Level III measurement accuracy of field testers for Twisted Pair Copper Cabling Explained in Technical Detail

Size: px
Start display at page:

Download "Level III measurement accuracy of field testers for Twisted Pair Copper Cabling Explained in Technical Detail"

Transcription

1 Level III measurement accuracy of field testers for Twisted Pair Copper Cabling Explained in Technical Detail 1 Outline Henriecus Koeman Fluke Networks July 9, 2001 This rather technical discussion contains detailed explanation of field tester measurement accuracy. It includes a discussion of test configurations, measurement accuracy related requirements, what the sensitivity of performance parameters is on overall measurement accuracy and worst case measurement performance per applicable standards. The following topics are addressed: What are the test configurations? (Permanent Link, Channel, Baseline) Parameters that have to be measured and over what frequency range. A reference to channel and permanent link pass/fail limits. Accuracy dependency on both field tester properties and link properties. The way accuracy is formally specified? 1. Individual performance parameters 2. Network analyzer comparisons What is every field tester performance parameter? Other aspects of field testers related to measurement accuracy. 1.1 Level III Field Tester Accuracy Summary First, the bottom line is shown. The worst case measurement accuracies for a Level III compliant field tester are shown in the following figures. The typical measurement accuracy is typically ½ of these values. 1

2 Insertion loss (attenuation) measurement accuracy at permanent link pass/fail limits for baseline and permanent link and channel pass/fail limits for the channel test configuration. 5 4 Accuracy in db 3 2 Channel Level III Accuracy Permanent link Level III Accuracy Baseline Level III Accuracy Frequency in MHz Figure 1: Insertion loss (attenuation) measurement accuracy NEXT loss, pair-to-pair, measurement accuracy at permanent link pass/fail limits for baseline and permanent link and channel pass/fail limits for the channel test configuration. 5 4 Channel Level III Accuracy Accuracy in db 3 2 Permanent link Level III Accuracy Baseline Level III Accuracy Frequency in MHz Figure 2: NEXT loss measurement accuracy 2

3 Return loss measurement accuracy at permanent link pass/fail limits for baseline and permanent link and channel pass/fail limits for the channel test configuration. 5 4 Permanent link Level III Accuracy Channel Level III Accuracy Accuracy in db Note: The 3 db rule generally applies at low frequencies. Baseline Level III Accuracy Frequency in MHz Figure 3: Return loss measurement accuracy ELFEXT, pair-to-pair, measurement accuracy at permanent link pass/fail limits for baseline and permanent link and channel pass/fail limits for the channel test configuration. 5 Channel Level III Accuracy 4 Permanent link Level III Accuracy Accuracy in db 3 2 Baseline Level III Accuracy Frequency in MHz Figure 4: ELFEXT measurement accuracy 3

4 2 Relevant standards The approved and draft standards that relate to field testing of twisted pair copper cabling are shown in Table 1. Standard Status Application Identification Freq. range IEC approved Class C and D cabling Level IIE MHz TIA/EIA-568B-2 approved Category 3 and 5E cabling Level IIE MHz IEC revision draft Class E added Level III MHz TIA/EIA-568B-cat 6 draft Category 6 added Level III MHz Table 1: Overview of field testing standards The standards that specify ISO/IEC Class E and TIA/EIA-568B Category 6 are still under development, and therefore the field testing requirements (Level III) are still under discussion. However, performance requirements for field testers are relatively stable and are being refined. 3 Test configurations The test configurations for which pass/fail limits are specified are: Permanent link Channel This is now true in both international and TIA specifications (starting with TIA/EIA-568B, approved in March 2001). Previously, the TIA recognized the Basic Link (as in TSB-67). This is now formally obsolete after the approval of TIA/EIA-568B. The baseline performance requirements are an indication of performance of the field tester by itself at the high performance reference plane of measurement, without the use of a suitable adapter to make a permanent link or channel measurement. As will become clear in this document: the overall measurement performance is highly dependent on the properties of the adapter that is used, as well as the signal processing capability of the field tester. 3.1 Channel Both international and US standard specify that the following connector and component segments can make up a channel configuration. Starting out at the equipment room or closet, where the jack on the equipment is mated with the plug of the user patch cord (see Figure 5 for a schematic diagram): Equipment in Floor Distributor a b c d e Terminal equipment in work area C2 C1 CP TO Figure 5: Schematic diagram of a channel configuration 4

5 A segment of patch cable a to a connection. This connection may be part of a cross-connect system (we label that C1 in that case) or a patch panel, which makes a connection to horizontal cable (in that case it will be directly to a connector labeled C2). The connection to either the cross-connect connector C1 or connection to the horizontal cable C2. A jumper cable b between C1 and C2, in case a cross-connect system is used. If there is no cross-connect, this jumper cable b is not present. We call a system without a cross-connect an interconnect cabling system. Connection C2, which is the entrance to the horizontal cabling. Horizontal cable c. This is generally the long segment of cable in a link. An optional consolidation point connector CP. This was previously called a transition point. This optional connection CP is sometimes used in Open Office Cabling systems. If there is this optional consolidation point CP, there is may be another segment of cable d to a telecommunication outlet TO. A telecommunications outlet connector TO. A segment of patch cable e to make the connection to the workstation (network interface card). There are really two versions of an Open Office Cabling system. This first type uses at the location of the CP an Multi-User-Telecommunication Outlet Assembly (MUTOA), and then a long patch cable, up to 20 m long to the work station. In this case, the MUTOA provides the function of a regular TO. The second type is as shown in the right portion of Figure 6: a CP is used, followed by segments of cable d to a telecommunications outlet to make the final connection to the work station. Often one finds 25 pair cabling between the equipment room or closet to the CP. At the location of the CP, the 25 pair cable transitions in individual 4-pair cables to the TO s near the workstation locations. A very important observation The plug of the user patch cord attached to cable segments a and e and which provides the connection to the equipment at either end is considered to be part of the equipment, and its impact on signal transmission is NOT considered part of the channel. Therefore, the channel starts or ends where the patch cable exits the plug mating with equipment. This is shown in a simplified schematic diagram in Figure 6. Equipment (hub) Beginning of channel user supplied test cords Simplified channel End of the channel Figure 6: Formal definition of the channel configuration Equipment (workstation) 5

6 The reason for this apparently odd definition is that the electrical performance of the equipment is tested with a plug mated with the equipment (you cannot test the equipment without anything connected to it!). The unfortunate consequence of this definition is that when testing the electrical performance of a channel, it is necessary to measure the channel through the standard modular 8-pin connector, but without the degradation of the measurement of this connection to the test equipment at both ends. This actually does have a considerable influence on measurement accuracy and field tester manufacturers to some degree have been successful in eliminating this connection from influencing a test result. It is a big deal and more about this later. 3.2 Permanent link Schematic diagram of the current ISO/IEC and TIA (per TIA/EIA-568B) permanent link is shown in Figure 7. Beginning of the (obsolete) basic link Local test unit Beginning of the permanent link Field test manufacturer supplied test cords High Quality Test port High Quality Test port Remote test unit Permanent link End of the permanent link End of the (obsolete) basic link Figure 7: Formal definition of the permanent link A number of observations of interest: The goal of the permanent link definition was to define a configuration, which was as permanent as possible, and subject to changes to the absolute minimum extent possible. Patch cords can be exchanged rather easily, so the main aspect was to minimize its impact by excluding it when acceptance testing the cabling. Therefore, the key difference between the (obsolete) basic link (see the next section for a detailed description) and permanent link definitions is that the reported result must not include the impact of the cable portion of the adapter cord. This is in addition to the mating connector with the field tester and its remote unit. However, the question remains on the plug that mates with the first jack of the permanent link. The plug of the test adapter to the first jack of the permanent link remains to be included in the definition of the permanent link, and its impact must be included in the reported results. Contrary to the basic link definition (see the next section for a detailed description), an optional connection (this is the consolidation point) is allowed in the permanent link. More about this later. Again, the performance of the plug that is part of the test adapter affects the reported result for the permanent link, and must be tuned to the cabling components of the permanent link. 6

7 The adapter of the field tester affects the performance of the permanent link that is measured. Possible permanent link configurations When referring to Figure 5 showing the channel, you can easily identify the portions which may be considered permanent (see Figure 8 for schematic diagrams). c C2 c TO C2 CP c d C2 CP TO Figure 8: Possible permanent link configurations The first option is the most simple one: you just have in the equipment room or closet a patch panel and in the work area you have a telecommunications outlet. This permanent link includes two connections and one segment of cable (which can be up to 90 m long). The second option is also like the top one. In this case, your installer only tests up to the consolidation point. Later you may add the Open Office cable to a telecommunication outlet. All connectors are subject to the same performance requirements and therefore from a performance point of view the second configuration is subject to the same test limits as the top configuration in figure 5. The last option shows the implementation with a consolidation point (CP). This causes an additional connector in the permanent link. During the measurement of some parameters this is a significant contributor (NEXT and return loss) and during other measurements its impact is minor. The pass/fail limit requirements for all permanent link configurations are the same and independent of the number of connectors in the permanent link. There are discussions within the ISO/IEC standardization working groups on making it possible to perform incremental testing: First test the cabling between C2 to the CP (this test configuration is called the CP link). Then extend the CP link to a permanent link (from C2 to the TO), or Extend the CP link to a channel test configuration. The difficulty is to provide consistent pass/fail limits for each test configuration. The CP link pass/fail limits need to be tighter than those for the permanent link and allow for variations in mated plug/jack performance. This topic is still being discussed. 7

8 3.3 Basic Link (baseline) The approved TIA standard TIA/EIA-568B no longer recognizes the basic link as a test configuration. The international ISO/IEC standard has never recognized the basic link. The obsolete TIA standards include TSB-67, TSB-95 and Addendum #5 to TIA/EIA-568-A for Enhanced Category 5 cabling. As long as return loss was not included as a measurement parameter, there was no real difference between testing a basic link and a permanent link, since virtually all test adapters by field tester manufacturers used cable with individually shielded wire pairs and thereby avoiding any amount of NEXT. However, return loss effects in adapter cable cannot be avoided and represents a potentially very significant source of measurement error. Major developments in the design of permanent link adapters have occurred recently. For reference purposes, the basic link test configuration is described here. There is an important difference between the basic link and permanent link test configurations, with a major impact on measurement accuracy in many cases. The configuration of the TIA basic link is shown in Figure 9. Local test unit Beginning of the (obsolete) basic link Field test manufacturer supplied test cords High Quality Test port Remote test unit Basic link End of the (obsolete) basic link High Quality Test port Figure 9: Formal definition of the TIA basic link A couple of observations of interest: Since the patch cord used to connect the field test instrument and its remote unit is supplied by the manufacturer of the field tester, there is no requirement that the mating connector to the field tester is of the modular 8-pin, RJ-45 type. Most often, the high quality test port of the field tester is also the location where the performance of the field tester is calibrated and therefore the highest in terms of accuracy. To really show off the measurement accuracy of the field tester, the accuracy in this test configuration is often emphasized. Standards now refer to this performance as baseline accuracy. The baseline accuracy has become essentially irrelevant for field testing purposes, because the measurement performance with permanent or channel adapter is critical. The cable portion and plug mating with the first jack (internationally often the word socket is used) is formally part of the basic link. The field tester manufacturer therefore influences the quality of the basic link as it is reported. By selecting patch cable with high performance, this enhances the overall outcome, in particular for the return loss property. Also, by selecting a plug that mates electrically well with the jack, that will enhance the reported performance, in 8

9 particular for the near-end-crosstalk (NEXT) measurement. Of major importance therefore is the quality of the adapter which the field tester manufacturers deliver with their test instrument. These adapters have to imitate to the degree possible, the highest quality of cabling used by the end user. The basic link definition does NOT allow for any connection in the middle (the consolidation point (CP) or transition point (which is the old name for consolidation point). 3.4 Special rules for Open Office cabling There are two versions of Open Office Cabling. In each case, often 25-pair cable is used to connect the equipment in the telecommunications outlet or room to a central location in the work area. Since the space needed for a single 25 pair cable is less than six (6) 4-pair cables, this is often considered an attractive solution. The one version uses a Consolidation Point (CP) (see Figure 10) and another segment of horizontal cable often called the CP cable to a Telecommunications Outlet (TO). HUB or other equipment Patch panel or crossconnect (not shown) Equipment Room/ Floor Distributor Connections to other equipment Cable bundle or 25-pair cable Consolidation Point Telecommunications Outlet Workstations Work Area Cable bundle or 25-pair cable Connections to other telecommunications outlets and workstations Figure 10: Principle of implementation of Open Office Cabling: use of Consolidation Point (CP). Testing this configuration is subject to discussions in the ISO/IEC working group. In this situation, the desired configuration to be tested is the permanent link from the equipment room/floor distributor to the TO, so that a compliant patch cord can be added with confidence that the channel performance is achieved. It will generally not possible to pre-test the CP link and expect no failures when the CP cable between CP and TO is added. 9

10 The configuration is subject to the same rules as for a permanent link or channel (the basic link does not allow a CP). The second version of Open Office Cabling uses a Multi-User Telecommunications Outlet instead of the CP and TO, and uses long (up to 20 m) patch cords directly to the workstation (see Figure 11). Same circuit arrangements as in Figure 10. Multi User Telecommunications Outlet Assembly (MUTOA) Workstations Work Area Cable bundle or 25-pair cable Connections to other workstations Figure 11: Principle of implementation of Open Office Cabling: use of Multi-User Telecommunication Outlet Assembly (MUTOA) Testing this configuration is subject to discussions in the ISO/IEC working group. This situation is addressed by extending the CP link to the channel end configuration. In this case, long patch cables may be used. The maximum length can be determined by subtracting the measured insertion loss (attenuation) from the channel pass/fail limit and dividing the difference by the insertion loss (attenuation) of patch cable per unit length. 10

11 4 Link parameters to be measured 4.1 Link parameters Table 2 contains an overview on the field parameters that need to be tested per ISO/IEC and TIA/EIA-568B and related draft standards. Standard: ISO/IEC TIA/EIA 568B ISO/IEC Status Approved Approved Draft Draft Class or Category Cl. C: 16 MHz Cat 3: 16 MHz Frequency range Cl. D: 100 MHz Cat 5e: 100 MHz Cl. C: 16 MHz Cl. D: 100 MHz Cl. E: 250 MHz Cl. F: 600 MHz Addendum to TIA/EIA 568-B Cat 3: 16 MHz Cat 5e: 100 MHz Cat 6: 250 MHz Wire Map x x x x Length x x Propagation delay x x x x Delay skew x x x x Insertion loss x x x x (attenuation) PP NEXT loss x x x x PS NEXT loss x x x x PP ACR x PS ACR x PP ELFEXT x x x x PS ELFEXT x x x x Return loss x x x x DC resistance x x Table 2: Overview of parameters that must be measured. 4.2 Pass/fail limits The pass/fail limits for each test configuration of the ISO/IEC and TIA standards can be found in the Expert Copper Cabling section of the Fluke Networks WEB site. They are regularly updated per the most recent drafts. 11

12 4.3 Brief description of link parameters Table 3 contains a summary description of each parameter to be measured. Parameter Description Wire Map Verifies proper connectivity of pairs 1,2 3,6 4,5 and 7,8 Length This is the physical length of the link. Propagation delay The travel time of the signal from the beginning to the end of the link. It is based on the phase shift of a 10 MHz sinusoidal signal. Delay skew The maximum difference of travel times between any two wire pairs. Insertion loss Loss of signal along the length of the link (attenuation) PP NEXT loss Pair-to-pair Near-end-crosstalk: the coupling from one wire pair to another measured at the beginning of the link. PS NEXT loss Power sum Near-end-crosstalk: the power sum of pair-to-pair NEXT couplings to a wire pair from all other wire pairs. This is a computed value from the pair-to-pair NEXT loss results. PP ELFEXT Pair-to-pair Equal level far end crosstalk: the coupling of a disturber pair to a disturbed pair measured at the remote end of the link relative to the insertion loss of the disturbed pair. PS ELFEXT Power sum Equal Level far end crosstalk: the power sum of all ELFEXT disturbers on a certain wire pair. This is a computed value from the pair-topair ELFEXT measurements. Return loss The reflected signal on a given wire pair. PP ACR Pair-to-pair attenuation-to-crosstalk ratio. This is a computed value from pair-to-pair NEXT loss and insertion loss. PS ACR Power sum attenuation-to-crosstalk ratio. This is a computed value from power sum NEXT loss and insertion loss. DC resistance DC loop resistance of a wire pair. Table 3: Summary description of each parameter to be measured. 12

13 4.3.1 Wire Map Measurement requirements The Wire Map test includes the test for proper connectivity. For the modular plug the correct connectivity has been specified as shown in figure 6. Two standard configurations have been called out: 568A and 568B. Electrically there is absolutely no difference: pair 1,2 is always connected to pair 1,2, etc. The color codes for the wires differ however. The Wire Map test contains a test for split pairs. Split pairs do have correct pin-to-pin connectivity, but the wires are not twisted together correctly in a pair. Refer to figure 7 for illustrations of correct and incorrect connectivity. TIA-568A shows 568A to be the preferred color coding. Modular jacks and punch down blocks generally show color coding. Plug color codes per 568A, locking tab is up 1 White/Green 1 2 Green 2 Pair White/Orange Blue 4 5 Pair White/Blue Orange White/Brown Brown 7 8 Pair 2 Pair 4 Plug color codes per 568B, locking tab is up 1 2 White/Orange Orange White/Green Blue White/Blue Green White/Brown Brown 7 8 Pair 2 Pair 1 Pair 3 Pair 4 Figure 12: Connectivity and color code assignments per 568A and 568B Note that it is not sufficient to measure DC resistance. An ac signal is needed in order to detect split pairs (connections to twisted pairs are mixed up at both ends). See Figure 13 for an example of a split pair situation. Other errors, like open circuits and shorts are readily detected by pulse reflections. 13

14 Figure 13: Examples of correct and incorrect wiring The reporting requirement for the Wire Map function is that the wire map is correct and as shown in Figure 13, graph at the left Length measurement requirements Length is expressly defined as the physical length of the cable. Field testers attempt to measure the propagation delay of an electrical signal in the cable and relate the measured delay to the length of the cable. Of course, the propagation delay time depends on the speed of the signal, which is expressed as a percentage of the speed of light. This quantity is called the Nominal Velocity of Propagation (NVP). Since the signal has to travel up and down the cable, the equation for length is: MeasuredTimeDelay* NVP* SpeedOfLight Length = 2 The Speed-of-Light is 300,000,000 meters/second. Practically the speed of the signal is approx. 0.2m/ns or 8 inches/ns (NVP is approximately 67%). Problems with the measurement of physical length by electronic means are: The speed of travel of electrical signals varies widely from lot to lot of cable. Differences of 10% are quite possible. The shape of a TDR pulse changes considerably as it travels to the end of the cable and back, and therefore it is not always easy to measure the time delay accurately. This is a problem for the tester and the length measurement accuracy requirement for the tester includes this factor. The pairs in a 4-pair cable all have different twist lengths in order to improve crosstalk performance, therefore the propagation delays are different. The (electrical) lengths of the pairs are based on propagation delay and are different as a result. Differences of 5% are quite common. However, the physical lengths of the pairs inside the jacket is the same. Standards specify that the shortest length must be used for NVP calibration and PASS/FAIL testing. The speed of travel is actually slightly dependent on frequency. For purposes of reporting the phase delay is measured at 10 MHz. Since the period of a 10 MHz signal is 100 ns, multiply the phase delay and 100 ns to obtain the propagation delay. 14

15 Calibrate Cable must be performed by the installer/user of test equipment Test standards recommend that the NVP of every new spool of cable is measured (use the calibrate cable function: measure 300 m or 1000 feet of cable and adjust the reported length to 300 m or 1000 ft). After cable from this spool has been installed, the length should be measured using the NVP of the spool that the cable came from and the NVP, as well as other measured data, be recorded in the cable administration system. NVP calibration improves the accuracy of the length measurement substantially (to a few percent). However, it is recognized that few users of test equipment actually maintain the discipline of properly measuring the NVP before installation and more often than not, the value of NVP and length of each link is not recorded in the cabling documentation of a building. The requirements for PASS/FAIL are therefore adjusted, so that anything less than the maximum length of the link + 10 % (110 m for a channel and 99 m for a permanent link) is a PASS. Anything in excess of the 10 % allowance for NVP uncertainty is a FAIL. The field tester adds an additional uncertainty of better than ±1 meter ±4 %. If the measured result is closer to the test limit than the accuracy of the tester, an asterisk is added to the PASS or FAIL result. This represents a warning to the user/installer, meaning that the outcome of the length test cannot be relied upon: a PASS may actually be a FAIL or a FAIL may actually be a PASS. Test standards also state that the pair with the longest twist length (therefore with the shortest electrical delay) shall be used to calibrate the cable. The test instrument must be able to measure all pairs, and report the length of the pair with the shortest delay (typically the same pair that was used when measuring the NVP). This length should apply to all wire pairs. (Again, propagation delays will differ!) The nominal test limits for length (TIA only) are: 100 m + 10% = 110 m for a channel 90 m + 10 % = 99 m for a permanent link 4.4 Minimum reporting requirements The minimum reporting requirements by field testers are specified in IEC , TIA/EIA- 568B.2 and applicable draft standards. The requirements include: Ability to download all datapoints Provide a minimum summary report output. The requirements for the minimum summary report output are shown in Table 4. It is generally sufficient to retain the summary data. The detailed data is very useful when 1) It includes diagnostic information, such as time domain responses (time domain NEXT and time domain reflections (return loss)). 2) A failure needs to be diagnosed. Natural variability, that the result of the mating different plugs (of a test adapter or user patch cord) with the jack (of the link under test) is generally high enough to limit reproducibility. Refer to section 5.4 for more information. 15

16 Function Wire Map Insertion loss (attenuation) Length (ISO/IEC: not required) NEXT loss pair-to-pair (ISO/IEC only: If PP NEXT loss fails, ACR must pass to obtain a passing test result) NEXT loss power sum (ISO/IEC only: If PS NEXT loss fails, ACR must pass to obtain a passing test result) ELFEXT pair-to-pair Measured from either end (if measurement from both directions is not required) All connectivity, including shields (if present) Pass/fail Worst case insertion loss (1 of 4 possible) Test worst case worst case Pair with worst case Pass/fail Length Test limit Pass/fail Worst case margin (1 of 6 possible) Test worst case margin worst case margin Pair worst case margin Pass/fail AND Worst case (1 of 6 possible) Test worst case worst case Pair combination with worst case Worst case margin (1 of 4 possible) Test worst case margin worst case margin Pair with worst case margin Pass/fail AND Worst case power sum NEXT loss (1 of 4 possible) Test worst case worst case Pair with worst case Worst case margin (1 of 12 possible) Test worst case margin worst case margin Pair worst case margin (disturber, disturbed) Pass/fail AND Worst case pair-to-pair ELFEXT Test worst case worst case Pair combination with worst case Measured from opposite end (if measurement from both ends is required) Worst case margin (1 of 6 possible) Test worst case margin worst case margin Pair worst case margin Pass/fail AND Worst case (1 of 6 possible) Test worst worst case Pair combination with worst case Worst case margin (1 of 4 possible) Test worst case margin worst case margin Pair with worst case margin Pass/fail AND Worst case power sum NEXT loss (1 of 4 possible) Test worst case worst case Pair with worst case Worst case margin (1 of 12 possible) Test worst case margin worst case margin Pair worst case margin (disturber, disturbed) Pass/fail AND Worst case pair-to-pair ELFEXT Test worst case worst case Pair combination with worst case ELFEXT power sum Worst case margin (1 of 4 possible) Test worst case margin worst case margin Pair combination with worst case margin (disturber, disturbed) Pass/fail AND Worst case power sum ELFEXT Test worst case worst case Pair combination with worst case Worst case margin (1 of 4 possible) Test worst case margin worst case margin Pair combination with worst case margin (disturber, disturbed) Pass/fail AND Worst case power sum ELFEXT Test worst case worst case Pair combination with worst case Table 4 Field tester summary reporting requirements 16

17 Function Return loss (pass/fail does not apply when insertion loss (attenuation) is less than 3 db) PROPAGATION DELAY Delay skew Measured from either end (if measurement from both directions is not required) Worst case margin (1 of 4 possible) Return loss Note worst case margin. Test worst case margin. worst case margin Pair with worst case margin Pass/fail AND Worst case return loss (1 of 4 possible) Test worst case Return worst case worst case Pair with worst case Worst case delay (1 of 4 possible) Test worst case Pair with worst case Pass/fail Worst case delay skew (1 of 1 possible) Test limit Pass/fail Measured from opposite end (if measurement from both ends is required) Worst case margin (1 of 4 possible) Return worst case margin. Test worst case margin. worst case margin Pair with worst case margin Pass/fail AND Worst case return loss (1 of 4 possible) Test limit at worst case Return loss at worst case Frequency at which worst case occurs. Pair with worst case DC resistance (TIA: not required) Worst case DC resistance (1 of 4 possible) Test limit Pass/fail Table 4 (continued) Summary reporting requirements for field testers 5 Measurement accuracy requirements 5.1 Types of requirements for field tester measurement accuracy There are two types of requirements specified in applicable standards: Specifications for field tester properties, that significantly affect measurement accuracy. The standards contain formulas how to obtain a computed measurement accuracy from the performance of each relevant property. Methods to compare the results obtained with field testers with results measured on the same link using laboratory equipment (i.e., network analyzers). This results in an observed measurement accuracy. The applicable standards stipulate that the computed accuracy must be in agreement with the observed measurement accuracy. This stipulation solves the following dilemna: There is no guarantee that there are no other properties than those specified in the standard that significantly affect measurement accuracy. This of course depends on the way the measurements are implemented. If an unspecified parameter affects measurement accuracy substantially, the results of comparing field tester results with those from laboratory equipment will likely be in disharmony with the computed measurement accuracy. When comparing the results of field testers with those of laboratory equipment, the question is how many links must be tested before concluding that a certain measurement accuracy is actually achieved. Requiring that critical performance parameters are met reduces the probability that insufficient links have been tested to establish compliance. 17

18 5.2 Computed measurement accuracy specifications Dependency of link properties on measurement accuracy The measurement accuracy not only depends on the properties of the field tester, the measurement accuracy depends also on properties of the link under test. The dependency of measurement accuracy on both link properties and field tester properties is shown by using a simple DC volts measurement example. A voltmeter with a 10 kω internal impedance is used to measure a battery that has an unknown internal impedance. This internal impedance may vary and can be as high as 1 kω depending on its state of charge. The accuracy of the voltmeter is better than 1 % when connected to a known voltage (with a very low source impedance!). What voltage does the voltmeter measure, assuming that the true battery voltage is 1 V? Ignoring the 1 % accuracy of the voltmeter, the indication may be as low as 0.91 V. This is a variation of 10 %. In addition, there is the accuracy of the voltmeter itself and the answer can therefore be as low as 0.9 V. So, while the accuracy of the voltmeter may be specified at 1 %, the measurement accuracy is far worse as a result of the unknown source impedance of the battery. < 1 kω voltmeter 10 kω V? battery 1 V Figure 14: Illustration of tester accuracy versus measurement accuracy For the RF measurements of cable testing, the situation is considerably more complex and more quantities than just the internal impedance of the voltmeter and the source impedance of the battery are involved Properties of links under test affecting measurement accuracy Since Level III measurement accuracy for testing ISO/IEC Class E or TIA Category 6 links is of highest interest, this discussion addresses only measurement accuracy for these conditions. The assumed link properties as defined in applicable standards are shown in Table 5. Parameter Return loss of permanent link Return loss of the channel Value (in db) 1 MHz 40 MHz: 26-5*log(f), 21 db max 40 MHz 250 MHz: 34-10*log(f) 1 MHz 40 MHz: 24-5*log(f), 19 db max 40 MHz 250 MHz: 32-10*log(f) Differential to common mode conversion gain 10 Common to differential mode conversion gain 5 Table 5: Properties of links affecting measurement accuracy 18

19 Return loss of the link under tests interacts with the source/load return loss properties of the tester, and thereby affects measurement accuracy. Normally crosstalk effects are measured by applying a differential mode signal to a wire pair and measuring the differential mode signal on a different wire pair. In reality, some portion of the signal that is applied couples as a common mode signal in that different wire pair and as a result of limited Common Mode Rejection (CMR) manifests itself as an additional differential mode signal. Similarly, if the signal is not applied in a perfectly balanced manner (the measure for this is Output Signal Balance), a common mode signal on one wire pair causes a differential mode signal (which is measured) on the other wire pair. Both coupling effects are stronger than the differential-to-differential mode coupling (estimated at 10 db and 5 db respectively), and thereby affect the measurement accuracy. 5.3 Observed measurement accuracy The standards define in great detail how to make the comparison of field tester results with those obtained with laboratory equipment. The principle is straightforward, but the implementation rather difficult as a result of differences in the connections. In each RF measurement a reference plane of measurement is present, and it is essential that the reference plane of measurement (for example, the locations where the permanent link or channel starts and where it ends). To conduct these tests, special adapters and test programs may be needed, which are generally not made available by field tester manufacturers. More details can be provided on this topic. 5.4 Natural variability of results, not included in accuracy specifications The sources of variability that are NOT included in accuracy specifications are the variations of mated performance when a jack of the permanent link under test is mated with the plug attached to the permanent link adapter (formerly the basic link adapter). From this discussion it will also become evident that the channel test results can and often will be highly dependent on the properties of the user patch cords. The variability depends on the parameter that is measured : Insertion loss Variability is small relative to measurement accuracy. NEXT loss Substantial, refer to the discussion that follows. ELFEXT Not evaluated, but considered less critical, since ELFEXT margins are generally very high and measurement accuracy is therefore not very important. Return loss Significant, refer to the discussion that follows. 19

20 5.4.1 NEXT loss variability The variability during NEXT loss measurement with different, compliant adapters can be estimated by recognizing the fundamental aspects of mating a plug and a jack, see Figure 15. The mated connection is 54 db = 1/8 of the plug by itself! The plug by itself is 36 db Figure 15: NEXT loss compensation in a mated connection Starting with a plug with MHz NEXT loss (which is the approximate de-embedded NEXT loss value of a reference test plug, as specified in applicable standards), the category 6 mated connection has to meet MHz NEXT loss. This is only 1/8 of the NEXT loss of the plug by itself. There can be an equal amount of overcompensation as undercompensation 180 out of phase, assuming that both mated connections are compliant with the requirement (e.g, MHz). When using the first measurement as a reference, the worst case change in the second measurement is twice the specification for the mated connection. This is worst case, of course. A more reasonable assumption is that the amount of change is reflected by a single connection. The impact of this additional connection on the MHz pass/fail limit level of a TIA category 6 or ISO/IEC Class E permanent link is approx. 1.9 db. This variability is even higher than the measurement accuracy of the field tester. However, this variability is currently not recognized in the standards for the purposes of estimating the accuracy band (commonly called grey zone ). Given typical NEXT loss measurement accuracy of a field tester with permanent link adapter as shown in section 3, it is very well possible that results obtained using different adapters do not agree within the accuracy specifications of the field tester (even exchanging the local and remote adapter may cause these changes) Return loss variability The considerations for variability of return loss are similar to those for NEXT loss. This time the variability is considerably less pronounced, although not insignificant relative to measurement accuracy that is often achieved by a field tester. See Figure 16. The mated connection is 24 db = 2.25 x the plug by itself! The plug by itself is 31 db Figure 16: Return loss compensation in a mated connection 20

21 In this case, the return loss of the plug has to be within 30 db and MHz (per TIA/EIA-568B.2). The return loss specification for the mated connection is MHz. The variability of the connection can therefore be represented by another connection with MHz return loss. This causes a change of approx db at the permanent link pass/fail limit Additional variability in channel test configurations The user patch cord is formally part of the channel that is tested, and must not be changed (no change at all is allowed after certifying a channel test result, not even reversing the orientation of the user patch cord!). One can understand the following changes in performance that might occur, if a change is made. The performance of the key transmission parameters NEXT loss and return loss is discussed. NEXT loss changes due to changing patch cords in a channel configuration Changes due to the different patch cable (just the cable portion of a patch cord assembly!) are minimal. The change at a nominally compliant channel, using compliant patch cable will be as low as MHz or less. Changes due to the different matings of plug at the end of the user patch cord and jack of the link are as discussed for the permanent link (approx MHz for a nominally compliant link; higher if the channel performs better than nominal). Return loss changes due to changing patch cords in a channel configuration Changes due to different patch cable (just the cable portion of a patch cord asembly!) can be substantial and is highly influenced by the characteristic impedance properties, as reflected in return loss specifications at low frequencies. In fact, a patch cord by itself can cause a return loss failure in the channel by itself, even if the remainder of the cable has excellent return loss performance. This is particularly often the case near 20 MHz, where the ¼ wavelength matches the typical length of a patch cable. This behavior is also the reason why permanent link testing is preferable over basic link testing: avoided is the variability that is caused by the return loss properties of basic link adapters. Changes due to the different matings of plug at the end of the user patch cord and jack of the link are as discussed for the permanent link (approx MHz for a nominally compliant link; higher if the channel performs better than nominal). 21

22 5.5 Properties of the field tester affecting measurement accuracy The properties of field testers that affect measurement accuracy and are recognized in applicable standards and Level III performance requirements are shown in Table 6. Parameters Baseline (db) Permanent Link (db) MHz MHz: 150 khz MHz: 250 khz 100 MHz 250 MHz: 500 khz Frequency range Frequency resolution (minimum resolution, all parameters except insertion loss; insertion loss resolution: 1 MHz) Dynamic accuracy Insertion loss 0.75 Dynamic accuracy NEXT loss 0.75 Dynamic accuracy FEXT loss Note Channel (db) Source/load return loss *log(f/100) 20 db max *log(f/100) 20 db max Random noise floor 75-15*log(f/100) Residual NEXT Note *log(f/100) test up to 85 db 54-20*log(f/100) test up to 85 db Residual FEXT Note *log(f/100) test up to 85 db *log(f/100) test up to 85 db Output Signal Balance 40-20*log(f/100) test up to 60 db 37-20*log(f/100) test up to 60 db Common Mode Rejection 40-20*log(f/100) test up to 60 db 37-20*log(f/100) test up to 60 db Tracking 0.5 Directivity 27-7*log(f/100) 30 db max 25-20*log(f/100) 25 db max Source Match *log(f/100) 20 db max Return loss of termination 20-15*log(f/100) 25 db max 16-15*log(f/100) 25 db max Note 1: It is assumed that the dynamic accuracy of insertion loss and FEXT loss measurements add up to 1 db total dynamic accuracy for ELFEXT. Note 2: The Level III residual NEXT requirements for the channel test configuration 54 20log(f/100) should take into consideration reflected FEXT (in the mated instrument connector) effects, which appear as residual NEXT. The standard needs to be clarified. Note 3: The current draft of the TIA Level III requirements shows a residual FEXT loss of 65-20log(f/100) requirement. This is to be corrected to match the FEXT loss requirement of compliant category 6 connecting hardware. The requirements and the method of verification of residual FEXT need to be clarified. Table 6: Field tester performance requirements as a function of test configuration (with adapter) 22

23 5.6 Length, Propagation Delay, Delay Skew and DC resistance measurement accuracy The measurement accuracy for length, propagation delay and delay skew are shown intable 7. Performance Parameter Length Propagation Delay Delay Skew DC resistance Range m 0 µs to 1 µs 0 ns 100 ns MHz Resolution 0.1 m 1 ns 1 ns 1 Ω Accuracy ± 1 m ± 4 % ± 5 ns ± 4 % ± 10 ns ± 1 Ω ± 1 % Table 7: Measurement accuracy for length, propagation delay, delay skew and DC resistance 5.7 Explanation of field tester performance parameters affecting measurement accuracy Dynamic accuracy All measurements involve applying a stimulus signal to the cabling under test, and measure the response to the stimulus signal. The gain ratio is the desired measure. The linearity of that ratio is called dynamic accuracy. It is more challenging to maintain linearity (dynamic accuracy) over a large dynamic range and over a wide frequency band. In the case of insertion loss the challenge to maintain good dynamic accuracy is the least as a result of a worst case 40 db (1 in 100) dynamic range. In the case of NEXT loss, the dynamic range is highest at low frequencies (65 db or approx. 1 in 2000), but declines at high frequencies. During FEXT loss measurements (to be able to compute ELFEXT), the dynamic range is highest at both low frequencies and high frequencies, and is therefore most challenging. In addition, stray coupling during dynamic accuracy verification make it very difficult to avoid measurement errors when performing testing dynamic accuracy for FEXT Source/load return loss Return Loss indicates the loss of signal due to reflections at the transmit output or the receive input of the tester. It is commonly known that if the impedance levels are not perfectly matched, that the signal energy that is measured is not optimized. The magnitude of the reflections are also influenced by the return loss properties of the link under test. Both source/load return loss of the tester and return loss of the link become worse as the test frequency increases. This property has a major impact at the measurement accuracy for insertion loss (attenuation), NEXT loss and ELFEXT at high frequencies Random noise floor The random noise floor is the signal that is measured when there is no stimulus applied to the link under test. In some measurements, the measured signals are extremely small, and the random noise that is generated in the measurement channel limits the measurement accuracy. This is most pronounced during the measurement of (EL) FEXT. There is virtually no impact from random noise during the insertion loss (attenuation) and return loss measurements. 23

24 5.7.4 Residual NEXT Residual NEXT is the NEXT loss measured by the field tester, when there is basically nothing connected to it. The tester measures the NEXT from its own internal measurement circuitry and the NEXT from the connector to the link to be tested. Per the definition of the links (which exclude the connection to the equipment itself), the NEXT contribution by this connector must be excluded. The Residual NEXT can add or subtract from the NEXT of the link that is measured, because the phase relationship is not known, but likely adds somewhere in the frequency range of interest. In the case of residual NEXT for the baseline and permanent link test configurations, this is not a critical problem, since the connection with the field tester involves a high quality connection, with very good NEXT properties. In case of a channel measurement residual NEXT is not a simple topic. The most serious error contribution is from the NEXT of the mated jack of the channel adapter and the plug of the user patch cord at the near end. Proprietary time domain techniques are used to reduce the impact of this modular 8-pin, RJ-45 connection. The NEXT loss from the mated connection with the channel adapter at the remote end and the remote user patch cord does have an influence at low frequencies with short links. The standards have not at all addressed this error contribution by assuming that the round trip insertion loss (attenuation) of the link reduces the impact to an insignificant value. In addition, at high frequencies, the FEXT loss performance is having an impact as well on the residual NEXT performance. Test signals are partly reflected (= return loss properties of the link) and arrive back in the measurement circuit as a result of the FEXT coupling in the channel adapter. The current test methods do not properly cover reflected FEXT at all, and in fact after correction of the local and remote residual NEXT contributions dominate the equivalent residual NEXT. Refer to section 7 for more information Residual FEXT FEXT is measured by applying a test signal to one wire pair at the beginning of the link and measuring the response on a different wire pair at the end of the link. If there were no FEXT in the link under test, residual FEXT would be the FEXT that is actually measured. The origin is from coupling inside the local and remote field tester units and connections to and from the field tester. For the baseline and permanent link test configurations, this is not a critical problem, since the connection with the field tester involves a high quality connection, with very good FEXT properties. In the case of a channel measurement, as in the case for NEXT, the FEXT loss of a modular 8-pin RJ-45 connection is having a significant impact. Any compensation for significant residual FEXT in the channel adapter is considerably more complex and the test procedure for residual FEXT does not address this complexity. Assuming that the mated FEXT is relatively independent of plug and jack matings, and no delay skew in the cable under test, all FEXT contributions remain in phase and theoretically can be subtracted out. However, practically there is delay skew (up to 50 ns or 5x 360 phase 100 MHz). An accurate compensation over the full length of a link requires a complex proprietary compensation scheme. 24

TSB-67. Transmission Performance Specifications for Field Testing of UTP Cabling Systems

TSB-67. Transmission Performance Specifications for Field Testing of UTP Cabling Systems TSB-67 Transmission Performance Specifications for Field Testing of UTP Cabling Systems Prepared by: ANSI/EIA/TIA PN-3287 Task Group on UTP Link Performance Required Field Test Parameters for TSB-67 Wire

More information

Field Measurements of Return Loss

Field Measurements of Return Loss Field Measurements of Return Loss White Paper By Mark Johnston and Jim Tonti Microtest October 21, 1998 Page 1 12/15/99 Overview Return loss is an important new measurement used to qualify the performance

More information

n Proper pin termination at each end n Continuity to the remote end n Shorts between any two or more conductors n Transposed pairs: n Crossed pairs.

n Proper pin termination at each end n Continuity to the remote end n Shorts between any two or more conductors n Transposed pairs: n Crossed pairs. INTRODUCTION Structured Cabling or data cabling (also known Local Area Network or LAN Cabling) is increasing in its deployment for business, commercial and residential use to carry signaling for networks

More information

Independent Testing - For End User Confidence

Independent Testing - For End User Confidence Independent Testing - For End User Confidence EVALUATION OF PERFORMANCE OF LEVEL IIIe FIELD TESTER FROM FLUKE NETWORKS, TYPE DTX-1800 CABLE ANALYZER, FOR 500 MHz PERMANENT LINK MEASUREMENTS Main Unit,

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 61935-1 Edition 3.0 2009-07 Specification for the testing of balanced and coaxial information technology cabling Part 1: Installed balanced cabling as specified in ISO/IEC 11801

More information

DELTA Test Report. Certification testing of generic cabling products: Unscreened channel, Class E, 4 connector model. Performed for Sterling

DELTA Test Report. Certification testing of generic cabling products: Unscreened channel, Class E, 4 connector model. Performed for Sterling DELTA Test Report TEST Reg. no. 19 Certification testing of generic cabling products: Unscreened channel, Class E, 4 connector model Performed for Sterling DANAK-19/16909 Project no.: T213173-01 Page 1

More information

AMP NETCONNECT Category 6 System

AMP NETCONNECT Category 6 System AMP NETCONNECT Category 6 System 2 How Did We Get Here? Basic Cabling Structure Component Specifications Link/Channel Specifications Additional Structure Options EIA/TIA TSB36 EIA/TIA 568 TIA/EIA TSB40

More information

Cabling Ad Hoc Cat 5e Measurements

Cabling Ad Hoc Cat 5e Measurements Cabling Ad Hoc Cat 5e Measurements Larry Cohen Solarflare Communications 1 Overview Cabling Ad Hoc Test Plan Measurement One Cat 5e horizontal cable sample, four test channel configurations characterized

More information

Field Testing Update

Field Testing Update Field Testing Update Adrian Young Fluke Networks November, 2013 Singapore Objectives for this session Copper field standards update Look at new copper field measurements Fiber field standards update IEC

More information

Cable Analysis. Extracting Information from Measured Data. The Performance Leader in Hand-Held Network Tools. Fanny Mlinarsky.

Cable Analysis. Extracting Information from Measured Data. The Performance Leader in Hand-Held Network Tools. Fanny Mlinarsky. Cable Analysis Extracting Information from Measured Data Fanny Mlinarsky 2-Nov-98 The Performance Leader in Hand-Held Network Tools Introduction Every cable tells a story. Cable certification measurements

More information

Qualification testing of 100 ohm shielded channel, Class EA. Performed for Tyco Electronics Raychem N.V.

Qualification testing of 100 ohm shielded channel, Class EA. Performed for Tyco Electronics Raychem N.V. We help ideas meet the real world DELTA Test Report DANAK TEST Reg. no. 19 Qualification testing of 100 ohm shielded channel, Class EA Performed for Tyco Electronics Raychem N.V. DANAK-19J1636 Project

More information

AESA TECHNOLOGY OF LAN CABLE

AESA TECHNOLOGY OF LAN CABLE TECHNOLOGY OF LAN CABLE CONTENT CHAPTER INTRODUCTION CHAPTER LOCAL AREA NETWORK (LAN) CHAPTER STRUCTURED CABLING SYSTEM (SCS) CHAPTER OPTICAL FIBER CABLE CHAPTER STANDARD CHAPTER COPPER LAN CABLE DESIGN

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS IEC 61935.1:2006 IEC 61935-1:2005 AS/NZS IEC 61935.1:2006 Australian/New Zealand Standard Testing of balanced communication cabling in accordance with ISO/IEC 11801 Part 1: Installed cabling AS/NZS

More information

Independent Testing - For End User Confidence

Independent Testing - For End User Confidence Independent Testing - For End User Confidence ELECTRICAL TRANSMISSION PERFORMANCE TESTING OF SCREENED CATEGORY 6 ISO/IEC, EN & TIA/EIA CONNECTING HARDWARE ACCORDING TO REQUIREMENTS OF 2ND EDITION ISO/IEC

More information

Some considerations concerning alien crosstalk Dr.-Ing. J.-H. (Jo) Walling Consultant Beaconsfield, P.Q. Canada

Some considerations concerning alien crosstalk Dr.-Ing. J.-H. (Jo) Walling Consultant Beaconsfield, P.Q. Canada Some considerations concerning alien crosstalk Dr.-Ing. J.-H. (Jo) Walling Consultant Beaconsfield, P.Q. Canada jo.walling@sympatico.ca 0. Summary Contrary to the simplified perception about alien crosstalk,

More information

Bill Ham Martin Ogbuokiri. This clause specifies the electrical performance requirements for shielded and unshielded cables.

Bill Ham Martin Ogbuokiri. This clause specifies the electrical performance requirements for shielded and unshielded cables. 098-219r2 Prepared by: Ed Armstrong Zane Daggett Bill Ham Martin Ogbuokiri Date: 07-24-98 Revised: 09-29-98 Revised again: 10-14-98 Revised again: 12-2-98 Revised again: 01-18-99 1. REQUIREMENTS FOR SPI-3

More information

B. Division-16 Basic Materials and Methods section apply to work specified in this section.

B. Division-16 Basic Materials and Methods section apply to work specified in this section. Section 16745 PREMISE CABLING SYSTEMS PART ONE GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification

More information

Communications Integrators, Inc. June S. Wilson Street, Suite 105 Tempe, Arizona Toll Free (800) Web Site

Communications Integrators, Inc. June S. Wilson Street, Suite 105 Tempe, Arizona Toll Free (800) Web Site Communications Integrators, Inc. June 2008 2625 S. Wilson Street, Suite 105 Tempe, Arizona 85282 Toll Free (800) 679-9711 Web Site www.ciinet.com Product Guide Specification Specifier Notes: This product

More information

XX.7 Link segment characteristics

XX.7 Link segment characteristics XX.7 Link segment characteristics 10GBASE-T is designed to operate over a 4-pair balanced cabling system. Each of the four pairs supports an effective data rate of 2500 Mbps in each direction simultaneously.

More information

A Few (Technical) Things You Need To Know About Using Ethernet Cable for Portable Audio

A Few (Technical) Things You Need To Know About Using Ethernet Cable for Portable Audio A Few (Technical) Things You Need To Know About Using Ethernet Cable for Portable Audio Rick Rodriguez June 1, 2013 Digital Audio Data Transmission over Twisted-Pair This paper was written to introduce

More information

1) The addition of TCL and ELTCTL requirements to Category 6

1) The addition of TCL and ELTCTL requirements to Category 6 Subject 444 TO: SUBJECT: 455 East Trimble Road San Jose, CA 95131 July 28, 2008 Subscribers to UL s Listing and Verification Services for Communications Cable (DUZX) Revised Test and Follow-Up Service

More information

This document is a preview generated by EVS

This document is a preview generated by EVS INTERNATIONAL STANDARD IEC 61935-1 Edition 4.0 2015-12 colour inside Specification for the testing of balanced and coaxial information technology cabling Part 1: Installed balanced cabling as specified

More information

AUTOMOTIVE ETHERNET CONSORTIUM

AUTOMOTIVE ETHERNET CONSORTIUM AUTOMOTIVE ETHERNET CONSORTIUM Clause 96 100BASE-T1 Physical Medium Attachment Test Suite Version 1.0 Technical Document Last Updated: March 9, 2016 Automotive Ethernet Consortium 21 Madbury Rd, Suite

More information

High Data Rate Characterization Report

High Data Rate Characterization Report High Data Rate Characterization Report VPSTP-016-1000-01 Mated with: VRDPC-50-01-M-RA and VRDPC-50-01-M-RA Description: Plug Shielded Twisted Pair Cable Assembly, 0.8mm Pitch Samtec, Inc. 2005 All Rights

More information

- Characteristic impedance of cabling links is characterised by Return Loss

- Characteristic impedance of cabling links is characterised by Return Loss ISO/IEC 11801 ISO 11801 is the principle design standard for structured cabling systems for all countries of the world that do not have more specific standards, such as ISO 11801 (European Union), TIA

More information

User s Manual for Integrator Short Pulse ISP16 10JUN2016

User s Manual for Integrator Short Pulse ISP16 10JUN2016 User s Manual for Integrator Short Pulse ISP16 10JUN2016 Specifications Exceeding any of the Maximum Ratings and/or failing to follow any of the Warnings and/or Operating Instructions may result in damage

More information

High Speed Characterization Report

High Speed Characterization Report TCDL2-10-T-05.00-DP and TCDL2-10-T-10.00-DP Mated with: TMMH-110-04-X-DV and CLT-110-02-X-D Description: 2-mm Pitch Micro Flex Data Link Samtec, Inc. 2005 All Rights Reserved Table of Contents Introduction...1

More information

TEST REPORT. DANAK Reg. no. 19. Electrical performance testing of: Connecting Hardware according to IEC

TEST REPORT. DANAK Reg. no. 19. Electrical performance testing of: Connecting Hardware according to IEC Page 1 of 12 2 Appendices TEST REPORT DANAK Reg. no. 19 DELTA Danish Electronics, Light & Acoustics Venlighedsvej 4 DK-2970 Hørsholm Denmark Tel. (+45) 45 86 77 22 Fax (+45) 45 86 58 98 www.delta.dk Electrical

More information

High Data Rate Characterization Report

High Data Rate Characterization Report High Data Rate Characterization Report EQRF-020-1000-T-L-SMA-P-1 Mated with: QSE-xxx-01-x-D-A and SMA-J-P-x-ST-TH1 Description: Cable Assembly, High Speed Coax, 0.8 mm Pitch Samtec, Inc. 2005 All Rights

More information

ST-CCTV-VBAC16 16-Channel Active UTP Video Receiver

ST-CCTV-VBAC16 16-Channel Active UTP Video Receiver INSTALLATION MANUAL ST-CCTV-VBAC16 16-Channel Active UTP Video Receiver Copyright North American Cable Equipment, Inc. 1 PACKAGE CONTENTS This package contains: One ST-CCTV-VBAC16 16-channel active UTP

More information

High Speed Characterization Report

High Speed Characterization Report PCRF-064-1000-SMA-P-1 Mated with: PCIE-XXX-02-X-D-TH and SMA-J-P-X-ST-TH1 Description: Cable Assembly, Low Loss Microwave Coax, PCI Express Breakout Samtec, Inc. 2005 All Rights Reserved Table of Contents

More information

High Data Rate Characterization Report

High Data Rate Characterization Report High Data Rate Characterization Report ERDP-013-39.37-TTR-STL-1-D Mated with: ERF8-013-05.0-S-DV-DL-L and ERM8-013-05.0-S-DV-DS-L Description: Edge Rate Twin-Ax Cable Assembly, 0.8mm Pitch Samtec, Inc.

More information

ST-CCTV-VBAC8 8-Channel Active UTP Video Receiver

ST-CCTV-VBAC8 8-Channel Active UTP Video Receiver INSTALLATION MANUAL 8-Channel Active UTP Video Receiver Copyright North American Cable Equipment, Inc. 1 PACKAGE CONTENTS This package contains: One 8-channel active UTP video receiver One AC power cord

More information

Automatic measuring system for xdsl & LAN cables (100 MHz) Designed to measure all types of telecom and special cables

Automatic measuring system for xdsl & LAN cables (100 MHz) Designed to measure all types of telecom and special cables Indicative picture Phoenix 1004 DT Automatic measuring system for xdsl & LAN cables (100 MHz) Designed to measure all types of telecom and special cables Compliant to all major national standards for telephone,

More information

User s Manual for Integrator Long Pulse ILP8 22AUG2016

User s Manual for Integrator Long Pulse ILP8 22AUG2016 User s Manual for Integrator Long Pulse ILP8 22AUG2016 Contents Specifications... 3 Packing List... 4 System Description... 5 RJ45 Channel Mapping... 8 Customization... 9 Channel-by-Channel Custom RC Times...

More information

A Novel Simplified Four-Port Scattering Parameter Model for Design of Four-Pair Twisted-Pair Cabling Systems for Local Area Networks

A Novel Simplified Four-Port Scattering Parameter Model for Design of Four-Pair Twisted-Pair Cabling Systems for Local Area Networks IEEE TRANSACTIONS ON MICROWAVE THEORY AND TECHNIQUES, VOL. 48, NO. 5, MAY 2000 815 A Novel Simplified Four-Port Scattering Parameter Model for Design of Four-Pair Twisted-Pair Cabling Systems for Local

More information

Category 7 A /Class F A Products

Category 7 A /Class F A Products CATEGORY 7 A /CLASS F A PRODUCTS Category 7 A /Class F A Products Exceeding ISO/IEC category 7 A /class F A specifications, Siemonʼs fully shielded TERA endto-end cabling solution is the highest-performing,

More information

GSM Transmitter Modulation Quality Measurement Option

GSM Transmitter Modulation Quality Measurement Option Performs all required measurements for GSM transmitters Outputs multiple time mask parameters for process control analysis Obtains frequency error, rms phase error, and peak phase error with one command

More information

Media. Twisted pair db/km at 1MHz 2 km. Coaxial cable 7 db/km at 10 MHz 1 9 km. Optical fibre 0.2 db/km 100 km

Media. Twisted pair db/km at 1MHz 2 km. Coaxial cable 7 db/km at 10 MHz 1 9 km. Optical fibre 0.2 db/km 100 km Media Attenuation Repeater spacing Twisted pair 10-12 db/km at 1MHz 2 km Coaxial cable 7 db/km at 10 MHz 1 9 km Optical fibre 0.2 db/km 100 km conniq.com provides an excellent tutorial on physical media.

More information

Operational Amplifier

Operational Amplifier Operational Amplifier Joshua Webster Partners: Billy Day & Josh Kendrick PHY 3802L 10/16/2013 Abstract: The purpose of this lab is to provide insight about operational amplifiers and to understand the

More information

High Data Rate Characterization Report

High Data Rate Characterization Report High Data Rate Characterization Report EQCD-020-39.37-STR-TTL-1 EQCD-020-39.37-STR-TEU-2 Mated with: QTE-020-01-X-D-A and QSE-020-01-X-D-A Description: 0.8mm High-Speed Coax Cable Assembly Samtec, Inc.

More information

This document is a preview generated by EVS

This document is a preview generated by EVS TECHNICAL REPORT ISO/IEC TR 11801-9901 Edition 1.0 2014-10 colour inside Information technology Generic cabling for customer premises Part 9901: Guidance for balanced cabling in support of at least 40

More information

FIBRE CHANNEL CONSORTIUM

FIBRE CHANNEL CONSORTIUM FIBRE CHANNEL CONSORTIUM FC-PI-2 Clause 9 Electrical Physical Layer Test Suite Version 0.21 Technical Document Last Updated: August 15, 2006 Fibre Channel Consortium Durham, NH 03824 Phone: +1-603-862-0701

More information

This is a preview - click here to buy the full publication

This is a preview - click here to buy the full publication ISO/IEC TR 11801-9901 TECHNICAL REPORT Edition 1.0 2014-10 colour inside Information technology Generic cabling for customer premises Part 9901: Guidance for balanced cabling in support of at least 40

More information

There is a twenty db improvement in the reflection measurements when the port match errors are removed.

There is a twenty db improvement in the reflection measurements when the port match errors are removed. ABSTRACT Many improvements have occurred in microwave error correction techniques the past few years. The various error sources which degrade calibration accuracy is better understood. Standards have been

More information

Application Note. Signal Integrity Modeling. SCSI Connector and Cable Modeling from TDR Measurements

Application Note. Signal Integrity Modeling. SCSI Connector and Cable Modeling from TDR Measurements Application Note SCSI Connector and Cable Modeling from TDR Measurements Signal Integrity Modeling SCSI Connector and Cable Modeling from TDR Measurements Dima Smolyansky TDA Systems, Inc. http://www.tdasystems.com

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer IN 1000-S N = 1000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Closed loop (compensated)

More information

Test report number CRT-001b Project number CRT-001b

Test report number CRT-001b Project number CRT-001b 3933 US Route 11 Cortland, NY 13 Telephone: (7) 3-6711 Facsimile: (7) 8-39 www.intertek.com July 24, 215 Nexans Cabling Solutions Alsembergsesteenweg 2, b3 B-151 Buizingen BELGIUM Test report number 12193693CRT-1b

More information

Application Note 5044

Application Note 5044 HBCU-5710R 1000BASE-T Small Form Pluggable Low Voltage (3.3V) Electrical Transceiver over Category 5 Unshielded Twisted Pair Cable Characterization Report Application Note 5044 Summary The Physical Medium

More information

University of New Hampshire InterOperability Laboratory Gigabit Ethernet Consortium

University of New Hampshire InterOperability Laboratory Gigabit Ethernet Consortium University of New Hampshire InterOperability Laboratory Gigabit Ethernet Consortium As of June 18 th, 2003 the Gigabit Ethernet Consortium Clause 40 Physical Medium Attachment Conformance Test Suite Version

More information

Agilent AN Applying Error Correction to Network Analyzer Measurements

Agilent AN Applying Error Correction to Network Analyzer Measurements Agilent AN 287-3 Applying Error Correction to Network Analyzer Measurements Application Note 2 3 4 4 5 6 7 8 0 2 2 3 3 4 Table of Contents Introduction Sources and Types of Errors Types of Error Correction

More information

GIGABIT ETHERNET CONSORTIUM

GIGABIT ETHERNET CONSORTIUM GIGABIT ETHERNET CONSORTIUM Clause 126 2.5G/5GBASE-T PMA Test Suite Version 1.2 Technical Document Last Updated: March 15, 2017 2.5, 5 and 10 Gigabit Ethernet Testing Service 21 Madbury Road, Suite 100

More information

Successful SATA 6 Gb/s Equipment Design and Development By Chris Cicchetti, Finisar 5/14/2009

Successful SATA 6 Gb/s Equipment Design and Development By Chris Cicchetti, Finisar 5/14/2009 Successful SATA 6 Gb/s Equipment Design and Development By Chris Cicchetti, Finisar 5/14/2009 Abstract: The new SATA Revision 3.0 enables 6 Gb/s link speeds between storage units, disk drives, optical

More information

Test Report based on DIN EN ISO/IEC 17025: 2005

Test Report based on DIN EN ISO/IEC 17025: 2005 Test Report based on DIN EN ISO/IEC 1725: 25 GHMT Type Approval 2 Connector Permanent Link, Copper, Class EA according ISO/IEC 1181-1 Ed.1. Document-no: P582a-18-E This Test Report with the measurements

More information

Test Report based on DIN EN ISO/IEC 17025:2005

Test Report based on DIN EN ISO/IEC 17025:2005 Test Report based on DIN EN ISO/IEC 1725:25 GHMT Type Approval 2 Connector Permanent Link, Copper, Class E according ISO/IEC 1181-1 Ed.1. 217-11 Document-no: P4945b-18-E This Test Report with the measurements

More information

2.5G/5G/10G ETHERNET Testing Service

2.5G/5G/10G ETHERNET Testing Service 2.5G/5G/10G ETHERNET Testing Service Clause 126 2.5G/5GBASE-T PMA Test Plan Version 1.3 Technical Document Last Updated: February 4, 2019 2.5, 5 and 10 Gigabit Ethernet Testing Service 21 Madbury Road,

More information

BACKPLANE ETHERNET CONSORTIUM

BACKPLANE ETHERNET CONSORTIUM BACKPLANE ETHERNET CONSORTIUM Clause 72 10GBASE-KR PMD Test Suite Version 1.1 Technical Document Last Updated: June 10, 2011 9:28 AM Backplane Ethernet Consortium 121 Technology Drive, Suite 2 Durham,

More information

Chapter 12: Transmission Lines. EET-223: RF Communication Circuits Walter Lara

Chapter 12: Transmission Lines. EET-223: RF Communication Circuits Walter Lara Chapter 12: Transmission Lines EET-223: RF Communication Circuits Walter Lara Introduction A transmission line can be defined as the conductive connections between system elements that carry signal power.

More information

Keysight Technologies Making Accurate Intermodulation Distortion Measurements with the PNA-X Network Analyzer, 10 MHz to 26.5 GHz

Keysight Technologies Making Accurate Intermodulation Distortion Measurements with the PNA-X Network Analyzer, 10 MHz to 26.5 GHz Keysight Technologies Making Accurate Intermodulation Distortion Measurements with the PNA-X Network Analyzer, 10 MHz to 26.5 GHz Application Note Overview This application note describes accuracy considerations

More information

10 GIGABIT ETHERNET CONSORTIUM

10 GIGABIT ETHERNET CONSORTIUM 10 GIGABIT ETHERNET CONSORTIUM Clause 54 10GBASE-CX4 PMD Test Suite Version 1.0 Technical Document Last Updated: 18 November 2003 10:13 AM 10Gigabit Ethernet Consortium 121 Technology Drive, Suite 2 Durham,

More information

10GBASE-T. Channel Model Proposal

10GBASE-T. Channel Model Proposal Channel Model Proposal March 2004 Orlando, FLA 0 Overview Purpose of presentation: Get agreement on a baseline channel models that will be used for evaluating PHY proposals Channel models must be acceptable

More information

Call For Interest PoE- plus. Chris Di Minico MC Communications

Call For Interest PoE- plus. Chris Di Minico MC Communications Call For Interest PoE- plus Chris Di Minico MC Communications cdiminico@ieee.org 1 IEEE 802.3 CFI Powering Ethernet Devices Over Data Cabling IEEE 802.3af Web Cameras Ethernet Switch Data and Power Security

More information

A local 3.5 mm network jack allows a convenient way to connect an installation or diagnostic tool to the network without disconnecting any wires.

A local 3.5 mm network jack allows a convenient way to connect an installation or diagnostic tool to the network without disconnecting any wires. FEATURES - Extends wiring distance of FTT-10 LonWorks Networks. - Up to 5 repeaters can be daisy chained together to create a multi-segment repeater of up to 10 channels. - Low cost alternative to routers

More information

Samtec MODS-LJ Series (LIFEJACK ) Category 5/5e Qualification

Samtec MODS-LJ Series (LIFEJACK ) Category 5/5e Qualification Samtec MODS-LJ Series (LIFEJACK ) Category 5/5e Qualification J. Ferry, C. Arroyo Copyright 2008 Samtec, Inc Page 1 Summary LIFEJACK met or exceeded TIA/EIA-568-B.2-2001 Category 5e requirements for Insertion

More information

Exercise 3-2. Effects of Attenuation on the VSWR EXERCISE OBJECTIVES

Exercise 3-2. Effects of Attenuation on the VSWR EXERCISE OBJECTIVES Exercise 3-2 Effects of Attenuation on the VSWR EXERCISE OBJECTIVES Upon completion of this exercise, you will know what the attenuation constant is and how to measure it. You will be able to define important

More information

Data sheet MC GC1200 pro22 Cat.7A S/FTP 4P LSHF-FR, class Dca s2 d2

Data sheet MC GC1200 pro22 Cat.7A S/FTP 4P LSHF-FR, class Dca s2 d2 Page 1/7 Illustrations Principle diagram See enlarged drawings at the end of document Product specification 10 GBit installation cable, simplex installation cable Cat.7A AWG 22 S/FTP with wires shielded

More information

TYPE 874-GAL ADJUSTABLE ATTENUATOR

TYPE 874-GAL ADJUSTABLE ATTENUATOR OPERATING INSTRUCTIONS TYPE 874-GAL ADJUSTABLE ATTENUATOR DESCRIPTION The Type 874-GAL Adjustable Attenuator is of the wave-guidebelow-cutoff type operating in the TE 1 mode (inductive coupling). The waveguide

More information

Cable Testing TELECOMMUNICATIONS AND NETWORKING

Cable Testing TELECOMMUNICATIONS AND NETWORKING Cable Testing TELECOMMUNICATIONS AND NETWORKING Analog Signals 2 Digital Signals Square waves, like sine waves, are periodic. However, square wave graphs do not continuously vary with time. The wave holds

More information

Automatic measuring system for LAN cables AXT & Cat 8 HF only

Automatic measuring system for LAN cables AXT & Cat 8 HF only Picture for information only Automatic measuring system for LAN cables AXT & Cat 8 HF only The fastest measuring system on the market Checked against certified ISO 17025 standards High accuracy Easy to

More information

IEEE Std 802.3ap (Amendment to IEEE Std )

IEEE Std 802.3ap (Amendment to IEEE Std ) IEEE Std 802.3ap.-2004 (Amendment to IEEE Std 802.3.-2002) IEEE Standards 802.3apTM IEEE Standard for Information technology. Telecommunications and information exchange between systems. Local and metropolitan

More information

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Current Transducer IN 1000-S I P N = 1000 A For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit. Features Closed loop (compensated)

More information

PDI TEST REPORT. No.0437

PDI TEST REPORT. No.0437 ABN 21 002 065 769 PDI TEST REPORT No.0437 COMPREHENSIVE Cat 6 TRANSMISSION TESTING ON 4 Pair 5m RJ45 Patch Cord With COBLE (COB) Cat 6 RJ45 Plug for Australian Communications Laboratories Pty Ltd DATE:

More information

Correct Measurement of Timing and Synchronisation Signals - A Comprehensive Guide

Correct Measurement of Timing and Synchronisation Signals - A Comprehensive Guide Correct Measurement of Timing and Synchronisation Signals - A Comprehensive Guide Introduction This document introduces the fundamental aspects of making valid timing and synchronisation measurements and

More information

6100A/6101A - Alternative verification methods

6100A/6101A - Alternative verification methods 6100A/6101A - Alternative verification methods Alternative verification of 6100A/6101A 6100A/6101A - Alternative verification methods Title Page Alternative verification of 6100A/6101A... 2 Recommendation...

More information

Electromagnetic Effects, original release, dated 31 October Contents: 17 page document plus 13 Figures. Enclosure (1)

Electromagnetic Effects, original release, dated 31 October Contents: 17 page document plus 13 Figures. Enclosure (1) Electromagnetic Effects, original release, dated 31 October 2005 Contents: 17 page document plus 13 Figures Enclosure (1) Electromagnetic effects. 1. Purpose. To ensure that the addition of fiber optic

More information

Microwave Circuit Design and Measurements Lab. INTRODUCTION TO MICROWAVE MEASUREMENTS: DETECTION OF RF POWER AND STANDING WAVES Lab #2

Microwave Circuit Design and Measurements Lab. INTRODUCTION TO MICROWAVE MEASUREMENTS: DETECTION OF RF POWER AND STANDING WAVES Lab #2 EE 458/558 Microwave Circuit Design and Measurements Lab INTRODUCTION TO MICROWAVE MEASUREMENTS: DETECTION OF RF POWER AND STANDING WAVES Lab #2 The purpose of this lab is to gain a basic understanding

More information

Tektronix Inc. DisplayPort Standard. Revision Tektronix MOI for Cable Tests (DSA8200 based sampling instrument with IConnect software)

Tektronix Inc. DisplayPort Standard. Revision Tektronix MOI for Cable Tests (DSA8200 based sampling instrument with IConnect software) DisplayPort Standard Revision 1.0 05-20-2008 DisplayPort Standard Tektronix MOI for Cable Tests (DSA8200 based sampling instrument with IConnect software) 1 Table of Contents: Modification Records... 4

More information

SECTION BUILDING WIRE AND CABLE

SECTION BUILDING WIRE AND CABLE SECTION 260519 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Building wire and cable. 2. Wiring connectors and connections. B. RELATED SECTIONS 1. Section 26 05 53 Electrical Identification. 2. Section

More information

Keysight MOI for USB Type-C Connectors & Cable Assemblies Compliance Tests (Type-C to Legacy Cable Assemblies)

Keysight MOI for USB Type-C Connectors & Cable Assemblies Compliance Tests (Type-C to Legacy Cable Assemblies) Revision 01.01 Jan-21, 2016 Universal Serial Bus Type-C TM Specification Revision 1.1 Keysight Method of Implementation (MOI) for USB Type-C TM Connectors and Cables Assemblies Compliance Tests Using Keysight

More information

ENT-AN0098 Application Note. Magnetics Guide. June 2018

ENT-AN0098 Application Note. Magnetics Guide. June 2018 ENT-AN0098 Application Note Magnetics Guide June 2018 Contents 1 Revision History... 1 1.1 Revision 2.2... 1 1.2 Revision 2.1... 1 1.3 Revision 2.0... 1 1.4 Revision 1.2... 1 1.5 Revision 1.1... 1 1.6

More information

University of New Hampshire InterOperability Laboratory Fast Ethernet Consortium

University of New Hampshire InterOperability Laboratory Fast Ethernet Consortium University of New Hampshire InterOperability Laboratory Fast Ethernet Consortium As of February 25, 2004 the Fast Ethernet Consortium Clause 25 Physical Medium Dependent Conformance Test Suite version

More information

Verifying the Wideband Input of an AC Measurement Standard

Verifying the Wideband Input of an AC Measurement Standard Abstract erifying the of an AC Measurement Standard Speaker David Deaver Fluke Corporation PO Box 9090, Everett, WA, 98206 Phone: (425) 446-6434 FAX: (425) 446-5649 E-mail: david.deaver@fluke.com Authors:

More information

EFFECT OF SHIELDING ON CABLE RF INGRESS MEASUREMENTS LARRY COHEN

EFFECT OF SHIELDING ON CABLE RF INGRESS MEASUREMENTS LARRY COHEN EFFECT OF SHIELDING ON CABLE RF INGRESS MEASUREMENTS LARRY COHEN OVERVIEW Purpose: Examine the common-mode and differential RF ingress levels of 4-pair UTP, F/UTP, and F/FTP cables at an (RJ45) MDI port

More information

CABLE TESTER. Models CA7024, CA7026 & CA7028. Call toll free (800) or visit

CABLE TESTER. Models CA7024, CA7026 & CA7028. Call toll free (800) or visit CABLE TESTER Models CA7024, CA7026 & CA7028 Call toll free (800) 537-0351 or visit www.allspec.com Hand-held LAN Cable Mapping and Troubleshooting Tester (Model CA7028) Hand-held Alphanumeric TDR (Time

More information

DC CIRCUITS AND OHM'S LAW

DC CIRCUITS AND OHM'S LAW July 15, 2008 DC Circuits and Ohm s Law 1 Name Date Partners DC CIRCUITS AND OHM'S LAW AMPS - VOLTS OBJECTIVES OVERVIEW To learn to apply the concept of potential difference (voltage) to explain the action

More information

Validation & Analysis of Complex Serial Bus Link Models

Validation & Analysis of Complex Serial Bus Link Models Validation & Analysis of Complex Serial Bus Link Models Version 1.0 John Pickerd, Tektronix, Inc John.J.Pickerd@Tek.com 503-627-5122 Kan Tan, Tektronix, Inc Kan.Tan@Tektronix.com 503-627-2049 Abstract

More information

MODEL 5002 PHASE VERIFICATION BRIDGE SET

MODEL 5002 PHASE VERIFICATION BRIDGE SET CLARKE-HESS COMMUNICATION RESEARCH CORPORATION clarke-hess.com MODEL 5002 PHASE VERIFICATION BRIDGE SET TABLE OF CONTENTS WARRANTY i I BASIC ASSEMBLIES I-1 1-1 INTRODUCTION I-1 1-2 BASIC ASSEMBLY AND SPECIFICATIONS

More information

Transmission Line Drivers and Receivers for TIA/EIA Standards RS-422 and RS-423

Transmission Line Drivers and Receivers for TIA/EIA Standards RS-422 and RS-423 Transmission Line Drivers and Receivers for TIA/EIA Standards RS-422 and RS-423 Introduction With the advent of the microprocessor, logic designs have become both sophisticated and modular in concept.

More information

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual.

Manual Supplement. This supplement contains information necessary to ensure the accuracy of the above manual. Manual Title: 550A Getting Started Supplement Issue: Part Number: 415509 Issue Date: 9/18 Print Date: November 01 Page Count: 19 Revision/Date: This supplement contains information necessary to ensure

More information

Data sheet MC GC1200 pro22 Cat.7A S/FTP 2x4P LSHF-FR 1640 ft

Data sheet MC GC1200 pro22 Cat.7A S/FTP 2x4P LSHF-FR 1640 ft Page 1/7 Illustrations Principle diagram Product specification 10 GBit installation cable, duplex installation cable Cat.7A AWG 22 S/FTP with wires shielded in pairs 2x4 pairs (PiMF) pair shield: plastic

More information

Keysight MOI for USB Type-C Connectors & Cable Assemblies Compliance Tests (Type-C to Legacy Cable Assemblies)

Keysight MOI for USB Type-C Connectors & Cable Assemblies Compliance Tests (Type-C to Legacy Cable Assemblies) Revision 01.00 Nov-24, 2015 Universal Serial Bus Type-C TM Specification Revision 1.1 Keysight Method of Implementation (MOI) for USB Type-C TM Connectors and Cables Assemblies Compliance Tests Using Keysight

More information

High Speed Characterization Report

High Speed Characterization Report HDLSP-035-2.00 Mated with: HDI6-035-01-RA-TR/HDC-035-01 Description: High Density/High Speed IO Cable Assembly Samtec, Inc. 2005 All Rights Reserved Table of Contents Introduction...1 Product Description...1

More information

RESISTANCE & OHM S LAW (PART I

RESISTANCE & OHM S LAW (PART I RESISTANCE & OHM S LAW (PART I and II) Objectives: To understand the relationship between potential and current in a resistor and to verify Ohm s Law. To understand the relationship between potential and

More information

Practical PoE Tutorial

Practical PoE Tutorial Practical PoE Tutorial Chris DiMinico, MC Communications/Panduit Chad Jones, Cisco Systems Ron Nordin, Panduit Lennart Yseboodt, Philips Lighting Berlin, Germany July 10, 2017 Agenda Background/Scope Chris

More information

SPECIFICATION AND PERFORMANCE CHARACTERISTICS SERIAL ATA CABLE ASSEMBLIES

SPECIFICATION AND PERFORMANCE CHARACTERISTICS SERIAL ATA CABLE ASSEMBLIES SPECIFICATION AND PERFORMANCE CHARACTERISTICS OF SERIAL ATA CABLE ASSEMBLIES CIRCUIT ASSEMBLY CORP. 18 THOMAS STREET, IRVINE, CA 92618-2777 Page No. 1 CONTENTS: 1.0 SCOPE.. 3 2.0 APPLICABLE DOCUMENTS 3

More information

5 Mbit/s Repeater Carrierband to Single-mode Fiber Optic

5 Mbit/s Repeater Carrierband to Single-mode Fiber Optic Installation and Testing 5 Mbit/s Repeater Carrierband to Single-mode Fiber Optic Models CBR-7AC CBR-7DC This manual describes the procedures for installing and testing the CBR-7 Fiber-Optic Repeaters.

More information

Physical Test Setup for Impulse Noise Testing

Physical Test Setup for Impulse Noise Testing Physical Test Setup for Impulse Noise Testing Larry Cohen Overview Purpose: Use measurement results for the EM coupling (Campbell) clamp to determine a stable physical test setup for impulse noise testing.

More information

Testing Power Sources for Stability

Testing Power Sources for Stability Keywords Venable, frequency response analyzer, oscillator, power source, stability testing, feedback loop, error amplifier compensation, impedance, output voltage, transfer function, gain crossover, bode

More information

CHAPTER 9. Solutions for Exercises

CHAPTER 9. Solutions for Exercises CHAPTER 9 Solutions for Exercises E9.1 The equivalent circuit for the sensor and the input resistance of the amplifier is shown in Figure 9.2 in the book. Thus the input voltage is Rin vin = v sensor Rsensor

More information

Today s modern vector network analyzers

Today s modern vector network analyzers DISTORTION INHERENT TO VNA TEST PORT CABLE ASSEMBLIES Fig. 1 VNA shown with a flexible test port cable assembly on. Today s modern vector network analyzers (VNA) are the product of evolutionary advances

More information