DELTA Test Report. Certification testing of generic cabling products: Unscreened channel, Class E, 4 connector model. Performed for Sterling
|
|
- Pamela Farmer
- 5 years ago
- Views:
Transcription
1 DELTA Test Report TEST Reg. no. 19 Certification testing of generic cabling products: Unscreened channel, Class E, 4 connector model Performed for Sterling DANAK-19/16909 Project no.: T Page 1 of 72 7 October 2016 DELTA Venlighedsvej Hørsholm Denmark Tel. (+45) Fax (+45) VAT No This report is issued under the rules of DANAK (Danish Accreditation) and ILAC (International Laboratory Accreditation Cooperation) including its MRA (Mutual Recognition Arrangement). Further information can be found at and The report must not be reproduced, except in ful l, without the written approval of DELTA.
2 Page 2 of 72 DELTA Headquarter, Hørsholm Denmark
3 Page 3 of 72 Title Product description Certification testing of generic cabling products Unscreened channel, Class E, 4 connector model Product identification See Clause 2 EC Cabling product ID 6080 Compliance statement Accreditation no. DANAK-19/16909 Project no. T Test object received 22 September 2016 Test period September - October 2016 Client Contact Sterling 3 The Business Centre Molly Millars Lane Wokingham Berks RG41 2EY Daniel Nicholson Specification ISO/IEC Results Prepared by Reviewed by Compliance with specifications is verified Lars Bjerring Lars Lindskov Pedersen Date 7 October 2016 Responsible Lars Lindskov Pedersen, Test Manager DELTA LAN Components and Systems Testing
4 Page 4 of 72 Table of content Page 1. Summary 5 2. Channel components 6 3. Conclusion 8 4. Test results Cable marking High frequency transmission test results. Channel #1 (85 m horizontal cable) High frequency transmission test results. Channel #2 (85 m horizontal cable) High frequency transmission test results. Channel #3 (15 m horizontal cable) Resistance properties Reference to applicable standards and documents Generic cabling standards Special requirements for EC VERIFIED Test procedures Electrical test Attenuation (Att) Return loss (RL) Near end crosstalk (NEXT) Powersum near end crosstalk (PSNEXT) Attenuation to crosstalk loss ratio (ACR-N) Power sum ACR (PSACR-N) Attenuation to crosstalk ratio-far end (ACR-F) Power sum attenuation to crosstalk ratio far end (PSACR-F) Attenuation unbalance, near end (Transverse conversion loss, TCL) DC loop resistance Propagation delay Delay skew Test software 72
5 Page 5 of Summary A communication channel has been tested for compliance with generic cabling standards. The purpose of the testing was to certify certification of the channel according to the EC VERIFIED programme. The channel for this electrical performance test was assembled and delivered to DELTA by the client. The channel testing has been performed under laboratory conditions at the EC Cabling Group of DELTA. This report firstly gives a detailed description of the channels under test. Then the conclusion is given followed by the test results. At last an overview of the test procedures and applied standards are given.
6 Page 6 of Channel components Terminal (PC) TO B CP C1 C2 Equipment (Server) D A C E Channel under test (without end plugs) Figure 1. Channel definition (4 connector model). The channel consists of the following components: Item Name Cable type Length Connecting hardware A Terminal cord Flexible cable 5 m 1 plug B Consolidation point cable Flexible cable 5 m 1 socket 1 plug C Horizontal cable Horizontal cable Channel #1: 85 m Channel #2: 85 m Channel #3: 15 m 2 sockets D Patch cord Flexible cable 2m 2 plugs E Equipment cord Flexible cable 3 m 1 socket TO CP C1, C2 Telecommunications Outlet / Wall Outlet Consolidation Point connector (Sockets) Horizontal cross-connector / Floor Distributor / Patch panel
7 Page 7 of 72 Test samples and qualification status Horizontal cable (C): Sterling Cat6 U/UTP LSZH horizontal cable. Part no Telecommunication outlet (TO): Sterling Cat6 UTP module. Part no. C6-UTP-50FMx (x: colour) Consolidation point connector (CP): Sterling Cat6 UTP keystone jack. Part no. C6-UTP-KSx (x: colour) Equipment cord (E) and CP cord (B): Sterling Cat6 U/UTP consolidation cable. Part no. C6-PCSx-xx-x (x: length and colour) (with jack C6-UTP-KSx added for CP cord, and equipment cord terminated in patch panel) Patch panel (C1, C2): Sterling Cat6 UTP patch panel. Part no. C6-UTP-PPxx (xx: number of ports) Terminal cord and patch cord (A/D): Sterling Cat6 U/UTP patch cable. Part no. 66xxxx (xxxx: length and colour)
8 Page 8 of Conclusion The tested samples comply with the applied requirements. The test results are only applicable for the tested samples.
9 Page 9 of Test results 4.1 Cable marking Table 1. Cable marking, horizontal cable Characteristic Type of printing Colour of text Text Result jet ink black on a mauve jacket STERLING CAT6 U/UTP LSZH 23AWG VERIFIED TO TIA/EIA-568-B.2-1 & ISO/IEC M 03/07/2015 Table 2. Cable marking, flexible cable (cords and CP cable) Characteristic Type of printing Colour of text Text Result jet ink blue on a grey jacket 550 MHz (UL) E TYPE CM 24AWG 75 C CSA CM 75 C ETL VERIFIED TIA/EIA-568-C.2 UTP CAT.6 STERLING
10 Page 10 of High frequency transmission test results. Channel #1 (85 m horizontal cable) NEAR END CROSSTALK (NEXT). From terminal end Channel #1. Worst case margin: 5.5 db at MHz for Blue /Orange pair. Table 3. Worst case margins at selected nominal frequencies
11 Page 11 of 72 PS NEAR END CROSSTALK(PSNEXT). From terminal end Channel #1. Worst case margin: 5.6 db at MHz for Blue pair. Table 4. Worst case margins at selected nominal frequencies
12 Page 12 of 72 RETURN LOSS. From terminal end Channel #1. Worst case margin: 6 db at MHz for Orange pair. Table 5. Worst case margins at selected nominal frequencies
13 Page 13 of 72 ATTENUATION TO CROSSTALK RATIO, NEAR END (ACR-N). From terminal end Channel #1. Worst case margin: 10.3 db at MHz for Blue/Green-Blue pair. Table 6. Worst case margins at selected nominal frequencies
14 Page 14 of 72 PS ATT TO CROSSTALK RATIO, NEAR END (PSACR-N). From terminal end Channel #1. Worst case margin: 11.4 db at MHz for Blue pair. Table 7. Worst case margins at selected nominal frequencies
15 Page 15 of 72 TRANSVERSE CONVERSION LOSS (TCL). From terminal end Channel #1. Worst case margin: 4.8 db at 40.8 MHz for Green pair. Table 8. Worst case margins at selected nominal frequencies
16 Page 16 of 72 NEAR END CROSSTALK (NEXT). From equipment end Channel #1. Worst case margin: 1.4 db at MHz for Blue /Green pair. Table 9. Worst case margins at selected nominal frequencies
17 Page 17 of 72 PS NEAR END CROSSTALK(PSNEXT). From equipment end Channel #1. Worst case margin: 3.5 db at MHz for Blue pair. Table 10. Worst case margins at selected nominal frequencies
18 Page 18 of 72 RETURN LOSS. From equipment end Channel #1. Worst case margin: 4.1 db at MHz for Brown pair. Table 11. Worst case margins at selected nominal frequencies
19 Page 19 of 72 ATTENUATION TO CROSSTALK RATIO, NEAR END (ACR-N). From equipment end Channel #1. Worst case margin: 7.3 db at MHz for Blue/Green-Blue pair. Table 12. Worst case margins at selected nominal frequencies
20 Page 20 of 72 PS ATT TO CROSSTALK RATIO, NEAR END (PSACR-N). From equipment end Channel #1. Worst case margin: 9.4 db at MHz for Blue pair. Table 13. Worst case margins at selected nominal frequencies
21 Page 21 of 72 TRANSVERSE CONVERSION LOSS (TCL). From terminal end Channel #1. Worst case margin: 14.2 db at 4.1 MHz for Orange pair. Table 14. Worst case margins at selected nominal frequencies
22 Page 22 of 72 BALANCED MODE ATTENUATION. Channel #1. Worst case margin: 0.7 db at 4.1 MHz for Green pair. Table 15. Worst case margins at selected nominal frequencies
23 Page 23 of 72 ATTENUATION TO CROSSTALK RATIO - FAR (ACR-F). Channel #1. Worst case margin: 7.3 db at 98.7 MHz for Blue/Green-Blue pair. ATTENUATION TO CROSSTALK RATIO - FAR (ACR-F). Channel #1. Worst case margin: 9.4 db at MHz for Green/Blue-Green pair.
24 Page 24 of 72 ATTENUATION TO CROSSTALK RATIO - FAR (ACR-F). Channel #1. Worst case margin: 8 db at MHz for Green/Orange-Green pair. Table 16. Worst case margins at selected nominal frequencies
25 Page 25 of 72 PS SUM ATTENUATION TO CROSSTALK RATIO - FAR (PSACR-F). Channel #1. Worst case margin: 8.6 db at MHz for Green pair. Table 17. Worst case margins at selected nominal frequencies
26 Page 26 of 72 PROPAGATION DELAY. Channel #1. Worst case margin: µs at MHz for Green pair. Table 18. Worst case margins at selected nominal frequencies. [ns] [ns] [ns]
27 Page 27 of 72 DELAY SKEW. Channel #1. Worst case margin: 26.6 ns. Table 19. Worst case margins at selected nominal frequencies. [ns] [ns] [ns]
28 Page 28 of High frequency transmission test results. Channel #2 (85 m horizontal cable) NEAR END CROSSTALK (NEXT). From terminal end Channel #2. Worst case margin: 7.8 db at MHz for Blue /Green pair. Table 20. Worst case margins at selected nominal frequencies
29 Page 29 of 72 PS NEAR END CROSSTALK(PSNEXT). From terminal end Channel #2. Worst case margin: 8.7 db at MHz for Green pair. Table 21. Worst case margins at selected nominal frequencies
30 Page 30 of 72 RETURN LOSS. From terminal end Channel #2. Worst case margin: 5.3 db at 66.4 MHz for Green pair. Table 22. Worst case margins at selected nominal frequencies
31 Page 31 of 72 ATTENUATION TO CROSSTALK RATIO, NEAR END (ACR-N). From terminal end Channel #2. Worst case margin: 11.6 db at 4.1 MHz for Blue/Orange-Blue pair. Table 23. Worst case margins at selected nominal frequencies
32 Page 32 of 72 PS ATT TO CROSSTALK RATIO, NEAR END (PSACR-N). From terminal end Channel #2. Worst case margin: 11 db at 4.1 MHz for Orange pair. Table 24. Worst case margins at selected nominal frequencies
33 Page 33 of 72 TRANSVERSE CONVERSION LOSS (TCL). From terminal end Channel #2. Worst case margin: 2.1 db at MHz for Green pair. Table 25. Worst case margins at selected nominal frequencies
34 Page 34 of 72 NEAR END CROSSTALK (NEXT). From equipment end Channel #2. Worst case margin: 2 db at MHz for Blue /Green pair. Table 26. Worst case margins at selected nominal frequencies
35 Page 35 of 72 PS NEAR END CROSSTALK(PSNEXT). From equipment end Channel #2. Worst case margin: 3.5 db at MHz for Green pair. Table 27. Worst case margins at selected nominal frequencies
36 Page 36 of 72 RETURN LOSS. From equipment end Channel #2. Worst case margin: 4.9 db at MHz for Brown pair. Table 28. Worst case margins at selected nominal frequencies
37 Page 37 of 72 ATTENUATION TO CROSSTALK RATIO, NEAR END (ACR-N). From equipment end Channel #2. Worst case margin: 7.2 db at MHz for Blue/Green-Blue pair. Table 29. Worst case margins at selected nominal frequencies
38 Page 38 of 72 PS ATT TO CROSSTALK RATIO, NEAR END (PSACR-N). From equipment end Channel #2. Worst case margin: 8.9 db at MHz for Green pair. Table 30. Worst case margins at selected nominal frequencies
39 Page 39 of 72 BALANCED MODE ATTENUATION. Channel #2. Worst case margin: 0.7 db at 4.1 MHz for Green pair. Table 31. Worst case margins at selected nominal frequencies
40 Page 40 of 72 ATTENUATION TO CROSSTALK RATIO - FAR (ACR-F). Channel #2. Worst case margin: 5.3 db at 98.7 MHz for Blue/Green-Blue pair. ATTENUATION TO CROSSTALK RATIO - FAR (ACR-F). Channel #2. Worst case margin: 9.7 db at MHz for Green/Blue-Green pair.
41 Page 41 of 72 ATTENUATION TO CROSSTALK RATIO - FAR (ACR-F). Channel #2. Worst case margin: 5.4 db at 250 MHz for Green/Orange-Green pair. Table 32. Worst case margins at selected nominal frequencies
42 Page 42 of 72 PS SUM ATTENUATION TO CROSSTALK RATIO - FAR (PSACR-F). Channel #2. Worst case margin: 7.3 db at 98.7 MHz for Green pair. Table 33. Worst case margins at selected nominal frequencies
43 Page 43 of 72 PROPAGATION DELAY. Channel #2. Worst case margin: 0.04 µs at MHz for Green pair. Table 34. Worst case margins at selected nominal frequencies. [ns] [ns] [ns]
44 Page 44 of 72 DELAY SKEW. Channel #2. Worst case margin: 26.2 ns. Table 35. Worst case margins at selected nominal frequencies. [ns] [ns] [ns]
45 Page 45 of 72 TRANSVERSE CONVERSION LOSS (TCL). From terminal end Channel #2. Worst case margin: 13.5 db at MHz for Blue pair. Table 36. Worst case margins at selected nominal frequencies
46 Page 46 of High frequency transmission test results. Channel #3 (15 m horizontal cable) NEAR END CROSSTALK (NEXT). From terminal end Channel #3. Worst case margin: 0.2 db at 240 MHz for Blue /Green pair. Table 37. Worst case margins at selected nominal frequencies
47 Page 47 of 72 PS NEAR END CROSSTALK(PSNEXT). From terminal end Channel #3. Worst case margin: 2.4 db at 240 MHz for Blue pair. Table 38. Worst case margins at selected nominal frequencies
48 Page 48 of 72 RETURN LOSS. From terminal end Channel #3. Worst case margin: 1.3 db at 8.5 MHz for Green pair. Table 39. Worst case margins at selected nominal frequencies
49 Page 49 of 72 ATTENUATION TO CROSSTALK RATIO, NEAR END (ACR-N). From terminal end Channel #3. Worst case margin: 15.2 db at 18.4 MHz for Blue/Orange-Blue pair. Table 40. Worst case margins at selected nominal frequencies
50 Page 50 of 72 PS ATT TO CROSSTALK RATIO, NEAR END (PSACR-N). From terminal end Channel #3. Worst case margin: 16 db at 3.5 MHz for Green pair. Table 41. Worst case margins at selected nominal frequencies
51 Page 51 of 72 TRANSVERSE CONVERSION LOSS (TCL). From terminal end Channel #3. Worst case margin: 8.7 db at 34 MHz for Green pair. Table 42. Worst case margins at selected nominal frequencies
52 Page 52 of 72 NEAR END CROSSTALK (NEXT). From equipment end Channel #3. Worst case margin: 2.5 db at MHz for Blue /Green pair. Table 43. Worst case margins at selected nominal frequencies
53 Page 53 of 72 PS NEAR END CROSSTALK(PSNEXT). From equipment end Channel #3. Worst case margin: 3.1 db at MHz for Blue pair. Table 44. Worst case margins at selected nominal frequencies
54 Page 54 of 72 RETURN LOSS. From equipment end Channel #3. Worst case margin: 3 db at 17.8 MHz for Orange pair. Table 45. Worst case margins at selected nominal frequencies
55 Page 55 of 72 ATTENUATION TO CROSSTALK RATIO, NEAR END (ACR-N). From equipment end Channel #3. Worst case margin: 16.7 db at 27.8 MHz for Blue/Orange-Blue pair. Table 46. Worst case margins at selected nominal frequencies
56 Page 56 of 72 PS ATT TO CROSSTALK RATIO, NEAR END (PSACR-N). From equipment end Channel #3. Worst case margin: 17.5 db at 4.7 MHz for Brown pair. Table 47. Worst case margins at selected nominal frequencies
57 Page 57 of 72 TRANSVERSE CONVERSION LOSS (TCL). From terminal end Channel #3. Worst case margin: 9.2 db at 34 MHz for Green pair. Table 48. Worst case margins at selected nominal frequencies
58 Page 58 of 72 BALANCED MODE ATTENUATION. Channel #3. Worst case margin: 2.9 db at 3.5 MHz for Green pair. Table 49. Worst case margins at selected nominal frequencies
59 Page 59 of 72 ATTENUATION TO CROSSTALK RATIO - FAR (ACR-F). Channel #3. Worst case margin: 9.9 db at MHz for Blue/Green-Blue pair. ATTENUATION TO CROSSTALK RATIO - FAR (ACR-F). Channel #3. Worst case margin: 6.2 db at MHz for Green/Blue-Green pair.
60 Page 60 of 72 ATTENUATION TO CROSSTALK RATIO - FAR (ACR-F). Channel #3. Worst case margin: 11.5 db at MHz for Brown/Blue-Brown pair. Table 50. Worst case margins at selected nominal frequencies
61 Page 61 of 72 PS SUM ATTENUATION TO CROSSTALK RATIO - FAR (PSACR-F). Channel #3. Worst case margin: 11.5 db at MHz for Blue pair. Table 51. Worst case margins at selected nominal frequencies
62 Page 62 of 72 PROPAGATION DELAY. Channel #3. Worst case margin: µs at MHz for Green pair. Table 52. Worst case margins at selected nominal frequencies. [ns] [ns] [ns]
63 Page 63 of 72 DELAY SKEW. Channel #3. Worst case margin: 44 ns. Table 53. Worst case margins at selected nominal frequencies. [ns] [ns] [ns] Equipment: Network Analyser Hewlett Packard, type 8753E Instrument no.: Switch Agilent, type 87050A Instrument no.: Balun BH, type Instrument no.: to 31182
64 Page 64 of Resistance properties Table 54. DC loop resistance, channel #1 Pair Resistance [Ohm] Requirement Compliance < 25 YES YES YES YES Table 55. DC resistance unbalance, channel #1 Pair R unbalance [%] Requirement Compliance < 3 % YES YES YES YES Equipment: Micro-Ohmmeter Keithley, type 2000 Instrument no.: 31092
65 Page 65 of Reference to applicable standards and documents Test of the cabling product is performed with reference to the following standards: 5.1 Generic cabling standards ISO/IEC 11801:2011 (Ed. 2.2) Information technology - Generic cabling for customer premises CENELEC EN :2011 (Ed. 3.0) Information Technology - Generic cabling systems - Part 1: General requirements CENELEC EN :2007 Information technology - Generic cabling systems - Part 2: Office premises CENELEC EN /A1:2010 Amendment 1 to EN :2007 ANSI/TIA-568-C.2:2009 Commercial Building Telecommunications Cabling Standard - Part 2: Balanced Twisted-Pair Telecommunications Cabling and Components 5.2 Special requirements for EC VERIFIED DQP (version 28, 28 April 2015) Terms and conditions for the EC VERIFIED programme for Generic and Coaxial cabling
66 Page 66 of Test procedures The tests carried out on the communication cabling under test are performed according to the standard: IEC Specification for the testing of balanced and coaxial information technology cabling - Part 1: Installed balanced cabling as specified in ISO/IEC and related standards. The test methods are detailed in test procedures worked out by DELTA and approved by DANAK. In this section the procedures are described briefly. 6.1 Electrical test The electrical tests on the communication channel under test are performed according to the procedures described in this section. The performed tests are shown in the following table. The floor cable is stretched on a non-conductive surface. Table 56. Performed tests Measured from Equipment end (patch panel) Terminal end (wall outlet) Attenuation x Near end crosstalk (NEXT) x x Attenuation to crosstalk, far (ACR-F) x Return loss x x Propagation delay Delay skew x x TCL x x Resistance properties x
67 Page 67 of Attenuation (Att) Network Analyser Computer Network Balun Channel under test Balun Figure 2. Test set-up for attenuation measurements. Terminal end and equipment end are connected to one balun each. The measurement uncertainty for Attenuation is dependant of the level of measured Attenuation. The uncertainty is shown in the table below: Measured attenuation Uncertainty 1 db 0.1 db 10 db 0.3 db 60 db 0.5 db 80 db 2 db
68 Page 68 of Return loss (RL) Network Analyser Computer Network Balun Channel under test Load Figure 3. Test set-up for return loss measurements. The return loss of the channel under test is measured with the far end terminated with a resistance of the specified characteristic impedance of the channel under test. The measurement uncertainty for impedance is 1 % at 100 MHz. The measurement uncertainty for return loss is dependant of the measured return loss value. The error band is specified in the table below: Measured return loss Error band 5 db ±0.2 db 10 db ±0.3 db 15 db ±0.5 db 20 db ±1 db 25 db ±2 db 30 db ±3 db At frequencies above 500 MHz add 1 db to the uncertainty.
69 Page 69 of Near end crosstalk (NEXT) Network Analyser Computer Network Balun Channel under test Balun Pair 1 Pair 2 Load Load Figure 4. Test set-up for near end crosstalk measurements. Near end crosstalk, NEXT, is measured as the attenuation from one pair to the others and these measurements are repeated for all pair combinations. In the far end all pairs are terminated with a resistor with a value of the nominal characteristic impedance of the component under test. The measurement uncertainty for NEXT is dependant of the level of measured NEXT. The uncertainty is shown in the table below: Measured NEXT Uncertainty 40 db 0.5 db 60 db 0.6 db 70 db 0.8 db 80 db 1.7 db Powersum near end crosstalk (PSNEXT) PSNEXT is calculated for each pair according to the formula: PSNEXT 10log( x1 / 10 x2 / 10 x3 / 10 ) where x1, x2, x3 are the pair-to-pair crosstalk measurements in db between the selected pair and the other three pairs. The measurement uncertainty is the same as for NEXT measurements.
70 Page 70 of Attenuation to crosstalk loss ratio (ACR-N) Attenuation to crosstalk ratio loss near end, ACR-N is calculated for each pair as the difference between the near end crosstalk loss and the attenuation. The measurement uncertainty is the same as for NEXT measurements Power sum ACR (PSACR-N) PSACR_N is calculated according to the formula: PSACR N 10log( x1/10 x2 /10 x3/10 x4 /10 Where x1, x2, x3, and x4 are the ACR-N values in db for each pair. The measurement uncertainty is the same as for NEXT measurements. ) Attenuation to crosstalk ratio-far end (ACR-F) Network Analyser Computer Network Channel under test Load Balun Pair 1 Pair 2 Load Balun Figure 5. Test set-up for far end crosstalk measurements. ACR-F is calculated from the measured values of far end cross talk, FEXT and attenuation, ATT. ACR-F = FEXT - ATT The measurement uncertainty for ACR-F is the sum of uncertainties for NEXT and ATT.
71 Page 71 of Power sum attenuation to crosstalk ratio far end (PSACR-F) PSACR-F is calculated for each pair according to the equation: PSACR F PSFEXT ATTENUATION PSFEXT 10log( x1 / 10 x2 / 10 x3 / 10 ) Where x1, x2, x3 are the pair-to-pair crosstalk measurements in db between the selected pair and the other three pairs Attenuation unbalance, near end (Transverse conversion loss, TCL) Network Analyser Computer Network Channel under test 25 Ω 50 Ω Figure Ω Test set-up for balance characteristics measurements. Balance characteristics, transverse conversion loss, is measured as the signal attenuation between the common mode and the differential mode port of the test balun. The test set-up is calibrated by imposing a known unbalance, consisting of a 50 Ohm resistor from one of the balance output terminals to ground. The instrument is adjusted for a reading of 16 db for this unbalance. All pairs are terminated for differential and common mode signals during the test. The measurement uncertainty for balance measurements is dependant of the level of balance. The uncertainty is shown in the table below: Measured TCL Uncertainty 20 db 0.3 db 30 db 1 db 40 db 3 db
72 Page 72 of DC loop resistance DC loop resistance is measured for each conductor in a pair. The loop resistance is calculated by adding the resistance of each conductor. The measured value is corrected for the temperature of the test object in order to obtain the resistance at 20 C. The measurement uncertainty for DC resistance is 1.4 % Propagation delay Propagation delay is measured by determining the phase delay of a signal transmitted through the cable. 2 f where is the phase delay. f is the frequency in Hertz. The measurement uncertainty for delay is 1 % Delay skew Delay skew is calculated as the difference between the maximum and minimum propagation delay over the four pairs at each frequency. The measurement uncertainty for skew is 10 %. 6.2 Test software Test software according to information in the table below is used for the conducted tests. Software name Function File name Version Date Cablingtotal Electrical cable tests Cabltot ECCalculate Calculated parameters ECCalculate ECReport Report Xreport Report programme Report Rapgen.xls DELTA Automatic Reporting Program Automatic word processing Rapport Cable report 2002 Cable report generation Cable report
Qualification testing of 100 ohm shielded channel, Class EA. Performed for Tyco Electronics Raychem N.V.
We help ideas meet the real world DELTA Test Report DANAK TEST Reg. no. 19 Qualification testing of 100 ohm shielded channel, Class EA Performed for Tyco Electronics Raychem N.V. DANAK-19J1636 Project
More informationTEST REPORT. DANAK Reg. no. 19. Electrical performance testing of: Connecting Hardware according to IEC
Page 1 of 12 2 Appendices TEST REPORT DANAK Reg. no. 19 DELTA Danish Electronics, Light & Acoustics Venlighedsvej 4 DK-2970 Hørsholm Denmark Tel. (+45) 45 86 77 22 Fax (+45) 45 86 58 98 www.delta.dk Electrical
More informationSpecial testing of 100 ohm unshielded channel, Class E. Performed for HCS KABLOLAMA SISTEMLERI SAN.VE TIS.A.S.
We help ideas meet the real world Test Report DANAK Reg. no. 19 Special testing of 100 ohm unshielded channel, Class E Performed for HCS KABLOLAMA SISTEMLERI SAN.VE TIS.A.S. DANAK-19J1508 Project no.:
More informationIndependent Testing - For End User Confidence
Independent Testing - For End User Confidence ELECTRICAL TRANSMISSION PERFORMANCE TESTING OF SCREENED CATEGORY 6 ISO/IEC, EN & TIA/EIA CONNECTING HARDWARE ACCORDING TO REQUIREMENTS OF 2ND EDITION ISO/IEC
More informationSuperiorr Essex. Suite 150
3933 US Route 11 Cortland, NY 1345 Telephone: (67) 753-6711 Facsimile: (67) 758-3659 www.intertek.com March 2, 216 Test Report Number: 1246639CRT-14 Project Number: 1246639 Legrand North America 125 Eugene
More information125 Eugene O Neill Drive 6120 Powers Ferry Road New London, CT Suite 150 Ph (860) Atlanta, GA Fax (860)
3933 US Route 11 Cortland, NY 1345 Telephone: (67) 753-6711 Facsimile: (67) 758-3659 www.intertek.com December 16, 214 Test Report Number: 33592CRT-136 Project Number: 33592 Legrand North America Superior
More information125 Eugene O Neill Drive 6120 Powers Ferry Road New London, CT Suite 150 Ph (860) Atlanta, GA Fax (860)
3933 US Route 11 Cortland, NY 1345 Telephone: (67) 753-6711 Facsimile: (67) 758-3659 www.intertek.com December 16, 214 Test Report Number: 33592CRT-137 Project Number: 33592 Legrand North America Superior
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 61935-1 Edition 3.0 2009-07 Specification for the testing of balanced and coaxial information technology cabling Part 1: Installed balanced cabling as specified in ISO/IEC 11801
More informationTest Report based on DIN EN ISO/IEC 17025:2005
Test Report based on DIN EN ISO/IEC 1725:25 GHMT Type Approval 2 Connector Permanent Link, Copper, Class E according ISO/IEC 1181-1 Ed.1. 217-11 Document-no: P4945b-18-E This Test Report with the measurements
More information- Characteristic impedance of cabling links is characterised by Return Loss
ISO/IEC 11801 ISO 11801 is the principle design standard for structured cabling systems for all countries of the world that do not have more specific standards, such as ISO 11801 (European Union), TIA
More informationAustralian/New Zealand Standard
AS/NZS IEC 61935.1:2006 IEC 61935-1:2005 AS/NZS IEC 61935.1:2006 Australian/New Zealand Standard Testing of balanced communication cabling in accordance with ISO/IEC 11801 Part 1: Installed cabling AS/NZS
More informationThis document is a preview generated by EVS
TECHNICAL REPORT ISO/IEC TR 11801-9901 Edition 1.0 2014-10 colour inside Information technology Generic cabling for customer premises Part 9901: Guidance for balanced cabling in support of at least 40
More informationLevel III measurement accuracy of field testers for Twisted Pair Copper Cabling Explained in Technical Detail
Level III measurement accuracy of field testers for Twisted Pair Copper Cabling Explained in Technical Detail 1 Outline Henriecus Koeman Fluke Networks July 9, 2001 This rather technical discussion contains
More informationPDI TEST REPORT. No.0437
ABN 21 002 065 769 PDI TEST REPORT No.0437 COMPREHENSIVE Cat 6 TRANSMISSION TESTING ON 4 Pair 5m RJ45 Patch Cord With COBLE (COB) Cat 6 RJ45 Plug for Australian Communications Laboratories Pty Ltd DATE:
More informationIndependent Testing - For End User Confidence
Independent Testing - For End User Confidence EVALUATION OF PERFORMANCE OF LEVEL IIIe FIELD TESTER FROM FLUKE NETWORKS, TYPE DTX-1800 CABLE ANALYZER, FOR 500 MHz PERMANENT LINK MEASUREMENTS Main Unit,
More informationThis is a preview - click here to buy the full publication
ISO/IEC TR 11801-9901 TECHNICAL REPORT Edition 1.0 2014-10 colour inside Information technology Generic cabling for customer premises Part 9901: Guidance for balanced cabling in support of at least 40
More informationTSB-67. Transmission Performance Specifications for Field Testing of UTP Cabling Systems
TSB-67 Transmission Performance Specifications for Field Testing of UTP Cabling Systems Prepared by: ANSI/EIA/TIA PN-3287 Task Group on UTP Link Performance Required Field Test Parameters for TSB-67 Wire
More informationAMP NETCONNECT Category 6 System
AMP NETCONNECT Category 6 System 2 How Did We Get Here? Basic Cabling Structure Component Specifications Link/Channel Specifications Additional Structure Options EIA/TIA TSB36 EIA/TIA 568 TIA/EIA TSB40
More information1) The addition of TCL and ELTCTL requirements to Category 6
Subject 444 TO: SUBJECT: 455 East Trimble Road San Jose, CA 95131 July 28, 2008 Subscribers to UL s Listing and Verification Services for Communications Cable (DUZX) Revised Test and Follow-Up Service
More informationTest Report based on DIN EN ISO/IEC 17025: 2005
Test Report based on DIN EN ISO/IEC 1725: 25 GHMT Type Approval 2 Connector Permanent Link, Copper, Class EA according ISO/IEC 1181-1 Ed.1. Document-no: P582a-18-E This Test Report with the measurements
More informationSamtec MODS-LJ Series (LIFEJACK ) Category 5/5e Qualification
Samtec MODS-LJ Series (LIFEJACK ) Category 5/5e Qualification J. Ferry, C. Arroyo Copyright 2008 Samtec, Inc Page 1 Summary LIFEJACK met or exceeded TIA/EIA-568-B.2-2001 Category 5e requirements for Insertion
More informationProduct Bulletin. Belden DataTwist 4800 Cables
Product Bulletin PB 296 Belden DataTwist 4800 Cables DataTwist 4800 UTP Cables provide significant headroom and robust data transmission performance for today s most demanding applications. The cables
More informationCAT. 5e U/UTP 4x2x24AWG/1 CCA DOUBLE SHEATH
CAT. 5e U/UTP 4x2x24AWG/1 CCA DOUBLE SHEATH FIGURE CONSTRUCTION Inner conductor CCA Φ 0.50±0.01mm Insulation Solid HDPE Φ 0.90±0.05mm Color 1 Blue & White/ Blue 2 Orange & White/ Orange 3 Green & White/
More informationn Proper pin termination at each end n Continuity to the remote end n Shorts between any two or more conductors n Transposed pairs: n Crossed pairs.
INTRODUCTION Structured Cabling or data cabling (also known Local Area Network or LAN Cabling) is increasing in its deployment for business, commercial and residential use to carry signaling for networks
More informationAutomatic measuring system for LAN cables AXT & Cat 8 HF only
Picture for information only Automatic measuring system for LAN cables AXT & Cat 8 HF only The fastest measuring system on the market Checked against certified ISO 17025 standards High accuracy Easy to
More informationThis document is a preview generated by EVS
INTERNATIONAL STANDARD IEC 61935-1 Edition 4.0 2015-12 colour inside Specification for the testing of balanced and coaxial information technology cabling Part 1: Installed balanced cabling as specified
More informationCOPPER + LWL RAW CABLES
COPPER + LWL RAW Twisted Pair Cables... 112 TV/SAT Cables... 116 Fiber Optic Raw Cables... 120 DIGITUS CAT 7 twisted pair installation cable 4x2xAWG23 S-FTP CAT 7 1000 MHz LSZH installation cable For installation
More informationCategory 6 UTP EuroClass C ca Cables
Category 6 UTP EuroClass C ca Cables Datasheet: GD103704v1 APPLICATION Brand-Rex Cat6Plus C6U cables exceed the Category 6 performance standards. They are rated to 250MHz and are suitable for use in all
More informationTest Report. Test Result: PASS
Test Report Designation : C6 A TIA/EIA68B. UTP Length :. m Temp :. Deg C Specification : CAT6 A MHZ UTP Test Date/Time : 11--16 1:1 Sample-ID-No. : GGRQ4 Customer : Rertech Drum no. :. Cable type : CAT6A
More informationTest report number CRT-001b Project number CRT-001b
3933 US Route 11 Cortland, NY 13 Telephone: (7) 3-6711 Facsimile: (7) 8-39 www.intertek.com July 24, 215 Nexans Cabling Solutions Alsembergsesteenweg 2, b3 B-151 Buizingen BELGIUM Test report number 12193693CRT-1b
More informationCategory 7 A /Class F A Products
CATEGORY 7 A /CLASS F A PRODUCTS Category 7 A /Class F A Products Exceeding ISO/IEC category 7 A /class F A specifications, Siemonʼs fully shielded TERA endto-end cabling solution is the highest-performing,
More informationAESA TECHNOLOGY OF LAN CABLE
TECHNOLOGY OF LAN CABLE CONTENT CHAPTER INTRODUCTION CHAPTER LOCAL AREA NETWORK (LAN) CHAPTER STRUCTURED CABLING SYSTEM (SCS) CHAPTER OPTICAL FIBER CABLE CHAPTER STANDARD CHAPTER COPPER LAN CABLE DESIGN
More informationCabling Ad Hoc Cat 5e Measurements
Cabling Ad Hoc Cat 5e Measurements Larry Cohen Solarflare Communications 1 Overview Cabling Ad Hoc Test Plan Measurement One Cat 5e horizontal cable sample, four test channel configurations characterized
More informationPerformed for LEO Pharma A/S, LEO Innovation Lab
DELTA Test Report TEST Reg. no. 19 Radio parameter test of KlikKit Performed for LEO Pharma A/S, LEO Innovation Lab DANAK-19/18090 Project no.: 117-24389-1 Page 1 of 47 13 July 2017 DELTA Venlighedsvej
More informationXX.7 Link segment characteristics
XX.7 Link segment characteristics 10GBASE-T is designed to operate over a 4-pair balanced cabling system. Each of the four pairs supports an effective data rate of 2500 Mbps in each direction simultaneously.
More informationAutomatic measuring system for xdsl & LAN cables (100 MHz) Designed to measure all types of telecom and special cables
Indicative picture Phoenix 1004 DT Automatic measuring system for xdsl & LAN cables (100 MHz) Designed to measure all types of telecom and special cables Compliant to all major national standards for telephone,
More informationTest Report based on DIN EN ISO/IEC 17025
Test Report based on DIN EN ISO/IEC 17025 GHMT PREMIUM Verification Program Recertification Connector, Copper, Category 6A ISO/IEC 11801 Ed.2.2 This Test Report with the measurements consists of 28 pages.
More informationInformation technology. Generic cabling systems, General requirements
KRAMER WELL CONNECTED WITH KRAMER BCLS-33OR-5 Al-Mylar Conductor CAT6A F/UTP LSZH Cable Drain Wire Kramer s BCLS-33OR is a high performance CAT6A F/UTP cable designed for IT, LAN and Ethernet installations.
More informationNETWORK CONNECTIVITY SYSTEMS
NETWORK CONNECTIVITY SYSTEMS Installation Cable KS-STP Category 7 Installation Cable Certificates 10GBaseT FTP Category 6 Installation Cable UTP Category 6 Installation Cable UTP Category 5E Installation
More informationInstall & Go Cat.8 S/FTP Trunk Cable Assembly Description
Description Cat 8 Filler Cat.8.2 S/FTP Horizontal cables (x6) Fan-Out Cables Cat 8 STP Keystones TRUNK CABLE SECTION VIEW Assembly Isometric Front View RiT s Copper Install & Go System provides a pre-terminated
More informationISO/IEC JTC 1/SC 25/WG 3 N 755 Date: Replaces ISO/IEC JTC 1/SC 25/WG 3 N n/a
ISO/IEC JTC 1/SC 25/WG 3 N 755 Date: 2005-05-18 Replaces ISO/IEC JTC 1/SC 25/WG 3 N n/a ISO/IEC JTC 1/SC 25/WG 3 Customer Premises Cabling Secretariat: Germany (DIN) DOC TYPE: Liaison document TITLE: Letter
More informationHelios Automatic measuring system for telephone cables. Designed to measure all types of telecom cables
Automatic measuring system for telephone cables Helios 10104 Indicative picture Designed to measure all types of telecom cables Checked against certified ISO 17025 standards (LF) Automatic calibration
More informationCall For Interest PoE- plus. Chris Di Minico MC Communications
Call For Interest PoE- plus Chris Di Minico MC Communications cdiminico@ieee.org 1 IEEE 802.3 CFI Powering Ethernet Devices Over Data Cabling IEEE 802.3af Web Cameras Ethernet Switch Data and Power Security
More informationField Measurements of Return Loss
Field Measurements of Return Loss White Paper By Mark Johnston and Jim Tonti Microtest October 21, 1998 Page 1 12/15/99 Overview Return loss is an important new measurement used to qualify the performance
More informationCable Testing TELECOMMUNICATIONS AND NETWORKING
Cable Testing TELECOMMUNICATIONS AND NETWORKING Analog Signals 2 Digital Signals Square waves, like sine waves, are periodic. However, square wave graphs do not continuously vary with time. The wave holds
More informationDELTA Test Report. Performed for INWIDO Denmark A/S. DANAK 100/2331 Project no.: Page 1 of October 2017
DELTA Test Report TEST Reg. no. 100 Laboratory measurement of airborne sound insulation of a INWIDO Denmark A/S coupled sidehung construction with Float 6 mm glass in the external sash and a Float 3145
More informationSynergy RJ45 LCS 6 Category 6 data outlets
Legrand Electric Ltd. Arena Park - Dial Lane West Bromwich - West Midlands - B70 0EB- United Kingdom Technical enquiries : Tel. 0870 8 90 - Fax. 0870 8 9021 CONTENTS PAGE 7300 56 7300 57 1. Applications...
More informationSECTION BUILDING WIRE AND CABLE
SECTION 260519 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Building wire and cable. 2. Wiring connectors and connections. B. RELATED SECTIONS 1. Section 26 05 53 Electrical Identification. 2. Section
More informationInstall & Go Cat.8 STP Trunk Cable Assembly Description
Description Cat 8 Filler Cat.8.2 S/FTP Horizontal cables (x6) Fan-Out Cables Cat 8 STP Keystones TRUNK CABLE SECTION VIEW Assembly Isometric Front View RiT s Copper Install & Go System provides a pre-terminated
More informationCABLE.
CABLE www.pcnet-cable.com.tw sales@pcnet-cable.com.tw PCnet Leading Your Net! PCnet was founded in 1985 and is a leading manufacturer of netwking industries. We provide a complete range of products f structured
More informationCombined vibration and temperature test of CX4 Antennas
DELTA Test Report TEST Reg. no. 19 Combined vibration and temperature test of CX4 Antennas Performed for AC Marine A/S DANAK-19/14553 Revision B Project no.: T209198 Page 1 of 14 including 1 annex 10 October
More informationEFFECT OF SHIELDING ON CABLE RF INGRESS MEASUREMENTS LARRY COHEN
EFFECT OF SHIELDING ON CABLE RF INGRESS MEASUREMENTS LARRY COHEN OVERVIEW Purpose: Examine the common-mode and differential RF ingress levels of 4-pair UTP, F/UTP, and F/FTP cables at an (RJ45) MDI port
More informationContents. Category7 SSTP Solid Indoor Cable - Page 03
Product Catalog Contents Category7 SSTP Solid Indoor Cable - Page 03 Category6A UTP Solid Indoor Cable - Page 04 Category6A Keystone Jack - Page 05 Category6A Unshielded Patch Cord - Page 05 Category6
More informationCommunications Integrators, Inc. June S. Wilson Street, Suite 105 Tempe, Arizona Toll Free (800) Web Site
Communications Integrators, Inc. June 2008 2625 S. Wilson Street, Suite 105 Tempe, Arizona 85282 Toll Free (800) 679-9711 Web Site www.ciinet.com Product Guide Specification Specifier Notes: This product
More informationBill Ham Martin Ogbuokiri. This clause specifies the electrical performance requirements for shielded and unshielded cables.
098-219r2 Prepared by: Ed Armstrong Zane Daggett Bill Ham Martin Ogbuokiri Date: 07-24-98 Revised: 09-29-98 Revised again: 10-14-98 Revised again: 12-2-98 Revised again: 01-18-99 1. REQUIREMENTS FOR SPI-3
More informationDetailed Specifications & Technical Data
For more Information please call 1-800-Belden1 Description: Banana Peel Composite - (2) Cat 5e 4-pair 24 AWG unshielded plus (2) Series 6 Coax with Duobond IV Quad shield, polyolefin insulation on the
More informationSome considerations concerning alien crosstalk Dr.-Ing. J.-H. (Jo) Walling Consultant Beaconsfield, P.Q. Canada
Some considerations concerning alien crosstalk Dr.-Ing. J.-H. (Jo) Walling Consultant Beaconsfield, P.Q. Canada jo.walling@sympatico.ca 0. Summary Contrary to the simplified perception about alien crosstalk,
More informationCAT 5e UTP Cable: NETSET BOX [305m], indoor
Code: E08_05 CAT 5e UTP Cable: NETSET BOX [05m], indoor NETSET BOX UTP 5e Ethernet cable far exceeds the requirements for Category 5e twisted pair cables. View of the cable box - inside 05m of the cable.
More informationUTP Cat 5e cable (200 MHz) (PVC sheath)
JetLan is the only structured cabling system that includes all the passive components required for the installation or adaptation of your data network, as we include all the different types of high performance
More informationInstall & Go SMARTen (Cat.6A) STP Trunk Cable Assembly General
Install & Go SMARTen (Cat.6A) STP Trunk General Cat 8 Filler Cat.6A U/FTP Horizontal cables (x6) Fan-Out Cables Cat.6A STP Keystones TRUNK CABLE SECTION VIEW Trunk Isometric Front View RiT s Copper Install
More informationData sheet MC GC1000 pro23 Cat.7 S/FTP 4P LSHF-FR 1640 ft
Page 1/6 MC GC0 pro23 Cat.7 S/FTP 4P LSHF-FR 1640 ft 18427034141 Illustrations Principle diagram Product specification 10 GBit installation cable, simplex installation cable Cat.7 AWG 23 S/FTP with wires
More informationB. Division-16 Basic Materials and Methods section apply to work specified in this section.
Section 16745 PREMISE CABLING SYSTEMS PART ONE GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification
More informationExcel Third Party Verification Pack
Excel Third Party Verification Pack Excel is a world-class premium performing end-to-end infrastructure solution - designed, manufactured, supported and delivered - without compromise. Excel Third Party
More informationST-CCTV-VBAC16 16-Channel Active UTP Video Receiver
INSTALLATION MANUAL ST-CCTV-VBAC16 16-Channel Active UTP Video Receiver Copyright North American Cable Equipment, Inc. 1 PACKAGE CONTENTS This package contains: One ST-CCTV-VBAC16 16-channel active UTP
More informationCAT 6 Data Wiring System Connectors
NEW CAT 6 Data Wiring System Connectors TM2 Series Features. High-Speed Data Transfer Conforms to the TIA/EIA-568B.2- data Wiring standard, thereby clears CAT 6 transfer performance requirements. As such,
More informationELECTRICAL TESTING
ELECTRICAL TESTING 0839.01 Hermon Laboratories Ltd. Harakevet Industrial Zone, Binyamina 30500, Israel Tel. +972-4-6288001 Fax. +972-4-6288277 E-mail: mail@hermonlabs.com TEST REPORT ACCORDING TO: FCC
More informationHigh Speed Characterization Report
TCDL2-10-T-05.00-DP and TCDL2-10-T-10.00-DP Mated with: TMMH-110-04-X-DV and CLT-110-02-X-D Description: 2-mm Pitch Micro Flex Data Link Samtec, Inc. 2005 All Rights Reserved Table of Contents Introduction...1
More informationCAT 6 Data Wiring System Connectors
CAT Data Wiring System Connectors TM23 Series Features 1. High-Speed Data Transfer Conforms to the TIA/EIA-58B.2-1 data Wiring standard, thereby clears CAT transfer performance requirements. As such, these
More informationVideo Mono Audio Baluns
FEBRUARY 1998 IC443A Video Mono Audio Baluns Video Mono Audio Balun AUDIO 1 PAIR 1 (4 & 5) VIDEO 1 PAIR 4 (7 & 8) AUDIO 2 PAIR 2 (3 & 6) VIDEO 2 PAIR 3 (1 & 2) CUSTOMER SUPPORT INFORMATION Order toll-free
More informationPart VI: Requirements for Integrated Services Digital Network Terminal Equipment
Issue 9, Amendment 1 September 2012 Spectrum Management and Telecommunications Compliance Specification for Terminal Equipment, Terminal Systems, Network Protection Devices, Connection Arrangements and
More informationPart Number: 7953A Cat 6 600V DataTuff, (4 pr) 23 AW G Solid BC, PP/PVC/PVC, Foil Shld, CMR, CMX-Outdoor
Part Number: Cat 6 600V DataTuff, (4 pr) 23 AW G Solid BC, PP/PVC/PVC, Foil Shld, CMR, CMX-Outdoor Product Description Four Cat 6 23 AW G solid bare copper conductors, bonded pair polypropylene insulation,
More informationST-CCTV-VBAC8 8-Channel Active UTP Video Receiver
INSTALLATION MANUAL 8-Channel Active UTP Video Receiver Copyright North American Cable Equipment, Inc. 1 PACKAGE CONTENTS This package contains: One 8-channel active UTP video receiver One AC power cord
More informationCTAG:b01ac469edcbee4d9e5f84a83a1962a5 Certificate of Calibration
CTAG:bac69edcbeed9e5f8a8a96a5 Certificate of Calibration Data Type: FOUND-LEFT Certificate No: 859 Instrument Description Manufacturer Model Serial Number Inventory Number CABLE ANALYZER FLUKE NETWORKS
More informationData sheet Patch cord Cat.6 A AWG m yellow
Illustrations Dimensional drawing Page 1/6 See enlarged drawings at the end of document Product specification especially suitable for shielded and unshielded class E A systems fully shielded Cat.6 A patch
More informationNew Product Bulletin. Belden Digital Audio Cable. Belden Brilliance AES/EBU
New Product Bulletin NP 267 Belden Digital Audio Cable Belden Brilliance AES/EBU Digital Audio Cable, Part No. 1353A, is a robust single-pair Cat 5e patch cord that utilizes Belden s exclusive Bonded-Pair
More informationUTP Copper. SFTP Copper. FUTP Copper. Composite. Special Applications Copper. Category 5e. Category 6 Category 5E Category 3. Category 7A Category 7
05/2011 Table of Contents n Table of Contents 1 n Product Selection 2 n HCM Overview 4 n HCM Certified Cabling Systems 6 n UTP Copper 8 n SFTP Copper 32 n FUTP Copper 36 n Special Applications Copper 42
More informationProtocol based on DIN EN ISO/IEC 17025
Protocol based on DIN EN ISO/IEC 17025 GHMT Informative Measurement 2 Connector Channel (30m), Copper, Class II according ISO/IEC/TR 11801-9901: 2014 Document-no.: I875a-16-E This Test Report with the
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60603-7-7 First edition 2002-04 Connectors for electronic equipment Part 7-7: Detail specification for 8-way, shielded, free and fixed connectors, for data transmission with
More informationINTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60603-7-7 Second edition 2006-06 Connectors for electronic equipment Part 7-7: Detail specification for 8-way, shielded, free and fixed connectors, for data transmissions with
More informationDELTA Test Report. FCC Part 15 C test of Trackman III (TMA3A) Performed for Trackman A/S
DELTA Test Report TEST Reg. no. 19 FCC Part 15 C test of Trackman III (TMA3A) Performed for Trackman A/S Project no.: T200869 Page 1 of 51 Including 4 annees 07 February 2012 DELTA Venlighedsvej 4 2970
More informationMatric Limited Hill City Road R.R. #1 Box 421A Seneca, PA 16346
FCC CERTIFICATION TEST REPORT for Hill City Road R.R. #1 Box 421A Seneca, PA 16346 FCC ID: K5B-TP105 May 14, 2001 Revised: June 18, 2001 WLL PROJECT #: 6182X This report may not be reproduced, except in
More informationFour Cat 5e 24 AW G Bonded-Pairs solid bare copper conductors, polyolefin insulation, PVC jacket.
Part Number: 7923A Cat 5e MSHA DataTuff, (4 pr) 24 AW G Solid BC, PO/PVC, EtherNet/IP, CMR, CMX-Outdoor Product Description Four Cat 5e 24 AW G Bonded-Pairs solid bare copper conductors, polyolefin insulation,
More informationC-Tick EMC TEST REPORT. For. AC/DC Switching Power Supply
C-Tick EMC TEST REPORT For AC/DC Switching Power Supply Model: CP0515(5V/1.5A); CP0520(5V/2A); CP0530 (5V/3A); CP0540 (5V/4A); CP0550 (5V/5A); CP0560 (5V/6A);CP0615(6V/1.5A); CP0620(6V/2A); CP0625 (6V/2.5A);
More informationECE 528 Understanding Power Quality
ECE 528 Understanding Power Quality http://www.ece.uidaho.edu/ee/power/ece528/ Paul Ortmann portmann@uidaho.edu 208-733-7972 (voice) Lecture 41 1 Today Wiring for communications Decibels Coupling Avoiding
More informationVideo Stereo Audio Baluns
FEBRUARY 1998 IC441A Video Stereo Audio Baluns Video Stereo Audio Balun VIDEO PAIR 4 (7 & 8) AUDIO(L) PAIR 2 (3 & 6) AUDIO(R) PAIR 3 (1 & 2) CUSTOMER SUPPORT INFORMATION Order toll-free in the U.S. 24
More informationCopper Cords. Clarity Patch Cords. Clarity Shielded Patch Cords. Clarity 110 Patch Cords. Custom Assemblies
HIGH PERFORMANCE STRUCTURED CABLING PRODUCTS AND SOLUTIONS Copper Cords Clarity Clarity 10G, Clarity 6 and Clarity 5E patch cords lead the impressive family of Ortronics cable assemblies. Patch cords are
More informationDataTwist 5 ScTP Cable
케이블콘 ( 주 ) 기술지원팀 :: 콘넥터문의 0707-3-770 케이블문의 0707-3-7702 N E T W O R K I N G C O P P E R 5.69 DataTwist 5 ScTP Cable TIA/EIA-568-TSB 36, Category 5 Nonbonded-Pair Cables 2 AWG Solid Bare Copper Conductors
More informationTEST REPORT. Power Spout PLT V. tested to the specification. EN : Amendment 1: Electromagnetic compatibility (EMC)
EMC Technologies (NZ) Ltd PO Box 68-307, Newton Auckland 1145 New Zealand Phone 09 360 0862 Fax 09 360 0861 E-Mail Address: aucklab@ihug.co.nz Web Site: www.emctech.com.au TEST REPORT Power Spout PLT 100
More informationA Study of Conducted-Emission Stable Source Applied to the EMC US and EU Standards
Fourth LACCEI International Latin American and Caribbean Conference for Engineering and Technology (LACCEI 2006) Breaking Frontiers and Barriers in Engineering: Education, Research and Practice, 21-23
More informationCompass safe distance measurements of Trackball
We help ideas meet the real world Test Report DANAK Reg. no. 19 Compass safe distance measurements of Trackball Performed for CASP Elektronik DANAK-198084 Project no.: A503330-1 Page 1 of 7 2 annexes 22
More informationData sheet MC GC1200 pro22 Cat.7A S/FTP 4P LSHF-FR, class Dca s2 d2
Page 1/7 Illustrations Principle diagram See enlarged drawings at the end of document Product specification 10 GBit installation cable, simplex installation cable Cat.7A AWG 22 S/FTP with wires shielded
More informationActual Cable Data update
Actual Cable Data update Insertion loss, return loss, charcteristic impedance at worst case condition, propagation delay Coupling attenuation at different ageing conditions Screening attenuation at different
More informationAppendix A: Specifications
Established 1981 Advanced Test Equipment Rentals www.atecorp.com 800-404-ATEC (2832) Appendix A: Specifications This section provides a complete description of the video measurement set specifications.
More informationL.S. Compliance, Inc. W66 N220 Commerce Court Cedarburg, WI
L.S. Compliance, Inc. W66 N220 Commerce Court Cedarburg, WI 53012 262-375-4400 COMPLIANCE TESTING OF: Quartex Synchronization Transmitter Model FM-72 PREPARED FOR: Quartex, Division of Primex, Inc. 965
More informationDetailed Specifications & Technical Data
RFP Specification #17-11125-C, Exhibit 2 Programmable Light Poles for BART Plaza ENGLISH MEASUREMENT VERSION 1502SB Multi-Conductor - Multimedia Control Cable For more Information please call 1-800-Belden1
More informationShip Hybrid Cable DL 58 5 x UC1500 SS22 2x SM BendBright XS G.657.A2 6x MM MaxCap-BB-OM4
Wiking Ship Hybrid Cable Application Hybrid cable for shipboard applications DATA ELEMENT Primary (Campus), Secondary (Riser), Tertiary (Horizontal) IEEE 802.3: 10Base-T; 100Base-T; 1000Base-T; 10GBase-T
More informationHigh Data Rate Characterization Report
High Data Rate Characterization Report VPSTP-016-1000-01 Mated with: VRDPC-50-01-M-RA and VRDPC-50-01-M-RA Description: Plug Shielded Twisted Pair Cable Assembly, 0.8mm Pitch Samtec, Inc. 2005 All Rights
More informationData sheet. Connection line M12 plug straight - M12 jack straight drag chain suitable, 8-pole, X-coded 2.0 m. Illustrations
Page 1/7 Illustrations Dimensional drawing Cut-out See enlarged drawings at the end of document Product specification shielded M12 Ethernet connection cable drag chain suitable Cat.6A, 8 pole, X-coded
More informationData sheet E-DAT modul 2 port AP Cat.6 A, pearl white
Illustrations Dimensional drawing Wiring Page 1/7 See enlarged drawings at the end of document Product specification surface-mounted termination unit with E-DAT modul component testing for Cat.6 A to ISO/IEC
More informationIrish Standard I.S. EN :2009
Irish Standard I.S. EN 61935-1:2009 Specification for the testing of balanced and coaxial information technology cabling -- Part 1: Installed balanced cabling as specified in the standards series EN 50173
More information