ministry of Power, Govt. of India) NAGPUR TENDER DOCUMENT SUPPLY OF DRAWING TABLES AND STOOLS
NATIONAL POWER TRAINING INSTITUTE (WR) (Ministry of Power, Govt. of India) NAGPUR-440022 TENDER DOCUMENT SUPPLY OF DRAWING TABLES AND STOOLS At NPTI (WR), NAGPUR, MAHARASHTRA 1 NATIONAL POWER TRAINING
More informationPROCUREMENT OF SERVO CONTROLLED VOLTAGE STABILIZER FOR STPI-NASIK
PROCUREMENT OF SERVO CONTROLLED VOLTAGE STABILIZER FOR STPI-NASIK Sealed quotations are invited under Two-Bid system from reputed agencies, either by themselves or as a joint venture/consortium/partnership
More informationDEPARTMENT OF ARCHITECTURE
DEPARTMENT OF ARCHITECTURE Web : www.nitt.edu Phone : 0431-2503001 Short Tender Notification No.: NITT/ARCH/04/2012/ DRAWING TABLE Dated : 19-04 -2012 (Retender Those previously quoted for this tender
More information50-SDMS-01 SPECIFICATIONS FOR
SPECIFICATIONS FOR CURRENT TRANSFORMERS UP TO 36 KV This specification is property of SEC and subject to change or modification without any notice C O N T E N T S CLAUSE TITLE PAGE NO. ------------ --------
More informationBasic Energy Metering. TYPES OF METERS AND ITS Testing. Meter Tampering
Basic Energy Metering TYPES OF METERS AND ITS Testing Meter Tampering BRAJANATH DEY (Meter Testing Laboratory) TATA Power - DDL 23 rd Nov. 2017 What is Energy METER? An electricity energy meter is a device
More informationThe RSM shall be extensively used in field & laboratory for verification of the accuracy of all types of single-phase energy meters.
TECHNICAL SPECIFICATION FOR PORTABLE ELECTRONIC REFERENCE STANDARD METER (ERS) FOR TESTING OF SINGLE PHASE KILOWATT HOUR ENERGY METERS (ACCURACY CLASS 0. 2) 1. SCOPE: The specification covers the requirement
More informationCertificate by the Architect: Certified that no addition and deletion has been made to the tender documents downloaded from the IIT Madras web site.
INDIAN INSTITUTE OF TECHNOLOGY MADRAS ENGINEERING UNIT CHENNAI 600 036 NOTICE INVITING TENDERS FOR APPOINTMENT OF ARCHITECTURAL CONSULTANT No: 35/ ARC / 2013 14 TECHNICAL BID COVER 2 NAME OF WORK: Providing
More informationPROCUREMENT OF GOODS UNDER OPEN TENDER PROCEDURE
IFB NO. KGEC/DST-WB/EE /2018-19/995 PROCUREMENT OF GOODS UNDER OPEN TENDER PROCEDURE Kalyani Government Engineering College Kalyani 741 235; Nadia, West Bengal 1 Government of West Bengal Office of the
More informationTECHNICAL SPECIFICATIONS FOR BOLT HEATING EQUIPMENT
III IV. Annexure-1 TECHNICAL SPECIFICATIONS FOR BOLT HEATING EQUIPMENT I- INPUT & OUTPDUT Rated Power : 95 / 125 KVA at 50% duty cycle. Primary Voltage : 415V, 2 Phase, 50 Hz Secondary Voltage : 12.5 Volts
More informationNATIONAL DOPE TESTING LABORATORY JAWAHARLAL NEHRU STADIUM, EAST GATE, LODHI ROAD, NEW DELHI
NATIONAL DOPE TESTING LABORATORY JAWAHARLAL NEHRU STADIUM, EAST GATE, LODHI ROAD, NEW DELHI 110 003 TERMS & CONDITIONS OF TENDER DOCUMENT FOR SUPPLY OF DESKTOPS, LAPTOPS, PRINTERS & UPS DATE OF ISSUE 09/10/2014
More informationTENDER COVER PAGE (CHECK LIST)
CORRIGENDUM 01 ON 15.06.2015 BHEL Tender Enquiry :: 15E0035 Dt: 21.05.2015 Due date extended up to 23.06.2015 BHEL NIT No :: NIT_22630 Dt: 22.05.2015 Tender Item :: SPBD FABRICATION ON JOB WORK BASIS TENDER
More informationUnited Nations Development Programme
Tax on Price Quotation Payment Terms (max. advanced payment is 20% of total price) must be inclusive of VAT and other applicable indirect taxes must be exclusive of VAT and other applicable indirect taxes
More informationINDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR Tender No. IIT/GG/SKG/Furniture/ /2 Date:
INDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR 721 302 Tender No. IIT/GG/SKG/Furniture/2017-18/2 Date: 19.01.2018 Sub: Furniture for new Experimental Petrology Laboratory Indian Institute of Technology, Kharagpur,
More informationSUPPLY OF CARRIER PROTECTION COUPLER TYPE NSD-50
(I) GENERAL : Indoor PLCC Equipments are required for important 400KV, 220KV and 132KV Sub/station for Speech, Data Transmission, Protection and Teleprinter Links. (II) GENERAL REQUIREMENT : The equipments
More information071-3: 2009 CEB SPECIFICATION
071-3: 2009 CEB SPECIFICATION PROGRAMMABLE POLY PHASE METERING EQUIPMENT - CT CONNECTED CEYLON ELECTRICITY BOARD SRI LANKA Specification for PROGRAMMABLE POLY PHASE CT CONNECTED METERING EQUIPMENT ACCURACY
More informationINVITATION FOR QUOTATION. TEQIP-II/2017/btec/Shopping/2
INVITATION FOR QUOTATION TEQIP-II/2017/btec/Shopping/2 12-Oct-2017 To, Sub: Invitation for Quotations for supply of Goods Dear Sir, 1. You are invited to submit your most competitive quotation for the
More informationNOTICE INVITING TENDER Limited Tender on Single Bid Basis Milling Cutters. Tender Enquiry No: Due Date:
SCOOTERS INDIA LIMITED Sarojini Nagar, Lucknow - 226008 (Phones: 0522-2476090, 2476242 (Exchange) Direct: 0522-2476139) Fax: 91-522-2476190 Email: materials@scoootersindia.com NOTICE INVITING TENDER Limited
More informationTECHNICAL SPECIFICATIONS
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Corporate Office, Sardar Patel Vidyut Bhavan, Race Course, VADODARA 390 007. TECHNICAL SPECIFICATIONS OF CVT / COUPLING CAPACITOR STRUCTURE SPECIAL INSTRUCTIONS
More informationRef No : PUR/GT/IMP/VELC-ADITYA/20/ September 19, 2016.
Ref No : PUR/GT/IMP/VELC-ADITYA/20/2016-17. September 19, 2016. M/s. Dear Sir/s, The Director, Indian Institute of Astrophysics, Bangalore, invites Sealed Tenders (both price bid & technical bid) for the
More informationBharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT
An ISO 9001 Company Bharat Heavy Electricals Limited (High Pressure Boiler Plant), TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT ENQUIRY NOTICE INVITING TENDER Phone: +91 431 257 7653 Fax
More informationPROCEDURE FOR INSPECTION OF ELECTRICAL INSTALLATIONS ABOVE 250KVA
PROCEDURE FOR INSPECTION OF ELECTRICAL INSTALLATIONS ABOVE 250KVA Generally inspection of electrical installations is carried out under Regulation-30 (Periodical inspection & testing) & Regulation-43 (Approval
More informationDelhi Regional Office, F-8-11 Flatted Factory Complex, Rani Jhansi Road, NEW DELHI ===========================================================
Delhi Regional Office, F-8-11 Flatted Factory Complex, Rani Jhansi Road, NEW DELHI 110055 =========================================================== MMTC/DRO/SMVDSB/REF/03/2017-18 Date: 22 nd.dec. 2017
More informationINSTRUCTION FOR BIDDERS FOR PROVIDING ARCHITECTURAL CONSULTANCY SERVICES FOR THE UPGRADATION OF A GOVERNMENT HOSPITAL IN KERALA
INSTRUCTION FOR BIDDERS FOR PROVIDING ARCHITECTURAL CONSULTANCY SERVICES FOR THE UPGRADATION OF A GOVERNMENT HOSPITAL IN KERALA JANUARY 2019 HITES (A FULLY OWNED SUBSIDIARY OF HLL LIFECARE LTD, A GOVERNMENT
More informationHoward Smart Transformer Specification Guide
Howard Smart Transformer Specification Guide General Requirements Overhead pole-type smart distribution transformers shall be single phase, 60 Hz, mineral-oil filled and self-cooled and shall conform as
More informationODISHA CONSTRUCTION CORPORATION LTD. (A GOVT. OF ODISHA UNDERTAKING) CENTRAL WORKSHOP,RASULGARH, BHUBANESWAR (ODISHA)
ODISHA CONSTRUCTION CORPORATION LTD. (A GOVT. OF ODISHA UNDERTAKING) CENTRAL WORKSHOP,RASULGARH, BHUBANESWAR-751010 (ODISHA) TENDER DOCUMENT FOR SUPPLY OF HEX HEAD BOLT, NUT, SCREW, WASHER, CONICAL HEAD
More informationTECHNICAL SPECIFICATION OF UNIVERSAL TYPE COMBINED THREE PHASE & SINGLE PHASE PORTABLE ELECTRONIC REFERENCE STANDARD METER CAPABLE OF TESTING OF ALL
TECHNICAL SPECIFICATION OF UNIVERSAL TYPE COMBINED THREE PHASE & SINGLE PHASE PORTABLE ELECTRONIC REFERENCE STANDARD METER CAPABLE OF TESTING OF ALL 1.0 Scope: TYPE OF HT AND LT METERS This specification
More informationTender NO. PGVCL/PROC/Cable & Pipeline Locator/832
SPECIFICATION FOR Multipurpose Precision Locator for Cables and Pipes below Ground 1. SCOPE The Specification covers design, manufacturing Factory testing and supply of Multipurpose and Multi-function
More informationTender Ref: ELCOT/Proc/OT/32954/Multimedia Projectors/
Tender Ref: ELCOT/Proc/OT/32954/Multimedia Projectors/2017-18 Electronics Corporation of Tamil Nadu Limited Rate Contract Tender S u p p l y, i n s t a l l a t i o n a n d c o m m i s s i o n i n g o f
More informationRef No: HOlTaarangan/SMS/ /-1763 Date: 16 th Dec, 2013
Taarangan Division, Human Resource Department, Head Office Ref No: HOlTaarangan/SMS/2013-14/-1763 Date: 16 th Dec, 2013 TENDER FOR DESIGNING & PRINTING OF OUR HOUSE JOURNAL "TAARANGAN" Sealed Tenders are
More informationPlant Client Contract Code Document ID Contract No. TECHNICAL SPECIFICATIONS DC SHUNT Rev 00 Page 1 of 2
TECHNICAL SPECIFICATIONS Rev 00 Page 1 of 2 0 IFI Release for Enquiry 14/12/18 SSS 14/12/18 HGG 14/12/18 RBU - Rev. Status Description Date Prepared Date Checked Date Approved AC Based on: PIN-QMC-03-F101
More informationTechnical Specifications SECTION C
Page 1 of 12 INSTITUTE FOR PLASMA RESEARCH Technical Specifications SECTION C Design, Fabrication, assembly, testing and supply of Filter polychromators & associated components and demonstration of performance
More informationSECTION - II BID DATA SHEET
SECTION - II BID DATA SHEET Kenya Power and Lighting Company II - 1 Contract: A36 SECTION -II BID DATA SHEET The following bid-specific data for the plant and equipment to be procured shall amend and/or
More informationDPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters
DPM - Mesta Electronics, Inc. Low Voltage Active Harmonic Filters Section [26 35 26][16280] Active Harmonic Filters (Low Voltage) Part 1 General 1.1 Summary A. Scope: Provide design and engineering, labor,
More informationTender Management System Version 1.0 [ Tender Document ]
Tender Management System Version 1.0 [ Tender Document ] Initiated By Subhash Chandra Virmani Approved by Subhash Chandra Virmani Approved On 24-09-2014 Page No. :1 Tender No GDS/TE/077/14-15[21392] -
More informationTECHNICAL DESCRIPTION THREE-PHASE SUBSTATION ELECTRONIC METERS
HELLENIC ELECTRICITY DISTRIBUTION NETWORK OPERATOR S.A. NOTICE OF CALL FOR TENDERS No ND-207 PROJECT: Pilot Telemetering and Management System for the Electric Power Supply Demand by Residential and Small
More informationSection Meetings Section Material and Equipment. None Required
January 2000 Page 1 of 8 PART 1 GENERAL 1.01 OTHER CONTRACT DOCUMENTS 1.02 DESCRIPTION OF WORK 1.03 RELATED WORK PART 2 PRODUCTS The General Conditions of the Contract, General Requirements and Supplemental
More informationTo be completed by the Bidder. Sl.No. Parameters CPRI Specification / Requirements Qty
Revision N : 03 Issue No : 2 Dt of Revis : 25.07.207 Issue Dt. : 30.06.2003 Page No. : of 5 Issued by : P A CENTRAL POWER RESEARCH INSTITUTE, BHOPAL, Web: www.cpri.in, www.tenderwizard.com/cpri, Telefax:
More information001: 2007 CEB STANDARD
001: 2007 CEB STANDARD ALUMINIUM RE-DRAW RODS FOR ELECTRICAL PURPOSES CEYLON ELECTRICITY BOARD SRI LANKA Specification for ALUMINIUM RE-DRAW RODS FOR ELECTRICAL PURPOSES CEB Standard 001: 2007 CEYLON ELECTRICITY
More informationINVITATION FOR QUOTATION. TEQIP-II/2013/UP1G01/Shopping/28
INVITATION FOR QUOTATION TEQIP-II/2013/UP1G01/Shopping/28 09-Nov-2013 Sub: Invitation for Quotations for supply of Goods Dear Sir, 1. You are invited to submit your most competitive quotation for the following
More informationWATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO Job No.:
WATER MAIN ALONG ENTRANCE TO ENCINO PS / HWY 281 TO ENCINO TANK Solicitation Number: CO-00111 Job No.: 16-7003 To Respondent of Record: ADDENDUM 2 July 5, 2017 This addendum, applicable to work referenced
More informationBidder : M/s Arya Communications Pvt. Ltd., Mumbai.
Bidder : M/s Arya Communications Pvt. Ltd., Mumbai. Tender No. - 1936 Serial No DGP/17/6162/DMR-Navi Mumbai/69/2018 Clarification in Technical Specifications DMR System in UHF 400 Mhz. for Navi Mumbai
More informationOIL INDIA LIMITED (A Govt. of India Enterprise) P.O. Duliajan , Assam. Fax No ,
Page : 1 / 4 10 03548380 OIL INDIA LIMITED (A Govt. of India Enterprise) P.O. Duliajan-786602, Assam. Fax No. 91-374-2800533, E-mail:material@oilindia.in Tender No. TUBING HEAD SPOOL Tubing Head Spool
More informationfcgkj ljdkj ¼Je lalk/ku fohkkx½ fcgkj dks'ky fodkl fe'ku] fu;kstu Hkou] csyh jksm] bade VSDl xksyecj ds ikl nwjhkk"k ua0&0612&
fcgkj ljdkj ¼Je lalk/ku fohkkx½ fcgkj dks'ky fodkl fe'ku] fu;kstu Hkou] csyh jksm] bade VSDl xksyecj ds ikl nwjhkk"k ua0&0612&2528454 Tender No. 12/2016-2017 Date-02.03.2017 Tender for Printing and Supply
More informationELECTRONIC SINGLE PHASE AND THREE PHASE L.V. METER SPECIFICATIONS
HELLENIC ELECTRICITY DISTRIBUTION NETWORK OPERATOR S.A. NOTICE OF CALL FOR TENDERS No ND-207 PROJECT: Pilot Telemetering and Management System for the Electric Power Supply Demand by Residential and Small
More informationINDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR , INDIA
INDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR- 721302, INDIA No. IIT/ISE/RO WATER PURIFIER/2018-19/1 Date: 18.04.2018 Last date for submission: Friday, May 11,2018 at 3:00 PM Time &Date for Opening: Friday,
More informationAnswer: Qualification statement should be provided with the bid.
Little Diversified Architectural Consulting, Inc. 5815 Westpark Drive Charlotte, North Carolina 28217 Phone: 704-525-6350 Fax: 704-561-8700 Lincoln County Probation Renovation 208 N. Government Street
More informationLOCOMOTIVE ENGINEERING DEPTT.
SHEET 1 OF 9 SUBJECT: FOR DESIGN MANUFACTURING INSTALLATION OF FIXTURES FOR MANUFACTURING OF SHELL ASSEMBLY OF WAG7 LOCOMOTIVE Enclosures: Rev Date Prepared Rev Date Prepared Rev Date Prepared Approved
More informationTECHNICAL BID. T 4262 (E-Tender I.D. No. ) Subject: Supply of HT & SS fasteners, circlip & cotter pins for BMD-6 Ukai GSECL TPS. EMD D. D. No.
GUJARAT STATE ELECTRICITY CORPORATION LIMITED Ukai Dam, Taluka: Fort Songadh, Dist:Tapi 394680. Ph. 91-2624-233215, 233257 Fax: 91-2624-233300, 233315.e-mail: ukaitps@gebmail.com. Website: www.gsecl.in
More informationIssue No : 2 Dt of Revision :
PURCHASE DIVISION DEPARTMENT QUALITY MANUAL Revision No. : 02 Issue No : 2 Dt of Revision : 17.9.2012 Issue Dt. : 30.06.2003 Page No. : 1 OF 3 Issued by : Q A Section : 0 Document : DQM-01 Topic : FORMAT
More informationCAPITAL ELECTRICAL DIVISION ITANAGAR
GOVERNMENT OF ARUNACHAL PRADESH DEPARTMENT OF POWER BID DOCUMENT PART-III (Volume-2/3) TECHNICAL SPECIFICATIONS OF AUTOMATION OF ELECTRIC ENERGY METERING AND BILLING WITH AMR AND PRE-PAID METERS IN CAPITAL
More informationPURCHASE SPECIFICATIONS 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS
PURCHASE SPECIFICATIONS OF 500KVA DRY TYPE TRANSFORMER FOR OIL RIG APPLICATIONS SPECIFICATION NO. : OR12423 REVISION NO. : Rev 00 DATE : 01.03.2011 DISTRIBUTION : PI - 4 copies O/C - 1 copy PREPARED BY
More informationSULTANATE OF OMAN METERING AND DATA EXCHANGE CODE
1.0 GENERAL SULTANATE OF OMAN METERING AND DATA EXCHANGE CODE STANDARD: OES-22F THREE PHASE KILOWATT-HOUR DIGITAL METERS, CURRENT TRANSFORMER OPERATED, CONNECTED FOR SERVICE CONNECTIONS Electronic three
More informationStatement on variation of 900 MHz and 1800 MHz Wireless Telegraphy Act licences
Statement on variation of 900 MHz and 1800 MHz Wireless Telegraphy Act licences Statement Publication date: 06 January 2011 Contents Section Page 1 Executive summary 1 2 Introduction 2 3 Assessment of
More informationTENDER (OPEN & SHORT TERM TENDER OF 07 DAYS)
TENDER (OPEN & SHORT TERM TENDER OF 07 DAYS) Name of Scope of Work: Paper based Drafting, Designing, Printing, Publication and Supply work (Digital and Offset printing only) TERMS AND CONDITIONS The undersigned
More informationTENDER (OPEN & SHORT TERM TENDER OF 07 DAYS)
TENDER (OPEN & SHORT TERM TENDER OF 07 DAYS) Name of Scope of Work: Paper based Drafting, Designing, Printing, Publication and Supply work (Digital and Offset printing only) TERMS AND CONDITIONS The undersigned
More informationTOURISM CORPORATION OF GUJARAT LIMITED
TOURISM CORPORATION OF GUJARAT LTD. Block No.16/17, 4th Floor, UdyogBhavan, Sector 11, Gandhinagar(Gujarat) Phone : (079) 23222645 / 23220002 Fax: (079) 23238908 TENDER NOTICE Offers are invited from reputed
More informationEnquiry Generation Details
Enquiry Generation Details Page 1 of 4 ल म अन स ध न स थ न INSTITUTE FOR PLASMA RESEARCH परम ण ऊज वभ ग, भ रत सरक र क एक सह यत त स थ न An Aided Institute of Department of Atomic Energy, Government of India
More informationTOSHIBA International Corp
TOSHIBA International Corp GUIDE SPECIFICATIONS THREE PHASE UNINTERRUPTIBLE POWER SYSTEM TOSHIBA 4200FA 30 kva CT Internal Battery UPS GUIDE SPECIFICATIONS 1 (30 kva CT) 1.0 SCOPE 1.1 System This specification
More informationDIRECT CONNECTED STATIC POLY PHASE ENERGY METER OF ACCURACY CLASS 1
CEB SPECIFICATION DIRECT CONNECTED STATIC POLY PHASE ENERGY METER OF ACCURACY CLASS 1 CEYLON ELECTRICITY BOARD SRI LANKA Telephone: +94 11 232 0953 Fax: +94 11 232 393 CONTENTS Page 1. Scope 2 2. System
More informationRMU3 Remote Monitoring Unit and GPS Interrupter
About Mobiltex Mobiltex Data Ltd., formed in 1985 and headquartered in engages in the engineering, design and manufacture of high-quality industrial mobile data systems. RMU3 Remote Monitoring Unit and
More informationNo. COA/BHL/2018/293 Dated: REQUEST FOR QUOTATIONS
College of Agriculture, Maharana Pratap University of Agriculture & Technology, Bhilwara-311001 (Rajasthan) Phone: 01482-246118 (O), Email: coabhilwara@gmail.com, No. COA/BHL/2018/293 Dated: 07.06.2018
More informationPower Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL
Power Meter PQM (EnerSure Enkapsis) Guide Form Specification PART 1: GENERAL 1.01 SUMMARY: The following technical specification describes the requirements of the high accuracy standalone 3 phase Power
More informationDescription of Changes ADDENDUM NO. 7
SAN JOSE EVERGREEN COMMUNITY COLLEGE DISTRICT Physical Education Building San Jose City College Bid #0119-16 Description of Changes March 7, 2016 ADDENDUM NO. 7 The Following Changes, deletions, additions,
More information[Corporate Communications Department] Notice Inviting Tender
[Corporate Communications Department] Notice Inviting Tender Tender Ref: CorpComm/GreetingCardPrinting/2017 Tender Date: 26.10.2016 Last Date for Tender Submission: 07.11.2016 Balmer Lawrie & Co. Ltd.
More informationMATERIAL SPECIFICATIONS CELL TECHNICAL SPECIFICATION
MATERIAL SPECIFICATIONS CELL TECHNICAL SPECIFICATION LT AC THREE PHASE, FOUR WIRE 10-40 AMPS STATIC TOD TRI-VECTOR ENERGY METER WITH LPRF AS COMMUNICATION CAPABILITY. TECHNICAL SPECIFICATION NO. CE / MMC
More informationMGVCL/MM/ /2082/11KV AB CABLE TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES
TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES 1. Qualifying Requirement of AB Cable Manufacture/Supplier The manufacturer should have manufactured, successfully type tested
More informationSI.No Parameters CPRI Specification/Requirements To be Completed by the Bidder Guaranteed Technical
Section II Technical Specifications Tender enquiry no. : STDS/12-1/2016-17/PUR/STL/A-1849 Name of the equipment : SPECIFICATIONS OF SYSTEM FOR CONDUCTING DETERMINATION OF ERRORS TEST ON INSTRUMENT TRANSFORMERS
More informationTECHNICAL SPECIFICATION FOR ANNUBAR (DELTA TUBE)
TECHNICAL SPECIFICATION FOR ANNUBAR (DELTA TUBE) SPEC NO.: PE-SS-999-145-I009 REV. NO. 01 DATE : 20.04.2012 SHEET 1 OF 4 1.0 SCOPE This specification covers the Design, Manufacture, Inspection and Testing
More information[Corporate Communications Department] Notice Inviting Tender
[Corporate Communications Department] Notice Inviting Tender Tender Ref: CorpComm/GreetingCardPrinting/2018 Tender Date: 22.11.2017 Last Date for Tender Submission: 28.11.2017 Balmer Lawrie & Co. Ltd.
More informationTHE KENYA POWER AND LIGHTING CO. LTD. SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT
THE KENYA POWER AND LIGHTING CO. LTD SPECIFICATIONS for IMPULSE VOLTAGE TEST EQUIPMENT NAME DESIGNATION SIGNATURE DATE Compiled by Ephantus Nyagah Ag. Senior Engineer Checked by Eng. Thagichu Kiiru Deputy
More informationINDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR , INDIA
INDIAN INSTITUTE OF TECHNOLOGY KHARAGPUR 721302, INDIA No. IIT/CHEMISTRY/FURNITURE/2017-18 /A Date: 08 th May, 2018 _Procurement and Installation of Laboratory furniture and fume hoods in Chemistry Laboratory,
More informationشركة كهرباء محافظة القدس المساهمة المحدودة JERUSALEM DISTRICT ELECTRICITY CO. LTD.
Our Ref.: 14/2018- Date : Messrs: Dear sir, Tender 14/2018 11& 33 KV Lightning Arrestors. You are kindly requested to quote for the supply and delivery to our stores in Shufat Jerusalem, (DDP) of the following
More informationSchedule - 20 LED LAMPS
Date: 8 th February, 2018 Revision 2 (*Red color represents the changes inserted.) Schedule - 20 LED LAMPS 1. SCOPE 1.1. This schedule specifies the energy labeling requirements for self-ballasted nondirectional
More informationQUOTATION. Procurement of Equipments for Physics Laboratory
Notification No.: NITPY/PHY/LAB/Q-0/014-15 31.1.014 QUOTATION Procurement of Equipments for Physics Laboratory National Institute of Technology Puducherry invites sealed quotations from the reputed vendors/manufacturers
More informationTECHNICAL SPECIFICATION OF LT SHACKLE BOLT (G. I. BOLT) WITH NUT AND SPRING WASHER
TECHNICAL SPECIFICATION OF LT SHACKLE BOLT (G. I. BOLT) WITH NUT AND SPRING WASHER 1.0 SCOPE: This specification covers the manufacture, testing at works and supply of G. I. Bolts with Nut and Spring Washer
More informationRFP # CULVER CITYBUS: BUS SIGNAL PRIORITY SYSTEMS PROJECT Response to Questions
RFP #1587 - CULVER CITYBUS: BUS SIGNAL PRIORITY SYSTEMS PROJECT Response to Questions 1. Question: Spec requires connects to bitrans, are you going to modify the specs? Answer: City of Culver City s ATCS
More informationH.O-Civil- T&E E-3 /04/2011 / Date QUOTATION CALL NOTICE
Orissa Industrial Infrastructure Development Corporation (A Government of Orissa Undertaking) IDCO Towers, Jan path, Bhubaneswar - 751022, Orissa, India Phones: (0674) 2542784, 2540820,Fax: 542 956 Email:
More informationTECHNICAL SPECIFICATION FOR 11KV, 3C x95mm mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED)
TECHNICAL SPECIFICATION FOR 11KV, 3C x95mm 2 + 80mm 2 AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of, 3C x95mm 2 +
More informationA. Action Submittals: Written and graphic information that requires Engineer's responsive action.
SECTION 01330 - SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 1 Specification
More informationSmart Prepaid Meter Specification: 3ph-WCM. Three Phase Whole current Meter with GPRS/3G communication
Smart Prepaid Meter Specification: 3ph-WCM Three Phase Whole current Meter with GPRS/3G communication 1 CONTENTS 1.0 SCOPE... 3 2.0 STANDARDS... 3 3.0 TECHNICAL SPECIFICATION... 4 4.0 SMART METER FEATURES...
More informationTABLE OF CONTENTS FOREWORD... 3 INTRODUCTION SCOPE NORMATIVE REFERENCES... 4
TITLE SPECIFICATION FOR CRIMPED CONNECTING LUGS AND FERRULES PAGE: 1 OF 29 ISION DATE: SEPTEMBER 2014 TABLE OF CONTENTS Page FOREWORD... 3 INTRODUCTION... 4 1 SCOPE... 4 2 NORMATIVE S... 4 3 REQUIREMENTS...
More informationTitle: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS
TABLE OF CONTENTS PAGE 1.0 SCOPE... 2 2.0 STANDARDS... 2 3.0 DESIGN REQUIREMENTS... 2 3.01 Service Conditions... 2 3.02 Ratings... 3 4.0 Sectionalizer Construction... 4 5.0 Mechanism... 6 6.0 Solid Dielectric
More informationCompany Directive STANDARD TECHNIQUE: SD1E/2. Technical Requirements for Customer Export Limiting Schemes
Company Directive STANDARD TECHNIQUE: SD1E/2 Technical Requirements for Customer Export Limiting Schemes Policy Summary This Standard Technique specifies the requirements for customer owned Export Limitation
More informationRHODE ISLAND TURNPIKE AND BRIDGE AUTHORITY P.O. Box East Shore Road Jamestown, Rhode Island Invitation to Bid Request for Proposals
RHODE ISLAND TURNPIKE AND BRIDGE AUTHORITY P.O. Box 437 1 East Shore Road Jamestown, Rhode Island 02835-0437 Invitation to Bid Request for Proposals Mototrbo Digital VHF Radio System Solicitation Number:
More informationMATERIAL SPECIFICATIONS CELL TECHNICAL SPECIFICATION
MATERIAL SPECIFICATIONS CELL TECHNICAL SPECIFICATION THREE PHASE FOUR WIRE CT / PT OPERATED 0.5S ACCURACY CLASS (0.5S FOR ACTIVE ENERGY & 0.5S FOR REACTIVE ENERGY), 1 AMP OR 5 AMPS FULLY STATIC AMR COMPATIBLE
More informationizòkxh; ou vfìdkjh dk dk;kzy;
izòkxh; ou vfìdkjh dk dk;kzy; OFFICE OF THE DIVISIONAL FOREST OFFICER e/; v.meku / MIDDLE ANDAMAN TENDER NOTICE The Divisional Forest Officer, Middle Andaman Forest Division, Rangat (Dept. of Environment
More informationTECHNICAL SPECIFICATION OF PORTABLE ELECTRONIC REFERENCE STANDARD ENERGY METER (ERS METER) FOR T E S T I N G O F HT THREE PHASE ENERGY METERS:-
TECHNICAL SPECIFICATION OF PORTABLE ELECTRONIC REFERENCE STANDARD ENERGY METER (ERS METER) FOR T E S T I N G O F HT THREE PHASE ENERGY METERS:- 1.0 SCOPE:- A lightweight electronic precision portable energy
More informationUniversity Visvesvaraya College of Engineering
University Visvesvaraya College of Engineering K.R.Circle, -560001 INVITATION FOR QUOTATION TEQIP-II/2013/KA2G01/Shopping/25 29-Nov-2013 To, Sub: Invitation for Quotations for supply of Goods Dear Sir,
More informationLandis+Gyr S650 Smart Grid Terminal. a smart grid innovation
Landis+Gyr S650 Smart Grid Terminal a smart grid innovation 2 Emerging challenges in the distribution system. Utilities, both DNOs and DSOs, are facing growing challenges due to quick changes happening
More informationTENDER DOCUMENT FOR PURCHASE OF: ENDMILL CUTTERS, HSS DRILL BITS ETC. Tender Number: /46/GWS, Dated:
India Government Mint, IDA, Phase-II, Cherlapally,(R.R district), Hyderabad Pin-500051 India Ph. No: 91-40-27261731-34, 27266095 Fax No: 040-27262951 CIN: U22213DL2006GOI144763 E-Mail: igm.hyderabad@spmcil.com
More informationSPECIAL SPECIFICATION Inch LED Traffic Signal Lamp Unit
1993 Specifications SPECIAL SPECIFICATION 1201 12 Inch LED Traffic Signal Lamp Unit 1. Description. This specification describes the minimum acceptable design and performance requirements for a twelve
More informationTECHNICAL SPECIFICATIONS for 300KV CONSTANT POTENTIAL X RAY EQUIPMENT (for industrial applications) S. No. PARTICULARS BHEL SPECIFICATIONS
TECHNICAL SPECIFICATIONS for 300KV CONSTANT POTENTIAL X RAY EQUIPMENT (for industrial applications) BIDDER s OFFER S. No. PARTICULARS BHEL SPECIFICATIONS 1.0 Area of Application The 300kV Constant potential
More information015 : 1993 CEB STANDARD
015 : 1993 CEB STANDARD UNGALVANIZED STAY ASSEMBLIES CEYLON ELECTRICITY BOARD SRI LANKA Specification for UNGALVANIZED STAY ASSEMBLIES CEB Standard 015 : 1993 CEYLON ELECTRICITY BOARD No. 50, Sir Chittampalam
More informationPMAC770 Multifunction Power Meter. Installation & Operation Manual V2.0 ZHUHAI PILOT TECHNOLOGY CO., LTD.
PMAC770 Multifunction Power Meter Installation & Operation Manual V2.0 ZHUHAI PILOT TECHNOLOGY CO., LTD. Danger and warning! This device can be installed only by professionals. The manufacturer shall not
More informationOFFICE OF THE PRINCIPAL ACCOUNTANT GENERAL (A&E), ODISHA : BHUBANESWAR. No. Rec-I(A&E)/ Stnry/ /03 Date : TENDER CALL NOTICE
OFFICE OF THE PRINCIPAL ACCOUNTANT GENERAL (A&E), ODISHA : BHUBANESWAR No. Rec-I(A&E)/ Stnry/2018-19/03 Date : 09-04-2018 TENDER CALL NOTICE Sealed quotations are invited from Registered Firms/Co-operative
More informationMATERIAL SPECIFICATIONS CELL TECHNICAL SPECIFICATION
MATERIAL SPECIFICATIONS CELL TECHNICAL SPECIFICATION TECHNICAL SPECIFICATION OF LT AC THREE PHASE, FOUR WIRE, 40-200 AMPS AMR COMPATIBLE STATIC TOD TRI-VECTOR ENERGY METER WITH IN-BUILT CT & MODEM (THREAD
More information